olympia electronics GR-8600, GR-8600/300/4, GR-8600/600/8, GR-8600/300/8 Installation, Programming, Use

Page 1
GR-8600
24VDC Address Central Battery System
Installation
Programming
Use
Page 2
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
2 from 44
Contents
1. General information ................................................................................................................................................................................... 4
1.1 Technical Characteristics ................................................................................................................................................ 5
2. Installation.................................................................................................................................................................................................. 6
2.1 Designing the installation ................................................................................................................................................ 6
2.2 Connecting luminaries on illumination zones .................................................................................................................. 7
2.3 Luminary Types .............................................................................................................................................................. 8
2.4 Connecting the batteries ................................................................................................................................................. 9
2.5 Describing the general inputs and outputs of the panel ................................................................................................ 10
2.6 Powering On ................................................................................................................................................................. 12
3. Indicators - Controls ................................................................................................................................................................................ 13
4. Programming ........................................................................................................................................................................................... 14
4.1 Programming using the keypad .................................................................................................................................... 14
4.1.1 Programming the System...................................................................................................................................... 14
4.1.2 Programming the Zones ....................................................................................................................................... 16
4.1.3 Programming the luminaries ................................................................................................................................. 17
4.1.4 Check Luminary .................................................................................................................................................... 18
4.1.5 Programming Timers ............................................................................................................................................ 18
4.1.6 System Settings .................................................................................................................................................... 19
4.1.7 Clearing Events ..................................................................................................................................................... 21
4.1.8 Change Code ........................................................................................................................................................ 21
4.1.9 Inhibit mode .......................................................................................................................................................... 22
4.1.10 Programming the function test .......................................................................................................................... 22
4.1.11 Programming the capacity test .......................................................................................................................... 22
4.1.12 Capacity test ..................................................................................................................................................... 23
4.1.13 Reset Defaults .................................................................................................................................................. 23
4.1.14 Annual Test ....................................................................................................................................................... 23
4.1.15 Network Setting ................................................................................................................................................. 24
4.2 Programming via PC ..................................................................................................................................................... 25
4.2.1 Programming the zones ........................................................................................................................................ 26
4.2.2 Programming timers .............................................................................................................................................. 26
4.2.3 Programming Points ............................................................................................................................................. 27
4.2.4 Programming the battery capacity and the autonomy ........................................................................................... 27
4.2.5 Dimming Level ...................................................................................................................................................... 28
4.2.6 INHIBIT function .................................................................................................................................................... 28
4.2.7 Adjusting the date and time................................................................................................................................... 28
4.2.8 Battery cooler ........................................................................................................................................................ 29
4.2.9 Change Language ................................................................................................................................................ 29
4.2.10 Staircase time ................................................................................................................................................... 29
4.2.11 Clearing the events log ..................................................................................................................................... 29
4.2.12 Changing the tech code .................................................................................................................................... 30
Page 3
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
3 from 44
4.2.13 Network of panels ............................................................................................................................................. 30
4.2.14 Subpanel Setup ................................................................................................................................................ 30
4.2.15 Set Battery Current ........................................................................................................................................... 31
4.2.16 Autodetect Luminaries ...................................................................................................................................... 31
4.2.17 Check Current Zones ........................................................................................................................................ 31
4.2.18 Function test ..................................................................................................................................................... 32
4.2.19 Capacity test ..................................................................................................................................................... 32
4.2.20 Programming the function test .......................................................................................................................... 32
4.2.21 Programming the capacity test .......................................................................................................................... 32
4.2.22 Programming the annual check warning ........................................................................................................... 33
4.2.23 Annual Test ΟΚ ................................................................................................................................................. 33
4.2.24 Setting Defaults ................................................................................................................................................. 33
4.2.25 Changing information ........................................................................................................................................ 33
4.2.26 ΙΡ address ......................................................................................................................................................... 34
4.2.27 Resetting faults ................................................................................................................................................. 34
5 Use ................................................................................................................................................................................................................. 35
5.1 Operation using the keypad .......................................................................................................................................... 35
5.1.1 Current faults ........................................................................................................................................................ 35
5.1.2 Test ....................................................................................................................................................................... 36
5.1.3 Dimming Level ...................................................................................................................................................... 37
5.1.4 Information ............................................................................................................................................................ 37
5.1.5 Reset .................................................................................................................................................................... 39
5.1.6 All Events .............................................................................................................................................................. 39
5.1.7 Earth Test ............................................................................................................................................................. 39
5.1.8 LED test ................................................................................................................................................................ 40
5.2 Operation via PC................................................................................................................................................................. 41
5.2.1 Panel Information .................................................................................................................................................. 41
5.2.2 Zone programming information ............................................................................................................................. 42
5.2.3 Zones status information ....................................................................................................................................... 42
5.2.4 Information Point ................................................................................................................................................... 42
5.2.5 Timer information .................................................................................................................................................. 43
5.2.6 Function test results .............................................................................................................................................. 43
5.2.7 Capacity test results .............................................................................................................................................. 43
5.2.8 Last autonomies .................................................................................................................................................... 43
5.2.9 All events .............................................................................................................................................................. 44
5.2.10 Network information .......................................................................................................................................... 44
5.2.11 Panels network ................................................................................................................................................. 44
Page 4
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
4 from 44
Thank you for your trust in our products
Olympia Electronics - European manufacturer
1. General information
The GR-8600 family consists of 3 models of central battery systems for emergency illumination. They are produced
in accordance with the current European norms ΕΝ50171 and ΕΝ50172. Depending on the model, they contain 4
to 8 illumination circuits (zones). Each illumination circuit (zone) can support up to 32 points (addressed luminaries)
that can be programmed individually to operate in maintained or non-maintained mode. Each point provides
information about its lamp and connection status to the panel. A 24VDC voltage is provided by internal power
supply unit to the illumination circuits, when the mains power is active. In case of mains power interruption, the
system is provided with 24VDC from the batteries. The interior of the panel is divided into 2 compartments, the
electronics compartment and the batteries’ compartment. A sensor monitors the batteries’ temperature
continuously.
Page 5
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
5 from 44
1.1 Technical Characteristics
GR-8600/300/4
GR-8600/300/8
GR-8600/600/8
Operating voltage
~230V 50-60Hz
Batteries
2 x12V/33Ah
2 x 12V/55Ah
Illumination circuits (zones)
4 8 8
Maximum AC power (input)
900VA
1.4kVA
Max. power output (emergency)
300W
600W
Max. power output (per zone)
75W
Operating temperature range
5 – 40 oC
Degrees of cover protection
ΙΡ 21
Dimensions
67 x 50 x 27 cm
Weight (w/o batteries)
17.3kg
17.6kg
18.7kg
Battery fuse
30A/32V (maxi)
Zones fuse (output)
4A/250V (slow)
Mains fuse
8A/250V (slow)
Battery fan fuse
0.3A/250V (slow)
Type of electric shock protection
Class I
Max. operating altitude (above sea level)
1000m.
Max. relative humidity
95%
Guarantee
2 years
All fuses are size 5x20, battery fuse is 29mm car type.
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
The class of Volt-meter and Ampere-meter is 1.5.
Page 6
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
6 from 44
2. Installation
This section contains information that concerns the designing of the installation, the connection of the panel with the luminaries and the use of the auxiliary outputs and inputs. The instructions must be read carefully by the installer that is set to commission the panel. Skill and knowledge about the panel as well as its peripherals is essential for the good operation of the installation.
All the connections described below must be done with the 230VAC mains power supply isolated and the battery fuse removed.
2.1 Designing the installation
Before starting to install the cable you must take into account some critical parameters.
