Olsen LRF90, LRFV90, LRF100, LRFV100, LRF65NXU Installation, Operation & Maintanance Manual

...
Page 1
LRF
Lowboy Rear Flue Model
LRFV
Lowboy Rear Flue Model with ECM Blower
Oil Fired Warm Air Furnaces
INSTALLATION, OPER ATION &
MAINTENANCE MANUAL
ECR International
2210 Dwyer Avenue, Utica NY 13501
P/N 240011511, Rev. C [05/31/2017]
Page 2
DIMENSIONS
F
1
4.8cm
7
"
8
H
G
B
E
D
C
A
Table 1 - Dimensions
Furnace
Model
LRF/ LRFV
WidthALengthBHeight
22" 53-½" 33-⁵/8" 20-½" x 18"
55.8 cm 135.9 cm 85.4 cm
Cabinet Plenum - Openings
C
Supply
D x E
52.1 cm x 45.7cm 52.1 cm x 47.3cm
Return
F x G
20-½" x 18-⁵/8"
2
Flue
Diameter
5" 29" 20" x 20" x 1" 240 LB
12.7 cm 73.7cm 51cm x51cm x 2.5cm 108Kg
Height
H
Filter
(Permanent)
240011511 REV. C [05/31/2017]
Shipping
Weight
Page 3
1. General ............................................................................................................................... 4
2. Safety Symbols .................................................................................................................... 4
3. Introduction Models LRF/LRFV ................................................................................................ 4
4. Heat Loss ............................................................................................................................ 4
5. Locating the Unit ................................................................................................................. 5
6. Furnace Used In Conjunction With Air Conditioning .................................................................... 5
7. Air Filter .............................................................................................................................. 6
8. Ductwork ............................................................................................................................. 6
9. Combustion and Ventilation Air ............................................................................................... 6
10. Chimney Venting ................................................................................................................... 6
11. Barometric Damper Control .................................................................................................... 6
12. Optional Direct Venting .......................................................................................................... 6
13a. Fan Timer Board And Limit Control (LRF) [See Figure 2, page 15] ............................................. 6
13b. Fan Timer Board And Limit Control (LRFV) [See Figure 3, page 15] ............................................ 7
14. Electrical Connections ............................................................................................................ 7
15. Humidier ............................................................................................................................ 7
16. Piping Installation ................................................................................................................. 7
17. Oil Filter .............................................................................................................................. 7
18. Oil Burner Nozzles ................................................................................................................. 8
19. Oil Burner Adjustment ........................................................................................................... 8
20. Burner Electrodes.................................................................................................................. 8
21. Burner Primary (Safety) Control .............................................................................................. 8
22a. Circulating Air Blower (LRF/LRFV) .......................................................................................... 8
22b. Circulating Air Blower (LRFV) ............................................................................................... 9
23. Maintenance And Service ....................................................................................................... 9
24. Operating Instructions (LRF) ..................................................................................................10
25. Operating Instructions (LRFV) ................................................................................................10
Appendix A - Checkout and Adjustments ................................................................................. 11
A.1 Oil Burner Air Adjustment ..............................................................................................13
A.2 Burner Electrodes .........................................................................................................13
A.3 Start Up ......................................................................................................................14
A.4 Final Checkout .............................................................................................................14
A.5 Blower Setup ...............................................................................................................16
Appendix B - Wiring Diagrams ................................................................................................. 18
Chimney Vent Furnace Wiring Diagram LRF/LRFV ...................................................................19
Direct Vent Furnace Wiring Diagram LRF/LRFV......................................................................20
Appendix C - Sequence of Operation and Troubleshooting ...................................................... 21
C.1 Troubleshooting ...........................................................................................................23
C.2 Preliminary Steps: ........................................................................................................23
C.3 Check Oil Primary Control ..............................................................................................23
Appendix D - Home Owners Reference Table ........................................................................... 27
Parts Listing: Chimney Vent Models LRF/LRFV ........................................................................ 28
Parts Listing: Direct Vent Models LRF/LRFV ............................................................................ 30
Parts Diagram ......................................................................................................................... 31
Check our website frequently for updates: www.ecrinternational.com
Information and specications outlined in this manual in effect at the
time of printing of this manual. Manufacturer reserves the right to
discontinue, change specications or system design at any time without
notice and without incurring any obligation, whatsoever.
3
240011511 REV. C [05/31/2017]
Page 4
1. General
Furnace installation shall be completed by qualied agency. See
glossary for additional information.
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
WARNING
!
Fire, burn, asphyxiation hazard. Do not use gasoline, crank case oil, or any oil containing gasoline. Failure to follow these instructions could result in death or serious injury.
3. Introduction Models LRF/LRFV
Models LRF and LRFV are oil red forced air lowboy furnaces with an output capacity range of 65,000 BTU/hr to 100,000 BTU/hr.
• LRF may be equipped with either 1/2 HP PSC 4 speed direct drive or single speed belt drive blower motor.
• LRFV is equipped with 1/2 HP ECM variable speed blower motor.
• Furnaces are factory equipped for chimney venting or factory equipped for direct venting.
» Chimney vent and direct vent models are not eld
convertible.
» Supplemental direct vent installation instructions are
included with direct vent models.
Installation shall conform to requirements of authority having jurisdiction or in absence of such requirements:
2. Safety Symbols
Become familiar with symbols identifying
potential hazards.
This is the safety alert symbol. Symbol alerts you to potential personal injury hazards. Obey all safety messages following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• Canada - CAN/CSA - B139, Installation Code for Oil-Burning Equipment.
• United States - National Electrical Code, NFPA31, Standard for the Installation of Oil-Burning Equipment.
Models are CSA listed, (NRTL/C) for use with No. 1 (Stove) and No. 2 (Furnace) Oil.
Refer to tables in Appendix A for performance data.
4. Heat Loss
Maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures described in the manuals of:
• Canada - The Heating, Refrigeration and Air Conditioning Institute of Canada (HRAI), or by other means prescribed, or approved by the local authority having jurisdiction.
• United States - Manual J. titled, "Load Calculation" published by the Air Conditioning Contractors of America, describes a suitable procedure for calculating maximum hourly heat loss.
NOTICE
Used to address practices not related to personal injury.
4
240011511 REV. C [05/31/2017]
Page 5
!
WARNING
Fire hazard. Do not install furnace on tiled oors or
carpeting. Failure to follow these instructions could result in death or serious injury.
5. Locating the Unit - [See Table 2]
Locate furnace so ue connection to chimney is short, direct and consists of as few elbows as possible.
• Centralize furnace location with respect to supply and return air ductwork. Central location minimizes trunk duct sizing.
All models may be installed on combustible oors.
Do not install furnace on carpet or tiled oors.
Maintain all clearances to combustibles. See Table 2.
Table 2: Minimum Installation Clearances
Location
Top 1" (26mm)
Bottom 0"
Plenum 1" (26 mm)
Rear 6" (152 mm)*
Sides 1" (26 mm)**
Front 1" (26 mm) *
Flue Pipe 5" (127 mm)
Enclosure Closet
* 24" (610 mm) Service Clearance
** 18" (457 mm) required from on side for access to rear
Clearance to Combustibles
LRF and LRFV
FIGURE 1a: Evaporator Coil
Block-Off Plates
FIGURE 1b: Evaporator Coil Centered Over Narrow Furnace
6. Furnace Used In Conjunction With Air Conditioning
• Install furnace in parallel with or upstream from evaporator
coil to avoid condensation in heat exchanger.
• When installed in parallel, prevent chilled air from entering
furnace by use of dampers or other air controlling means.
• Manually operated dampers must have a control to prevent
operation of either system unless dampers are in full heat or full cool position.
• Air heated by the furnace shall not pass through evaporator
coil unless coil is specically approved for such service.
• Check and adjust blower speed to compensate for pressure
drop caused by evaporator coil.
• Maintain required clearance between bottom of coil drain pan
and top of heat exchanger as specied by coil manufacturer.
• Cased evaporator coils with cases that are slightly larger
than the furnace cabinet may be used by employing eld
fabricated block off plates to close gap between furnace cabinet and coil casing. See Figures 1a and 1b.
• Cased evaporator coils with cases that are smaller than
the furnace cabinet should not be used as they will restrict
airow.
5
240011511 REV. C [05/31/2017]
Page 6
7. Air Filter
Install properly sized air lter on return air side of unit.
Furnace is supplied with 20" x 20" permanent air lter and
lter slot in blower compartment.
If lter is damaged, replace with lter of same size and type.
