User’s Guide
www.omega.com
iSeries info: www.omega.com/specs/iseries
Temperature & Humidity
CNiTH-i8DH, i8DV, i16D, i32
Controller Manual
Shop on line at
RoHS 2 Compliant
®
®

!
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or
commissioning this device as the guide contains important information relating to safety and EMC.
®
®
OMEGAnet® On-Line Service
www.omega.com
Internet e-mail
Servicing North America:
USA: One Omega Drive, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700
Canada:
976 Bergar
Laval (Quebec) H7L 5A1
TEL: (514) 856-6928 FAX: (514) 856-6886
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
Customer Service: 1-800-622-2378 / 1-800-622-BEST
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
Mexico and TEL: (001)800-TC-OMEGA® FAX: (001) 203-359-7807
Latin America: En Español: (001) 203-359-7803
®
®
®
Servicing Europe:
Benelux: Postbus 8034, 1180 LA Amstelveen, The Netherlands
Czech Republic:
France:
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
United Kingdom:
ISO 9002 Certified River Bend Technology Centre
TEL: +31 20 3472121 FAX: +31 20 6434643
Toll Free in Benelux: 0800 0993344
Frystatska 184, 733 01 Karviná
TEL: +420 59 6311899 FAX: +420 59 6311114
11, rue Jacques Cartier, 78280 Guyancourt
TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27
Toll Free in France: 0800 466 342
TEL: +49 7056 9398-0 FAX: +49 7056 9398-29
Toll Free in Germany: 0800 639 7678
One Omega Drive
Northbank, Irlam Manchester M44 5BD United Kingdom
TEL: +44 161 777 6611 FAX: +44 161 777 6622
Toll Free in England: 0800 488 488
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the mark to
every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WA
RNING: These products are not designed for use in, and should not be used for, patient-connected applications.

TABLE OF CONTENTS
Part 1: Introduction............................................................................................2
1.1 Description .................................................................................2
1.2 Safety Considerations ...............................................................3
1.3 Before You Begin .......................................................................4
Part 2: Setup.......................................................................................................5
2.1 Front Panel .................................................................................6
2.2 Rear Panel Connections............................................................6
2.3 Electrical Installation .................................................................7
2.3.1 Power Connections........................................................7
2.3.2 Humidity and Temperature Probe .................................8
2.3.3 Wiring Outputs - Wiring Hookup...................................9
2.3.4 Dual Display Color Setup.............................................11
Part 3: Operation: Configuration Mode .........................................................12
3.1 Introduction ..............................................................................12
Turning your Instrument On for the First Time
Buttons Functions in Configuration Mode
3.2 Menu Configuration ................................................................13
3.2.1 ID Number .....................................................................14
3.2.2 Setpoints .......................................................................15
3.2.3 Configuration Menu ....................................................15
3.2.4 Reading Configuration Menu .....................................16
3.2.5 Alarm 1 Menu ...............................................................17
3.2.6 Analog Output (Retransmission) Menu......................21
3.2.7 Alarm 2 Menu................................................................24
3.2.8 Loop Break Time Menu/Field Calibration...................25
3.2.9 Output 1 Menu ..............................................................27
3.2.10 Output 2 Menu ..............................................................34
3.2.11 Ramp and Soak Menu ..................................................36
3.2.12 ID Code Menu ...............................................................38
3.2.13 Communication (Options) Menu.................................40
3.2.14 Display Color Selection Menu.....................................46
Part 4: Specifications ......................................................................................49
Part 5: Factory Preset Values.........................................................................52
APPROVAL INFORMATION .......................................................................54

LIST OF FIGURES:
Figure 2.1 Front Panel Display..............................................................................5
Figure 2.2 Rear Panel Power and Output Connections ......................................6
Figure 2.3 Rear Panel Input Connections ............................................................6
Figure 2.4 Main Power Connections.....................................................................7
Figure 2.5 Probe Wiring Hookup...........................................................................8
Figure 2.6 Output Connections:
a) Mechanical Relay and SSR Outputs – Wiring Hookup...............9
b) Pulse and Analog Outputs – Wiring Hookup...............................9
Figure 2.7 Typical Application...............................................................................9
Figure 2.8 Communication Output:
a) RS-232 Output – Wiring Hookup ................................................10
b) RS-485 Output – Wiring Hookup ................................................10
Figure 2.9 Excitation Output................................................................................10
Figure 2.10 Snubber Circuits Wiring Hookup ......................................................10
Figure 2.11 i/8D Locations of S1 and Selectable Jumper Positions..................11
Figure 2.12 i/16D Location of S1 and Selectable Jumper Positions..................11
Figure 3.1 Flow Chart for ID and Setpoints........................................................13
Figure 3.2 Flow Chart for Configuration Menu ..................................................15
Figure 3.3 Flow Chart for Reading Configuration Menu ...................................16
Figure 3.4 Flow Chart for Alarm 1.......................................................................17
Figure 3.5 Flow Chart for Analog Output (Retransmission).............................21
Figure 3.6 Flow Chart for Alarm 2.......................................................................24
Figure 3.7 Flow Chart for Loop Break Time.......................................................25
Figure 3.8 Flow Chart for Output 1 .....................................................................27
Figure 3.9 Flow Chart for Output 2 .....................................................................34
Figure 3.10 Flow Chart for Ramp and Soak .........................................................36
Figure 3.11 Flow Chart for ID Code.......................................................................38
Figure 3.12 Flow Chart for Communication Option ............................................40
Figure 3.13 Flow Chart for Display Color Selection............................................46
LIST OF TABLES:
Table 2.1 Front Panel Annunciators....................................................................5
Table 2.2 Rear Panel Connector..........................................................................6
Table 2.3 Fuse Requirement ................................................................................7
Table 3.1 Button Function in Configuration Mode...........................................12
Table 3.2 Command Letters and Suffix for iTH ...............................................41
Table 5.1 Factory Preset Values........................................................................52
ii

NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provides you with information that is important to successfully
setup and use the Programmable Digital Meter.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or
practices that can effect the instrument’s functionality and must refer
to accompanying documents.
TIP: Provides you helpful hints.
1

PART 1
INTRODUCTION
1.1 Description
The iTH Series instruments monitor and control both temperature and relative humidity.
• Used with an iTH probe the controller comes with dual displays. The top displays
relative humidity and the bottom displays temperature. Relative Humidity can be
toggled with Temperature readings (by pressing the bbutton) or Dewpoint readings
(by pressing the cbutton). Dewpoint is the temperature at which water vapor from
the air begins to form droplets and condenses on surfaces that are colder than the
dewpoint of air.
• The temperature and humidity control can be achieved by using on/off or PID
heat/cool control strategy. Control can be optimized with an auto tune feature. The
instrument offers a ramp to setpoint with timed soak period before switching off the
output.
The instruments are simple to configure and use, while providing tremendous versatility
and a wealth of powerful features. The iTH Series instruments are available either as
monitors or controllers. The monitors are extremely accurate programmable digital panel
meters displaying humidity, temperature, or dew point. The controllers also provide dual
loop control for both humidity and temperature and are easily programmed for any
control or alarming requirement from simple on-off to full autotune PID control.
The iTH family of meters and controllers are available in four true DIN Sizes with NEMA 4,
IP65 splash resistant bezels: the ultra compact 1/32 DIN (the world's smallest dual loop
Humidity + Temperature controller); the popular midsize 1/16 DIN square bezel with dual
display; the 1/8 DIN vertical, and the 1/8 DIN horizontal with the big bright 21mm digits.
The iTH series LED displays can be programmed to change color between Green,
Amber, and Red at any set point or alarm point.
The iTH controller models offer a choice of two control or alarm outputs in almost any
combination: solid state relays (SSR); Form "C" SPDT (Single Pole Double Throw)
relays; pulsed 10 Vdc output for use with an external SSR; or Analog Output selectable
for control or retransmission of the process value. Universal power supply accepts 90 to
240 Vac. Low voltage power option accepts 24 Vac or 12 to 36 Vdc.
The Networking and Communications options include direct Ethernet LAN connectivity
with an Embedded Web Server, and serial communications. The -C24 serial
communications option includes both RS-232 and RS-485. Protocols include both
MODBUS and a straightforward ASCII protocol. The -C4EI option includes both Ethernet
and RS-485 ASCII/MODBUS on one device.
The iTH Series meters and controllers are designed for easy integration with popular
industrial automation, data acquisition and control programs as well as Microsoft Visual
Basic and Excel. provides free configuration and data acquisition software and demos
which makes it fast and easy to get up and running with many applications.
2

1.2 Safety Considerations
This device is marked with the international caution symbol. It is important
to read this manual before installing or commissioning this device as it
contains important information relating to Safety and EMC
(Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with
EN 61010-1:2001, electrical safety requirements for electrical equipment
for measurement, control and laboratory. Installation of this instrument
should be done by qualified personnel. In order to ensure safe operation,
the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuitbreaker shall be included in the building installation as a disconnecting
device. It shall be marked to indicate this function, and it shall be in close
proximity to the equipment within easy reach of the operator. The switch or
circuit-breaker shall meet the relevant requirements of IEC 947–1 and
IEC 947-3 (International Electrotechnical Commission). The switch shall
not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn
from the main supply in case of a fault in the equipment, an overcurrent
protection device shall be installed.
• Do not exceed voltage rating on the label located on the top of the
instrument housing.
• Always disconnect power before changing signal and power
connections.
• Do not use this instrument on a work bench without its case for safety
reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate ventilation to ensure
instrument does not exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain
and power requirements. Install without exposing bare wire outside the
connector to minimize electrical shock hazards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC
problems persist.
Failure to follow all instructions and warnings may result in injury!
3

1.3 Before You Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything
listed. Inspect the container and equipment for signs of damage as soon
as you receive the shipment. Note any evidence of rough handling in
transit. Immediately report any damage to the shipping agent. The carrier
will not honor damage claims unless all shipping material is saved for
inspection. After examining and removing the contents, save the packing
material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service
Department, listed in this manual.
Manuals, Software:
The latest Operation and Communication Manual as well as free
configuration software and ActiveX controls are available from
the
website listed in this manual or on the CD-ROM enclosed with your
shipment
.
For first-time users: Refer to the QuickStart Manual for basic operation
and set-up instructions.
If you have the Serial Communications/Ethernet Option you can easily
configure the controller on your computer or on-line.
To Disable Outputs:
To ensure that menu changes are properly stored, Standby Mode should
be used during setup of the instrument. During Standby Mode, the
instrument remains in a ready condition, but all outputs are disabled.
Standby Mode is useful when maintenence of the system is necessary.
When the instrument is in "RUN" Mode, push d twice to disable all
outputs and alarms. It is now in "STANDBY" Mode. Push d once more
to resume "RUN" Mode.
PUSH d TWICE to disable the system during an EMERGENCY.
To Reset the Meter:
When the controller is in the "MENU" Mode, push c once to direct
controller one step backward of the top menu item.
Push c twice to reset controller, prior to resuming "Run" Mode except
after "Alarms", that will go to the "Run" Mode without resetting the
controller.
4