- Each luminary installed in any zone can be programmed individually to operate in maintained or non­maintained mode.
- Each luminary in a zone should get a unique address. If 2 or more luminary are installed with the same address in a single zone, there will be a data collision and the specific point (address) will not function properly.
- There is an option for wall mounting the panel with the correct accessories. Please refer to manufacturer for further information for wall mounting.
2.2 Choosing the correct cable
The cable between the panel and the luminaries must have the following specifications:
2-core twisted pair cable. Normally the cables are unshielded but if the cable passes near
noisy/industrial environment the cables must be shielded.
The cable must have only 2 cores, no other cables. If the environment is too noisy (motors, industrial
etc) a cable with shield must be used.
The cable must have low resistance, below 25 Ohm/km. The total impedance of the cable of each core
from start to finish must be more than 9 Ohm or the maximum voltage drop 3,5V.
The capacitance of the cable must be low (below 200pF/m). The total capacitance of the whole
installation must not exceed 800nF.
The cable that will be used must be resistant to fire for at least 90 minutes.
The cable cross section depends on the consumption of the luminaries on the zone and the total
length. It can be calculated using the table below. The table shows the required cross section of the cable depending on the length and the consumption.
Typical cable cross section is from 1mm2 to 4mm2 depending on the number of connected luminaires,
topology of the installation and length of cable runs.
Page 7
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
7 from 44
The first step to calculate the cross section of the cable is to calculate the current of each zone. You must add the current of each luminary at 24VDC and multiply with 1.4 factor. Then you pick the correct cross section cable from the below table. For example, if you want to connect 10 luminaries with lamp 30L the current is 10*85mA = 0.850A multiply 1.4 factor is 0.850A*1.4 = 1.19A. From the table, for a length less than 100m you must choose cable 1,5 mm2.
0.5 A
1 A
1.5A
2 A
2.5A
3 A
100m
1mm2
1mm2
1.5mm2
2.5mm2
2.5 mm2
4mm2
150m
1mm2
1.5mm2
2.5mm2
2.5mm2
4mm2
4mm2
200m
1mm2
2.5mm2
2.5 mm2
4mm2
4mm2
250m
1mm2
2.5mm2
4mm2
300m
1.5mm2
2.5mm2
4mm2
400m
2.5mm2
4mm2
500m
2.5mm2
4mm2
600m
4mm2
The values on the table are calculated when most of the load (luminaries) are placed at the end of the cable. It is the worst condition.
It is better to connect the luminaries along the length of the cable.
You can use a star connection at the zone to reduce the voltage drop.
This is recommended to check the currents and the voltage drop when the installation is finish just for verification.
Olympia Electronics recommends the following cables:
1. NHXH FE180/E90.
2. YSLY-OZ
3. LiYCY with shield
2.3 Connecting luminaries on illumination zones
The connection of the luminaries is the same as common luminaries. Below you can see an example:
Page 8
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
8 from 44
All connections to the illumination zones as well as any other modifications afterward require that the mains power supply is isolated and that the battery fuse is removed
Every Zone (illumination circuit) can support up to 32 unique addressed points. Same address between two or more points in the same zone can lead to malfunction. Point location in a row does not affect proper operation, it’s not necessary the first point to be address #1. Maximum points table is shown below. Each line refers to zone number and each column to point number.
Calculate the load according to the model. Do not exceed 75W per zone.
2.4 Luminary Types
The possible luminary types the system can recognize are the following:
1
NO LUMINARY
17
SPOT LIGHT 60L
2
LUMINARY 15 LED
18
SPOT LIGHT 1P
3
LUMINARY 30 LED
19
SLD-28
4
LUMINARY 3L
20
SLD-34
5
LUMINARY 6L
21
SLD-44
6
LUMINARY 4P
22
ZLD-28
7
LUMINARY 6P
23
ZLD-34
8
LUMINARY 12 LED
24
ZLD-44
9
LUMINARY 21 LED
25
DOUBLE LIGHT
10
POWER LIGHT 1 LAMP
26
ADAPTOR A
11
POWER LIGHT 2 LAMP
27
ADAPTOR B
12
EXIT SIGN
28
ADAPTOR C
13
DOUBLE EXIT SIGN
29
ADAPTOR D
14
SLIM LIGHT
30
ADAPTOR E
15
EASY LIGHT
31
ADAPTOR F
16
SPOT LIGHT 30L
32
OTHER LUMINARY
Page 9
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
9 from 44
2.5 Connecting the batteries
It’s recommended to use the following types of batteries: A-1200 (12V/33Ah) and A-1202 (12V/55Ah). Both of these types are designed for Central Battery Systems (CBS) and the stated minimum life expectancy is at least 10 years at 20°C ambient temperature.
First remove the battery fuse from its socket. The batteries must be connected in series. Two cables, one red and one black can be found in the batteries’ compartment. There is also a short cable (12cm black) contained in the package with two hole terminals on its ends. The red cable must be connected to the positive pole of the 1st battery and the black cable must be connected to the negative pole of the 2nd battery. The 3rdshort cable must be used to connect the negative pole of the first battery to the positive pole of the second battery.
WARNING!! Do not plug the battery fuse in this phase.
Warning!! In case of wrong battery polarity and battery fuse is plugged in DO NOT turn off the main switch before removing the
battery fuse.
-Batteries compartment-
Page 10
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
10 from 44
2.6 Describing the general inputs and outputs of the panel
On the printed circuit board located to the left side of the panel you can see the general purpose input and output terminal blocks. The figure below shows the terminals of the circuit board and they are described from left to right.
The next 3 outputs are relay outputs that are mandatory by the European norms. These outputs are connected to the building BMS and relays that require information regarding the status of the central battery illumination system.
FAULT YES / NO. Fault relay contact. When there is no system fault, the NO contact is active otherwise the YES contact is active.
SUPPLY MAINS / BAT. Relay contact that indicates what source of voltage is powering the system. When the power is supplied by the batteries then the BAT contact is active and when it is powered from the mains230VAC the MAINS contact is active.
OPERATION OFF / ON. Relay contact indicating the operation status of the panel. When the panel is operating, the ON contact is active. When the panel is shut down or is in cut-off mode the OFF contact is active.
The next 4 outputs-inputs are not relay contacts and they are supplied by live voltage so safety has to be considered when connecting those terminals. Don’t connect the mains power cord before completing the following connections (if any).
BAT FAN. Output for connecting an AC 230V cooling fan (optional). (fuse 0.3A/250V)
STRCS SWITCH. This input is used to connect in parallel, common staircase light buttons. By programming, some
illumination zones can be activated for a pre-programmed time period by pressing one of the staircase light buttons.
3 PHASE MONITOR. This contact by default has a jumper installed. When the contact is open then the panel activates the emergency luminaries. By using one or more mains voltage monitors you can activate the emergency
Page 11
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
11 from 44
light circuits even when the power to the panel has not been cut. It can also be used as a trigger input that is controlled by a higher level building management system which can give a command for the emergency illumination to turn ON.
Below you can see the connection with 3 mains voltage monitoring devices connected to individual electrical panels.
If any phase on any electrical panel fails, then a command is sent and the emergency illumination is turned ON.
AC POWER. Mains AC power connection terminal. It is suggested to do this connection after all the other connections are finished. WARNING!! Connect the supply accordingly to the indications L – N – PE. The polarity is crucial for the normal operation and the user’s safety.
-Interior of a GR-8600 (8 Zones)-
Page 12
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
12 from 44
2.7 Powering On
Before powering on the device, reassure that the batteries and the mains power cord are connected with correct polarity and the battery fuse is unplugged. Then turn on the green switch (mains power switch).