Manufacturer recommends breech draft of -0.02 in. w.c.
Flue pipe must not pass through any oor or ceiling, may pass through a wall where suitable re protection provisions have been
installed.
• Canada, refer to CAN/CSA B-139 for rules governing the installation of oil burning equipment.
8. Ductwork
• Supply and return air ductwork must be designed and installed in accordance with approved methods, local and national codes as well as good trade practices.
• When ductwork supplies air to space other than where furnace is located, return air must be sealed and directed to this space.
9. Combustion and Ventilation Air
Comply with CSA B139 (Canada) or NFPA 31 (US) standards for the Installation of Oil Burning Equipment and applicable provisions of local building codes to provide combustion and ventilation air.
WARNING
!
Failure to provide adequate combustion and ventilation air could result could result in death or serious injury.
WARNING
!
Asphyxiation hazard. Chimney vented versions of
furnace must be connected to ue having sufcient
draft at all times. Failure to follow these instructions could result in death or serious injury.
• United States, refer to NFPA 31 for regulations governing the installation of oil burning equipment.
See appendix A for burner set-up.
11. Barometric Damper Control
Barometric damper control, also known as draft regulator, is used on conventional chimney venting only. Control automatically maintains constant negative pressure. Ensures proper pressures
are not exceeded. If chimney does not develop sufcient draft,
draft control does not function properly.
• Install draft regulator in same room or enclosure as furnace. Draft regulator should not interfere with combustion air supplied to the burner.
Locate control near furnace ue outlet.
• Install per instructions supplied with regulator.
• Set breech draft to -0.02 in. w.c.
12. Optional Direct Venting
Certain LRF/LRFV furnaces are manufactured as direct vent units. Refer to Direct Vent Supplement Installation, Operation and Maintenance Manual, part number 240011896, included with direct vent furnace, for details.
Direct venting requires use of specic oil burners, Beckett NX or
Riello 40BF3 or 40BF5.
Refer to Appendix A, Tables A-2 and A-4.
NOTICE
This furnace is approved for use with Type L vent or equivalent. Maximum vent temperature for Type L vent is 575°F (300°C).
10. Chimney Venting
• Flue pipe should be as short as possible with horizontal pipes sloping upward toward the chimney at a rate of one-quarter inch per foot.
• Flue pipe should not be smaller in cross sectional area than
ue collar on the furnace.
Flue pipe should connect to chimney so the ue pipe extends into, and terminates ush with the inside surface of chimney
liner. Seal the joint between pipe and lining.
• Chimney outlet should be at least two feet above highest point of peaked roof.
• All unused chimney openings should be closed.
• Chimneys must conform to local, provincial or state codes, or in the absence of local regulations, to the requirements of the National Building Code.
13a. Fan Timer Board And Limit Control (LRF) [See Figure 2, page 15]
Electronic Fan Timer integrates control of burner and circulator fan operations. Control is central wiring point for most of furnace electrical components.
• United Technologies 1158-120 has an adjustable fan on time set by selecting dipswitch combination displayed in Chart
1. Fan on delay can be set at 30, 60, 90 or 120 seconds. Provides a delay between burner ignition and blower start-up
to eliminate excessive ow of cold air when blower comes
on. Manufacturer recommended fan on delay is 30 seconds for LRF100 models and 60 seconds for LRF65/80/90 models.
• United Technologies 1158-120 has an adjustable fan off time of 2, 3, 4 or 6 minutes as displayed in Chart 1. Fan off delay time starts when burner motor is de-energized at end of call for heat. Blower shutdown is delayed to remove any residual heat from heat exchanger. Manufacturer recommended fan off delay is 2 minutes.
• Electronic fan timer board works in conjunction with snap disc limit controls, performing a safety function, shutting off burner if furnace over-heats.
6
240011511 REV. C [05/31/2017]
Page 7
• Limit control is thermally operated and automatically resets. Limit control is factory installed, pre-set and is not adjustable.
• If limit control opens with United Technologies 1158-120 electronic fan control, circulating fan will energize. When limit closes, fan off timer begins. At the end of fan off time cycle burner is energized, initiating normal burner cycle.
Chart 1- United Technologies 1158-120 (LRF)
Dip Switch Position Blower Delay Times
1 2 3 4 On Seconds Off Minutes
Off Off 30 On Off 60 Off On 90 On On 120
Off Off 2 On Off 3 Off On 4 On On 6
• Accessories requiring 120 VAC power sources such as
electronic air cleaners and humidier transformers may be
powered from electronic fan timer board where provisions have been made for connections, but should have their own controls.
• Do not use direct drive motor connections as a power source, there is risk of damaging accessories.
• Thermostat wiring connections are shown in wiring diagrams in Appendix B. Some micro-electronic thermostats require additional controls and wiring. Refer to thermostat manufacturer's instructions.
• ECM Blower note - Single stage cooling use terminal Y/Y2.
Two stage cooling use terminal Y1 for rst stage and Y/Y2 for second stage. When Y1 is energized, air ow is reduced
by 20%. Do not use terminal Y1 with single stage cooling or heat pump.
Locate thermostat approximately 5 feet above oor, on inside wall, and where thermostat is exposed to average room temperatures. Avoid locations where thermostat is exposed to cold drafts, heat from nearby lamps and appliances, exposure to sunlight, heat from inside wall stacks, etc.
13b. Fan Timer Board And Limit Control (LRFV) [See Figure 3, page 14]
United Technologies 1168-1 ECM tap board has adjustable fan on/
off delay and airow settings that must be adjusted in accordance
with furnace input rating (nozzle size). Refer to Table A-10 for ECM blower set-up.
14. Electrical Connections
• Furnace is listed by Canadian Standards Association under NRTL (North American) Standard.
All eld wiring shall conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail.
• United States, wiring shall conform to National Fire Protection Association NFPA-70, National Electrical Code, and with local codes and regulations.
• Wire furnace to separate dedicated circuit in main electrical panel.
• Suitably located circuit breaker can be used as service switch, separate service switch is advisable.
• Service switch is necessary if circuit breaker is close to the furnace, or furnace is located between circuit breaker and entry to furnace room.
• Clearly mark service switch. Install in accessible area between furnace and furnace room entry. Locate so as to reduce possibility it can be mistaken as light switch or similar device.
• Power requirement for all LRF models is: 120 VAC, 1 Ø, 60 Hz., 12A.
• Accessory equipment such as electronic air cleaners and
humidiers may be included on furnace circuit.
• Adjust thermostat heat anticipator to amperage draw of heating control circuit as measured at "R" and "W" terminals of thermostat. Do not measure current with thermostat connected to the circuit. Measure amperage by connecting ammeter between two wires which connect to thermostat "R" and "W" terminals.
15. Humidier
Humidier is optional accessory available through most heating supplies outlets.
Follow humidier manufacturer's installation instructions
• Protect furnace heat exchanger from water or water droplets
from humidier.
• Do not use direct drive motor connections as source of
power for 120 VAC humidiers and humidier transformers.
16. Piping Installation
• Install fuel system in accordance with requirements of CAN/ CSA B-139, and local regulations.
• United States installation shall conform to NFPA No. 31 and local codes and authorities.
Use only approved fuel oil tanks, piping, ttings and oil lter.
Install oil lter as close to burner as possible.
• Refer to instructions and illustrations in oil burner and oil pump instructions shipped with the furnace.
17. Oil Filter
Install oil lter between fuel oil storage tank and oil burner. When
using oil burner nozzle smaller than 0.65 U.S. Gallons Per Hour,
install additional 7 to 10 micron lter as close as possible to oil
burner.
7
240011511 REV. C [05/31/2017]
Page 8
18. Oil Burner Nozzles
Furnaces are certied for multiple ring rates. Furnace may be red at ideal rate for wide range of structures by manipulating oil
burner setup and blower settings. Refer to Table A-1 thru A-9, and furnace rating plate to determine proper combinations. Nozzles for
alternate ring rates are included with furnace.
WARNING
!
Fire, burn, asphyxiation hazard. Do not start the burner unless blower access door is secured in place. Failure to follow these instructions could result in death or serious injury.
19. Oil Burner Adjustment
• Adjust burner air supply to maintain fuel to air ratio to obtain ideal combustion conditions.
Lack of air causes "soft" and "sooty" ames, resulting in soot build-up throughout heat exchanger passages.
Excess combustion air causes bright roaring re and high
stack temperatures resulting in poor fuel efciency.
