Omega AQ-CDTA-QS-2 User guide

Page 1
PWR COM B[+] A[-]
Bulletin AQ-CDTA-QS-2
TO
SUPPLY
NEXT
PWR COM B[+] A[-]
[1
1-3/32 [27.69]
®
Series CDTA and CDTC Communicating Carbon Dioxide Detector
Specications - Installation and Operating Instructions
2-51/64 [71.12]
4-1/2
14.30]
The Series CDTA and CDTC Communicating Carbon Dioxide Detector combines the function of several room sensors into a single, compact housing. Both the Series CDTA and the CDTC’s parameters include carbon dioxide, temperature, and temperature set point with override while the CDTA also includes a humidity sensor.
By having eld selectable Modbus® and BACnet Communications, only four wires are
needed for power and the communication signal. The communicating detectors can be daisy chained together to further reduce installation cost. In order to reduce the set up
time, the RS-485 MAC address is set up using on-board DIP switches. A second set of DIP switches are used to select whether output is Modbus® RTU or BACnet MS/TP
communication protocols and to limit access to the set up menu.
The barometric pressure can be programmed to correct for altitude. The humidity parameter in the Series CDTA uses a capacitive polymer sensor and the temperature
is measured using a 10KΩ thermistor sensor.
Optional integral display is available to display any of the parameters. For applications in which the building occupants aren’t familiar with CO2 concentrations, the LCD can be programmed to display temperature, humidity (only for Series CDTA), or temperature set point instead. For environments occupied 24 hours per day it is recommended to periodically expose the CO2 sensor to outside ambient air.
The Series CDTA and CDTC CO2 transmitters are maintenance free instruments with the ability to adjust the CO2 calibration by using the on-board Automatic Background Calibration (ABC) logic for intermittently occupied spaces. The ABC algorithm accounts for long term drift by making small adjustments to it’s zero calibration point based on the lowest CO2 readings it measures eight day cycles.
INSTALLATION
WARNING
national and local electrical codes. Use copper conductors only.
Avoid locations where severe shock or vibration, excessive
NOTICE
NOTICE
MOUNTING
1. Push tab on top and bottom of cover and lift cover from back plate (See Figure 1).
2. Select the mounting location, away from diffusers, lights or any external inuences.
3. Mount transmitter on a vertical surface to a standard electrical box using the two #6 M2C type screws provided.
4. Pull wires through sub base hole and make necessary connections.
5. Reattach cover to base plate.
Disconnect power supply before installation to prevent electrical
shock and equipment damage. Make sure all connections are in
accordance with the job wiring diagram and in accordance with
moisture or corrosive fumes are present.
Do not exceed ratings of this device, permanent damage not covered by warranty may result.
SPECIFICATIONS
Sensor: CO expectancy; Humidity*: Capacitive
polymer; Temperature: 10KΩ thermistor.
Range: CO2: 0 to 2000 or 5000 PPM CO2 (depending on model); Humidity*: 0 to 100% RH; Temperature: 32 to 122 °F (0 to 50 °C).
Accuracy**: CO2: ±40 PPM ±3% of reading 2000 PPM; ±50 PPM + 5% of reading 5000 PPM; RH*: ±2% (10 to
90% RH); Temperature: ±1°C @ 25°C. Response Time (CO2): 2 min for 90% step change.
*Only the Series CDTA has humidity sensing capabilities.
**The specied CO2 accuracy is only guaranteed after three weeks of continuous
operation in environments which are intermittently occupied.
WIRING
Wiring should comply with Electrical Characteristics of Generators
When using a common power supply, wire the CDTA and CDTC as shown in Figure 2, using two twisted pair conductors. One pair is to be used for B[+] and A[-]. The
other pair is to be used for power and common. This conguration is not suitable for
AC supplies. Use a DC supply only. Care should be taken that there are not too many devices powered from the same supply as voltage drops will occur in the wiring. If you
have many devices, or have long cable runs, the local supply conguration may be a
better choice.
TO PREVIOUS
suitable for this conguration.
In either conguration, the B[+] and A[-] lines must be terminated at both ends with a 120 Ω resistor. If the CDTA is an end device it has an on-board resistor that may be
used. See DIP SWITCH SETTINGS to enable it.
