Olsen HTL-140D, HTL-100D, HTL-120D, HTL-130D, HTLV-90DNX Installation, Operation & Maintenance Manual

...
HTL-D (Up-Flow Model)
R
HTLV-D (Up-Flow Model with ECM)
Oil Fired Warm Air Furnaces
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
An ISO 9001-2000 Certified Company
ECR International
2201 Dwyer Avenue
www.ecrinternational.com
P/N# 240007799, Rev. C [12/2009]
HTLD & HTLDV OIL FIRED WARM AIR FURNACE
IMPORTANT: THIS MANUAL MUST BE KEPT NEAR THE FURNACE FOR FUTURE REFERENCE!!
ALL INSTALLATIONS MUST MEET ALL LOCAL, PROVINCIAL/STATE, AND FEDERAL
CODES WHICH MAY DIFFER FROM THIS MANUAL
Read this complete manual before beginning installation.
These instructions must be kept with the furnace for future
reference.
2
TITLE OF DOCUMENT
Installation Requirements .....................................................................................................................................4
Location Of The Unit ...............................................................................................................................................5
Controls & Connections ........................................................................................................................................6
Oil Burners ...............................................................................................................................................................7
Combustion Chamber ............................................................................................................................................8
Circulating Air Blower ............................................................................................................................................8
Maintenance And Service ......................................................................................................................................9
Operating Instructions (HTL-D) .............................................................................................................................9
Operating Instructions (HTLV-D) ........................................................................................................................ 10
ECM Blower Motor Operation (HTLV-D) ............................................................................................................. 10
Oil Burner Set-Ups ............................................................................................................................................... 11
Oil Burner Air Adjustment ................................................................................................................................... 12
Burner Electrodes ................................................................................................................................................ 12
Start Up ................................................................................................................................................................. 13
Special Instructions For Units Equipped With Riello Burners ........................................................................... 13
Direct Drive Blower PSC Motor ........................................................................................................................... 14
HTL-D & HTLV-D Dimensions .............................................................................................................................. 15
ECM Blower (HTLV-D) .......................................................................................................................................... 16
Wiring Diagrams .................................................................................................................................................. 18
Oil Burner Operation ........................................................................................................................................... 19
Oil Primary Control - Sequence Of Operation .................................................................................................... 20
Oil Primary Control -Troubleshooting ................................................................................................................ 25
Homeowner's Reference Table ........................................................................................................................... 31
Parts Listing: Highboy Model: HTL-D And HTLV-D ............................................................................................ 32
WARNINGS AND SAFETY SYMBOLS
DANGER
Indicates an imminently hazardous situation which, if not
!
avoided, WILL result in death, serious injury or substantial property damage.
!
Indicates an imminently hazardous situation which, if not avoided, may result in injury or property damage.
CAUTION
WARNING
Indicates an imminently hazardous situation which, if not
!
avoided, may result in death, serious injury or substantial property damage.
NOTICE
Indicates information which should be followed to ensure proper installation and operation.
3
INSTALLATION REQUIREMENTS
Introduction
Please read these instructions completely and carefully before install­ing and operating the furnace.
MODELS HTL-D AND HTLV-D Models HTL-D and HTLV-D are oil red forced air up-ow furnaces
with an output capacity range of 89,000 BTU/Hr. to 140,000 BTU/ Hr.
CAUTION
DO NOT USE GASOLINE, CRANK CASE OIL, OR ANY OIL CONTAINING GASOLINE.
!
FOR YOUR SAFETY: DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE VICIN­ITY OF THIS OR ANY OTHER APPLIANCE.
All models are CSA listed, (NRTL/C) for use with No. 1 (Stove) and No. 2 (Furnace) Oil. Please refer to the tables on page 11 (Oil Burner Setups) of this manual for performance and dimensional data.
In Canada, the installation of the furnace and related equipment shall be installed in accordance with the regulations of CAN/CSA
- B139, Installation Code for Oil-Burning Equipment, as well as in accordance with local codes.
In the United States of America, the installation of the furnace and related equipment shall be installed in accordance with the regula­tions of NFPA No. 31, Standard for the Installation of Oil-Burning Equipment, as well as in accordance with local codes.
Regulations prescribed in the National Codes and Local regulations take precedence over the general instructions provided in this instal­lation manual. When in doubt, please consult your local authorities.
All models are shipped assembled and pre-wired. e furnace should be carefully inspected for damage when being unpacked.
Location of Unit
e furnace should be located such that the ue connection to the chimney is short, direct and consists of as few elbows as possible. When possible, the unit should be centralized with respect to the supply and return air ductwork. A central location minimizes the trunk duct sizing. All models may be installed on combustible oors.
e minimum installation clearances are listed in
Table 1
.
Table 1 - Clearances
Clearance to Combustibles
Location
HTL-D and HTLV-D
Up ow
To p 1"
Bottom 0* Combustible Floor
S /A Plenum 1"
Rear 1"
Sides 1"
Front 1" **
Flue Pipe 9"
Enclosure Closet
* No carpet or vinyl ** 24 in. Required for service clearance
Figure 1 - Heat Exchanger Support Screws
Heat Loss
e maximum hourly heat loss for each heated space shall be calcu­lated in accordance with the procedures described in the manuals of the Heating, Refrigeration and Air Conditioning Institute of Canada (HRAI), or by other means prescribed, or approved by the local authority having jurisdiction.
In the United States, Manual J. titled, "Load Calculation" published by the Air Conditioning Contractors of America, describes a suitable procedure for calculating the maximum hourly heat loss.
HEAT EXCHANGER SUPPORT SCREWS
Before nal placement of the furnace, the heat exchanger support screws should be removed (See
Figure 1
). is may be preferable if the furnace rear panel will be inaccessible aer installation. e screws must be removed if the heat exchanger needs to be removed from the cabinet.
4
LOCATION OF THE UNIT
Air Conditioning Applications
If the furnace is used in conjunction with air conditioning, the fur­nace shall be installed in parallel with or upstream from the evapora­tor coil to avoid condensation in the heat exchanger. In a parallel in­stallation, the dampers or air controlling means must prevent chilled air from entering the furnace. If the dampers are manually operated, there must be a means of control to prevent the operation of either system unless the dampers are in the full heat or full cool position. e air heated by the furnace shall not pass through a refrigeration unit unless the unit is specically approved for such service.
e blower speed must be checked and adjusted to compensate for the pressure drop caused by the evaporator coil. Refer to page 18 of this manual, for recommended wiring and electrical connections of the air conditioning controls.
Combustion Air
If the furnace is installed in a closet or utility room, two openings must be provided connecting to a well-ventilated space (full base­ment, living room or other room opening thereto, but not a bed­room or bathroom). One opening shall be located above the level of the upper vent opening and one opening below the combustion air inlet opening in the front of the furnace. Each opening shall have a minimum free area of 1½ square inches per 1,000 Btu/h of total input rating of all appliances installed in the room.
For furnaces located in buildings of unusually tight construction, such as those with high quality weather stripping, caulking, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communicating with a well ventilated attic or with the outdoors shall be provided, using a duct if necessary. e duct opening shall have a free area of 1½ square inches per 1,000 Btu/h of total input rating of all appliances to be installed. When a furnace is installed in a full basement, inltration is normally adequate to provide air for combustion and dra opera­tion. Furnace rooms under 65m³ (2295  treated as conned space.