The switch must light on and the panel starts up. The system goes on a brief self-test while the message “CBS­24V/AD/R, Ver.x.xx, PLEASE WAIT” appears on screen. W hen it’s done, main screen appears. It’s now safe to plug the battery fuse (30A). The fault “BATTERY, FUSE FAULT” should appear on screen, but it will disappear in a minute or less from the time the battery fuse is plugged in.
2.8 Configuring initial installation
The following 3 actions are crucial to be done after initial installation for the proper operation. These steps have to be done when new luminaries are installed to or removed from the whole installation also.
i) AUTODETECT LUMINARIES This is the first step needed to be made in order for the system to auto-
detect all connected points in the installation. The system goes on an automatic scanning and registers every connected point to its memory. After autodetect takes place, every illumination zone operates in maintained mode and every luminary will light. This is an assisting function to confirm which of the luminaries are detected. Every successfully installed luminary will light. If a single luminary or a group of luminaries are not lighting there may be a problem, such as a faulty connection, conflicted addresses (same addresses in a zone) or the address set in that point(s) may be invalid. In that occasion the operation AUTODETECT LUMI/RIES has to be done again after fixing the problem.
For AUTODETECT LUMI/RIES operation see 4.1.1.
ii) CHECK CURRENT ZONES This procedure is a tool to determine if the load installed in a zone
exceeds the permitted values. The maximum load in a zone should not exceed 75W. When the system detects a zone with a load current at 3.5A or more, then a fault message is displayed. This message cannot be reset unless the load is adjusted correctly and the operation CHECK CURRENT ZONES takes place again.
For CHECK CURRENT ZONES operation see 4.1.1.
iii) IDLE ZONES This operation is also critical in order to ensure proper communication between the panel
and the luminaries. When this function is selected, all communications shut off, and there is no voltage modulation on the power lines. This helps the installer to check the voltage drop on the last point of each illumination circuit (zone). When the cable powering the luminaries is installed according to the table on par 2.2, then there should be a voltage drop less than 3.5V. Voltage drop more than 3.5V can cause communication issues. (The voltage supply when mains power is active is 25V, this means that on the last point of each line the voltage should be at least 21.5V).
For IDLE ZONES operation see 4.1.1
iv) SET BATTERY CURRENT This procedure is also significant for the system to calculate the output
current (sourced by the battery). When this action takes place, the system acts like in emergency mode and the electrical current value (in Amperes) that the illumination circuits draw from the battery is stored in the system memory. Each time the system goes in emergency mode the current consumption is compared to the stored values and if there is more current drawn than the initial configuration then a related message is displayed.
For SET BATTERY CURRENT operation see 4.1.1
Due to AUTODETECT LUMINARIES procedure, all the luminaries in every zone will operate in maintained mode. To change mode to a whole zone (all luminaries) to non-maintained with one action, you can use the SETUP LUMINARIES option and then select NON MAINTAINED in the desired zone.
For SETUP LUMINARIES function see 4.1.1.
Page 13
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
13 from 44
3. Indicators - Controls
The panel has the following controls and indicators.
On the left section of the front face there are LED indications which show the status of the zones:
The green LED next to each zone, lights on continuously when the zone is installed and is supplied by mains voltage. When the green LED blinks, the luminaries in that zone are powered by the batteries. Green LED blinking occurs in emergency mode or in test function mode. When the green LED is off, the zone is either not installed or set on “OFF” mode.
The red LED next to each zone lights on when there is a fault on the specific zone (like fuse fault, etc)
On the middle section of the panel there is the system screen and some indication LEDs which are described below:
POWER. A green LED which is lit when the panel has a 230VAC (mains) power supply. Blinking in emergency mode.
CHARGE. A green LED which is lit when the batteries of the panel are charging.
TEST. An orange LED which is lit during a function test procedure or a capacity test.
BATTERY. An orange LED which is lit when the illumination output circuits are powered by the batteries.
FAILURE. An orange LED which is lit when at least one system error has occurred.
INDICATION CUT-OFF. An orange LED which is lit when the batteries’ voltage is low and cut-off is about to take
place in a few minutes.
On the right section of the front face there is a group of buttons (keypad) and the INHIBIT indication LED.
INHIBIT LED. A green LED which is lit when “inhibit” mode is active. In this state, the panel charges the batteries but does not enter emergency operation, meaning that the zones’ output is inactive when the mains
power fails. This is useful for buildings that are not used for long periods of time.
The INHIBIT button next to the LED has a toggle function. It will change the state between “NORMAL” and “INHIBIT” and vice versa in every push.
Above the “inhibit” button, there are 6 main buttons used for the programming and control of the panel. The buttons with the arrows (up/down/left/right) are used to navigate, select and increase/decrease a variable. “Enter” button is used for selecting an option and “Esc” is for rejection or returning to the previous state.
Page 14
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
14 from 44
4. Programming
The programming of the panel can be done using the keypad and the screen. Alternatively, can be done using a PC via Ethernet connection. In case of a network of panels, some settings can only be done using a PC.
4.1 Programming using the keypad
After correctly completing the whole installation and powering on the system, the screen on the right should appear.
If “Enter” key is pressed the next screen shows up (MENU). In order to start programming the system, press the down arrow until the cursor goes to the selection TECHNICIAN MENU and select by pressing the “Enter” key again.
For safety reasons, programming can be done only by personnel that are allowed know the technician code. To enter the 4-digit code, use the arrow keys. Use the up/down arrow keys for increasing/decreasing the value and the right/left keys to go to the next or previous digit. When the code is entered press Enter.
The factory default code for the Technician Menu is “1000”.
4.1.1 Programming the System
If a correct code is given and the “Enter” key is pressed the Technician Menu screen is shown, else an error is displayed. The Technician Menu also has some additional settings that can be shown if you scroll down the menu, pressing down arrow. These are CHANGE TECH CODE, MODE INHIBIT, SET FUNCTION TEST, SET CAPACITY TEST, MAKE A CAPACITY TEST, RESET DEFAULTS, ANNUAL CHECK DONE, and NETWORK.
By selecting SYSTEM and pressing the “Enter” key the menu on the right is shown.
By pressing “Enter” on the first option, AUTODETECT LUMI/RIES, the system goes on an auto-detection process where all installed luminaries in the illumination circuits (zones) are automatically registered in the system’s memory. Before starting this process first make sure that all connections have been made properly and all the luminaries have been correctly addressed. This process is crucial for the system when a new installation takes place, in
Page 15
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
15 from 44
order for the panel to be able to communicate with the luminaries. It also has to be done when new luminaries are installed to a present system, or when old luminaries are removed. Otherwise, manual registration is also possible (see par.4.1.3)
The AUTODETECT LUMI/RIES procedure lasts for 75 seconds. During this procedure the screen on the right is shown. The remaining time in seconds is displayed too.
When the process is over, the screen on the right is shown. On the top section of the screen, the amount of the luminaries installed in each zone (from 1 to 8) is displayed. The total amount of all luminaries is also displayed. Pressing “Esc” key goes back to the previous menu, or else waiting 9 seconds goes back automatically.
Note that after this procedure every luminary in every zone will be set as maintained. This way you can confirm that all illumination circuits are working. Also, the total amount of found luminaries must match to the luminaries installed, otherwise there has to be a connection problem.
By selecting SET BATTERY CURRENT and pressing “Enter” the screen on the right is shown. The system begins a procedure that simulates an emergency situation. During this procedure that lasts 90 seconds, the luminaries installed in every zone are powered from the batteries and are lit. The batteries’ voltage and the total current drawn by the luminaries are displayed. This function is necessary after completing the installation and is crucial for current fault detection.