PART 2
SETUP
2.1 Front Panel
Figure 2.1 Front Panel Display
The upper display may be RH, Temperature or Dewpoint readings
depending on your Reading Configuration selections. Factory defaults
are shown in Figure 2.1.
The Dual Display allows the user to observe the
Relative Humidity or Dewpoint (upper display) and Temperature Value
(lower display), at the same time.
Table 2.1 Front Panel Annunciators
1
Output 1/Setpoint 1/ Alarm 1 indicator
2
Output 2/Setpoint 2/ Alarm 2 indicator
°C
°C unit indicator for Temperature or Dewpoint
°F
°F unit indicator for Temperature or Dewpoint
%RH
Display shows the Percent Relative Humidity
D
Display shows the Dewpoint
a
Changes display to Configuration Mode and advances through menu items*
b
Used in Program Mode:
On Dual Display: swaps the upper and lower displays from RH readings to
Temperature readings. Note: this eliminates the small LED ennuciators*
On Single Display units: replaces RH readings to Temperature readings*
c
Used in Program Mode:
On Dual Display: changes upper display from RH readings to Dewpoint readings*
On Single Display units: replaces RH readings to Dewpoint readings*
d
Accesses submenus in Configuration Mode
and stores selected values*
* See Part 3 Operation: Configuration Mode.
5
Refer to the Quick Start
Guide for assembly and
disassembly instructions.
Relative Humidity
Upper Display
Temperature
Lower Display
iTH-i32
1
2
%RH
D
1
2
%RH
D
1
1.00
[25.4]
1
2
%RH
D
1
1
2
C
F
2
1
%RH
D
iTH-i16D
iTH-i8DH
iTH-i8DV

2.2 Rear Panel Connections
The rear panel connections are shown in Figures 2.2 and 2.3.
Figure 2.2 Rear Panel Power and Output Connections
Figure 2.3 Rear Panel Input Connections
Table 2.2 Rear Panel Connector
POWER AC/DC Power Connector: All models
INPUT iTH-PROBE
OUTPUT 1 Based on one of the following models:
Relay SPDT
Solid State Relay
Pulse
Analog Output (Voltage and Current)
OUTPUT 2 Based on one of the following models:
Relay SPDT
Solid State Relay
Pulse
OPTION Based on one of the following models:
RS-232C or RS-485 programmable
Excitation
6 5 4 6 5 4 6 5 4 3 2 1 3 2 1
8 7 6 5 4 3 2 1
N/C
SHIELD
RED(VCC)
WHITE(CLK)
BLACK(RTN)
GREEN(DATA)

2.3 Electrical Installation
2.3.1 Power Connections
Caution: Do not connect power to your device until you have completed all
input and output connections. Failure to do so may result in injury!
Connect the main power connections as shown in Figure 2.4.
Figure 2.4 Main Power Connections
Table 2.3 Fuse Requirement (see specifications)
FUSE Connector Output Type For 115Vac For 230Vac DC
FUSE 1 Power N/A 100 mA(T) 100 mA(T) 100 mA(T)
FUSE 2 Power N/A N/A N/A 400 mA(T)
For the low voltage power option, in order to maintain the same degree of
protection as the standard high voltage input power units (90 - 240 Vac),
always use a Safety Agency Approved DC or AC source with the same
Overvoltage Category and pollution degree as the standard AC unit (90 240 Vac).
The Safety European Standard EN61010-1 for measurement, control,
and laboratory equipment requires that fuses must be specified based on
IEC127. This standard specifies for a Time-lag fuse, the letter code “T”.
The above recommended fuses are of the type IEC127-2-sheet III. Be
aware that there are significant differences between the requirements
listed in the UL 248-14/CSA 248.14 and the IEC 127 fuse standards. As a
result, no single fuse can carry all approval listings. A 1.0 Amp IEC fuse
is approximately equivalent to a 1.4 Amp UL/CSA fuse. It is advised to
consult the manufacturer’s data sheets for a cross-reference.
7
Use copper conductors
only for power connections

2.3.2 Humidity and Temperature Probe
The figure below shows the wiring hookup for the temperature and humidity probe.
Choose one which gives the best signal integrity-
1) Connect Probe’s Shield to RTN if Probe Housing is not
connected to
Earth Ground.
OR
2) Connect Probe’s Shield to Earth Ground if Probe Housing is not
connected to Earth Ground.
Figure 2.5 Probe Wiring Hookup
METAL HOUSING
IS CONNECTED
TO SHIELD WIRE
N/C
RED(VCC)
WHITE(CLK)
BLACK(RTN)
GREEN(DATA)
SHIELD(See Note)

9
2.3.3 Wiring Outputs
This meter has two factory installed outputs. The SPDT Mechanical Relay, SPST
Solid State Relay, Pulse and Analog Output Connection are shown below.
Figure 2.6
a) Mechanical Relay and SSR b) Pulse and Analog
Outputs Wiring Hookup Outputs Wiring Hookup
Figure 2.7 Typical Applications
Use copper conductors
only for power connections
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH dc VOLTAGE SSR DRIVER OUTPUT
Vac
TEMPERATURE
CONTROLLER
CONTROL
SIDE
0 or 5 Vdc,
TYPICALLY
dc INPUT
SSR
431
LOAD
SIDE
2
HEATER
FAST BLOW
FUSE
Vac
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OUTPUT
TEMPERATURE
CONTROLLER
Vac
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH TRIAC OUTPUT
TEMPERATURE
CONTROLLER
Vac
CONTROL
SIDE
Vac
DRIVING
SSR
CONTROL SIDE
LOAD
RESISTOR
Vac
DRIVING
SSR
ac INPUT
SSR
431
ac INPUT
SSR
431
LOAD
SIDE
2
LOAD
SIDE
2
HEATER
FAST BLOW
FUSE
HEATER
FAST BLOW
FUSE
Vac
Vac

10
This device may have a programmable communication output. The RS-232 and
RS-485 Output Connection are shown below.
Figure 2.8
a) RS-232 Output Wiring Hookup b) RS-485 Output Wiring Hookup
This device may also have an excitation
output.
Excitation is not available if
communication option is installed.
If the Dual Display model has a Low
Voltage power supply option, then
excitation is not available.
This device has snubber circuits designed to
protect the contacts of the mechanical relays
when it switches to inductive loads (i.e.
solenoids, relays). These snubbers are
internally connected between the Common (C)
and Normally Open (NO) relay contacts of
Output 1 and Output 2.
If you have an inductive load connected
between Common (C) and Normally
Closed (NC) contacts of the
mechanical relays and you want to
protect them from the rush current
during the switching period, you have
to connect an external snubber circuit
between Common (C) and Normally
Closed (NC) contacts as indicated in
Figure 2.10.
Figure 2.10
Snubber Circuits Wiring
Hookup
Figure 2.9
Excitation Output

11
2.3.4 Dual Display Color Setup
The dual display option allows the user to change the color of the upper and
lower displays.
To change the color of the upper display, see Section 3.2.14
(Display Color section).
To change the color of the lower display follow the instructions below:
The unit should be removed from the panel and opened.
Refer to the Quick Start Guide for assembly and disassembly instructions.
The S1 jumper is located on the back side of the display board.
The location of S1 and pin selection jumpers are shown below.
Use a jumper for GREEN or RED, never leave S1 open.
Figure 2.11 i/8D Location of S1 and Selectable Jumper Positions
Figure 2.12 i/16D Location of S1 and Selectable Jumper Positions
i/8DH
Dual
Horizontal
i/8DV
Dual
Vertical

12
PART 3
OPERATION: Configuration Mode
3.1 Introduction
The instrument has two different modes of operation. The first, Run Mode, is
used to display Temperature and Relative Humidity. The other mode, Menu
Configuration Mode, is used to navigate through the menu options and
configure the controller. Part 3 of this manual will explain the Menu
Configuration Mode. For your instrument to operate properly, the user must
first "program" or configure the menu options.
Turning your Controller On for the First Time
The device becomes active as soon as it is connected to a power source. It
has no On or Off switch. The device at first momentarily shows the software
version number, followed by reset
RST
, and then proceeds to the Run Mode.
For first-time users: Refer to the QuickStart Manual for basic operation
and set-up instructions.
If you have the Serial Communications/Ethernet Option you can easily
configure the controller on your computer or on-line.
Table 3.1 Button Function in Configuration Mode
• To enter the Menu, the user must first press abutton.
• Use this button to advance/navigate to the next menu item. The user can
navigate through all the top level menus by pressing a.
• While a parameter is being modified, press ato escape without saving the
parameter.
• Press the up bbutton to scroll through “flashing” selections. When a
numerical value is displayed press this key to increase value of a parameter
that is currently being modified.
• Pressing the bbutton for approximately 3 seconds will speed up the rate at
which the set point value increments.
• In the Run Mode, pressing the b button changes display from RH readings
to Temperature readings.
• Press the down c button to go back to a previous Top Level Menu item.
• Press this button twice to reset the controller to the Run Mode.
• When a numerical value is flashing (except set point value) press cto scroll
digits from left to right allowing the user to select the desired digit to modify.
• When a setpoint value is displayed press c to decrease value of a setpoint
that is currently being modified. Pressing the c button for approximately 3
seconds will speed up the rate at which the setpoint value is decremented.
• In the Run Mode, pressing the c button changes from RH readings to
Dewpoint readings.
• Press the enter d button to access the submenus from a Top Level Menu item.
• Press d to store a submenu selection or after entering a value — the display
will flash a
STRD
message to confirm your selection.
• In the Run Mode, press d twice to enable Standby Mode with flashing
STBY
.
Reset: Except for Alarms, modifying any settings of the menu configuration
will reset the instrument prior to resuming Run Mode.
a
MENU
b
(UP)
c
(DOWN)
d
ENTER

13
3.2 Menu Configuration
It is required that you put the controller in the Standby Mode for any
configuration change other than Setpoints & Alarms.
Figure 3.1 Flow Chart for ID and Setpoints
RdG

14
3.2.1 ID Number
TO ENABLE/DISABLE OR CHANGE ID CODE, SEE SECTION 3.2.12.
If ID Code is Disabled or set as Default (0000) the menu will skip ID
step to Setpoint Menu.
If ID Code is set to Full Security Level and user attempts to enter the
Main Menu, they will be prompted for an ID Code.
If ID Code is set to Setpoint/ID Security Level and user attempts to
enter the Configuration Menu, they will be prompted for an ID Code.
ENTERING YOUR NON-DEFAULT FULL SECURITY ID NUMBER.
Press a 1) Display shows ID.
Press d 2) Display advances to
____
.
Press b & c 3) Press bto increase digit 0-9. Press cto activate next digit
(flashing). Continue to use band c to enter your 4-digit ID
code.
Press d 4) If the correct ID code is entered, the menu will advance to
the Setpoint 1 Menu, otherwise an error message
ERRo
will
be displayed and the instrument will return to the Run Mode.
To change ID Code, see ID Menu in the Configuration section.
ENTERING YOUR NON-DEFAULT SETPOINT/ID SECURITY ID NUMBER.
Press a 5) Display shows
SP1
Setpoint 1 Menu.
Press a 6) Display shows
SP2
Setpoint 2 Menu.
Press a 7) Display shows IDID Code Menu.
Press d 8) Display advances to
____
.
Press b & c 9) Use b and c to change your ID Code.
Press d 10) If correct ID Code is entered, the display will advance to
the
INPT
Input Menu, otherwise the error message
ERRo
will be displayed and the controller will return to the Run
Mode.
To prevent unauthorized tampering with the setup parameters, the
instrument provides protection by requiring the user to enter the ID
Code before allowing access to subsequent menus. If the ID Code
entered does not match the ID Code stored, the controller responds
with an error message and access to subsequent menus will be denied.
Use numbers that are easy for you to remember. If the ID Code is
forgotten or lost, call customer service with your serial number to
access and reset the default to
0000
.

