Olsen BMLV-80BRBU2, BMLV-90BRBU2, BML-80BRBU2, BMLV-60BRBU2, BML-60BRF2 Installation, Operation & Maintenance Manual

...
Page 1
BML
(Lowboy Model)
BMLV
(Lowboy Model with ECM)
Series B
Oil Fired Warm Air Furnaces
INSTALLATION, OPERATION & MAINTENANCE MANUAL
ECR International
2210 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
Page 2
Dimensions
F
1¾" (4.5cm)
H
G
E
D
C
B
A
Furnace
Model
BML
BMLV
WidthALengthBHeight
22" 51½" 32" 20½"x 19" 20½"x 18½" 5" 26¼" 20"x 20"x1" 240 LB
55.8 cm 130.8 cm 81.3 cm 52 cm x 49 cm
Cabinet Plenum Openings Flue
C
Supply
D x E
Return
F x G
52.1 cm x 47 cm
2
Diameter
12.7 cm 66.7 cm
Height
Filter
(Permanent)
H
51cm x 5cm x
2.6cm
Shipping
Weight
(LB)
108 Kg
Page 3
1. General ................................................................................................................................ 4
2. Safety Symbols ..................................................................................................................... 4
3. Introduction Models BML And BMLV .......................................................................................... 4
4. Heat Loss ............................................................................................................................. 4
5. Locating the Unit ................................................................................................................... 5
6. Furnace Used In Conjunction With Air Conditioning .................................................................... 5
7. Combustion Air ..................................................................................................................... 6
8. Chimney Venting ................................................................................................................... 6
9. Barometric Damper Control ..................................................................................................... 7
10. Optional Side Wall Venting ..................................................................................................... 7
11a. Fan Timer Board And Limit Control (BML) See Figure 3, page 15 ............................................... 7
11b. Fan Timer Board And Limit Control (BMLV) See Figure 4, page 15 ............................................. 7
12. Electrical Connections ........................................................................................................... 7
13. Humidier ........................................................................................................................... 8
14. Piping Installation ................................................................................................................ 8
15. Oil Filter ............................................................................................................................. 8
16. Oil Burner Nozzles ............................................................................................................... 8
17. Oil Burner Adjustment .......................................................................................................... 8
18. Burner Electrodes ................................................................................................................ 8
19. Burner Primary (Safety) Control ............................................................................................. 9
20. Combustion Chamber ........................................................................................................... 9
21a. Circulating Air Blower (BML/BMLV) ........................................................................................ 9
21b. Circulating Air Blower (BMLV) .............................................................................................10
22. Maintenance And Service .....................................................................................................11
23. Operating Instructions (BML) ................................................................................................12
24. Operating Instructions (BMLV) ..............................................................................................12
Appendix A: Checkout and Adjustments ................................................................................. 13
A.1 Oil Burner Air Adjustment ..................................................................................................14
A.2 Burner Electrodes .............................................................................................................15
A.3 Start Up ..........................................................................................................................15
A.4 Special Instructions For Units Equipped With Riello Burners .....................................................15
A.5 Final Check Out ................................................................................................................16
Appendix B: Wiring Diagrams ................................................................................................ 20
Chimney Vent Furnace Wiring Diagram BML/BMLV ......................................................................20
Direct Vent Furnace Wiring Diagram BML/BMLV ..........................................................................21
Appendix C - Sequence of Operation and Troubleshooting ..................................................... 22
C.1 Troubleshooting ................................................................................................................23
C.2 Preliminary Steps ..............................................................................................................23
C.3 Check Oil Primary Control ...................................................................................................23
Appendix D - Homeowner’s Reference Table .......................................................................... 27
Parts Listing: Chimney Vent Models BML80(B2,BRF2) and BMLV80(B2,BRF2) ....................... 28
Parts Listing: Direct Vent Models BML80(BB2U2,BRBU2) and BMLV80(BB2U2,BRBU2) .......... 30
Parts Diagram BML and BMLV ................................................................................................ 31
Check our website frequently for updates: www.ecrinternational.com
Information and specications outlined in this manual in effect at the
time of printing of this manual. Manufacturer reserves the right to
discontinue, change specications or system design at any time without
notice and without incurring any obligation, whatsoever.