LRF and LRFV operate most efciently with No. 1 smoke spot on Bacharach Scale. Dust will eventually build up on air moving components of oil burner assembly resulting in
decreased air supply with potential soot build up in ue gas
passageways of heat exchanger. Soot behaves as insulator and impairs good heat transfer. Stack temperature increases,
and efciency decreases. To avoid this problem, adjust the air
supply as follows:
» Chimney vented units - adjust air supply to provide no
more than a trace smoke spot on the Bacharach scale.
» Direct vented units - adjust air supply for zero smoke per
the Direct Vent Supplement Installation, Operation and Maintenance Manual included with direct vent furnace.
20. Burner Electrodes
Correct positioning of electrode tips with respect to each other, fuel oil nozzle, and burners is essential for smooth light ups and proper operation.
Refer to oil burner instructions provided with furnace and
Appendix A Section A.2 in this manual for electrode specications.
NOTICE
Do not tamper with furnace controls they are sensitive. If problems persist, call your service contractor.
21. Burner Primary (Safety) Control
Furnace is equipped with primary combustion control, also referred to as burner relay or burner protector relay, which uses a cad cell located in burner housing, to monitor and control combustion.
Dust or combustion residuals can build up on lens of cad cell
impairing its response to ame. Check cad cell for cleanliness
and proper alignment if primary control frequently shuts down combustion.
22a. CIRCULATING AIR BLOWER (LRF/LRFV)
• LRF furnace models may be equipped with either direct drive or belt drive blower systems.
• LRFV furnace models are equipped with direct drive blower systems.
• LRF models are equipped with PSC motors.
• LRFV models are equipped with electronically commutated motors (ECM).
Direct Drive Blower Systems
• Direct drive blower speed adjustments are not normally required in properly sized extended plenum duct systems. Motor RPM and air CFM delivery will vary automatically to accommodate conditions within usual range of external static pressures typical of residential duct systems.
• Under-sized duct systems may require higher blower speed to obtain system temperature rise.
• Some older duct systems were not designed to provide static pressure. They typically feature special reducing
ttings at each branch run and lack block ends on the trunk ducts. These systems may require modication to provide some resistance to the airow to prevent over-amping of
direct drive blower motor. Selecting a lower blower speed may correct this problem.
• Direct drive blower speeds are adjusted by changing "hot" wires to motor winding connections. Refer to wiring
diagrams in Appendix B or wiring diagram label afxed to
furnace.
• Do not move neutral wire (normally white wire) to adjust blower speed.
• Single blower speed for both heating and cooling modes may be used. Use a "piggy-back connector" accommodating both wires on a single motor tap.
• It is also acceptable to connect selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut.
• Safety precaution against accidental disconnection of wires by vibration, secure wire nut and wires with few wraps of electricians tape.
• Do not connect power leads between motor speeds. Always connect neutral wire to motor's designated neutral terminal.
• If joining blower speed wiring is done in furnace junction box, tape off both ends of unused wire.
• Do not use blower speed wires as source of power to
accessories as electronic air cleaners and humidier
transformers. Unused motor taps auto-generate
sufciently high voltages to damage accessory
equipment.
8
240011511 REV. C [05/31/2017]
Page 9
Belt Drive Blower Systems
WARNING
!
Improper installation could result in death or serious injury. Belt drive components operate at high speeds and may snag loose clothing resulting in injury or death. Have a trained service professional preform the following instructions. Failure to follow these instructions could result in death or serious injury.
!
WARNING
Electrical shock hazard. Turn OFF electrical power supply at service panel before opening blower access door. Failure to do so could result in death or serious injury.
22b. Circulating Air Blower (LRFV)
LRFV furnace models are equipped with electronically commutated motors (ECM).
Belt drive blower systems can be modied for speed and air deliv­ery by adjusting variable speed motor pulley and changing blower pulley.
• Adjust variable speed motor pulley by loosening 5/32 Allen set screw in outer sheave. Turn outer sheave clockwise to increase blower speed, counter clockwise to reduce speed.
Verify setscrew is tightened at one of the at spots, failure
to do so will convert the variable speed pulley to a xed
speed pulley by ruining the threads.
• Modify blower speed by changing the blower pulley. Smaller blower pulley will cause the blower to turn faster. Large pulley reduces blower speed.
• Large increases in the blower speed may increase power requirements.
• Check amperage draw of the blower motor after making changes. If amperage draw is greater than the value listed on the motor rating plate, replace with motor of higher horsepower.
Deection of 3/4 of an inch to 1 inch fan belt tension is
necessary. Less deection places a strain on the blower
bearings and increases start up amperage draw.
More deection allows excess slippage and causes premature motor pulley wear.
• Automotive belt dressings are not recommended.
• Bar soap will work as belt dressing to reduce belt squeaks, etc. If using soap apply to the sides of belt only.
If operating belt drive blower at speeds above 1100 RPM, replace sintered bronze blower bearings with roller bearings.
Setting Blower Speed and “ON” and “OFF” Timings
Blower speed and on/off time delays are handled by ECM motor programming and are set via dipswitches per Table A-10.
Heating airow rate is SW1 and on/off delay is SW4, both are set according to ring rate. Cooling airow rate is SW2 and if used
is set according to installed cooling capacity. SW3 can be used
to adjust airow rate by (+) or (-) 15%. Features of this ECM variable speed motor are that it will deliver a constant airow
within a wide range of external static pressures, and also includes:
• Soft Start: ECM will slowly ramp up to required operating speed. In heating cycle allows heat exchanger to reach operating temperature before set heat speed, minimizes noise and increases comfort.
• Soft Stop: At end of heating cycle, ECM will slowly ramp
down. Allows increased energy efciency and reduced noise
levels.
Dehumidication: Feature is programmed into the variable speed motor. At start of each cooling cycle, variable speed
motor will run at 82% of rated airow for 7.5 minutes. After
7.5 minutes has elapsed, motor will increase to 100% of
rated airow. Used to provide dehumidication and improve system efciency.
• Continuous Fan Operation: When thermostat continuous fan (G) switch is on without call for heating or cooling, indoor fan is immediately energized at 50% of cooling speed. Allows continuous circulation of air between calls for heating or cooling. If call for heat (W) or cool (Y) occurs during continuous fan, blower remains energized.
23. Maintenance And Service
Routine Maintenance By Home Owner
• Arrange for professional servicing of furnace by the service or installation contractor annually.
Homeowner is to maintain air lter or lters. A dirty lter can cause furnace to over-heat, fail to maintain indoor temperature during cold weather, increase fuel consumption and cause component failure.
Inspect, clean or replace lter monthly.
Furnace is supplied with semi-permanent type lter. If lter
is damaged, replace with lters of same size and type.
During monthly lter inspection, inspect general condition of furnace. Watch for signs of oil leaks in vicinity of oil burner, soot forming on any external part of furnace, soot forming around joints in vent pipe, etc. If any of these conditions are present, please advise your service or installation contractor.
9
240011511 REV. C [05/31/2017]
Page 10
Annual Service By Contractor
• Inspect heat exchanger periodically and clean if necessary.
!
WARNING
Electrical shock hazard. Turn OFF electrical power supply at service panel before service or maintenance Failure to do so could result in death or serious injury.
• If cleaning is necessary, shut off oil supply, shut off power to the furnace and remove burner.
• Remove cleanout cover and turbulators.
• Wire brush can be used to loosen dirt and debris on the inside surfaces of heat exchanger. Clean out all accumulated dirt, soot and debris with a wire handled brush and industrial vacuum cleaner.
• Clean and reinstall turbulators.
• Before replacing cleanout cover, inspect gaskets. If gasket is broken, remove remnants and replace with new gaskets. Replace cleanout cover.
• Blower motor is factory oiled and permanently sealed. Do not lubricate. Excess oil causes premature electric motor failure.
• Inspect blower fan. Clean if necessary.
• Oil Burner Maintenance: Follow oil burner manufacturer instructions.
Change oil burner nozzle and oil lter annually.
• Clean and inspect venting system for signs of deterioration and leakage. Replace pitted or perforated vent pipe and
ttings.
• Barometric damper should open and close freely.
• Check electrical connections to ensure tight connections. Safety controls such as the high limit controls should be tested for functionality.
• Check fan control to ensure fan on and off delay function continues to start and stop blower fan at optimal settings.
• Check operation of limit switch.
24. Operating Instructions (LRF)
Before Lighting
1.
Open all supply and return air registers and grilles.
WARNING
!
Fire, burn, explosion, asphyxiation hazard.
• Do not start burner when excess oil has accumulated, furnace is full of vapor, or combustion chamber is very hot.
• Do not burn garbage or paper in furnace.
