Omega CN38S User Manual

2.1 - MOUNTING REQUIREMENTS
This instrument is intended for permanent installation, for indoor use only, in an electrical panel which encloses the rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1) It should be easily accessible;
2) There is minimum vibrations and no impact;
4) There are no water or other fluid (i.e. condensation);
5) The ambient temperature is in accordance with the opera­tive temperature (0 to 50 °C);
6) The relative humidity is in accordance with the instrument specifications (20% to 85
%).
The instrument can be mounted on panel with a maximum thickness of 15 mm. When the maximum front protection (IP65) is desired, the optional gasket must be mounted.
2.2 - GENERAL NOTES ABOUT INPUT WIRING
1) Do not run input wires together with power cables;
2) External components (like zener barriers, etc.) connected between sensor and input terminals may cause errors in measurement due to excessive and/or not balanced line resistance or possible leakage currents;
3) When a shielded cable is used, it should be connected at one point only;
4) Pay attention to the line resistance; a high li
ne resistance
may cause measurement errors.
2.3 - THERMOCOUPLE INPUT
Fig. 3 - Thermocouple input wiring External resistance: 100 max., max. error 0.5% of span. Cold junction: automatic compensation from 0 to 50°C. Cold junction accuracy: 0.1 °C/°C after a warm-up of 20
minutes.
Input impedance: > 1 M. Calibration: according to EN 60584-1.
Note: Por TC wiring use proper compensating cable preferable
shielded.
2.4 - PT100 INPUT
Fig. 4 - PT100 input wiring Input circuit: current injection (135 µA). Line resistance: not compensated. Calibration: according to EN 60751/A2.
2.5 - PTC/NTC/
PT1000 INPUT
Fig. 5 - PTC/NTC/PT1000 input wiring Input circuit: current injection (25µA). Line resistance: not compensated.
2.6 - OUTPUTS Safety notes:
1) To avoid electrical shock, connect supply cables last.
2) For supply connections use 16 AWG or larger wires rated for at last 75°C.
3) Use copper conductors only.
4) SSR (Solid State Relay) Outputs are NOT isolated. A double or reinforced isolation between instrument output and power supply must be assured by the external solid state relay.
a) Output 1 Relay Contact rating: 8 A /250 V cosϕ =1
3 A /250 V cosϕ =0.
4
Operations: 1 x 10
5
SSR Logic level 0: Vout < 0.5 Vdc
Logic level 1: 12 V ±20% @ 1 mA
10 V ±20% @ 20 mA.
b) Output 2 Relay Contact rating: 8 A /250 V cosϕ =1
3 A /250 V cosϕ =0.4
Operations: 1 x 10
5
SSR Logic level 0: Vout < 0.5 Vdc
Logic level 1: 12 V ±20% @ 1 mA
10 V ±20% @ 20 mA.
2.7 - POWER SUPPLY
Power consumption: 5VA max. Supply voltage:
100 V to 240 VAC/DC (+10%) 12 VDC (-15% to +10%) 24 VAC/DC (-15% to +10%)
Notes:
1) Before connecting the instrument to the electrical supply, make sure that line voltage is equal to the voltage shown on the identification label.
2) To avoid electrical shock, connect supply cables at the end of the wiring procedure.
3) For supply connections use 16 AWG or larger wires rated for at last 75°C.
4) Use copper conductors only.
5) Do not place signal cables parallelly or next to power cables or to noise sources.
6) The power supply input is NOT fuse protected. Please, provide a T type 1A, 250 V fuse externally.
7) For DC power supply the polarity is a do not care condition.
3.1 - TECHNICAL SPECIFICATIONS
Case:
Plastic, self-extinguishing degree: V-0 according to UL 94.
Front protection: IP 65 (when the optional panel gasket is mounted) for indoor locations according to EN 60070-1.
Rear terminals protection: IP 20 according to EN 60070-1. Installation: Panel mounting. Terminal block: 11screw terminals (screw M3, for cables from
0.25 to 2.5 mm
2
or from 22 AWG to 14 AWG).