3
) should automatically be
NOTICE
THE FURNACE IS APPROVED FOR USE WITH TYPE L VENT OR EQUIVALENT.
CAUTION
CHIMNEY VENTED VERSIONS OF THE FURNACE
!
MUST BE CONNECTED TO A FLUE HAVING SUFFI­CIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF THE APPLIANCE.
NOTICE
THE RECOMMENDED FLUE DRAFT PRESSURE IS
-0.02 IN. W.C. (See
e ue pipe must not pass through any oor or ceiling, but may pass through a wall where suitable re protection provisions have been installed. Refer to the latest edition of CAN/CSA B-139 for rules governing the installation of oil burning equipment. In the United States, refer to the latest edition of NFPA 31 for regulations governing the installation of oil burning equipment.
See Page 11, (Oil Burner Setups) of this manual for burner set-up.
Figure 2
)
Figure 2 - Checking Over-Fire Draft
Chimney Venting
e ue pipe should be as short as possible with horizontal pipes sloping upward toward the chimney at a rate of one-quarter inch to the foot. e ue pipe should not be smaller in cross sectional area than the ue collar on the furnace. e ue pipe should connect to the chimney such that the ue pipe extends into, and terminates ush with the inside surface of the chimney liner. Seal the joint between the pipe and the lining. e chimney outlet should be at least two feet above the highest point of a peaked roof. All unused chimney openings should be closed. Chimneys must conform to local, provincial or state codes, or in the absence of local regulations, to the requirements of the National Building Code.
Over-re dra access port
5
CONTROLS & CONNECTIONS
Barometric Damper Control
e barometric damper control, also known as a dra regulator, is used on conventional chimney venting only. is control auto­matically maintains a constant negative pressure in the furnace to obtain maximum eciency. It ensures that proper pressures are not exceeded. If the chimney does not develop sucient dra, the dra control cannot function properly. e dra regulator, when installed should be in the same room or enclosure as the furnace and should not interfere with the combustion air supplied to the burner. e control should also be located near the furnace ue outlet and installed according to the instructions supplied with the regulator. e ue outlet pressure (measured between the furnace and dra regulator, or the oil burner mounting plate over-red dra access port ,
Figure 2
) should be set to -0.02 in. w.c.
Fan Timer Board and Limit Control (FIG. 4) (page 21)
e Electronic Fan Timer integrates control of all burner and circu­lator fan operations. is control is the central wiring point for most of the electrical components in the furnace. e United Technolo­gies 1158-120 (HTL-D) has an adjustable fan on time that is set by selecting the dipswitch combination displayed in
Table 2
. is fan on delay can be set at 30, 60 90 or 120 seconds. is provides a delay between the burner ignition and blower start-up to eliminate excessive ow of cold air when the blower comes on. e United Technologies 1158-120 (HTL-D) has an adjustable fan o time of 1, 2, 4 or 6 minutes displayed in
Table 2
. e fan o delay time starts when the burner motor is de-energized at the end of a call for heat. Blower shutdown is delayed to remove any residual heat from the heat exchanger and improve the annual eciency of the furnace.
e electronic fan timer board works in conjunction with snap disc limit controls, which perform a safety function, and breaks power to the oil burner primary control, which shuts o the burner if the furnace over-heats. e limit control is thermally operated and automatically resets. e limit control is factory installed, pre-set and is not adjustable.
If the limit control opens with the United Technologies 1158-120 (HTL-D) electronic fan control, the circulating fan will be energized as well. When the limit closes, the fan o timer will begin. At the end of the fan o time cycle the burner will be energized, initiating a normal burner cycle.
Fan Timer Board and Limit Control (Fig. 5) (Page 21)
e United Technologies 1168-1 ECM (HTLV-D) tap board has an adjustable fan on/o delay that must be adjusted in accordance with the furnace input rating (nozzle size).
(pg 16 and 17)
for ECM blower set-up.
Refer to Tables 8A and 8B
Table 2 - United Technologies 1158-120 (HTL-D)
Dip Switch Position Blower Delay Times
1 2 3 4
O O 30
On O 60
O On 90
On On 120
O O 1
On O 2
O On 4
On On 6
ON
Seconds
OFF
Minutes
Electrical Connections
e furnace is listed by the Canadian Standards Association un­der the NRTL (North American) Standard. It is factory wired and requires minimal eld wiring. All eld wiring should conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail. In the United States, the wiring must be in accordance with the National Fire Protection Association NFPA-70, National Electrical Code, and with local codes and regulations.
e furnace should be wired to a separate and dedicated circuit in the main electrical panel; however, accessory equipment such as electronic air cleaners and humidiers may be included on the fur­nace circuit. Although a suitably located circuit breaker can be used as a service switch, a separate service switch is advisable. e service switch is necessary if reaching the circuit breaker involves becoming close to the furnace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room. e furnace switch (service switch) should be clearly marked, installed in an eas­ily accessible area between the furnace and furnace room entry, and be located in such a manner to reduce the likelihood that it would be mistaken as a light switch or similar device.
e power requirement for the HTL-D and HTLV-D models is: 120 VAC, 1 Ø, 60 Hz., 12A.
Accessories requiring 120 VAC power sources such as electronic air cleaners and humidier transformers may be powered from the electronic fan timer board where provisions have been made for con­nections, but should have their own controls. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the auto-generating windings of the direct drive motor.
ermostat wiring connections and air conditioning contactor low voltage connections are shown in the wiring diagrams on page 18 of this manual. Some micro-electronic thermostats require additional controls and wiring. Refer to the thermostat manufacturer's instruc­tions.
6
OIL BURNERS
e thermostat should be located approximately 5 feet above the oor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room tempera­tures. Avoid locations where the thermostat will be exposed to cold dras, heat from nearby lamps and appliances, exposure to sunlight, heat from inside wall stacks, etc.
e thermostat heat anticipator should be adjusted to the amper­age draw of the heating control circuit as measured at the "R" and "W" terminals of the thermostat. To reduce the risk of damaging the heat anticipator, do not measure this current with the thermostat connected to the circuit. Measure the amperage by connecting an ammeter between the two wires that will connect to the thermostat "R" and "W" terminals.
Humidier
A humidier is an optional accessory available through most heating supply outlets. Installation should be carried out in accordance with the humidier manufacturer's installation instructions. Water or water droplets from the humidier should not be allowed to come into contact with the furnace heat exchanger. Do not use direct drive motor connections as a source of power for 120 VAC humidiers and humidier transformers.
Piping Installation
e entire fuel system should be installed in accordance with the requirement of CAN/CSA B-139, and local regulations. Use only ap­proved fuel oil tanks, piping, ttings and oil lter.
In the United States the installation must be in accordance with NFPA No. 31 and local codes and authorities.
Install the oil lter as close to the burner as possible. For further details of the oil supply tank and piping requirements, please refer to the instructions and illustrations in the oil burner and oil pump instructions shipped with the furnace.
