Omega CN63100, CN63300 User Manual

Page 1
omega.com
e-mail: info@omega.com
User’s Guide
Shop online at
CN63100/CN63300 Series 1/16 DIN
Temperature/Process Controllers
UL Recognized Component, File # E123489
LP0679A
Page 2
OMEGAnet®Online Service
omega.com
Internet e-mail
info@omega.com
Servicing North America:
U.S.A.: ISO 9001 Certified Canada:
One Omega Drive, P.O. Box 4047 976 Bergar Stamford, CT 06907-0047 Laval (Quebec) H7L 5A1, Canada TEL: (203) 359-1660 FAX: (203) 359-7700 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.com e-mail: info@omega.ca
For immediate technical or application assistance:
U.S.A. and Canada: Mexico:
Sales Service: 1-800-826-6342/1-800-TC-OMEGA
®
En Español: (001) 203-359-7803
Customer Service: 1-800-622-2378/1-800-622-BEST
®
FAX: (001) 203-359-7807
Engineering Service: 1-800-872-9436/1-800-USA-WHEN®e-mail: espanol@omega.com info@omega.com.mx
Servicing Europe:
Czech Republic: Germany/Austria:
Frystatska 184, 733 01 Karviná, Czech Republic Daimlerstrasse 26, D-75392 Deckenpfronn, Germany TEL: +420 (0)59 6311899 FAX: +420 (0)59 6311114 TEL: +49 (0)7056 9398-0 FAX: +49 (0)7056 9398-29 Toll Free: 0800-1-66342 e-mail: info@omegashop.cz Toll Free in Germany: 0800 639 7678 e-mail: info@omega.de
United Kingdom: One Omega Drive, River Bend Technology Centre
ISO 9002 Certified Northbank, Irlam, Manchester M44 5BD United Kingdom
TEL: +44 (0)161 777 6611 FAX: +44 (0)161 777 6622 Toll Free in United Kingdom: 0800-488-488 e-mail: sales@omega.co.uk
It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
WARNING : These products are not designed for use in, and should not be used for, human applications.
Page 3
Table of Contents
GENERAL DESCRIPTION····························································· 1
SafetySummary ·································································· 1
INSTALLATION DESCRIPTION ······················································· 2
Instructions:······································································ 2 MultipleUnitStacking······························································ 3 Unit Removal Procedure···························································· 3 RemovingBezelAssembly·························································· 3 Installing Bezel Assembly··························································· 3
CONNECTIONDESCRIPTION ························································· 4
EMCInstallationGuidelines························································· 4 Wiring Connections ································································ 5 Signal Wiring ····································································· 5
Thermocouple (CN63100)························································ 5 RTD (CN63100) ································································ 5
Signal (CN63300) ······························································ 6 PowerWiring····································································· 6 ControlandAlarmOutputs·························································· 6
Relay Connections ····························································· 6
Logic/SSR Connections (CN63100 only) ············································ 7 RemoteSetpointWiring ···························································· 7 Main Linear DC Output Wiring ······················································· 7 Second Linear DC Output Wiring····················································· 7 User Input Wiring ································································· 7 RearTerminalAssignments························································· 8
CN63100 Models Without RS-485 and Analog Output ································· 8
CN63100 Models With RS-485 or Linear DC Analog Output ···························· 8
············································································· 8
ALL CN63300 Models ··························································· 9 Serial Connections to a Host Terminal ··············································· 10 Linear DC Analog Output Jumper Selection ··········································· 11
FRONTPANELDESCRIPTION ······················································· 12
ButtonFunctions································································· 12
INITIALCONFIGURATIONSTART-UP ················································· 13
-i-
Page 4
ControllerPower-up ······························································ 13 ParameterConfigurationOverview·················································· 13 ParameterConfigurationBasicStart-up·············································· 13 ParameterConfigurationforSerialStart-up··········································· 13 ControlStart-up·································································· 13 ValidControlModeCombinations··················································· 14 Front Panel Programming Chart For CN63100 & CN63300 Controllers ···················· 15
NORMALDISPLAYMODE··························································· 16 FRONTPANELPROGRAMDISABLE·················································· 16 UNPROTECTEDPARAMETERMODE ················································· 17 PROTECTEDPARAMETERMODE···················································· 18 HIDDEN FUNCTION MODE ·························································· 19 CONFIGURATIONPARAMETER MODE················································ 19 REFERENCETABLES:CONFIGURATIONPARAMETERMODULES························ 20
Configure Module 1 - Input Parameters (1-IN) CN63100································· 20 Configure Module 1 - Input Parameters (1-IN) CN63300································· 21 Configure Module 2 - Output Parameters (2-OP) ······································· 22 Configure Module 3 - Lockout Parameters (3-LC) ······································ 23 Configure Module 4 - Alarm Parameters (4-AL) ········································ 24 Configure Module 5 - Cooling Parameters (5-O2) ······································ 25 Configure Module 6 - Serial Communications (6-SC) ··································· 26 Configure Module 7 - Remote Setpoint Parameters (7-rS or 7-n2) ························· 27 Configure Module 8 - Second Linear DC Analog Output (8-A2) ····························· 27 Configure Module 9 - Factory Service Operations (9-FS) ································ 27
USERPARAMETERVALUECHART··················································· 28 CONFIGURATION PARAMETER EXPLANATIONS ······································· 30
Input Parameter Module (1- IN) CN63100 Models ······································ 30
Input Type (tYPE) ····························································· 30
TemperatureScale(SCAL) ····················································· 30
TemperatureResolution(dCPt)·················································· 30
Digital Input Filtering and Display Update Rate (FLtr) ································ 30
Input Sensor Correction Constant (SHFt) ·········································· 30
SetpointLimitValues(SPLO&SPHI)············································· 30
-ii-
Page 5
SetpointRampRate(SPrP)····················································· 31
User Input (InPt) ······························································ 31 Input Parameter Module (1- In) CN63300 models ······································ 32
Input Type (tYPE) ····························································· 32
DecimalPointPosition(dCPt) ··················································· 32
Rounding Increment ( rnd) ······················································ 32
Digital Input Filtering and Display Update Rate (FLtr) ································ 32
ScalingPoints································································ 32
DisplayValues(dSP1&dSP2) ·················································· 33
Signal Input Values (INP1 & INP2) ··············································· 33
SetpointLimitValues(SPLO&SPHI)············································· 33
SetpointRampRate(SPrP)····················································· 33
User Input (InPt) ······························································ 34 Output Parameter Module (2-OP) ··················································· 35
Time Proportioning Cycle Time (CYCt) ············································ 35
OutputControlAction(OPAC)··················································· 35
OutputPowerLimits(OPLO&OPHI) ············································· 35
Sensor Fail Power Level (OPFL) CN63100 only···································· 35
Output Power Dampening Filtering Time (OPdP) ···································· 35
ON/OFFControlHysteresis(CHYS) ·············································· 36
Auto-TuneCode(tcod)························································· 36
Main Linear DC Output Range (ANtP) (Optional) ···································· 36
Main Linear DC Output Source (ANAS) (Optional) ··································· 36
Main Linear DC Update Time (ANUt) (Optional) ····································· 36
Main Linear DC Output Scaling Points (ANLO, ANHl) (Optional) ······················· 36 Lockouts Parameter Module (3-LC)·················································· 37
Lower DisplayLockouts(SP,OP,dEv,UdSPandbdSP) ····························· 37
ProtectedModeLockouts (CodE,PId,andAL) ····································· 37
Hidden Mode Lockouts (ALrS, SPSL, trnF, and tUNE ) ······························· 37 Alarm Parameter Module (4-AL) (Optional)············································ 38
AlarmAction(Act1,Act2)······················································· 38
AlarmActionFigures··························································· 39
AlarmReset(rSt1,rSt2)························································ 41
Alarm Standby Delay (Stb1, Stb2) ················································ 41
-iii-
Page 6
AlarmValue(AL-1,AL-2) ······················································· 41
AlarmHysteresis (AHYS)······················································· 41 Cooling Parameters Module (5-02) (Optional) ········································· 42
CoolingOutputCycleTime(CYC2)··············································· 42
CoolingRelative Gain(GAn2) ··················································· 42
Heat and Cool Overlap/Deadband (db-2) ·········································· 42 Serial Communications Module (6-SC) (Optional) ······································ 43
BaudRate(bAUd)····························································· 43
CharacterFrameFormat(ConF)················································· 43
ControllerAddressNumber(Addr) ··············································· 43
AbbreviatedorFullTransmission(Abrv)··········································· 43
PrintOptions(PoPt) ··························································· 43 Remote Setpoint Parameters Module (7-n2 or 7-rS) (Optional) ···························· 44
RemoteSetpointDisplayValues(dSP1anddSP2)·································· 44
Remote Setpoint Signal Input Values (INP1 and INP2) ······························· 44
RemoteSetpointFiltering(FltrandbANd) ········································· 44
Remote/LocalSetpointTransferOptions(trnF) ····································· 44 Second Linear DC Analog Output Module (8-A2) (Optional) ······························ 45
Second Linear DC Output Range (A2tP) ··········································· 45
Second Linear DC Output Scaling Points (A2LO, A2Hl) ······························ 45 Factory Service Operations Module (9-FS)············································ 45
MANUALCONTROL ································································ 46 ON/OFFCONTROL································································· 47 AUTO-TUNE FORPIDCONTROL····················································· 50
InitiateAuto-Tune ································································ 51 Auto-TuneOfHeat/CoolSystems ··················································· 51 Auto-TuneOfCascadeControl ····················································· 51
PID CONTROL EXPLANATIONS ······················································ 52
Proportional Band ································································ 52 IntegralTime···································································· 52 DerivativeTime·································································· 53 Output Power Offset (Manual Reset)················································· 53 PIDAdjustments································································· 53
MANUALTUNINGFORPIDCONTROL ················································ 55
-iv-
Page 7
REMOTESETPOINTOPTION ························································ 56 CASCADECONTROL ······························································· 56 SERIALCOMMUNICATIONS INTERFACE·············································· 57
RS-485SerialCommunications····················································· 57 ControllerConfiguration··························································· 57 Sending Commands And Data ······················································ 57 Sending Numeric Data ···························································· 57 Controller (Node) Address ························································· 57 Commands Table ································································ 57 Register Identification Table························································ 58 TerminatorTable································································· 58 ExamplesofCommandStrings:····················································· 58 Command Code Explanations ······················································ 58
Controller (Node) Address: N ···················································· 58
Read Register Command Code: T ················································ 59
Write Register Command Code: V ················································ 59
Reset Alarm Command Code: R ················································· 59
Control Action Command Code: C ················································ 59
Block Read Register Command Code: P··········································· 59
Terminator:*or$····························································· 59 BlockReadCommandByteTable··················································· 60 Unique Register Explanations ······················································ 61
SetpointRampUsingAutomaticSetpointRampingRegister:K ························ 61
SetpointRampUsingPeriodicSetpointWriteRegister:B····························· 61
Periodic Setpoint Write Commands (E
2
PROM precautions)··························· 61
OutputStatus:W······························································ 61 CommunicationFormat···························································· 61 Command Response Time ························································· 62 FullFieldControllerTransmissionByteFormat········································ 63 AbbreviatedControllerTransmissionByteFormat······································ 64 Troubleshooting Serial Communications·············································· 64
APPLICATIONEXAMPLES ·························································· 65
CN63100 OEM Paint Sprayer Application ············································ 65 CN63300 Water Processing Application ·············································· 66
-v-
Page 8
CHECKSANDCALIBRATION ························································ 67
Main Input Check ································································ 67
mV Reading Check (CN63100) ·················································· 67
Thermocouple Cold Junction Temperature Check (CN63100) ························· 67
RTD Ohms Reading Check (CN63100) ············································ 67
Voltage Check (CN63300) ······················································ 67
Current Check (CN63300) ······················································ 67 Remote Setpoint Input Check (CN63100 and CN63300) ································· 67 ErrorFlagE-CL·································································· 67 Calibration For CN63100 ·························································· 68
FactoryServiceOperations-Calibration(9-FS)····································· 68
Millivolt Calibration (CAL) ······················································· 68
Thermocouple Cold Junction Calibration (CJC) ····································· 69
RTDOhmsCalibration(rtd) ····················································· 69
Main or Second Linear DC Analog Output Calibration ································ 69
RemoteSetpointCalibration····················································· 69 Calibration For CN63300 ·························································· 70
FactoryServiceOperations(9-FS) ··············································· 70
Input Calibration ······························································ 70
Main or Second Linear DC Analog Output Calibration ································ 70
RemoteSetpointCalibration····················································· 70
TROUBLESHOOTING······························································· 71 REPLACEABLEOUTPUTBOARDDESCRIPTION ······································· 73 SPECIFICATIONS AND DIMENSIONS ············································· 74 CN63100 TEMPERATURE CONTROLLER PART NUMBERS ·························· 78 CN63300 PROCESS CONTROLLER PART NUMBERS ································ 79
-vi-
Page 9
GENERAL DESCRIPTION
The CN63100 Controller accepts signals from a variety of temperature sensors (thermocouple or RTD elements), while the CN63300 Controller accepts either a 0 to 10 VDC or 0/4 to 20 mA DC input signal. Both controllers precisely display the process, and provide an accurate output control signal (time proportional or linear DC) to maintain a process at the desired control point. The controllers’ comprehensive programming allows them to meet a wide variety o f application requirements.
The controller can operate in the PID control mode for both heating and cooling, with on-demand Auto-Tune, which will establish the tuning constants. The PID tuning constants may be fine-tuned by the operator at any time and then locked out from further modification. The controller employs a unique overshoot suppression feature, which allows the quickest response without excessive overshoot. Operation of the controller can be transferred to manual mode, providing the operator with direct control of the output. The controller may also be programmed to operate in the ON/OFF control mode with adjustable hysteresis.
Dual 4-digit displays allow viewing of the process/temperature and setpoint simultaneously. Front panel indicators inform the operator of the controller and output status. The control output and the alarm outputs are field replaceable on select models.
Optional alarm (s) can be configured to activate according to a variety of actions (Absolute HI or LO, Deviation HI or LO, Band IN or OUT, and Heater Current Break) with adjustable hysteresis. A standby feature suppresses the alarm during power-up until the process stabilizes outside the alarm region.
Optional Main Linear DC output (10 V and 20 mA) can be used for control or retransmission purposes. Programmable output update time reduces valve or actuator activity. The output range can be scaled independent of the input range.
Optional Second Linear DC output (10 V or 20 mA) provides an independent process retransmission, while the main Linear DC output is being used for control. The output range can be scaled independent of the input range.
A Remote Setpoint input (0/4 to 20 mA) allows for cascade control loops, where tighter control quality is required; and allows for remotely driven setpoint signal from computers or other similar equipment. Straightforward end point scaling with independent filtering and local/remote transfer option expands the controller’s flexibility.
The optional RS485 serial communication interface provides two-way communication between a controller and other compatible equipment such as a printer, PLC, HMI, or a host computer. In multipoint applications (up to thirty-two), the address number of each controller on the line can be programmed from 0 to 99. Data from the controller can be interrogated or changed, and alarm output(s) may be reset by sending the proper command code via serial communications.
The unit is constructed of a lightweight, high impact plastic case with a tinted front panel. The front panel meets NEMA 4X/IP65 specifications when properly installed. Multiple units can be stacked horizontally or vertically. Modern surface-mount technology, extensive testing, plus high immunity to noise interference makes the controller extremelyreliableinindustrialenvironments.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so, can be potentially harmful to persons or equipment in the event of a fault to the unit. An independent and redundant temperature limit indicator with alarm outputs is strongly recommended.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
-1-
Page 10
INSTALLATION DESCRIPTION
The controller meets NEMA 4X/IP65 requirements for indoor use to provide a watertight seal in steel panels with a minimum thickness of 0.09 inch, or aluminum panels with a minimum thickness of 0.12 inch. The units are intended to be mounted into an enclosed panel. It is designed so that the units can be stacked horizontally or vertically (see Figure
1). The bezel assembly MUST be in place during installation of the unit.
INSTRUCTIONS:
1. Prepare the panel cutout to the dimensions shown in
Figure 1, Panel Installation.
2. Remove the panel latch from the unit. Discard the
cardboard sleeve.
3. Carefully remove the center section of the panel gasket
and discard. Slide the panel gasket over the unit from the
rear, seating it against the lip at the front of the case.
4. Insert the unit into the panel cutout. While holding the
unit in place, push the panel latch over the rear of the
unit, engaging the tabs of the panel latch in the farthest
forward slot possible.
5. To achieve a proper seal, tighten the panel latch screws
evenly until the unit is snug in the panel, torquing the
screws to approximately 7 in-lbs (79 N-cm). Over
tightening can result in distortion of the panel, and
reduce the effectiveness of the seal.
Note: The installation location of the controller is important.
Be sure to keep it awayfrom heat sources (ovens, furnaces,
etc.), and away from direct contact with caustic vapors,
oils, steam, or any other process byproducts in which
exposure may affect proper operation.
Figure 1, Panel Installation
-2-
Page 11
MULTIPLE UNIT STACKING
The controller is designed for close spacing of multiple units. Units can be stacked either horizontally or vertically. For vertical stacking, install the panel latch with the screws to the sides of the unit. For horizontal stacking, the panel latch screws should be at the top and bottom of the unit. The minimum spacing from center line to center line of units is 1.96" (49.8 mm). This spacing is the same for vertical or horizontal stacking.
Note: When stacking units, provide adequate panel ventilation to ensurethat
the maximum operating temperature range is not exceeded.
Figure 2, Multiple Unit Stacking Horizontal Arrangement
Caution: Disconnect power to the unit and to the output
control circuits to eliminate the potential shock hazard when removing the bezel assembly.
UNIT REMOVAL PROCEDURE
To remove a unit from the panel, first loosen the panel latch screws. Insert flat blade screwdrivers between the latch and the case on either side of the unit, so that the latches disengage from the grooves in the case. Push the unit through the panel from the rear.
REMOVING BEZEL ASSEMBLY
The bezel assembly, shown in Figure 3, must be removed from the case to replace the output board. To remove the bezel assembly, insert a flat blade screwdriver into the pry slot on either side of the unit. Twist the screwdriver handle until the unit is ejected enough to allow removal.
Figure 3, Bezel Assembly
Caution: The bezel assembly contains electronic circuits that can be damaged by
static electricity. Before removing the assembly, discharge static charge on your body by touching an earth ground point. It is also important that the bezel assembly be handled only by the bezel itself. Additionally, if it is necessary to handle a circuitboard,be certain that hands arefree from dirt, oil, etc.,to avoid circuit contamination that may lead to malfunction. If it becomes necessary to ship the unit for repairs, place the unit in its case before shipping.
INSTALLING BEZEL ASSEMBLY
To install the bezel assembly, insert the assembly into the case until the bezel is fully seated against the lip o f the case. Properly installing the bezel assembly is necessary for watertight sealing.
-3-
Page 12
CONNECTION DESCRIPTION
EMC INSTALLATION GUIDELINES
Although Red Lion Controls Products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly connected
to protective earth.
2. Use shielded cables for all Signal and Control inputs. The shield
connection should be made as short as possible. The connection point for
the shield depends somewhat upon the application. Listed below are the
recommended methods of connecting the shield, in order of their
effectiveness.
a. Connect the shield to earth ground (protective earth) at one end where
the unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually
when the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors, feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run through metal conduit that is
properly grounded. This is especially useful in applications where cable
runs are long and portable two-way radios are used in close proximity or if
the installation is near a commercial radio transmitter. Also, Signal or
Control cables within an enclosure should be routed as far away as possible
from contactors, control relays, transformers, and other noisy components.
4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI suppression devices such as Ferrite Suppression Cores for signal and control cables is effective. The following EMI suppression devices (or equivalent) are recommended: Fair-Rite part number 0443167251 (RLC part number FCOR0000) Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)
6. To protect relay contacts that control inductive loads and to minimize radiated and conducted noise (EMI), some type of contact protection network is normally installed across the load, the contacts or both. The most effective location is across the load. a. Using a snubber, which is a resistor-capacitor (RC) network or metal
oxide varistor (MOV) across an AC inductive load is very effective at reducing EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled by a
transistor switch, care must be taken not to exceed the breakdown voltage of the transistor when the load is switched. One of the most effective ways is to place a diode across the inductive load. Most RLC products with solid state outputs have internal zener diode protection. However external diode protection at the load is always a good design practice to limit EMI. Although the use of a snubber or varistor could be used.
RLC part numbers: Snubber: SNUB0000
Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output devices to the instrument. When a separate input and output common is provided, they should not be mixed. Therefore a sensor common should NOT be connected to an output common. This would cause EMI on the sensitive input common, which could affect the instrument’s operation.
Visit RLC’s web site at:
http://www.redlion.net/Support/InstallationConsiderations.html for more information on EMI guidelines, Safety and CE issues as they relate to Red Lion Controls products.
-4-
Page 13
WIRING CONNECTIONS
After the unit has been mechanically mounted, it is ready to be wired. All wiring connections are made to the rear screw terminals. When wiring the unit, use the numbers on the label and those embossed on the back of the case, to identify the position number with the proper function.
All conductors should meet voltage and current ratings for each terminal. Also cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that power supplied to the unit (AC or DC) be protected by a fuse or circuit breaker. Strip the wire, leaving approximately 1/4" (6 mm) bare wire exposed (stranded wires should be tinned with solder). Insert the wire under the clamping washer and tighten the screw until the wire is clamped tightly.
Caution: Unused terminals are NOT to be used as tie points. Damage to the
controller may result if these terminals are used.