Dimensions: 75 x 33 mm, depth 75.5 mm. Cutout: 71 (-0 to +0.5 mm) x 29 (-0 to +0.5 mm). Weight: 180 g approximately. Insulation voltage: 2300 V rms according to EN 61010-1. Display: one 3 digits red display h 12 mm. Display updating time: 500 ms. Sampling time: 130 ms. Resolution: 20000 counts. Total Accuracy: +0.5% E.S.V. +1 digi
t @ 25°C of room temp..
Electromagnetic compatbility and safety requirements: Compliance:directive EMC 2004/108/CE (EN 61326-1),
directive LV 2006/95/CE (EN 61010-1).
Installation category: II. Pollution category: 2. Temperature drift: It is part of the global accuracy. Operating temperature: 0 to 50°C (32 to 122°F). Storage temperature: -30 to +70°C (-22 to 158°F). Humidity: 20% to 85% RH, non condensing.
3.2 - HOW TO ORDER
Model
CN38S =
Controller with S-touch keyboard (capacitive keyboard)
Input:
T = TC J or K RTD = PT100 TH = PTC, NTC or PT1000
Output Out1:
R1 = SPDT 8A-AC1
relay
DC1 = VDC for SSR.
Output Out2:
R2 = SPDT 8A-AC1 relay DC2 = VDC for SSR.
Power supply:
(none)
= 100... 240 VAC
12V = 12 VDC not isolated 24V = 24 VAC/DC.
4.1 - INTRODUCTION
When the instrument is powered, it initially works according to the parameter values loaded in its memory. The instruments behavior and its performance are governed by the value of the stored parameters. At the first start up the instrument will use a "default" parameter set (factory parameter set); this set is a generic one (e.g. a TC J input is programmed). We recommend that you modify the parame
ters to suit your ap­plication (e.g. set the right input type, Control strategy and define an alarm, etc.). To change these parameters you will need to enter the "Configuration procedure".
4.2 - INSTRUMENT BEHAVIOUR AT POWER UP
At power up the instrument can start in one of the following modes depending on its configuration:
Auto mode
- The display will show the measured value;
- The instrument is performing the standard loop control.
Stand by mode (St.bY)
- The display will show alternately the measured value and
the message <<St.bY>> or <<od>>;
- The instrument does not perform any control
(the control
outputs are OFF);
- The instrument is working as an indicator.
We define the above conditions as "Standard Display".
4.3 - FRONT PANEL DESCRIPTION
1 - Key
- Pressed for 5 s, it allows access to the parameters pro-
gramming mode.
- In the programming mode, it is used for the change of the
parameters and for the confirmation of the values.
- Still in the programming mode, it can be used together with
the key to modify the level of access (operator level or configuration level) of the selected parameter.
- During the normal functioning (no
t in programming phase),
pressed together with the key for 5 s, it allows to lock and unlock the keyboard.
- During the normal functioning (not in programming phase),
pressed together with the key for 5 s, it allows the reset or the acknowledgement of the alarms.
2 - Key
-
In the programming mode, it is used for to decrease the values to be programmed and for the selection of the parameters.
- During the normal functioning (not in programming phase),
quickly pressed, it allows to visualize and to modify the value of the set poin
t.
3 - Key
- In the programming mode, it is used to increase the values
to be programmed and for the selection of the parameters.
-
Kept pressed for 3 s in the programming mode it can be used to exit from it and come back to the normal functioning.
- Still in the programming mode, it can be used together with
the P key, to modify the level of access (operator level or configuration level) of the selected parameter.
- Pressed together with the key for 5 s, it unlocks the
keyboard, when previously locked.
- Du
ring the normal functioning (not in programming phase),
quickly pressed, it allows to visualize the output power.
4 - Key
-
If programmed through par. "ub.F", pressed for 1 s in the normal functioning mode, it allows the switch on/off (Stand­by) or to perform one of the possible functions (to start a cycle of Autotuning, etc.).