Warning. Before starting the procedure, the batteries of the panel must be charged at least to their 60% capacity.
Warning. This procedure must be done every time a new luminary is installed or removed, after it has first been registered in the system’s memory.
By selecting SETUP LUMINARIES and pressing “Enter” key, the screen on the right is shown. This option gives the ability to set all the luminaries installed in a zone as maintained or non-maintained at once. The system asks for a zone selection. Use the “Up & Down” keys to select the desired zone and press “Enter”.
After selecting the required zone, the system asks for operation mode for all luminaries in that zone. These modes are MAINTAINED or NON MAINTAINED. After selecting an option and pressing “Enter” all luminaries installed in that zone operate under the same mode.
This procedure is time-saving, after an auto-detection process, when one or more zones are required to be set completely non-maintained.
Page 16
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
16 from 44
By selecting CHECK CURRENT ZONES and pressing “Enter” key, the system starts a procedure that is able to calculate the current drawn by each zone individually. At first, Z0 is being calculated. Z0 refer to in-system circuits and the current must be less than 0.1A, usually 0.05A.
Then, Z1 and the rest of the zones are calculated step by step. The whole procedure lasts 4 minutes. If the output current in a zone exceeds 3.5A then a warning message is displayed on the main screen. In order to reset the fault message, the load in the zone that the fault was found, has to be re­adjusted. After fixing the problem run CHECK CURRENT ZONES again.
In the end, when all zones’ output current has been calculated, there will be a summary screen similar to the one on the right. The Amperes in each zone should match with the installed load in each circuit.
By selecting IDLE ZONES and pressing “Enter” key the screen on the right is shown. During this function, all the communications between the panel and the luminaries (points) is shut off. There is no voltage modulation on the lines, therefore, the voltage drop on the last point of each power line can be clearly measured with a DC voltmeter. The maximum voltage drop allowed for a proper communication between the panel and the luminaries when the IDLE ZONES function is selected, should be 3.5V or less. This means that when mains power is active, voltage supply on the zones output is 25V. So the last point on each line should have at least 21.5V on its terminal. There should be no issues when the cables connecting the luminaries are installed according to the table on par 2.2.
4.1.2 Programming the Zones
After completing the “System Programming”, get back to the previous menu, called TECHNICIAN MENU by pressing “Esc”.
The second option in the TECHNICIAN MENU is ZONES. Select this option and press “Enter”. The screen on the right is shown. Select the required zone number and press “Enter”.
First select if the zone is installed or not. NO is selected only if the zone is not physically installed. With the selection NO the panel returns to the TECHNICIAN MENU.
If you select YES, you proceed to further programming. If you select YES for a zone that is not physically installed, then the programming will be done but after a while an error message “NOT CONNECTED” will be shown on the main screen.
By selecting YES in the previous menu, the system asks for staircase function on the specific zone. By selecting YES and pressing “Enter” the zone programming is over and the TECHNICIAN MENU is shown again. STAIRCASE FUNCTION takes place when a button that is connected to the terminal “STRCS SWITCH” is pressed. Then all the luminaries in that zone/s which is/are programmed to operate in STAIRCASE FUNCTION will light for period of time. The time can be set with the option STAIRCASE TIME (see
4.1.5). Selecting NO option, the system continues further zone programming.
Page 17
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
17 from 44
WARNING! Staircase Function works with Maintained mode only. If staircase function is selected in a zone, then only the luminaries that are set as maintained will light in staircase function. Those maintained luminaries
are not lighting continuously though, but only when the staircase switch is pressed.
In the table below you can see when a luminary is lit (supposing that the system is in charging mode and the mains power is on)
Zone (luminaries) mode
Staircase Function
Luminaries’ Light
Maintained
No
ON
Non-Maintained
No
OFF
Maintained
Yes
Only in staircase
function
Non-Maintained
Yes
OFF
It’s also important to know that staircase function and timer function is affected by dimming level.
By selecting NO option in the staircase function, the system asks for a timer.
Timers are used to turn OFF or ON luminaries at specific hours when people are not in the building. Timers affect only the luminaries that are programmed to operate as maintained. By selecting a timer, on NO TIMER, the zone programming is over and then the previous menu (TECHNICIAN MENU) is shown.
(For timers programming, see par. 4.1.4) (For programming luminaries see par. 4.1.3)
4.1.3 Programming the luminaries
In order to register and program a specific luminary manually, select the option LUMINARIES in the TECHNICIAN MENU and press “Enter”. The screen on the right is shown, where the system asks for a zone selection. Select the zone that the required luminary is installed to with “Up & Down” keys and press “Enter”.
After selecting the zone number, the system asks for the luminary’s address. Select the required address with “Up & Down” keys and press “Enter”. The system displays the selected zone number and luminary address for 2 seconds.
The system asks if the required luminary in that address is installed or not. By selecting NO and pressing “Enter” the system goes back in the zone selection. If you select YES, the system continues the luminary programming.
Note that if you select NO for a luminary that is already installed, later in the system screen a fault “POINT NOT REGISTERED” will be displayed. If you
Page 18
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
18 from 44
select YES for a luminary that is not present, then there will be a communication loss fault on the main screen.
If you select YES in the previous menu, then the system asks for mode in the selected address. The mode can be MAINTAINED or NON MAINTAINED. In the maintained mode, the luminary in the selected address will keep lighting continuously even if the mains power is up (excluding staircase function zones). If a timer is selected to the zone that the address belongs to, then the luminaries will light for the programmed time.
In non-maintained mode, the luminary in the selected address will stay off until an emergency situation (mains power failure).
By selecting a mode for the luminary in the required address, the system asks for the luminary type. For luminary types available see par. 2.3. Select the matched type in the specific address.
4.1.4 Check Luminary
Check Luminary function is a tool to check packet communication between the panel and a specific luminary/point. Select CHECK LUMINARY in tech menu and the screen on the right is shown. In first place, point 1 in zone 1 appears (POINT 1.01). To chance the address press up/down arrow keys. Change the zone by pressing the right/left arrow keys.
First line indicates luminary type that the system reads. Second line shows the communication status (OK or FAULT).
The next line shows the lamp (LED) status.
On the last line there are 3 counters for packet communication. G stands for “Good” packets, N for “Not good” and W for “Without answer”.
4.1.5 Programming Timers
Timers are used to automatically turn OFF the luminaries connected to MAINTAINED zones when there are no people in the building. This way you can save power without degrading the safety level of the building. Even if a zone has been turned OFF by a timer, during a mains power failure the luminaries connected to the zone will light. There are 8 timer memory slots that can be individually programmed to operate in different hours of the day.
Select TIMER option and press “Enter”, then the next screen shows up. With the Up/Down keys you can change the timer. Press “Enter” once the required timer has been selected.
By default, all timers are deactivated. To program a timer, you must first activate it by selecting the option ACTIVE and pressing “Enter”.
Page 19
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
19 from 44
Select the start time of the Timer (this is the hour that the luminaries will be turned ON). With the “Up/Down” keys you can change the digit value and with the “Right” key you select the next digit. To store the time, press the right key past the last digit.
Select the start week day of the timer. With the selection EVERY DAY the timer will repeat daily. There are also available WEEKEND and WEEK DAY options.
Select the stop time of the Timer (this is the hour that the luminaries will be turned OFF). With the “Up/Down” keys you change the digit value and with the “Right” key you select next digit. Enter the required time. To store the time, press the right key past the last digit.
Select the end day of the timer. If you have previously selected EVERY DAY or WEEKEND or WEEK DAY, then this screen will not be shown.