15
3.2.2 Set Points
SETPOINT 1:
Press a 1) Press a, if necessary until
SP1
prompt appears.
Press d 2) Display shows previous value of “Setpoint 1”.
Press b & c 3) Press b and c to increase or decrease Setpoint 1
respectively.
Holding b & c buttons down for approximately 3 seconds will speed up the
rate at which the Setpoint value increments or decrements.
Press b & c 4) Continue to use b and c to enter your 4-digit Setpoint 1 value.
Press d 5) Display shows
STRD
stored message momentarily and then
advances to
SP2
only, if a change was made, otherwise press
a to advance to
SP2
Setpoint 2 Menu.
SETPOINT 2:
Press d 6) Display shows previous value of “Setpoint 2”.
Press b & c 7) Press b and c to increase or decrease Setpoint 2
respectively.
Holding b & c buttons down for approximately 3 seconds will speed up
the rate at which the setpoint value increments or decrements.
Press d 8) Display shows
STRD
stored message momentarily and then
advances to
CNFG
only, if a change was made, otherwise press
a to advance to
CNFG
Configuration Menu.
3.2.3 Configuration Menu
Figure 3.2 Flow Chart for Configuration Menu

16
3.2.4 Reading Configuration
It is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.
Figure 3.3 Flow Chart for Reading Configuration Menu
ENTER READING CONFIGURATION MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu.
Press
d
3) Display advances to
SNSR
Sensor.
SENSOR SUBMENU:
Press
d
4) Sensor selection for Autotune, Loop, or Ramp and Soak
°F.°C
is for temperature and
DRRh
is for Humidity.
TEMPERATURE UNIT SUBMENU:
Press
d
5) Display flashes previous Temperature Unit selection.
Press
b
6) Scroll though the available selections to the Temperature Unit
of your choice: °For °C.
Press
d
7) Display shows
STRD
stored message momentarily and then
advances to
FLTR
Filter Constant.
FILTER CONSTANT SUBMENU:
Press
d
8) Display flashes previous selection for Filter Constant.
Press
b
9) Scroll though the available selections:
0001,0002,0004,0008,0016,0032,0064,0128
Press
d
10) Display shows
STRD
stored message momentarily only, if
change was made, otherwise press ato advance to the next
menu.
The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. A filter value of 2 is
approximately equal to 1 second RC low pass time constant.

17
3.2.5 Alarm 1
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out
available only if Analog Output Option board is factory installed. Alarm1 will only
work for Humidity, not Temperature.
If Analog Output Option is
installed, the controller will skip
Alarm 1 Menu item to Analog
Output.
Alarm must be DISABLED if
Ramp is ENABLED.
Figure 3.4 Flow Chart for Alarm 1
ENTER ALARM 1 MENU:
Press a 1) Press a, if necessary, until
CNFG
prompt appears.
Press d 2) Display advances to
RDG
Reading Configuration Menu.
Press a 3) Press a, until Display advances to
ALR1
Alarm 1 Menu.
Press d 4) Display advances to Alarm 1
ENBL
Enable or
DSBL
Disable
Submenu and flashes the previous selection.
Alarm 1 is designed to
monitor the humidity value
around Setpoint 1 and Alarm
2 is designed to monitor the
temperature value around
Setpoint 2.

18
ALARM 1 ENABLE/DISABLE SUBMENU:
Press b 5) Scroll though the available selection until
ENBL
displays to
use Alarm 1.
Press d 6) Display shows
STRD
stored message momentarily and then
advances to
ABSo
only if it was changed, otherwise press a to
advance to
ABSo
Alarm 1 Absolute/Deviation Submenu.
If
DSBL
Alarm 1 Disabled was selected, all submenus of Alarm 1
Menu will be skipped and meter advances to
ALR2
Alarm 2
Menu. If
ENBL
Alarm 1 Enabled was selected, Output 1 would
be automatically Disabled.
ALARM 1 ABSOLUTE/DEVIATION SUBMENU:
Press
d
7)
Display flashes previous selection. Press bto
ABSo
Absolute or
_DEV
Deviation.
Press
d
8) Display shows
STRD
stored message momentarily (only if it
was changed) and then advances to
LTçH
.
Absolute Mode allows Alarm 1 to function independently from Setpoint 1. If the
process being monitored does not change often, then "Absolute" Mode is
recommended. The absolute Setpoint values are placed in the Alarm 1 Low and
Hi values.
Deviation Mode allows Alarm 1 trigger at the Setpoint 1 value, as long as the
Alarm 1 Low and Hi values equal 0. Deviation mode is typically the ideal mode if
the process temperature changes often.
ALARM 1 LATCH/UNLATCH SUBMENU:
Press
d
9) Display flashes previous selection. Press bto
LTçH
Latched or
UNLT
Unlatched.
Press
d
10) Display shows
STRD
stored message momentarily (only if it
was changed) and then advances to
CT.CL
.
Latched Mode: Relay remains "latched" until reset. To reset already latched
alarm, select Alarm Latch and press Max twice (i.e. Unlatch and then back to
Latch) or from a Run Mode, push dtwice to put the controller in Standby Mode
and then push done more time to return to the Run Mode.
Unlatched Mode: Relay remains latched only as long as the alarm condition is
true.

19
CONTACT CLOSURE SUBMENU:
Press
d
11) Display flashes previous selection. Press b to
N.ç.
Normally
Closed or
N.o.
Normally Open.
Press
d
12) Display shows
STRD
stored message momentarily (only if it
was changed) and then advances to
AçTV
.
Normally Open: If this feature is selected, then the relay is "energized" only
when an alarm condition occurs.
Normally Closed: "Fail Safe" Mode. Relay is energized under "normal"
conditions and becomes de-energized during alarm or power failure.
ACTIVE SUBMENU:
Press
d
13) Display flashes previous selection. Press bto scroll through
the available selections:
ABoV
Above,
BELo
Below,
HI.Lo
HI/Low and
BAND
Band. (Band is active if
_DEV
Deviation was
selected).
Press
d
14) Display shows
STRD
stored message momentarily (only if it
was changed) and then advances to
A.P.oN
.
Above: In Absolute Mode, Alarm 1 is triggered when the process variable is
greater than the Alarm Hi Value (Low value ignored). In Deviation Mode
, Alarm 1 is
triggered at the Setpoint plus any offset placed in the Alarm Hi value.
Below: In Absolute Mode
, Alarm 1 is triggered when the process variable is less
than the Alarm Low Value (Hi value ignored). In Deviation Mode, Alarm 1 is
triggered at the Setpoint plus any offset placed in the Alarm Low value.
Hi/Low: In Absolute Mode, Alarm 1 is triggered when the process variable is less
than the Alarm Low Value or above the Hi Value. In Deviation Mode
, Alarm 1 is
triggered when the process variable is less than the Setpoint minus any offset in
the Alarm Low or greater than the Setpoint plus any offset in the Alarm Hi value.
Band: Alarm 1 is triggered when the process variable is above or below the
"band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.

20
ALARM ENABLE/DISABLE AT POWER ON:
Press
d
15) Display flashes previous selection. Press bto
ENBL
enable
or
DSBL
disable.
Press d 16)
Display shows
STRD
stored message. momentarily
(only if it
was changed)
and then advances to
ALR.L
.
If Alarm at Power On is enabled, the alarm will be active when an alarm
condition occurs.
If Alarm at Power On is disabled, the alarm will not be active (even if an
alarm condition exists) unless the process value moves into a non-alarm
condition and back into an alarm condition.
ALARM 1 LOW VALUE SUBMENU:
Press
d
17) Display flashes 1stdigit of previous value. Use band cto
enter new value.
Press b& c18) Use band cto enter Alarm 1 Low Value.
Press
d
19) Display shows
STRD
storage message momentarily (only if
it was changed) and then advances to
ALR.H
.
ALARM 1 HI VALUE SUBMENU:
Press
d
20) Display flashes 1stdigit of previous value. Use band cto
enter new value.
Press b& c21) Use band cto enter Alarm1 Hi Value.
Press
d
22) Display shows
STRD
stored message momentarily (only if it
was changed) and then advances to the next menu.

21
3.2.6 Analog Output (Retransmission)
Analog Output works only for Humidity Readings and can be configured
as Retransmission or Control outputs. This section will explain
Retransmission Output.
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output
1 & Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog
Output is available only if Analog Output Option board is factory installed.
If Analog Output Option is not installed, the instrument will skip to Alarm 2 Menu.
Figure 3.5 Flow Chart for Analog Output (Retransmission)
ENTER ANALOG OUTPUT MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu.
Press
a
3) Press a, if necessary, until Display advances to
ANLG
Analog Output Menu.
Press
d
4) Display advances to Analog Output
ENBL
Enable or
DSBL
Disable Submenu and flashes the previous selection.

22
ANALOG OUTPUT ENABLE/DISABLE SUBMENU:
Press
b
5) Scroll though the available selection until
ENBL
displays to
use Analog Output Retransmission (output proportional to the
input signal).
Press
d
6) Display shows
STRD
stored message momentarily and then
advances to
CURR
or
VoLT
Submenu only if it was changed,
otherwise press a to advance to
CURR
or
VoLT
Current/Voltage Submenu.
If
DSBL
Analog Output Disabled was selected, all submenus of Analog
Output Menu will be skipped and the meter will advance to
ALR2
Alarm 2
Menu. If
ENBL
Analog Output Enabled was selected, Output 1 would be
automatically Disabled, and reassigned as Analog Output.
CURRENT/VOLTAGE SUBMENU:
Press
d
7) Display flashes
CURR
Current or
VoLT
Voltage.
Press
b
8) Scroll through the available selection: Current or Voltage
(Example
VoLT
).
Press
d
9) Display shows
STRD
stored message momentarily and then
advances to
RD1
Submenu only if it was changed, otherwise
press ato advance to
RD1
Reading 1 Submenu.
READING 1:
Press
d
10) Display flashes 1
st
digit of previous “Reading 1” value.
Press b& c11) Enter “Reading 1” value. (Example 0000)
Press
d
12) Display advances to
OUT.1
Out 1 Submenu.
OUT 1:
Press d 13) Display flashes 1
st
digit of previous “Out 1” value.
Press b & c 14) Enter “Out 1” value. (Example 00.00)
Press d 15) Display advances to RD!2 Reading 2 Submenu.
READING 2:
Press
d
16) Display flashes 1
st
digit of previous “Reading 2” value.
Press b& c17) Enter “Reading 2” value. (Example 100.0)
Press
d
18) Display advances to
OUT.2
Out 2 Submenu.
OUT 2:
Press
d
19) Display flashes 1
st
t
digit of previous “Out 2” value.
Press b& c20) Enter “Out 2” value. (Example 10.00)
Press
d
21) Display advances to the
ALR2
Alarm 2 Menu.
The above example (also the factory default) is for 0-10 V of the entire
range of the Humidity Input and Analog Output. For 0-20 mA output you
need to set “Analog Type” to Current and OUT 2 to 20.00.