-
During the normal functioning (not in programming phase),
pressed together with the key for 5 s, it allows the reset or the aknowledgement of the alarms.
5 - LED Set
- In the programming
mode, it is used for indicating the level
of programming of parameters.
- If ub.F = Sb.o, when the instrument is in Stand-by mode, it
remains the only lit LED.
- In the normal functioning mode, it flashes when a key is
pressed to indicates the pressure has happend on the key.
6 - LED Out1
- It indicates the Out 1 condition ( compressor or tempera-
ture control device) activated (on), deactivated (off) or inhibited (flashing).
7 - LED Out2
- It indicates the Out 2 condition.
8 - LED Tun
- It indicates the Autotuning is in progress.
4.4 - HOW TO ENTER THE CONFIGUR
ATION
PARAMETERS
Press key and keep it pressed. Condition 1: the instrument will show "Ln" (lock ON). The keyboard is locked. Mantaining the pressure on the key, also press the key. The LED Set begins to flash. Keep the pressure on the two. Keep the pressure on the two keys until the display shows "LF" (lock OFF). Now release the keys. The keyboard is now unlocked.
Note: If no button is pressed for a time longer than the time
programmed with the Lo parameter, the key lock will be automatically enabled.
Condition 2: The instrument displays no message. In this situation we can have 2 different cases
:
Case 1: The parameters protection (password) is not active. Press key and keep it pressed for around 5 seconds. The display will show the code of the first configuration parameter. With the
and
keys, select the parameter to be edited.
Case 2: The parameters protection (password) is active. Press key and keep it pressed for more than 5 seconds. The display will show the code that identifies the first parameter that has been moved into the Operator level. Press key. The display will visualize "r.P". Press P key again. The display will show "0". With the and
keys, program the password and confirm
it pushing key again.
Note: the factory default pa
ssword is 0 (no password).
2.A) If the password is correct, the instrument will show the
code that identifies the first configuration parameter.
2.B) If the password is not correct, the instrument will show "r.P"
again.
a) Once entered into the configuration parameters, select the
parameter to be modified using the and
keys.
b) Press key. The instrument will alternatively visualize
the parameter's code and its value.
c)
Modify the value of the parameter using the and keys.
d) Press key to memorize the new value. The display will
return to visualize on
ly the code of the selected parameter.
e) Working on and keys, it is therefore possible to
select another parameter and to modify it as described on points a, b, c, d.
Note: The instrument will only show the parameters applicable
to its hardware options in accordance with the specific instrument configuration (i.e.setting AL1t [Alarm 1 type] equal to <<nonE>> [not used], all parameters related with the alarm 1 will be skipped).
To go out from the programming mode do not work on any key for around 30 s, or press key for around 5 s.
4.5 - PARAMETERS PROTECTION THROUGH A PASSWORD
The instrument has a function that protects the parameters through a password, programmable through parameter "PP."
If you wish to have this protection, you have to set parameter "PP" to the number you'd like to be your password and then exit from parameters programming
.
When the protection is active, to be able to have access to the parameters, press key and keep it pressed for around 5 s. Afterwards, the display will visualize "r.P" , push the key again and the display will visualize "0." Now, through the and
keys, set the number of your
password and press key. If the password is correct the display will visualize the code that
identifies the first parameter and it will be possible to program it with the same procedure as described on the previous paragraph.
The protection through password is disabled setting par. "PP" = oF.
Note: If the password is forgotten, use password -18. This will
allow you access to the protected parameters and it will be possible therefore to verify and also modify the parameter "PP."
4.6 - CUSTOMIZED PARAMETERS PROGRAMMING (levels of parameters programming)
The factory programming makes hides all the parameters behind the password with exception of the set point 1.
If you wish to modify some parameters, maintaining the protection on the others, after setting the Password through parameter "PP", it is necessary to follow this procedure:
a) Enter the
programming through the Password.
b)
Select the parameter to be programmable without password.
c.1) The LED Set is flashing.