• Do not leave paper or rags around furnace.
Failure to follow these instructions could result in death or serious injury.
2.
Open all valves in oil pipes.
3.
Turn on electric power supply
To Light Unit
1.
Set thermostat above room temperature to call for heat. Burner should start. It may be necessary to press RESET button on primary combustion control relay.
2.
There is a fan on time delay before circulating fan is energized. United Technologies 1158-120 has adjustable fan on time set by selecting dipswitch combination displayed in Chart 1. Fan on delay can be set at 30, 60, 90 or 120 seconds. Manufacturer recommended fan on delay is 30 seconds for LRF100 models and 60 seconds for LRF65/80/90 models.
3.
Set thermostat below room temperature. Oil burner stops.
4.
Air circulation blower continues to operate until time off setting selected on electronic fan timer control times out. United Technologies 1158-120 has adjustable fan off time of 2, 3, 4 or 6 minutes. Manufacturer recommended fan off delay is 2 minutes for all models. Fan timer control adjustments may be altered if air at room registers is high upon blower start up or shutdown.
5.
Restore thermostat setting to comfortable temperature.
NOTICE
If furnace is to be shut down for extended period of time, close oil supply valve to burner.
To Shut Down Unit
1.
Set thermostat to lowest possible setting.
2.
Set manual switch (if installed) in electrical power supply line to "OFF".
25. Operating Instructions (LRFV)
Before Lighting
1.
Open all supply and return air registers and grilles.
2.
Open all valves in oil pipes.
3.
Turn on electric power supply.
To Light Unit
1.
Set thermostat above room temperature to call for heat. Burner should start. It may be necessary to press RESET button on primary combustion control relay.
2.
There is a fan on time delay before circulating fan is energized. United Technologies 1168-1 has adjustable fan on/off time delay programmed into ECM motor, and is set by selecting SW4 DIP switch combination displayed in Table A-10. Adjust Fan on/off delay according to input (nozzle size).
3.
Set thermostat below room temperature. Oil burner stops.
4.
Air circulation blower continues to operate until blower off delay setting programmed into ECM motor times out.
5.
Restore thermostat setting to comfortable temperature.
If furnace is to be shut down for extended period of time, close oil supply valve to burner.
To Shut Down Unit
1.
Set thermostat to lowest possible setting.
2.
Set manual switch (if installed) in electrical power supply line to "OFF".
10
NOTICE
240011511 REV. C [05/31/2017]
Page 11
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Check out and adjustments
LRF and LRFV furnaces may be used with following oil burners.
Beckett AFG and Riello 40F3 and Carlin EZ-LF oil burners are for chimney vent applications using indoor air for combustion only.
Beckett NX and Reillo 40BF3/40BF5 oil burners are for direct vent applications using outdoor air for combustion only.
Settings shown below are for initial startup only. Final adjustments shall be made using combustion test instructions
Table A-1 Beckett AFG Oil Burner Set-Up
Beckett AFG Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
Output
BTU/Hr
Burner Model
Delavan
Nozzle
Pump
Pressure
[PSIG]
Flow Rate
[USGPH]
Head
Air
Setting
LRF65
66,000 AFG70MPSS 0.50 / 45°W 140 0.55 L2 4
LRFV65
LRF80
78,000 AFG70MPSS 0.50 / 45°W 175 0.65 L2 5
LRFV80
LRF90
89,000 AFG70MPSS 0.60 / 60°W 175 0.75 L2 7
LRFV90
LRF100
100,000 AFG70MPSS 0.65 / 60°W 175 0.85 L2 8
LRFV100
Table A-2 Beckett NX Oil Burner Setup
.
Beckett NX Series Oil Burners
(For use with direct vent units using outdoor combustion air only)
Furnace Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
[PSIG]
Flow Rate
[USGPH]
Low Firing
Rate Bafe
LRF65NXU
65,000 NX56LQ 0.50 / 60°W 140 0.55 Yes 3
LRFV65NXU
LRF80NXU
76,000 NX56LQ 0.50 / 60°W 175 0.65 Yes 3.25
LRFV80NXU
LRF90NXU
87,000 NX56LQ 0.60 / 60°W 175 0.75 No* 3.25
LRFV90NXU
LRF100NXU
98,000 NX56LQ 0.65 / 60°W 175 0.85 No* 3.75
LRFV100NXU
* Burner is factory equipped with low ring rate bafe. Remove for 0.75 and 0.85 USGPH ring rates.
Air
Setting
11
240011511 REV. C [05/31/2017]
Page 12
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Table A-3 Riello 40F3 Burner Set-Up
Riello 40F3 Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
LRF65RF
Output
BTU/Hr
Burner
Model
40F3
66,000
LRFV65RF
LRF80RF
VSBT
40F3
77,000
LRFV80RF
LRF90RF
VSBT
40F3
88,000
LRFV90RF
LRF100RF
VSBT
40F3
99,000
LRFV100RF
VSBT
Table A-4 Riello 40BF Burner Set-Up
Riello 40BF3/40BF5 Series Oil Burners
(For use with direct vent units using outdoor combustion air only)
Furnace Model
Output BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
[PSIG]
Flow Rate
[USGPH]
Head
Setting
Air
Setting
0.50 / 90°B 125 0.55 0 1.6
0.55 / 80°B 140 0.65 0 2.1
0.65 / 80°B 133 0.75 1 2.5
0.75 / 80°B 128 0.85 2 3
Delavan
Nozzle
Pump
Pressure
[PSIG]
Flow Rate
[USGPH]
Turbulator
Setting
Air
Setting
LRF65RBU
65,000 40BF3 0.50 / 90°B 125 0.55 0.0 4.25
LRFV65RBU
LRF80RBU
76,000 40BF3 0.55 / 80°B 140 0.65 1.0 5.25
LRFV80RBU
LRF90RBU
87,000 40BF5 0.65 / 80°B 140 0.75 0.0 3.75
LRFV90RBU
LRF100RBU
98,000 40BF5 0.75 / 80°B 130 0.85 0.0 4.25
LRFV100RBU
Note: Riello 40BF3 burner is required for 0.55 and 0.65 USGPH ring rates. Riello 40BF5 burner is required for 0.75 and 0.85 USGPH ring rates.
12
240011511 REV. C [05/31/2017]
Page 13
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Table A-5 Carlin EZ-LF Oil Burner Set-Up
Carlin EZ-LF Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
[PSIG]
LRF65C
66,000 EZ-LF 0.50 / 70°B 125 0.55
LRFV65C
LRF80C
78,000 EZ-LF 0.50 / 70°B 170 0.65
LRFV80C
LRF90C
89,000 EZ-LF 0.65 / 70°B 135 0.75
LRFV90C
LRF100C
100,000 EZ-LF 0.65 / 70°B 170 0.85
LRFV100C
* Burner is factory equipped with single slot air band. Replace with furnished two slot air band for 0.75 and 0.85 USGPH ring rates.
A.1 Oil Burner Air Adjustment
Consult oil burner instructions provided in furnace documents
envelope for specic information concerning burner adjustments,
operation and troubleshooting.
Beckett AFG Burner (Chimney Vent)
Adjust air band by loosening locking screw. Re-tighten locking screw after each adjustment. Locking screw must be tight when
taking combustion readings, as airow changes when screw is
loosened.
A.2 Burner Electrodes
Adjustment of electrode tips with respect to each other, nozzle, burner head is very important to ensure smooth start-ups and to
permit efcient combustion.
Beckett AFG
• Electrode gap: 5/32 inch.
• Distance above horizontal center-line: 1/4 inch.
• Distance ahead of nozzle: 1/8 inch.
Flow Rate
[USGPH]
Air
Band
Single
Slot
Single
Slot
Two
Slot*
Two
Slot*
Head Bar
Setting
0.60 / 0.65 35%
0.60 / 0.65 65%
0.75 45%
0.85 / 1.00 45%
Air
Beckett NX Burner (Direct Vent)
Loosen splined nut on nozzle line one turn. Turn adjustment screw clockwise to increase air and counter clockwise to decrease air. Tighten splined nut after obtaining proper setting.
Riello 40F3 Burner (Chimney Vent)
Combustion air is adjusted by removing burner cover. Loosen screws that secure air adjustment plate. Move adjusting plate to either increase or decrease combustion air. When proper air
setting is achieved, re-tighten xing screws. Re-install cover.
Riello 40BF Burner (Direct Vent)
Combustion air can be adjusted with burner cover on. Remove plastic cover on top right hand side of burner cover. With Phillips screwdriver turn adjusting screw clockwise to increase air and counter clockwise to decrease air. When combustion air is set, reinsert plastic cover.
