Omega CDTA, CDTC User guide

Page 1
Series CDTA and CDTC Communicating Carbon Dioxide Detector
BACnet Protocol Implementation Conformance Statement
Date 12/18/2013 Vendor Name Dwyer Instruments, Inc. Product Name CDTA, CDTC Application
Product Module Number
Product Description
BACnet Standardized Device Prole (Annex L): BACnet Application Specic Controller (B-ASC)
List all BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B DS-RPM-B DS-WP-B DS-COV-B DM-DDB-B DM-DOB-B DM-DCC-B DM-RD-B
Segmentation Capability: None Standard Object Types Supported: (See Table 1)
CDTA-2N000(-LCD) CDTA-5N000(-LCD) CDTC-2N000(-LCD) CDTC-5N000(-LCD)
All-in-One CO2/RH/ Temp /SetPoint IAQ
Software Version Firmware
Revision
BACnet Protocol Revision
1.6
1.5
12
Bulletin AQ-CDTA-CDTC-PIC
Data Link Layer Options:
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 57600, 76800, 115200
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)
Networking Options: None
Network Security Options: Non-secure Device - is capable of operating without BACnet Network Security
Character Sets Supported: ISO 10646 (UTF-8)
Gateway: This product does not support gateway functionality for any types of non-BACnet equipment/network(s).
Yes No
Page 2
TABLE 1: STANDARD OBJECT TYPES SUPPORTED
Object
Device 607xxx – “CDTA IAQ 607xxx”. Where xxx defaults to the selected MS/TP address.
Analog Input 1 – “CO2 Concentration”
Analog Input 2 – “Relative Humidity” Analog Input 3 – “Temperature” Analog Value 1 – “Set Point” Analog Value 2 – “Set Point Low Limit” Analog Value 3 – “Set Point High Limit” Analog Value 4 – “Dew Point” Analog Value 5 – “Wet Bulb” Analog Value 6 –
“Specic Enthalpy”
Analog Value 7 – “Display Mode” Analog Value 8 – “CO2 Offset” Analog Value 9 – “Barometric Pressure”
Analog Value 10 – “Relative Humidity Offset”
Analog Value 11 – “Temperature Offset”
Binary Value 1 – “Override” Binary Value 2 – “Use SI Units
Create Object Service
No No Description, Location, Max_Master,
No No Reliability,
No No Reliability,
No No Reliability,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Out_Of_Service,
No No Reliability Out_Of_Service,
No No Reliability Out_Of_Service,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
No No Reliability Present_Value,
Delete Object Service Optional Properties Supported
Max_Info_Frames, Active_COV_Subscriptions
COV_Increment
COV_Increment
COV_Increment
Writable Properties
Description, Location, Max_Master, Max_Info_Frames,
Object_Identier,
Object_Name, APDU_Timeout, Number_Of_APDU_Retries Out_Of_Service, COV_Increment
Out_Of_Service, COV_Increment Out_Of_Service, Units, COV_Increment
Out_Of_Service, Units
Out_Of_Service, Units
Out_Of_Service, Units
Units
Units
Units
Out_Of_Service
Out_Of_Service
Out_Of_Service, Units
Out_Of_Service
Out_Of_Service, Units
Out_Of_Service
Out_Of_Service
Proprietary
Properties
1000 (Serial Number)
None Units: parts-per-million,
None Units: percent-rela-
None Units: Celsius or
None Units: Celsius or
None Units: Celsius or
None Units: Celsius or Fahr-
None Units: Celsius or
None Units: Celsius or
None Units: kilojoules-per-ki-
None Units: No-units
None Units: parts-per-million,
None Units: hectopascals or
None Units: Percent-rela-
None Units: Celsius or
None None
None Active = SI Units,
Property Range
Restrictions
String length maximum 32 characters
Range depends on model
tive-humidity
Fahrenheit
Fahrenheit 0-50°C
Fahrenheit 0-50°C
enheit 0-50°C
Fahrenheit
Fahrenheit
logram-dry-air or btus­per-pound-dry-air
Integer values 0 – 7
±500ppm
inches-of-mercury 677-1016 hPa
tive-humidity ±30% in 0.1% incre­ments
Fahrenheit ±30° in 0.1° incre­ments
Inactive = US Custom­ary Units
Printed in U.S.A.8/22 FR# 444131-30 Rev. 1©Copyright 2022 Dwyer Instruments, Inc.
Loading...