23
Accuracy of Analog Output board is +/-1% of FS (Full Scale) when following
conditions are satisfied:
1. The input is not scaled below 1% of Input FS (10 mV @ 1 V or 0.2 mA @
20 mA input ranges).
2. Analog Output is not scaled below 3% of Output FS (300 mV @ 10 V or
0.6 mA @ 20 mA output ranges).
Otherwise certain corrections need to be applied.
For example:
For entire range of Humidity Input, the Analog Output on 10 V FS scaled for
300 mV output range:
Rd1 = 0000, Out1 = 00.00
RD2 = 100.0, Out2 = 00.30
The measured output will be as follows:
Rd1 = 0000, Out1 = -0.07 V
Rd2 = 100.0, Out2 = 0.23 V
This means that for 300 mV output range we have -70 mV offset at zero and at
full scale. In order to compensate this 70 mV offset the correct scaling will be
as follows:
Rd1 = 0000, Out1 = 00.07
Rd2 = 100.0, Out2 = 00.37
The above corrections need to be applied only for Input scaled below 1% of FS
and Output scaled below 3% of FS or if you need the Analog Output
accuracy to be better than 1% of FS.

24
3.2.7 Alarm 2
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out
available only if Analog Output Option board is factory installed. Alarm 2 only
works for Temperature, not Humidity.
Alarm must be DISABLED if Ramp is ENABLED.
Figure 3.6 Flow Chart for Alarm 2
ENTER ALARM 2 MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu.
Press
a
3)
Press a, if necessary, until Display advances to
ALR2
Alarm 2 Menu.
Press
d
4)
Display advances to Alarm 2
ENBL
Enable or
DSBL
Disable
Submenu.
ALARM 2 ENABLE/DISABLE SUBMENU:
5) Display flashes previous selection. Press buntil
ENBL
displays
to use Alarm 2.
Press
d
6) Display shows
STRD
stored message momentarily and then
advances to
ABSo
only if it was changed, otherwise press ato
advance to
ABSo
Absolute/Deviation Submenu.
If
DSBL
Alarm 2 Disabled was selected, all submenus of Alarm 2 will
be skipped and meter advances to
LOOP
Loop Break Time Menu. If
ENBL
Alarm 2 Enabled was selected, Output 2 will automatically
Disabled, and reassigned as Alarm 2.
The remaining Alarm 2 menu items are identical to Alarm 1 Menu. Modifying
Alarm Settings will not reset the instrument.

25
3.2.8 Loop Break Time
Figure 3.7 Flow Chart for Loop Break Time
ENTER LOOP BREAK TIME MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu.
Press
a
3) Press a, if necessary, until Display advances to
LOOP
Loop
Break Time Menu.
Press
d
4) Display advances to Loop Break Time
ENBL
Enable or
DSBL
Disable Submenu and flashes the previous selection.
LOOP BREAK ENABLE/DISABLE SUBMENU:
Press b 5) Scroll through the available selections:
ENBL
or
DSBL
.
Press
d
6) Display shows
STRD
stored message momentarily and then
advances to
B.TIM
Loop Break Time Value Submenu.
Loop Break is an additional safety feature intended to monitor the rate of
change of the process value, while approaching the SP1, if on the Sensor Menu
DRRh
is selected, or SP2 if
°F.°C
is selected. It is strictly intended as an
additional warning system, therefore its use is entirely optional. An active Loop
Break will cause the Process Value digits to blink in a rotating pattern. If the
process value reaches the set point the blinking will stop and
B.TIM
is
completed successfully, otherwise
BR.AL
Break Alarm warning will flash, and
Output 1 will be turned off.
LOOP BREAK TIME VALUE SUBMENU:
Press
d
7) Display flashes 1stdigit of previous Loop Value.
Press b& c8)
Press band cbuttons to enter a new Loop Value (0 to
99.59).
Press
d
9) Display shows
STRD
stored message momentarily and then
advances to
R.ADJ
Reading Adjust Menu.
Loop Break Time Value allows the user to determine the time interval in MM:SS
(from zero to 99 minutes and 59 seconds) that the Process Value changes at
least 10 counts. At the specified time interval, if the process value change is less
than the stated rate, flashing
B.TIM
will be displayed, the output will be deenergized, and Alarm energized. Loop break time will be disabled when the
Process Value (PV) enters the control band.
Loop Break Alarm can work on the RH or Temperature function of the
selection made on the Sensor Menu.
It is required
that you put
the controller
in the Standby Mode
for any configuration
change other than
Set Points & Alarms.

26
READING ADJUST SUBMENU:
Press
d
10) Display flashes 1stdigit of previous reading adjust value.
Press b& c11) Press band cbuttons to enter a new Reading Adjust value
(-1999 to 9999).
Press
d
12) Display shows
STRD
stored message momentarily and then
advances to
SP.DV
Setpoint Deviation Menu.
Reading Offset Adjust
For Relative Humidity, the controller allows the user to fine tune a minor error of
the transducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ± R.ADJ).
R.ADJ is adjustable between -19.99 to 99.99
SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:
Press
d
13) Display advances to Setpoint Deviation
ENBL
Enable or
DSBL
Disable Submenu and flashes the previous selection.
Press
b
14) Scroll through the available selections:
ENBL
or
DSBL
.
Press
d
15) Display shows
STRD
stored message momentarily and
then advances to
OUT1
Menu.
Setpoint Deviation Submenu, if “enabled”, allows changes to Setpoint 1 to be
made automatically to Setpoint 2. This mode is very helpful if the Process Value
changes often. In Setpoint Deviation Mode, set SP2 a certain number of degrees
or counts away from SP1 - this relation remains fixed when SP1 is changed. For
instance: Setting SP1=200 and SP2=20 and enabling
SP.DV
means that the
absolute value of SP2=220. Moving SP1 to 300, the absolute value of SP2
becomes 320.

27
3.2.9 Output 1
Alarm 1 and Output 1 or Analog Output (Retransmission) share the same contacts
on the rear panel connector. If Alarm 1 or Analog Output (Retransmission) is
Enabled, Output 1 is automatically Disabled.
Figure 3.8 Flow Chart for Output 1
It is required that you
put the controller in the
Standby Mode for any
configuration change
other than Set Points &
Alarms. Alarm 1 and
Output 1 will work for
Humidity only.

28
ENTER OUTPUT 1 MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu.
Press
a
3) Press a, if necessary, until Display advances to
OUT1
Output
1 Menu.
Press
d
4) Display advances to
SELF
Self Submenu.
SELF SUBMENU:
The Self Option allows the output of the instrument to be controlled manually
from the front panel.
Press
d
5) Display flashes the current setting of Self,
ENBL
Enabled or
DSBL
Disabled.
Press
b
6) Press the bbutton to select between Enable and Disable.
Press
d
7) If Self
ENBL
Enabled was selected, display shows
STRD
stored message momentarily and then advances to the next
menu (Output 1 setting is completed).
The output is now under the direct control of the operator and
can be adjusted in the Run Mode (
M00.0
to
M99.9
), by pressing
the band cbuttons, where M calls for the Manual (Self)
Control. For example, setting of
M50.0
of an Analog Output of 0
to 10 Vdc would produce roughly 5 Vdc at the output.
8) If Self
DSBL
Disabled was selected, display shows
STRD
stored message momentarily and then advances to
oPLO
Minimum/Percent Low Submenu of Output 1 Menu.
There is a shorter way to Enable or Disable Self Mode. From a Run
Mode, press dand then press a. Self Mode is Enabled now. Press bor
c
to display MXX.X. To disable Self, press dand then press a. Display
goes to the Run Mode. Self Mode is Disabled now.
MINIMUM/PERCENT LOW SUBMENU:
Specify in percent, the minimum value (0000) for control output. If the output is
analog proportional (Current or Voltage), then the minimum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR or Pulse),
then the minimum duty-cycle, in percent, is specified.
Press
d
9) Display flashes 1st digit of previous “Percent Low” setting.
Press b& c10) Use band cbuttons to enter a new value for “Percent Low”.
Press
d
11) Display shows
STRD
stored message momentarily and then
advances to
oPHI
Maximum/Percent High Submenu.

29
MAXIMUM/PERCENT HIGH SUBMENU:
Specify in percent, the maximum value (99) for control output. If the output is
analog proportional (Current or Voltage), then the maximum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR, or Pulse),
then the maximum duty-cycle, in percent, is specified.
Press
d
12) Display flashes 1
st
digit of previous “Percent High” setting.
Press b& c13) Use band cbuttons to enter a new value for “Percent High”.
Press
d
14) Display shows
STRD
stored message momentarily and then
advances to
CTRL
Control Type Submenu.
Example: On an Analog Output of 0~10 Vdc, a setting of %LO = 10 and %HI = 90,
cause the minimum on the control output to be 1 V and the maximum on the
control output to be 9 V. The same setting on a time proportional output, will
cause 10% duty cycle for the minimum control output and 90% duty cycle for
maximum control output. To disable %LO/HI, set LO to 00 and HI to 99. If
%LO/HI
is at other values than the default (%LO = 00, %HI = 99),
SOAK
is disabled.
*CONTROL TYPE OUTPUT:
(Relay, SSR, Pulse or Analog)
Press
d
15) Display flashes
ON.OF
On/Off or
PID
Proportional, Integral,
Derivative.
Press
b
16) Scroll through the available selections: “ON/OFF” or “PID”.
Press
d
17) Display flashes
STRD
stored message momentarily and
then advances to
AçTN
only, if it was changed, otherwise press
a to advance to
AçTN
Action Type Submenu.
The ON/OFF control is a coarse way of controlling the process. The “Dead
Band” improves the cycling associated with the On/Off control. The PID control is
best for processes where the Setpoint is continuously changing and/or a tight
control of the process variable is required. PID control requires tuning and
adjustment of the "Proportional", "Integral or Reset" and "Derivative or Rate"
terms by a trial-and-error method. The instrument provides an "Auto Tuning"
feature making the tuning process automatic, possibly optimum.
* If Analog Output (Current/Voltage) is your control Output 1, this menu i.e.
CTRL
type will not appear, instead
4-20
Current will be displayed. Select
ENBL
for a
4-20 mA current (2-10 V Voltage) outputs or
DSBL
for a 0-20 mA current (0-10 V
Voltage) outputs. If 4-20 mA is enabled, %HI/LO setting will have no effect.
Both Current and Voltage control outputs are active simultaneously.