Oil Burner Adjustment
e burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions. A lack of air causes "so" and "sooty" ames, resulting in soot build-up throughout the heat exchanger passages. Excess combustion air causes a bright roaring re and high stack temperatures resulting in poor fuel eciency. e HTL-D and HTLV-D furnaces operate most eciently with a No. 1 smoke spot on the Bacharach Scale. is is not necessarily the opti­mum setting; however, because dust will inevitably build up on the air moving components of the oil burner assembly. is will result in decreased air supply with the potential result of soot building up in the ue gas passageways of the heat exchanger. Soot behaves as an insulator and impairs good heat transfer. Stack temperature will in­crease, and the overall eciency will decrease. As a means of avoid­ing this problem, it is advisable to adjust the air supply to provide no more than a trace smoke spot on the Bacharach Scale.
CAUTION
BEFORE OPERATING THE FURNACE CHECK BURN­ER ALIGNMENT WITH COMBUSTION CHAMBER.
!
THE END CONE OF THE AIR TUBE MUST BE CEN­TRED TO THE ACCOMMODATING RING PROVIDED IN THE DESIGN OF THE COMBUSTION CHAMBER. ADJUST AS NECESSARY.
Burner Electrodes
Correct positioning of the electrode tips with respect to each other, to the fuel oil nozzle, and to the rest of the burner is essential for smooth light ups and proper operation. Refer to the oil burner in­structions shipped with the furnace for electrode specications.
NOTICE
Oil Filter
All fuel systems should include an oil lter between the fuel oil stor­age tank and the oil burner. When using an oil burner nozzle smaller than 0.65 U.S. Gallons Per Hour, install an additional 7 to 10 micron lter as close as possible to the oil burner.
Oil Burner Nozzles
e HTL-D and HTLV-D are certied for multiple ring rates, rang­ing from 89,000 to 140,000 Btu/h. By manipulating the oil burner nozzle, ame retention head, static plate and temperature rise; the furnace may be red at an ideal rate for a wide range of structures.
Refer to Tables 3A, B and C,
to determine the proper combinations.
page 11 and the furnace rating plate
Beckett AF Series Burner electrode specications have been revised. ey should be adjusted to be 5/16” above the nozzle centerline.
Burner Primary (Safety) Control
e furnace is equipped with a primary combustion control, some­times referred to as the burner relay or burner protector relay, which uses a light sensing device (cad cell) located in the burner housing, to monitor and control combustion. Over time, dust or combus­tion residuals can build up on the lens of the cad cell impairing its response to the ame. e cad cell should be checked for cleanliness and proper alignment if the primary control frequently shuts down combustion.
7
COMBUSTION CHAMBER
CAUTION
ALL FURNACE CONTROLS ARE SENSITIVE AND
!
SHOULD NOT BE SUBJECTED TO TAMPERING. IF PROBLEMS PERSIST, CALL YOUR SERVICE CON­TRACTOR.
Combustion Chamber
is furnace is equipped with a high quality cerafelt combustion chamber. It is held in place by a retaining bracket.
NOTICE
Check the alignment of the combustion chamber and oil burner before ring. It is possible for the combustion chamber to shi if subjected to rough handling during transit.
CIRCULATING AIR BLOWER
Circulating Air Blower (HTL-D)
e HTL-D and HTLV-D furnace models are equipped with direct drive blower systems. HTL-D models are equipped with PSC mo­tors; HTLV-D models are equipped with electronically commutated motors (ECM). Direct drive blower speed adjustments are not normally required in properly sized extended plenum duct systems. e motor RPM and air CFM delivery will vary automatically (on ECM motor equipped models) to accommodate conditions within the usual range of external static pressures typical of residential duct systems. Under-sized duct systems may require a higher blower speed to obtain a reasonable system temperature rise. Some older duct systems were not designed to provide static pressure. ey typically feature special reducing ttings at each branch run and lack block ends on the trunk ducts. ese systems may require modica­tion to provide some resistance to the airow to prevent over amping of the direct drive blower motor. Selecting a lower blower speed may correct this problem. Direct drive blower speeds are adjusted by changing the "hot" wires to the motor winding connections. Please refer to wiring diagrams on page 18 of this manual or the wiring dia­gram label axed to the furnace. THE NEUTRAL WIRE (normally the white wire) IS NEVER MOVED TO ADJUST THE BLOWER SPEED.
It is possible and acceptable to use a single blower speed for both heating and cooling modes. e simplest method to connect the wiring from both modes is to use a "piggy-back connector" accom­modating both wires on a single motor tap. It is also acceptable to connect the selected motor speed with a pigtail joined to both heat­ing and cooling speed wires with a wire nut. As a safety precaution against accidental disconnection of the wires by vibration, it is advis­able to secure the wire nut and wires with a few wraps of electricians tape.
e combustion chamber should be inspected for damage or carbon build up whenever the oil burner is removed for repairs or routine maintenance.
CAUTION
!
DO NOT START THE BURNER UNLESS THE BLOWER ACCESS DOOR IS SECURED IN PLACE.
CAUTION
DO NOT CONNECT POWER LEADS BETWEEN MO-
!
TOR SPEEDS. THE NEUTRAL WIRE MUST ALWAYS BE CONNECTED TO THE MOTOR'S DESIGNATED NEUTRAL TERMINAL.
If the joining of the blower speed wiring is done in the furnace junc­tion box, tape o both ends of the unused wire.
Do not use the blower speed wires as a source of power to acces­sories as electronic air cleaners and humidier transformers. e unused motor taps auto-generate suciently high voltages to dam­age accessory equipment.
WARNING
DISCONNECT THE POWER SUPPLY TO THE FUR­NACE BEFORE OPENING THE BLOWER ACCESS
!
DOOR TO SERVICE THE AIR FILTER, FAN AND MOTOR. FAILURE TO SHUT OFF POWER COULD ALLOW THE BLOWER TO START UNEXPECTEDLY, CREATING A RISK OF DEATH OR PERSONAL INJURY.
Circulating Air Blower (HTLV-D) - (See Page 10, ECM BLOWER MOTOR OPERATION HTLVD)
8
MAINTENANCE AND SERVICE
Routine Maintenance By Home Owner
Other than remembering to arrange for the annual professional servicing of the furnace by the service or installation contractor, the most important routine service performed by the homeowner is to maintain the air lter or lters. A dirty lter can cause the furnace to over-heat, fail to maintain indoor temperature during cold weather, increase fuel consumption and cause component failure.
e furnace lter(s) should be inspected, cleaned or replaced month­ly. e furnace is factory equipped with a semi-permanent type lter. If the lter is damaged, replace with lters of the same size and type. (See Parts Listing Ref. No. 21).
During the routine service, inspect the general condition of the fur­nace watching for signs of oil leaks in the vicinity of the oil burner, soot forming on any external part of the furnace, soot forming around the joints in the vent pipe, etc. If any of these conditions are present, please advise your service or installation contractor.
Annual Service By Contractor
CAUTION
THE COMBUSTION CHAMBER (FIREPOT) IS FRAG-
!
ILE. USE CARE WHEN INSPECTING AND CLEANING THIS AREA.
e heat exchanger should be inspected periodically and cleaned if necessary. If cleaning is necessary, SHUT OFF POWER TO THE
FURNACE and remove the burner. Using a sti brush with a wire handle, brush o scale and soot from inside the drum and ue pipe. To clean the radiator, remove the clean-out caps screws, and remove the caps carefully to avoid tearing the gaskets. A wire brush can be used to loosen dirt and debris on the inside surfaces of the radiator. Clean out all accumulated dirt, soot and debris with a wire handled brush and an industrial vacuum cleaner. Before replacing the clean­out caps, inspect the gaskets. If the gaskets are broken, remove the remnants and replace with new gaskets.
e blower motor is factory oiled and permanently sealed. DO NOT LUBRICATE. Excess oil causes premature electric motor failure.