SIGNAL WIRING
Thermocouple (CN63100)
When connecting the thermocouple, be certain that the connections are clean and tight, refer to Figure 4 for terminal connections. If the thermocouple probe cannot be connected directly to the controller, thermocouple wire or thermocouple extension-grade wire must be used to extend the connection points (copper wire does not work). Always refer to the thermocouple manufacturer’s recommendations for mounting, temperature range, shielding, etc. For multi-probe temperature averaging applications, two or more thermocouple probes may be connected to the controller (always use the same type). Paralleling a single thermocouple to more than one controller is not recommended. Generally, the red wire from the thermocouple is negative and connected to the controller’s common.
Figure 4, Thermocouple Connection
RTD (CN63100)
When connecting the RTD, be certain that the connections are clean and tight, refer to Figure 5 for terminal connections. RTD sensors have a higher degree of accuracy and stability than thermocouple sensors. Most RTD sensors available are the three wire type. The third wire is a sense lead f or canceling the effects of lead resistance of the probe. Four wire RTD elements may be used by leaving one of the sense leads disconnected. Two wire RTD sensors may be used in either of two ways:
A) Attach the RTD to terminals #8 and #10. Install a copper sense wire of the
same wire gage as the RTD leads. Attach one end of the wire at the probe
and the other end to terminal #9. Complete lead wire compensation is
obtained. This is the preferred method. B) Attach the RTD to terminals #8 and #10. Install a shorting wire between
terminals #9 and #10, as shown in Figure 5, RTD Connection. A
temperature offset error of 2.5°C/ohm of lead resistance exists. The error
may be compensated by programming a temperature offset.
Note: With extended cable runs, be sure the lead resistance is less than 15
ohms/lead. For thermocouple or RTD runs longer than 100 feet, convert the
signal to acurrent near the temperature probe.Currentor 20 mA loop signals
are less susceptible to noise and signal loss than long thermocouple or RTD
runs. By convertingthetemperature signal, the CN63300 canbe used in place
of a CN63100.
-5-
Figure 5, RTD Connection
Page 14
Signal (CN63300)
When connecting signal leads, be certain that the connections are clean and tight. For voltage signals, use terminal #8 for common and terminal #9 for signal. For current signals, use terminal #8 for common and terminal #10 for signal. These connections are shown in Figure 6. Multicontroller applications using the same signal source are possible, by connecting current signals in series, and voltage signals in parallel.
POWER WIRING
AC Power
Primary AC power is connected to terminals #11 and #12, labeled AC. To reduce the chance of noise spikes entering the AC line and affecting the controller, an AC feed separate from that of the load should be used to power the controller. Be certain that the AC power to the controller is relatively “clean” and within the variation limit. Connecting power from heavily loaded circuits or circuits that also power loads that cycle on and off, (contacts, relays, motors, etc.) should be avoided.
DC Power
DC power (18 to 36 VDC) is connected to terminals #11 and #12 labeled DC+ and DC- respectively.
CAUTION: Observe proper polarity when connecting DC voltages.
Damage to the unit may occur if polarity is reversed.
CONTROL AND ALARM OUTPUTS
For CN63100 heating, cooling, and alarms, there are up to two types of ON/OFF outputs. These outputs can be relay, or logic for control or alarm purposes. Relay outputs can switch user applied AC or DC voltages. Logic/SSR drive outputs supply power to external SSR power units. One Logic/SSR Drive output can control up to four SSR power units at one time. The CN63300 is only available with relay outputs. Terminal numbers for the outputs and output types vary from model to model. Refer to the Rear Terminal Assignment Tables or the label on the controller for the terminal numbers corresponding to the model being wired.
Relay Connections
To prolong contact life and suppress electrical noise interference due to the switching of inductive loads, it is good installation practice to install a snubber across the contactor. Follow the manufacturer’s instructions for installation.
Note: Snubber leakage current can cause some electromechanical devices to be
held ON.
Relay Outputs:
Type: Form-A Rating: 3 Amps @ 250 VAC or 30 VDC (resistive load). Life Expectancy: 100,000 cycles at maximum load rating. (Decreasing
load and/or increasing cycle time, increases life expectancy).
-6-
Figure 6, CN63300 Signal Connection
Figure 7, Relay Output
Page 15
Logic/SSR Connections (CN63100 only)
Logic/SSR Drive Output:
Rating: 45 mA @ 4 V min., 7 V nominal (current limited)
Figure 8, Logic/SSR Output
REMOTE SETPOINT WIRING
Models with the Remote Setpoint option have two input terminals to receive a 0 to 20 mA signal. Connect the Remote Setpoint signal to terminals labeled #13 (+) and #14 (-), “2nd Input Option”. The common of this input is isolated from input common, but is not isolated from the Linear DC output commons. For proper operation, keep this common isolated from all other controller commons.
MAIN LINEAR DC OUTPUT WIRING
Models with the Linear DC output option provide either a linear 10 V or a linear 20 mA signal. The output range is selected by jumpers on the output board. (See Linear DC Analog Output Jumper Selection, page 11). The terminals are #1 (-) and #2 (+). The common of this output is isolated from input common, but is not isolated from other commons. For proper operation, keep this common isolated from all other controller commons.
SECOND LINEAR DC OUTPUT WIRING
Models with the Second Linear DC output option provide a conditioned and scaled retransmitted signal output. The terminals are #13 (+) an d #14 (-). The common of this output is isolated from the input common, but not from the other commons. For proper operation, keep this common isolated from all other controller commons.
USER INPUT WIRING
The use of shielded cable is recommended. Follow the EMC installation guidelines for shield connection.
Terminal #6 is the User Input, which is programmable for a variety of functions. Any form of mechanical switch may be connected to terminal #6 (USER INPUT) and terminal #8 (COMM.). Sinking open collector logic with less than 0.7 V saturation and off-state leakage current of less than 1 μAmay also be used.
-7-
Page 16
REAR TERMINAL ASSIGNMENTS
CN63100 Models Without RS-485 and Analog Output
TC RTD AC/DC Power A2 or 02
(+) (-) Short (C) AC/(+) AC/(-) (C) (C) (C) (C) (+) (-)
989108 11 12 4 5 6 8 -R1 -R1-LV
9 8 9 10 8 11 12 1 2 3 2 4 5 6 8 -R1-R2-AL -R1-R2-AL-LV
9 8 9 10 8 11 12 1 2 3 2 4 5 6 8 13 14 -R1-R2-AL-RSP -R1-R2-AL-RSP-LV
9 8 9 10 8 11 12 4 5 6 8 -DC1 -DC1-LV
9 8 9 10 8 11 12 1 2 3 2 4 5 6 8 -DC1-R2-AL -DC1-R2-AL-LV
(C) is the Common Terminal
Terminals 9 & 10 need to be shorted together.
* Remote Setpoint
DedicatedA1Dedicated
O1
User Input
2nd Input
Option *
AC Model # DC Model #
CN63100 Models With RS-485 or Linear DC Analog Output
TC RTD
(+) (-) Short (C) AC/(+) AC/(-) (+) (-) (C) (C) (C) (C) (C) A(+) B(-) (+) (-) (+) (-)
9 8 9 10 8 11 12 2 1 3 4 5 4 6 8 13 14 -R1-R2-F3 -R1-R2-F3-LV
9 8 9 10 8 11 12 2 1 3 4 5 4 6 8 13 14 -R1-R2-F3-RSP -R1-R2-F3-RSP-LV
9 8 9 10 8 11 12 2 1 3 4 5 4 6 8 13 14 -R1-R2-F3-C4 -R1-R2-F3-C4-LV
9 8 9 10 8 11 12 1 2 3 2 4 5 6 8 13 14 -R1-R2-AL-C4 -R1-R2-AL-C4-LV
9 8 9 10 8 11 12 1 2 3 2 4 5 6 8 13 14 -DC1-R2-AL-C4 -DC1-R2-AL-C4-LV
(C) is the Common Terminal
Terminals 9 & 10 need to be shorted together.
* Remote Setpoint
AC/DC Power
Analog
Main Out
A2 or O2
Dedicated
A1
O1 or A1
DedicatedO1User
Input
RS485
Output
2nd Input
Option *
Analog
2nd Out
AC Model # DC Model #
-8-
Page 17
REAR TERMINAL ASSIGNMENTS
ALL CN63300 Models
0 - 10V
0-20mA
Input
(+) (-) (+) (-) AC/(+) AC/(-) (+) (-) (C) (C) (C) (C) (C) A(+) B(-) (+) (-)
9 8 10 8 11 12 4 5 6 8 -R1 -R1-LV
9 8 10 8 11 12 2 1 3 4 5 4 6 8 -R1-R2-F3 -R1-R2-F3-LV
9 8 10 8 11 12 2 1 3 4 5 4 6 8 13 14 -R1-R2-F3-RSP -R1-R2-F3-RSP-LV
9 8 10 8 11 12 2 1 3 4 5 4 6 8 13 14 -R1-R2-F3-C4 -R1-R2-F3-C4-LV
9 8 10 8 11 12 1 2 3 2 4 5 6 8 -R1-R2-AL -R1-R2-AL-LV
9 8 10 8 11 12 1 2 3 2 4 5 6 8 13 14 -R1-R2-AL-C4 -R1-R2-AL-C4-LV
(C) is the Common Terminal.
* Remote Setpoint Input.
Input
AC/DC Power
Analog
Main Out
A2 or O2
Dedicated
A1
O1 or A1
DedicatedO1User
Input
RS485
Output
2nd Input
Option *
AC Model # DC Model #
-9-
Page 18
SERIAL CONNECTIONS TO A HOST TERMINAL
Six controllers are used to monitor and control parts packaging machines in a plant. The controllers are located at each machine in the production area of the building. A communication line is run to an industrial computer located in the production office.
Each controller is programmed for a different address and all are programmed for the same baud rate and parity as the computer (ex. 9600 baud, parity even). An application p rogram is written by the user to send and receive data from the units using the proper commands.
Figure 9, Connecting to a Host Terminal
-10-
Page 19
LINEAR DC ANALOG OUTPUT JUMPER SELECTION
(Main & Second)
The Linear Analog DC Output ranges are selectable for either voltage (0-10 V) or current (0/4-20 mA). The main set of jumpers must correspond with the configuration in Linear Output Range (ANAS) in the Output Parameter Module (2-OP). The optional secondary set of jumpers must correspond with the configuration in Second Linear DC Output Range (A2tP) in the Second Linear DC Analog Output Module (8-A2). The jumpers are accessible from the rear after removing the controller from the case. Dashed lines show factory setting of 20 mA.
Figure 10, Linear Output Range Jumpers
-11-
Page 20
FRONT PANEL DESCRIPTION
The front panel bezel material is flame and scratch resistant, tinted plastic that meets NEMA 4X/IP65 requirements, when properly installed. Continuous exposure to direct sunlight may accelerate the aging process of the bezel. The bezel should be cleaned only with a soft cloth and neutral soap product. Do NOT use solvents. There are two 4-digit LED displays, a red upper Main Display and a lower green Secondary Display.
There are up to six annunciators, with red backlighting, that illuminate to inform the operator of the controller and output status. See Figure 11, Front Panel, for a description of the annunciators.
Four front panel buttons are used to access diff erent modes and parameters. The following is a description of each button.
Do NOT use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of this unit.
BUTTON FUNCTIONS
D - In the Normal Display Mode, the
Display (D) button is used to
select one of the operational
parameters in the secondary
display. In other modes, pressing
the D button causes the controller
to exit (escape) directly to the
Normal Display Mode. P - The Parameter (P) button is used
to access programming, enter the
change, and scroll through the
available parameters in any mode. UP, DN - In the Normal Display
Mode, the Up/Down (L /M)
buttons can be used to directly
modify the setpoint value or
% output power (manual control
only), when viewed in the
secondary display.
Figure 11, Front Panel
-12-
Page 21
INITIAL CONFIGURATION START-UP
CONTROLLER POWER-UP
Upon applying power, the controller delays input indication and control action for five seconds to perform several self-diagnostic tests and to display basic controller information. Initially, the controller illuminates both displays and all annunciators to verify that all display elements are functioning. The controller then displays the programmed input sensor type in the main (top) display and the revision number of the controller’s operating system software in the secondary (bottom) display. The controller checks for correct internal operation and displays an error message (E-xx) if an internal fault is detected. (See Troubleshooting, page 71, for further information).
Upon completion of this sequence, the controller begins displaying the input value and updating the outputs based upon the control calculation.
PARAMETER CONFIGURATION OVERVIEW
The controller is programmed with certain parameter settings from the factory. Factory settings are listed in parentheses in the various Configuration of Parameters tables. In many cases, these settings must be changed to the particulars of the application before proper operation can be started.
The controller is typically in the Normal Display Mode. When changes to parameter configurations are needed, the P button is pressed. From the factory, the controller will enter directly into the Unprotected Parameter Mode. Continue to press the P button until CnFP appears in the bottom display. At this time, press the Up arrow button and 1-In will appear in the bottom display. This will be the Configuration Parameter Mode. This programming flow is shown in the Front Panel Programming Chart. (If at any time during front panel programming the D button is pressed, the controller will return to the Normal Display Mode and the programming can be started over.)
In the Configuration Parameter Mode, the Up or Down arrow buttons can be pressed to move to the desired Parameter Module. The P button is then pressed to enter into that module. The main (top) display will be the parameter and the secondary (bottom) display will be the parameter value. The Up or Down arrow buttons are used to change the desired parameter value and the P button enters the new value and moves to the next parameter.
The Setpoint value (lower display) is changed with the Up or Down arrow buttons when it is selected in the Normal Display Mode.
PARAMETER CONFIGURATION BASIC START-UP
For basic start-up, it is important to verify or change Input Parameter Module (1-IN) parameters tYPE and SCAL, and Output Parameter Module (2-OP) parameter OPAC. For alarm and heat/cool set-up, it is important to verify or change Alarms Parameter Module (4-AL) parameters ACt1, AL-1, ACt2 and AL-2.
If the above Input Parameters or the input wiring connections are not correct, then the main (top) display may display an error message or incorrect value. Verify the input programming and wiring. (If incorrect display continues refer to Troubleshooting, page 71.) All other parameter configurations are important but will not prevent the controller from showing a correct display.
PARAMETER CONFIGURATION FOR SERIAL START-UP
The parameter settings can be changed by the front panel button. For serial communications set-up, it is important to check serial wiring and verify or change Serial Parameter Module (6-SC) p arameters bAUd, ConF,s and Addr. (See Serial Communications Interface, page 57, for more details.)
CONTROL START-UP
After verifying proper programming and system start-up, a controlling method needs to be configured. For Manual Control or open loop, where the control does not work from the setpoint or process feedback, see Manual Control, page 46. For On / Off Control, set Proportional Band Prop to 0.0% and see On / Off Control, page 47. The controller comes with factory setting for PID Control. However, for optimum PID Control, several options exist for configuring Proportional Band, Integral Time, and Derivative Time parameters for specific applications.
a. Use controller’s built-in Auto-Tune feature (See Auto-Tune For PID
Control, page 50).
b. Use a manual tuning technique (See Manual Tuning For PID Control,
page 55). c. Use a third party tuning software package. d. Use values based on control loop experience, calculated values or values
from a similar process or previous controller.
-13-
Page 22
VALID CONTROL MODE COMBINATIONS
ON/OFF, PID, and Manual Control can be used for O1 (heat) and O2 (cool)
outputs according to the combinations below.
O1 & O2 VALID CONTROL MODES
O1 MODE O2 MODE
PID 0% to +100% O1-TP
ON/OFF (ProP = 0.0)
PID PID -100% to +100% O1-TP O2-TP
PID ON/OFF
ON/OFF (ProP=0.0)
TP - Time Proportioning
100% O1-ON
(GAN2=0.0)
ON/OFF (GAN2=0.0)
MANUAL CONTROL
OUTPUT POWER
RANGE
Any other setting O1-OFF
0% to +100% O1-TP O2-OFF
-100% to 0% O1-TP O2-ON
+100% O1-ON O2-OFF
-100% O1-OFF O2-ON
Any other setting O1-OFF O2-OFF
O1 STATE O2 STATE
-14-
Page 23
FRONT PANEL PROGRAMMING CHART FOR CN63100 & CN63300 CONTROLLERS
-15-
Page 24
NORMAL DISPLAY MODE
In the Normal Display Mode, the temperature or scaled process value is displayed in the main (top) display. By successively pressing the D button, the parameters listed below can be viewed in the secondary (bottom) display. Each of these p arameters can be independently locked out from appearing or from being modified through the Lockout Parameter 3-LC. If all four displays are locked out, the display blanks after pressing the D button. To gain access to the next modes, press the P button from any parameter.
To modify values in % Output Power (for Manual Control) or Setpoint, use the Up or Down arrows while the parameter is displayed and not locked. If locked, these parameters can be changed in the Protected Parameter Mode. The controller responds to the new values immediately, however, the change is not committed to permanent memory until 10 seconds after the last key press.
Normal Display Mode Reference Table
Illuminates Parameter
—- Local Setpoint
SP1 or SP2
%P % Output
Power
DV Setpoint
Deviation
—- Units Symbol °For°C
—- Blank Blank display
Range and Units (Factory Setting)
-999 to 9999 (0) for CN63100 (0.0) for CN63300
-99.9% to 100.0% Read only Unless in Manual Control
-999 to 9999 Read only
Read only
Description/Comments
Range limited by SPLO & SPHI in 1-In.
Not limited by OPLO & OPHI in 2-OP.
Shows difference between Temp/Process (top display) and Setpoint.
CN63100 models only
CN63300 models only
FRONT PANEL PROGRAM DISABLE
There are several ways to limit the programming of parameters from the front panel buttons. The settings of the parameters in the Lockout Module 3-LC, the code number entered, and the state and/or function programmed for the User Input (Terminal #6) will all affect front panel access.
The following chart d escribes the possible program disable settings.
User Input State Code Number Description
Inactive or User Input not programmed for PLOC
Active with User Input programmed for PLOC
Active with User Input programmed for PLOC
OR User Input not programmed for PLOC
Note: A universal code number 222 can be entered to gain access to the
unprotected mode and configuration modules, independent of the programmed code number.
0 Full access to all modes and
0 Access to protected parameter
Any # between 1 & 250
parameter modules.
mode only. Code number does not appear.
Access to protected parameter mode. Correct programmed code number allows access to unprotected parameter mode and configuration modules.
-16-
Page 25
UNPROTECTED PARAMETER MODE
The Unprotected Parameter Mode is accessed by pressing the P button from the Normal Display Mode with Program Disable inactive. While in this mode, the operator has access to the most commonly modified controller parameters by pressing the P button. The temperature or scaled process value is displayed in the main (top) display. The parameter display will appear with the corresponding range and units in the secondary (bottom) display.
To modify values, use the Up or Down arrows while the parameter is displayed. The controller responds to the new values immediately, however, the change is not committed to non-volatile memory until the controller is returned to the Normal Display Mode. If power loss occurred before returning to the Normal Display Mode, the new values must be entered again.
To gain access to the Configuration Parameter Modules, continue to CnFP and press the Up arrow. These modules allow access to the fundamental set-up parameters of the controller. When the program list has been scrolled through, or the D button is pressed, the controller displays “End” and returns to the normal display mode. The unit automatically returns to the Normal Display Mode if no action is taken.
Unprotected Parameter Mode Reference Table
Display Parameter
SP Local **
Setpoint SP1 or SP2 *
OPOF %Output **
Power Offset
OP % Output **
Power
ProP Proportional
Band
Intt Integral
Time
dErt Derivative
Time
AL-1 Alarm 1
Value *
AL-2 Alarm 2
Value *
CNFP Configuration
Access Point
End Returns to
Normal Display Mode
* Model Number Dependent. ** Only appears if locked out from Normal Display Mode.
Range and Units (Factory Setting)
-999 to 9999 (0) CN63100 (0.0) CN63300
-99.9% to 100.0% (0.0)
-99.9% to 100.0% (0.0)
0.0 to 999.9% of selected input range (4.0) CN63100 (100.0) CN63300
0 to 9999 sec. (120) CN63100 (40) CN63300
0 to 9999 sec. (30) CN63100 (4) CN63300
-999 to 9999, (0) CN63100 (0.0) CN63300
-999 to 9999, (0) CN63100 (0.0) CN63300
Up Arrow
____ Brief display message while the
Description/ Comments
Range limited by SPLO & SPHI. User Input or Hidden Function Mode selects SP1 or SP2
Appears only if Intt = 0 and unit is in Automatic Control.
Appears only if unit is in Manual Control. This parameter is not limited to output power limits (OPLO & OPHI).
0.0% is ON/OFF control. If using ON/OFF, set control hysteresis appropriately.
0 is off. This parameter does not appear if ProP = 0.0%.
0 is off. This parameter does not appear if ProP = 0.0%.
This parameter does not appear if configured for “heat”.
This parameter does not appear if configured for “cool”.
NO
Return to Normal Display Mode. Enter Configuration modules.
unit returns to Normal Display Mode.
-17-
Page 26
PROTECTED PARAMETER MODE
The Protected Parameter Mode is accessed by pressing the P button from the Normal Display Mode with Program Disable active. While in this mode, the p arameters can be accessed by pressing the P button. The temperature or scaled process value (after initial setup) will be displayed in the main (top) display. The parameter display will appear with the corresponding range and units in the secondary (bottom) display. Each of these parameters can be independently locked out from appearing or from being modified through the Lockout Parameter 3-LC.
To modify values, use the Up or Down arrows while the parameter is displayed. If locked, the parameter will not show in the Normal Display Mode, but can be changed in the Protected Parameter Mode. The controller responds to the new values immediately, however, the change is not committed to non-volatile memory until the controller is returned to the Normal Display Mode. If power loss occurred before returning to the Normal Display Mode, the new values must be entered again.