2: NDIR 15 year life
NOTICE
NOTICE
DEVICE
PWR COM
B[+]
A[-]
Temperature Limits: 32 to 122°F (0 to 50°C). Humidity Limits: 0 to 85% (non-condensing). Power Requirements: 10-42 VDC/ 10-30 VAC.
Device Load: 1/8 unit load.
Output: 2-wire RS-485, Modbus® RTU or BACnet MS/TP communication
protocol. Weight: 4.4 oz (125 g). Compliance: BTL, CE.
and Receivers for Use in Balanced Digital Multipoint Systems, TIA/
EIA-485-A-1998, Telecommunications Industry Association, 1998.
Use electrostatic discharge precautions (e.g., use of wrist straps) during installation and wiring to prevent equipment damage.
1 2 3 4
Figure 2: Common power supply wiring
TO NEXT
DEVICE
PWR COM
B[+]
A[-]
PREVIOUS
DEVICE
COM
B[+] A[-]
Figure 1: Removal of cover from back plate
DWYER INSTRUMENTS, LLC
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Figure 3: Local power supply wiring
Phone: 219-879-8000
Fax: 219-872-9057
1 2 3 4
POWER
www.dwyer-inst.com
TO
DEVICE
COM
B[+]
A[-]
Page 2
SETUP AND DIP SWITCH CONFIGURATION
ENABLE
PROTOCOL RESERVED
TERMINATION
OVERRIDE BUTTON
SECONDARY
RT
Use DIP Switch SW2 to congure the RS-485 MAC address of the device. The
address assignment is determined by adding the values for each of the switches that are in the ON position Table 1 below.
Switch Position 1 2 3 4 5 6 7 8
Address Value 128 64 32 16 8 4 2 1
Table 1: Address value for each switch position
The CDTA and CDTC comes from the factory with all of the DIP switches, except position 1, in the ON position as shown in Figure 4 below. The address of the transmitter
would be 127 as it would be 64+32+16+8+4+2+1 = 127. Another example would be
if the address desired was 008, the only DIP switch position in the ON position would be position 5.
A valid address depends on the protocol selected. Valid BACnet addresses range
from 0 to 127. Valid Modbus® addresses range from 1 to 247. A valid and unused
primary text and either “BAC” to indicate BACnet or “MOD” to indicate Modbus® as the secondary text. If the RS-485 MAC address is invalid, the invalid value is shown as the
primary value with “ERR” as the primary text.
ON
1 2 3 4 5 6 7 8
Figure 4: DIP switch SW2 (center-left)
Use DIP Switch SW1 (see Figure 5) to congure other hardware and software options
per Table 2 below.
Switch On Off
1 – Menu Enable
2 – Protocol 3 – Reserved 4 – Terminating Resister
Access to the setup menu is enabled
®
Modbus
120Ω between A[-] and B[+]
Access to the setup menu is disabled BACnet
Open
Table 2: DIP switch menu options
AUTO SERIAL CONFIGURATION
Auto serial conguration enables the device to determine the baud rate, parity and stop bits directly from the serial trafc. This allows a device to be quickly and easily deployed after a valid RS-485 MAC address is chosen. Note that the auto conguration procedure assumes a serial conguration appropriate to the selected protocol as
follows:
SUPPORTED SERIAL CONFIGURATIONS Protocol Supported Baud Rates Data Size Parity Stop Bits
BACnet 9600
®
Modbus
– RTU Even
19200 38400
57600 76800
115200
8 None 1
Odd None 2
1
Table 3: Supported serial congurations
If this is not the case, then the serial communication must be congured manually in
the setup menu.
To activate auto serial conguration, set a valid RS-485 MAC address using DIP switch
SW2, connect the serial bus and power wires, and apply power. The device will power up and begin examining the serial bus for communication.
When Modbus network, it is necessary to generate trafc in order to congure the serial communication. Attempting to read input registers is a good method to generate trafc. Note that while serial conguration is in progress, the device may not respond to requests. The device may require multiple read requests to complete the serial conguration process.
The auto serial conguration process will complete once a message addressed to the device is received and processed successfully. The serial conguration parameters
are then saved to non-volatile storage and loaded by default each time the device
starts. If the serial conguration of the bus changes, a power cycle of the device is required to restart the Auto Serial Conguration process.