Inspect the blower fan. Clean if necessary. Oil Burner Maintenance: Follow the instructions of the oil burner
manufacturer. (See oil burner manufacturer's instructions supplied with furnace or burner). It is advisable to change the oil burner nozzle and oil lter on an annual basis.
e venting system should be cleaned and inspected for signs of deterioration. Replace pitted or perforated vent pipe and ttings. e barometric damper should open and close freely.
All electrical connections should be checked to ensure tight con­nections. Safety controls such as the high limit controls should be tested for functionality. e fan control should be checked to ensure that the fan on and o delay function continues to start and stop the blower fan at the optimal settings.
OPERATING INSTRUCTIONS HTLD
Before Lighting
Open all supply and return air registers and grilles. Open all valves in oil pipes. Turn on electric power supply.
To Light Unit
Set the thermostat above room temperature to call for heat. e burner should start. NOTE: It may be necessary to press the RESET button on the primary combustion control relay.
ere will be a fan on time delay before the circulating fan is ener­gized. e United Technologies 1158-120 has an adjustable fan on time that is set by selecting the dipswitch combination displayed in Table 2 on page 6. seconds. Set the thermostat below room temperature. e oil burner should stop.
e air circulation blower will continue to run until the time o setting selected on the electronic fan timer control times out. e United Technologies 1158-120 has an adjustable fan o time of 1, 2, 4,or 6 minutes.
e necessary adjustments to the fan control settings should be determined by measuring the temperature of the air in the supply air take-o, or within the rst few inches of the supply air trunk. e
is fan on delay can be set at 30, 60, 90 or 120
side mid point of the transition is usually ideal, providing that the thermometer probe is beyond the "line of sight" wherein false read­ings from radiant heat could be observed. System temperature rise is the dierence in temperature between the supply air and return air.
To check the operation of the limit switch, shut o power to the furnace. Temporarily remove the neutral wire from the direct drive blower motor. Restore the electrical power to the furnace and set the thermostat above room temperature.
Aer three or four minutes of burner operation, the limit control should turn the burner o. When the limit function test is complete, shut o electrical power to the furnace, replace the neutral wire to the blower fan motor, and then restore power. e blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan o time is achieved. e oil burner will then resume operation and continue until the thermostat is satised. Restore the thermostat setting to a comfortable temperature.
To Shut Down Unit
Set the thermostat to the lowest possible setting. Set the manual switch (if installed) in the Electrical Power Supply
Line to "OFF".
9
OPERATING INSTRUCTIONS HTLVD
Before Lighting
Open all supply and return air registers and grilles. Open all valves in oil pipes. Turn on electric power supply
To Light Unit
Set the thermostat above room temperature to call for heat. e burner should start. NOTE: It may be necessary to press the RESET button on the primary combustion control relay.
ere will be a fan on time delay before the circulating fan is ener­gized. e United Technologies 1168-1 has an adjustable fan on/ o time delay that is programmed into the ECM motor, and is set by selecting the SW4 DIP switch combination displayed in
and B
pages 16 and 17. Fan on/o delay must be adjusted according
to input (nozzle size).
1.
Set the thermostat below room temperature. e oil burner should stop.
2.
e air circulation blower will continue to run until the blower o delay setting programmed into the ECM motor times out.
3.
To check the operation of the limit switch, shut o power to the furnace. Temporarily remove the 5 pin power connector plug from the ECM blower motor.
NOTICE
Tables 8 A
4.
Aer three or four minutes of burner operation, the limit control should turn the burner o. When the limit function test is complete, shut o electrical power to the furnace, replace the 5 pin power plug to the blower fan motor, and then restore power. e blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan o time is achieved. e oil burner will then resume operation and continue until the thermostat is satised. Restore the thermostat setting to a comfortable temperature.
NOTICE
IF THE FURNACE IS TO BE SHUT DOWN FOR AN EXTENDED PERIOD OF TIME, CLOSE THE OIL SUP­PLY VALVE TO THE BURNER.
CAUTION
DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED, WHEN THE
!
FURNACE IS FULL OF VAPOR, OR WHEN THE COM­BUSTION CHAMBER IS VERY HOT. NEVER BURN GARBAGE OR PAPER IN THE FURNACE, AND NEVER LEAVE PAPER OR RAGS AROUND THE UNIT.
Isolate the AC Line pins on the 5 pin power connec­tor with electrical tape to prevent electric shock hazard. Restore the electrical power to the furnace and set the thermostat above room temperature.
ECM BLOWER MOTOR OPERATION HTLVD
Setting Blower “ON” and “OFF” Timings
Blower on/o time delays are handled by ECM motor programming. Features of this ECM variable speed motor are that it will deliver a constant airow within a wide range of external static pressures, and also includes:
Soft Start
the required operating speed. is feature in the heating cycle allows the heat exchanger to reach operating temperature before the blower motor starts, which minimizes noise and increases comfort.
Soft Stop
motor will slowly ramp down. is feature allows for increased energy eciency and reduced noise levels.
: is ECM variable speed motor will slowly ramp up to
: At the end of the heating cycle, the ECM variable speed
Dehumidication
grammed into the variable speed motor. At the start of each cooling cycle, the variable speed motor will run at 82% of the rated airow for 7.5 minutes. Aer 7.5 minutes has elapsed, the motor will increase to 100% of the rated airow. is prole is used to provide dehumidication and improve system eciency.
Continuous Fan Operation:
fan (G) switch is on without a call for heating or cooling, the indoor fan is immediately energized up to 50% of the cooling speed. is feature allows continuous circulation of air between calls for heating or cooling.
If a call for heat (W) or cool (Y) occurs during continuous fan, the blower will remain energized.
: A dehumidication feature has been pro-
When the thermostat continuous
10
OIL BURNER SETUPS
HTL-D and HTLV-D furnaces may be used with the following oil burners.
Please note: e Beckett AF, NX and Riello 40F oil burners are for applications using indoor air for combustion only.
Table 3A - Beckett AF Oil Burner Set-Up
Beckett AF Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
Output
BTU/Hr
Burner
Model
Nozzle
Pump
Pressure
Flow Rate Head 1
HTL-90D 89,200 AF76XN 0.75 / 60°W 100 PSIG 0.75 USGPH F3 2- ¾ in. HTL-100D 101,100 AF76XN 0.85 / 60°W 100 PSIG 0.85 USGPH F3 2- ¾ in. HTL-120D 117,600 AF76XN 1.00 / 60°W 100 PSIG 1.00 USGPH F3 2- ¾ in. HTL-130D 129,300 AF76YB 1.10 / 60°W 100 PSIG 1.10 USGPH F6 2- ¾ in. HTL-140D 139,400 AF76YB 1.20 / 60°W 100 PSIG 1.20 USGPH F6 2- ¾ in.
