Omega DP25-S, DP25B-S Quick Start Manual

Using This Quick Start Manual
Use this Quick Start Manual to set up your Strain Meter and begin operation. Information is provided on how to:
• Connect ac power • Set basic options for operation
• Connect the sensor • Scale the meter.
Features with are for the “B” version which has three­color programmable “Big” LED display - All segment characters shown are for the “B” version.
IMPORTANT:For complete information on all setup options, please refer to the Operator’s Manual.
Mount the Unit
1. Cut a panel opening using the dimensions shown to the right.
2. Position the unit in the opening, making sure the front bezel is flush with the panel.
3. Install retaining clips on both sides of the meter and tighten against the panel.
Wiring
1. Remove the panel at the back of the unit.
2. Locate the TB1 connector.
3. Insert the correct wire in each terminal as shown in the following figure and tighten the lockdown screws.
4. Tug gently on the wires to verify the connections.
Connect the Sensor
1. Locate the TB2 connector on the rear of the unit.
2. Attach the sensor wires and tighten the lockdown screws. The diagram below shows the wiring for bridge sensors with internal excitation.
NOTE: Refer to the Operator’s Manual for setup requirements for other sensor types.
Bridge Sensor with Internal Excitation
3. Tug gently on the wires to verify the connections.
4. Replace the panel at the back of the unit.
Using the Configuration Menu
To configure the meter, you use the buttons on the front panel.
To: Take This Action:
Display the Press the MENU button. The first function Configuration Menu on the menu, INPT, displays. Select a submenu 1. Press MENU until the function you function want is shown.
2. Press /TARE.
The information you can change flashes.
Select a value 1. Press /NT/GRS to display the option for that submenu you want. function 2. Press MENU to store it.
STRD quickly flashes, indicating that the selection has been stored in memory. Then the next menu function displays.
Go back to previous Press RESET once. menu function Exit the Press RESET twice. The unit displays Configuration RST as it reinitializes. When a numeric Menu value displays, the unit is in run mode.
(Optionally, you can press MENU to move through all the menu functions until the unit reinitializes.)
NOTE: This Quick Start Manual includes specific configuration parameters for bridge sensors with an output range of 0–100 mV and 10 V excitation. Other sensor types may require different parameters or additional ones. When this is the case, we refer you to the Operator's Manual for detailed instructions.
2
34
Warning: Do not connect AC power to your device until you have completed all input and output connections. This device must only be installed by a specially trained electrician with corresponding qualifications. Failure to follow all instructions and warnings may result in injury!
DC Powered Unit Connections
AC Powered Unit Connections
When using DC power, do not use internal excitation or Isolated Analog Output for high color brightness. For low or medium brightness, internal excitation is limited to 24 V @ 25 mA; 5 V, 10 V, 12 V @ 35 mA.
To Set the Input Type
1. Press MENU until the unit displays:
2. Press /TARE. The unit displays:
3. For this application you want 100M. If 100M is not
displayed, press /NT/GRS until it appears. Other choices are 50M, 10V, 5V and 0-20.
NOTE: Refer to the Operator's Manual for more information
on changing ranges.
4. Press MENU to select the sensor shown. The meter
displays the next menu item. If you changed input type, the meter displays:
To Set the Decimal Point
1. If it's not already shown, press MENU
until the unit displays:
2. Press /TARE. The unit displays:
3.
Press /NT/GRS to move the decimal point to the desired location. The factory settings is FFFF. The other choices are F.FFF, FF.FF, and FFF.F.