®
is selected, and the device is setup ofine or away from the main
USER INTERFACE
PRESSED INDICATOR
VALUE
SECONDARY TEXT
PRIMARY TEXT
ON
1 2 3 4
MENU
NETWORK
Figure 5: DIP switch SW1 (bottom-center)
PRIMARY VALUE
Figure 7: Display layout
Home Screen
For models with the LDC display option, or when using the A-449A remote display tool, the home (idle) screen displays up to two measured values and is the steady state of the device. The information displayed on the home screen can be changed by the “DSP” value in the setup menu.
Set Point
When idle, a single press of either the UP or DOWN button will display the current set point value with the selected units displayed as the primary text. Additional presses of the UP or DOWN buttons will increase or decrease the set point value by 1 degree. A press and hold of the UP or DOWN button will initiate continuous changing of the set point value. The set point display will timeout and return to the home screen after 5 seconds of inactivity. At this point the new set point value is stored in non-volatile
memory. The range of the set point value can be congured with “SOH” and “SOL”
values in the setup menu. A display is not required to change the set point value.
Override
When on the home screen or when changing the set point, the override button (middle button) can be pressed. When the override button is pressed in these states, a snow
ake symbol is displayed momentarily to indicate the button was pressed.
REMOTE DISPLAY PO
UP
ENTER
DOWN
Figure 6: Internal view of transmitter
Figure 8: Side view of transmitter
Page 3
Setup Menu
The setup menu provides a means to congure the device locally. The setup menu can only be entered if the Menu Enable switch is in the on position and a display is present
(local or remote). To enter the setup menu, press and hold the UP and DOWN buttons for at least 3 seconds or until the display changes.
The setup menu contains a scrollable list of values that can be changed. Use the UP and DOWN buttons to scroll through the available values. The scrollable list is circular to allow continuous scrolling in either direction.
A value can be modied by rst scrolling to the desired value, then press and hold the
UP and DOWN buttons for at least 0.5 seconds, or until to word SET is displayed. The value can now be changed with the UP and DOWN buttons. Numerical values are displayed in the primary value area of the display with the current units in the primary text area. Some settings are text based and only show values in the primary text area. When the desired value is reached, press and hold the UP and DOWN buttons for
0.5 seconds to store the value in non-volatile memory and return to the setup menu.
The setup menu will timeout and return to the home screen after 30 seconds of inactivity. The setup menu can also be exited manually by a press and hold of the DOWN button for 0.5 seconds.
SETUP MENU VALUES Value Description Value Description
MAX
Maximum CO
DSP
Home screen conguration
UNI
Units selection
SOL
Set point low limit temperature
SOH
Set point high limit temperature
LON
CO2 warning indicator limit
(Model dependent)
LOF
CO2 warning indicator off level
(Model dependent)
2 Value
BAR
Typical barometric pressure
ABC
Automated background calibration
OFH*
Relative humidity offset
OFT
Temperature offset
OFC
CO2 offset
AUT
Auto serial conguration
BAU
Baud rate selection
PAR
Parity selection
STP
Stop bits selection
RST
Reset to factory defaults
*Only the Series CDTA has humidity sensing capabilities.
Table 4: Setup values
Home Screen Conguration (DSP)
This value controls what information is displayed on the home screen.
DSP Setting
Value
“CH”* “CT” “HT”* “TS” “S” “T” “H”* “C”
Primary
Value
CO
2 concentration
CO2 concentration Relative humidity Temperature Set point Temperature Relative humidity CO2 concentration
Primary Text
“PPM” “PPM”
“%” “°C” or “°F” “°C” or “°F” “°C” or “°F” “%”
“PPM”
Secondary
Value
Relative humidity Temperature Temperature Set point
Secondary Text
“%” “°C” or “°F” “°C” or “°F” “°C” or “°F”
*Only the Series CDTA has humidity sensing capabilities.
Maximum CO2 Value (MAX)
Displays the highest CO2 concentration value observed by the sensor since the last
power cycle or reset. Reset the MAX CO2 concentration by pressing and holding the
UP and DOWN buttons for 1 second.
Units Selection (UNI)
This value controls the units that data is displayed in.