To gain access to the Unprotected Parameter Mode (with User Input inactive or not programmed for PLOC), continue to CodE and press the arrow buttons until the value equals the Code as entered in parameter lockouts. When an incorrect code value is entered, or when the D button is pressed, “End” will momentarily appear and the controller will return to the Normal Display Mode.
Protected Parameter Mode Reference Table
Display Parameter
ProP Proportional
Band
Intt Integral
Time
dErt Derivative
Time
AL-1 Alarm 1
value *
AL-2 Alarm 2
value *
CodE Access
code to Unprotected Parameter Mode
End Returns to
Normal Display Mode.
* Model Number Dependent.
Range and Units (Factory Setting)
0.0 to 999.9% of selected input range (4.0) CN63100 (100.0) CN63300
0 to 9999 sec. (120) CN63100 (40) CN63300
0 to 9999 sec. (30) CN63100 (4) CN63300
-999 to 9999 (0) CN63100 (0.0) CN63300
-999 to 9999 (0) CN63100 (0.0) CN63300
0to250 (0)
—-
Description/Comments
0.0% is ON/OFF Control. Adjusted by Auto-Tune.
0 is off. This parameter does not appear if ProP = 0.0%. Adjusted by Auto-Tune.
0 is off. This parameter does not appear if ProP = 0.0%. Adjusted by Auto-Tune.
This parameter does not appear if configured for “heat”.
This parameter does not appear if configured for “cool”.
To gain access to Unprotected Parameter Mode, enter the same value for Code as used in parameter lockouts. Does not appear if zero is entered in code parameter lockout.
Brief display message while the unit returns to Normal Display Mode.
-18-
Page 27
HIDDEN FUNCTION MODE
The Hidden Function Mode is only accessible from the Normal Display Mode by pressing and holding the P button for three seconds. These functions must first be unlocked in Configuration Module 3-LC. Factory settings for these parameters is lock. In this mode, these controller functions can be performed.
buttons are used to select the operation. Pressing the P button while the function is displayed executes the function, and returns the unit to the Normal Display Mode. Pressing the D button exits this mode with no action taken. The unit automatically returns to the Normal Display Mode if no action is taken within a few seconds.
Hidden Function Mode Reference Table
Display Parameter
SPSL Setpoint
trnF Transfer
tUNE Auto-tune
ALrS Alarm
* Model Number Dependent
Remote/SP1/SP2 Setpoint Selection Automatic/Manual Transfer Initiate/Cancel Auto-tune Reset Alarm Outputs
The P button is used to scroll to the desired function and the Up and Down
Select
mode of operation
Invocation
Reset *
Range and Units
(Factory Setting Value)
SP1 - Setpoint 1 SP2 - Setpoint 2 rSP - Remote Setpoint
Auto - Automatic control User - Manual control (Auto)
Yes: starts the
auto-tune sequence.
No: terminates the
auto-tune sequence.
(NO) UP button resets Alarm 1
DOWN button resets Alarm 2
Description/ Comments
Exits to Normal Display Mode after being executed.
Exits to Normal Display Mode after being executed.
Exits to Normal Display Mode after being executed.
Does not exit to Normal Display Mode after being executed.
CONFIGURATION PARAMETER MODE
The Configuration Parameter Mode is accessed by pressing the Up button from CnFP in the Unprotected Parameter Mode. While in this mode, the various Configuration Modules can be displayed by pressing the Up or Down buttons. The process value (after initial setup) will be displayed in the main (top) display. The Configuration Module will appear alternating with CnFP in the secondary (bottom) display.
To access a Configuration Module, press the P button when the desired Configuration Module is displayed. The parameters of that Configuration Module can be accessed by pressing the P button. (The module’s parameters are listed in the appropriate Configuration Module table in this section with configuration parameter explanations beginning on page 30.) To modify ranges and units, use the Up or Down arrows while the parameter is displayed. The controller responds to the new values after the P button is pressed, however, the change is not committed to permanent memory until the controller is returned to the Normal Display Mode. If power loss occurred before returning to the Normal Display Mode, the new values must be entered again. Whenever the D button is pressed, End will momentarily appear and the controller will return to the Normal Display Mode. At the end of each module, the controller will go to CnFP no. Pressing the Up or Down arrows will continue in Configuration Parameter Mode and pressing the P will return to the Normal Display Mode.
Unless specified, the parameters, ranges, units and factory settings are the same for CN63100 and CN63300 controllers. Parameters that are model number or program dependent will only be displayed when the appropriate options are installed or programmed. Some parameters are accessible but may not be applicable for the chosen output control mode type.
-19-
Page 28
REFERENCE TABLES: CONFIGURATION PARAMETER MODULES
Configure Module 1 - Input Parameters (1-IN) CN63100
These tables are only used for programming the CN63100 models. Use the tables on page 21 if you are programming a CN63300.
Display Parameter
tYPE Input Type tc-t - Type T TC
SCAL Temperature
Scale
dCPt Temperature
Resolution
FLtr Digital Input
Filtering And Display Update
Range and Units (Factory Setting)
tc-E - Type E TC tc-J - Type J TC tc-k - Type K TC tc-r-TypeRTC tc-S - Type S TC tc-b - Type B TC tc-N - Type N TC LIN - Linear mV display
r385 - 385 curve RTD r392 - 392 curve RTD rLIN - Linear ohms display
(tc-J)
°F/°C (°F)
0or0.0 (0)
0to4 (1)
Description/
Comments
Thermocouple select
RTD select
If scale is changed, be sure to check all parameters.
If resolution changed, be sure to check all parameters.
Increase number for more filtering effect. 4 = 500 msec display update rate. Adjusted by Auto-Tune.
Display Parameter
SHFt Input Signal
Shift (correction offset)
SPLO Setpoint Lower
Limit
SPHI Setpoint Upper
Limit
SPrP Setpoint Ramp
Rate
InPt User Input * PLOC - Program disable
Range and Units (Factory Setting)
-999 to 9999 1 or 0.1 degree (0)
-999 to 9999 0 or 0.1 degree (0)
-999 to 9999 1 or 0.1 degree (9999)
0.0 to 999.9 degrees/minute (0.0)
ILOC - Integral action on/off trnF - Auto/manual select SPrP - Setpoint ramp on/off ALrS - Reset alarm output(s) SP2 - Select SP1/SP2 rSP - Select
Local/Remote PrNt - Serial block print (PLOC)
* Model Number Dependent
-20-
Description/
Comments
Normally set to 0.
Set low limit below high limit.
Set high limit above low limit.
0.0 is off (no ramping)
Low = lock Low = off Low = manual Low = end ramp Low = reset Low = SP2 Low =remote
Low =block print
Page 29
Configure Module 1 - Input Parameters (1-IN) CN63300
These tables are only used for programming the CN63300 models. Use the tables on page 20 if you are programming a CN63100.
Display Parameter
tYPE Input Type VOLt - Voltage
dCPt
rnd Rounding
FLtr Digital Input
dSP1 Scaling Point #1
InP1 Scaling Point #1
dSP2 Scaling Point #2
Decimal Point 0, 0.0, 0.00, or 0.000
Increment
Filtering And Display Update
Display Value
Input Signal 0/4-20 mA DC 0-10 VDC
Value Key-in Method
Signal Input Method
Display Value
Range and Units (Factory Setting)
Curr - Current (Curr)
(0.0)
1, 2, 5, 10, 20, 50, or 100 (0.1)
0to4 (1)
-999 to 9999 (0.0)
0.00 to 20.00 mA
0.00 to 10.00 V (4.00)
-999 to 9999 (100.0)
Description/
Comments
If 0.000 is selected, scaling points must be a positive value.
Used in conjunction with filtering to stabilize the display reading.
Increase number for more filtering effect. 4 = 500 msec display update rate. Adjusted by Auto-Tune.
Key-in display low value.
Press D button to select Signal Input method.
Key-in input low value.
Apply input low value.
Key-in display high value.
Display Parameter
InP2 Scaling Point #2
Input Signal 0/4-20 mA DC 0-10 VDC
Value Key-in Method
Signal Input Method
SPLO Setpoint Lower
Limit
SPHI Setpoint Upper
Limit
SPrP Setpoint Ramp
Rate
InPt User Input * PLOC - Program disable
Range and Units (Factory Setting)
0.00 to 20.00 mA
0.00 to 10.00 V (20.00)
-999 to 9999 (0.0)
-999 to 9999 (999.9)
0 to 9999 units/minute (0.0)
ILOC - Integral action on/off trnF - auto/manual select SPrP - Setpoint ramp on/off ALrS - Reset alarm output(s) SP2 - Select SP1/SP2 rSP - Select
Local/Remote PrNt - Serial block print (PLOC)
* Model Number Dependent
-21-
Description/
Comments
Press D button to select Signal Input method.
Key-in input low value.
Apply input low value.
Set low limit below high limit.
Set high limit above low limit.
0.0 is off (no ramping).
Low = lock Low = off Low = manual Low = end ramp Low = reset Low = SP2 Low =remote
Low =block print
Page 30
Configure Module 2 - Output Parameters (2-OP)
Display Parameter
CYCt Time
Proportioning Cycle Time
OPAC Output Control
Action
OPLO Output Power
Lower Limit (Not used in Manual Control)
OPHI Output Power
Upper Limit (Not used in Manual Control)
OPFL Sensor Fail
Power Level (Not used in Manual Control)
OPdP Output Power
Dampening (filtering) Time
Range and Units (Factory Setting)
0 to 250 seconds (2)
drct - cooling rEv - heating (rEv)
0% to 100%, O1 (0)
-100% to 100%, O1 & O2 (-100)
0% to 100%, O1 (100)
-100% to 100% O1 & O2 (100)
0% to 100%, O1 (0)
-100% to 100% O1 & O2 (0)
0 to 250 seconds (3) CN63100 (1) CN63300
Description/
Comments
0 turns O1 off. Set to zero for Linear DC output control. Not used for ON/OFF Control.
For both PID & ON/OFF control.
Set OPLO < OPHI
Negative % is only valid for O2 cooling control.
Set OPHI > OPLO
Negative % is only valid for O2 cooling control.
Select a level to safely control the process in the event of input sensor failure. CN63100 only.
0 = off (no dampening) Set in range of 1/50 to 1/10 of integral time. Adjusted by Auto-Tune.
Display Parameter
CHYS ON/OFF Control
Hysteresis
tcOd Auto-tune
Dampening Code
ANtP Main Linear DC
Output Range *
ANAS Main Linear DC
Output Source *OPInP
ANUt Main Linear DC
Output Update *
ANLO Main Linear DC
Output Low Scaling Value *
ANHI Main Linear DC
Output High Scaling Value *
* Model Number Dependent
Range and Units (Factory Setting)
1to250 (2) CN63100 (0.2) CN63300
0to2 (0)
0to10V 0to20mA 4to20mA (4 to 20 mA)
SP (OP)
0 to 250 secs (0)
-999 to 9999 (0.0)
-999 to 9999 (100.0)
Description/
Comments
For O1 ON/OFF Control. Change to Factory Setting prior to Auto-Tune.
0 = fastest response 2 = slowest response
Set linear output range jumper to match.
SP = Active Setpoint
0 = Update rate of 0.1 sec.
Value depends on ANAS assignment.
Value depends on ANAS assignment.
-22-
Page 31
Configure Module 3 - Lockout Parameters (3-LC)
Display Parameter
SP Setpoint access LOC - lockout
OP Output power
access
dEv Deviation display
access
UdSP Units display
access For CN63100
bdSP Blank display
access For CN63300
CodE Access code 0 to 250
Range and Units (Factory Setting)
rED - read only Ent - enter (Ent)
LOC - lockout rED - read only Ent - enter (Ent)
LOC - lockout rEd - read only (rEd)
LOC - lockout rEd - read only (rEd)
LOC - lockout rEd - read only (rEd)
(0)
Description/ Comments
Determines access to temperature setpoint.
Determines direct access to output power. %P indicator illuminates when parameter is selected in display.
Determines display of deviation. DV indicator illuminates when parameter is selected in display.
Determines display of F or C.
Determines blank secondary display.
Refer to front panel disable section for access levels.
Display Parameter
PId PID values
access
AL Alarm values
enable *
ALrS Reset alarms
enable *
SPSL SP1/SP2/Remote
setpoint enable *
trnF Automatic/Manual
(user) mode select enable
tUNE Auto-tune enable LOC- lockout
Range and Units (Factory Setting)
LOC - lockout rEd - read only Ent - enter (LOC)
LOC - lockout rEd - read only Ent - enter (LOC)
LOC - lockout ENBL - enable (LOC)
LOC- lockout ENBL - enable (LOC)
LOC - lockout ENBL - enable (LOC)
ENBL - enable (LOC)
* Model Number Dependent
Description/ Comments
Protected Mode lockout.
Protected Mode lockout.
Hidden Mode lockout.
Hidden Mode lockout.
Hidden Mode lockout.
Hidden Mode lockout.
-23-
Page 32
Configure Module 4 - Alarm Parameters (4-AL)
Controller returns to configuration access point (CnFP NO) if alarm(s) are
not installed.
Display Parameter
ACt1 Alarm 1 action
mode
rSt1 Alarm 1 reset
mode
Stb1 Alarm 1 standby
function (delay)
AL-1 Alarm 1 value -999 to 9999
ACt2 Alarm 2 action
mode *
Range and Units (Factory Setting)
A-HI - absolute high A-LO - absolute low d-HI - deviation high d-LO - deviation low b-IN - band inside
b-ot - band outside Heat - control output * (A-HI)(HEAt) *
Auto - automatic LAtc - manual reset (Auto)
yes/no (no)
(0) CN63100 (0.0) CN63300
A-HI - absolute high A-LO - absolute low d-HI - deviation high d-LO - deviation low b-IN - band inside b-ot - band outside CooL- cooling output (A-HI)
Description/
Comments
If changed, check alarm values. If heat is selected, the remaining alarm parameters do not appear. For CN63300, heat is main control output.
Manual reset via Hidden Mode or user input.
Power-up standby delay.
If band alarm action, then only a positive value can be entered.
If changed, check alarm values. If cooling is selected, the remaining Alarm 2 parameters do not appear. For CN63300, cool is second PID control output.
Display Parameter
rSt2 Alarm 2 reset
mode *
Stb2 Alarm 2 standby
function (delay) *
AL-2 Alarm 2 value * -999 to 9999
AHYS Alarm Hysteresis
value
Range and Units (Factory Setting)
Auto - automatic LAtc - manual reset (Auto)
yes/no (no)
(0) CN63100 (0.0) CN63300
1to250 (1) CN63100 (0.1) CN63300
* Model Number or Mode Setting Dependent
Description/
Comments
Manual reset via hidden Mode or user input.
Power-up standby delay.
If band alarm action, then only a positive value can be entered.
Applies to both alarms. Set to eliminate chatter.
-24-
Page 33
Configure Module 5 - Cooling Parameters (5-O2)
Controller returns to configuration access point (CnFP NO) if Alarm 2 is not configured as cooling output in Alarm Module (4-AL). Cooling output for the CN63300 is referred to as the second control output.
Display Parameter
CYC2 Cooling output cycle
time
GAN2 Relative cooling
gain
db-2 Heating or cooling
overlap/deadband
Range and Units (Factory Setting)
0to250sec
(2)
0.0 to 10.0 (1.0)
-999 to 9999 (0)
Description/
Comments
0 turns O2 off.
0.0 places cooling output into ON/OFF Control and db-2 becomes hysteresis value.
Positive value is deadband. Negative value is overlap. If GAN2 = 0, this parameter is cooling ON/OFF Control hysteresis. Change to Factory Setting prior to Auto-Tune.
-25-
Page 34
Configure Module 6 - Serial Communications (6-SC)
Controller returns to configuration access point (CnFP NO) if RS485 serial
option is not installed.
Display Parameter
bAUd Baud rate 300 to 9600
ConF Character Frame
format
Addr Controller address 0 to 99
Abrv Abbreviated or full
transmission
PoPt Print options yes/no
INP Input yes/no
SEt Setpoint yes/no
OPr % Output Power yes/no
Pbd % Proportional Band yes/no
INt Integral Time yes/no
Range and Units (Factory Setting)
(9600)
7O1
7E1
7n2
8n1 (7O1)
(0)
yes/no (no)
(no)
(yes)
(yes)
(yes)
(no)
(no)
Description/
Comments
Baud rate of unit must match connected equipment.
7 data, odd parity, 1
stop (was odd)
7 data, even parity, 1
stop (was even)
7 data, no parity, 2
stop (was none)
8 data, no parity, 1
stop
For multiple unit applications, each unit must have a unique node address.
Selecting yes, the controller does not transmit mnemonics.
Selecting yes allows print options shown below, to be programmed.
Display Parameter
dEr Derivative Time yes/no
AL1 Alarm 1 * yes/no
AL2 Alarm 2 * yes/no
dEv Deviation From
Setpoint *
OFP % Output Power
Offset
r-P Setpoint Ramp Rate yes/no
Crg Relative Gain yes/no
Cdb Deadband yes/no
OSt Output Status yes/no
rSP Remote Setpoint * yes/no
Range and Units
(Factory Setting)
(no)
(no)
(no)
yes/no (no)
yes/no (no)
(no)
(no)
(no)
(no)
(no)
* Model Number Dependent
Description/
Comments
-26-
Page 35
Configure Module 7 - Remote Setpoint Parameters (7-rS or 7-n2)
Controller returns to configuration access point (CnFP NO) if remote
setpoint option is not installed.
Display Parameter
dSP1 Remote setpoint
display scaling point #1
INP1 Remote setpoint
input scaling point #1.
dSP2 Remote setpoint
display scaling point #2
INP2 Remote setpoint
input scaling point #2
FLtr Remote setpoint
filter time constant
bAnd Remote setpoint
filter band
trnF Remote/Local
setpoint transfer options
Range and Units
(Factory Setting)
-999 to 9999 (0) CN63100 (0.0) CN63300
0.00 to 20.00 mA (4.00)
-999 to 9999 (1000) CN63100 (100.0) CN63300
0.00 to 20.00 mA (20.00)
0 to 25 seconds (2)
0to250 (5)
nor - normal Auto - Automatic trAC - Tracking (nor)
Description/
Comments
Remote setpoint display low value.
Key in input low value or Press D to select Signal Input method.
Remote setpoint display high value.
Key in input low value or Press D to select Signal Input method.
0=off
0 = filter always engaged.
Auto = Bumpless, other modes may bump.
Configure Module 8 - Second Linear DC Analog Output (8-A2)
Controller returns to Configuration Access Point (CnFP-NO) if second
linear DC analog option is not installed.
Display Parameter
A2tP Second linear DC
output range
A2LO Second linear DC
output low scaling value
A2Hl Second linear DC
output high scaling value
Range and Units
(Factory Setting)
0to10V 0to20mA 4to20mA (4-20)
-999 to 9999 (0) CN63100 (0.0) CN63300
-999 to 9999 (1000) CN63100 (100.0) CN63300
Description/
Comments
Set Secondary Output jumper to match.
Corresponding temp or process value for low output.
Corresponding temp / process value for high output.
Configure Module 9 - Factory Service Operations (9-FS)
Display Parameter
CodE Factory service
function code.
Range and Units (Factory Setting)
48 - Calibrate instrument
66 - Reset parameters to factory settings
77- (twice in succession) Reset controller calibration to nominal values (Caution: This operation results in up to ±10% reading error.)
Description/
Comments
Refer to Calibration Section for details.
-27-
Page 36
USER PARAMETER VALUE CHART
CONTROLLER NUMBER
MNEMONIC PARAMETER
SP Setpoint
OPOF % Output Power Offset
OP % Output Power
ProP Proportional Band
Intt Integral Time
dErt Derivative Time
AL-1 Alarm 1 Value
AL-2 Alarm 2 Value
CN63100 CONFIGURE INPUT 1-INP
MNEMONIC PARAMETER
tYPE Input Sensor Type
SCAL Temperature Scale Units
dCPt Temperature Resolution
FLtr Digital Filtering
SHFt Input Offset
SPLO Setpoint Lower Limit
SPHI Setpoint Upper Limit
SPrP Setpoint Ramp Rate
InPt User Input
USER SETTING
USER SETTING
CN63300 CONFIGURE INPUT 1-INP
MNEMONIC PARAMETER
tYPE Input Type
dCPt Decimal Point
rnd Rounding Increment
FLtr Digital Filtering
dSP1 Display Value #1
InP1 Signal Input Value #1
dSP2 Display Value #2
InP2 Signal Input Value #2
SPLO Setpoint Lower Limit
SPHI Setpoint Upper Limit
SPrP Setpoint Ramp Rate
InPt User Input
CONFIGURE OUTPUT 2-OP
MNEMONIC PARAMETER
CYCt Cycle Time
OPAC Output Control Action
OPLO Output Power Lower Limit
OPHI Output Power Upper Limit
OPFL Sensor Fail Power Preset
OPdP Output Power Dampening
CHYS ON/OFF Control Hysteresis
tcod Auto-Tune Dampening Code
ANtP Linear Output Range
ANAS Linear Output Source
ANUt Linear Output Update time
ANLO Linear Output Scale Point Low
ANHI Linear Output Scale Point High
USER SETTING
USER SETTING
-28-
Page 37
CONFIGURE LOCKOUTS 3-LC
MNEMONIC PARAMETER
SP Access Setpoint OP Access Output Power dEv Access Deviation Display UdSP Access Display Units CodE Access Code Number PId Access PID Values AL Access Alarm(s) Values ALrS Enable Reset Alarm(s) SPSL Enable Remote/Local Transfer trnF Enable Auto/Man Transfer tUNE Enable Auto-tune
CONFIGURE ALARMS 4-AL
MNEMONIC PARAMETER
Act1 Alarm 1 Action Mode rSt1 Alarm 1 Reset Mode Stb1 Alarm 1 Standby Enabled AL-1 Alarm 1 Value Act2 Alarm 2 Action Mode rSt2 Alarm 2 Reset Mode Stb2 Alarm 2 Standby Enabled AL-2 Alarm 2 Value AHYS Alarm Hysteresis Value
CONFIGURE COOLING 5-O2
MNEMONIC PARAMETER
CYC2 O2 Output Cycle Time GAN2 Relative Cooling Gain db-2 Heat-Cool Overlap/Deadband
USER SETTING
USER SETTING
USER SETTING
CONFIGURE SERIAL COMMUNICATIONS 6-SC
MNEMONIC PARAMETER USER SETTING
bAUd Baud Rate ConF Character Frame Format Addr Controller Address Abrv Abbrev. or Full Transmission PoPt Print Options
INP dEv SEt OFP OPr r_P Pbd Crg Int Cdb dEr OSt AL1 RSP AL2
CONFIGURE REMOTE SETPOINT 7-rS / 7-n2
MNEMONIC PARAMETER
dSP1 Remote Setpoint Display Value #1 INP1 Remote Setpoint Input Value #1 dSP2 Remote Setpoint Display Value #2 INP2 Remote Setpoint Input Value #2 FLtr Remote Setpoint Filter Time Constant bAnd Remote Setpoint Filter Band trnF Local/Remote Transfer Options
USER SETTING
CONFIGURE SECOND LINEAR OUTPUT 8-A2
MNEMONIC PARAMETER
A2tP Second Linear Output Range A2LO Second Linear Output Low Value A2HI Second Linear Output High Value
USER SETTING
-29-
Page 38
CONFIGURATION PARAMETER EXPLANATIONS
Input Parameter Module (1- IN) CN63100 Models
The controller has several input set-up parameters that must be
programmed prior to setting any other controller parameters.