4.1.6 System Settings
By selecting SETTINGS and then pressing “Enter” the screen on the right is shown. The SETTINGS menu includes some additional options that can become visible by scrolling down the menu with the “down” key. These are SELECT LANGUAGE, ANNUAL CHECK WARNING, STAIRCASE TIME, BATTERY COOLER and MENU MANUFACTURER.
By selecting BATTERY CAPACITY and pressing “Enter” you see the next screen. The batteries that can be used are 33Ah or 55Ah depending on the model. Using the up/down keys select the required capacity and press “Enter”.
Page 20
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
20 from 44
By selecting SYSTEM AUTONOMY and pressing “Enter” you see the next screen. Using the up/down keys you can select one of the five options available. Press “Enter” when finished. With this selection you do not actually change the autonomous duration of the panel. You only inform the system of the required emergency duration so it can use it in future autonomous duration test. The actual duration must be calculated before
the installation by calculating the consumption of the luminaries in emergency operation and selecting the appropriate batteries. The
calculated duration must be equal to or greater than the required.
By selecting the BUTTON INHIBIT and pressing “Enter” you can see the next screen. There you can set whether the INHIBIT key is functional or not. The function of the INHIBIT key can be seen in par. 3. Sometimes for safety reasons it is required that the INHIBIT key is not functional. In this case select NO and press “Enter”. By default, BUTTON INHIBIT is set to YES.
With the next 3 functions you can modify the date and hour. This must be done during the installation to enable all logged events to have the correct time and date stamp. It’s also crucial for the timers to operate in the correct time.
By selecting the DAY OF WEEK SETTING and pressing “Enter” you can see the following screen on the right. Select the current day of the week using the “Up/Down” keys and press “Enter”.
By selecting DATE SETTING and pressing “Enter” you see the screen on the right. With the “Up/Down” keys you can change the value of each digit. With the “Right” key you can select next digit. Select the correct date and press “Enter”.
Note that date format is day/month/year.
By selecting TIME SETTING and pressing “Enter” you can see the screen on the right. With the “Up/Down” keys you can change the value of each digit. With the “Right” key you can select next digit. To store the time, press the right key past the last digit.
By selecting SELECT LANGUAGE and pressing “Enter” you can see the screen on the right. With the “Up/Down keys” select between Greek, English or Norge and then press “Enter”. When changed, all logged events use the new language.
Page 21
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
21 from 44
By selecting ANNUAL CHECK WARNING and pressing “Enter” you see the screen on the right. With the “Up/Down” keys select NO or YES and press “Enter”. If you select YES, then every year you will be getting a reminding message about the Annual inspection.
By selecting STAIRCASE TIME and pressing “Enter” you can see the screen on the right. With the “Up/Down” keys you can select the required minutes that the staircase light will remain on and then press “Enter”. The default value is 3 minutes. (min 1’, max 30’)
By selecting BATTERY COOLER and pressing “Enter” you can see the screen on the right. With the “Up/Down” keys you select NO or YES and then press “Enter”. The option YES must only be selected if a cooling fan has been installed. Deactivated by default.
The MANUFACTURER MENU does not contain any option that can be adjusted by the installer.
4.1.7 Clearing Events
By selecting CLEAR EVENTS in the TECHNICIAN MENU and pressing “Enter” you can see the screen on the right. The system requests a confirmation. If you actually need to clear the events, then with the down key select YES and then press “Enter”. Clearing of event must be done after the initial installation has finished.
4.1.8 Change Code
By selecting CHANGE CODE and pressing “Enter” you can see the screen on the right. Using the “Up/Down” and “Right/Left” keys enter the desired 4digit code and press “Enter”. The new code is the one to be used for programming the system from PC also. Changing the technician code is an action that must be responsibly done. In case of a code loss, there is no way to reset the code to the previous one without knowing the current code.
Page 22
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
22 from 44
4.1.9 Inhibit mode
This option sets the INHIBIT mode ON/OFF.
About INHIBIT mode, see par. 3.
4.1.10 Programming the function test
By selecting SET FUNCTION TEST and pressing “Enter” you can set the parameters for the automatic function test. The options are Daily, Every Other Day or once a week on a specific day. The duration of the test is 90 seconds. During this test all the luminaries are supplied by the batteries (simulating a power failure). Batteries’ discharge current and zones’ current consumption are compared to the values that were logged during “SET BATTERY CURRENT” procedure.
Select the required interval and press “Enter”.
Now set the hour for the test. With the “Up/Down” keys you can change the value of each digit. With the “Right” key you can select next digit. To store the time, press the right key past the last digit.
It is wise to program the function test to take place in hours and days when the building is not crowded or even closed so it does not interfere with other tasks. The default setting is 8:00 am every day.
4.1.11 Programming the capacity test
The capacity test procedure is able to determine if the required system autonomy can be achieved. There are 2 memory positions to adjust two different in time tests. The capacity test must be done from once every 6 months to once a year. The capacity test lasts maximum for the 2/3 of the stated autonomous duration of the system.
By selecting SET CAPACITY TEST and pressing “Enter” you see the screen on the right. Select the required test number, 1or 2 and press “Enter”.
By default, both tests are active. To continue select ACTIVE and press “Enter”.
Page 23
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
23 from 44
Select the desired date for the test using the arrow keys. The last 2 digits are for the year. Once the required date is set, press “Enter”.
Select the hour for the test using the arrow keys.
You must select wisely the time and date of the capacity test because for the next 12 hours after the test finishes, the system will not achieve the stated autonomous duration due to batteries’ discharging.
4.1.12 Capacity test
By selecting MAKE A CAPACITY TEST and pressing the “Enter” key the system conducts a manual capacity test and you see the screen on the right. On the first line with the big letters you see the duration of the test. On the next 3 lines you can see the voltage of the batteries, the current that discharges the batteries and the capacity that has determined until this time.
Warning. Before starting the procedure, the batteries must be fully charged (24h charge at least).
You can let the test to end automatically when the autonomy hits the 2/3 of the stated autonomous duration or you can stop the test at any time by pressing the “Esc” key.
Stated autonomous duration is set by the user. See par. 4.1.5
4.1.13 Reset Defaults
To reset all settings to factory default, select RESET DEFAULTS and press “Enter”. When the message on the right is shown then the procedure has finished.
4.1.14 Annual Test
If you have finished with the annual tests and want to delete the related message, select ANNUAL TEST DONE and then press “Enter”. When the screen shows the message on the right then the related message has been deleted.
Page 24
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
24 from 44
4.1.15 Network Setting
By selecting NETWORK and pressing “Enter” you see the settings for using the panel via an Ethernet connection. The panel can be connected to a network in order to cooperate with other panels or to be programmed by a computer. In order to operate a panel via a network, the Ethernet module has to be installed. It’s not installed by default, unless it has been ordered so. The Ethernet module is placed behind the main board on the front door (above locking mechanism).
If the panel has an Ethernet module installed then select ETHERNET CARD, press “Enter” and then select YES.
If you select ΙΡ ADDRESS and press “Enter” you see the screen on the right. The panel must have an IP address that is compatible with the network that it will be connected to. Consult your network administrator for the IP address. In order to program the address, use the arrow keys. The up/down keys are used to increase the value and the right/left keys are used to select the digit. Once the IP address is set press “Enter”. By default, the IP address is
10.0.1.143.
If any adjustments are made (like setting a new IP address) on the Ethernet module, please select the option RESET ETHERNET and press “Enter”. This procedure initializes the connection so the panel is able to connect with the new IP address.