3
Page 4
1. General
Furnace installation shall be completed by qualied agency.
See glossary for additional information.
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
WARNING
!
Fire, burn, asphyxiation hazard. Do not use gasoline, crank case oil, or any oil containing gasoline. Failure to follow these instructions could result in death or serious injury.
2. Safety Symbols
Become familiar with symbols identifying potential hazards.
3. Introduction Models BML And BMLV
Models BML and BMLV are oil red forced air up-ow furnaces with an output capacity range of 59,000 btu/hr to 89,000 btu/hr.
• BML models are equipped with 1/2 HP PSC 4 speed blower motor.
• BMLV models are equipped with 1/2 HP ECM variable speed blower motor.
Furnace models are either factory equipped for chimney venting or factory equipped for direct venting.
Chimney vent models and direct vent models are not
eld convertible. Direct vent installation instructions are
included with the direct vent models.
Installation shall conform to requirements of authority having jurisdiction or in absence of such requirements:
Canada - CAN/CSA - B139, Installation Code for Oil- Burning Equipment.
United States - National Electrical Code, NFPA31,
Standard for the Installation of Oil-Burning Equipment.
This is the safety alert symbol. Symbol alerts you to potential personal injury hazards. Obey all safety messages following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
Models are CSA listed, (NRTL/C) for use with No. 1 (Stove) and No. 2 (Furnace) Oil.
Refer to tables in Appendix A for performance data.
4. Heat Loss
Maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures described in the manuals of:
Canada - The Heating, Refrigeration and Air Conditioning Institute of Canada (HRAI), or by other means prescribed, or approved by the local authority having jurisdiction.
United States - Manual J. titled, "Load Calculation" published by the Air Conditioning Contractors of America, describes a suitable procedure for calculating maximum hourly heat loss.
4
Page 5
5. Locating the Unit - [See Table 1]
Locate furnace so ue connection to chimney is short, direct and consists of as few elbows as possible.
• Centralize furnace location with respect to supply and return air ductwork. Central location minimizes trunk duct sizing.
All models may be installed on combustible oors.
6. Furnace Used In Conjunction With Air Conditioning
• Install furnace in parallel with or upstream from evaporator coil to avoid condensation in heat exchanger.
• When installed in parallel, prevent chilled air from entering furnace by use of dampers or air controlling.
• Manually operated dampers must have a control to prevent operation of either system unless dampers are in full heat or full cool position.
• Air heated by the furnace shall not pass through
evaporator coil unless coil is specically approved for
such service.
Table 1: Minimum Installation Clearances
Clearance to Combustibles
Location
Top 1" (26 mm) Bottom 0"
S/A Plenum 1" (26 mm)
Rear 6"** (152 mm) Sides 1"* (26 mm) Front 1"** (26 mm)
4" (102 mm) measured horizontally
Flue Pipe
8" (204 mm) measured vertically or
Enclosure Closet
*18 in. (458 mm) Required from 1 side for access to rear ** 24 in. (610 mm) Service Clearance
BML and BMLV
Lowboy
or below ue pipe
above ue pipe
• Check and adjust blower speed to compensate for pressure drop caused by evaporator coil.
• Maintain required clearance between bottom of coil
drain pan and top of heat exchanger as specied by
coil manufacturer.
5
Page 6
7. Combustion Air
Comply with CSA B139 (Canada) or NFPA 31 (U.S.) standards for the Installation of Oil Burning Equipment and applicable provisions of local building codes to provide combustion and ventilation air.
WARNING
!
Asphyxiation hazard. Chimney vented versions of furnace
must be connected to ue having sufcient draft at all
times. Failure to follow these instructions could result in death or serious injury.
8. Chimney Venting
• Flue pipe should be as short as possible with
horizontal pipes sloping upward toward the chimney
at a rate of one-quarter inch per foot.
• Flue pipe should not be smaller in cross sectional
area than ue collar on the furnace.
Flue pipe should connect to chimney so the ue pipe
extends into, and terminates ush with the inside
surface of chimney liner. Seal the joint between pipe and lining.