4. Press MENU to select the decimal point position shown.
The unit displays:
MENU SUBMENU /TARE DESCRIPTION
INPT 100M, ±50M,!1 0V ,!±5 V , 0-20*Input DEC.P FFFF*, F.FFF, FF.FF, FFF.F Decimal Point RD.S.O IN!1, RD!1, IN!2, RD!2 Scale and Offset RD.CF R.1=T*, R.1=N
Reading Configuration
R.2=0, R.2=1, R.2=2 , R.2=3, R.2=4
*
R.3=F*, R.3=U
R.4=P, R.4=G COLR GRN, RED, AMBR Display Color S1.CF S.1=A*, S.1=B
Setpoint 1 Configuration
S.2=U*, S.2=L
S.3=N*, S.3=G
shown if R.4=G
S2.CF S.1=A*, S.1=B
Setpoint 2 Configuration
S.2=U*, S.2=L
S.3=N*, S.3=G
shown if R.4=G
S1.DB 0003
*
Setpoint 1, Deadband
S2.DB 0003
*
Setpoint 2, Deadband
OT.CF O.1=E*, 0.1=D Analog Output
O.2=C*, 0.2=V
Configuration
O.3=A*, 0.3=P OT.S.O RD!1, OUT1 , RD!2, OUT2
Output Scale & Offset
LK.CF RS=E*, RS=D
Lockout Configuration
SP=E*, SP=D
L3=0*, L3=1 BRIT M.BrT, L.BrT, H.BrT
Display Brightness
External Fuse Required:
Time-delay, UL248-14 listed Time-lag, IEC 127-3 recognized
175 mA (115 Vac line) 125 mA (115 Vac line) 80 mA (230 Vac line) 63 mA (230 Vac line)
Safety Consideration
This device is marked with the international Caution symbol.
The instrument is a panel mount device protected in accordance with Class I of EN61010-1 (AC units) and Class III (DC units). Remember that the unit has no power-on switch. Building installation should include a switch or circuit-breaker that must be compliant to IEC 947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on the top of the instrument housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the instrument if EMC problems persist.
10-32 Vdc, 7.5 W
* Factory Default Settings
DP25-S and DP25B-S
Strain Gage Panel Meter
In order to maintain the same degree of protection as the AC units, always use a Safety Agency Approval DC source with the same Overvoltage Category and Pollution Degree.
Servicing North America:
USA: One Omega Drive, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com
Canada: 976 Bergar Laval (Quebec) H7L 5A1 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.ca
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
®
Customer Service: 1-800-622-2378 / 1-800-622-BEST
®
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
®
Mexico and TEL: (001)800-TC-OMEGA® FAX: (001) 203-359-7807 Latin American: En Espa
ñol: (001) 203-359-7803
e-mail: espanol@omega.com
Servicing Europe:
Benelux: Postbus 8034, 1180 LA Amstelveen, The Netherlands TEL: +31 20 3472121 FAX: +31 20 6434643 Toll Free in Benelux: 0800 0993344 e-mail: sales@omegaeng.nl
Czech Republic: Frystatska 184, 733 01 Karviná TEL: +420 59 6311899 FAX: +420 59 6311114 e-mail: info@omegashop.cz
France: 11, rue Jacques Cartier, 78280 Guyancourt TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27 Toll Free in France: 0800 466 342
e-mail: sales@omega.fr
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany TEL: +49 7056 9398-0 FAX: +49 7056 9398-29 Toll Free in Germany: 0800 639 7678 e-mail: info@omega.de
United Kingdom: One Omega Drive
ISO 9002 Certified River Bend Technology Centre
Northbank, Irlam Manchester M44 5BD United Kingdom TEL: +44 161 777 6611 FAX: +44 161 777 6622 Toll Free in England: 0800 488 488 e-mail: sales@omega.co.uk
OMEGAnet® On-Line Service
www.omega.com
Internet e-mail
info@omega.com
®
®
Scaling Without Known Loads (Continued)
To define the maximum load (IN!2 and RD!2
):
1. Repeat steps 3–8 above, entering the values for IN!2 and RD!2 .
2. Once you've completed all steps, the unit displays:
To begin operation: Reinitialize the unit (press RESET twice or press MENU until RST flashes on the
display). When a numeric reading appears, the unit is operational.
Determining Reading Offset
The run mode reading for meters scaled without known loads may reflect an offset. For example, say you set
RD!1
to 0 and
RD!2
to 100, but when the minimum load is applied, a
negative value of –1.5 displays on the front panel. To correct the reading offset:
1. With zero load applied, note the reading on the display.
2. Subtract that amount from the RD!1 and RD!2 values you originally entered.
In the example, the offset would be –1.5. If RD!1 is to read 0 in Run Mode, it must be reentered as 1.5. RD!2 must likewise be reentered as 101.5 if the meter is to read 100 when the maximum load is applied.
3.
Repeat the steps for "Scaling Without Known Loads," but when the values for IN!1 and IN!2 display, do not change them. Instead, press MENU to move to the prompts for RD!1 and RD!2 and make the necessary changes.