Input Type (tYPE)
Select from the list of various thermocouple and RTD sensors. The following is a list of the possible sensors:
tc-t Type T TC tc-E Type E TC tc-J Type J TC tc-k Type K TC tc-r Type R TC tc-S Type S TC tc-b Type B TC tc-N Type N TC LIN Linear mV display r385 385 curve RTD r392 392 curve RTD rLIN Linear ohms display
Temperature Scale (SCAL)
Select either degrees Fahrenheit (F) or degrees Celsius (C).
If changed, be sure to check all parameters.
Temperature Resolution (dCPt)
Select either 1 or 0.1 degree resolution.
If changed, be sure to check all parameters.
Digital Input Filtering and Display Update Rate (FLtr)
Select the relative degree of input signal filtering and display update rate. The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes. Therefore, the influence on
step response time is minimal. If the signal is varying too greatly due to measurement noise, increase the filter v alue. Additionally, with large derivative times, control action may be too unstable for accurate control. Increase the filter value. Conversely, if the fastest controller response is desired, decrease the f ilter value.
The Auto-tune procedure sets the filter value appropriate to the process characteristics. Also see Output Power Dampening parameter (OPdP), page 35, for filtering the output.
Fltr- 0 to 4
0 = least input filtering 3 = most input filtering 4 = most input filtering and slower (500 msec) display update rate
(outputs update at 100 msec rate)
Input Sensor Correction Constant (SHFt)
If the controller temperature disagrees with a reference temperature instrument or if the temperature sensor has a known calibration, the controller temperature can be compensated by a correction offset (SHFt).
SHFt - -999 to 9999 The following equation expresses the relationship: Desired Display Temp = (Controller Temp) + SHFt
Example 1: The controller reads 293°F while a reference instrument indicates
300°F. A SHFt value of +7°F corrects the controller indication to match the reference.
Setpoint Limit Values (SPLO & SPHI)
The controller has programmable high and low setpoint limit values to
restrict the setting range of the setpoint. Set the limit values so that the temperature setpoint value cannot be set outside the safe operating area of the process.
SPLO - -999 to 9999
SPHI - -999 to 9999
-30-
Page 39
Setpoint Ramp Rate (SPrP)
The setpoint can be programmed to ramp independent of the controller’s display resolution. The setpoint ramp feature can reduce thermal shock to the process, reduce temperature overshoot on start-up or setpoint changes, or ramp the process at a controlled rate.
SPrP - 0.0 to 999.9 degrees/minute
A ramp value of zero disables setpoint ramping, allowing the controller to stabilize as fast as possible to the new setpoint. If the user input is programmed for setpoint ramp, it affects the enabling and disabling of setpoint ramping. Setpoint ramping is initiated on power-up or when the setpoint value is changed. Active setpoint ramping is indicated by the left most decimal point flashing in the main display.
Figure 12, Setpoint Ramp Rate
Once the ramping setpoint reaches the target setpoint, the setpoint ramp rate disengages until the setpoint is changed again. If the ramp value is changed during ramping, the new ramp rate takes effect. If the setpoint is ramping prior to invoking Auto-Tune, the ramping is suspended during Auto-Tune and then resumed afterward using the current temperature as a starting value. Deviation and band alarms are relative to the target setpoint, not the ramping setpoint.
The Remote Setpoint input is also controlled by the setpoint ramp feature. In situations where the remote setpoint must be rate controlled, this parameter can be used to slowly increment (or decrement) the signal to its final value. The target value, not the instantaneous ramp value, is displayed. Setpoint ramp indication is disabled during remote setpoint ramping.
Note: Depending on the thermal characteristics of the process, the process
temperature may not track the programmed setpoint rate.
User Input (InPt)
The user input may be programmed to perform a variety of controller functions. The input must be in its active state for 120 msec minimum to perform the function. A function is performed when the User Input, (Terminal 6) is pulled low to common (Terminal 8).
Note: Do not tie the commons of multiple units to a single switch. Use either a
multiple pole switch for ganged operation or a single switch for each unit.
Note: “Low Level” is switch closed.
“High Level” is switch open.
PLOC - Program Lock. A low level enables the program disable function
which places the unit in the Protected Parameter Mode.
ILOC - Integral Action Lock. A low level disables the integral action of the
PID computation. A high level resumes the integral action.
trnF - Auto/Manual Transfer. A negative transition places the unit in the
manual (user) mode and a positive transition places the unit in the
automatic operating mode. The output is “bumpless” when transferring to
either operating mode. SPrP - Setpoint Ramp. A low level terminates setpoint ramping and the
controller operates at the target setpoint. Terminating setpoint ramping is
the same as setting the ramp rate to zero (SPrP = 0.0). A high level enables
the programmed setpoint ramp rate. ALrS - Alarm Reset. On models with alarms, a low level resets any active
alarm(s) to their inactive state as long as the user input is low. SP2 - Setpoint 1/ Setpoint 2 Select. On models with Second Setpoint, a low
level selects setpoint 2. A high level selects setpoint 1.
SPSL or RSP - Local/Remote Select. On models with Secondary Analog
Input, a negative transition engages Remote Setpoint operation and a positive transition engages Local Setpoint operation. The response of the controller to the setpoint transfer is set by the setpoint transfer parameter “trnF”, under “ 7-rS” or “7-n2” module.
Prnt - Print Request. On models with Serial Communications, a low level
transmits the print option selected in the Serial Communications Module (6-SC). If the user input is held low, after the printing is complete, another request is issued.
-31-
Page 40
Input Parameter Module (1- In) CN63300 models
The controller has several input set-up parameters that must be
programmed prior to setting any other controller parameters.
Input Type (tYPE)
Select the signal input type: Voltage (VOLt), or Current (Curr). The signal
input terminal for voltage is #9 and for current is #10. Common is #8.
Decimal Point Position (dCPt)
Select the desired decimal point position for the scaled display. The selected decimal point position appears in the following parameters; rnd, dSP1, dSP2, SPLO, SPHI, SP, AL1, AL2, db-2, AHYS, and CHYS.
0
0.0
0.00
0.000
Rounding Increment ( rnd)
Rounding values other than “ 1” causes the scaled number to ‘round’ to the nearest rounding increment selected (i.e.. rounding of ‘5’ causes ‘122’ to round to ‘120’ and ‘123’ to round to ‘125’). If the process is inherently jittery, the display value may be rounded to a higher value than “1”. If the range of the process exceeds the required resolution, (ex. 0-1000 PSI, but only 10 PSI resolution required), a rounding increment o f 10 will effectively make the display more stable.
This programming step is usually used in conjunction with programmable digital filtering to help stabilize display readings. (If display stability appears to be a problem and the sacrifice in display resolution is unacceptable, program higher levels of digital filtering or increase the level of process dampening.) Rounding increments of 10, 20, 50, and 100 may also be used to add “dummy zeroes” to the scaled readings, as desired.
1 2 5 10 20 50 100
The rounding increment is for the controller’s display only and does not affect (improve or degrade) the control accuracy of the unit.
Digital Input Filtering and Display Update Rate (FLtr)
Select the relative degree of input signal filtering and display update rate. The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes. Therefore, the influence on step response time is minimal. If the signal is varying too greatly due to measurement noise, increase the filter v alue. Additionally, with large derivative times, control action may be too unstable for accurate control. Increase the filter value. Conversely, if the fastest controller response is desired, decrease the f ilter value.
The Auto-tune procedure sets the filter value appropriate to the process characteristics. See Output Power Dampening parameter (OPdP), page 35, for filtering the output.
Fltr- 0 to 4
0 = least input filtering 3 = most input filtering 4 = most input filtering and slower (2/sec) display update rate
(outputs update at 10/sec rate)
Scaling Points
Prior to installing and operating the controller, it may be necessary to change the scaling to suit the display units particular to the application. Although the unit has been programmed at the factory, the scaling will generally have to be changed.
The controller is unique in that two different scaling methods are available. The two scaling procedures are similar in that the operator keys in the display values and either keys in or applies a signal value that corresponds to those scaling points. The location of the scaling points should be near the process end limits, for the best possible accuracy.
Once these values are programmed (coordinates on a graph), the indicator calculates the slope and intercept of the signal/display graph automatically. No span/zero interaction occurs, making scaling a one-pass exercise.
-32-
Figure 13, Scaling Points
Page 41
Before programming the indicator, it is advised to organize all the data for
the programming steps to avoid possible confusion.
To scale the indicator, two signal values and two display values that correspond to the signal values must be known. These four values are used to complete the scaling operation. An example is listed below:
Scaling Point #1 Scaling Point #2
0.0% @ 4.00 mA & 100.0% @ 20.00 mA
Reverse acting indication can be accomplished by either reversing the two signal points or the display value points, but not both. If both are reversed, then forward (normal) acting indication will occur. In either case, do not reverse the input wires to correct the action.
Display Values (dSP1 & dSP2)
Key-in the display value for scaling point one and scaling point two.
dSP1 -999 to 9999 (Ex. 0.0%) dSP2 -999 to 9999 (Ex. 100.0%)
Signal Input Values (INP1 & INP2)
The signal input value can either be keyed in via the front panel buttons or an input signal can be applied to the appropriate signal input terminals. When entering the signal input parameter, the unit is in the key-in mode.
Key-in Method
Key-in the signal value for scaling point one and scaling point two.
INP1 -999 to 9999 (Ex. 0.00 VDC or 4.00 mA DC) INP2 -999 to 9999 (Ex. 10.00 VDC or 20.00 mA DC)
Signal Input Method
To change to the apply signal method press the D button. Front panel annunciators %P and DV will flash, and the display indicates the signal value applied to the input terminals. The unit can be toggled to the key-in method by pressing the D button again.
Signal Range Display Range
4.00 to 20.0 mA DC 0.00 to 20.00
0.00 to 10.00 VDC 0.00 to 10.00
When the desired value is indicated on the display, press the P button to store the value and advance to the next parameter.
Setpoint Limit Values (SPLO & SPHI)
The controller has programmable high and low setpoint limit values to restrict the setting range of the setpoint. Set the limit values so that the setpoint value cannot be set outside the safe operating area of the process. On models equipped with Second Analog Input, configured as a Remote Setpoint, the Remote Setpoint reading is also restricted to these limits.
SPLO - -999 to 9999
SPHI - -999 to 9999
Setpoint Ramp Rate (SPrP)
The setpoint can be programmed to ramp independent of the controller’s decimal point position and rounding increment. The setpoint ramp rate can reduce sudden shock to the process, reduce overshoot on start-up or setpoint changes, or ramp the process at a controlled rate.
SPrP - 1 to 9999 units/minute
Note: Defined here, a unit is the LSD of the display, regardless of decimal point
position.
A ramp value of zero disables setpoint ramping. If the optional user input is programmed for setpoint ramp, it affects the enabling and disabling of setpoint ramping. Setpoint ramping is initiated on power-up or when the setpoint value is changed. Active Setpoint Ramping is indicated by the left most decimal point flashing in the main display.
Figure 14, Setpoint Ramp Rate
-33-
Page 42
Once the ramping setpoint reaches the target setpoint, the setpoint ramp rate disengages until the setpoint is changed again. If the ramp value is changed during ramping, the new ramp rate takes effect. If the setpoint is ramping prior to invoking Auto-Tune, the ramping is suspended during Auto-Tune and then resumed afterward using the current display as a starting value. Deviation and band alarms are relative to the target setpoint, not the ramping setpoint.
The Remote Setpoint input is also controlled by the setpoint ramp feature. In situations where the remote setpoint must be rate controlled, this parameter can be used to slowly increment (or decrement) the signal to its final value. The target value, not the instantaneous ramp value, is displayed. Setpoint ramp indication is disabled during remote setpoint ramping.
Note: Depending on the ramp rate relative to the process dynamics, the actual
scaled process value may not track the ramping setpoint value.
User Input (InPt)
The user input may be programmed to perform a variety of controller functions. The input must be in its active state for 120 msec minimum to perform the function. A function is performed when the User Input, (Terminal 6) is pulled low to common (Terminal 8).
Note: Do not tie the commons of multiple units to a single switch. Use either a
multiple pole switch for ganged operation or a single switch for each unit.
Note: “Low Level” is switch closed.
“High Level” is switch open.
PLOC - Program Lock. A low level enables the program disable function
which places the unit in the Protected Parameter Mode.
ILOC - Integral Action Lock. A low level disables the integral action of the
PID computation. A high level resumes the integral action.
trnF - Auto/Manual Transfer. A negative transition places the unit in the
manual (user) mode and a positive transition places the unit in the
automatic operating mode. The output is “bumpless” when transferring to
either operating mode. SPrP - Setpoint Ramp. A low level terminates setpoint ramping and the
controller operates at the target setpoint. Terminating setpoint ramping is
the same as setting the ramp rate to zero (SPrP = 0.0). A high level enables
the programmed setpoint ramp rate.
ALrS - Alarm Reset. On models with alarms, a low level resets any active
alarm(s) to their inactive state as long as the user input is low.
SP2 - Setpoint 1/ Setpoint 2 Select. On models with Second Setpoint, a low
level selects setpoint 2. A high level selects setpoint 1.
SPSL or RSP - Local/Remote Select. On models with Secondary Analog
Input, a negative transition engages Remote Setpoint operation and a positive transition engages Local Setpoint operation. The response of the controller to the setpoint transfer is set by the setpoint transfer parameter “trnF”, under “ 7-n2” module.
PrNt - Print Request. On models with Serial Communications, a low level
transmits the print option selected in the Serial Communications Module (6-SC). If the user input is held low, after the printing is complete, another request is issued.
-34-
Page 43
Output Parameter Module (2-OP)
The controller has parameters that affect how the main control output (O1) and Main Linear DC output control signal responds to temperature changes and sensor failures.
Time Proportioning Cycle Time (CYCt)
The selection of cycle time depends on the time constant of the process and the type of output used.
CYCt - 0 to 250 seconds
For best control, a cycle time equal to 1/10 of the process time constant, or less is recommended; longer cycle times could degrade temperature control, and shorter cycle times provide little benefit at the expense of shortened relay life. When using a Logic/SSR drive output with the SSR Power Unit, a relatively short cycle time may be selected.
A setting of zero keeps the main control output and front panel indicator off. This is useful if using the linear DC output signal for control. On some models, output (O1) can be configured as an alarm output ACt1 under Module “4-AL”.
Output Control Action (OPAC)
For heat and cool applications, the main output (O1) is normally used for heating (reverse acting) and the optional cooling output (O2) is normally used for cooling (direct acting).
OPAC - rEv (Reverse acting)
drct (Direct acting)
If O2 (cooling) is not used, then the action can be reverse or direct acting. When used for control output, the Main Linear DC output operation is affected by this parameter.
Output Power Limits (OPLO & OPHI)
Enter the safe output power limits for the process. These parameters may also be used to limit the minimum and maximum controller power due to process disturbances or setpoint changes, to reduce overshoots b y limiting the process approach level.
OPLO & OPHI - 0 to 100%
If the cooling output is selected, the limits range from:
OPLO & OPHI - -100 to 100%
With Alarm 2 selected for cooling, the Lower Limit can be set to less than 0% to limit maximum cooling or set to greater than 0% to limit minimum heating. Set the High Limit to less than 0% to limit minimum cooling or greater than 0% to limit maximum heating. When controlling power in the manual control mode, the output power limits do not take effect.
Sensor Fail Power Level (OPFL) CN63100 only
If a failed sensor is detected, the control output(s) default to a preset power output.
OPFL - 0% (O1 output full “off”) to 100% (O1 output full “on”)
If Alarm 2 is selected for cooling , the range is extended from:
OPFL - -100% to +100%
At 0% both outputs are off, at 100% O1 is on and O2 is off, and at -100% O2 is on and O1 is off. The alarm outputs are up-scale drive (+9999) with an open sensor, and down-scale drive (-9 999) with a shorted sensor (RTD only), independent of this setting. Manual Control overrides OPFL.
Output Power Dampening Filtering Time (OPdP)
The output power calculated by the PID controller can be dampened (filtered) to reduce the controller output activity. Those processes with high gain and/or derivative times, or those processes with a relatively high noise content, can benefit f rom the dampening action.
OPdP - 0 to 250 seconds
The dampening parameter is expressed as a time constant in seconds. Increasing the value increases the dampening or filtering effect. A value of zero disables output power dampening. The amount of dampening to be used depends primarily on the response time of the process and the amount of final actuator activity desired. Generally, dampening times in the range of 1/20 to 1/50 of the controller’s integral time (or process time constant) prove to be effective. Dampening times longer than these may cause controller instability due to the added lag effect of too much filtering.
In the case where a relatively high dampening time is desired, the controller’s proportional band may be increased to restore an adequate stability margin. The Auto-tune procedure of the controller sets the dampening value appropriate to the characteristics of the process.
-35-
Page 44
ON/OFF Control Hysteresis (CHYS)
The controller can be placed in the ON/OFF control mode by setting the proportional band to 0.0%. The control hysteresis value affects only the control outputs. Alarms have a separate hysteresis setting. See ON/OFF Control, page 47, for more details.
CHYS - 1 to 250
The h ysteresis band should be set to a minimum value to eliminate output chatter at the setpoint. Generally, 2 to 5 is sufficient for this purpose. Set the hysteresis band to factory setting prior to invoking Auto-Tune. After Auto-Tune, the hysteresis band has no effect on PID Control.
Auto-Tune Code (tcod)
Prior to invoking Auto-Tune, the Auto-Tune code should be set to achieve the desired dampening level under PID Control. After Auto-Tune is complete, changes to “tcod” parameter have no effect until Auto-Tune is restarted. When set to 0, this yields the fastest process response with possible overshoot. A setting of 2 yields the slowest response with the least amount of overshoot. Dampening codes of 0 or 1 are recommended for most thermal processes.
Main Linear DC Output Range (ANtP) (Optional)
Select the type of output range:
0-10 = 0 to 10 V 0-20 = 0 to 20 mA 4-20 = 4 to 20 mA
The linear DC output range jumper must be set to match the range selected. See Linear DC Output Jumper Selection, page 11. The linear DC output can be re-calibrated to provide up to 5% of over range operation. See Main or Second Linear DC Analog Output Calibration, page 69.
Main Linear DC Output Source (ANAS) (Optional)
The output can be programmed to transmit one of the below variables:
OP - Output Power % control INP - Temperature retransmission SP - Setpoint (local or remote) retransmission
For Linear DC Output control, the main output (O1) can be disabled by setting the Cycle Time (CYCt) to 0 in Output Parameter 2-OP or configuring it as an alarm in Alarm 1 Action (ACt1) in Alarm Parameter 4-AL. For heat/cool with 4 to 20 mA control applications, the heat (0 to 100%) will be 12 to 20 mA and the cool (-100 to 0%) will be 4 to 12 mA. Notice that 0% (no heat or cool) is 12 mA.
Main Linear DC Update Time (ANUt) (Optional)
To reduce excess valve actuator, or pen recorder activity, the update time of the linear output can be set over the range of 0.1 to 250 seconds. A value of 0 seconds results in an update time of 0.1 second.
Main Linear DC Output Scaling Points (ANLO, ANHl) (Optional)
The output is scaled based on the Output Source (ANAS) display by use of low and high scaling parameters. Reverse acting output is possible by reversing the scaling points.
Figure 15, Auto-Tune Code
ANLO Display value that corresponds to 0 V, 0 mA, or 4 mA as
selected.
ANHI Display value that corresponds to 10 V or 20 mA as
selected.
-36-
Page 45
Lockouts Parameter Module (3-LC)
The controller can be programmed to limit operator access to various parameters, control modes, and display contents. The configuration of the lockouts is grouped into three sections: Lower Display Lockouts, Protected Mode Lockouts and Hidden Mode Lockouts.
Lower Display Lockouts (SP, OP, dEv, UdSP and bdSP)
The contents of the secondary display can be changed in the Normal Display Mode by successively pressing the D button. This action scrolls through the possible display parameters, when enabled. If all parameters are settolock“LOC”,pressDtoblankthedisplay.