• Chimney outlet should be at least two feet above
highest point of peaked roof.
• All unused chimney openings should be closed.
• Chimneys must conform to local, provincial or state
codes, or in the absence of local regulations, to the requirements of the National Building Code.
NOTICE
This furnace is approved for use with Type L vent or equivalent. Maximum vent temperature for Type L vent is 575°F (300C).
Manufacturer recommends over re draft of -0.02 in. w.c. See gure 2.
Flue pipe must not pass through any oor or ceiling, may pass through a wall where suitable re protection
provisions have been installed.
Refer to CAN/CSA B-139 for rules governing the installation of oil burning equipment.
• United States, refer to NFPA 31 for regulations governing the installation of oil burning equipment.
See appendix A for burner set-up.
Figure 2 - Check Over-Fire Draft
Over-re draft access port.
6
Page 7
9. Barometric Damper Control
Barometric damper control, also known as draft regulator, is used on conventional chimney venting only. Control automatically maintains constant negative pressure. Ensures proper pressures are not exceeded. If chimney
does not develop sufcient draft, draft control does not
function properly.
• Install draft regulator in same room or enclosure as furnace. Draft regulator should not interfere with combustion air supplied to the burner.
Locate control near furnace ue outlet.
• Install per instructions supplied with regulator.
Set over re draft, measured at oil burner mounting
plate over-re draft access port, to -0.02 in. w.c. See
Figure 2 page 6.
10. Optional Side Wall Venting
Certain BML and BMLV furnace models are manufactured as sidewall vented units. Refer to Direct Venting Instructions, P/N 240006979 included with Vent Kit for details.
Sidewall Venting (Direct Venting) requires use of specic oil burners; Beckett AFII, or Riello 40BF.
Refer to Appendix A, Tables A2, and A4.
11a. Fan Timer Board And Limit Control (BML) See Figure 3, page 15.
Electronic Fan Timer integrates control of burner and circulator fan operations. Control is central wiring point for most of furnace electrical components.
United Technologies 1158-120 (BML) has an adjustable fan on time set by selecting dipswitch combination displayed in Chart 1. Fan on delay can be set at 30, 60, 90 or 120 seconds. Provides a
delay between burner ignition and blower start-up to eliminate excessive ow of cold air when blower
comes on.
United Technologies 1158-120 (BML) has an adjustable fan off time of 2, 3, 4 or 6 minutes as displayed in Chart 1. Fan off delay time starts when
burner motor is de-energized at end of call for heat.
Blower shutdown is delayed to remove any residual heat from heat exchanger.
• Electronic fan timer board works in conjunction with snap disc limit controls, performing a safety function, and breaks power to oil burner primary control,
shutting off burner if furnace over-heats.
• Limit control is thermally operated and automatically
resets. Limit control is factory installed, pre-set and
is not adjustable.
If limit control opens with United Technologies 1158- 120 (BML) electronic fan control, circulating fan will energize. When limit closes, fan off timer begins. At the end of fan off time cycle burner is energized, initiating normal burner cycle.
Chart 1- United Technologies 1158-120 (BML)
Dip Switch Position Blower Delay Times
1 2 3 4 On Seconds Off Minutes
Off Off 30 On Off 60 Off On 90 On On 120
Off Off 2 On Off 3 Off On 4 On On 6
11b. Fan Timer Board And Limit Control (BMLV) [See Figure 4, page 15]
United Technologies 1168-1 ECM (BMLV) tap board has an adjustable fan on/off delay and airow settings that must
be adjusted in accordance with furnace input rating (nozzle
size). Refer to Table A-9, page 17 for ECM blower set-up.
12. Electrical Connections
• Furnace is listed by Canadian Standards Association under NRTL (North American) Standard.
All eld wiring shall conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail.
• United States, wiring shall conform to National Fire
Protection Association NFPA-70, National Electrical
Code, and with local codes and regulations.
• Wire furnace to separate dedicated circuit in main electrical panel.
• Suitably located circuit breaker can be used as service switch, separate service switch is advisable.
• Service switch is necessary if circuit breaker is close to the furnace, or furnace is located between circuit breaker and entry to furnace room.
