Omega CCS User guide

Page 1
]
2-31/64 [63.03]
4-1/64 [102.00]
Ø13/64 [Ø5.00]
2X Ø13/64
[25.00]
SERIES CCS
CURRENT SWITCHES
Solid or Split Core, LED Visual Conrmation, Fixed or Adjustable Set Point
YEAR LIMITED
WARRANTY
Current Transformers/
Switches
The Series CCS Current Switches are ideal for monitoring the operating status of fans, pumps, and motors. These self-powered switches can be hung or tied directly to cables or wires. For use on existing installations, split core models can be installed
without disconnecting cables. LED indicators provide a visual conrmation that the currentisowingthroughthecore.Bothxedandadjustablesetpointsareavailable.
The adjustable models utilize a potentiometer to easily adjust the set point.
BENEFITS/FEATURES
• Integralmountingangeforquickinstallation
• Solidcoreorsplitcorecongurations
• LED indicator
• Fixed and adjustable set points
APPLICATIONS
• Proofofinstallation/ow
• Monitoring
• Lighting and heating circuits
• Conveyors
MODEL CHART Model Case Set Point Minimum Set Point (A) LED Dry Contact Output CCS-121050
CCS-111100 CCS-221100 CCS-211150 CCS-131100 CCS-231150
2-33/64
[64.00]
2X
43/64
[17.00]
55/64
[22.00]
Red Red/green Red Red/green Red/green Red/green
3-1/2 [89.00]
2-3/4 [70.00]
Yes No Yes No Yes Yes
33/64
[13.00]
2-7/16 [62.00]
[Ø5.00]
45/64
[18.00]
55/64
[22.00]
1-17/64
[32.00]
19/32
[15.00]
2-29/32
63/64
33/64
[13.00]
1-9/64 [29.00]
55/64
[22.00]
SPECIFICATIONS Amperage Range: 0 to 200 A AC.
Maximum Switch Rating: For dry contact models: 0.3 A @ 135 VAC/DC; For non-
dry contact models: 1 A @ 240 VAC.
Power Requirements: None, self-powered. Temperature Limits: -22 to 158°F (-30 to 70°C). Humidity Limits: 0 to 95% (non-condensing). Isolation Voltage: 2000 V. Frequency: 40 to 400 Hz. Enclosure Rating: UL94V-0ammabilityrated,ABSplastichousing. Compliance: CE, cULus.
Solid core Solid core Split core Split core Solid core Split core
[74.00]
2-31/64
[63.00]
Ø3/4
[Ø19.00]
3-1/2 [89.00]
Solid Split
Fixed Adjustable Fixed Adjustable Adjustable Adjustable
0.50 (±0.2)
1.00 (±0.2)
1.00 (±0.2)
1.50 (±0.2)
1.00 (±0.2)
1.50 (±0.2)
DWYER INSTRUMENTS, LLC | dwyer-inst.com