Carlin EZ-LF (Chimney Vent)
Adjust air band by loosening locking screw. Re-tighten locking screw after adjustment.
• “Z” dimension, distance from front of end cone (head) to
Beckett NX
• Electrode gap: 5/32 inch.
• Distance above horizontal center-line: 1/4 inch.
• Distance ahead of nozzle: 3/32 inch.
Check/adjust zero calibration per Beckett NX oil burner
Riello Burners
• Electrode gap: 5/32 inch.
• Distance above horizontal center-line: 13/64 inch.
• Distance ahead of nozzle: 5/64 to 7/64 inch.
Carlin Burners
• Electrode gap: 1/8 inch to 5/32 inch.
• Distance above horizontal center-line: 5/16 inch.
• Distance ahead of nozzle: Flush to 1/16 inch.
13
face of nozzle should be 1-3/4 inch.
manual supplied with furnace.
240011511 REV. C [05/31/2017]
Page 14
APPENDIX A - CHECK OUT AND ADJUSTMENTS
A.3 Start Up
Use following instructions to set the burner:
1.
Shut off electrical power to the furnace.
2.
Install oil pressure gauge to pressure port on oil pump.
(Refer to oil pump specication sheet included with burner
instructions).
3.
Restore electrical power to furnace.
4.
Start furnace and bleed all air from fuel oil lines.
5.
Close purge valve and re the unit.
6.
Allow furnace to warm up to normal operating temperatures. During this time, set pump pressure in accordance with data provided in Appendix A, Table A-1 thru A-3.
7.
Chimney vented units - Drill 1/4" test port in venting
between furnace ue outlet and draft regulator (barometric
damper) to take smoke readings.
8.
Direct vented units - Do not drill. Use test port in furnished appliance connector to take smoke readings.
9.
When furnace has reached "steady state" (after approximately 10 minutes), set combustion air damper to get TRACE of smoke for chimney vented units.
10.
Check system temperature rise. Temperature rise is the difference between return air temperature measured at a point near return air inlet, and supply air temperature measured near furnace outlet.
System temperature rise is listed on furnace rating plate. If
temperature rise is too high, airow must be increased. If
temperature rise is too low, slow fan down.
11.
Chimney vented units - after air adjustments have been completed, recheck the breech draft. Breech draft should be adjusted to -0.02 inches w.c.
12.
Turn burner off. Observe duct thermometer in supply air stream, note temperature blower fan stops. Fan adjustments can be made by moving dipswitch settings on timer control board for fan off delay.
14.
Set heat anticipator adjustment in thermostat (if so equipped), by removing "R" or "W" wire to thermostat. Read
amperage draw between the two wires. Failure to remove one of the wires from thermostat while performing this test could burn out heat anticipator. Set heat anticipator to amperage measured.
15.
Direct vented units - Check all joints in positive pressure venting system for leaks before leaving site.
16.
Run furnace through at least three full cycles before leaving installation, to ensure all controls are operating properly.
A.4 Final Check Out
Verify all safety devices and electrical components have been set for normal operation.
Verify all electrical connections are tight and wiring is secure.
Verify homeowner is informed and understands:
• Where circuit breaker or fuse is located in main electrical panel.
• Where furnace switch is located, and switch "on" and "off" positions if not obvious.
• Where oil shut-off valve from oil storage tank is located.
• Thermostat operation, and other related accessories.
• How to operate manual reset button on primary control, and when not to push the reset button.
• How and where to visually inspect venting system for leaks or other problems.
How to inspect, clean and replace air lter, and other homeowner maintenance procedures.
• Who to call for emergency service and routine annual service.
13.
Check operation of limit switch. A. Shut off power to furnace.
B. Temporarily remove neutral wire from PSC blower motor
or from neutral terminal on fan timer control, or remove 5 pin power connector from ECM blower motor. Isolate AC line voltage pins on 5 pin power connector with
electrical tape to prevent electric shock hazard. C. Restore electrical power to furnace. D. Set thermostat above room temperature. E. After two or three minutes of burner operation, limit
control should turn burner off. F. When limit function test is complete, shut off electrical
power to furnace, replace neutral wire or 5 pin power
connector. Restore power. G. Blower fan will start up immediately. Once temperature
has dropped and limit control has reset, fan will operate
until fan off time is reached. H. Oil burner will resume operation and continue until
thermostat is satised.
I. Restore thermostat setting to comfortable temperature.
14
240011511 REV. C [05/31/2017]
Page 15
APPENDIX A - CHECK OUT AND ADJUSTMENTS
FIGURE 2: UNITED TECHNOLOGIES 1158-120 FAN TIMER BOARD (LRF)
FIGURE 3: UNITED TECHNOLOGIES 1168-1 ECM TAP BOARD (LRFV)
15
240011511 REV. C [05/31/2017]
Page 16
APPENDIX A - CHECK OUT AND ADJUSTMENTS
A.5 Blower Setup
Table A-6 Direct Drive Blower Motor Setup - 1/2 HP PSC 4 Speed Motor
Heating Blower Set-Up Cooling Capacity
0.20 in. w.c. 0.50 in. w.c.
Speed Speed
∆T Speed
0.20 0.30 0.40 0.50 0.60
High 1455 1383 1314 1249 1160
Med-High 1427 1345 1286 1216 1128
Med-Low 1234 1170 1135 1054 973
Low 827 819 805 766 709
Furnace
Model
LRF
65 – 100
Furnace
Model
LRF65 100-10T DD Low Low 3 766-1249
LRF80 100-10T DD Low Medium Low 3 766-1249 LRF90 100-10T DD Medium Low Medium High 3 766-1249
LRF100 100-10T DD Medium High High 3 766-1249
Blower
Table A-7 Direct Drive Blower Characteristics - 1/2 HP PSC 4 Speed Motor
Blower
100-10T DD 6.0 55-85 °F
Motor
FLA
Tons
CFM
External Static Pressure – Inches w.c.
CFM Range
@ 0.5 in. w.c.
Table A-8 Belt Drive Blower Motor Setup - 1/2 HP PSC Single Speed Motor
Heating Blower Set-Up Cooling Capacity
Furnace
Model
LRF65 100-10T 3-1/4" X 1/2" 3 T.O. LRF80 100-10T 3-1/4" X 1/2" 2 T.O. LRF90 100-10T 3-1/4" X 1/2" 1 T.O.
LRF100 100-10T 3-1/4" X 1/2" 0 T.O.
Blower
Motor Blower
0.20 in. w.c. 0.2 in. w.c.
Pulley
6" X 3/4" 4L370 2.5-3.0 960-1300
Table A-9 Belt Direct Drive Blower Characteristics - 1/2 HP PSC Single Speed Motor
Furnace
Model
LRF65 LRF80 1 1307 1190 1061 915 752
LRF90 2 1217 1076 927 744 544
LRF100 3 1110 960 793 536 248
Motor
FLA
7.9 55-85 °F 100-10T
∆T Blower
Motor
Pulley
Turns Out
0 1400 1300 1183 1052 904
External Static Pressure – Inches w.c.
0.1 0.2 0.3 0.4 0.5
Belt Tons CFM Range
CFM
TIP
Formulas will assist with design of duct-work and determination of air ow delivery.
CFM = Bonnet Output / (1.085 x System Temperature Rise (T) System Temperature Rise (T) = Bonnet Output / (1.085 x CFM)
16
240011511 REV. C [05/31/2017]
Page 17
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Table A-10 Direct Drive Blower Motor Setup - 1/2 HP ECM Variable Speed Constant CFM Motor
Dip Switch Adjustment Chart
For Input 0.55 USGPH TO 0.85 USGPH
SW1 - HEAT
DIP Switch
Position
1 2 USGPH 1 2 (TON)
OFF OFF A 0.65
ON OFF B 0.85
OFF ON C 0.75
ON ON D 0.55
SW3 - ADJUST
DIP Switch
Position
1 2
OFF OFF A 0% OFF OFF A 0.65
ON OFF B (+)15% ON OFF B 0.85
OFF ON C (-)15% OFF ON C 0.75
ON ON D N/A ON ON D 0.55
POS.
POS.
INPUT
CFM
1 2 USGPH
SW2 - COOL
DIP Switch
Position
OFF OFF A 3.5
ON OFF B 3.0
OFF ON C 2.5
ON ON D 2.0
SW4 - DELAY
DIP Switch
Position
POS.
POS.