• Clearly mark service switch. Install in accessible area between furnace and furnace room entry. Locate so as to reduce possibility it can be mistaken as light switch or similar device.
• Power requirement for BML and BMLV models is: 115 VAC, 1 Ø, 60 Hz., 12A.
• Accessory equipment such as electronic air cleaners
and humidiers may be included on furnace circuit.
• Accessories requiring 115 VAC power sources such
as electronic air cleaners and humidier transformers
may be powered from electronic fan timer board where provisions have been made for connections, but should have their own controls.
• Do not use direct drive motor connections as a power source, there is risk of damaging accessories.
7
Page 8
• Thermostat wiring connections are shown in wiring
diagrams in Appendix B. Some micro-electronic
thermostats require additional controls and wiring.
Refer to thermostat manufacturer's instructions.
Locate thermostat approximately 5 feet above oor, on inside wall, and where thermostat is exposed to average room temperatures. Avoid locations where thermostat is exposed to cold drafts, heat from nearby lamps and appliances, exposure to sunlight, heat from inside wall stacks, etc.
• Adjust thermostat heat anticipator to amperage draw of heating control circuit as measured at "R" and "W" terminals of thermostat. Do not measure current with thermostat connected to the circuit. Measure amperage by connecting ammeter between two wires which connect to thermostat "R" and "W" terminals.
13. Humidier
Humidier is optional accessory available through most heating supplies outlets.
Follow humidier manufacturer's installation instructions
• Protect furnace heat exchanger from water or water
droplets from humidier.
• Do not use direct drive motor connections as source
of power for 115 VAC humidiers and humidier
transformers.
16. Oil Burner Nozzles
BML and BMLV are certied for multiple ring rates, ranging from 59,000 to 89,000 Btu/h output. Furnace may be red
at ideal rate for wide range of structures by manipulating
oil burner nozzle, ame retention head, and temperature rise. Refer to Table A-1 thru A-4, and furnace rating plate
to determine proper combinations.
17. Oil Burner Adjustment
• Adjust burner air supply to maintain fuel to air ratio to obtain ideal combustion conditions.
Lack of air causes "soft" and "sooty" ames, resulting
in soot build-up throughout heat exchanger passages.
Excess combustion air causes bright roaring re and high stack temperatures resulting in poor fuel
efciency.
BML and BMLV operate most efciently with No. 1 smoke spot on Bacharach Scale. Dust will eventually build up on air moving components of oil burner assembly resulting in decreased air supply with
potential soot build up in ue gas passageways
of heat exchanger. Soot behaves as insulator and impairs good heat transfer. Stack temperature
increases, and efciency decreases. To avoid this
problem, adjust the air supply to provide no more than trace smoke spot on Bacharach Scale.
See Venting Instructions included in Vent Kits for set- up details for sidewall vented furnaces.
14. Piping Installation
• Install fuel system in accordance with requirements
of CAN/CSA B-139, and local regulations.
• United States installation shall conform to NFPA No. 31 and local codes and authorities.
Use only approved fuel oil tanks, piping, ttings and
oil lter.
Install oil lter as close to burner as possible.
• Refer to instructions and illustrations in oil burner and oil pump instructions shipped with the furnace.
15. Oil Filter
Install oil lter between fuel oil storage tank and oil burner.
When using oil burner nozzle smaller than 0.65 U.S.
Gallons Per Hour, install additional 7 to 10 micron lter as
close as possible to oil burner.
NOTICE
Set up sidewall vented models to deliver zero (0) smoke.
NOTICE
Before operating furnace check burner alignment with combustion chamber. End cone of air tube must be centred to accommodating ring of combustion chamber. Adjust as necessary.
18. Burner Electrodes
Correct positioning of electrode tips with respect to each other, fuel oil nozzle, and burners is essential for smooth light ups and proper operation.
Refer to oil burner instructions provided with furnace and Appendix A Section A.2 in this manual for electrode
specications.
8
Page 9
NOTICE
Do not tamper with furnace controls they are sensitive. If problems persist, call your service contractor.
19. Burner Primary (Safety) Control
Furnace is equipped with primary combustion control, also referred to as burner relay or burner protector relay, which uses a cad cell located in burner housing, to monitor and control combustion.