Table 3B - Beckett NX Oil Burner Set-Up
Beckett NX Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
Output
BTU/Hr
Burner
Model
Nozzle Pump
Pressure
Flow Rate
HTLV-90DNX 93,000 NX70LHHS 0.65 x 60°W 120 PSIG 0.75 USGPH HTLV-100DNX 101,100 NX70LHHS 0.75 x 60°W 125 PSIG 0.85 USGPH HTLV-120DNX 117,600 NX70LHHS 0.90 x 60°W 125 PSIG 1.00 USGPH HTLV-130DNX 129,300 NX70LB 1.00 x 60°W 120 PSIG 1.10 USGPH HTLV-140DNX 139,400 NX70LB 1.10 x 60°W 120 PSIG 1.20 USGPH
Static
Plate
Furnace
Model
Output
BTU/Hr
HTL-90DRF
90,300 40F3 0.65 / 60°W 120 PSIG 0.75 USGPH
HTLV-90DRF HTL-100DRF
101,100 40F3 0.75 / 60°W 125 PSIG 0.85 USGPH
HTLV-100DRF
HTL-115DRF
114,600 40F3 0.85 / 60°W 115 PSIG 0.95 USGPH
HTLV-115DRF
Table 3C - Riello 40F Series Oil Burner Set-Up
Riello 40F Series Oil Burners
(For use with chimney vented units only)
Burner
Nozzle Pump
Model
11
Flow Rate
Pressure
OIL BURNER AIR ADJUSTMENT
e burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions. A lack of air causes "so" and "sooty" ames, resulting in soot build-up throughout the heat exchanger passages. Excess combustion air causes a bright roaring re and high stack temperatures resulting in poor fuel eciency. e HTL-D and HTLV-D furnaces operate most eciently with a No. 1 smoke spot on the Bacharach Scale. is is not necessarily the opti­mum setting; however, because dust will inevitably build up on the air moving components of the oil burner assembly. is will result in decreased air supply with the potential result of soot building up in the ue gas passageways of the heat exchanger. Soot behaves as an insulator and impairs good heat transfer. Stack temperature will in­crease, and the overall eciency will decrease. As a means of avoid­ing this problem, it is advisable to adjust the air supply to provide no more than a trace smoke spot on the Bacharach Scale.
For complete details, consult the oil burner instruction manual pro­vided in the furnace documents envelope.
Beckett AF Burner
Adjust the air shutter by loosening the locking screws and moving the air shutter, and if necessary, the bulk air band.
Beckett NX Burner
Adjust the burner Head/Air supply by rst loosening the spline screw. Turn the adjustment screw clockwise to decrease the com­bustion air and counter-clockwise to increase the combustion air. Re-tighten the spline screw aer obtaining the proper setting. (Refer to Beckett NX Oil Burner manual).
Riello 40 Series (Chimney Vented)
Riello burners are factory set with respect to nozzle size; pump pres­sure, air gate and turbulator adjustments for each model and ring rate. By removing the burner cover and loosening the screws that secure the air adjustment plate, the combustion air can be adjusted. Move the adjusting plate to either increase or decrease combustion air. When the proper air setting is achieved, retighten the xing screws.
Adjustment of the electrode tips with respect to each other, the nozzle, and to the rest of the burner is very important to ensure smooth start-ups and to permit ecient combustion.
Beckett AF Burner
Electrode gap: 5/32 inch. Distance above horizontal centerline: 5/16 inch. Older instruction
sheets specify 7/16 inch. e current specication is 5/16 inch. Distance ahead of nozzle: 1/16 inch. “Z” dimension, the distance from the front of the end cone (head)
to the face of the nozzle should be 1-1/8 inches. If a ceramic head is used, the distance from the end cone to the nozzle face is increased to 1-3/8 inches.
BURNER ELECTRODES
Beckett NX Burner
Electrode gap: 5/32 inch. Distance above nozzle centre line: 1/4 inch. Nozzle-to-electrode tip Spacing: 3/32 inch.
Riello 40F
Electrode gap: 5/32 inch. Distance above horizontal centerline: 13/64 inch. Distance ahead of nozzle: 5/64 to 7/64 inch.
12
START UP
e furnace should be operated for a minimum of 10 minutes to reach steady state conditions before ne tuning combustion. e warm up time is ideal for testing the oil pump pressure.
Drill a 1/4-inch test port in the venting between the furnace ue outlet and dra regulator (barometric damper). Insert a stack ther­mometer and note the ue gas temperature. e ue gases should be within a range of 350°F to 450°F. If the ue gases are below the range, it may be necessary to slow down the blower fan. If the ue gases are above the range, the blower fan may require speeding up or the barometric damper needs adjusting. Stack temperature varies directly with the system temperature rise. System temperature rise is the dierence between the furnace outlet temperature and furnace inlet temperature as measured in the vicinity of the connection between the plenum take-os and the trunk ducts. Temperature rise
value is listed on the system rating plate. Perform a smoke spot test. e smoke spot should not exceed No. 1
on the Bacharach Scale. Aer the air adjustments have been completed, re-check the dra
pressure at the test port on the burner mounting plate as shown in
Figure 2.
In the United States, the Beckett AF Burner may be equipped with Beckett's "Inlet Air Shut-O" to increase eciency. (Beckett Part No. AF/A 5861).
e dra should be adjusted to -0.02 inches w.c.
NOTICE
USE OF THE INLET AIR SHUT-OFF COULD CAUSE POST COMBUSTION NOZZLE DRIP.
SPECIAL INSTRUCTIONS FOR UNITS EQUIPPED WITH RIELLO BURNERS
Riello burners are factory set with respect to nozzle size, pump pres­sure, air gate and turbulator adjustments for each model and ring rate; therefore, do not use the above listed set up procedures.
Riello specications are listed in Consult the Riello Installation Instructions supplied with the Burner for specic information concerning burner adjustments, operation, and trouble-shooting.
Table 3C,
page 11 of this manual.
13
DIRECT DRIVE BLOWER PSC MOTOR
Table 4 - Direct Drive Blower Set-Up PSC Motor
Blower Set-Up Cooling Capacity
Furnace Model Blower
0.20 in. w.c. 0.50 in. w.c. To ns Power CFM Range
Speed Motor Speed Motor
HTL-90D 100-10 DD Med-Low 1/2 HP Med-High 1/2 HP 3 1/2 HP 650 – 1400 HTL-100D 100-10 DD Med-Low 1/2 HP Med-High 1/2 HP 3 1/2 HP 650 – 1400 HTL-120D 100-10 DD Med-High 1/2 HP Med-High 1/2 HP 3 1/2 HP 650 – 1400 HTL-120D 120-10 DD Low 3/4 HP High 3/4 HP 5 3/4 HP 1500 - 2000 HTL-130D 120-10 DD Low 3/4 HP High 3/4 HP 5 3/4 HP 1500 - 2000 HTL-140D 120-10 DD Med-Low 3/4 HP High 3/4 HP 5 3/4 HP 1500 - 2000
Table 5 - Direct Drive Blower Characteristics PSC Motor
CFM
Furnace
Model
Blower
Motor HPMotor
FLA
∆T Speed
External Static Pressure – Inches w.c.
0.2 0.3 0.4 0.5 0.6
High 1639 1581 1507 1440 1374
HTL-D 90-120 100-10 DD 1/2 HP 7 70°F
HTL-D 120-
140
120-10 DD 3/4 HP 9 70°F
Med-High 1544 1493 1429 1366 1300
Med-Low 1158 1144 1121 1084 1040
Low 766 743 703 696 661
High 2111 2030 1974 1924 1857
Med-High 1974 1923 1885 1832 1792
Med-Low 1785 1753 1729 1679 1636
Low 1623 1594 1564 1513 1468
Furnace
Model
HTLV-D
90 – 120
HTLV-D
90 – 140
Table 6- Direct Drive Blower Characteristics ECM Motor
CFM RANGE
Blower
Motor HPMotor
FLA
∆T
Continuous
Fan
Heating Cooling
0.38 - 0.48 inches w.c. 0.5 inches w.c.