If you select NETWORK PANELS and press “Enter” you see the screen on the right. This option sets the panel as master or subpanel in a network. Master panel can be set to operate as in emergency mode, if one or more of the subpanels are currently in emergency mode. Select YES to set the panel as master panel or NO for subpanel.
There can’t be more than one master panel in the same network.
If you select NETWORK LIGHTS ON and press “Enter” you see the screen on the right. By selecting YES, if this panel is a master panel, when a subpanel enters emergency mode, this master panel will light on its illumination circuits. If this is a subpanel, when the master panel enters emergency mode, this subpanel will light on its illumination circuits.
Page 25
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
25 from 44
4.2 Programming via PC
No special software is needed to program the system from a PC. A common web browser such as Google Chrome, Mozilla Firefox, Internet Explorer, etc. can be used. The following photos show the use of Google Chrome. We recommend using Google Chrome web browser.
The requirements needed are a common network with a PC and a CBS panel connected to it. In order for a CBS panel to be able to connect to a network, an Ethernet Card has to be installed. You also need to know the IP address of the CBS panel in order to operate it remotely. There is the option to have access to the system via internet globally, if the correct adjustments on the network are made by the network administrator of the building.
The first action is to open a web browser and then enter the IP address of the panel in the URL area. If everything is connected correctly, then you will see the following page.
By clicking on the link TECHNICIAN MENU you see the following page
Place the cursor on the TECH CODE field, enter the 4digit tech code and press SEND. If the code is correct then the following page appears. If not, then a “wrong code” message is displayed.
Page 26
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
26 from 44
4.2.1 Programming the zones
Click on the first link ZONES and then the following page appears. In this page you can set all the available options for each zone.
First click on the zone that you want to program.
Then, select if the specific zone is installed or not. Select YES only when that zone is installed, else a fault will be displayed in the system. Select NO only when that zone is not installed, else there will be a fault displayed too.
Now select if the specific zone operates in staircase function. When staircase function is ON all the luminaries in that zone that are set as maintained will be lit when the staircase switch is pressed. (see 4.1.2 for staircase function).
Select if the zone operates with a timer selection. No timer means that a maintained luminary in that zone will light continuously. Else, if a timer is selected, then the luminary will operate according to the timer. The timers are used to turn OFF the luminaries that have been programmed as MAINTAINED automatically when there are no people in the building. This way you can save energy without degrading the safety level of the building. Even if a zone has been turned OFF by a timer, in an event of a power failure the luminaries connected to this zones will be turned ON.
Timer selection and staircase function are not affecting luminaries that are set as non-maintained in a zone.
Staircase function overrides timers (if selected).
When done press the SAVE button on top to keep the adjustments into the memory. You can adjust all zones by selecting a zone and repeating the procedure.
Clicking on TECHNICIAN MENU link goes back to the technician menu page.
4.2.2 Programming timers
By selecting in the technician’s menu the TIMERS option you see the page below.
In this screen you can program the timers. Click on the desired timer and YES to activate. Adjust the start time and day and the end time and day. The option DAY OF THE WEEK START has the options DAILY, WEEKDAY andWEEKEND. With the selection DAILY the timer is repeated daily. With the option WEEKDAY the timer is repeated from Monday to Friday and during the weekend it is off. With the option WEEKEND the timer will be repeated only on weekend. If you select one of these options, it does not matter what end date you select.
Click the SAVE button to keep the settings on the system memory.
By clicking TECHNICIAN MENU, you can go back to the technician menu page.
Page 27
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
27 from 44
4.2.3 Programming Points
Luminaries that are addressed are also referred under the term points. By selecting the third option POINTS in the technician menu, the page below is displayed:
Enter the zone number that the luminary is installed to and then the address. Press SETUP to continue point programming. The page below is displayed:
First select if the point is installed or not. Select YES only for a point that is already installed, else there will be a fault displayed. Select NO for a point that is not installed, else there will be a fault too.
Choose an operation mode for that point, MAINTAINED or NON MAINTAINED.
You can choose a name for that point too (CAPITAL ALPHANUMERIC CHARACTERS).
Select the luminary type in the dropdown list.
When done, click SAVE to store all the adjustments in the systems memory.
4.2.4 Programming the battery capacity and the autonomy
Clicking on the BATTERY CAPACITY & SYSTEM AUTONOMY you can see the following page:
Use the keyboard to write the battery capacity (33 or 55Ah). In the option SYSTEM AUTONOMY select one of the following durations (1HOUR, 1.5 HOUR, 2 HOURS, 3 HOURS or 8 HOURS). This option DOES NOT change the actual autonomous duration of the system. It informs the system about the minimum required autonomous duration, so the system can determine if the required autonomy can be achieved under the capacity test, or a power failure.
The autonomous duration when there is the maximum load installed in the system, is 1 hour. For more duration the load must be calculated according to the system capacity.
Press the SAVE button to keep the settings in the system memory.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
Page 28
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
28 from 44
4.2.5 Dimming Level
Dimming level is an operation that scales down the light output power. There are 8 selections available in the dropdown list: 12%, 25%, 37%, 50%, 67%, 75%, 87% and 100%. The last selection is the maximum light intensity available and is selected by default. Choose an option and then press SAVE.
Dimming level affects all zones, every luminary that is set to operate in maintained mode. Also affects the same way staircase function and timers. Dimming level does NOT affect emergency mode.
4.2.6 INHIBIT function
By default, this option is set to OFF. If you select YES and press SAVE the system automatically enters a state where it only charges the batteries. Maintained-mode zones will keep lighting when the mains power is on but in case of a power failure (emergency) all zones will be inactive and will not light. INHIBIT function is used when a building is not in use and without occupants for a large time period.
If you select NO and press SAVE, the panel enters the normal operation state.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.7 Adjusting the date and time
By clicking DATE SETTING & TIME SETTING you enter to the following page.
Adjust the date, time and day of the week and press SAVE. These setting must be done during the initial system setup so as to have an accurate log of the events.
Note that the date format is year/month/date and time is 24h format.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
Page 29
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
29 from 44
4.2.8 Battery cooler
Clicking on BATTERY COOLER goes in the following page.
By default, this option is set to NO. If a cooling fan has been installed, then to enable it you must select YES and press SAVE.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.9 Change Language
Clicking on SELECT LANGUAGE goes in the following page.
Select GREEK, ENGLISH or NORGE and press SAVE. The language selection affects the language of the panel, the language of the PC software and the logged events. All previously logged events will be displayed in the current language.
4.2.10 Staircase time
Click on STAIRCASE TIME to adjust it in the following page.
Type the time that the staircase luminaries will be ON and press SAVE. By default, the time is 3 minutes.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.11 Clearing the events log
Click on CLEAR EVENTS LOG to clear all logged events in the following page.
In this page you see the confirmation screen. If you press YES, then all the events will be wiped from the memory and you will be redirected to the previous page. This action should be done after initial installation.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
Page 30
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
30 from 44
4.2.12 Changing the tech code
By clicking on CHANGE TECH CODE you can change the technician code. Before changing this code mind that once changed, there is no way to reset the code to the previous one if you don’t have the new one, so it has to be responsibly done. Enter a new 4-digit code and press SAVE.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.13 Network of panels
With the option PANELS NETWORK combined with the SUBPANELS SETUPyou can adjust the network if more than one panel are required in the same building to operate in cooperation with each other.
First select if the panel is the Master (select YES) or a subpanel (select NO).
In the option LIGHTS ON FROM SUBPANEL, if you select No then the specific panel (either master or subpanel) will not enter emergency operation if another subpanel has entered it. If you select YES, then the specific panel will enter emergency operation when any other subpanel enters it.