AC Size
INPUT
NOTE:
SW1 (HEAT) AND SW4 (DELAY) DIP SWITCHES MUST BOTH BE ADJUSTED ACCORDING TO INPUT (FIRING RATE).
SW2 (COOL): 1 TON is approximately equal to 400 CFM
SW3 (ADJUST)
Increase OR decrease CFM respectively
Table A-11 Direct Drive Blower Characteristics - 1/2 HP ECM Variable Speed Constant CFM Motor
Furnace Model Blower Motor HP Motor FLA ∆T
LRFV 65 – 100
SW1 HEAT
DIP SWITCH POSITION
A (1=OFF, 2=OFF) 0.65 1016 1168 864
B (1=ON, 2=OFF)
C (1=OFF, 2=ON)
D (1=ON, 2=ON)
SW2 COOL
DIP SWITCH POSITION
A (1=OFF, 2=OFF) 3.5 700 805 595
B (1=ON, 2=OFF)
C (1=OFF, 2=ON)
D (1=ON, 2=ON)
100-10T DD 1/2 HP ECM 7.7 55-85 °F
OIL HEATING
INPUT
[USGPH]
0.85 1430 1600 1216
0.75 1229 1413 1045
0.55 828 952 704
AC SIZE
[TONS]
3.0 600 690 510
2.5 500 575 425
2.0 400 460 340
CFM WITH SW3-ADJ
DIP SWITCH POSITION A
CONTINUOUS FAN
CFM WITH SW3-ADJ
DIP SWITCH POSITION A
CFM WITH SW3-ADJ
DIP SWITCH POSITION B
CFM WITH SW3-ADJ
DIP SWITCH POSITION B
DIP SWITCH POSITION C
DIP SWITCH POSITION C
CFM WITH SW3-ADJ
CFM WITH SW3-ADJ
17
240011511 REV. C [05/31/2017]
Page 18
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Table A-11 Direct Drive Blower Characteristics - 1/2 HP ECM Variable Speed Constant CFM Motor - continued
COOLING OR HEAT PUMP HEATING
SW2 COOL
DIP SWITCH POSITION
A (1=OFF, 2=OFF) 3.5 1400 1600 1190
B (1=ON, 2=OFF)
C (1=OFF, 2=ON)
D (1=ON, 2=ON)
The CFM's shown are reduced by 20% if 24 VAC input is to Y1 (slow speed of 2 speed compressor) instead of Y/Y2
SW4 DELAY
DIP SWITCH POSITION
A (1=OFF, 2=OFF) 0.65 60 SECONDS - 0% 60 SECONDS - 63% 2 MINUTES - 75%
B (1=ON, 2=OFF)
C (1=OFF, 2=ON)
D (1=ON, 2=ON)
AC SIZE
[TONS]
3.0 1200 1380 1020
2.5 1000 1150 850
2.0 800 920 680
INPUT
[USGPH]
0.85 30 SECONDS - 0% 60 SECONDS - 63% 2 MINUTES - 88%
0.75 60 SECONDS - 0% 60 SECONDS - 88% 2 MINUTES - 82%
0.55 60 SECONDS - 0% 60 SECONDS - 50 % 2 MINUTES - 69%
CFM WITH SW3-ADJ
DIP SWITCH POSITION A
DELAY PROFILE FOR OIL HEATING
PRE RUN ON DELAY
TIME - CFM LEVEL
CFM WITH SW3-ADJ
DIP SWITCH POSITION B
SHORT RUN ON DELAY
TIME - CFM LEVEL
CFM WITH SW3-ADJ
DIP SWITCH POSITION C
OFF DELAY
TIME - CFM LEVEL
NO ADJUSTMENT
REQUIRED
N/A
DELAY PROFILE FOR COOLING OR HEAT PUMP HEATING
AC SIZE
[TONS]
ALL 7.5 MINUTES - 82% NONE NONE
PRE RUN ON DELAY
TIME - CFM LEVEL
SHORT RUN ON DELAY
TIME - CFM LEVEL
OFF DELAY
TIME - CFM LEVEL
18
240011511 REV. C [05/31/2017]
Page 19
APPENDIX B - WIRING DIAGRAMS
Chimney Vent Furnace Wiring Diagram LRF/LRFV
19
240011511 REV. C [05/31/2017]
Page 20
APPENDIX B - WIRING DIAGRAMS
Direct Vent Furnace Wiring Diagram LRF/LRFV
20
240011511 REV. C [05/31/2017]
Page 21
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-1: 1158-120 Electronic Fan Timer Board (EFT) Detailed Sequence Of Operation (LRF)
Mode Action System Response
EFT closes the oil primary control T - T connections.
Ignition system and the oil primary control start the furnace. Oil ows as long as the oil primary control senses ame.
Burner motor is energized and heat "fan on" delay timing begins. When timing is complete, the circulator fan is energized at heat speed. The oil primary control is de-energized, terminating the burner cycle.
Heat "fan off" delay timing begins. Length of delay depends on EFT dipswitch settings. When timing is complete, the circulator fan is de-energized.
EFT returns to standby mode, (Oil primary control and circulator fan are off, unless continuous fan operation is selected at the thermostat).
Oil primary control locks out within lockout timing, (15 seconds). Burner motor is de-energized. (Even though thermostat is still calling for heat). If circulator fan has started, it continues through the selected heat “fan off” delay period.
Burner motor is de-energized and oil primary control goes into recycle mode. If the selected heat “fan off” delay timing is longer than the recycle delay timing, the
circulator fan continues to run through the next trial for ignition.
Cooling contactor is energized immediately. Circulator fan is energized at cool speed.
Cooling contactor is de-energized immediately. Circulator fan turns off immediately.
HEAT
COOL
Thermostat calls for heat. ("W" terminal is energized).
Thermostat ends call for heat. ("W" terminal is de-energized).
Burner fails to light.
Established ame fails.
Thermostat begins call for cool. (G and Y terminals are energized).
Thermostat ends call for cool. (G and Y terminals are de­energized).
FAN
LIMIT
FAN
EAC
Thermostat begins call for fan. (G terminal is energized).
Thermostat ends call for fan. (G terminal is de-energized).
Limit switch string opens.
Limit switch string closes (with existing call for heat).
Limit switch string closes (without existing call for heat).
Continuous circulating fan is connected.
Electronic Air Cleaner is connected.
Circulator fan is energized immediately at cooling speed.
Circulator fan is de-energized immediately.
Oil primary control shuts off burner. Circulator fan is energized immediately at heat speed. EFT opens the oil primary control T - T connections. Circulating fan runs as long as limit
string stays open. If there is a call for cooling or fan, the circulating fan switches from heating to cooling
speed. EFT begins heat “fan off” delay sequence.
Circulating fan turns off after the selected heat “fan off” timing. EFT re-closes the oil primary control T - T connections. Oil primary control is energized, initiating burner light off.
Circulator fan turns off when heat “fan off” delay time is complete. Normal operation resumes; EFT control is in standby mode awaiting next thermostat
command.
Circulating fan is energized when there is no call for heat, cool, or fan. If fan operation is required by a call for heat, cool, or fan, the EFT switches off the
continuous fan speed tap before energizing the other fan speed.
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of the circulator fan is energized. EAC connections are not energized when the optional continuous fan terminal is energized.
21
240011511 REV. C [05/31/2017]
Page 22
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-2: 1168-1 ECM Tap Board Sequence of Operation (LRFV)
Thermostat Input LEDs (LED 1-5, LED 8)
Six green LEDs are placed behind their respective thermostat connections (Y1, Y/Y2, G, DH, O, W) and
illuminate whenever a call is present.
HLRF Humidity control is connected. Humidier connections are energized when the oil burner motor is energized.
Mode Action System Response
The 24 VAC input signal is passed to pin 2 of P1 and will drive the K1 relay that provides
HEAT Thermostat call for heat "W"
Thermostat calls for single stage cooling or second stage
COOL
FAN Thermostat calls for fan "G"
DEHUMID
REVERSING VALVE
of two stage cooling "Y/Y2"
Thermostat calls for rst stage
of two stage cooling "Y1" while "Y/Y2" is not calling
Thermostat calls for
Dehumidication "DH"
Thermostat calls for reversing valve "O"
dedicated contacts to the T-T input of the oil primary control. Blower runs on heating speed
prole.
The 24 VAC input signal is passed to pin 14 of P1. Blower runs on cooling speed prole.
The 24 VAC input signal is passed to pin 6 of P1. Blower runs at 80% of cooling speed
prole.