30
ACTION TYPE SUBMENU:
The error that results from the measurement of the Process Variable may be
positive or negative since it may be greater or smaller than the Setpoint. If a
positive error should cause the instrument output to increase (i.e. cooling), it would
be called Direct Acting. If a negative error should cause the output to increase
(i.e. heating), it would be called Reverse Acting.
Press
d
18) Display flashes
DRçT
Direct or
RVRS
Reverse.
Press
b
19) Scroll through the available selections: “Direct” or “Reverse”.
Press
d
20) Display shows
STRD
stored message momentarily and then
advances to
AUTo
only, if it was changed, otherwise press ato
advance to
AUTo
Auto PID Submenu (if PID Control Type was
selected).
If “ON/OFF” was selected in the Control Type, the display skips
to the Dead Band Submenu.
AUTO PID SUBMENU:
Press
d
21) Display flashes
ENBL
or
DSBL
.
Press
b
22) Scroll through the available selections: “Enable” or
“Disable”.
Press
d
23) Display shows
STRD
stored message momentarily and then
advances to
ANTL
only, if it was changed, otherwise press ato
advance to
ANTL
Anti Integral Submenu.
If “Enabled”, the controller can determine, by enabling Start PID, the
optimum values for the three adjustments — Proportional, Reset and
Rate corresponding to P, I, and D. These values may be changed once
the auto tuning is complete.
If “Disabled” is selected, the user will manually enter these three
adjustment values. If you want the instrument to do the auto PID and the
P , PI or PID, first select auto disable and enter 0000 for unwanted
parameter. i.e. for PI enter 0000 for the rate.
ANTI INTEGRAL SUBMENU:
Press
d
24) Display flashes
ENBL
or
DSBL
.
Press
b
25) Scroll through the available selections: “Enable” or “Disable”.
Press
d
26) Display shows
STRD
stored message momentarily and then
advances to
STRT
only, if it was changed, otherwise press ato
advance to
STRT
to Start Auto Tune PID Submenu (If auto PID
was Enabled).
If Auto PID was disabled display advances to
PRoP
Proportional Band Submenu.

31
If Anti Integral (Anti Windup) Submenu “Enabled”, this feature allows
the error term outside the proportional band to be calculated and
accumulated for integration. This may be an important feature in
applications where fast response time is desirable.
START AUTO TUNE PID:
Press
d
27) Display flashes
ENBL
or
DSBL
.
Press
b
28) Scroll through the available selections: “Enable” or “Disable”.
Press
d
29) Display shows
STRD
stored message momentarily and then
advances to
CYCL
only, if it was changed, otherwise press ato
advance to
CYCL
Cycle Time Submenu.
If “Enabled”, an output needs to be selected from the Reading
Configuration Menu
°F.°C
, or
DRRh
. This way the microcontroller knows
which one of the outputs to Autotune for Temperature or Humidity. Also,
the controller is ready to calculate P, PI or PID parameters. The
instrument performs this by activating the output and observing the delay
and rate at which the Process Value changes. The setpoints must be at
least 18°F (10°C) or 10%RH above the (PV) Process Value in order to
perform Auto Tune, otherwise an error message will be displayed.
To start Auto Tune PlD select PID, enable Auto PID and enable Start PID.
Sometimes Auto PID parameter needs fine tuning i.e. for each 5°F over
shoot increase the Proportional Band (PB) by 15% and for each ±1°F
fluctuation at the Setpoint (SP) increase reset by 20%.
Once started, display shows A.TUN with letters blinking in the rotating
pattern. When auto tune stops, display will show process value. Do not
perform any operations or settings before first stopping Auto Tune. Any
alarms or other output is disabled during Auto Tune.
If “AUTO PID” was “DISABLED”, the display will show the following
three submenus. This allows the user to manually enter values for
Proportional, Reset and Rate terms corresponding to P, I, and D. It also
can be used for auto PID for disabling unwanted parameter i.e. PI enter
0000 for rate.
PROPORTIONAL BAND SUBMENU:
Press
d
30) Display flashes 1stdigit of the previous P
PRoP
Proportional
band value.
Press b& c31) Press band cbuttons to enter a new “Proportional Band”
value.
Press
d
32) Display shows
STRD
stored message momentarily and then
advances to
REST
only, if it was changed, otherwise press ato
advance to
REST
Reset Setup Submenu.
Proportional band is in degrees of temperature or counts of process. Proportional
band is defined, as the change in the instrument input to cause a 100% change in
the controller output.

32
RESET SETUP SUBMENU:
Press
d
33) Display flashes 1stdigit of the previous I
REST
Reset value.
Press b& c34) Press band cbuttons to enter a new “Reset” value.
Press
d
35) Display shows
STRD
stored message momentarily and then
advances to
RATE
only, if it was changed, otherwise press ato
advance to
RATE
Rate Setup Submenu.
Reset unit is in seconds 0-3999.
RATE SETUP SUBMENU:
Press
d
36) Display flashes 1stdigit of previous D
RATE
Rate value.
Press b& c37) Press band cbuttons to enter a new
RATE
value.
Press
d
38) Display shows
STRD
stored message momentarily and then
advances to the
CYCL
only, if it was changed, otherwise press
a
to advance to
CYCL
Cycle Time submenu for RTD and
Thermocouple types.
Rate unit is in seconds 000.0-399.9.
If the Output 1 is Analog Option the display skips to Damping
Factor.
CYCLE TIME SUBMENU:
Press
d
39) Display flashes 1stdigit of the previous
CYCL
Cycle Time
value.
Press b& c40) Press band cbuttons to enter a new “Cycle Time” value.
(1 to 199 seconds)
Press
d
41) Display shows
STRD
stored message momentarily and then
advances to
DPNG
only, if it was changed, otherwise press ato
advance to
DPNG
Damping Factor Submenu.
A Cycle Time selected between 1 and 199 seconds determines the total On/Off
time of each proportional cycle. For example, a 15 second cycle time means that
every 15 seconds the output will turn on for part or all of the cycle. For Relay
control outputs, do not select a cycle time of less than 7 seconds or the relays’
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or
DC pulse. Use an external SSR with the DC pulse option for higher currents
(higher than 1 Amp).

33
DAMPING FACTOR SUBMENU:
Press
d
42) Display flashes the previous “Damping Factor” selection.
Press
b
43) Scroll through the available selections:
0000,0001,0002
,
0003,0004,0005,0006,0007
.
Press
d
44) Display flashes
STRD
stored message and then advances
to
OUT2
only, if it was changed, otherwise press ato advance
to
OUT2
Output 2 Menu.
Damping Factor is a measure of speed, overshoot, and undershoot in which the
process variable responds to the output changes of the instrument, which were
used during the Auto Tune. This value is typically set to the ratio of Rate to
Reset. This Default value is (0003). For fast response time, this value should be
decreased while for slow response time it should be increased.
The "DEADBAND" Submenu will only appear if "ON/OFF" was
selected from the "Control Type" Menu.
DEADBAND SUBMENU:
Press
d
45) Display flashes 1stdigit of the previous
DEAD
Deadband
value.
Press b& c46) Press band cbuttons to enter a new “Deadband” value.
Press
d
47) Display shows
STRD
stored message and then advances to
OUT2
only, if it was changed, otherwise press ato advance to
OUT2
Output 2 Menu.
Dead Band units are the same as Proportional Band units.
The Dead Band or neutral zone is the percentage (humidity) or number of
degrees around the Setpoint which the Process Variable must pass
above or below the Setpoint, before the output changes state.

34
3.2.10 Output 2
Output 2 and Alarm 2 share the same contacts on the rear panel connector. If
Alarm 2 is Enabled, Output 2 is automatically Disabled.
Figure 3.9 Flow Chart for Output 2
ENTER OUTPUT 2 MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu..
Press
a
3) Press a, if necessary, until Display advances to
OUT2
Output 2 Menu.
Press
d
4) Display advances to
CTRL
Control Type Submenu.
CONTROL TYPE SUBMENU:
Press
d
5) Display flashes
ON.OF
ON/OFF, or
PID
PID.
Press b 6) Scroll through the available selections: “ON/OFF” or “PID”.
Press
d
7) Display shows
STRD
stored message momentarily and then
advances to
AçTN
only, if it was changed, otherwise press ato
advance to
AçTN
Action Type Submenu.
The ON/OFF control is a coarse way of controlling the Process. The “Dead
Band” improves the cycling associated with the ON/Off control. The PID control
is best for processes where the Setpoint is continuously changing and/or tight
control of the Process Variable is required.
It is required that you put
the controller in the
Standby Mode for any
configuration change other
than Set Points & Alarms.
Alarm 2 and Output 2 works
for Temperature only.
RESET
RATE
RES/VALUE
RATE/VALUE

35
ACTION TYPE SUBMENU:
The error that results from the measurement of the Process Variable may be
positive or negative since it may be greater or smaller than the Setpoint. If a
positive error should cause the instrument output to increase (i.e. cooling), it
would be called Direct Acting. If a negative error should cause the output to
decrease (i.e. heating), it would be called Reverse Acting.
Press
d
8) Display flashes
DRçT
Direct or
RVRS
Reverse.
Press
b
9) Scroll through the available selections: “Direct” or “Reverse”.
Press
d
10) Display shows
STRD
stored message momentarily and then
advances to
AUTo
only, if it was changed, otherwise press ato
advance to
AUTo
Auto PID Submenu (If PID Control type was
selected).
If ON/OFF was selected in the Control Type, the display skips to
the Dead Band Submenu.
AUTO PID SUBMENU:
Press
d
11) Display flashes
ENBL
Enable or
DSBL
Disable.
Press
b
12) Scroll through the available selections: “Enable” or “Disable”.
If "Enabled", the PID parameter of Output 1 will be copied to
Output 2.
Press
d
13) Display shows
STRD
stored message momentarily and then
advances to the next submenu only, if it was changed, otherwise
press ato advance to the next submenu.
If AUTO PID was ENABLED", the display skips to the
CYCL
CYCLE TIME submenu. If "AUTO PID" was "DISABLED", the
display will show
PRoP
PROPORTIONAL BAND Submenu
allowing the user to manually enter the Proportional Band value.
Refer to “Proportional Band”, “Reset”, “Rate”, and “Cycle Time”
Submenus of “Output 1” Menu.
DEADBAND SUBMENU: The DEADBAND Submenu will only appear if the
ON/OFF was selected from the "Control Type" Submenu.
Press
d
14) Display flashes 1stdigit of the previous “Dead Band” value.
Press b& c15) Press band cbuttons to enter a new “Dead Band” value.
Press
d
16) Display shows
STRD
stored message momentarily and then
advances to
RAMP
only, if it was changed, otherwise press ato
advance to
RAMP
Ramp Value Menu.
Dead Band units are the same as Proportional Band units.
The Dead Band is the number of degrees or counts around the Setpoint
which the Process Variable must pass through before the output changes
state.

36
3.2.11 Ramp & Soak
Alarm must be DISABLED if Ramp is ENABLED.
Figure 3.10 Flow Chart for Ramp and Soak
ENTER RAMP AND SOAK MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu.
Press
a
3) Press a, if necessary, until Display advances to
RAMP
Ramp
and
SOAK
Soak Menu.
RAMP ENABLE/DISABLE SUBMENU:
Press
d
4) Display advances to “Ramp Enable/Disable” Submenu and
flashes
ENBL
or
DSBL
.
Press
b
5) Scroll through the available selections: “Enable” or “Disable”.
Press
d
6) Display shows
STRD
stored message momentarily and then
advances to
SOAK
Soak Enable/Disable Menu.
If
RAMP
Disable was selected, display skips to the next menu
item (ID Code).
It is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.
If
DRRh
is selected in the Reading Configuration Menu the unit will
ramp only on humidity, but if
°F.°C
is selected, both humidity and
temperature will ramp to Setpoint.