Table 5: Display values
UNI Setting Value Description
“US” “SI”
US customary units (°F, in Hg) International system units (°C, hPa)
Table 6: Unit values
Set Point Low Limit Temperature (SOL)
This value sets a lower limit on the current set point value. The set point low limit
value is a numerical setting that supports continuous change (increment/decrement)
by press and holding of either UP or DOWN button. If the new set point low limit temperature is higher than the current set point temperature, then the set point temperature will be set to the new set point low limit temperature.
SOL Default Value Minimum Value Maximum Value Increment
20°C (68°F) 0°C (32°F) Set point high limit 1°
Table 7: Set point for low temperature limit
Set Point High Limit Temperature (SOH)
This value sets an upper limit on the current set point value. The set point high limit
value is a numerical setting that supports continuous change (increment/decrement)
by press and holding of either UP or DOWN button. If the new set point high limit temperature is lower than the current set point temperature, then the set point temperature will be set to the new set point high limit temperature.
SOH Default Value Minimum Value Maximum Value Increment
35°C (95°F) Set point low limit 50°C (122°F) 1°
Table 8: Set point for high temperature limit
2 Warning Indicator Limit (Model Dependent) (LON)
CO
The CO2 concentration that will turn on the warning LED
LON Default Value Minimum Value Maximum Value Increment
1100 PPM 0 PPM 9999 PPM 1 PPM
Table 10: CO
2 warning indicator on limit
CO2 Warning Indicator Off Level (Model Dependent) (LOF)
The CO2 concentration that will turn off the warning LED
LOF Default Value Minimum Value Maximum Value Increment
1050 PPM 0 PPM 9999 PPM 1 PPM
Table 11: CO2 warning indicator off limit
Typical Barometric Pressure (BAR)
This value sets the typical barometric pressure for the location where the device is mounted. The factory setting is for standard pressure at sea level. Adjusting the barometric pressure gives a more accurate measurement, especially at higher elevations.
BAR Default Value Minimum Value Maximum Value Increment
1013 hPa (29.9 inHg)
677 hPa
(20.0 inHg)
1016 hPa
(30.0 inHg)
1 hPa (0.1 inHg)
Table 12: Elevation/barometric pressure compensation
Automated Background Calibration (ABC)
Enables/disables the Automated Baseline Correction algorithm for disabling in
locations that experience elevated levels of CO2 due to constant occupancy of the area. Select “ON” to enable ABC and select “OFF” to disable ABC. Factory Default is “ON.”
ABC Setting Value Description
“ON” “OFF”
Enables ABC algorithm Disables the ABC algorithm
Table 13: Automated background calibration setting
Relative Humidity Offset (OFH)
This value, allows the relative humidity to be adjusted by a xed amount to match
another calibrated measurement. The display shows the current relative humidity value plus any previous offset value.
RHU Default Value Minimum Value Maximum Value Increment
0% -30% 30% 0.1%
Temperature Offset (OFT)
This value allows the temperature to be adjusted by a xed amount to match another
calibrated measurement. The display shows the current temperature value plus any previous offset value.
Table 14: RH offset value
OFT Default Value Minimum Value Maximum Value Increment
0° -30° 30° 0.1°
CO2 Offset (OFC)
This value allows the CO2 Concentration to be adjusted by a xed amount to match another calibrated measurement. The display shows the current CO2 concentration value plus any previous offset value.
Table 15: Temperature offset value
OFC Default Value Minimum Value Maximum Value Increment
0 PPM -500 PPM 500 PPM 1 PPM
Table 16: CO
Auto Serial Conguration (AUT)
This value enables or disables the automatic baud rate detection. If the device fails to
communicate or the serial conguration is not one of the options in Table 3, then this value should be set to “OFF”. The serial can then be congured manually.
2 offset value
AUT Setting Value Description
“ON” “OFF”
Baud Rate (BAU)
This value provides the selection of the desired serial baud rate. This value is only visible when the value of AUT is “OFF”.
Auto baud enabled Auto baud disabled
Table 17: Automatic baud rate value
BAU Setting Value Baud Rate Setting Value Baud Rate
9.6 K
19.2 K
38.4 K
9,600
19,200 38,400
57.6 K
76.8 K
115.2 K
57,600 76,800
115,200
Table 18: Serial baud rate value
Parity Selection (PAR)
This value provides the selection of the desired serial parity. This value is only visible when the value of AUT is “OFF”.