The 24 VAC input signal is passed to pin 15 of P1. Blower runs at continuous low speed
prole which is 50% of cooling speed.
The 24 VAC input signal is passed to pin 10 of P1. Blower runs according to "Y1" and "Y/Y2" calls as noted above.
The 24 VAC input signal is passed to pin 9 of P1. Blower runs according to "Y1" and "Y/Y2" calls as noted above.
22
240011511 REV. C [05/31/2017]
Page 23
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
C.1 Troubleshooting
!
WARNING
Electrical shock hazard. Only a trained, experienced service technician should perform troubleshooting procedure. Failure to do so could result in death or serious injury.
C.2 Preliminary Steps:
Consult Beckett or Riello instruction manuals provided with oil
burner for specic information regarding oil burner primary control
sequence of operation, diagnostics and troubleshooting.
Check diagnostic light for indications of burner condition.
NOTICE
When simulating call for heat at oil primary control, disconnect at least one thermostat lead wire from T - T terminals to prevent damage to thermostat. Neglecting this procedure may burn out heat anticipator of standard 24 vac thermostat, or cause harm to components within micro-electronic thermostat.
Before checking oil primary control, perform these preliminary checks, repair or replace controls as necessary:
• Check power supply, fuse box or breaker, any service switches, all wiring connections, and burner motor reset button (if equipped).
• Check limit switches to ensure switch contacts are closed.
• Check electrode gap and position.
• Check contacts between oil primary control and electrodes.
• Check oil supply (tank gauge).
Check oil nozzle, oil lter, and oil valves.
• Check piping or tubing to oil tank.
• Check oil pump pressure.
C.3 Check Oil Primary Control
If the trouble does not appear to be in the burner or ignition hardware, check the oil primary control per manufacturer's instructions included with oil burner.
23
240011511 REV. C [05/31/2017]
Page 24
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
!
WARNING
Electrical shock hazard. Only a trained, experienced service technician should perform troubleshooting procedure. Failure to do so could result in death or serious injury.
Table C-3 - System and General Troubleshooting
Problem Possible Cause Remedy
Furnace will not start.
Thermostat not calling for heat
No power to furnace
Thermostat faulty
Oil primary control faulty
Photo Cell wiring shorted or room light leaking into photo cell compartment
Open safety switch
No fuel oil
Check thermostat and adjust. Check thermostat for accuracy; if mercury switch type, it might be off level.
Check furnace switch, main electrical panel furnace fuse or circuit breaker. Look for any other hand operated switch, such as old poorly located furnace
switch, which was not removed during furnace replacement.
Remove thermostat wires from oil primary control terminals T-T. Place a jumper across T-T. If furnace starts, replace thermostat, thermostat sub-base (if equipped), or both.
Check reset button on oil primary control. Remove thermostat wires from oil primary control terminals T - T. Check for 24V across T -T. If no voltage is present, check for 115V to oil
primary control. If 115V is present, refer to oil primary control documentation provided with
oil burner.
Check photo cell (cad cell) wiring for short circuits. Check for room light leaking into cad cell compartment. Repair light leak if
necessary.
Check for open limit or auxiliary limit. Check internal wiring connections; loose connectors, etc.
Check fuel oil supply. Check all hand operated fuel oil valves are in open position. Fill oil storage
tank if necessary.
Clogged nozzle
Furnace will not start
without rst pushing oil
primary control reset
button.
(Happens on frequent
basis)
Clogged oil lter Replace oil tank lter or in-line lter if used.
Low oil pump pressure
Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective
Defective burner motor
Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Verify erratic pressure readings are not caused by defective fuel oil line. Check fuel oil lines.
Replace any compression ttings found with high quality ared ttings.
Check for signs of oil leaks. Any oil leak is potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load, determine why. Replace if
necessary.
24
240011511 REV. C [05/31/2017]
Page 25
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-3: System and General Troubleshooting continued
Problem Possible Cause Remedy
Furnace starts, but cuts out requiring manually resetting oil protector reset button.
Furnace starts, but cuts out requiring manually resetting oil protector reset button.
Photo Cell (Cad Cell) defective.
No fuel oil.
Clogged nozzle.
Clogged oil lter. Replace oil tank lter or in-line lter if used.
Low oil pump pressure.
Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.
Defective burner motor.
Water or contaminants in oil. Drain fuel oil storage tank; replace fuel oil. (Consult with fuel oil supplier).
If cad cell is dirty, clean it. Determine why cad cell is getting dirty. If cad cell is poorly aimed, realign it.
NOTE: Photocell should have resistance of 100 KΩ in absence of light; maximum of 1500 Ω in presence of light.
Verify room light is not leaking into the cad cell compartment. (See diagnostic light section). Check fuel oil supply.
Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Verify erratic pressure readings are not caused by defective fuel oil line.
Check fuel oil lines. Replace any compression ttings found with high quality ared ttings.
Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load, determine why. Replace if necessary.
Oil burner sputtering at nozzle
Excessive fuel oil consumption.
Frozen oil line.
Electrodes out of adjustment or defective.
Poor igniter connections or defective igniter.
Fuel oil lter clogged. Replace fuel oil storage tank lter and / or fuel oil in-line lter.
Defective oil pump.
Fuel oil line partially clogged or contains air.
System temperature rise too high.
Poor “fan off” delay timing selection, (fan stops too soon).
Fuel oil leak. Check fuel oil line for leaks. Repair or replace if necessary.
Gently warm oil line. Insulate oil line. (Outdoor piping size may require increased diameter).
Check electrode settings. Check electrodes for dirt build-up or cracks in porcelain.
Check contacts between the igniter and electrodes. If OK, replace the igniter
Check burner motor and / or fuel oil pump coupling. Check oil pump pressure. Replace fuel oil pump if necessary.
Bleed air from oil line. If problem persists, replace oil line.
System temperature rise should not exceed 75°F. Check for clogged air
lters. Check blower fan for excess dirt build-up or debris. Speed up
blower fan if necessary.
Check “fan off” delay timing setting. Use duct thermometer in supply air
plenum take-off or rst few inches of supply air trunk duct. Fan should
shut off at 90° - 100°F. Manipulate dip switch settings to come as close as possible to this “fan off” temperature.
Stack temperature too high.
Thermostat improperly adjusted or in poor location.
Check stack temperature. Stack temperatures will normally range from 400° to 500°F. Check draft regulator. Draft should be set to -0.02 in. w.c.
Check thermostat heat anticipator setting against measured amperage draw. Increase heat anticipator setting if necessary. If thermostat is being
inuenced by drafts, sunlight, duct work, etc., relocate to suitable location.
25
240011511 REV. C [05/31/2017]
Page 26
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-3: System and General Troubleshooting continued
Problem Possible Cause Remedy
Insufcient combustion air
adjustment at oil burner, or
Too much smoke.
Soot building up on blast tube (end coning).
improper draft pressure.
Heat exchanger partially clogged.
Poor alignment between oil
burner blast tube and re pot.
Flame impingement caused by Incorrect nozzle angle.
Defective re-pot Check re-pot. Repair or replace.
Airow blocked or dirty air lter. Clean or replace air lter.
Adjust oil burner combustion air band and draft regulator to gain highest
practical CO2 or lowest practical O2 content in ue gases.
See Burner Set Up.
Check for soot build-up in heat exchanger ue passages, especially in
outer radiator.
Check alignment. Blast tube should be centered with re pot burner opening. Oil burner head should be ¼ inch back from inside surface of re
pot.
Check nozzle size and angle. (See Appendix A).
Check distance from head to inside surface of re pot.
Furnace will not warm home to desired temperature.
Home does not heat evenly
Supply air temperature too hot.
Supply air temperature too cool.
Thermostat adjustments or location.
Insufcient airow.
Defective high limit control.
Under-sized nozzle.
Blower fan motor stopping intermittently on overload.
Burner motor stopping intermittently on overload.
Improper distribution of heat. This is not likely to be a furnace problem. Balance duct system.
Airow blocked or dirty air lter. Clean or replace air lter.
Insufcient airow.
Excess airow. Check system temperature rise. Slow down blower fan if necessary.
Excessive duct losses.
Check thermostat heat anticipator setting against measured amperage draw. Increase heat anticipator setting if necessary. If thermostat is being
inuenced by drafts, sunlight, duct work, etc., relocate to suitable location.
Check all dampers. Open closed dampers including registers in unused rooms.
Check system temperature rise. If temperature rise is too high, speed up blower fan. Test high limit function of all limit switches. Use duct thermometer to verify accuracy of limit control.
Check for obstructions to airow around limit switch bimetal elements.