37
SOAK ENABLE/DISABLE SUBMENU:
Press
d
7) Display flashes
ENBL
or
DSBL
.
Press
b
8) Scroll through the available selections: “Enable” or “Disable”.
Press
d
9) Display shows
STRD
stored message momentarily and then
advances to “Ramp Value” Submenu.
Ramp & Soak provides users with the flexibility to slowly bring the Process
Variable (PV) to the desired setpoint. Ramp & Soak values are specified in
HH.MM format. The Ramp value indicates the time specified to bring the
process variable to Setpoint 1 (SP1). Once the set point is reached, the PID
takes over and the Process Variable will be controlled at the desired set point
indefinitely. If Soak is enabled, PID will control the Process Variable at the
specified Setpoint for the duration of Soak time and then will turn off Output 1.
To start a new Ramp/Soak cycle, reset the instrument by pressing aand then
c
button.
An active Ramp/Soak will change SP1 one degree above the PV and will cause
the most significant digit to blink. The SP1 will be incremented by one degree
until it reaches the original SP1. The minimum Ramp time must be at least twice
the time that it will take the PV to reach the Setpoint Value (SV) with OUT 1 fully
ON.
RAMP VALUE SUBMENU:
Press
d
10) Display flashes 1stdigit of previous stored “Ramp Value”.
Press b& c11) Press band cbuttons to enter a new “Ramp Value”.
Press
d
12) Display shows
STRD
stored message momentarily and then
advances to “Soak Value” Submenu.
SOAK VALUE SUBMENU:
Press
d
13) Display flashes 1stdigit of previous stored “Soak Value”.
Press b& c14) Press band cbuttons to enter a new “Soak Value”.
Press
d
15) Display shows
STRD
stored message and advances to the
ID
ID Code Menu.
The Ramp and Soak time is 00:00 to 99:59 i.e. HH.MM. (from zero to 99 hours
and 59 minutes) During Ramp & Soak do not perform any operations or settings
before first stopping it. Any alarms or other output are disabled during this time.
To stop Ramp & Soak first put instrument into Standby Mode, then go to Ramp &
Soak Menu and disable it.

38
3.2.12 ID CODE
Figure 3.11 Flow Chart for ID Code
ENTER ID CODE MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press d 2) Display advances to
RDG
Reading Configuration Menu.
Press
a
3) Press a, if necessary, until Display advances to IDID Code
Menu.
ENTERING OR CHANGING YOUR (NON-DEFAULT) ID CODE:
Press d 4) Display advances to
____
with 1stunder score flashing.
Press b& c5) Press band cto enter your 4-digit “ID Code” number.
Press d 6) Display advances to
CH.ID
Change ID Code Submenu.
If entered “ID Code” is incorrect display shows
ERRo
Error
message momentarily and then skips to the Run Mode.
Press
d
7) Display flashes the first digit of previous entered “ID Code”
number.
Press b& c8) Press band cbuttons to enter your new “ID Code” number.
Press
d
9) Display shows
STRD
stored message momentarily and then
advances to the
FULL
Full Security Submenu.

39
ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:
Enter IDmenu (Repeat steps from 1 to 3).
Press
d
10) Display advances to
CH.ID
Change ID Code Submenu.
Press
d
11) Display shows
0000
message with flashing 1stdigit.
If you want to change your default “ID Code” you can do it now,
otherwise press aand menu will skip to
FULL
Full Security
Submenu.
Press b& c12) Press band cbuttons to enter your new “ID Code” number.
Press
d
13) Display shows
STRD
stored message momentarily and then
advances to the
FULL
Full Security Submenu.
FULL SECURITY LEVEL SUBMENU:
Press
d
14) Display flashes
ENBL
Enable or
DSBL
Disable.
Press
b
15) Scroll through the available selections: “Enable” or “Disable”.
Press
d
16) Display shows
STRD
stored message momentarily and then
advances to
SP.ID
Setpoint/ID Submenu.
If "Full" Security Level is "Enabled" and the user attempts to
enter the Main Menu, they will be prompted for an ID Code. The
ID Code should be correct to enter the instrument Menu item.
SETPOINT/ID SECURITY LEVEL SUBMENU:
This Security Level can be functional only if
FULL
Security
Level is Disabled.
Press
d
17) Display flashes
ENBL
Enable or
DSBL
Disable.
Press
b
18) Scroll through the available selections: “Enable” or “Disable”.
Press
d
19) Display shows
STRD
stored message momentarily and then
advances to
COMM
Communication Submenu.
If "Setpoint/ID" Security Level is "Enabled" and the user
attempts to advance into the
CNFG
Configuration Menu, he will
be prompted for ID Code number. The ID Code should be
correct to proceed into the Configuration Menu, otherwise
display will show an Error and skip to the Run Mode.
If “Full” and “Setpoint/ID” Security Levels are "Disabled", the
ID code will be “Disabled” and user will not be asked for ID
Code to enter the Menu items (“ID” Submenu will not show up in
“ID/Setpoint” Menu).

40
3.2.13 COMMUNICATION OPTION
Purchasing the controller with Serial Communications permits an instrument to be
configured or monitored from an IBM PC compatible computer using software
available from the website or on the CD-ROM enclosed with your shipment.
For complete instructions on the use of the Communications Option, refer to the
Serial Communications Reference Manual.
Figure 3.12 Flow Chart for Communication Option
With the exception
of DATA FORMAT
Sub Menu, all
other command
formats are the
same in the Serial
Communications
Manual.

41
The following table are the exceptions to the Serial Communication Manual’s Table 5.3
Table 3.2 Command Letters and Suffix for iTH
ENTER COMMUNICATION OPTION MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu.
Press
a
3) Press a, if necessary, until Display advances to
COMM
Communication Options Menu.
Press
d
4) Display advances to
C.PAR
Communication Parameters
Submenu.
If Communication Option is not installed, the display shows
NONE
and skips to the Color Display Menu.
COMMUNICATION PARAMETERS SUBMENU:
Allows the user to adjust Serial Communications Settings of the instrument.
When connecting an instrument to a computer or other device, the
Communications Parameters must match. Generally the default settings
(as shown in Section 5) should be utilized.
Press
d
5) Display advances to
BAUD
Baud Submenu.
BAUD SUBMENU:
Press
d
6) Display flashes previous selection for
BAUD
value.
Press
b
7) Scroll through the available selections:
300_, 600_, 1200
,
2400, 4800
,
9600, 19.2K
.
Press
d
8) Display shows
STRD
stored message momentarily and then
advances to
PRTY
only, if it was changed, otherwise press ato
advance to
PRTY
Parity Submenu.
PARITY SUBMENU:
Press
d
9) Display flashes previous selection for “Parity”.
Press
b
10) Scroll through the available selections: NO, ODD, EVEN.
Press
d
11) Display shows
STRD
stored message momentarily and then
advances to
DATA
only, if it was changed, otherwise press ato
advance to
DATA
Data Bit Submenu.
DATA BIT SUBMENU:
Press
d
12) Display flashes previous selection for “Data Bit”.
Press
b
13) Scroll through the available selections: 7-BIT, 8-BIT.
Press
d
14) Display shows
STRD
stored message and then advances to
STOP
only, if it was changed, otherwise press ato advance to
STOP
Stop Bit Submenu.
Command Command Function Command # Of Default
Index Bytes Characters Value
X 01 Send RH Reading 0 0 X 02 Send Temperature Reading 0 0 X 03 Send Dewpoint Reading 0 0 -

42
STOP BIT SUBMENU:
Press
d
15) Display flashes previous selection for “Stop Bit”.
Press
b
16) Scroll through the available selections:
1-BIT, 2-BIT
.
Press
d
17) Display shows
STRD
stored message momentarily and then
advances to
BUS.F
only, if it was changed, otherwise press ato
advance to
BUS.F
Bus Format Submenu.
BUS FORMAT SUBMENU:
Determines Communications Standards and Command/Data Formats for
transferring information into and out of the controller via the Serial
Communications Bus. Bus Format submenus essentially determine how and
when data can be accessed via the Serial Communications of the device.
Press
d
18) Display advances to
M.BUS
Modbus Submenu.
MODBUS PROTOCOL SUBMENU:
Press
d
19) Display flashes previous selection for
M.BUS
.
Press
b
20) Scroll through the available selections: NO, YES.
Press
d
21) Display shows
STRD
stored message momentarily and then
advances to
_LF_
only, if it was changed, otherwise press ato
advance to
_LF_
Line Feed submenu.
To select iSeries Protocol, set Modbus submenu to “No”.
To select Modbus Protocol, set Modbus submenu to “Yes”.
If Modbus Protocol was selected, the following Communications
Parameters must be set as: No Parity, 8-bit Data Bit, 1-Stop Bit. Do not
attempt to change these parameters.
LINE FEED SUBMENU:
Determines if data sent from the instrument will have a Line Feed appended to
the end - useful for viewing or logging results on separate lines when displayed
on communications software at a computer.
Press
d
22) Display flashes previous selection for “Line Feed”.
Press
b
23) Scroll through the available selections: NO, YES.
Press
d
24) Display shows
STRD
stored message momentarily and then
advances to
ECHO
only, if it was changed, otherwise press ato
advance to
ECHO
Echo Submenu.
ECHO SUBMENU:
When valid commands are sent to the instrument, this determines whether the
command will be echoed to the Serial Bus. Use of echo is recommended in most
situations, especially to help verify that data was received and recognized by the
controller.

43
Press
d
25) Display flashes previous selection for “Echo”.
Press
b
26) Scroll through the available selections: NO, YES.
Press
d
27) Display flashes
STRD
stored message momentarily and then
advances to
STND
only if it was changed, otherwise press ato
advance to
STND
Communication Standard Submenu.
COMMUNICATION INTERFACE STANDARD SUBMENU:
Determines whether device should be connected to an RS-232C serial port
(as is commonly used on IBM PC-compatible computers) or via an RS-485 bus
connected through appropriate RS-232/485 converter. When used in RS-485
Mode, the device must be accessed with an appropriate Address Value as
selected in the Address Submenu described later.
Press
d
28) Display flashes previous selection for “Standard”.
Press
b
29) Scroll through the available selections: 232C, 485.
Press
d
30) Display shows
STRD
stored message momentarily and then
advances to
MoDE
only, if it was changed, otherwise press ato
advance to
MoDE
Data Flow Mode Submenu.
DATA FLOW MODE SUBMENU:
Determines whether the instrument will wait for commands and data requests
from the Serial Bus or whether the instrument will send data automatically and
continuously to the Serial Bus. Devices configured for the RS-485
Communications Standard operate properly only under Command Mode.
Press
d
31) Display flashes previous selection for “Mode”.
Press
b
32) Scroll through the available selections:
CMD
__
“Command”,
CoNT
“Continuous”.
Press
d
33) Display shows
STRD
stored message momentarily and then
advances to
SEPR
only, if it was changed, otherwise press ato
advance to
SEPR
Data Separation Submenu.
DATA SEPARATION CHARACTER SUBMENU:
Determines whether data sent from the device in Continuous Data Flow Mode
will be separated by spaces or by Carriage Returns.
Press
d
34) Display flashes previous selection for “Separation” Submenu.
Press
b
35) Scroll through the available selections:
SPCE
“Space” or
_çR_
“Carriage Return”.
Press
d
36) Display shows
STRD
stored message momentarily and then
advances to
DAT.F
only, if it was changed, otherwise press ato
advance to
DAT.F
Data Format Submenu.