100-10 DD
120-10 DD 1 HP ECM 12.8 70°F 750 - 1000 1100 - 2100 800 - 2000
TIP: ese formulae will assist with the design of the ductwork and the determination of airow delivery:
CFM = BONNET OUTPUT / (1.085 X System Temperature Rise (∆T)) System Temperature Rise (∆T) = Bonnet Output/(1.085 x CFM)
1/2 HP
ECM
7.7 70°F 500 - 700 1100 - 1500 600 - 1200
14
Furnace
Model
HTLD & HTLVD DIMENSIONS
Table 7 - General Dimensions (Inches)
Cabinet Plenum Openings
Width Depth Height Supply
Return
Side Bottom
Flue
Diameter
Filter Shipping
Type Size
Weight
(LB.)
HTL-D
HTLV-D
22 30-3/4 58
Figure 3 - HTL-D & HTLV-D Dimensions
20½ x
20
14 x 22 14 x 22 6 Permanent 16 x 25 x 1 270
15
ECM BLOWER HTLVD
Table 8A - ECM Blower Set-Up (HTLV-D)
100-10DD Blower with ½ HP ECM
DIP SWITCH ADJUSTMENT CHART
FOR INPUT 0.75 USGPH TO 1.00 USGPH
SW1 - HEAT
INPUT
DIP Switch Position DIP Switch Position
1 2 1 2
OFF OFF A 1.00 OFF OFF A 3
ON OFF B 1.10 ON OFF B 4
OFF ON C 1.20 OFF ON C 5
ON ON D 0.85 ON ON D 2
POS.
USGPH
SW3- ADJUST
DIP Switch Position DIP Switch Position
1 2 1 2
OFF OFF A 0% OFF OFF A 1.00
ON OFF B (+) 15% ON OFF B 1.10
OFF ON C (-) 15% OFF ON C 1.20
ON ON D N/A ON ON D 0.85
POS. CFM
SW2 - COOL
POS.
SW4- DELAY
POS.
Figure 4 - ECM Blower Set-Up (HTLV-D)
AC
SIZE
(TON)
INPUT
USGPH
NOTICE
SW1 (HEAT) AND SW4 (DELAY) DIP SWITCHES MUST BOTH BE ADJUSTED ACCORDING TO INPUT (NOZZLE SIZE). SW2 (COOL): 1 TON is approximately equal to 400 CFM SW3 (ADJUST): (Heating Mode) Increase OR decrease temperature rise respectively (Cooling Mode) Increase OR decrease CFM respectively
16
ECM BLOWER HTLVD
Table 8B - ECM Blower Set-Up (HTLV-D)
120-10DD Blower with 1 HP ECM
DIP SWITCH ADJUSTMENT CHART
FOR INPUT 0.85 USGPH TO 1.20 USGPH
SW1 - HEAT
INPUT
DIP Switch Position DIP Switch Position
1 2 1 2
OFF OFF A 1.00 OFF OFF A 3
ON OFF B 1.10 ON OFF B 4
OFF ON C 1.20 OFF ON C 5
ON ON D 0.85 ON ON D 2
POS.
USGPH
SW3- ADJUST
DIP Switch Position DIP Switch Position
1 2 1 2
OFF OFF A 0% OFF OFF A 1.00
ON OFF B (+) 15% ON OFF B 1.10
OFF ON C (-) 15% OFF ON C 1.20
ON ON D N/A ON ON D 0.85
POS. CFM
SW2 - COOL
POS.
SW4- DELAY
POS.
Figure 5 - ECM Blower Set-Up (HTLV-D)
AC
SIZE
(TON)
INPUT
USGPH
NOTICE
SW1 (HEAT) AND SW4 (DELAY) DIP SWITCHES MUST BOTH BE ADJUSTED ACCORDING TO INPUT (NOZZLE SIZE). SW2 (COOL): 1 TON is approximately equal to 400 CFM SW3 (ADJUST): (Heating Mode) Increase OR decrease temperature rise respectively (Cooling Mode) Increase OR decrease CFM respectively
HTLV-90DRF Riello 40F3 Input 0.75 USGPH. SET: SW1-HEAT “D”, SW3-ADJUST “C”, SW4-DELAY “D”
17
WIRING DIAGRAMS
Figure 6 - Chimney Vent Burner Wiring Diagram HTL-D & HTLV-D
18
OIL BURNER OPERATION
Once the furnace ue pipe, electrical and oil line connections have been made, use the following instructions to set the burner:
Shut o the electrical power to the furnace. Install an oil pressure gauge to the pressure port on the oil pump.
(Refer to the oil pump specication sheet included with the burner instructions).
Restore electrical power to the furnace. Start the furnace and bleed all air from the fuel oil lines. Close the purge valve and re the unit. Allow the furnace to warm up to normal operating temperatures.
During this time, set the pump pressure in accordance with the data provided in
Tables 3A, B & C ,
page 11
.
When the furnace has reached "steady state" (aer approximately 10 minutes). Set combustion air damper to get a TRACE of smoke.
Check the system temperature rise. e temperature rise is the dierence between the return air temperature measured at a point near the return air inlet, and the supply air temperature measured near the furnace outlet. e system temperature rise is listed on the furnace rating plate. If the temperature rise is too high, the airow must be increased. If the temperature rise is too low, the fan should be slowed down.
Turn o the burner. Observing the duct thermometer in the supply air stream, note the temperature at which the blower fan stops. e fan adjustments can be made by moving the dipswitch settings on the timer control board for fan o delay.
To check the operation of the limit switch, shut o power to the furnace. Temporarily remove the neutral wire from the direct drive blower motor. Restore the electrical power to the furnace and set the thermostat above room temperature. Aer three or four minutes of burner operation, the limit control should turn the burner o. When the limit function test is complete, shut o electrical power to the furnace, replace the neutral wire to the blower fan motor, and then restore power. e blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan o time is achieved. e oil burner will then resume operation and continue until the thermostat is satised. Restore the thermostat setting to a comfortable temperature.
Set the heat anticipator adjustment in the thermostat (if so equipped), by removing the "R" or "W" wire to the thermostat, then reading the amperage draw between the two wires. Failure to remove one of the wires from the thermostat while performing this test could burn out the heat anticipator. Set the heat anticipator to the amperage measured.
NOTICE
THE FURNACE SHOULD BE RUN THROUGH AT LEAST THREE FULL CYCLES BEFORE LEAVING THE INSTALLATION, TO ENSURE THAT ALL CONTROLS ARE OPERATING PROPERLY AND AS EXPECTED.
NOTICE
ALL JOINTS IN ANY POSITIVE PRESSURE VENTING SYSTEM MUST BE CHECKED FOR LEAKS BEFORE LEAVING THE INSTALLATION SITE.
19
OIL PRIMARY CONTROL  SEQUENCE OF OPERATION
Oil Primary Control Detailed Sequence of Operation
Power is applied to unit. e oil primary control completes a self­diagnostic procedure. If no light or ame is present, and unit passes its self-diagnostic procedure, the control enters into the idle mode.