The parameters can be set for one of the following:
LOC (Lockout) – Prevents the parameter from appearing in the
rEd (Read only) – Parameter appears, but cannot be modified. Ent (Entry) – Parameter appears and can be modified.
The lower display content possibilities are:
SP – Setpoint Value OP – % Output Power dEv – Setpoint Deviation UdSP – Temperature Units (CN63100) bdSP – Blank Display (CN63300)
Note: If a parameter is active in the lower display and is then subsequently
locked out, press “D” once in the Normal Display Mode to removeit from the
display.
Protected Mode Lockouts (CodE, PId, and AL)
The protected mode is active when program disable is active. The parametersin the protected mode can be set for one of the following modes:
LOC (Lockout) – Prevents the parameter from appearing in the
rEd (Read only) – Parameter appears, but cannot be modified. Ent (Entry) – Parameter appears and can be modified.
secondary display.
*
protected mode.
The code number allows access to the unprotected mode. To enter the unprotected mode from the protected mode, the code number entered must match the code number entered here. See Front Panel Program Disable, page 16, for a description of the various program access levels.
CodE – 0 to 250 PId – Permits access to the main PID parameters. AL – Permits access to the alarm value(s).
Hidden Mode Lockouts (ALrS, SPSL, trnF, and tUNE )
The hidden mode is accessible f rom the Normal Display Mode by pressing and holding the P button for three seconds. The parameters can be set for:
LOC (Lockout) – Prevents the parameter from appearing in the
ENbL (Enable) – Allows operator to perform the selected hidden
hidden mode.
mode function.
The functions available in the hidden mode are accessible independent of the status of program disable.
ALrS – Reset (override) the alarm output(s). SPSL – SP1/SP2/Remote setpoint selection. trnF – Select Automatic or Manual operation. tUNE – Invoke or cancel Auto-Tune.
**
** Model Number Dependent.
-37-
Page 46
Alarm Parameter Module (4-AL) (Optional)
The controller may be equipped with one or two optional alarms. On some models alarm output #1 is the same output as main control O1. In this case, the output is either programmed f or the main output control function (O1) or as an alarm function (A1). This is set by alarm #1 action parameter (Act1).
If heat is selected, the remaining Alarm 1 parameters do not appear.
To enable the cooling output of the controller, select CooL for Alarm 2 action (Act2). The controller then utilizes the alarm 2 output as the cooling output (O2). Front panel annunciator A2 illuminates whenever the cooling output is on. See Cooling Output Module (5-O2), page 42, for configuration of the cooling output.
If cooling is selected, the remaining Alarm 2 parameters do not appear.
Alarm Action (Act1, Act2)
Note: When deviation low-acting with positive alarm value (d-LO), deviation
high-acting with negative value (d-HI), or Band inside-acting (b-IN) is
selected for the alarm action, theindicator is “OFF” whenthe alarm output
is “ON”.
Caution: Inapplications where equipmentor material damage,or risk
to personnel due to controller malfunction could occur, an independent and redundant temperature limit indicator with alarm outputs is strongly recommended. The indicators should have input sensors and AC power feeds independent from theother equipment.
The configuration options of the alarm output are model dependent.
(Act1) - Alarm #1 (Act2) Alarm #2 A-HI Absolute High Acting A-HI Absolute High Acting A-LO Absolute Low Acting A-LO Absolute Low Acting d-HI Deviation High Acting d-HI Deviation High Acting d-LO Deviation Low Acting d-LO Deviation Low Acting b-In Band Inside Acting b-In Band Inside Acting b-Ot Band Outside Acting b-Ot Band Outside Acting Heat * Assigns output 01/A1
as control output
* Model Number Dependent. Note: Deviation and band type alarms track both local and remote setpoint.
CooL * Assigns 02/A2 as cooling
or second output
-38-
Page 47
Alarm Action Figures
The alarm action figures describe the status of the alarm output and the front panel indicator for various over/under temperature conditions. The alarm output wave form is shown with the output in the automatic reset mode.
Note: Select the alarm action with care. In some configurations, the front panel
indicator (LED) might be “OFF” while the output is “ON”.
-39-
Page 48
-40-
Page 49
Alarm Reset (rSt1, rSt2)
Each alarm reset action may be independently configured.
LAtC - Latched Auto - Automatic
Latched alarms require operator action to reset the alarm condition. The front panel buttons can be used to reset an alarm when the controller is in the Hidden Function Mode (See page 19). An alarm condition may also be reset via the user input.
Automatic reset alarms are reset by the controller when the alarm condition clears. Figure 16, Alarm Reset Sequence, depicts the reset actions.
Figure 16, Alarm Reset Sequence
Alarm Standby Delay (Stb1, Stb2)
The alarm(s) may be independently configured to exhibit a power-on, standby delay which suppresses the alarm output from turning “ ON” until the temperature first stabilizes outside the alarm region. After this condition is satisfied, the alarm standby delay is canceled and the alarm triggers normally, until the next controller power-on. This feature also works for deviation and band alarms when the setpoint is changed via keypad. This action suppresses “nuisance” alarms. Figure 17, Alarm Standby Delay Sequence, depicts a typical operation sequence.
Figure 17, Alarm Standby Delay Sequence
Alarm Value (AL-1, AL-2)
The alarm values are either absolute (absolute alarms) or relative to the setpoint value (deviation and band alarms). An absolute alarm value is the value that is entered. A relative alarm value is offset from the temperature setpoint value by the amount entered and tracks the setpoint value as it is changed.
AL-1 and AL-2 - -999 to 9999
If the alarm action is set as a Band Alarm, then only a positive value can be entered.
Alarm Hysteresis (AHYS)
The alarm value(s) have a programmable hysteresis band to prevent alarm output chatter near the alarm trigger point. The hysteresis value should be set to eliminate this effect. A value of 2 to 5 is usually sufficient for most applications. A single alarm hysteresis value applies to both alarms. See the Alarm Action Figures, page 39, for the effect of hysteresis on the various alarm types.
AHYS - 1 to 250
-41-
Page 50
Cooling Parameters Module (5-02) (Optional)
The cooling output (O2) is software selectable with dual alarm models (For the CN63300, this is referred to as the Second Control Output). This output operates as an independent cooling output for systems that use heating and cooling. To enter the Cooling Output Module, the cooling output of the controller must first be selected in Alarm Module (4-AL). When cooling is selected, alarm 2 is used for the cooling output.
The front panel indicator A2 illuminates when the cooling output (O2) is on. Cooling output power is defined as ranging from -100% (full cooling) to 0% (no cooling, unless a heat-cool band overlap is used). See Output Power Limits in Module 2 for maximum and minimum settings. The same PID values control both heat and cool.
Cooling Output Cycle Time (CYC2)
A value of 0 turns off the cooling output, independent of cooling power demand.
CYC2 - 0 to 250 seconds
Cooling Relative Gain (GAn2)
This parameter defines the gain of the cooling band relative to the heating band. A value of 0.0 places the cooling output into ON/OFF Control mode with the ON/OFF Control Hysteresis (CHYS) in Output Parameter Module (2-OP) becoming the cooling output hysteresis. This may be done independent of the main output control mode (PID or ON/OFF). Relative gain is generally set to balance the effects of cooling to that of heating for best control. Figures 18, 19, & 20, Heat/Cool Operation, illustrate the effect of different gains.
GAN2 - 0.0 to 10.0
Heat and Cool Overlap/Deadband (db-2)
This parameter defines the area in which both heating and cooling are active (negative value) or the deadband area between the bands (positive value). The parameter units are degrees or tenth’s o f degrees (depending on system resolution). If a heat/cool overlap is specified, the displayed percent output power is the sum of the heat power (O1) and the cool power (O2).
db-2 - -999 to 9999
When the Cooling Relative Gain is set to zero for ON/OFF Control mode, this parameter should only be set to a positive value or zero. The Heat/Cool Operation Figures illustrate the effects of different deadbands.
Figure 18, Heat/Cool Operation (db=0)
Figure 19, Heat/Cool Operation (db>0)
When using the cooling output, observe the controlled temperature characteristics. If the temperature remains above setpoint with a sluggish return, increase the cooling gain. Similarly, if the temperature drops too
-42-
Page 51
sharply with an overall saw-tooth pattern, decrease the cooling gain. Alter the heat-cool overlap until a smooth response in the controlled temperature is observed during band transition.
Figure 20, Heat/Cool Operation (db<0)
Serial Communications Module (6-SC) (Optional)
Unless controller serial configurations match those of the host communicating device, front panel serial parameter changing is needed for communication. Baud rate and character frame must be the same as the other communicating device. The controller address is the unique node address for multiple controllers applications. (See Serial Communications Interface, page 57, for further explanations.)
Baud Rate (bAUd)
The available baud rates are:
300, 600, 1200, 2400, 4800, or 9600
Character Frame Format (ConF)
The character frame can be 7O1, 7E1, 7n2, or 8n1..
Controller Address Number (Addr)
Multiple controllers connected on the same RS485 interface line must each have a different address number. A value of 0 does not require the address specifier command, when communicating with the controller. The address numbers range from 0 to 99.
Abbreviated or Full Transmission (Abrv)
When transmitting data, the controller can be programmed to suppress the address number, mnemonics, units, and some spaces by selecting YES. An example o f abbreviated and full transmission are shown below:
NO - 6 SET 123.8F<CR> <LF> Full Transmission YES - 123.8<CR> <LF> Abbreviated Transmission
Print Options (PoPt)
Selecting YES for the print options allows the operator to scroll through the available options using the P button. The up and down arrow keys toggle between “yes” and “no”. “yes” enables the option to b e printed when a print function occurs.
INP - Print Input Process Value SEt - Print Setpoint Value OPr - Print % Output Power Value Pbd - Print % Proportional Band Value INt - Print Integral Time Value dEr - Print Derivative Time Value AL1 - Print Alarm 1 Value AL2 - Print Alarm 2 Value dEv - Print Deviation From Setpoint Value OFP - Print % Output Power Offset Value r_P - Print Ramp Rate Crg - Print Relative Gain Value Cdb - Print Deadband Value OSt - Print Output Status rSP - Print Remote Setpoint Reading
-43-
Page 52
Remote Setpoint Parameters Module (7-n2 or 7-rS) (Optional)
Configuration of the Remote Setpoint involves scaling the input to the desired setpoint range, selecting filter characteristics, and setting remote/local setpoint transfer response.
Remote Setpoint Display Values (dSP1 and dSP2)
Key-in the display value for Scaling Point 1 and Scaling Point 2.
dSP1 -999 to 9999 (Ex. 0) dSP2 -999 to 9999 (Ex. 500)
Remote Setpoint Signal Input Values (INP1 and INP2)
The signal input value can either be keyed-in via the front panel buttons or an input signal can be applied to the appropriate signal input terminals. Initially, the unit is in the key-in method.
Key-in Method
Key-in the display value for Scaling Point 1 and Scaling Point 2.
INP1 0.00 to 20.00 (Ex. 4.00 mA DC) INP2 0.00 to 20.00 (Ex. 20.00 mA DC)
Signal Input Method
To change to the apply signal input method, press the D button while InP1 or InP2 is displayed. Front panel annunciators %P and DV flash and the display indicates the signal value applied to the input terminals. The controller can be toggled to the key-in method by pressing the D button again. In this case, the previously accepted value is recalled.
When the desired value is indicated on the display, press the P button to store the value and advance to the next parameter.
Remote Setpoint Filtering (Fltr and bANd)
The remote setpoint signals can be filtered with a time constraint from 1 to 25 seconds; or the filter can be disabled. The filter is an adaptive, first-order, low p ass type. As long as the difference between the current reading and the previous reading is less than the filter band value (band), the filter remains in effect. When the difference exceeds the filter band, the filter disengages until the difference is less than the filter band value. This action allows quick filter response to large setpoint changes, while retaining filtering action under normal process conditions.
Normally the filter band value is set slightly larger than the noise level of the remote input. The time constant of the filter is set consistent with the amount of filtering desired. Increased filter time constant values are effective for smoothing remote setpoint readings. This may be beneficial for cascade operation and other “live” signal applications.
Alternatively, the remote setpoint can be ramped at a controlled velocity to limit controller response to large setpoint changes.
Remote/Local Setpoint Transfer Options (trnF)
When switching between Local or Remote Setpoint, the response of the controller can be programmed in a variety of ways.
These responses apply to changes in setpoint mode from the controller’s front panel and User Input. The table summarizes the responses for Setpoint transfer operations:
SPtr Parameter Local to Remote Remote to Local
nor – Output may bump. Output may bump
Auto – No output bump. Process
error eliminated at rate of integral action
trAC – Output may bump. Local setpoint assumes
No output bump. Process error eliminated at rate of integral action
value of Remote setpoint (tracks). No Output bump.
Note: In situations where an output bump may occur,the setpoint ramp function
(SPrP) can be used to reduce or eliminate bumping when switching between
setpoints.
-44-
Page 53
Second Linear DC Analog Output Module (8-A2) (Optional)
The Second Linear DC Analog Output provides retransmission of the
conditioned and scaled input signal independent of the Main Linear DC Output.
Second Linear DC Output Range (A2tP)
Select the type of output range:
0-10 = 0 to 10 V 0-20 = 0 to 20 mA 0-40 = 4 to 20 mA
The linear DC output range jumper must be set to match the range selected. See Linear DC Output Jumper Selection, page 11. The linear DC output can be re-calibrated to provide up to 5% of over range operation. See Linear DC Output Calibration, page 69, for more details.
Second Linear DC Output Scaling Points (A2LO, A2Hl)
The output can be scaled based on the controller’s input display by use of low and high scaling parameters. Reverse acting output is possible by reversing the scaling points.
Factory Service Operations Module (9-FS)
The Factory Service Operations include: controller calibration, and reset programming to factory configuration setting. Access to each operation is protected by an access code number. Entering code 66 restores all parameters to factory settings, the unit indicates the operation after the P button is pressed, by displaying “rSEt” in the lower display momentarily.
Caution: Entering code 77,twice in succession, erases the controller calibration
values and defaults the values to nominal settings. Reading errors of
may result. Do not perform this operation unless the controller has lost
calibration. Loss of calibration is signaled by an “E-CL” error flag at
power-up. To clear this flag, perform calibration procedure as noted in
Factory Service Operations - Calibration (9-FS), page 68. Alternatively,
“stepping” through one of the calibration procedures clears the error flag,
but does NOT validate the calibration accuracy in any manner.
10%
-45-
Page 54
MANUAL CONTROL
The controller can be transferred between Automatic Control (closed loop; On/Off or PID control) and Manual Control (open loop; where the control does not work from the setpoint or process feedback.)
Manual operation provides percentage of control of the main output (per the direct or reverse action configured in Output Parameter 2-OP OPAC) from 0 to +100% power. When A2 is configured for cooling (O2), Manual operation still provides 0 to 100% power to the main (O1) output and provides percentage of control to cooling (O2) output from -100% to 0% power. (Negative percent power is positive cooling (O2) percent power.)
To allow front panel switching between control modes, the Transfer Parameter (trnF) must be enabled (Enbl) in Lockout Module (3-LC). The user can then select Manual Control from the Hidden Function Mode using Transfer Parameter (trnF). The percen t output power is then adjusted with the Up and Down arrow buttons in the Normal Display Mode with the %P and MN annunciators illuminated.
In Time Proportional output control (relay, or logic) the percent output power is converted into output on time using Time Proportioning Cycle Time (CYCt) value in Output Parameter Module (2-OP). For example with 4 cycle time and 75% power, the output will be on (4 x.75) for 3 seconds and off for 1 second.
In Linear DC output control (0-10 VDC or 0/4-20 mA), the percent output power is converted into a linear value per the Linear output low scaling value (AnLO) and Linear output high scaling value (AnHI) in Output Parameter Module (2-OP). For example with 0 VDC (scaled 0.0%) to 10 VDC (scaled 100%) and 75% power, the linear DC output will be 7.5 VDC.
When transferring the controller mode from or to Automatic Control, the controlling outputs remain constant, exercising true “bumpless” transfer. When transferring from Manual to Automatic, the power initially remains steady but integral actions corrects (if necessary) the closed loop power demand at a rate proportional to the Integral Time. The low (OPLO) and high (OPHI) output power limits in Output Parameter (2-OP) are ignored when the controller is in Manual Control.
-46-
Page 55
ON/OFF CONTROL
Single Output
The controller operates in ON/OFF Control when the Proportional Band is set to 0.0%. In this control, the process will constantly oscillate about the setpoint value. The amount of ON/OFF Control Hysteresis (CHYS) in Output Parameter Module (2-OP), together with the process characteristics determines the period and amplitude of the oscillations. Larger values of hysteresis increase both the amplitude and period of oscillations but also reduce the number of output switching cycles.
The Control Action (OPAC) in Output Parameter Module (2-OP) can be set to reverse (rEv) for heating (output on when below the setpoint) or direct (drct) for cooling (output on when above the setpoint) applications.
In controllers with operating system software revision earlier than V4.x, the ON/OFF Control Hysteresis value is not balanced around the setpoint value. In these controllers, the Hysteresis is totally added to the setpoint in reverse action and totally subtracted from the setpoint in direct action. The revision number of the controller’s operating system software is shown in the secondary (bottom) display during controller power up.
Figure 21, Output 1 (O1) ON/OFF Control
Software Revision V4.0 or Later
-47-
Figure 22, Output 1 (O1) ON/OFF Control
Software Revision V3.x or Earlier
Page 56
Dual Output
For heat and cool systems, the heat (O1) and cool (O2) outputs can be used together in the ON/OFF control. For this operation, set the Cooling Relative Gain (GAN2) in Cooling ParameterModule (5-02) to 0.0. This places O2 into ON/OFF Control. In this mode, the ON/OFF Control Hysteresis (CHYS) in Output Parameter Module (2-OP) applies to both O1 and O2. The Heat/Cool Deadband (db-2) in Cooling Parameter Module (5-02) sets the amount of operational deadband or overlap between the outputs.
For these applications, the Control Action (OPAC) in Output Parameter Module (2-OP) is normally set to reverse (rEv). This sets O1 into reverse (heat) with O2 always in direct (cool). Cooling output for the CN63300 is referred to as the second control output.
In controllers with operating system software revision lower than 4.0, the ON/OFF Control Hysteresis value is not balanced. In these controllers, the Hysteresis is totally added or subtracted from the setpoint. The revision number of the controller’s operating system software is shown in the secondary (bottom) display during controller power up.
Figure 23, O1/O2 ON/OFF Control
Software Revision V4.0 or Later
Figure 24, O1/O2 ON/OFF Control Software Revisions V3.x or Earlier
-48-
Page 57
Figure 25, O1/O2 ON/OFF Control
Software Revision V4.0 or Later
Figure 26, O1/O2 ON/OFF Control Software Revisions V3.x or Earlier
-49-
Page 58
AUTO-TUNE FOR PID CONTROL
Auto-Tune is a user initiated function in which the controller automatically determines the PID settings based upon the process characteristics. During Auto-Tune, the controller temporarily causes the system to oscillate by cycling the output power from 0 to 100%. The nature of these oscillations determines the settings of the controller’s parameters.
Auto-Tune Code. A code setting of zero gives the fastest response with possible overshoot, and a code of two gives the slowest response with minimum overshoot.
Figure 27, Auto-Tune Code
Note: If the induced oscillations caused by Auto-Tune can cause system
problems or are otherwise unacceptable, the Manual Tuning Procedure can
be used as a tuning alternative.
Prior to initiating Auto-Tune, it is essential that the controller be configured to the application. In particular, Control Hysteresis (CHYS) and Auto-Tune code (tcod) must be set in the Output Parameters section. Auto-Tune requires the hysteresis setting to be above the process noise floor; generally, 2 - 5 degrees or 1-2% of range is adequate. For most applications, the control hysteresis should be set at 2 (factory setting). The Auto-Tune code may be set to yield the response characteristics shown in Figure 27,
Figure 28, Auto-Tune Operation
The following controller parameters are automatically adjusted by
Auto-Tune according to the characteristics of the process:
Proportional Band (ProP) Integral Time (Intt) Derivative Time (dErt) Input Filter (Fltr) Output Power Dampening (OPdP)
As shown in Auto-Tune Operation, Figure 28, Auto-Tune Operation cycles the process at a control point 3/4 of the distance between the current process value (at the instant Auto-Tune is started) and the setpoint. The 3/4 control
-50-
Page 59
point was selected to reduce the chance of overshoot at setpoint when Auto-Tuning at start-up. If Auto-Tuning from setpoint and overshoot is unacceptable, temporarily lower the setpoint by an amount of the oscillation and then Auto-Tune. Reset the setpoint to the original value when Auto-Tune is complete. After starting Auto-Tune, the secondary display indicates the current phase (Aut1, Aut2, Aut3, & Aut4). If the controller remains in an Auto-Tune phase unusually long, the process or connections may be faulty. Additionally, during Auto-Tune it is important that disturbances to the system be minimized, as these may have an effect on the parameter determination.
Initiate Auto-Tune
Auto-Tune may be initiated at start-up, from setpoint, or at any other
process point.
To Initiate Auto-Tune:
1. Make sure that Auto-Tuning is enabled in Lockouts Parameter Module (3-LC).
2. Place the controller into the Normal Display Mode.
3. Press P for 3 seconds from Normal Display Mode.
4. Scroll to “tUNE” b y use of P, if necessary.
5. Select “YES” and press P.
Auto-Tune is initiated.
To Cancel Auto-Tune: (Old PID settings remain in effect). A) Make sure that Auto-Tuning is enabled in parameter lockouts module.