Replace control if necessary.
Check nozzle. If problem is not caused by air ow problems, use larger
nozzle, if permitted by rating plate. Check blower fan motor amperage draw. Check motor ventilation ports, clean if necessary. Replace motor if
necessary.
Check burner motor. Replace if necessary.
Check all dampers. Open closed dampers including registers in unused rooms.
Check system temperature rise. If temperature rise is too high, speed up blower fan.
Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork if necessary.
Fan control "fan on" setting too
Supply air temperature
too cool during rst
moments of furnace cycle.
low.
Excessive duct losses.
Increase "fan on” dipswitch settings on EFT if control has this option.
Register air deectors may help.
Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork if necessary.
26
240011511 REV. C [05/31/2017]
Page 27
APPENDIX D - HOMEOWNER’S REFERENCE TABLE
Model No.
Serial No.
Date Installed
Contractor
Contact
Address
Postal Code
Telephone No.
After Hours No.
Fuel Supplier
Fuel Oil Supplier
Contact
Telephone No.
After Hours No.
27
240011511 REV. C [05/31/2017]
Page 28
PARTS LISTING
Parts Listing: Chimney Vent Models LRF/LRFV
Ref. No. Description Part No.
1 Left Side Panel 109009625AD 2 Right Side Panel 109009624AD 3 Base Panel Assembly 550003225 4 Rear Panel 109009626AD 5 Blower Door 109009809AD 6 Front Panel 109009786AD
Logo Bezel 28479
7
8 Handle (2 per unit) 28673
9 Top Panel 109008787AD 10 Blower Division Panel 3002357 11 Inner Front Panel 109009627 12 Cleanout Cover (Includes one item 19) 550003223 13 14 Right Side Bafe 109009709 15 Vertical Bafe (2 per unit) 109009711 16 Insulation Retainer (4 per unit) 26047 17 Heat Exchanger (Includes 18,19,20, 25) 550003224 18 Turbulators (18 per unit) 109009176 19 Cleanout Cover Gasket (2 per unit) 240010371 20 Burner Plate Gasket 240010370 21 Front Flue Pipe Assembly 3002314 22 Rear Flue Pipe Assembly 3002317 23 Flue Pipe Insulator Pipe 29713 24 Flue Pipe Flange 109009797 25 Flue Pipe Gasket (3 per unit) 240011382 26 Observation Port Sight Glass 240008235 27 Sight Glass Washer 109009449 28 Plug for Draft Measurement Port M10 x 16 Flange Bolt 240010827 29 Limit Disc 60T11 BOF 260°F 30153 30 Limit Disc Retainer 109009401 31 Control Box 30010
32
33
34 Transformer 120-24 VAC 40VA 240005330 35 Low Speed Fan Switch (Direct Drive PSC Models Only) 20693
36
Logo Label Olsen 28563 Logo Label Airco 28564
Left Side Bafe
Control Box Cover (Direct Drive PSC Models) 109009791 Control Box Cover (Direct Drive ECM and Belt Drive Models) 29654 Fan Timer Control 1158-120 UTEC (PSC and Belt Drive Models) 29388 Fan Timer Control 1168-1 UTEC (ECM Models) 240007048
Blower Assembly - Direct Drive PSC Motor (includes 39) 550003217 Blower Housing and Wheel 100-10T Direct Drive 240010315 Blower Motor 1/2 HP 4 Speed 102000131 Motor Mounting Band TR6884B 17811
Motor Mounting Arms 26251 Motor Run Capacitor 10 mfd @ 370 VAC 27743 Capacitor Strap Blower Base (2 per unit) 109005826 Grommet, Blower Feet (4 per unit) 26415
109009710
27761
28
240011511 REV. C [05/31/2017]
Page 29
PARTS LISTING
Parts Listing: Chimney Vent Models LRF/LRFV - CONTINUED
Ref. No. Description Part No.
Blower Assembly - Direct Drive ECM Motor (includes 39) 550003218
Blower Housing and Wheel 100-10T Direct Drive 240010315
37
38
39 Auxiliary Limit Disc 60T11 BOF 130°F 30388
40
41 Filter Side Rail (2 per unit) 27370 42 Filter Blower Division Rail 27369
* * * * * * * * * * * * * * * * * *
* = Not Shown
Blower Motor 1/2 HP ECM Programmed 102000186 Motor Mounting Band TR6884B 17811 Motor Mounting Arms 26251 Blower Base (2 per unit) 109005826 Grommet, Blower Feet (4 per unit) 26415 Blower Assembly - Belt Drive Motor (includes 39) 550003219 Blower Housing and Wheel 100-10T Belt Drive 240011512 Blower Motor 1/2 HP Single Speed 1725 RPM 102000154 Pulley Motor 3-1/4 x 1/2 MVL 2240001 Pulley Blower 6 x 3/4 2240006 Belt 4L370 2240016 Motor Support Bracket 109008679 Tensioner Support Bracket 109008680 Blower Base (2 per unit) 109005826 Grommet, Blower Feet (4 per unit) 26415
Oil Burner Assembly Beckett AFG70MPSS 0.50-45°W 550003220 Oil Burner Assembly Riello 40F3 0.55-80°B 550003221 Oil Burner Assembly Carlin EZ-LF 0.50-70°B 550003222
Air Filter 20 x 20 x 1 Permanent 2180032 Wire Harness Control Board Power 29751 Wire Harness Direct Drive PSC Blower 240011383 Wire Harness Control Board to Burner and Limits 240011384 Wire Harness Direct Drive ECM Blower Control Intermediate 240011385 Wire Harness Direct Drive ECM Blower Control Ends (2 per unit) 240011386 Wire Harness Direct Drive ECM Blower Power 240011387 Wire Harness Belt Drive Blower 240011389 Blocked Vent Safety Switch Kit Complete 30690 Blocked Vent Safety Switch - Replacement Switch Only 30660 Flue Pipe for Blocked Vent Safety Switch 30655 Draft Regulator 27494
0.60-60°W Oil Nozzle 240007739
0.65-60°W Oil Nozzle 240006431
0.50-90°B Oil Nozzle 240010815
0.65-80°B Oil Nozzle 1320011
0.75-80°B Oil Nozzle 1320008
0.65-70°B Oil Nozzle 14619022
29
240011511 REV. C [05/31/2017]
Page 30
PARTS LISTING
Parts Listing: Direct Vent Models LRF/LRFV
Ref. No. Description Part No.
All parts are same as listed for chimney vent models secept as listed below.
12 Cleanout Cover w/ Pressure Tap for Direct Vent (Includes one item 19) 550003409
Oil Burner Assembly, Beckett NX56LQ 0.50-60°W 550003406
40
* Pressure Switch for use with Riello Burners 0.42" WC (Blocked Vent Safety Switch) 240011861 * Pressure Switch for use with Beckett Burners 0.65" WC (Blocked Vent Safety Switch) 240011862 * 5" x 4" Appliance Adapter - Connects Furnace to Vent Pipe 240011898 * Combustion Air Intake Collar 4" for Beckett Burner 109005950 * Combustion Air Intake Collar 3" for Riello Burner 109006030 * Combustion Air Intake Elbow 3" for Riello Burner 240011899 * Combustion Air Intake Increaser 3" x 4" for Riello Burner 240011310 * 4" x 10' Vent Kit (Includes Vent Terminal Connector) 240006909 * 4" x 15' Vent Kit (Includes Vent Terminal Connector) 240006910 * 4" x 20' Vent Kit (Includes Vent Terminal Connector) 240006911 * 4" Vent Terminal Connector - Connects Vent Pipe to Vent Terminal 240006914 * Standard Vent Terminal 28972 * Riser Vent Terminal 29231 * Wire Harness Control Board to Burner and Limits and Pressure Switch 240011894
* = Not Shown
Oil Burner Assembly, Riello 40BF3 0.55-80°B (0.55/0.65 USGPH Firing Rates) 550003407 Oil Burner Assembly, Riello 40BF5 0.65-80°B (0.75/0.85 USGPH Firing Rates) 550003408
30
240011511 REV. C [05/31/2017]
Page 31
Model LRF/LRFV Diagram
PARTS LISTING
1
25
4
41
24
13
25
21
9
15
16
29
7
19
12
30
18
20
25
10
17
3
22
32
35
23
33
31
34
14
42
39
38
15
37
36
8
5
41
2
16
8
6
40
27
26
28
11
19
31
31
16
240011511 REV. C [05/31/2017]
Page 32
ECR International
2210 Dwyer Avenue, Utica NY 13501
Loading...