Dust or combustion residuals can build up on lens of cad
cell impairing its response to ame. Check cad cell for
cleanliness and proper alignment if primary control fre­quently shuts down combustion.
20. Combustion Chamber
Furnace is equipped with cerafelt combustion chamber, held in place by a retaining bracket.
Check the alignment of the combustion chamber
and oil burner before ring. It is possible for the
combustion chamber to shift if subjected to rough handling during transit.
Inspect combustion chamber for damage or carbon build up whenever oil burner is removed for repairs or routine maintenance.
WARNING
!
Fire, burn, asphyxiation hazard. Do not start the burner unless blower access door is secured in place. Failure to follow these instructions could result in death or serious injury.
• Some older duct systems were not designed to provide static pressure. They typically feature special
reducing ttings at each branch run and lack block
ends on the trunk ducts. These systems may require
modication to provide some resistance to the airow to prevent over-amping of direct drive blower motor.
Selecting a lower blower speed may correct this problem.
• Direct drive blower speeds are adjusted by changing "hot" wires to motor winding connections. Refer to wiring diagrams in Appendix B or wiring diagram
label afxed to furnace.
• Do not move neutral wire (normally white wire) to adjust blower speed.
• Single blower speed for both heating and cooling
modes may be used. Use a "piggy-back connector"
accommodating both wires on a single motor tap.
• It is also acceptable to connect selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut.
• Safety precaution against accidental disconnection of wires by vibration, secure wire nut and wires with few wraps of electricians tape.
• Do not connect power leads between motor speeds. Always connect neutral wire to motor's designated neutral terminal.
• If joining blower speed wiring is done in furnace junction box, tape off both ends of unused wire.
• Do not use blower speed wires as source of power to accessories as electronic air cleaners
and humidier transformers. Unused motor taps auto-generate sufciently high voltages to
damage accessory equipment.
21a. CIRCULATING AIR BLOWER (BML/BMLV)
• BML furnace models may be equipped with either direct drive or belt drive blower systems.
• BMLV furnace models are equipped with direct drive blower systems.
• BML models are equipped with PSC motors.
• BMLV models are equipped with electronically commutated motors (ECM).
Direct Drive Blower Systems
• Direct drive blower speed adjustments are not normally required in properly sized extended plenum duct systems. Motor RPM and air CFM delivery will vary automatically to accommodate conditions within usual range of external static pressures typical of residential duct systems.
Under-sized duct systems may require higher blower speed to obtain system temperature rise.
Belt Drive Blower Systems
WARNING
!
Improper installation could result in death or serious injury. Belt drive components operate at high speeds and may snag loose clothing resulting in injury or death. Have a trained service professional preform the following instructions. Failure to follow these instructions could result in death or serious injury.
Belt drive blower systems can be modied for speed and
air delivery by adjusting variable speed motor pulley and changing blower pulley.
• Adjust variable speed motor pulley by loosening 5/32 allen set screw in outer sheave. Turn outer sheave clockwise to increase blower speed, counter clockwise to reduce speed.
9
Page 10
Verify setscrew is tightened at one of the at spots, failure to do so will convert the variable speed pulley
to a xed speed pulley by ruining the threads.
• Modify blower speed by changing the blower pulley. Smaller blower pulley will cause the blower to turn faster. Large pulley reduces blower speed.
!
WARNING
Electrical shock hazard. Turn OFF electrical power supply at service panel before opening blower access door. Failure to do so could result in death or serious injury.
• Large increases in the blower speed may increase power requirements.
• Check amperage draw of the blower motor after making changes. If amperage draw is greater than the value listed on the motor rating plate, replace with motor of higher horsepower.
Deection of 3/4 of an inch to 1 inch fan belt tension
is necessary. Less deection places a strain on the
blower bearings and increases start up amperage draw.
More deection allows excess slippage and causes premature motor pulley wear.
• Automotive belt dressings are not recommended.
• Bar soap will work as belt dressing to reduce belt squeaks, etc. If using soap apply to the sides of belt only.
If operating belt drive blower at speeds above 1100 RPM, replace sintered bronze blower bearings with roller bearings.