5.
Carryover timer expires.
Enters run state.A.
Igniter turns o.•
ermostat calls for heat:
1.
Safety check is made for ame (4 second delay).
If ame is not present, the oil primary control will apply A. power to the burner motor and igniter.
If ame is present, the control remains in the idle state.B.
2.
Unit enters a pre-purge period of 15 seconds. Aer 10 seconds, control checks for ame presence.
3.
If ame is not present, the oil primary control enters the A. trial for ignition state.
When ame is present, the control enters lock out mode. B.
4.
e Oil Primary Control monitors the burner ame.
When ame is present, the control enters ignition carry-A. over state. (Continues to spark for 10 sec.).
Provides continuous spark aer ame is sensed to assure • that burner remains lit.
Turns on LED diagnostic light.•
Starts carryover timer.•
a) Flame and call for heat are monitored.
■ If ame is lost and lockout timer has not expired, the control will return to trial for ignition state.
■ If ame is lost and lockout timer has expired, the control will enter the recycle state.
Recycle timer starts.• Burner motor and igniter and solenoid •
valve are turned o. LED diagnostic light ashes slowly.•
Combustion continues until thermostat is satised, or the oil pri­mary control detects a loss of ame and enters into Recycle Mode.
6.
ermostat is satised - call for heat is terminated:
Oil primary control shuts o burner motor and solenoid A. valve.
If the control utilizes a blower motor o delay, aer 30 • seconds, ame presence is checked.
■ If ame is not present, the control LED diagnostic light is o and returns to idle state.
■ If ame is presence is detected, the control enters lock out mode.
20
OIL PRIMARY CONTROL  SEQUENCE OF OPERATION
Figure 7 - United Technologies 1158-120 Fan Timer Board (HTL-D)
Figure 8 - United Technologies 1168-1 ECM Tap Board (HTLV-D)
21
OIL PRIMARY CONTROL  SEQUENCE OF OPERATION
22
OIL PRIMARY CONTROL  SEQUENCE OF OPERATION
Table 9: 1158-120 Electronic Fan Timer Board (Eft) Detailed Sequence Of Operation
23
OIL PRIMARY CONTROL  SEQUENCE OF OPERATION
Oil Primary Control Led Diagnostic Light
e LED diagnostic light has several functions. It indicates the state or mode in which the oil burner is operating. It will also indicate fault conditions, and help determine cad cell resistance while the burner is operating. Please refer to included burner manual for more details.
Normal Conditions:
e LED diagnostic light will turn on when the burner enters the carryover state; the point at which ignition spark is on, and will remain on through the run state, where the ignition spark is termi­nated but the burner continues to re.
e LED diagnostic light will turn o at the end of the burner cycle as the oil primary control enters the idle state, and will remain o until the next heating cycle.
Fault Conditions:
If the LED diagnostic light is ashing quickly; 1 Hz (½ second on / ½ second o), the oil primary control is in the lockout state or in restricted mode. To exit the lockout state, press the reset button.
If the LED diagnostic light is ashing slowly; ¼ Hz (2 seconds on / 2 seconds o), the oil primary control is in the recycle state. is indicates that ame sensing was lost aer the lockout timer expired during the ignition carryover state. e oil primary control will return to the idle state within 60 seconds.
NOTICE
IMPORTANT: Due to the potential hazard of line volt­age, only a trained, experienced service technician should perform the troubleshooting procedure.
Preliminary Steps:
Check the diagnostic light for indications of burner condition. Refer to the oil primary control LED DIAGNOSTIC LIGHT section for details.
CAUTION
WHEN SIMULATING A CALL FOR HEAT AT THE OIL PRIMARY CONTROL, DISCONNECT AT LEAST ONE THERMOSTAT LEAD WIRE FROM THE T1 - T2 TER­MINALS TO PREVENT DAMAGE TO THE THERMO-
!
STAT. NEGLECTING THIS PROCEDURE MAY BURN OUT THE HEAT ANTICIPATOR OF A STANDARD 24 VAC THERMOSTAT, OR CAUSE HARM TO COMPO­NENTS WITHIN A MICRO-ELECTRONIC THERMO­S TAT.
Before checking the oil primary control, perform these preliminary checks, (repair or replace controls as necessary):
Check the power supply; fuse box or breaker, any service • switches, all wiring connections, and burner motor reset button (if equipped).
Cad Cell Condition:
If the LED diagnostic light is o, the cad cell is not sensing ame. If the LED diagnostic light is on, the cad cell is sensing ame, or
viewing ambient light. e resistance of the cad cell may be checked while the oil primary
control is in the run state by pressing the reset button. e LED diagnostic light will ash the following code:
Table 10: Cad Cell Resistance
Flashes Resistance in Ohms
1 Less than 400
2 Between 400 - 800
3 Between 800 – 1600
4 Between 1600- 5000
Troubleshooting
Check the limit switches to ensure that the switch contacts • are closed.
Check the electrode gap and position.•
Check the contacts between the oil primary control and the • electrodes.
Check oil supply (tank gauge).•
Check the oil nozzle, oil lter, and oil valves.•
Check the piping or tubing to the oil tank.•
Check the oil pump pressure.•
Check Oil Primary Control And Igniter
If the trouble does not appear to be in the burner or ignition hard­ware, check the oil primary control and the igniter by using the following equipment:
Screwdriver. Voltmeter (0 - 150 VAC) Insulated jumper wires with both ends stripped.
24
OIL PRIMARY CONTROL TROUBLESHOOTING
WARNING
ELECTRICAL SHOCK HAZARD.
!
TROUBLESHOOTING IS DONE WITH THE SYSTEM POWERED. BE CAREFUL TO OBSERVE ALL NECES­SARY PRECAUTIONS TO PREVENT ELECTRICAL SHOCK OR EQUIPMENT DAMAGE.
Table 11: Oil Primary Control TROUBLESHOOTING
Preliminary Checks:
Make sure that limit switches are closed and those contacts are clean. Check for line voltage power on the oil primary control black and
white lead wires. Refer to
Table 11 or 12
for further troubleshooting information
25
OIL PRIMARY CONTROL TROUBLESHOOTING
Table 11: Oil Primary Control TROUBLESHOOTING continued from previous page
26
OIL PRIMARY CONTROL TROUBLESHOOTING
Table 11: Oil Primary Control TROUBLESHOOTING continued from previous page
Table 12: System and General Trouble Shooting
27
OIL PRIMARY CONTROL TROUBLESHOOTING
Table 12: System and General Trouble Shooting continued from previous page
Problem Possible Cause Remedy
Furnace will not start
Furnace will not start without rst pushing oil primary con­trol reset button. (Happens on frequent basis.)
Furnace starts, but cuts out
requiring manually resetting
the oil protector reset button.
Furnace starts, but cuts out requiring manually resetting the oil protector reset button
Oil burner sputtering at nozzle
Photo Cell wiring shorted or room light leaking into photo cell com­partment.
Open safety switch
No fuel oil.
Clogged nozzle.
Clogged oil lter. Replace oil tank lter or in-line lter if used.
Low oil pump pressure.
Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.
Defective burner motor.
Photo Cell (Cad Cell) defective.
No fuel oil.
Clogged Nozzle.
Clogged oil lter. Replace oil tank lter or in-line lter if used.