44
DATA FORMAT SUBMENU:
Preformatted data can be sent automatically or upon request from the controller.
Use the Data Format Submenus to determine what data will be sent in this
preformatted data string. Refer to the iSeries Communications Manual for more
information about the data format. At least one of the following suboptions must
be enabled and hence output data to the Serial Bus.
This menu is applicable for Continuous Mode of RS-232 communication.
Press
d
37) Display advances to
STAT
Alarm Status Submenu.
ALARM STATUS SUBMENU:
Includes Alarm Status bytes in the data string.
Press
d
38) Display flashes previous selection for “Status” (alarm status).
Press
b
39) Scroll through the available selections: NO, YES.
Press
d
40) Display shows
STRD
stored message momentarily and then
advances to
HUMD
only, if it was changed, otherwise press ato
advance to
HUMD
Humidity Submenu.
HUMIDITY READING SUBMENU:
Includes Humidity Reading in the data string.
Press
d
41) Display flashes
HUMD
.
Press
b
42) Scroll through the available selections: NO, YES.
Press
d
43) Display shows
STRD
stored message momentarily and then
advances to
TEMP
only, if it was changed, otherwise press ato
advance to
TEMP
Temperature Submenu.
TEMPERATURE READING SUBMENU:
Includes Temperature Reading in the data string.
Press
d
44) Display flashes
TEMP
.
Press
b
45) Scroll through the available selections: NO, YES.
Press
d
46) Display shows
STRD
stored message momentarily and then
advances to
DEU
only, it was changed, otherwise press ato
advance to
DEU
Dewpoint Submenu.
DEWPOINT READING SUBMENU:
Includes Dewpoint Reading in the data string.
Press
d
47) Display flashes
DEU
.
Press
b
48) Scroll through the available selections: NO, YES.
Press
d
49) Display shows
STRD
stored message momentarily and then
advances to
UNIT
only, if it was changed, otherwise press ato
advance to
UNIT
Temperature Unit Submenu.

45
TEMPERATURE UNIT SUBMENU:
Includes a byte in the data string to indicate whether reading is in Celsius or
Fahrenheit.
Press
d
50) Display flashes previous selection for
UNIT
.
Press
b
51) Scroll through the available selections: NO, YES.
Press
d
52) Display shows
STRD
stored message momentarily and then
advances to
ADDR
only, if it was changed, otherwise press ato
advance to
ADDR
Address Setup Submenu.
ADDRESS SETUP SUBMENU:
This menu is applicable to the RS-485 Option only.
Press
d
53) Display advances to “Address Value” (0000 to 0199) Submenu.
ADDRESS VALUE SUBMENU:
Press
d
54) Display flashes 1
st
digit of previously stored Address Value.
Press b& c55) Press band cto enter new “Address Value”.
Press
d
56) Display shows
STRD
stored message momentarily and then
advances to
TR.TM
only, if it was changed, otherwise press ato
advance to
TR.TM
Transmit Time Interval Submenu.
TRANSMIT TIME INTERVAL SUBMENU:
This menu is applicable if “Continuous” Mode was selected in the “Data
Flow Mode” Submenu and the device is configured as an RS-232C
Standard device. Also, one or more options under the Data Format
Submenu must be enabled.
Press
d
57) Display advances to “Transmit Time Value” Submenu.
TRANSMIT TIME INTERVAL VALUE SUBMENU:
Determines the interval at which data will be emitted to the RS-232 Serial Bus
when the instrument is in Continuous Data Flow Mode.
Press
d
58) Display flashes 1
st
digit of previous “Transmit Time Value” in
seconds.
Press b& c59) Press band cto enter new “Transmit Time Value”, e.g.
0030 will send the data every 30 seconds in Continuous Mode.
Press
d
60) Display shows
STRD
stored message momentarily and then
advances to
COLR
only, if it was changed, otherwise press ato
advance to
COLR
Color Display Selection Menu.
For more details, refer to the Serial Communication Manual
available at the website listed in the cover page of this manual.

46
3.2.14 DISPLAY COLOR SELECTION
This submenu allows the user to select the color of the upper display.
Figure 3.13 Flow Chart for Display Color Selection
ENTER DISPLAY COLOR SELECTION MENU:
Press
a
1) Press a, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
RDG
Reading Configuration Menu.
Press
a
3) Press a, if necessary, until Display advances to
COLR
Display Color Selection Menu.
Press
d
4) Display advances to
N.CLR
Normal Color Submenu.
NORMAL COLOR DISPLAY SUBMENU:
Press
d
5) Display flashes the previous selection for “Normal Color”.
Press
b
6) Scroll through the available selections:
GRN, RED
or
AMBR
.
Press
d
7) Display shows
STRD
stored message momentarily and then
advances to
1.CLR
only, if it was changed, otherwise press ato
advance to
1.CLR
Alarm 1 Display Color Submenu.
The menu below allows the user to change the color of the upper display when
Alarm 1 is triggered.
ALARM 1 DISPLAY COLOR SUBMENU:
Press
d
8) Display flashes previous selection for “Alarm 1 Color
Display”.
Press
b
9) Scroll through the available selections:
GRN, RED
or
AMBR
.
Press
d
10) Display shows
STRD
stored message momentarily and then
advances to
2.CLR
only, if it was changed, otherwise press ato
advance to
2.CLR
Alarm 2 Display Color Submenu.
A color change is based on the Relative Humidity value only.
If this value causes an alarm condition, the upper display will change to
the selected Alarm 1 Color. A color change will occur whether Alarm 1 is
enabled or disabled.

47
ALARM 2 DISPLAY COLOR SUBMENU:
Press
d
11) Display flashes previous selection for “Alarm 2 Color Display”.
Press
b
12) Scroll through the available selections:
GRN, RED
or
AMBR
.
Press
d
13) Display shows
STRD
stored message momentarily and then
momentarily shows the software version number, followed by
RST
Reset, and then proceeds to the Run Mode.
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON ALL THREE SUBMENUS ABOVE.
Example 1:
Output 1 & Output 2 = SSR
Alarm Setup: Absolute, Above, Alarm 2 HI Value “ALR.H” = 200, Alarm 1
HI Value “ALR.H” = 400
"Color Display" Setup: Normal Color “N.CLR” = Green, Alarm 1 Color
“1.CLR” = Amber, Alarm 2 Color “2.CLR” = Red
Display Colors change sequences:
GREEN RED AMBER
•
--➤------------------------------•-----------------------------•------------------------------
➤
0 AL2.H = 200 AL1.H = 400
Example 2:
Output 1 & Output 2
= Pulse
Alarm Setup: Absolute, Below, Alarm 2 Low Value “ALR.L” = 300, Alarm 1
Low Value “ALR.L” = 100
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
AMBER RED GREEN
•
--------------•----------------------------------•------------------------------------------- --
•
0 AL1.L = 100 AL2.L = 300
➤ ➤

48
Example 3:
Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300,
Output 2 = Relay, Setpoint 2 = 200
Alarm 1 & 2 Setup: Deviation, Band, “ALR.H” = 10
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Display Colors change sequences:
RED RED RED GREEN RED
•➤
---------------•------•------•--------------------------------•------•-------•----------------
➤
0 190 200 210 290 300 310
Alarm 1 is designed to monitor the Process Value around the Setpoint 1.
Alarm 2 is designed to monitor the Process Value around the Setpoint 2.
If Analog Output Option board is installed (Alarm 1 is disabled), only
Alarm 2 is active and only two colors are available.
Example 4:
Output 1
= Relay, Setpoint 1 = 200
Output 2 = Relay, Setpoint 2 = 200
Alarm 1 Setup
: Deviation, Band, “ALR.H” = 20
Alarm 2 Setup
: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Display colors change sequences:
AMBER RED GREEN GREEN RED AMBER
•
--➤---------------•----------------•-------------•--------------•-------------•---------------------
➤
0 180 195 200 210 220
Reset: The instrument automatically resets after the last menu of
the Configuration Mode has been entered. After the instrument
resets, it advances to the Run Mode.

49
PART 4
SPECIFICATIONS
SENSOR SPECIFICATIONS
Relative Humidity (RH)
Accuracy/Range: ±2% for 10 to 90% RH
±3% for 0 to 10%RH and 90 to 100%RH
Non-linearity: ±3%
Hysteresis: ±1% RH
Response Time:
4 sec (63% slowly moving air)
Repeatability: ±0.1%
Resolution: 0.03%, 12bit
NOTE: Reconditioning of the probe may
be necessary if the probe is stored for a
period of time in a harsh environment
(e.g. high humidity or exposure to
chemicals). To recondition the probe:
heat probe for 1 day at 100°C to return
it to calibration conditions.
Temperature (T)
Accuracy/Range*:
±1°C (±2°F) for
-40 to 0°C and 80 to 123.8°C
(-40 to 32°F and 176 to 254°F)
±0.5°C (±1°F) for 0 to 80°C (32 to 176°F)
*NOTE: extended temperature range is
for Probe only, the Controller’s
operating temperature is 0-50°C
Response Time:
5 sec (63% slowly moving air)
Repeatability: ±0.1°C
Resolution: 0.01°C, 14 bit
METER SPECIFICATIONS
NMRR: 60 dB
CMRR: 120 dB
A/D Conversion:
12 bit RH and 14 bit Temperature
Reading Rate:
2 samples per seconds max.
Digital Filter: Programmable
Decimal Selection:
None, 0.1 for temp and humidity
Warm up to Rated Accuracy: 30 min.
Display
4-digit, 9-segment LED
•
10.2mm (0.40"): i32, i16D,
i8DV
• 10.2mm (0.40”) & 21mm (0.83”): i8DH
red, green and amber programmable
colors for process variable, set point
and temperature units
CONTROL
Action
Reverse (heat) or direct (cool)
Modes
Time and Amplitude Proportional
Control Modes; selectable Manual or
Auto PID, Proportional, Proportional
with Integral, Proportional with
Derivative with Anti-reset Windup and
ON/OFF
Rate
0 to 399.9 seconds
Reset
0 to 3999 seconds
Cycle Time
1 to 199 seconds; set to 0 for
ON/OFF operation
Gain
0.5 to 100% of span; Setpoints 1 or 2
Damping
0000 to 0008
Soak
00.00 to 99.59 (HH:MM), or OFF
Ramp to Setpoint
00.00 to 99.59 (HH:MM), or OFF
Auto Tune
Operator initiated from front panel for
one input at a time only