- the parameter is protected by the password.
c.2) The LED Set is lit but not flashing.
- The parameter is not protected by the password.
To modify the level of access of the parameter (in other words: to have the parameter protected or not by the password) press the key and keeping it pressed press the key.
The LED Set will change its state, pointing out the new level of accessibility of the parameter (switched on = not protected; flashing = protected
by password).
If the Password is enabled and some parameters have been set as "not protected", when entering the programming the instrument will first display all the parameters set as "not protected" and then, "r.P" parameter. By entering the password here all other parameters can be viewed.
4.7 - FACTORY RESET (default parameters loading procedure)
It is possible to restore the instruments factory configuration. To load the factory default parameter settings, proceed as follows:
- Enter in configuration mode (see 4.4 paragraph).
- If no password is programmed, set PP different from OFF.
- Exit from configuration procedure.
- Press the button for more than 7 seconds. The display
will show "rP".
- Release the button and push it again. The display will
show "0".
- By means of keys and
set the value -48.
Once the password has been confirmed by pressing the key, the display shows for approximatively 2 s "---", the instruments then runs through the start up procedure resetting all the parameters to the factory defaults.
4.8 - ON/STAND-BY FUNCTION
When supplied, the instrument can assume 2 different conditions:
- ON: means that the regulator activates the programmed
control functions.
- STAND-BY: means that the regulator does not activate any
control function and the control outputs are forced to zero (the display results switched on or off according to the pro-
gramming done on parameter ub.F). The instrument starts in the same way it was before the switch off. The condition of ON/STAND-BY can be selected through the
key when pressed for 1 s.
The passage from the STAND-BY to the ON condition, does not activate the Soft-start (or od) or the Autotuning and hides the alarms.
When the ins
trument is in STAND-BY mode with the display on the display alternates between the measure value and "St.b." When the instrument is in STAND-BY with display off, the dis­play is completely switched off except for the decimal point of the LSD (LED Set (5)). When the instrument is in STAND-BY mode (both the visualiza­tions) it is however possible to enter the parameters programming.
4.9 - ALL CONFIGURATION PARAMETERS
In the following pages we will describe all the parameters of the instrument. However, the instrument will only show the parameters applicable to its hardware options in accordance with the specific instrument configuration (i.e.setting o2F [Alarm] equal to <<no>> [not used], all parameters related with the alarm will be skipped).
[1] SPL: Minimum Set Point value Range: from -99.9 to SPH engineering units. [2] SPH: Maximum Set Point value Range: from SPL to 999 engineering units. [3] SP1: Set Point Range: from SPL to SPH engineering units. [4] SP2: Second Set Point
Note:
When 2 control outputs are programmed with ON/OFF action, the instrument uses SP1 to command OUT1 and SP2 (see following parameter) to command OUT2.
Available:
When Out 2 has been programmed as control output.
Range: from SPL to SPH engineering units. [5] AL : Alarm threshold Available: when Out 2 has been programmed as alarm. Range: -99.9 to 999 engineering units.
1. OUTLINE DIMENSIONS (mm)
2. CONNECTION DIAGRAM
Vr. 1 (ENG) - code.: ISTR-FCN38SENGOG1
OMEGA Enineering, Inc.