The option LIGHTS ON FROM MASTER PANEL matters only if you are programming a subpanel. If you select NO the specific subpanel will not enter emergency operation when the master panel enters it. Selecting YES it will enter emergency operation when the master panel enters it.
4.2.14 Subpanel Setup
If you set the current panel as Master, then via this page (SUBPANEL SETUP) you can program its subpanels. Enter the panel number (starting from 1 to 32) and press SELECT. You see the following image.
Page 31
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
31 from 44
Set the ENABLE option to YES and enter the IP and MAC address of the subpanel in position 1.
These addresses can be found in the option INFORMATION NETWORK in the initial menu of the subpanel (via Ethernet).
Select SAVE and continue with all consecutive subpanels.
4.2.15 Set Battery Current
By clicking on the option SET BATTERY CURRENT in the tech menuyou can see the above confirmation page. If you press YES, the panel erases from the memory all previous current entries and executes the operation CURRENT ADJUST. The adjustment of the current must be done when the installation has finished and when all luminaries have been verified that operate correctly. It must also be done every time a luminary is added or removed. The procedure lasts 90 seconds and when it finishes, the current that the total load draws, is saved in the system memory.
Note: Before starting this operation be sure that the batteries of the panel are charged to at least 60% of the capacity.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.16 Autodetect Luminaries
By clicking on the option AUTODETECT LUMI/RIES in the tech menu, you can see the confirmation page. Press YES and the system runs an automated scanning and registering procedure, where finds all installed luminaries and registers them in the system’s memory. This procedure lasts 75 seconds. After this action all luminaries correctly registered will turn on and light in maintained mode. If one or more luminaries are off, there might be a communication problem between the panel and that/those luminaries.
4.2.17 Check Current Zones
By clicking on the option CHECK CURRENT ZONES in the tech menu a confirmation screen appears. Select YES to run the test. The system step by stem calculates the current drawn by each zone (illumination circuit) separately in order to check for overloads. When the load exceeds 3.5A a similar error is displayed. This specific error cannot be cleared, unless the load is correctly adjusted and the CHECK CURRENT ZONES procedure is run again, this time without overloads.
Page 32
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
32 from 44
4.2.18 Function test
By pressing YES, a complete function test is conducted.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.19 Capacity test
By pressing YES, a complete capacity test is conducted.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.20 Programming the function test
Via this page you can program the automatic function test. In the selection TIME INTERVAL select DAILY, EVERY OTHER DAY or one of the days of the week. Enter the time in the TIME SETTING box and press SAVE. It’s wise to adjust the function test to take place when there are no people in the building or when there are no other active tasks that could interfere with the automated function test.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.21 Programming the capacity test
Via this page you can program the next 2 consecutive capacity tests. By default, both tests are active. To program the capacity test, select YES in the selection ACTIVE for test 1 and test 2 (if needed). Adjust the time and date for each test and press SAVE.
With the capacity test the system tests the batteries’ capability of sustaining the stated autonomy. The capacity test must be done from once every 6 months to once a year. The maximum duration of the capacity test is the 2/3 of the stated autonomous duration of the panel.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
Page 33
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
33 from 44
4.2.22 Programming the annual check warning
By selecting YES and pressing SAVE you will receive a reminding message on the panel’s screen or on the systems interface (via Ethernet) yearly.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.23 Annual Test ΟΚ
Via this page you can delete the reminding message for the required annual tests if they have been conducted. By pressing YES, the message is deleted.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
4.2.24 Setting Defaults
With this selection you can restore the panel to its factory default settings. For confirmation the panel asks for the technician code. After the end of the procedure the main menu is shown.
4.2.25 Changing information
Via this page you can change the general information of the panel. You can change the LOCATION (up to 24 characters), the TECHNICIAN INFO (up to 24 characters) and the TECH TELEPHONE (up to 16 characters).
By pressing SAVE all the information is stored in the system’s memory.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
Page 34
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
34 from 44
4.2.26 ΙΡ address
Via this screen you can change the IP address of the panel.
Press SAVE to keep the new IP address in the system’s memory. After saving, the communication between the panel and the PC web browser will terminate. Then you must manually enter the new IP address in the URL bar of the browser. (see par. 4.2).
4.2.27 Resetting faults
In this page if you press YES then all the current panel faults are cleared.
Clicking on TECHNICIAN MENU goes back to the technician menu page.
Page 35
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
35 from 44
5 Use
The GR-8600 central emergency lighting system is made to operate without the continuous supervision from the user. The function test as well as the autonomous durations test can be programmed to be executed automatically. The building attendant can see the results at any time. If no errors are logged, then he does not have to take any actions. If any error is observed then he can fix it or he can consult an electrician, depending on the cause. The user has a variety of options to manually inspect the whole system whenever required.
When the panel is in normal operation the screen on the right is shown. Also the indicators POWER, CHARGE and zones’ POWER are lit. (for indicators see par. 3).
If for any reason you need to disable emergency operation (i.e. during closed periods of hotels), press the INHIBIT key. The indicator INHIBIT is lit and the screen should look like the image on the right. To exit INHIBIT mode simply press again the INHIBIT key.
Note that if the inhibit key is disabled from the technician menu, then there will be no response on pressing.
5.1 Operation using the keypad
5.1.1 Current faults
By pressing the “Enter” key you enter the user MENU as shown in the screen on the right. If faults have been detected in the system, then the first option would be CURRENT FAULTS. All the options except the TECHNICIAN MENU are available to the user. For tech menu entry the technician code is needed and should be accessed only by authorized personnel.
If there is a CURRENT FAULTS option and you press “Enter” you can see the screen on the right. If you select RESET FAULTS and press “Enter” the panel resets all the current faults (and logs them into the memory).
If you select SHOW FAULTS and press “Enter” you can see a screen as in the image on the right. When an error is displayed there is always a “Χ” on the top left corner that blinks. To the right with bold characters you can see the source of the fault (In our case Zone 4). Under the blinking “X” you can see the name of the zone (underground) followed by a detailed description. On the last line you can see the number of the fault to the total faults. With the up/down arrow keys you can navigate through the faults. With the “Esc” key you go to the previous menu.
Page 36
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
36 from 44
5.1.2 Test
If you select TEST and press “Enter” you will see the screen on the right.
If you select MAKE A FUNCTION TEST and press “Enter” a manual function test is conducted. Its duration is 90 seconds. The screen shows the remaining time, the battery voltage and the discharging current that the whole load consumes from the batteries.
When the test finishes the screen on the right is shown. The first line shows the date and the hour of the test. The following 3 lines show the faults that have been detected for the system, the zones and the battery. By pressing “Esc” you return to the previous menu. If faults have been detected, then you must go to the menu CURRENT FAULTS for more details.
If you select TEST RESULTS and press “Enter” you can see the screen on the right.
If you select FUNCTION TEST and press “Enter” you see the screen on the right. The first line shows the indication 01/ΧΧ (where ΧΧ the amount of tests in memory) as well as the date and hour of the test. The following 3 lines show the faults detected on the system zones and battery. The last line shows the battery voltage and current at the end of the test. If more than 1 test are in memory, then using the up/down arrow keys you can view them all.
If you select CAPACITY TEST and press “Enter” you see the screen on the right. The first line shows the indication 01/ΧΧ (where ΧΧ the amount of tests in memory) as well as the date and hour of the test. The following 3 lines show the results of the test (Passed or Failed), the duration and the capacity of the batteries. The last line shows the battery voltage and current at the end of the test. If more than 1 test are in memory, then using the up/down arrow keys you can view them all.