PAR Setting Value Description
“NON” “EVE” “ODD”
No parity Even parity Odd parity
Table 19: Serial parity value
Page 4
Stop Bits Selection (STP)
This value provides the selection of the desired serial stop bits. This value is only visible when he value of AUT is “OFF”
STP Setting Value Description
1 2
Reset To Factory Defaults (RST)
This value, when set to “YES”, will reset all user settings to their default values and reset the device. This applies to all settings including BACnet writable settings.
BACNET
BACnet installations should comply with ANSI/ASHRAE Standard
NOTICE
Refrigerating and Air-Conditioning Engineers, Inc., 2010
Communications wiring must be in a daisy-chain fashion. Star
NOTICE
BACnet Object Overview
The device supports the following objects:
SUPPORTED BACNET OBJECTS Object
Type
Device Analog Input Analog Input Analog Input Binary Value Binary Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value
*Only the Series CDTA has humidity sensing capabilities.
The default object identier is 607xxx, where xxx is replaced by the MS/TP MAC address set by DIP switch SW2. The object identier value will change as the MS/TP MAC address changes. However, if a specic object identier is written via BACnet, then that value is stored and changes to the MS/TP MAC address will no longer affect the object identier. Similarly, the default object name includes 607xxx. The object name will reect the current object identier. If a specic object name is written via BACnet, then that value is stored and changes to the object identier will no longer
affect the object name.
APDU Timeout values are rounded to the nearest second (1000ms). Values less than 500 will be rounded to 0 and Number of APDU Retries will be set to 0.
BACnet Objects
Device Object
Property Default Value Property Data Type Access
Object Identier
Object Name Object Type System Status Vendor Name
Vendor Identier Model Name
Firmware Revision Application Software Version Location Description Protocol Version Protocol Revision Protocol Services Supported Protocol Object Types Supported Object List Active COV Subscriptions
Maximum APDU Length Supported
Segmentation Supported APDU Timeout Number of APDU Retries
Max Master Max Info Frames
Device Address Binding Database Revision Serial Number (1000)
One stop bit Two stop bits
Table 20: Serial stop bits value
135-2010 BACnet A Data Communication Protocol for Building Automation and Control Networks, American Society of Heating,
connections and T connections are not permitted
Dynamically Creatable
No No No No No No No No No No No No No No No No No
Dynamically Deletable
No No No No No No No No No No No No No No No No No
Object Identier
607xxx
AI1 AI2 AI3 BV1 BV2 AV1 AV2 AV3 AV4 AV5
AV6
AV7 AV8 AV9 AV10 AV11
607xxx “CDTA IAQ 607xxx”
DEVICE(8) Operational(0) “Dwyer Instruments, Inc.”
607
“CDTA-???0-???” “?.?” “?.?”
“All-in-One CO2/RH/Temp/SetPoint”
1 12 See PICS See Table 2 See Table 2
480
NO_SEGMENTATION (3) 6000
3 127 1 Empty 1
Object
Name
CDTA IAQ CO
2 concentration
Relative humidity* Temperature Override Use SI units Set point Set point low limit Set point high limit Dew point Wet bulb
Specic enthalpy
Display mode CO2 Offset Barometric pressure Relative humidity offset* Temperature offset
BACnetObjectIdentier
CharacterString(32) BACnetObjectType BACnetDeviceStatus CharacterString Unsigned CharacterString CharacterString CharacterString CharacterString(32) CharacterString(32) Unsigned Unsigned BACnetServicesSupported BACnetObjectTypesSupported BACnetArray List of BACnetCOVSubscription Unsigned BACnetSegmentation Unsigned Unsigned Unsigned Unsigned BACnetAddressBinding Unsigned CharacterString
Read/Write Read/Write
Read Read Read Read Read Read Read
Read/Write Read/Write
Read Read Read Read Read Read Read Read
Read/Write Read/Write Read/Write Read/Write
Read Read Read
DWYER INSTRUMENTS, LLC
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Modbus® is a registered trademark of Schneider Electric USA, Inc.
Printed in U.S.A. 9/22 FR# 444131-10 Rev. 3©Copyright 2022 Dwyer Instruments, LLC
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
Loading...