One Omega Drive, P.O. Box 4047
Stamford, Connecticut 06907-0047
Phone: (800) 848-4286 or (203) 359-1660
Fax: (203) 359-7700
34
64
28
5.575
35
Type 1
panel gasket
Type 2
panel gasket
max. 29 mm
max. 12 mm
Out2
Out1 Tun
AL
CN38S
POW ER SUPPL Y
+
1 3 24
C
11
INPUT S
PTC/ NT C
86 5
OUT 1
NO
7 12
OUT 2
R3 8
Relays: 8 A- AC1 (6A- AC3)/250 VAC
Pt100/PT1000
tc
NC NO
C
10
+- +-
NC
SSR: 10 VDC/ 20 mA
11
12
+
-
11
12
+
-
RTD
11
12
+
-
PTC/N TC/PT1000
3. TECHNICAL CHARACTERISTICS
4. CONFIGURATION PROCEDURE
4C6
5
NONC
+ -
4 65
1C3
2
NON C
+ -
1 32
7
8
Power supply
CN38S - -
Input Out1-Out2-Power supply
5
1
2
3
4
Out2
Out1 Tun
AL
CN38S
Normal Mode
Password request Insert correct
password
Increase value
Decrease value
Parameters
(Program mode)
CN38S
Microprocessor Based Digital Electronic Controller
INSTRUCTION
SHEET
M5309/1114
Shop online at: www.omega.com e-mail: info@omega.com
For latest product manuals: www.omegamanual.info
Made In Italy
[6] tun = Autotuning Available: when o1.F = PID
ALL = the Autotuning is performed at every start up and
parameters Pb, Ti and Td are hidden. onE = the Autotuning is performed only at the next start up. ub = Manual start up through key (parameters Pb, Ti and
Td are visible).
Note: When the Autotuning and the soft start, or the delay at
the start up, have been programmed, the instrument
performs first the soft start (with the parameters it has in
memory) and then performs the Autotuning.
[7] Pb = Proportional band Available: when o1F=PID and tun = ub
.
Range: from 1 to 999 engineering units. [8] ti = Integral time Available: when o1F=PID and tun = ub. Range: from 1 to 500 seconds and OFF (excluded). [9] td = Derivative time Available: when o1F=PID and tun = ub. Range: from 0 (= OFF) to 200 seconds. [10] SEn = Input type
[11] dP = Decimal point Range: YES = Autoranging display;
nO = display without decimal point.
[12] CA = Offset on the displayed value Range: -300 to 300 engineering units. [13] Ft = Filter on the displayed value Range: from 0 (OFF) to 20 seconds. [14] o1F = Out 1 function Range: H.rE = PID control with heating action (reverse)
; C.rE = PID control with cooling action (direct); on.H = ON/OFF control with heating action (reverse); on.C = ON /OFF control with cooling action (direct).
[15] tr1 = Out 1 cycle time Range: from 1 to 250 seconds. [16] o2F = Out 2 function Range:
- When o1F is equal to H.rE or C.rE:
no = Not used HAL = Absolute high alarm; LAL = Absolute low alarm; b.AL = Band alarm (simmetric to the set point); dHA = Deviation high alarm; dLA = Deviation low alarm.
- When o1F = on.H or on.C:
no = Not used; HAL = Absolute high alarm ; LAL = Absolute low ala
rm; b.AL = Band alarm (simmetric to the set point); dHA = Deviation high alarm ; dLA = Deviation low alarm; SP.C = SP2 - ON /OFF control with cooling action ; SP.H = SP2 - ON /OFF control with heating action ; nr = ON/OFF Neutral Zone (o2F will make the opposite action to the one programmed on o1F, while the hysteresis [par. d1] becomes the neutral zone).
Note:
The Neutral Zone functioning is used to control the plants with an element that causes a positive increase (ex. Heating, Humidifying etc.) and an elemen
t that causes a
negative increase (ex. Cooling, Dehumidifying etc.).
The control works on the programmed outputs depending on the measure, on the active Set point "SP", and on the programmed hysteresis "d1".
The regulator works in the following way: it switches off the outputs when the process value reaches the Set and activates the heating output when the process value is lower than [SP-d1], or it switches on the cooling output when the process value is higher than [SP+d1].
Accordingly, the element that causes positive increase must be connected to the output pr
ogrammed as heating, while the element of negative increase must be connected to output programmed as cooling.
Table of the possible combinations
[17] d1 = Out 1 hysteresis or neutral zone Available: when Out 1 is equal to hn.H or on.C. Range: 0.1 to 999 engineering units. [18] d2 = Out 2 hysteresis Available: when o2F is different from nr. Range: 0.1 to 999 engineering units.