50
CONTROL OUTPUT 1 & 2
Relay
250 Vac or 30 Vdc @ 3 A
(Resistive Load); configurable for
on/off, PID and Ramp and Soak
Output 1: SPDT type, can be
configured as Alarm 1 output
Output 2: SPDT type, can be
configured as Alarm 2 output
SSR
20-265 Vac @ 0.05-0.5 A
(Resistive Load); continuous
DC Pulse
Non-Isolated; 10 Vdc @ 20 mA
Analog Output (Output 1 only)
Non-Isolated, Proportional 0 to 10
Vdc or 0 to 20 mA; 500 Ω max
NETWORK AND COMMUNICATIONS
(Optional -C24, -C4EI, -EI)
Ethernet: Standards Compliance
IEEE 802.3 10Base-T
Supported Protocols: TCP/IP,
ARP, HTTPGET
RS-232/RS-422/RS-485/MODBUS:
Selectable from menu; both ASCII
and modbus protocol selectable
from menu.
Programmable 300 to 19.2 K baud;
complete programmable setup
capability; program to transmit
current display, alarm status,
min/max, actual measured input
value and status.
RS-485
Addressable from 0 to 199
Connection
Screw terminals
ALARM 1 & 2 (programmable):
Type
Same as Output 1 & 2
Operation
High/low, above/below, band,
latch/unlatch, normally open/normally
closed and process/deviation; front
panel configurations
ANALOG OUTPUT (programmable)
Non-Isolated, Retransmission 0 to 10
Vdc or 0 to 20 mA, 500 Ω max (Output 1
only). Accuracy is +
1% of FS when
following conditions are satisfied.
1) Input is not scaled below 1% of
Input FS.
2) Analog Output is not scaled below
3% of Output FS.
EXCITATION
(optional in place of Communication)
24 Vdc @ 25 mA
Not available for Low Power Option
INSULATION
Power to Input/Output
2300 Vac per 1 min. test
1500 Vac per 1 min. test
(Low Voltage/Power Option)
Power to Relays/SSR Outputs
2300 Vac per 1 min. test
Relays/SSR to Relay/SSR Outputs
2300 Vac per 1 min. test
RS-232/485 to Inputs/Outputs
500 Vac per 1 min. test
APPROVALS
UL, C-UL, and see Approval Section

GENERAL
External Fuse Required
Time-Delay, UL 248-14 listed:
100 mA/250 V
400 mA/250 V
(Low Voltage/Power Option)
Time-Lag, IEC 127-3 recognized:
100 mA/250 V
400 mA/250 V
(Low Voltage/Power Option)
Environmental Conditions
• i32: 0 to 55°C (32 to 131°F),
90% RH non-condensing
• i8DV, i8DH, i16D:
0 to 50°C (32 to 122°F),
90% RH non-condensing
• Cable: operating temperature
0-105°C (32 to 221°F)
Protection
NEMA-4x/Type 4/IP65 front bezel:
i32, i16D
NEMA-1/Type 1 front bezel: i8DH, i8DV
Dimensions
i/8 Series:
48 H x 96 W x 127 mm D
(1.89 x 3.78 x 5")
i/16 Series:
48 H x 48 W x 127 mm D
(1.89 x 1.89 x 5")
i/32 Series:
25.4 H x 48 W x 127 mm D
(1.0 x 1.89 x 5")
Industrial Probe iTHP-2:
16mm Dia. x 51mm Long (0.63” x 2”)
with 0.9m long (3’ ) cable
Industrial Probe iTHP-5:
16mm Dia. x 137mm Long (0.63” x 5”)
with 6.1m long (20’ ) cable
Material: Probe Housing, SS316
Panel Cutout
i/8 Series:
45 H x 92 mm W (1.772" x 3.622 "),
1/8 DIN
i/16 Series:
45 mm (1.772") square, 1/16 DIN
i/32 Series:
22.5 H x 45 mm W (0.886" x 1.772"),
1/32 DIN
Weight
i/8 Series: 295 g (0.65 lb)
i/16 Series: 159 g (0.35 lb)
i/32 Series: 127 g (0.28 lb)
Line Voltage/Power
90-240 Vac +/-10%, 50-400 Hz*
110-375 Vdc, equivalent voltage
4 W, power for i32 Models
5 W, power for i8DV, i8DH, i16D M
* No compliance above 60 Hz
odels
Low Voltage/Power Option
12-36 Vdc or 24 Vac
**
+/-10%
, 3 W
External power source must meet
Safety Agency Approvals.
** Units can be powered safely with 24 Vac
power but, no Certification for UL are
claimed.

52
PART 5
FACTORY PRESET VALUES
Table 5.1 Factory preset value
MENU ITEMS FACTORY PRESET VALUES NOTES
Set Point 1 (SP1) 000.0
Set Point 2 (SP2) 000.0
Reading Configuration (RDG):
Sensor (SENS) %RH
Decimal Point FFF.F
not menu selectable
Temperature unit (tEMP) °F
Filter value (FLtR) 0004
Alarm 1 & 2
:
Alarm 1 (ALR1), Alarm 2 (ALR2) Disable (dSbL)
Absolute/Deviation (AbSO/dEV) Absolute (AbSO)
Latch/Unlatch (LtCH/UNLt) Unlatch (UNLt)
Contact Closure (Ct.CL) Normally Open (N.O.)
Active (ACtV) Above (AbOV)
Alarm At Power On (A.P.ON) Disable (dSbL) Alarm 1 only
Alarm Low (ALR.L) 000.0
Alarm High (ALR.H) 80.0
LOOP:
Loop Break Time (LOOP) Disable (dSbL)
Loop Value (B.tIM) 00:59
Reading Adjust Value (R.AdJ) 000.0
Setpoint Deviation (SP.dV) Disabled (dSbL)
ANALOG OUTPUT (Retransmission)
:
Analog Output (ANLG) Enabled (ENbL)
Current/Voltage (CURR/VOLt) Voltage (VOLt)
Scale and Offset Reading: 0 - 100.0 cts,
Output: 0 - 10 V
OUTPUT 1 & 2
:
Self (SELF) Disabled (dSbL) Output 1 only
% Low Value (%LO) 0000 Output 1 only
% High Value (%HI) 0099 Output 1 only
Control Type (CtRL) On/Off
Action Type (ACtN) Reverse (RVRS)
Dead Band (dEAd) 020.0
PID Auto (AUtO) Disable (dSbL)
Anti Integral (ANtI) Disable (dSbL) Output 1 only
Proportion Value (PROP) 020.0
Reset Value (RESt) 0180
Rate Value (RAtE) 0000
Cycle Value (CYCL) 0007
Damping Factor (DPNG) 0003

53
MENU ITEMS FACTORY PRESET VALUES NOTES
Ramp & Soak (RAMP)
:
Ramp (RAMP) Disable (dSbL)
Soak (SOAK) Disable (dSbL)
Ramp Value (RAMP) 00:00
Soak Value (SOAK) 00:00
ID
:
ID Value 0000
Full ID (FULL) Disable (dSbL)
Set Point ID (Id.SP) Disable (dSbL)
Communication Parameters:
Baud Rate (BAUd) 9600
Parity (PRtY) Odd
Data bit (DAtA) 7 bit
Stop Bit (StOP) 1 bit
Modbus Protocol (M.bUS) No
Line Feed (_LF_) No
Echo (ECHO) Yes
Standard Interface (StNd) RS-232 (232C)
Command Mode (MOdE) Command (CMd_)
Separation (SEPR) Space (SPCE)
Alarm Status (StAt) No
Humidity (HUMd) Yes
Temperature (TEMP) No
Dewpoint (dEU) No
Units (UNIt) No
Multipoint Address (AddR) 0001
Transmit Time (tR.tM) 0016
Display Color (COLR):
Normal Color (N.CLR) Green (GRN)
Alarm 1 Color (1.CLR) Red (RED)
Alarm 2 Color (2.CLR) Amber (AMbR)

PART 6
• Power to Input/Output: 2300Vac (3250Vdc)
• Power to Input/Output: 1500Vac (2120Vdc)
(Low Voltage dc Power Option*)
• Power to Relays/SSR Output: 2300Vac (3250Vdc)
• Ethernet to Inputs: 1500Vac (2120Vdc)
• Isolated RS232 to Inputs: 500Vac (720Vdc)
• Isolated Analog to Inputs: 500Vac (720Vdc)
• Analog/Pulse to Inputs: No Isolation
Measurement Category I
Category I are measurements performed on circuits not directly connected to the
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50Vac/dc.
This unit should not be used in Measurement Categories II, III, IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
• Input Power: 2500V
• Input Power: 1500V
(Low Voltage dc Power Option*)
• Ethernet: 1500V
• Input/Output Signals: 500V
Note: *Units configured for external low power dc voltage, 12-36Vdc
EMC EN61326:1997 + and A1:1998 + A2:2001
Immunity and Emissions requirements for electrical equipment for measurement,
control and laboratory.
• EMC Emissions Table 4, Class B of EN61326
• EMC Immunity** Table 1 of EN61326
Note: **I/O signal and control lines require shielded cables and these cables
must be located on conductive cable trays or in conduits. Furthermore,
the length of these cables should not exceed 30 meters
Refer to the EMC and Safety installation considerations (Guidelines) of this manual
for additional information.
APPROVALS INFORMA
Electrical Safety EN61010-1:2001
Safety requirements for electrical equipment for measurement, control and laboratory.
Double Insulation
Pollution Degree 2
Dielectric withstand Test per 1 min
TION

WARRANTY/DISCLAIMER
ARRANTY RETURNS, please have the following
information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was
PURCHASED,
2. Model and serial number of the product under warranty,
and
3. Repair instructions and/or specific problems relative to
the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for current
repair charges. Have the following information available
BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems relative to the
product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
© Copyright 2005 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
TRADEMARK NOTICE:
®
, omega.com
®
, , and ®are Trademarks of OMEGA ENGINEERING, INC.
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577;
6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150;
2048066 / UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The “Meter Bezel Design” is a Trademark
of NEWPORT Electronics, Inc. Used under License. Other US and International Patents pending or applied for.
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year
from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty
period for four (4) additional years if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found
to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any
action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered
with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration;
improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which
wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its
products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the
parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability
is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component”
under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on
humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on
humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER
language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage
whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING
ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM
OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR
number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.
FOR W

Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop on line at www.omega.com
TEMPERATURE
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrators & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
Transducers & Strain Gauges
Load Cells & Pressure Gauges
Displacement Transducers
Instrumentation & Accessories
FLOW/LEVEL
Rotameters, Gas Mass Flowmeters & Flow Computers
Air Velocity Indicators
Turbine/Paddlewheel Systems
Totalizers & Batch Controllers
pH/CONDUCTIVITY
pH Electrodes, Testers & Accessories
Benchtop/Laboratory Meters
Controllers, Calibrators, Simulators & Pumps
Industrial pH & Conductivity Equipment
DATA ACQUISITION
Data Acquisition & Engineering Software
Communications-Based Acquisition Systems
Plug-in Cards for Apple, IBM & Compatibles
Datalogging Systems
Recorders, Printers & Plotters
HEATERS
Heating Cable
Cartridge & Strip Heaters