1. Place the controller into the normal display mode.
2. Press P for 3 seconds from normal display mode.
3. Scroll to “tUNE” b y use of P, if necessary.
4. Select “NO” and p ress P.
5. Auto-Tune canceled.
B) Or reset the controller by disconnecting power.
Auto-Tune Of Heat/Cool Systems
During Auto-Tune of heat/cool systems, the controller switches the cooling output (O2) on and off in addition to the heat output (O1). The heat/cool overlap deadband parameter (db-2) determines the amount of overlap or deadband between the two outputs during Auto-Tune. For most applications, set this parameter to 0.0 prior to starting Auto-Tune. After the completion of Auto-Tune, this parameter may need to be reset.
It is important that external load disturbances be minimized, and if present, other zone controllers idled as these may have an effect on the PID constant determination. The controller additionally sets the Cooling Relative Gain parameter (GAN2) for heat/cool systems.
Some water cooled processes exhibit an extreme non-linear gain characteristic. That is, the process cooling gain starts very high and flattens out deeper into the cooling region. This ef fect may result in regular oscillations at setpoint as the controller applies heat to counteract the effect. These processes may benefit from a lower cooling fan setting and/or reduced water flow in the jacket or manifold. The process heat and cool gains should be balanced as much as possible, and the controller gains adjusted to the process.
Auto-Tune Of Cascade Control
The following procedure may be used to tune cascaded controllers:
1. Place the Secondary controller into Local Setpoint mode and Manual
(USEr) mode of operation
2. Adjust output power level of the secondary until primary variable is close
to primary setpoint (5% of range).
3. Key-in secondary setpoint value equal to secondary process value.
4. Auto-Tune the secondary controller while in Local Setpoint mode.
5. Place the secondary controller into Remote Setpoint mode and Automatic
(Auto) mode of operation.
6. Auto-Tune the primary controller while the primary is in Automatic mode
of operation.
7. Initial tuning of system is complete.
After the process has stabilized, the primary and secondary may be
re-tuned in Automatic mode of operation. Normally, the primary requires
re-tuning whenever the secondary PID constants are changed.
Note: For Remote Setpoint controllers, the Auto-Tune control point is derived
from the Remote Setpoint when in Remote Setpoint mode and from the Local
Setpoint when in Local Setpoint mode.
-51-
Page 60
PID CONTROL EXPLANATIONS
Proportional Band
Proportional band is defined as the “band” (range) the process changes to cause the percent output power to change from 0% to 100%. The band may or may not be centered about the setpoint value depending upon the steady state requirements of the process. The band is shifted by manual offset or integral action (automatic reset) to maintain zero error. Proportional band is expressed as percent of input sensor range.
For CN63100, the ranges are fixed for the thermocouple and RTD types.
For CN63300, the range is set by the difference between “dSP2 and dSP1”.
Figure 29, Proportional Band
Example: Thermocouple type T with a temperature range of 600°C is used
and is indicated in degrees Celsius with a proportional band of 5%. This
yields a band of 600°C X 5% = 30°C.
The proportional band should be set to obtain the best response to a disturbance while minimizing overshoot. Low proportional band settings (high gain) result in quick controller response at expense of stability and increased overshoot. Settings that are excessively low produce continuous oscillations at setpoint. High proportional band settings (low gain) result in a sluggish response with long periods of process “droop”. A proportional band of 0.0% forces the controller into ON/OFF control mode with its characteristic cycling at setpoint (See ON/OFF Control, page 47, for more information).
Integral Time
Integral time is defined as the time, in seconds, in which the output due to integral action alone equals the output due to proportional action with a constant process error. As long as a constant error exists, integral action repeats the proportional action each integral time. Integral action shifts the center point position of the proportional band to eliminate error in the steady state. The units of integral time are seconds per repeat.
Integral action (also known as “automatic reset”) changes the output power to bring the process to setpoint. Integral times that are too fast (small times) do not allow the process to respond to the new output value. This causes over-compensation and leads to an unstable process with excessive overshoot. Integral times that are too slow (large times) cause a slow response to steady state errors. Integral action may be disabled by setting the time to zero. If time is set to zero, the previous integral output power value is maintained.
If integral action is disabled, manual reset is available by modifying the output power offset (“OPOF” initially set to zero) to eliminate steady state errors. This parameter appears in unprotected parameter mode when integral time is set to zero. The controller has the feature to prevent integral action when operating outside the proportional band. This prevents “reset wind-up”.
Figure 30, Integral Time
-52-
Page 61
Derivative Time
Derivative time is defined as the time, in seconds, in which the output due to proportional action alone equals the output due to derivative action with a ramping process error. As long as a ramping error exists, the derivative action is “repeated” by proportional action every derivative time. The units of derivative time are seconds per repeat.
Derivative action is used to shorten the process response time and helps to stabilize the process by providing an output based on the rate of change of the process. In effect, derivative action anticipates where the process is headed and changes the output before it actually “arrives”. Increasing the derivative time helps to stabilize the response, but too much derivative time coupled with noisy signal processes, may cause the output to fluctuate too greatly, yielding poor control. None or too little derivative action usually results in decreased stability with higher overshoots. No derivative action usually requires a wider proportional and slower integral times to maintain the same degree of stability as with derivative action. Derivative action is disabled by setting the time to zero.
Output Power Offset (Manual Reset)
If the integral time is set to zero (automatic reset is off), it may be necessary to modify the output power to eliminate errors in the steady state. The output power offset (OPOF) is used to shift the proportional band to compensate for errors in the steady state. The output power offset (OPOF) parameter appears in the unprotected mode, if the integral time equals zero. If integral action (automatic reset) is later invoked, the controller continues from the previous output power offset and updates accordingly.
PID Adjustments
To aid in the adjustment of the PID parameters for improvedprocess control, a chart recorder is necessary to provide a visual means of analyzing the process. Compare the actual process response to the PID response figures with a step change to the process. Make changes to the PID p arameters in no more than 20% increments from the starting value and allow the process sufficient time to stabilize before evaluating the ef fects of the new parameter settings.
Figure 31, Derivative Time
Figure 32, Typical Response Curve
-53-
Page 62
PID Adjustments (Cont’d)
Figure 33, Process Response Extremes
-54-
Page 63
MANUAL TUNING FOR PID CONTROL
In some unusual cases, the Auto-Tune function may not yield acceptable control results. In this case, the controller can be manually tuned to optimize the PID setting according to the process and the desired control requirements.
Manual Tuning Procedure
A chart recorder or data logging device is necessary to measure the time between process cycles.
1. Set the Proportional Band (ProP) from the Unprotected Parameter Mode to
10.0% for CN63100 models and 100.0% for CN63300 models.
2. Set the Integral Time (Intt) and Derivative Time (dErt) to 0 seconds.
3. Set Output Power Dampening Time (OPdP) in Output Parameter Module
(2-OP) to 0 seconds.
4. Set Output Cycle Time (CYCt) in Output Parameter Module (2-OP) to no
higher than 1/10 of the process time constant (when applicable).
5. Place controller in Manual Control and set % Power f rom the Normal
Display Mode to drive the process value to the desired value. Make certain
that the controller can drive the process to the setpoint. Allow the process
to stabilize after setting the % Power.
6. Place controller into Automatic Control. If the process will not stabilize and
starts to oscillate, set the Proportional Band 2x higher and go back to step 5.
7. If the process is stable, decrease Proportional Band setting by 2x and
change the setpoint value a small amount to excite the process. Continue
with this step until the process oscillates in a continuous nature.
8. Fix the Proportional Band to 3x the setting that justcaused the oscillations.
9. Set the Integral Time to 2x the period of the oscillations.
10. Set the Derivative Time to 1/8 (0.125) the Integral Time.
11. Set Output Power Dampening Time to 1/40 (0.025) the period of the
oscillation.
Note: This procedure is an alternate to the controller’s Auto-tune function. It
will not provide acceptable results if system problems exist.
-55-
Page 64
REMOTE SETPOINT OPTION
A remote 0/4 to 20 mA analog input signal can be used to change the setpoint value. This input can be scaled over a process range independent of that of the system range. In operation, the front panel “MN” indicator illuminates for local setpoint operation and is off for remote setpoint operation. In either mode, the indicator flashes during Manual Mode. Filtering, ramp rate (velocity limiting), and local/remote transfer response options can be configured to suit the application. Local/Remote transfer operations are performed either externally (user input) or at the keypad.
If large changes in the remote setpoint signal result in undesirable controller performance, the remote setpoint can be velocity limited (ramped) by the setpoint ramp parameter (SPrP).
Similarly, if fluctuation in the remote setpoint signal also results in poor performance, the programmable filter can be used to provide a steady setpoint to the controller. A unique feature of the filter is the filter band. Fluctuations that occur that are less than the filter band value keep the filter engaged, while fluctuations outside the filter band d isable the f ilter. This action allows the controller to respond rapidly to large changes of the remote setpoint signal.
CASCADE CONTROL
External cascade control involves the use of two controllers, one of which
has a Remote Setpoint Input.
The outer loop controller (Primary controller) directs the setpoint of the inner loop controller (secondary controller) through the linear DC output. The secondary controller has a Remote Setpoint option in order to receive the directed setpoint. See Figure 34, Cascade Control, for more details.
Note: The Remote Setpoint of the secondary controller must be scaled prior to
tuning the controllers. Normally, the Remote Setpoint is scaled to equal the
actual process range of the secondary. Scaled in this way, the primary
controller can direct the setpoint of the secondary controller over its
operating range. Normally, the secondary controller is a faster control loop.
It is able to respond quickly to disturbances before they affect the primary
loop. Therefore, thecontrol quality of the primaryloop under cascade control
is superior to that of a single loop controller.
Figure 34, Cascade Control
-56-
Page 65
SERIAL COMMUNICATIONS INTERFACE
RS-485 Serial Communications
The optional RS-485 serial communication interface provides two-way communication between the controller and other compatible equipment such as a printer, PLC, HMI, or a host computer. In multipoint applications, each controller can be configured with a unique node address ranging from 0-99. Through this serial interface, data from the controller can be interrogated or changed, alarm output(s) reset and Auto-tune invoked.
Since the same pair of wires are used for both transmit and receive, only one-way communication is possible at a time. The controller has a variable response time, to allow the host device adequate time to release the communication line after issuing a command to the controller.
Controller Configuration
The controller’s serial communication format is configured in Serial Communication Program Module 6-SC using the front panel. Baud rate and character frame must be matched to the other communicating device. The node address parameter is a unique address number assigned to each slave unit on the bus.
Sending Commands And Data
When sending commands to the controller, a command string of ASCII characters must be constructed. The string varies in length depending on the nature of the command. At most, a command string consists of a Controller (Node) Address number (not required for address of 0), a Command Code character, a Register Identification character (for most commands), Numerical Data (if writing data to the controller) and ending with a string Terminator of “*” or “$”. The controller will not respond with an error message to invalid commands.
Sending Numeric Data
Data written to individual registers must be limited to the registers numerical data range (See Register Identification Table). If more digits are sent, the controller only accepts the last four digits of the numeric data. Negative numbers must have a minus sign. The controller ignores any decimal point and conforms the number to the register identification resolution. (Example: “25” is written to the proportional band register. The value recorded by the register is now 2.5. If a value of 25% is intended, write a value of 25.0 or 250.
Controller (Node) Address
Code Description Comments
N Controller Node
Address Specifier
Target a specific controller with the next Command. Must be followed by a one or two digit (0-99) controller node address number. Not required for a node address of 0.
Commands Table
Code Description Comments
T Read Value
(Transmit)
VWriteValue
(Change)
R Reset Alarm Write alarm register command. Must be followed
C Control Action Write control register command. Must be
P Print Block
Request
Read value register command. Must be followed by Register ID character A-M, BB, HC, or W.
Write value register command. Must be followed by Register ID character B-H or J-M and appropriate Numeric Data.
by Register ID character G or H.
followed by Register ID character S-U with Numeric Data of 1 or 2.
Read block register command. Allows multiple reads with one command.
-57-
Page 66
Register Identification Table
RegisterIDRegister
(Parameter)
A Input T CN63100: TMP
B Setpoint T, V SET -999 to 9999 CN63100: F or C
C Output
power D Proportional T, V PBD 0.0 to 999.9 % E Integral T, V INT 0 to 9999 S
F Derivative T, V DER 0 to 9999 S
G Alarm 1 T, V, R AL1 -999 to 9999 CN63100: F or C
H Alarm 2 T, V, R AL2 -999 to 9999 CN63100: F or C
I Deviation T DEV -999 to 9999 CN63100: F or C
J Power
Offset K Setpoint
Ramp
L Cooling
Gain M Cooling
Offset
BB Remote
Setpoint SAuto/
Manual
T Auto-tune C —- 1 (Start),
U Local /
Remote W Output
Status
Applicable Command
T, V (manual mode only)
T, V (auto mode only)
T, V RMP 0 to 9999 R
T, V CRG 0.0 to 10.0 G
T, V CDB -999 to 9999 CN63100: F or C
T RSP -999 to 9999 CN63100: F or C
C —- 1 (Auto),
C —- 1 (Local),
T OST 0000 to 1111 Blank
Abbreviation
(Mnemonic)
CN63300: INP
PWR -99.9 to 100.0 %
OFP -99.9 to 999.9 CN63100: F or C
Numeric Data
Range
-999 to 9999 CN63100: F or C
2 (Manual)
2 (Stop)
2(Remote)
Engineering Units
CN63300: Blank
CN63300: Blank
CN63300: Blank
CN63300: Blank
CN63300: Blank
CN63300: Blank
CN63300: Blank
CN63300: Blank Blank
Blank
Blank
Terminator Table
Character Description Comments
* Command Terminator Slow response (100 to 200 msec)
setpoint saved to E
$ Command Terminator Fast response (2 to 100 msec)
setpoint not savedtoE
2
PROM
Examples of Command Strings:
Example: Write 10.0 to Setpoint register with a controller address of 2.
Command String: N2VB100* Explanation: Address = 2, Command =V, Register ID = B, Numeric Data = 100, Terminator = * (with $ setpoint will not be saved to E
Example: Read input register of controller with an address of 3.
Command String: N3TA* Explanation: Address = 3, Command=T,RegisterID= A, Terminator = *
Example: Reset Alarm Output 1 of controller with an address of 0.
Command String: RG* Explanation: Address = not used for address 0, Command =R, Register ID =G,Terminator=*
Example: Write to Auto-Tune control register (start Auto-Tune) on
controller with an address of 5. Command String: N05CT1$ Explanation: Address = 5, Command = C, Register ID = T, Numeric Data = 1 (start), Terminator = $
Command Code Explanations
Controller (Node) Address: N
When more than one controller is on the serial communication bus, a
unique controller (node) address must be assigned to each unit. The address range extends from 0 to 99. This is defined in the controller configurations. To communicate with a specific controller, the address code N followed by the controller’s address value must start a command string. A controller with an address of 0 does not require the node address command. Controllers with an address greater than 0 will respond to transmit commands by sending their address followed by the requested data.
-58-
2
PROM
2
PROM)
Page 67
Read Register Command Code: T
The Read Register command is used to read data from a register. This command must be followed by a Register ID character. In full response mode, the controller responds to this command by transmitting its Address (if greater than 0), corresponding register mnemonic and register data. In abbreviated response mode, the controller transmits data only. The response time to this command is controlled by the type of termination character. This is a single register response.
Write Register Command Code: V
The Write Register command is used to write data to a register. This command must be fo llowed by a Register ID character and Numeric Data. A unique command line is required for each register write operation. No response occurs for invalid write operations. The Read Register command (T) can be used fo r readback verification.
Reset Alarm Command Code: R
The Reset Alarm command resets the alarm outputs. This command must be followed by a Register ID character (G for Alarm 1, and H for Alarm 2). This command does not alter the actual alarm mode or value setting.
Control Action Command Code: C
The Control Action command is used to aff ect certain controller operating modes.The registers used with this command are: Auto/Manual mode select, Auto-Tune mode select, and Remote Setpoint mode select. After the Register ID character, either a “1” or “2” is sent to set a specific controller mode.
Block Read Register Command Code: P
The Block Read Register command is used to read data from multiple registers with a single command. With this command, if no register ID characters follow, the controller responds with register data that is preset by the Print Options parameter (Module 6-SC). This mode is useful for print ticket applications. However, if Register ID characters follow this command, the controller responds with register data indicated by the ID character field. This character ID field does not follow the normal Register ID format, but instead is a field composed of ASCII encoded bit mapped bytes. (See Block Read Command Register ID Table.)
Four of these field bytes are used in this format:
P<Byte1><Byte2><Byte3><Byte4>
Each byte represents a code that selects a register(s) for transmission. The Block Read Command Byte Table relates specific registers for reads to the field bytes.
Examples:
Print:Alarm1andAlarm2values(bothareinByte2table)
Explanation: Byte1 = 0, Byte2 = 3, Byte3 & Byte4 are not needed
ASCII String : P03* (Either the “*” or “$” terminator could be used.)
For those programming in HEX: P = <50>, 0 = <30>, * = <2A>, $ = <24>
HEX String : <50><30><33><2A>
Print: Input, Cooling Deadband and Output Status (Input is in Byte1 table
and the other two are in Byte4 table) Explanation: Byte1 = 8, Byte2 = 0, Byte3 = 0, Byte4 = C ASCII String : P800C$ (Either the “*” or“$” terminator could be used.) HEX String : <50><38><30><30><43><24>
Terminator:*or$
After a Read Register command is sent, the response time of the controller
is determined by the type of command terminator character. The “$” terminator causes a response time of 2 msec to 100 msec and the “*” terminator causes a response time of 100 msec to 200 msec. (The 2 msec delay allows for a two character transmission time at 9600 baud. ) The controller does not begin processing the command string until the “$” or “*” is received. The Carriage Return <CR> and the Line Feed <LF> cause the controller to ignore the command string. When writing setpoint values, only values using the “*” terminator are saved to E
2
PROM memory.
-59-
Page 68
Block Read Command Byte Table
Locate the desired register combination for each Byte. X=register to be printed. Use ASCII 0 for blank trailing byte locations. For those programming in HEX: P = <50>, 0 = <30>, * = <2A>, $ = <24>
Byte1
Input Setpoint
X 4 <34> X X 5 <35> X X 6 <36>
X 8 <38> X X 9 <39> X X A <41> X X X B <42> X X C <43> X X X D <44> X X X E <45> X XXXF<46>
XXX7<37>
Byte2
Integral
Time
Derivative
Time
X 4 <34> X X 5 <35> X X 6 <36>
X 8 <38> X X 9 <39> X X A <41> X X X B <42> X X C <43> X X X D <44> X X X E <45> X XXXF<46>
XXX7<37>
Output Power
X 2 <32> X X 3 <33>
Alarm 1 Alarm 2 ASCII HEX
X 2 <32> X X 3 <33>
PBand ASCII HEX
X 1 <31>
X 1 <31>
Byte3
Deviation
X 8 <38> X X 9 <39> X X A <41> X X X B <42> X X C <43> X X X D <44> X X X E <45> X XXXF<46>
Offset
Power
X 4 <34> X X 5 <35> X X 6 <36> XXX7<37>
Setpoint
Ramp
X 2 <32> X X 3 <33>
Cooling
Gain
X 1 <31>
ASCII HEX
Byte4
Cooling
Deadband
X 8 <38> X X 9 <39> X X A <41> X X X B <42> X X C <43> X X X D <44> X X X E <45> X XXXF<46>
Output
Status
X 4 <34> X X 5 <35> X X 6 <36> XXX7<37>
Remote
Setpoint
X 2 <32> X X 3 <33>
Heater
Current
X 1 <31>
ASCII HEX
-60-
Page 69
Unique Register Explanations
Setpoint Ramp Using Automatic Setpoint Ramping Register: K
The controller’s Setpoint Ramp parameter provides a controlled ramp when the setpoint value is changed. (The Setpoint Ramp value can be changed by using VK command.) When the setpoint value is changed, the controller begins to ramp from the existing value to the new target setpoint, at a rate set by this register. A value of zero in the Setpoint Ramp register disables ramping.
During the controlled ramp phase, the Integral Action is automatically disabled. This tends to reduce overshoot due to excessive integral build-up. The Integral Action automatically resumes at the end of the controlled ramp phase.
To terminate a ramp in progress, write 0 (zero) to the Setpoint Ramp register. This results in immediate control to the target setpoint.
Setpoint Ramp Using Periodic Setpoint Write Register: B
A host computer can command the setpoint value of the controller by writing new setpoint values based on clock ticks. In this manner, the host has explicit control over setpoint values, ramp and hold phases.
During ramp phases, the Integral Action may lead to overshoot problems. In this case, the integral action may be slowed or completely disabled by setting the integral time register.
Periodic Setpoint Write Commands (E
In the case of periodically writing setpoint values to the controller (host is running a temperature/process profile), terminate the write command with the “$” terminator character. This instructs the controller to accept the setpoint value, but not to write the value to E cycling of the internal memory chip, which has a finite life-cycle rating (1 million typical). This rating should not be exceeded.
After power loss, the setpoint value written will be lost when using “$”. Termination of the setpoint write command with the “*” character instructs the controller to save the value to E value will be recalled after a power loss.
2
PROM precautions)
2
PROM memory. T his eliminates
2
PROM memory. In this case, the setpoint
Output Status: W
The Output Status register indicates the present status of the controller’s discrete alarm outputs (coils). This is a read only register. The controller responds with OST followed by a field consisting of 4 bytes. The bytes represent the status of the outputs in the following order: main output O1, cooling/ secondary output (O2), alarm 2 output (A2), alarm 1 output (A1). When the output is on, the corresponding byte is “1.” When the output is off, the corresponding byte is “0”.