[19] AL.F = Alarm function Available:
when o2F is programmed as alarm output.
Range: AL = Automatic reset Alarm;
AL.n = Latched Alarm; AL.A = Aknowledgeable Alarm.
AL = Automatic reset Alar
m
AL.n = Latched Alarm
AL.A = Acknowledgeable alarm
[20] AL.t = Inhibition time of the alarm at the start up or after a change of set point
Range: from 0 = OFF (any hidding) to 9.59 HH.mms
Note: When the measure reaches the alarm threshold, the
instrument disables the hidding of the alarm.
[21] Pct = Compressor protection time
The protection prevents the output cycling and therefore reduces relay wear by waiting for the time setting to elapse before allowing a subsequent switching of the output.
In other words, it defines the minimum time that will pass between the switch off of a cooling
output and its following reactivation.
Available:
if at least one output is programmed as cooling output.
Range: from 0=OFF to 9.59 HH.mm
Note: This parameter has effect to ALL the cooling outputs. [22] SSt = Soft start time Range: 0=OFF to 9.59 HH.mm.
Note: When the control is ON/OFF type, the time of the soft
start becomes an output time delay, the power is forced to 0 and the parameter SSP is hidden.
[23] SSP = Power during Soft Start Available: when Sst is different from 0. Range: 0 to 100%.
Note: if programmed = 0, also the alarms and/or the second
control output remains = 0 and
the instrument visualizes
"od" for the programmed time.
[24] ub.F = key function Range: no = No function
Tun = It activates the manual tuning; Sb = Stand-by mode; Sb.o = Stand-By mode with display off.
[25] PP = Parameters protection Password Range: 1 to 999. [26] Lo = Time for the Key lock automatic enable
This parameter allows to set the time that the instrument will wait before to automatically enable the key lock. The time count will re-start after a key pressure.
Range: from OFF (lock disabled) to 30 minutes.
5.1 - OUT OF RANGE SIGNALS
The display shows the OVER-RANGE
and UNDERRANGE
conditions with the following indications:
The sensor break will be signaled as follows:
Note: When an over-range or an under-range is detected, the
alarms operate as in presence of the maximum or the minimum measurable value respectively.
To check the out of span Error condition, proceed as follows:
1) Check the input signal source and the connecting line;
2) Make sure that the input signal is in accordance with the instrument configuration. Otherwise, modify the input con­figuration (see section 4).
3) If no error is detected, send the instrument to your supplier to be
checked.
5.2 - L
IST OF POSSIBLE ERRORS AtE - Auto-tune not finished within 12 hours. EPr - Possible problem of the instrument memory.
The messages disappears automatically. When the error continues, send the instrument to your supplier.
6.1 - PROPER USE
Every possible use not described in this manual must be considered as a improper use.
This instrument is in compliance with EN 61010-1 "Safety requirements for electrical equipment for measurement, control and laboratory use"; for this reason it must not be used as a safety equipment.
Whenever a failure or a malfunction of the con
trol device may cause dangerous situations for persons, thing or animals, please remember that the plant has to be equipped with additional safety devices. OMEGA Engineering Inc. and its legal representatives do not assume any responsibility for any damage to people, things or animals deriving from violation, wrong or improper use or in any case not in compliance with the instrument's features.
6.2 - WARRANTY AND REPAIRS
We warrant that the products will be free from defects in material and workmanship for 18 months from the date of delivery. Prod­ucts and components that are subject to wear due to conditions of use, serv
ice life, and misuse are not covered by this warranty.
The warranty is limited to repairs or to the replacement of the instrument.
The tampering of the instrument or an improper use of the product will bring about the immediate withdrawal of the warranty's effects. In the event of a faulty instrument, either within the period of war­ranty or further to its expiry, please contact our sales department to obtain authorisation for sending the instrument to our company. The faulty product must be shipped to OMEGA Engineering with a detailed description of the faults found, without any fees or charge for OMEGA Engineering, except in the event of alternative agreements.