4. Reinitialize the unit and resume operation.
Scaling Without Known Loads
For 0–100 mV sensors, the values for the minimum and maximum input loads are always as follows:
• Minimum load (IN!1)— 0
• Maximum load (IN!2)— 9999. If your installation uses a different sensor type, you must calculate the values for IN!1 and IN!2 before proceeding with the steps below. Use the formula provided in the Operator's Manual.
To define the minimum load
(
IN!1 and RD!1
):
1. If it's not already shown, press MENU
until the unit displays:
2. Press /TARE. The unit displays:
3. Press /TARE again. The unit
displays the last setting for IN!1. (The first digit flashes.)
4. Change IN!1 as necessary:
Press
/NT/GRS to set or change the digit's current value.
Continue to press
/NT/GRS until the meter displays the
desired value for the flashing digit. Values can range from 0 to 9. For the first digit, you can also enter a minus sign (–) or –1.
• Press /TARE to scroll to the digit(s) you want to change.
5. Press MENU to store IN!1.
The unit displays:
6. Press /TARE. The unit displays
the last setting for RD!1. (The first digit flashes.)
7. Change RD!1 as necessary:
• Press /NT/GRS until the meter displays the desired value for the flashing digit. Values can range from 0 to 9. For the first digit, you can also enter a minus sign (–) or –1.
• Press
/TARE to scroll to the digit(s) you want to change.
8. Press MENU to store the value
shown for RD!1. The unit displays:
Scaling With Known Loads (Continued)
6. Press MENU to store IN!1. The unit
displays:
7. Press /TARE. The unit displays the
last setting for RD!1.
8. Change RD!1 as necessary:
• Press /TARE to scroll to the digit(s) you want to change (it flashes on the display).
• Press
/NT/GRS to change the value of the flashing digit.
Values can range from 0 to 9. For the first digit, you can also enter a minus sign (–) or –1.
9. Press MENU to store the value shown
for RD!1. The unit displays:
To identify the maximum known load (IN!2 and RD!2
):
1. Apply the maximum known load (100%).
2. Repeat steps 4–9 for IN!2 and RD!2 .
Once you've completed all steps, the unit displays:
To begin operation:
Reinitialize the unit (press RESET twice or press MENU until RST flashes on the display). When a numeric reading appears, the unit is operational.
Scaling With Known Loads
To identify the minimum known load (IN!1 and RD!1
):
1. If it's not already shown, press MENU
until the unit displays:
2. Apply the minimum known load (0%).
3. Press /TARE. The unit displays:
4. Press /TARE again. The unit
displays the last setting for
IN!1
.
5. Press /TARE again. The unit
displays the actual reading being received from the sending device.
5678
To Scale the Meter
You can scale the meter in one of two ways:
1. With a known load — This method uses input (load) information sent from another device such as a scale or a simulator for voltage or current.
2. Without a known load — This involves calculating the load based on transducer specifications and manually entering it to the meter.
For both methods, you must first identify the minimum input load IN!1 and the corresponding display reading you want RD!1. Then you identify the maximum input load IN!2 and its corresponding display reading RD!2.
The decimal point is for display purposes only — you set it where you want it to display for your application. When entering IN!1 and IN!2 values, ignore any decimal point on the display. However, you must enter RD!1 and RD!2 values with the decimal point in the desired position.
MQS3598/0403
WARRANTY/DISCLAIMER
OMEGA Engineering, Inc. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at no charge. Omega's WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use if its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGAassumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:
1. P.O. number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-W
ARRANTY
REPAIRS, consult OMEGAfor current repair charges. Have the following information available BEFORE contacting OMEGA:
1. P.O. number to cover the COST of
the repair,
2. Model and serial number of product,
and
3. Repair instructions and/or specific
problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. © Copyright 2003 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without prior written consent of OMEGAENGINEERING, INC.
PATENTNOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577; 6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 / UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The “Meter Case Bezel Design” is a trademark of NEWPORT Electronics, Inc., registered in the U.S. USED UNDER LICENSE. Other U.S. and International patents pending or applied for.
This device is marked with the international caution symbol. It is important to read the SetupGuide before installing or commissioning this device as it contains important information relating to safety and EMC.
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
TRADEMARK NOTICE:
®
,
omega.com
®
and
are trademarks of OMEGA Engineering, Inc.
®
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
Loading...