To Set the Decimal Point
1. If it's not already shown,
press MENU until the unit
displays DEC.P
2. Press /DEV to show the
current decimal point location.
3. Press /MAX to move the
decimal point to the desired
location. The choices are
FFFF or FFF.F.
4. Press MENU to store the value.
5. Press RESET twice to display the current temperature.
To Select Temperature Unit
(Fahrenheit or Celsius):
1. Press MENU until the display
shows RD.CF
2. Press /DEV to display the
current temperature unit.
3. Press /MAX to select
between °F and °C.
4. Press MENU to store the value.
5. Press RESET twice to display the current temperature.
To Enter Setpoints:
1. Press SETPTS to display the
current setpoint. The leftmost
digit will flash.
2. Press /DEV to select the
digit you want to change.
3. Press /MAX to increase the
value of the flashing digit.
4. Press SETPTS to store the
setpoint.
5. Repeat steps 1 through 4 to enter the next setpoint.
DP25-TC and DP25B-TC
PROGRAMMABLE DIGITAL
THERMOCOUPLE CONTROLLER
This device is marked with the international caution symbol. It is important
to read the Setup Guide before installing or commissioning this device as
it contains important information relating to safety and EMC.
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI
regulations that apply. OMEGA is constantly pursuing certification of its products to
the European New Approach Directives. OMEGA will add the CE mark to every
appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA
Engineering, Inc. accepts no liability for any errors it contains, and reserves the right
to alter specifications without notice.
TRADEMARK NOTICE:
®
omega.com
®
, and ,
are trademarks of OMEGA Engineering, Inc.
WARNING: These products are not designed for use in, and should not be used
for, patient connected applications.
MQS3732/1205
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in
materials and workmanship for a period of one (1) year from the date of
purchase. In addition to OMEGA’s standard warranty period, OMEGA
Engineering will extend the warranty period for four (4) additional years if the
warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation.
OMEGA’s Customer Service Department will issue an Authorized Return (AR)
number immediately upon phone or written request. Upon examination by
OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any
action of the purchaser, including but not limited to mishandling, improper
interfacing, operation outside of design limits, improper repair, or unauthorized
modification. This WARRANTY is VOID if the unit shows evidence of having
been tampered with or shows evidence of having been damaged as a result of
excessive corrosion; or current, heat, moisture or vibration; improper
specification; misapplication; misuse or other operating conditions outside of
OMEGA’s control. Components which wear are not warranted, including but not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products.
However, OMEGA neither assumes responsibility for any omissions or
errors nor assumes liability for any damages that result from the use of its
products in accordance with information provided by OMEGA, either
verbal or written. OMEGA warrants only that the parts manufactured by it
will be as specified and free of defects. OMEGA MAKES NO OTHER
WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER,
EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED
WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order,
whether based on contract, warranty, negligence, indemnification, strict
liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be
liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall
it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with
any nuclear installation or activity; or (2) in medical applications or used on
humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA
assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER
language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA
harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service
Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA,
PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER
FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on
the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper
packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please
have the following information available
BEFORE contacting OMEGA:
1. P.O. number under which the
product was PURCHASED,
2. Model and serial number of the
product under warranty, and
3. Repair instructions and/or specific
problems relative to the product.
FOR NON-W
ARRANTY REPAIRS,
consult OMEGA for current repair
charges. Have the following information
available BEFORE contacting OMEGA:
1. P.O. number to cover the COST of
the repair,
2. Model and serial number of product,
and
3. Repair instructions and/or specific
problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an
improvement is possible. This affords our customers the latest in technology and
engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2005 OMEGA ENGINEERING, INC. All rights reserved.
This document may not be copied, photocopied, reproduced, translated, or reduced
to any electronic medium or machine-readable form, in whole or in part, without
prior written consent of OMEGA ENGINEERING, INC.
PATENT NOTICE: This product is covered by one or more of the following
patents: U.S. Pat. No. Des. 336,895; 5,274,577; 6,243,021 / CANADA 2052599;
2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN
2039150; 2048066 / UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY
DE 41 34398 C2. The “Meter Case Bezel Design” is a trademark of NEWPORT
Electronics, Inc. USED UNDER LICENSE. Other U.S. and International patents
pending or applied for.
56
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
®
®
OMEGAnet® On-Line Service
www.omega.com
Servicing North America:
USA: One Omega Drive, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700
e-mail: info@omega.com
Canada:> 976 Bergar
Laval (Quebec) H7L 5A1
TEL: (514) 856-6928 FAX: (514) 856-6886
e-mail: info@omega.ca
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
Customer Service: 1-800-622-2378 / 1-800-622-BEST
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
Mexico and TEL: (001)800-TC-OMEGA® FAX: (001) 203-359-7807
Latin American: En Espa
e-mail: espanol@omega.com
ñol: (001) 203-359-7803
Servicing Europe:
Czech Republic: Frystatska 184, 733 01 Karviná
TEL: +420 59 6311899 FAX: +420 59 6311114
e-mail: info@omegashop.cz
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 7056 9398-0 FAX: +49 7056 9398-29
Toll Free in Germany: 0800 639 7678
e-mail: info@omega.de
United Kingdom: One Omega Drive
ISO 9002 Certified River Bend Technology Centre
Northbank, Irlam Manchester M44 5BD United Kingdom
TEL: +44 161 777 6611 FAX: +44 161 777 6622
Toll Free in England: 0800 488 488
e-mail: sales@omega.co.uk
Internet e-mail
info@omega.com
®
®
®
START HERE
2
34
Thermocouple Wire Connection
1. Connect positive (+) lead of thermocouple.
2. Connect negative (-) lead of thermocouple.
Note: The negative lead is red.