21b. Circulating Air Blower (BMLV)
BMLV furnace models are equipped with electronically commutated motors (ECM).
Setting Blower Speed and “ON” and “OFF” Timings
Blower speed and on/off time delays are handled by ECM motor programming and are set via dipswitches per Table
A-9 on page 17. Heating airow rate is SW1 and on/off delay is SW4, both are set according to ring rate. Cooling airow rate is SW2 and if used is set according to installed cooling capacity. SW3 can be used to adjust airow rate by (+) or (-) 15%. Features of this ECM variable speed motor are that it will deliver a constant airow within a wide range
of external static pressures, and also includes:
• Soft Start: ECM will slowly ramp up to required operating speed. In heating cycle allows heat exchanger to reach operating temperature before set heat speed, minimizes noise and increases comfort.
• Soft Stop: At end of heating cycle, ECM will slowly
ramp down. Allows increased energy efciency and
reduced noise levels.
Dehumidication: Dehumidication feature is
programmed into the variable speed motor. At start of each cooling cycle, variable speed motor will run
at 82% of rated airow for 7.5 minutes. After 7.5 minutes has elapsed, motor will increase to 100% of rated airow. Used to provide dehumidication and improve system efciency.
10
• Continuous Fan Operation: When thermostat continuous fan (G) switch is on without call for heating or cooling, indoor fan is immediately
energized up to 50% of cooling speed. Allows
continuous circulation of air between calls for heating or cooling. If call for heat (W) or cool (Y) occurs during continuous fan, blower remains energized.
Page 11
22. Maintenance And Service
Routine Maintenance By Home Owner
• Arrange for professional servicing of furnace by the service or installation contractor annually.
Homeowner is to maintain air lter or lters. A dirty
lter can cause furnace to over-heat, fail to maintain
indoor temperature during cold weather, increase fuel consumption and cause component failure.
Inspect, clean or replace lter monthly.
Furnace is supplied with semi-permanent type lter.
If lter is damaged, replace with lters of same size
and type.
During monthly lter inspection, inspect general condition of furnace. Watch for signs of oil leaks in vicinity of oil burner, soot forming on any external part of furnace, soot forming around joints in vent pipe, etc. If any of these conditions are present, please advise your service or installation contractor.
Annual Service By Contractor
NOTICE
Combustion chamber (repot) is fragile. Use care
when inspecting and cleaning this area
• If cleaning is necessary, shut off oil supply, shut off power to the furnace and remove burner.
• Use stiff brush with wire handle, brush off scale and
soot from inside drum and ue pipe.
Clean radiator, remove clean-out cap screws. Remove caps carefully to avoid tearing gaskets.
• Wire brush can be used to loosen dirt and debris on the inside surfaces of radiator. Clean out all accumulated dirt, soot and debris with a wire handled brush and an industrial vacuum cleaner.
Before replacing clean-out caps, inspect gaskets. If gaskets are broken, remove remnants and replace with new gaskets.
• Blower motor is factory oiled and permanently sealed. Do not lubricate. Excess oil causes premature electric motor failure.
• Inspect blower fan. Clean if necessary.
• Oil Burner Maintenance: Follow oil burner manufacturer instructions.
Change oil burner nozzle and oil lter annually.
• Clean and inspect venting system for signs of deterioration. Replace pitted or perforated vent pipe
and ttings.
• Inspect heat exchanger periodically and clean if necessary.
!
WARNING
Electrical shock hazard. Turn OFF electrical power supply at service panel before service or maintenance Failure to do so could result in death or serious injury.
• Barometric damper should open and close freely.
• Check electrical connections to ensure tight connections. Safety controls such as the high limit controls should be tested for functionality.
• Check fan control to ensure fan on and off delay function continues to start and stop blower fan at optimal settings.
11
Page 12
WARNING
!
Fire, burn, explosion, asphyxiation hazard.
• Do not start burner when excess oil has accumulated, furnace is full of vapor, or combustion chamber is very hot.
• Do not burn garbage or paper in furnace.
• Do not leave paper or rags around furnace.
Failure to follow these instructions could result in death or serious injury.
23. OPERATING INSTRUCTIONS (BML)
Before Lighting
1.