Before supplying tension to the instrument, make sure that it is perfectly dry.
Model Selection Sensor Measuring range
F J .C TC J -40 to 999 °C
Ca.C TC K -40 to 999 °C
J .F TC J -40 to 999 °F
Ca.F TC K -40 to 999 °F
A Pt.C PT 100 -50.0 to 850 °C (autoranging)
Pt.F PT 100 -58.0 to 999 °F (autoranging)
T nC.C NTC -50.0 to 109 °C (autoranging)
PC.C PTC -50.0 to 150 °C (autoranging)
nC.F NTC -58.0 to 228 °F (autoranging)
PC.F PTC -58.0 to 302 °F (autoranging)
P1.C Pt 1000 -50.0 to 850 °C (autoranging)
P1.F Pt 1000 -58.0 to 999 °F (autoranging)
O1F O2F
Displayed
parameters
H.rE H.AL, L.AL, b.AL, dHA, dLA SP1, AL
C.rE H.AL, L.AL, b.AL, dHA, dLA SP1, AL
on.H H.AL , L.AL, b.AL, dHA, dLA SP1, AL
2PS ,1PSH.PS ,C.PS
ylno 1pSrN
on.C H.AL , L.AL, b.AL, dHA, dLA SP1, AL
2PS ,1PSH.PS ,C.PS
ylno 1PSrN
0N
O2F = nr (heating)
O1F = on.H (heating)
SP
PV
OFF
0N
OFF
time
D1
D1
OFF OFF
0N
5. ERROR MESSAGES
Time
Measure
Meas
Alx
Alarm hysteresis
Status
ON
OFF
Time
Automatic reset
Automatic
Time
Measure
Meas
Alx
Alarm hysteresis
Status
ON
OFF
Time
Manual reset
Manual reset
Latched
Time
Measure
Ambient temp.
Alx
Alarm hysteresis
Status
ON
OFF
Time
Automatic reset
ACK
Acknowledgeable
Over range Under range
Sensor break
6. GENERAL NOTES
7. PARAMETERS TABLE
no. Par. Description Range Default
Protec-
tion
1 SPL Minimum Set
Point value
From –99.9 to SPH E.U.
-99 Yes
2 SPH Maximum Set
Point value
From SPL to 999 E.U.
999 Yes
3 SP1 Set point From SPL to SPH
E.U.
0 No
4 SP2 Second Set
Point
From SPL to SPH E.U.
0 Yes
5 AL Alarm thres hold From – 99.9 to 999
E.U.
0 Yes
6 tun Autotuning ALL =Performed at
every start up onE =Performed at the first start up ub = Performed when U key is pressed
onE Yes
7 Pb Proport ional
Band
From 1 to 999 E.U. 50 Yes
8 t
i Integral time From 1 to 500
seconds and OFF
100 Yes
9 td Derivative time From 0 (OFF) to
200 seconds
25 Yes
10 SEn Input type
F type
A
type
T type
JC = TC J (°C) CA.C = TC K (°C) JF = TC J (°F) CA.F
= TC K (°F)
Pt.C = PT 100 (°C) Pt.F = PT 100 (°F)
nC.C = NTC (°C) PC.C = PTC (°C) nC.F = NTC (°F) PC.F = PTC (°F) P1C
= PT 1000 (°C)
P1F = PT 1000 (°F)
J.C
Pt.C
nC.C
Yes
11 DP Decimal point
YES
= Autoranging
visualization no = Visualization without decimal point
no Yes
12 CA Offset on the
displayed value
From -300 to 300 E.U.