Page 37
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
37 from 44
During the first three months after the installation probably there will be no data concerning the autonomous duration.
If no information is available, then the screen on the right is shown.
5.1.3 Dimming Level
By selecting DIMMING LEVEL option and pressing “Enter” the screen on the right appears. This is an option that can dim the luminary’s light when on maintained mode. The lower percentage means lower light level.
Select between 12%, 25%, 37%, 50%, 67%, 75%, 87% and 100% and press “Enter”. Dimming level affects zones in staircase function too.
Dimming level DOES NOT AFFECT emergency mode.
5.1.4 Information
By selecting INFORMATION and pressing “Enter” you see the screen on the right. The INFORMATION menu contains additional options that are not visible on the first screen. Using the “Up/Down” keys you can scroll down to these options. These are LAST AUTONOMIES, PANEL SOFT VERSION and TECHNICIAN INFO.
The battery information shows the battery voltage, charge/discharge current and the temperature of the batteries’ compartment.
The mains power information shows the current voltage of the mains power supply.
If you select ZONES and press “Enter” then you see the screen on the right. Use the up/down arrow keys to select the required zone and press “Enter”.
Page 38
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
38 from 44
The screen shows information of the selected zone. You can see if it is installed, the zone’s output current, if the fuse is OK (NORMAL or FAULT), the current status (MAINS, BAT or OFF) and the voltage state of the output (NORMAL or FAULT). By pressing “Esc” you return to the INFORMATION menu.
If you select LUMINARIES and press “Enter” the system asks for the zone that the required luminary is installed into. Select the zone and press “Enter”.
Now the system asks for the luminary’s address. Select the required address and press “Enter” again.
Information concerning the selected address is displayed, as seen on the screen on the right. The first line “POINT X.YY” refers to the luminary’s address. Next line indicates whether there is a luminary installed or not under the specific address. The third line indicates zone number and luminary address, fourth line luminary type, fifth line communication status and last line, lamp status (ON/OFF).
If you select PANEL and press “Enter” you can see the screen on the right. The CURERENT LIMIT shows the total current that is drawn from the batteries when in emergency mode. The CONS.FROM BATTERY shows the battery output power in Watts currently. You can also see if the battery fan is operating (OΝ or OFF) and finally the STATUS which is OK if no fault is detected and FAULT if an error is detected (on the battery fan). By pressing “Esc” you return to the INFORMATION menu.
If you select NETWORK and press “Enter” you can see the screen on the right. In this screen you can see if the Ethernet card is installed and also the IP and MAC address of the system. By pressing “Esc” you return to the INFORMATION menu
With the option LAST AUTONOMIES, you can see all the logged autonomy durations of the system. On the first line you can see 01/ΧΧ (where ΧΧ the number of logged duration tests) along with the date and time of each logged event. You can see if the panel is fully charged or not, the duration of the emergency operation and the battery capacity used. With the “Up/Down” arrow keys you can change the logged emergency states. By pressing “Esc” you go back to the INFORMATION menu.
Page 39
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
39 from 44
With the option PANEL SOFT VERSION, you can retrieve information regarding the firmware installed in the panel. By pressing “Esc” you go back to the INFORMATION menu.
By selecting TECHNICIAN INFO and pressing “Enter” you see information regarding the name of the technician the telephone number and a general description of the panel. This information can be changed only by using a PC (via Ethernet). Press “Esc” to return to the INFORMATION menu.
5.1.5 Reset
By selecting RESET all current faults will be reset, including “CUTOFF TOOK PLACE” message.
The message “CUTOFF TOOK PLACE” is displayed when there was previously a system cutoff by low battery voltage when in emergency.
5.1.6 All Events
By selecting the option ALL EVENTS in the main menu and pressing “Enter” you can see the screen on the right. The top screen shows the logged information and the bottom screen shows the logged faults.
On logs containing information you can see the symbol “i" on the top left. On
its right with bold characters you can see the source of the event (in this case GENERAL PANEL). Below this you can see a description of the event, the date and time. The last line shows the number of the event to the total number of logged events.
On logs containing faults you can see the symbol Χ on the top left. On its right with bold characters you can see the source of the fault (in this case the ZONE 04). Under the X you can see the name of the zone (UNDERGROUND). Below this you see a description of the fault, the date and time. The last line shows the number of the fault to the total number of logged events.
With the “Up/Down” arrow keys you navigate between events. Press “Esc” to return to the previous menu.
5.1.7 Earth Test
If you select TEST EARTH FAULT and press “Enter” you deliberately invoke an earth fault to determine if the circuit that detects earth fault and the indicators are operating. After the test finishes the system returns to the initial screen.
Please be informed that when the batteries are disconnected and the battery fuse is unplugged, the earth test will not function.
Page 40
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
40 from 44
5.1.8 LED test
If you select TEST LED and press “Enter” you see the blank screen on the right. All LEDs on the front face are lit so you can inspect them visually. Press “Esc” to return to the initial screen.
Page 41
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
41 from 44
5.2 Operation via PC
The text below describes how a user can retrieve information of the system via a PC. The access for a common user is not full, because there are no options to program the system. For system programming via a PC see par.
4.2.
No special software is needed to use the system via a PC. A common web browser such as Google Chrome, MozillaFirefox, Internet Explorer, etc. can be used. The following photos show the use of Google Chrome. The requirements are that the panel must have an Ethernet card installed, you have to know its IP address, the computer must be connected to the same network and the settings must be correct. With suitable settings you can have access to the panel via internet globally. All these setting must be adjusted from the network administrator of the building.
The first action is to open a web browser and for the URL you must enter the IP address of the panel. If everything is connected correctly, then you will see the following screen.
All options available to the user are shown in the LINKS on the left apart from the TECHNICIAN MENU.
5.2.1 Panel Information
By selecting INFORMATION PANEL, you see the following screen which shows the current state of the panel.
Page 42
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
42 from 44
5.2.2 Zone programming information
In this screen you can see how each zone has been programmed to operate. The current limit column displays the current that has been measured during the CURRENT MEASUREMENT in the initial installation.
5.2.3 Zones status information
5.2.4 Information Point
Choose zone by clicking the links above (1, 2, 3, 4, 5, 6, 7, 8). By clicking any zone, all 32 addresses in that specific zone are shown below.
First column indicates address (point number). Second indicates by YES/NO if a luminary is installed in the specific address. Third column indicates point name. Fourth column indicates mode of function (maintained – non maintained). Fifth column indicates luminary type. Sixth column indicates if there is any fault at that point. Seventh column indicates communication status and last column the lamp status.
Page 43
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
43 from 44
5.2.5 Timer information
You can see the programming of the timers.
5.2.6 Function test results
You can see the last 10 results of the function tests.
5.2.7 Capacity test results
You can see the last 10 results of the capacity tests.
5.2.8 Last autonomies
You can see the latest 10 time periods that the panel has entered emergency mode.
Page 44
Date
26/6/2017
Document
923860006_09_006
Document code
923860006_09_006
Page
44 from 44
5.2.9 All events
You can see the latest 250 events of the panel.
5.2.10 Network information
You can see the network IP and MAC address of the system.
5.2.11 Panels network
If there is a network of panels then with this option, you can see how many and which panels are installed as well as the most important information for each panel.
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is specified in the official catalogue of Olympia Electronics and also in the technical le aflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be returned to the premises of our company for repair or replacement, as long as the warranty period is valid. Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.
HEAD OFFICE
72 . . . . nd km O N R Thessaloniki-Katerini
P C P.O. Box 06 ginio Pierias Greece. . 60300 Ε
www.olympia-electronics.gr info@olympia-electronics.gr
Loading...