Low oil pump pressure.
Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.
Defective burner.
Water or contaminants in oil. Drain fuel oil storage tank; replace fuel oil. (Consult with fuel oil supplier).
Frozen oil line.
Electrodes out of adjustment or defective.
Poor transformer high voltage con­nections or defective transformer.
Fuel oil lter clogged. Replace fuel oil storage tank lter and/or fuel oil in-line lter.
Defective oil pump.
Fuel oil line partially clogged or contains air.
Clogged nozzle. Replace nozzle or clean it out.
Check photo cell (cad cell) wiring for short circuits. Also, check for room light leaking into cad cell compartment. Repair light leak if necessary. See Table C-3
Check for open limit or auxiliary limit. Also, check internal wiring connec­tions; loose connectors, etc.
Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line.
Check fuel oil lines. Replace any compression ttings found with high quality ared ttings. Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load, deter­mine why. Replace if necessary
If cad cell is dirty, clean it. (Determine why cad cell is getting dirty). If cad cell is poorly aimed, realign it. NOTE: e photocell should have a resis­tance of 100Ω in absence of light; a maximum of 1500 Ω in the presence of light. Ensure that room light is not leaking into the cad cell compartment (See diagnostic light section).
Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.
Replaces nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line.
Check fuel oil lines Replace any compression ttings found with high quality ared ttings. Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load, deter­mine why. Replace if necessary.
Gently warm oil line. Insulate oil line. (Outdoor piping size may require increased diameter).
Check electrode settings. Check electrodes for dirt build-up or cracks in porcelain.
Check contacts between the igniter and electrodes. If OK, replace the igniter.
Check burner motor and/or fuel oil pump coupling. Check oil pump pres­sure. Replace fuel oil pump if necessary.
Bleed air from oil line. If problem persists, replace oil line.
28
OIL PRIMARY CONTROL TROUBLESHOOTING
Table 12: System and General Trouble Shooting continued from previous page
Check Blower fan speed.
29
OIL PRIMARY CONTROL TROUBLESHOOTING
Table 12: System and General Trouble Shooting continued from previous page
NOTICE
FINAL CHECK OUT ENSURE THAT ALL SAFETY DEVICES AND ELECTRI-
CAL COMPONENTS HAVE BEEN SET FOR NORMAL OPERATION. ENSURE THAT ALL ELECTRICAL CON­NECTIONS ARE TIGHT AND THAT THE WIRING IS SECURE.
NOTICE
IMPORTANT:
Please ensure that the homeowner is informed and under­stands:
1.
Where the circuit breaker or fuse is located in the main electrical panel.
2.
Where the furnace switch is located, and the switch "on" and "o" positions if not obvious.
3.
Where the oil shut-o valve from the oil storage tank is located.
4.
How to operate the thermostat, and other related ac­cessories.
5.
How to operate the manual reset button on the primary control, and especially when not to push the reset button.
6.
How and where to visually inspect the venting system for leaks or other problems.
7.
How to inspect, clean and replace the air lter, and other homeowner maintenance procedures.
8.
Who to call for emergency service and routine annual service.
9.
e terms and conditions of the manufacturer's war­ranty and the contractor's warranty.
30
HOMEOWNER'S REFERENCE TABLE
31
PARTS LISTING  HIGHBOY MODELS: HTLD AND HTLVD
Ref. No.
1 109007731L Le Side Panel Assembly
2 109007729L Right Side Panel Assembly
3 109007727L Rear Panel
4 29189 Blower Division Assembly
5 26216 Base Panel
6 109007728 Inner Front Panel
7 29122L Blower Access Panel
8 21437L Top Panel
9 26097 Heat Exchanger Assembly
10 27068 Combustion Chamber Retainer Bracket
11 27000WP Replacement Combustion Chamber
12 109007674 Oil Burner Mounting Plate
13 28306 Flue Connector
14 2080175 Pouch Gasket
15 109007733 Air Bae
16 20602 Insulation Retainer
17
18
19 18020 Filter Frame 16” X 25”
20 5592B2 Filter Frame End Support
21 2180023 Filter 16” X 25” X 1” Permanent
24 29362 Control Box
25
26 28841 Limit Disc 60T11 BOF 220°F
27
28 29364 Wire Harness, Controls Fan Timer
29 29365 Wire Harness, Blower
30 29751 Wire Harness, Fan Timer Board, Transformer
31
32 240005330 Transformer
33 12240 (6”) Dra Regulator
Part No. DESCRIPTION
240007841 Radiator Clean-out Cover (2 per unit)
240006333 Radiator Clean-out Cover Gasket (2 per unit)
29161 Clean-out Gasket Retainer
29163 Clean-out Tube Gasket
21338L Upper Door Panel
28479 Logo Bezel
28563 Logo Label
29388 Fan Timer Control 1158-120 UTEC HTL
240007048 Fan Timer Control 1168-1 ECM UTEC HTLV
240006438 Wire Harness, ECM Control HTLV
240005742 Wire Harness, ECM Supply HTLV
Ref. No.
34a
34b
34c
35b
Part No. DESCRIPTION
240007760 Oil Burner Assembly, Beckett AF76XN
29689 Burner Motor 1/7 HP 3450 RPM PSC
29688 Beckett Clean-cut Oil Pump A2EA6520
29522 Solid State Ignitor 10SAY-01
240007858 Oil Primary Combustion Control Genisys
11961 Flame Retention Head F6
14619329 Nozzle, 1.00/60ºW
240007786 Oil Burner Assembly, Beckett AF76YB
29689 Burner Motor 1/7 HP 3450 RPM PSC
29688 Beckett Clean-cut Oil Pump A2EA6520
29522 Solid State Ignitor 10SAY-01
240007858 Oil Primary Combustion Control Genisys
12646 Flame Retention Head F6
14619333 Nozzle, 1.20/60ºW
240007794 Oil Burner Assembly, Beckett NX70LHHS
21839 Burner Motor 1/7 HP 3450 RPM PSC
27593
29522 Solid State Ignitor 10SAY-01
240007858 Oil Primary Combustion Control Genisys
240007859 Retention Head Assembly
240006431 Nozzle, 0.65/60ºW
109007722
109007724
30095 Blower Housing and Wheel, 120-10T DD
102000132 Blower Motor, 3/4 hp, 4-Speed HTL
109007745 Blower Motor, 1hp, ECM Programmed HTLV
17811 Motor Mounting Band – TR6884B
30259
27745 Motor Run Capacitor, 20 mfd @ 370 Vac HTL
27761 Capacitor Strap
27733 Blower Slide Rail 2 Per
Beckett Clean-cut Oil Pump A2EA6520
Blower Assembly Direct Drive 5-Ton PSC Motor HTL
Blower Assembly Direct Drive ECM 5-Ton ECM Motor HTLV
Motor Mount Arms – 12-10 DD Blower (3 per unit)
32
PARTS LISTING: HIGHBOY MODEL: HTLD AND HTLVD
Figure 9 - Model HTL-D and HTLV-D
33
NOTES:
HTLD & HTLVD OIL FIRED WARM AIR FURNACE
34
HTLD & HTLVD OIL FIRED WARM AIR FURNACE
35
HTLD & HTLVD OIL FIRED WARM AIR FURNACE
ECR International
2201 Dwyer Avenue
www.ecrinternational.com
36
Loading...