Series CDTA and CDTC Communicating Carbon Dioxide Detector
BACnet Protocol Implementation Conformance Statement
Date 12/18/2013 Vendor Name Dwyer Instruments, Inc.
Product Name CDTA, CDTC Application
Product
Module Number
Product
Description
BACnet Standardized Device Prole (Annex L): BACnet Application Specic Controller (B-ASC)
List all BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B DS-RPM-B
DS-WP-B DS-COV-B
DM-DDB-B DM-DOB-B
DM-DCC-B DM-RD-B
Segmentation Capability: None
Standard Object Types Supported: (See Table 1)
CDTA-2N000(-LCD)
CDTA-5N000(-LCD)
CDTC-2N000(-LCD)
CDTC-5N000(-LCD)
All-in-One CO2/RH/
Temp /SetPoint IAQ
Software Version
Firmware
Revision
BACnet Protocol
Revision
1.6
1.5
12
Bulletin AQ-CDTA-CDTC-PIC
Data Link Layer Options:
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 57600, 76800, 115200
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)
Networking Options: None
Network Security Options: Non-secure Device - is capable of operating without BACnet Network Security
Character Sets Supported: ISO 10646 (UTF-8)
Gateway: This product does not support gateway functionality for any types of non-BACnet equipment/network(s).
Yes No

TABLE 1: STANDARD OBJECT TYPES SUPPORTED
Object
Device 607xxx –
“CDTA IAQ 607xxx”.
Where xxx defaults to the
selected MS/TP address.
Analog Input 1 –
“CO2 Concentration”
Analog Input 2 –
“Relative Humidity”
Analog Input 3 –
“Temperature”
Analog Value 1 –
“Set Point”
Analog Value 2 –
“Set Point Low Limit”
Analog Value 3 –
“Set Point High Limit”
Analog Value 4 –
“Dew Point”
Analog Value 5 –
“Wet Bulb”
Analog Value 6 –
“Specic Enthalpy”
Analog Value 7 –
“Display Mode”
Analog Value 8 –
“CO2 Offset”
Analog Value 9 –
“Barometric Pressure”
Analog Value 10 –
“Relative Humidity Offset”
Analog Value 11 –
“Temperature Offset”
Binary Value 1 –
“Override”
Binary Value 2 –
“Use SI Units
Create Object
Service
No No Description, Location, Max_Master,
No No Reliability,
No No Reliability,
No No Reliability,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Out_Of_Service,
No No Reliability Out_Of_Service,
No No Reliability Out_Of_Service,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
Delete Object
Service Optional Properties Supported
Max_Info_Frames,
Active_COV_Subscriptions
COV_Increment
COV_Increment
COV_Increment
Writable
Properties
Description,
Location,
Max_Master,
Max_Info_Frames,
Object_Identier,
Object_Name,
APDU_Timeout,
Number_Of_APDU_Retries
Out_Of_Service,
COV_Increment
Out_Of_Service,
COV_Increment
Out_Of_Service,
Units, COV_Increment
Out_Of_Service, Units
Out_Of_Service, Units
Out_Of_Service, Units
Units
Units
Units
Out_Of_Service
Out_Of_Service
Out_Of_Service,
Units
Out_Of_Service
Out_Of_Service,
Units
Out_Of_Service
Out_Of_Service
Proprietary
Properties
1000
(Serial Number)
None Units: parts-per-million,
None Units: percent-rela-
None Units: Celsius or
None Units: Celsius or
None Units: Celsius or
None Units: Celsius or Fahr-
None Units: Celsius or
None Units: Celsius or
None Units: kilojoules-per-ki-
None Units: No-units
None Units: parts-per-million,
None Units: hectopascals or
None Units: Percent-rela-
None Units: Celsius or
None None
None Active = SI Units,
Property Range
Restrictions
String length maximum
32 characters
Range depends on
model
tive-humidity
Fahrenheit
Fahrenheit 0-50°C
Fahrenheit 0-50°C
enheit 0-50°C
Fahrenheit
Fahrenheit
logram-dry-air or btusper-pound-dry-air
Integer values 0 – 7
±500ppm
inches-of-mercury
677-1016 hPa
tive-humidity
±30% in 0.1% increments
Fahrenheit
±30° in 0.1° increments
Inactive = US Customary Units
Printed in U.S.A.8/22 FR# 444131-30 Rev. 1©Copyright 2022 Dwyer Instruments, Inc.