Communication Format
Data is transferred from the controller over a serial communication channel. In serial communications, the voltage is switched between a high and low level at a predetermined rate (baud rate) using ASCII encoding. The receiving device reads the voltage levels at the same intervals and then converts the number back to a character.
The table lists the required voltage levels at the receiver for RS485 interface.
Logic RS485 Interface State
1 a-b <-200 mV mark (idle)
0 a-b >+200 mV space (active)
Data is transmitted one byte at a time. Each ASCII character is “f ramed” with a beginning start bit, an optional error detection parity bit and one or more ending stop bits.
-61-
Page 70
Figure 36, Character Frame
To allow the host adequate time to release the bus after a transmission, the response time of the controller is programmable. The controller utilizes a receiver design that interprets a mark condition for open connections.
Start Bit and Data Bits
Data transmission always begins with the start bit. The start bit signals the receiving device to prepare for reception of data. One bit period later, the least significant bit of the ASCII encoded character is transmitted, followed by the remaining data bits. The receiving device then reads each bit position as it is transmitted. Since the sending and receiving devices operate at the same transmission speed (baud rate), the data is read without timing errors.
Parity Bit
After the data bits, the parity bit is sent. The transmitter sets the parity bit to a zero or a one, so that the total number of ones contained in the transmission (including the parity bit itself) is either even or odd. This bit is u sed by the receiver to detect one bit errors occurring in the transmission. Given this limitation, the parity bit is often ignored by the receiving device. The controller ignores the parity bit of incoming data and sets the parity bit to odd, even or none (mark parity) for outgoing data.
Stop Bit
The last character transmitted is the stop bit. The stop bit provides a single bit period pause to allow the receiver to prepare to re-synchronize to the start of new transmission (start bit of next byte). After the stop bit, the receiver continuously looks for the occurrence of the next start bit.
Command Response Time
The controller can only receive or transmit data at any one time (half-duplex operation). If bus activity, such as another command, occurs before the controller has ended its transmission, garbled data will result. When sending commands and data to the controller, timing restrictions are imposed when sending another command afterwards. This allows enough time for the controller to process the command and prepare for the next command. If the timing requirements are not obeyed, lost transmissions may result.
Figure 35, Timing Diagram
At the start of the time interval t string to the com port, thus initiating a transmission. During t characters are transmitting and at the end of this period, the command terminating character (*) is received by the controller. The time duration of t is dependent on the number of characters and baud rate of the channel.
-62-
, the computer program prints or writes the
1
1
, the command
1
Page 71
t1= (10 X # of characters) / baud rate
At the start of time interval t
command and when complete, performs the command function. This time
, the controller starts the interpretation of the
2
interval varies from 2 msec to 100 msec. If no response from the controller is expected, the controller is ready to accept another command at the end of t minimum delay of 100 msec for period t another command to the same controller.
If the controller is to reply with data, the time interval t
use of the command terminating character. The standard command line
must be observed before sending
2
is controlled by the
2
.A
2
terminating character is ‘*’. This terminating character results in a response time window of 100 msec minimum and 200 msec maximum. This allows sufficient time for the release of the bus by the transmitter. Terminating the command line with ‘$’ results in a response time window (t minimum and 100 msec maximum. The faster response time of this
)of2msec
2
terminating character requires that the transmitter release within 2 msec after the terminating character is received.
At the beginning of time interval t character of the reply. As with t number of characters and baud rate of the channel.
t
= (10 X # of characters) / baud rate.
3
, the controller responds with the f irst
3
, the time duration of t3is dependent on the
1
The number of response characters varies depending on the setting of the full / abbreviated transmissions parameter. At the end of t ready to receive the next command.
, the controller is
3
The maximum serial throughput of the controller is limited to the sum of:
t
and t3.
1,t2
Full Field Controller Transmission Byte Format
The first two characters transmitted are the node address, unless the node address assigned = 0, in which case spaces are substituted. A space follows the node address field. The next three characters are the register ID. The numeric data is transmitted next. The numeric field is 5-6 characters long. If the decimal point is present, the field is 6 characters. Negative values have a leading minus sign. The data field is right justified with leading spaces. Engineering Units byte is next. The end of the response string is terminated with a carriage return <CR> and line feed<LF>. When print block transmission is finished, an extra <SP><CR><LF> is used to provide separation between the blocks.
Byte Description
1-2 2 byte Node Address field [00-99]
3 <SP> (Space)
4-6 3 byte Register ID field
7-12 6 byte data field, 4 bytes for number, one byte for sign, one byte
for decimal point
13 1 byte Engineering Units
14 <CR>
15 <LF>
16 <SP>(Space). This character only appears in the last line of a print
block.
17 <CR> This character only appears in the last line of a print block.
18 <LF> This character only appears in the last line of a print block.
-63-
Page 72
Abbreviated Controller Transmission Byte Format
The abbreviated response suppresses the node address and register ID characters, leaving only the numeric part of the response. The numeric field is 5-6 characters long. If the decimal point is present, the field is 6 characters. Negative values have a leading minus sign. The data field is right justified with leading spaces.The end of the response string is terminated with a carriage return <CR> and line feed <LF>. When print block transmission is finished, an extra <SP><CR><LF> is used to provide separation between the blocks.
Byte Description
1-6 6 byte data field, 4 bytes for number, one byte for sign, one byte
for decimal point 7 <CR> 8<LF> 9 <SP>(Space). This character only appears in the last line ofa print
block.
10 <CR> This character only appears in the last line of a print block. 11 <LF> This character only appears in the last line of a print block.
Example of Full Field Printout of Factory Settings
CN63300 CN63100
INP 25.0 TMP 87F
SET 0.0 SET 0F
PWR 47.8% PWR 0.0%
PBD 100.0% PBD 4.0%
INT 40S INT 120S
DER 4S DER 30S
AL1 0.0 AL1 0F
AL2 0.0 AL2 0F DEV 25.0 DEV 87F OFP 0.0% OFP 0.0%
RMP 0.0R RMP 0.0R CRG 1.0G CRG 1.0G
CDB 0.0 CDB 0F OST 0000 RSP 0F
OST 0101
Troubleshooting Serial Communications
If problems are encountered when interfacing the controller(s) and host
device or printer, the following check list can be used to help find a solution.
1. Check all wiring. Proper polarity of all devices on the serial loop must be observed. Refer to previous application examples.
2. Check the controller’s communication format in module 6-SC. Make sure all devices on the serial loop are configured with the same communication format.
3. Check the requesting device constructed command string format.
4. When sending commands to the controller, an asterisk “*” or dollar sign “$” must terminate the command. Make sure a carriage return or line feed does not follow the command terminator.
5. Check the controller’s unit address in module 6-SC. It should be zero if the address command is not used in the command string for single controller configurations. In multiple controller configurations, make sure each controller has a unique unit address.
6. Initiate transmissions from the controller by programming the User Input for PrNt in module 1-IN for print and programming module 6-SC at PoPt set INP (input) to YES. As long as the user input is connected to common, controller data will be sent.
7. With two-way communications or multiple controller configurations, make sure only one device is communicating at a time.
8. If all of the above has been done, try reversing the polarity of the serial wires at host device or printer. Some devices have reversed polarity.
-64-
Page 73
APPLICATION EXAMPLES
CN63100 OEM Paint Sprayer Application
An OEM manufacturing spray painting equipment utilizes the CN63100 to maintain optimum paint temperature. In addition to the low cost, the 1/16 DIN package size permits the OEM to design temperature control into various sized painting equipment, from small hand sprayers to large paint booths. The heating element used to heat the paint, is connected to the Main Control Output (OP1) programmed for On/Off control. Alarm 1 is programmed as Band Inside Acting, so that as long as the paint temperature is within manufacturer’s specifications for temperature, the “GO” light is on. Alarm 2 is programmed as Band Outside acting so that the “NO GO” light is lit when the paint temperature is more than 12°outside the manufacturer’s specifications of 140 to 150°F.
Figure 37, OEM Paint Sprayer Application
Process Requirements
Unprotected Parameters PrOP 0 On/Off control AL-1 12 GO light on within setpoint ±12 AL-2 12 NO GO light on outside setpoint ±12
1 - In Configure Input Parameters tYPE tc-J * Thermocouple type “J” SCAL F * Control and indicate in °F dCPt 0 * One degree display resolution FLtr 1 * Nominal input signal digital filtering SHFt 0 * No shift correction necessary SPLO 140 Limit min. setpoint temperature to 140 °F SPHI 150 Limit max. setpoint temperature to 150 °F SPrP 0.0 * No setpoint ramping InPt PLOC * User Input program lock
2 - OP Configure Output Parameters CYCt 2 * Not used for On/Off control OPAC rEv * Use reverse acting for heating OPLO 0 * For on/off, leave at 0% OPHI 100 * For on/off, leave at 100% OPFL 0 * Turn off if sensor fails OPdP 3 * Output power dampening = 3 seconds CHYS 2 * 2 degree on/off band tcod 0 * Not used for On/Off control
4 - AL Configure Alarm Parameters Act1 b-IN Band Inside rSt1 Stb1 no * Power-up standby AL-1 12 Go light on within setpoint ±12 Act2 b-ot Band outside rSt2 Stb2 no * Power-up standby AL-2 12 No Go light on outside setpoint ±12 AHYS 1 * 1° alarm activation hysteresis
Auto * Automatic light on/off
Auto * Automatic light on/off
* Factory Settings
-65-
Page 74
CN63300 Water Processing Application
A city water company needs to maintain a steady flow of water for their customer needs. They have an existing 0 to 10 VDC flow transmitter to measure the water flow. They need to control the water flow, have a high and low alarm, and keep a recorded chart of the flow for later reference. The Main Linear DC output of the CN63300 is used to control the position of water value to maintain the desired flow setpoint value. The CN63300 relay outputs are programmed to give a high flow alarm and a low flow alarm. With the Second Linear DC output model, the f low measurement to the CN63300 can be retransmitted to a chart recorder.
ALARM POWER
+
-
CHART RECORDER
HIGH ALARM
CONTROL
VALVE
LOW ALARM
UNIT POWER
FLOW SENSOR
WATER FLOW
Process Requirements
Unprotected Parameters ProP XX Calculated by Auto-Tune Intt XX Calculated by Auto-Tune dErt XX Calculated by Auto-Tune AL-1 90.0 High alarm AL-2 20.0
1-IN Configure Input Parameters tYPE VOLt Voltage Input dCPt 0.0 * Resolution FLtr XX Calculated by Auto-Tune dSP1 0.0 Input low value INP1 0.00 Low display value dSP2 10.0 Input high value INP2 150.00 High display value SPLO 40.0 Setpoint low limit SPHI 80.0 Setpoint high limit SPrP 0.0 * No ramping INPt PLOC * User input program lock
2-OP Configure Output Parameters CYCt 0 Disable O1 output The remaining parameters in this module are set to factory settings.
4-AL Configure Alarm Parameters Act1 A-HI Set 01/A1 for control output rSt1 LAtC Manual reset Stb1 yes Disable alarm during power-up AL-1 90.0 Set 90.0 gal/min high alarm value Act2 A-LO Set alarm #2 for deviation band from setpoint rSt2
LAtC Manual reset Stb2 yes Disable alarm during power-up AL-2 20.0 Set 20.0 gal/min low alarm value AHYS 5.0 Alarm activation hysteresis
8-A2 Configure Second Analog Parameter A2tP 4-20 4-20 mA retransmitted A2LO 0.0 Display low value A2HI 150.0 Display high value
Low alarm
Figure 38, Water Processing Application
* Factory Settings
-66-
Page 75
CHECKS AND CALIBRATION
The instrument has been fully calibrated at the factory for all input types. If the unit appears to be indicating or controlling incorrectly, see Troubleshooting, page 71, before attempting this procedure.
If the controller is suspected of reading incorrectly, the instrument may be checked for indication accuracy without disturbing the factory calibration. The following procedures may be used for this purpose.
Note: Allow 1/2 hour warm-up before checking these parameters.
MAIN INPUT CHECK
mV Reading Check (CN63100)
1. Connect a DC mV source with an accuracy of 0.03% or better to terminal #8
(-) & #9 (+).
2. Configure Input Parameters Module 1 for linear mV (lin) input, under
tYPE.
3. Compare the controller read-out to the standard at various points over the
range (-5.00 mV to 56.00 mV). The tolerance is ±(0.15% of reading +1
LSD).
4. Calibrate the controller if the readings are out of tolerance.
Thermocouple Cold Junction Temperature Check (CN63100)
1. Connect a thermocouple probe of known accuracy (Types T, E, J, K, N
only) to controller. Select the probe used in Configure Module 1.
2. Connect a reference temperature probe to measuring end of thermocouple
to monitor temperature. Allow sufficient time for temperatures to equalize.
3. Compare controller display with reference temperature probe. The
controller display should equal the calibrated probe temperature.
(Tolerance is ±1°C).
4. Calibrate the cold junction temperature if out of tolerance.
RTD Ohms Reading Check (CN63100)
1. Connect RTD simulator (with an accuracy of 0.1 ohm or better) capable of
operating with less than 150 μA to terminals #8, #9, & #10.
2. Configure Input Parameters Module 1 for linear ohms (rLIn) input, under
tYPE.
3. Compare the controller read-out with the RTD simulator at various points
over the range 1.0 to 300.0 ohms. The tolerance is ±(0.3% of span ±1LSD).
4. Calibrate the controller RTD ohms if out of tolerance.
Voltage Check (CN63300)
1. Connect a DC voltage source with an accuracy of 0.1% or better. Apply a 0 to 10 V signal to terminals #8 (-) & #9 (+).
2. In Input Module 1, configure input signal InP1 and display value dSP1 to
0.00. Configure input signal InP2 and display value dSP2 to 10.00.
3. Compare the controller readout to the voltage source over the range (0-10 V). The tolerance is ±(0.3% of reading +0.03 V).
4. Calibrate the controller if the readings are out of tolerance.
Current Check (CN63300)
1. Connect a DC current source with an accuracy of 0.1% or better. Apply a 0 to 20 mA signal to terminals #8 (-) & #10 (+).
2. In Input Module 1, configure input signal InP1 and display value dSP1 to
0.00. Configure input signal InP2 and display value dSP2 to 20.00.
3. Compare the controller readout to the current source over the range (0-20 mA). The tolerance is ±(0.3% of reading +0.04 mA).
4. Calibrate the controller if the readings are out of tolerance.
Remote Setpoint Input Check (CN63100 and CN63300)
1. Connect a DC current source with an accuracy of 0.03% or better. Apply a 0 to 20 mA sig nal to terminals 13 (+) and 14 (-).
2. In Remote Setpoint Input Module 7, configure input signal InP1 and display value dSP1 to 0.00. Configure input signal InP2 and display value dSP2 to 20.00.
3. Compare the readout in the secondary main display to the current source over the range (0-20 mA). The tolerance is ±(0.2% of full scale +½ LSD).
4. Calibrate Remote Setpoint Input if readings are out of tolerance.
Error Flag E-CL
If error flag “E-CL” appears at power-up, a loss of calibration parameters
due to noise spikes has occurred. Entering code 77 twice in Factory Service Operations Module (9-FS) erases the controller calibration values and defaults the values to nominal settings. Reading errors of ±10% may result. It is recommended that the controller be fully re-calibrated. If using thermocouple only, the RTD calibration need not be performed.
-67-
Page 76
Note: The “E-CL” flag may be cleared by “stepping” through cold junction or
linear output calibration procedures without the need to change any calibration values. A
10% reading error will still exist.
Calibration For CN63100
When re-calibration is required (g enerally every two years), this procedure should be performed by qualified technicians using appropriate equipment. Equipment source accuracy of 0.03% or better is required.
The procedure consists of: applying accurate mV signals, setting the thermocouple cold junction temperature, and applying precision resistance, among others. Allow a 30 minute warm-up period before starting this procedure. Do not use thermocouple wire for the Millivolt or RTD ohms Calibration.
This procedure may be aborted b y disconnecting power to the controller before exiting the configuration mode. The existing calibration settings remain in affect.
Note: After completing any of the calibration sequences, the controller defaults
the input sensor type to thermocouple type “J” (tc-j). Be sure to set input
sensor for proper type. Note: The controller must be restored to normal display mode before any data
is stored.
Factory Service Operations - Calibration (9-FS)
Display Parameter Range Description/Comments
CodE Enter function code 48 Calibrate instrument CAL Millivolt Calibration yes/no Calibration required for both
CJC Thermocouple cold
rtd RTD Resistance
A1CL Main Linear DC
A2CL Second Linear DC
2CAL or N2CL
junction temperature calibration
Calibration
Output Calibration
Output Calibration
Remote Setpoint Calibration
yes/no Not required if only using RTD
yes/no Not required if only using TC
yes/no Model number dependent.
yes/no Model number dependent.
yes/no Model number dependent
RTD and TC input. If this procedure is performed, the cold junction temp or RTD ohms calibration procedures in turn must be completed.
input. This procedure can only be performed AFTER an accurate mV calibration.
input. This procedure can only be performed AFTER an accurate mV calibration.
Calibrate either 10 V or 20 mA Range
Calibrate either 10 V or 20 mA Range
Millivolt Calibration (CAL)
Connect precision millivolt source with an accuracy of 0.03% to terminals (-) #8 and (+) #9. Cold Junction or RTD Ohms calibration MUST be performed after millivolt calibration.
Display Action Description/Comments
StP1 Apply 0.0 mV Wait 10 seconds, press P. StP2 Apply 14.0 mV Wait 10 seconds, press P. StP3 Apply 28.0 mV Wait 10 seconds, press P. StP4 Apply 42.0 mV Wait 10 seconds, press P. StP5 Apply 56.0 mV Wait 10 seconds, press P.
-68-
Page 77
Thermocouple Cold Junction Calibration (CJC)
This procedure must be performed AFTER an accurate mV calibration.
1. Exit Factory Service Operations (press D) and return to Normal Display Mode.
2. Connect a thermocouple probe of known accuracy to the controller (Types T, E, J, K, and N only). Select the probe type used in Configure Module 1.
3. Connect a reference temperature probe to the measuring end of the CN63100 thermocouple probe. The two probes should be shielded from air movement and allowed sufficient time to equalize in temperature. (As an alternative, the CN63100 thermocouple probe may be placed in a calibration bath of known temperature.)
4. Compare controller display with reference temperature probe (or calibration bath). If the displayed controller temperature does not equal the reference probe temperature, calculate the CJ Error as follows:
CJ Error = reference probe temperature - displayed controller temperature
5. Enter Factory Service Operations Module (9-FS).
Display Parameter Description/Comments
CJC Cold Junction
Temperature
Observe the indicated cold junction temperature. Add the calculated CJ Error to the displayed value. Enter the sum as the new value for CJC. Exit 9-FS and repeat step 4.
Note: If the initial value for CJC is not within the range 15.0°C to 40.0°C, enter 25.0° Cfor CJC and repeat the Cold Junction Calibration procedure.
RTD Ohms Calibration (rtd)
This procedure must be performed AFTER an accurate mV calibration.
Connect one leg of precision resistance (accuracy of 0.1 ohm) to terminals #9 and #10 together, and the other leg to #8.
Display Action Description/Comments
Rtd1 Connect 0.0 ohm (jumper wire) Wait 10 seconds, press P. Rtd2 Connect 277.0 ohm Wait 10 seconds, press P.
Main or Second Linear DC Analog Output Calibration
1. Set the Linear DC Output jumper for the range to be calibrated. (See Linear DC Analog Output Jumper Selection, page 11).
2. Connect a meter with an accuracy of 0.05% or better to the output.
3. For each step, use the controller arrow keys to adjust the external meter display to match the parameter being calibrated. Press P when the output is correct, or if the parameter is not being calibrated.
Display Parameter External Meter Action
C 0V 0 V Calibration 0.00 Adjust if necessary, press P.
C 10V 10 V Calibration 10.00 Adjust if necessary, press P.
C 0c 0 mA Calibration 0.00 Adjust if necessary, press P.
C 20c 20 mA Calibration 20.00 Adjust if necessary, press P.
Remote Setpoint Calibration
Connect DC mA source with an accuracy of 0.03% or better.
Display Action Description/Comments
StP1 Apply 0 mA Wait 10 seconds, press P. StP2 Apply 5 mA Wait 10 seconds, press P. StP3 Apply 10 mA Wait 10 seconds, press P. StP4 Apply 15 mA Wait 10 seconds, press P. StP5 Apply 20 mA Wait 10 seconds, press P.
-69-
Page 78
Calibration For CN63300
When re-calibration is required (g enerally every two years), this procedure should be performed by qualified technicians using appropriate equipment. Equipment source accuracy of 0.03% or better is required.
The procedure consists of applying accurate voltage and current signals. Allow a 30 minute warm-up period before starting this procedure.
This procedure may be aborted b y disconnecting power to the controller before exiting the configuration mode. The existing calibration settings remain in effect.
Factory Service Operations (9-FS)
Display Parameter Range Description/Comments
CodE Enter factory service
function code
CAL Input calibration yes/no Calibration for both voltage and
A1CL Main Linear DC Output
calibration
A2CL Second Linear DC
Output calibration
n2CL Remote Setpoint
Calibration
Input Calibration
Connect voltage calibration source with an accuracy of 0.1% or better.
Display Action Description/ Comments
StP1 Apply 0.0 V Wait 10 seconds press P. StP2 Apply 2.5 V Wait 10 seconds press P. StP3 Apply 5.0 V Wait 10 seconds press P. StP4 Apply 7.5 V Wait 10 seconds press P. StP5 Apply 10 V Wait 10 seconds press P. Connect current calibration source with an accuracy of 0.1% or better. StPA Apply 0 mA Wait 10 seconds press P. StPB Apply 20 mA Wait 10 seconds press P.