Example hook up for AC Load
Alarm 1 (Setpoint) Hook-up
1. Connect a jumper from ac Line to Relay 1 Common
(Terminal 3).
2. Connect Relay 1 Normally Open (Terminal 1) to External
Alarm ac Line.
3. Connect External Alarm to ac Neutral.
Alarm 2 (Setpoint) Hook up
1. Connect a jumper from ac Line to Relay 2 Common
(Terminal 6).
2. Connect Relay 2 Normally Open (Terminal 4) to External
Alarm ac Line.
3. Connect External Alarm to ac Neutral.
Analog Output Wiring for 4 - 20 mA Current
1. Connect Positive Lead to Terminal 11.
2. Connect Negative Lead to Terminal 12.
For 0 -10 Voltage
1. Connect Positive Lead to Terminal 10.
2. Connect Negative Lead to Terminal 12.
Using This Quick Start Manual
Use this Quick Start Manual with your controller to make
changes to the thermocouple type, decimal point, units, and to
change the setpoints.
Features with are for the “B” version which has threecolor programmable “Big” LED display - All segment
characters shown are for the “B” version.
For detailed instructions, refer to the appropriate section
in the Operator’s Manual.
Before You Begin
In addition to the meter and the related parts, you will need
the following items to set up your meter:
• ac power, as listed on meter’s ID/Power Label
• Thermocouple
• 1/8” flat blade screwdriver
Mount the Unit
1. Cut a panel opening using
the dimensions shown to
the right.
2. Position the unit in the
opening, making sure the
front bezel is flush with the
panel.
3. Install retaining clip on the
meter and tighten against
the panel.
Wiring
1. Remove the panel at the back of the unit.
2. Locate the TB1 connector.
3. Insert the correct wire in each terminal as shown in the
following figure and tighten the lockdown screws.
4. Tug gently on the wires to verify the connections.
AC Powered Unit Connections
External Fuse Required:
Time-delay, UL 248-14 listed Time-lag, IEC 127-3 recognized
175 mA (115 Vac line) 125 mA (115 Vac line)
80 mA (230 Vac line) 63 mA (230 Vac line)
In order to maintain the same degree of
protection as the AC units, always use a
Safety Agency Approval DC source with
the same Overvoltage Category and
Pollution Degree.
Warning: Do not connect AC power to your device until you
have completed all input and output connections. This
device must only be installed by a specially trained
electrician with corresponding qualifications. Failure to
follow all instructions and warnings may result in injury!
Safety Consideration
This device is marked with the international Caution symbol.
The instrument is a panel mount device protected in
accordance with EN61010-1 (Safety requirements for electrical
equipment for measurement, control, and laboratory standard).
Remember that the unit has no power-on switch. Building
installation should include a switch or circuit-breaker that must
be compliant to IEC 947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on the
top of the instrument housing.
• Always disconnect power before changing signal and
power connections.
• Do not use this instrument on a work bench without its
case for safety reasons.
• Do not operate this instrument in flammable or explosive
atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
•
Install Ferrite Bead(s) on signal wire close to the instrument
if EMC problems persist.
Wiring the Controller
Typical Wiring of TB1
Using the Configuration Menu
To configure the meter, you use the buttons on the front panel.
To: Take This Action:
Display the Press the MENU button. The first function
Configuration Menu on the menu, INPT, displays.
Select a submenu 1. Press MENU until the function you
function want is shown.
2. Press /DEV.
The information you can change flashes.
Select a value 1. Press /MAX to display the option
for that submenu you want.
function 2. Press MENU to store it.
STRD quickly flashes, indicating that
the selection has been stored in memory.
Then the next menu function displays.
Go back to previous Press RESET once.
menu function
Exit the Press RESET twice. The unit displays
Configuration RST as it reinitializes. When a numeric
Menu value displays, the unit is in run mode.
(Optionally, you can press MENU to
move through all the menu functions
until the unit reinitializes.)
MENU SUBMENU /DEV DESCRIPTION
INPT J.TC, K.TC*, DJ.TC, T.TC Input
DEC.P FFFF*, FFF.F Decimal Point
RD.CF R.1=C, R.1=F
*
Reading Configuration
COLR GRN, RED , AMBR Display Color
S1.CF S.1=A*, S.1=B
Setpoint 1 Configuration
S.2=U*, S.2=L
S2.CF S.1=A*, S.1=B
Setpoint 2 Configuration
S.2=U*, S.2=L
S1.DB 0003
*
Setpoint 1, Deadband
S2.DB 0003
*
Setpoint 2, Deadband
OT.CF O.1=E*, 0.1=D Analog Output
O.2=C*, 0.2=V
Configuration
O.3=A*, 0.3=P
O.4=D, 0.4=R
O.5=F, 0.5=H
P.BND 0000 shown if 0.3 = P Proportional Band
M.RST 0000 shown if 0.3 = P Manual Reset
OT.S.O RD!1, OUT1, RD!2 , OUT2
Output Scale & Offset
CJ.OF 0000
Cold Junction Offset
LK.CF RS=E*, RS=D
Lockout Configuration
SP=E*, SP=D
L3=0*, L3=1
BRIT M.BrT, L.BrT, H.BrT
Display Brightness
* Factory Default Settings.
DC Powered Unit Connections
Using the Menus
To Change the Thermocouple Type:
1. Press MENU until the display
shows INPT
2. Press /DEV to show current
thermocouple type:
3. Press /MAX to select the
setting from J, K, T or DJ.TC.
4. Press MENU to store the value.
5. Press RESET twice to display the current temperature.
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX
SETPTS /DEV MENU RESET
/MAX