0 Yes
13 Ft Filter on the
displayed value
From 0 (OFF) to 20 seconds
0 Yes
14 O1F Out 1 function H.rE = PID control
with heating action C.rE = PID control with cooling action on.H = ON/OFF control wi
th
heating action on.C = ON/OFF control with cooling action
HrE Yes
15 tr1 Out 1 cycle time From 1 to 250
seconds
30
Yes
no. Par. Description Range Default
Protec-
tion
16 o2F Out 2 function
When o1F = H.rE or C.rE
When o1F = on.H or on.C
no = Not used HAL = Absolute
high alarm LAL = Absolute low alarm b.AL = Band alarm (simmetric to the set point) dHA = Deviation high alarm dLA = Deviation low alarm
no = Not used HAL = Absolute
high alarm LAL = Absolute low alarm b.AL = Band alarm (simmetric
to the
set point) dHA = Deviation high alarm dLA = Deviation low alarm SP.C = SP2 ON /OFFcontrol with cooling action SP.H = SP2 ON /OFF control
with heating action nr = ON/OFF neutral zone
No Yes
1
7 d1 Out 1 hysteresis
or neutral zone
From 0.1 to 999 E.U.
1 Yes
18 d2 Out 2 hysteresis From 0.1 to 999
E.U.
1 Yes
19 ALF Alarm function AL = Automatic
reset Alarm AL.n = Latched Alarm AL.A = Aknowledgeable Alarm
AL
Yes
20 ALt Inhibition time
of the alarm at the start up or after a change of set point
From 0 (OFF) to
9.59 HH.mm
0 Yes
21 Pct Compressor
protection time
From 0 (OFF) to
9.59 HH.mm
0 Yes
22 Sst Soft start time From 0 (OFF) to
9.59 HH.mm
0 Yes
23 SSP Power during
Soft Start
From 0 to 100% 0 Yes
24 UbF
key
function
no = No function Tun = It activates
the manual tuning Sb = Stand-by mode Sb.o = Stand-By mode with display off
tun Yes
25 PP Pa
rameters protection Password
From 1 to 999 0 Yes
26 Lo Key lock time
out
From 0 (key lock disabled) to 30 minutes
0 Yes
TEMPERATURE
Thermocouple, RTD & Thermistor
Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD &
Thermistor
Calibrators & Ice Point References Recorders, Controllers & Process
Monitors
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
Transducers & Strain Gages Load Cells & Pressure Gages Displacement Transducers Instrumentation & Accessories
FLOW/LEVEL
Rotameters, Gas Mass Flowmeters
& Flow Computers
Air Velocity Indicators Turbine/Paddlewheel Systems Totalizers & Batch Controllers
pH/CONDUCTIVITY
pH Electrodes, Testers & Accessories
Benchtop/Laboratory Meters
Controllers, Calibrators, Simulators
& Pumps
Industrial pH & Conductivity Equipment
DATA ACQUISITION
Data Acquisition & Engineering Software
Communications-Based
Acquisition Systems
Plug-in Cards for Apple, IBM
& Compatibles Data Logging Systems
Recorders, Printers & Plotters
HEATERS
Heating Cable Cartridge & Strip Heaters Immersion & Band Heaters
Flexible Heaters
Laboratory Heaters
ENVIRONMENTAL MONITORING AND CONTROL
Metering & Control Instrumentation Refractometers Pumps & Tubing Air, Soil & Water Monitors
Industrial Water & Wastewater Treatment
pH, Conductivity & Dissolved
Oxygen Instruments
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
sm
It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification. The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING: These products are not designed for use in, and should not be used for, human applications.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2014 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product. If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specifica­tion; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS:
Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
Servicing North America:
U.S.A.:
Omega Engineering, Inc., One Omega Drive, P.O. Box 4047
Stamford, CT 06907-0047 US A
Toll-Free: 1-800-826-6342 (USA & Canada only) Customer Service: 1-800-622-2378 (USA & Canada only) Engineering Service: 1-800-872-9436 (USA & Canada only) Tel: (203) 359-1660 Fax: (203) 359-7700 e-mail: info@omega.com
For Other Locations Visit omega.com/worldwide
omega.com info@omega.com
Loading...