48 Calibrate Instrument
current.
yes/no Model number dependent.
Calibrate either 10 V or 20 mA.
yes/no Model number dependent.
Calibrate either 10 V or 20 mA.
yes/no Model number dependent
Main or Second Linear DC Analog Output Calibration
1. Set the Linear DC Output jumper for the range to be calibrated. (See Linear DC Analog Output Jumper Selection, page 11).
2. Connect a meter with an accuracy of 0.05% or better to output.
3. For each step, use the controller arrow keys to adjust the external meter display to match the parameter being calibrated. Press P when the output is correct, or if the parameter is not being calibrated.
Display Parameter External Meter Action
C 0V 0 V Calibration 0.00 Adjust if necessary, press P.
C 10V 10 V Calibration 10.00 Adjust if necessary, press P.
C 0c 0 mA Calibration 0.00 Adjust if necessary, press P.
C 20c 20 mA Calibration 20.00 Adjust if necessary, press P.
Remote Setpoint Calibration
Connect DC mA source with an accuracy of 0.03% or better.
Display Action Description/Comments
StP1 Apply 0 mA Wait 10 seconds, press P. StP2 Apply 5 mA Wait 10 seconds, press P. StP3 Apply 10 mA Wait 10 seconds, press P. StP4 Apply 15 mA Wait 10 seconds, press P. StP5 Apply 20 mA Wait 10 seconds, press P.
-70-
Page 79
TROUBLESHOOTING
The majority of problems can be traced to improper connections or incorrect set-up parameters. Be sure all connections are clean and tight, that the correct output board is fitted, and that the set-up parameters are correct. For further technical assistance, contact technical support at the appropriate company numbers listed.
PROBLEMS POSSIBLE CAUSE REMEDIES
NO DISPLAY 1. Power off
CONTROLLER NOT WORKING
“E-FP” IN DISPLAY 1. Defective front panel button. 1. Press D to escape, then check all buttons for proper operation.
“E-UP” IN DISPLAY 1. Internal problem with controller. 1. Replace unit.
“E-E2” IN DISPLAY 1. Loss of set-up parameters due to noise spike. 1. Press D to clear, then check all set-up parameters.
“E-CL” IN DISPLAY 1. Loss of calibration parameters due to noise spike. 1. Press D to clear, then check accuracy of controller.
“...” OR “-..” IN DISPLAY 1. Display value exceeds display range.
“OPEN” IN DISPLAY
(CN63100)
2. Brown out condition.
3. Loose connection or improperly wired.
4. Bezel assembly not fully seated into rear of unit.
1. Incorrect parameter set-up. 1. Check set-up parameters.
2. Defective or mis-calibrated cold junction circuit.
3. Loss of set-up parameters.
4. Internal malfunction.
1. Probe disconnected.
2. Broken or burned out probe.
3. Corroded or broken terminations.
4. Excessive process temperature.
1. Check power.
2. Verify power reading.
3. Check connections.
4. Check installation.
2. Replace unit.
a. Check sensor input and AC line for excessive noise. b. If fault p ersists, replace unit.
a. Recalibrate controller. b. Reset calibration parameters to nominal values
(See Factory Service Operations Module).
1. Change resolution to display whole number. a. Verify reading.
2. Check cold junction calibration.
3. Check set-up parameters.
4. Check calibration.
1. Connect probe. (Connection must remain intact for 3 sec. to clear “OPEN” condition.)
2. Replace probe.
3. Check connections.
4. Check process parameters.
-71-
Page 80
TROUBLESHOOTING (Cont’d)
PROBLEMS POSSIBLE CAUSE REMEDIES
“SENS” IN DISPLAY
(CN63300)
“OLOL” IN UPPER DISPLAY 1. Input exceeds range of controller.
“ULUL” IN UPPER DISPLAY 1. Input is below range of controller.
“SHrt” IN DISPLAY
(CN63100)
CONTROL SLUGGISH OR NOT STABLE
“OLOL” OR “ULUL” IN LOWER DISPLAY
1. Input exceeds range of controller.
2. Incorrect input wiring.
3. Defective transmitter
4. Internal malfunction.
2. Temperature exceeds range of input probe.
3. Excessive positive probe temperature.
4. Loss of set-up parameters.
2. Temperature below range of input probe.
3. Excessive negative probe temperature.
4. Loss of set-up parameters.
1. RTD probe shorted. 1. Check wiring.
1. Incorrect PID v alues.
2. Improper probe location.
1. Signal input exceeds allowable range by 5%. 1. Check Remote Signal Source.
1. Check input signal level.
2. Check input wiring.
3. Check signal calibration.
4. Check calibration.
1. Check sensor or input signal level.
2. Change to input sensor with a higher temperature range.
3. Reduce temperature.
4. Check set-up parameters.
1. Check sensor or input signal level.
2. Change to input sensor with a lower bottom range.
3. Increase temperature.
4. Check set-up parameters.
2. Replace RTD probe.
1. See PID Control.
2. Evaluate probe location.
-72-
Page 81
REPLACEABLE OUTPUT BOARD DESCRIPTION
Output Board
The controller is supplied with an output board (relay, or logic/SSR) installed. The output board is configured for the type of Main Control and Alarm Output based upon the model number ordered. The output board is field replaceable in many models. (For models where the output board is not replaceable, the controller must be returned to the factory for output board repair.) See Part Numbers, page 78, for available models.
Replacing Output Board
1. Remove the bezel assembly. (See Removing Bezel Assembly, page 3).
2. Lift up on the top bezel board latch while gently pulling out on the
bezel/display board assembly. Do NOT remove the display board from
the bezel.
3. Remove the output board by pulling it away fromthe other boards. Replace
the output board by aligning the board to board connector. Be certain the
connector is fully mated.
4. Connect the bezel/display board assembly by guiding the board ends into the
bezel latches. Slide the assembly on evenly until the display board connector
is completely engaged and bezel latches are fully seated onto the boards.
Figure 40, Output Boards
Figure 39, Output Board Replacement
-73-
Page 82
SPECIFICATIONS AND DIMENSIONS
1. DISPLAY:Dual4-digit Upper Process Display: 0.4" (10.2 mm) high red LED Lower Auxiliary Display: 0.3" (7.6 mm) high green LED Display Messages:
“OLOL” Measurement exceeds + input range. “ULUL” Measurement exceeds - input range. “OPEN” Open sensor is detected. (CN63100 only) “SHrt” Shorted sensor is detected (RTD only) “SENS” Measurement exceeds controller limits. (CN63300
only) “...” Display values exceed + display range. “-..” Display values exceed - display range.
LED Status Annunciators:
%P Lower auxiliary display shows power output in (%). MN Flashing: Controller is in manual mode.
ON: Local Setpoint (Remote Setpoint option) OFF: Remote Setpoint
DV Lower auxiliary display shows deviation (error) from
process setpoint O1 Main control output is active. A1 Alarm #1 is active. (for AL1 Option) A2 Alarm #2 is active OR
Cooling (Second) output (O2) is active.
DIMENSIONS In inches (mm)
2. POWER: AC Versions: 85 VAC min. to 250 VAC max., 50 to 60 Hz, 8 VA max. DC Versions:
DC Power: 18 to 36 VDC; 7 W AC Power: 24 VAC ±10%; 50 to 60 Hz, 9 VA
3. CONTROLS: Four front panel push buttons for modification and setup of controller functions and one external user input for parameter lockout or other functions.
4. MEMORY: Nonvolatile E
2
PROM retains all programmable parameters
and values.
5. MAIN SIGNAL INPUT: Sample Period: 100 msec Response Time: Less than 300 msec typical, 400 msec max. (to within 99%
of final value w/step input; typically, response is limited to response time of probe)
Failed Sensor Response (CN63100 only):
Main Control Output(s): Programmable preset output Display: “OPEN” Alarms: Upscale drive
Normal Mode Rejection: 40 dB @ 50/60 Hz
(improves with increased digital filtering).
Common Mode Rejection: Greater than 120 dB, DC to 60 Hz
PANEL CUT-OUT
Figure 43, Dimensions
-74-
Page 83
Protection: Input overload 120 VAC max. for 15 sec. max.
6. CN63100 INDICATION ACCURACY: ±(0.3% of Span +1°C) Includes NIST conformity, cold junction effect and A/D conversion errors at 23°C after 20 min. warm-up.
7. THERMOCOUPLE INPUT (CN63100 only): Types: T, E, J, K, R, S, B, N, Linear mV, Sof tware selectable Input Impedance: 20 MΩ, all types Lead resistance effect: 0.25 μV/Ω Cold junction compensation: Less than ±C(±1.5°C max.) error over 0 to
50°C max. ambient temperature range. Defeated for Linear mV indication mode.
Resolution: 1° for all types, or 0.1° for T, E, J, K and N only.
TC TYPE RANGE
T -200 to +400°C
-328 to +752°F
E -200 to +750°C
-328 to +1382°F
J -200 to +760°C
-328 to +1400°F
K -200 to +1250°C
-328 to +2282°F
R 0 to +1768°C
+32 to +3214°F
S 0 to +1768°C
+32 to +3214°F
B +149 to +1820°C
+300 to +3308°F
N -200 to +1300°C
-328 to +2372°F
mV -5.00 to +56.00 no standard no standard
WIRE COLOR
ANSI BS 1843
(+) blue
(-) red
(+) violet
(-) red
(+) white
(-) red
(+) yellow
(-) red
(+) black
(-) red
(+) black
(-) red
(+) grey
(-) red
(+) orange
(-) red
(+) white
(-) blue
(+) brown
(-) blue
(+) yellow
(-) blue
(+) brown
(-) blue
(+) white
(-) blue
(+) white
(-) blue
(+) none
(-) blue
(+) orange
(-) blue
8. RTD INPUT (CN63100 only): 2 or 3 wire, 100 Ω platinum, alpha =
0.00385 (DIN 43760), alpha = 0.0039162 Excitation: 150 μA typical Resolution: 1 or 0 .1 degree Lead Resistance: 15Ω max. per input lead.
RTD TYPE RANGE
385 -200 to +600°C
392 -200 to +600°C
OHMS 1.0 to 320.0
-328 to +1100°F
-328 to +1100°F
9. CN63300 RANGE AND ACCURACY:
Input
Range
10 VDC
(-1 to 11)
20 mA DC
(-2 to 22)
Accuracy*
(18 to 28
0.10% of reading +0.02 V
0.10% of reading
+0.03 mA
Accuracy*
C)
(0 to 50 C)
0.30% of reading
+0.03 V
0.30% of reading
+0.04 mA
Impedance
1M ohm 300 V 10 mV
10 ohm 100 mA 10 uA
Max.
Continuous
Overload
Resolution
* Accuracies are expressed as ± percentages after 20 minute warm-up. The
controller’s accuracy is specified in two ways: Accuracy over an 18 to 28°C range at 10 to 75% RH environment; and accuracy over a 0 to 50°C range at 0 to 85% RH (non-condensing) environment. Accuracy over the wide sensor range ref lects the coefficient of the internal circuitry.
10. USER INPUT:Internallypulledupto+5VDC(1MΩ). V VDC; V Response time: 120 msec max
=0.85Vmax;VIH=3.65Vmin; I
IL
=1μAmax.
OFF
MAX = 5.25
IN
Functions: Program Lock
Integral Action Lock Auto/Manual Mode Select Setpoint Ramp Enable Reset Alarms Local/Remote Setpoint Select Setpoint 1/Setpoint 2 Select Serial Block Print
-75-
Page 84
11. CONTROL AND ALARM OUTPUTS (Heating, Cooling or Alarm): Relay outputs with Form A contacts
Contact Rating: 3 A @ 250 VAC or 30 VDC (resistive load) Life Expectancy: 100,000 cycles at max. load rating.
(Decreasing load and/or increasing cycle time, increases life expectancy.)
Logic/SSR Drive Outputs (CN63100 only):
Rating: 45 mA @ 4 V min., 7 V nominal Offstate Leakage Current: 7 mA max. @ 60 Hz Operating Frequency: 20 to 400 Hz Protection: Internal transient snubber
12. MAIN CONTROL: Control: PID or ON/OFF Output: Time proportioning or linear DC Cycle time: Programmable Auto-tune: When selected, sets proportional band, integral time, and
derivative time values.
Probe Break Action (CN63100 only): Programmable
13. ALARM: 1 or 2 alarms (model dependent)(optional) Modes:
Absolute high acting Absolute low acting Deviation high acting Deviation low acting Inside band acting Outside band acting
Reset Action: Programmable; automatic or latched Standby Mode: Programmable; enable or disable Hysteresis: Programmable Probe Break Action (CN63100 only): Upscale Annunciator: LED backlight for “A1”, “A2”
14. COOLING/SECOND: Software selectable (overrides alarm 2). Control: PID or ON/OFF Output: Time proportioning Cycle time: Programmable Proportional Gain Adjust: Programmable Heat/Cool Deadband Overlap: Programmable
15. MAIN AND SECOND LINEAR DC OUTPUT: (optional) Main: Control or Re-transmission, programmable update rate from 0.1 sec
to 250 sec
Second: Re-transmission only, fixed update rate of 0.1 sec
Output **
Range
Accuracy *
(18 to 28°C)
Accuracy * (0 to 50°C)
Compliance Resolution
0 to 10 V
0.10% of FS + 1/2 LSD
0.30% of FS + 1/2 LSD
10k ohm min. 1/3500
0 to 20 mA
0.10% of FS + 1/2 LSD
0.30% of FS + 1/2 LSD
500 ohm max. 1/3500
4 to 20 mA
0.10% of FS + 1/2 LSD
0.30% of FS + 1/2 LSD
500 ohm max. 1/2800
* Accuracies are expressed as ± percentages after 20 minute warm-up. Output
accuracy is specified in two ways: Accuracy over an 18 to 28°C range at 10 to 75% RH environment; and accuracy over a 0 to 50°C range at 0 to 85% RH (non-condensing) environment. Accuracy over the wide signal range reflects the coefficient of the internal circuitry.
** Outputs are independently jumper selectable for either 10 V or 20 mA. The
output range may be field calibrated to yield approximate 10% overrange and a small underrange (negative) signal.
16. REMOTE SETPOINT INPUT: (optional) Input type: 0/4 to 20 mA Input Resistance: 10 ohms. Overrange: -5% to 105% Overload: 100 mA (continuous) Scale Range: -999 to 9999 degrees or -99.9 to 999.9 degrees Resolution: 1 part in 10,000 Accuracy:
At 25°C: ±(0.1 % of full scale +1/2 LSD)
Over 0 to 50°C range: ±(0.2% of full scale +1/2 LSD) Reading Rate: 10/sec Setpoint Filtering: Programmable Digital Setpoint Ramping: Programmable, 0.1 to 999.9 degrees/minute.
-76-
Page 85
17. SERIAL COMMUNICATIONS: (optional) Type: RS485 multipoint, balanced interface Baud Rate: 300 to 9600 Data Format: 7O1, 7E1, 7N2, 8N1 Node Address: 0-99, max of 32 units per line Transmit Delay: 2-100 msec or 100-200 msec Data Encoding: ASCII Isolation w.r.t Main Input Common: 500 Vrms for 1 min. (50 V working)
Not isolated w.r.t. Remote Setpoint inputs, or Analog Output common
Note: RS485 and the Analog Output commons are not internally isolated
within the controller. The terminating equipment of these outputs must not share the same common (i.e.. earth ground).
18. ISOLATION BREAKDOWN RATINGS: AC line with respect to all Inputs and outputs: 250 V working (2300 V for 1
minute).
Main input with respect to Analog Outputs, Remote Setpoint Input: 50 V
working (2300 V for 1 minute). All other inputs and outputs with respect to relay contacts: 2000 VAC Not isolated between Analog Outputs, and Remote Setpoint commons.
19. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant UL Recognized Component: File #E123489 Type 4X Enclosure rating (Face only) IP65 Enclosure rating (Face only) IP20 Enclosure rating (Rear of unit)
Refer to the EMC Installation Guidelines section of the manual for
additional information.
20. ENVIRONMENTAL CONDITIONS: Operating Range: 0 to 50°C Storage Range: -40 to 80°C CN63100 Span Drift (maximum): 130 ppm/°C, main input CN63100 Zero Drift (maximum): 1 mV/°C, main input Operating and Storage Humidity:
85% max. relative humidity (non-condensing) from 0°C to 50°C.
Vibration to IEC 68-2-6: 5 to 150 Hz, 2 g. Shock to IEC 68-2-27: Operational 20 g, (10 g relay) Altitude: Up to 2000 meters
21. CONNECTION: Wire clamping screw terminals
22. CONSTRUCTION: Black plastic alloy case and collar style panel latch.
Panel latch can be installed for vertical or horizontal instrument stacking. One piece tinted plastic bezel. Bezel assembly with circuit boards can be removed from the case to change the output board without removing the case from the panel or disconnecting wiring. Unit meets NEMA 4X/IP65 requirements for indoor use when properly installed. Installation Category II, Pollution Degree 2.
23. WEIGHT: 0.38 lbs (0.17 kgs)
-77-
Page 86
CN63100 TEMPERATURE CONTROLLER PART NUMBERS
Options and Output Boards are factory configured per the part number specified. Part numbers without replacement output boards
listed must be returned to the factory for output board replacement.
MODELS WITHOUT RS485 AND LINEAR DC ANALOG OUTPUT
MAIN
ANALOG
OUTPUT**
@
PART NUMBERS
SECOND ANALOG
OUTPUT**
@
REPLACEMENT
OUTPUT BOARD
PART NUMBERS
18 to 36 VDC/
24 VAC
85 to 250 VA
CN63100-R1-R2-AL-C4-LV CN63100-R1-R2-AL-C4
DEDICATED
MAIN CONTROL
O1 OUTPUT
DEDICATED
ALARM 1
A1 OUTPUT
A2 (ALARM 2)
OR
02 (COOL) *
REMOTE
SETPOINT
INPUT@
18 to 36 VDC/24 VAC 85 to 250 VAC
Relay CN63100-R1-LV CN63100-R1 CN6-48100
Relay Relay Relay CN63100-R1-R2-AL-LV CN63100-R1-R2-AL CN6-48111
Relay Relay Relay YES CN63100-R1-R2-AL-RSP-LV CN63100-R1-R2-AL-RSP CN6-48111
Logic/SSR CN63100-DC1-LV CN63100-DC1 CN6-48200
Logic/SSR Relay Relay CN63100-DC1-R2-AL-LV CN63100-DC1-R2-AL CN6-48211
* - These part numbers have a single output, programmable as either Control (PID) or as an Alarm. @ - These part numbers are equipped with a second setpoint.
MODELS WITH RS485 OR LINEAR DC ANALOG OUTPUT
DEDICATED
MAIN
CONTROL
O1 OUTPUT
Relay Relay Relay YES
Logic/SSR Relay Relay YES CN63100-DC1-R2-AL-C4-LV CN63100-DC1-R2-AL-C4
* - These part numbers have a single output, programmable as either Control (PID) or as an Alarm.
** - These part numbers are jumper and program selectable for either a current or voltage Linear DC output.
@ - These part numbers are equipped with a second setpoint.
1
- Replacement Output Board CN6-48100 may be used.
2
- Replacement Output Board CN6-48111 may be used.
MAIN CONTROL
O1 OR A1
(ALARM 1)
DEDICATED
ALARM 1
A1 OUT PUT
(ALARM 2)
A2 OR 02
(COOL) *
REMOTE
SETPOINT
INPUT@
RS485
@
Relay Relay YES YES CN63100-R1-R2-F3-LV CN63100-R1-R2-F3 Relay Relay YES YES CN63100-R1-R2-F3-RSP-LV CN63100-R1-R2-F3-RSP Relay Relay YES YES CN63100-R1-R2-F3-C4-LV CN63100-R1-R2-F3-C4
2
C
-78-
Page 87
CN63300 PROCESS CONTROLLER PART NUMBERS
Options and Output Boards are factory configured per the part number specified. Part numbers without replacement output boards
listed must be returned to the factory for output board replacement.
All part numbers are software version V4.0 or greater. Models with Remote Setpoint Input, RS485, or Main Analog Output or include a
second setpoint.
DEDICATED
MAIN
CONTROL
O1 OUTPUT
MAIN
CONTROL
O1 OR A1
(ALARM 1)*
DEDICATED
ALARM 1
A1 OUT PUT
A2 (ALAR M 2)
A2 OR 02
(SECOND) *
REMOTE
SETPOINT
INPUT@
RS485@
MAIN
ANALOG
OUTPUT**
@
PART NUMBERS
18 to 36 VDC/ 24 VAC 85 to 250 VAC
REPLACEMENT
Relay CN63300-R1-LV CN63300-R1 CN6-48100
Relay Relay YES CN63300-R1-R2-F3-LV CN63300-R1-R2-F3 N/A Relay Relay YES YES CN63300-R1-R2-F3-RSP-LV CN63300-R1-R2-F3-RSP N/A
Relay Relay YES YES CN63300-R1-R2-F3-C4-LV CN63300-R1-R2-F3-C4 N/A Relay Relay Relay CN63300-R1-R2-AL-LV CN63300-R1-R2-AL CN6-48111 Relay Relay Relay YES CN63300-R1-R2-AL-C4-LV CN63300-R1-R2-AL-C4 CN6-48111
* - These part numbers have a single output, programmable as either Control (PID) or as an Alarm. ** - These part numbers are jumper and program selectable for either a current or voltage Linear DC output. @ - These part numbers are equipped with a second setpoint.
-79-
OUTPUT
BOARD
Page 88
-80-
Page 89
-81-
Page 90
-82-
Page 91
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 25 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal two (2) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
Page 92
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2006 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems relative to the product.
M4495/0313