5
CMDP Protocol Setup
No special soware is needed. User can use either the Tera Term program or the HyperTerminal program
on their PC. Connect the RS232 connecon from the Dew Tran and using a USB converter connect to your
PC.
Protocol conguraon: Baud rate 19.2K, 8 Bits, 1 stop Bit, No parity To access the menu, hit the “esc”
The Cap lock key must be on when selecng commands.
Calibrang Current Outputs:
There are 2 methods for calibrang the 4-20 mA outputs. Method 1 uses a digital ammeter, capable of 1
uA. Resoluon. The second method uses high precision (.005%) Resistor(s), In range of 10 – 750 ohms.
The factory Calibraon is done using 100.00 ohm resistors. For output 1, connect Ammeter across BLACK
Wire and RETURN.
From normal operaon, enter following keystrokes:
<ESC> <C>hange <O>utputs <C>alibrate <C>urrent at the “Sense Resistor Value (Y/N) OHMS?” Prompt,
enter <N> Enter<1> for Current output 1.
The prompt “4 mA. = ?, enter the value displayed on Ammeter, as mA’s Connue for the next 2 prompts
(12 mA. and 20 mA.)
The prompt “4 mA. = 1XXXX” is displayed, check Ammeter for 4.00 mA. reading.
Press <CR> to sequence (8, 12, 16 ,20 mA.) Values, with corresponding Ammeter Readings. If calibrated
values good, at “Save Calibraon (Y/N)?, enter<Y>.
Operaons
There are two ways to determine if the sensor is operang/properly funconing.
Reminder: When the unit is rst powered on, the unit will take 3-5 minutes to control. Typically, the unit
goes through what we call an ARC condion. Which is a balancing cycle, the unit inial heats up, then
goes into an acquiring mode (hunng for the dew point) and then the control mode.
1) If you are using the RS232, output you can view the data via your computer to see if the unit is in
control. The data will be streamlined on your PCs and you will see the word “control” at the end of each
line.
2) Another method is by viewing the red light on the PCB. If the red light is in a steady state (always on),
the unit is in control.
3) If the red light is blinking, the unit is most likely in one of these three states.
a. The unit was just powered on and is going through its ARC cycle for 3-5 minutes.
b. The mirror is dirty (has contaminants on it) and it needs to be cleaned. Refer to the clean
mirror procedure.
c. If the above 2 steps do not remove the blinking red light condion, the unit could be out of
range to measure that dew point/frost point. (Ex: if your ambient condion is 25C and your dew
points is below -20C, the unit can not measure that dew point (red light will blink). A way to
correct that is to lower the body temperature of the sensor to a point where the dew point is
measurable with this unit.