Open all supply and return air registers and grilles.
2.
Open all valves in oil pipes.
3.
Turn on electric power supply
To Light Unit
1.
Set thermostat above room temperature to call for heat. Burner should start. It may be necessary to press RESET button on primary combustion control relay.
2.
There is a fan on time delay before circulating fan
is energized. United Technologies 1158-120 has
adjustable fan on time set by selecting dipswitch combination displayed in Chart 1. Fan on delay can be set at 30, 60, 90 or 120 seconds.
3.
Set the thermostat below room temperature. Oil burner stops.
4.
Air circulation blower continues to operate until time off setting selected on electronic fan timer control times out. United Technologies 1158-120 has adjustable fan off time of adjustments may be altered if air at room registers is high upon blower start up or shutdown.
5.
Restore thermostat setting to comfortable temperature.
2, 3, 4 or 6 minutes.
Fan timer control
24. Operating Instructions (BMLV)
Before Lighting
1.
Open all supply and return air registers and grilles.
2.
Open all valves in oil pipes.
3.
Turn on electric power supply.
To Light Unit
1.
Set thermostat above room temperature to call for heat. Burner should start. It may be necessary to press RESET button on primary combustion control relay.
2.
There is a fan on time delay before circulating fan is
energized. United Technologies 1168-1 has adjustable
fan on/off time delay programmed into ECM motor, and is set by selecting SW4 DIP switch combination
displayed in Table A-9 page 17. Adjust Fan on/off
delay according to input (nozzle size).
3.
Set thermostat below room temperature. Oil burner stops.
4.
Air circulation blower continues to operate until blower off delay setting programmed into ECM motor times out.
5.
Restore thermostat setting to comfortable temperature.
NOTICE
If furnace is to be shut down for extended period of time, close oil supply valve to burner.
To Shut Down Unit
1.
Set thermostat to lowest possible setting.
2.
Set manual switch (if installed) in electrical power supply line to "OFF".
12
Page 13
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Check out and adjustments
BML and BMLV furnaces may be used with following oil burners.
Beckett AF, and Riello 40F oil burners are for applications using indoor air for combustion only.
Sidewall venting applications utilizing outdoor air for combustion, use Beckett AFII or Riello 40BF (Balanced Flue) oil burners only.
Table A-1 Beckett AF Oil Burner Set-Up
Beckett AF Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
BML-60B2
2
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
59,000 AF76BNHS 0.50 / 80°A 100 psig 0.50 usgph F3 3- ⅜ in.
BMLV-60B2²
BML-80B2
76,000 AF76BNHS 0.65 / 80°A 100 psig 0.65 usgph F3 3- ⅜ in.
BMLV-80B2
BML-90B2
85,000 AF76BNHS 0.75 / 80°A 100 psig 0.75 usgph F3 3- ⅜ in.
BMLV-90B2
1
Head is shielded by ceramic insulator.
2
Low Firing Rate Bafe required when using 0.50-gallon nozzle.
Table A-2 Beckett AFII Oil Burner Set-Up
Beckett AFII Series Oil Burners
(For use with sidewall vented units with outdoor combustion air,
or chimney vented units with indoor air for combustion)
Furnace Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
BML-60BB2U2
59,000 AFII-85 0.50 / 60°A 115 psig 0.50 usgph FB0
BMLV-60BB2U2
BML-80BB2U2
76,000 AFII-85 0.60 / 60°A 145 psig 0.65 usgph FB3
BMLV-80BB2U2
BML-90BB2U2
88,000 AFII-85 0.70 / 60°A 145 psig 0.75 usgph FB3
BMLV-90BB2U2
Flow Rate Head
Pump
Pressure
Static
1
Plate
Flow Rate Head
13
Page 14
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Table A-3 Riello 40F Series Oil Burner Set-Up
Riello 40F Series Oil Burners
(For use with chimney vented units)
Furnace Model
Output
BTU/Hr
Burner
Model
Delavan Nozzle
Pump
Pressure
Flow Rate Air Gate
Turbulator
Setting
BML-60BRF2
60,000 40F3 0.50 / 60°W 105 psig 0.50 usgph 2.6 1.0
BMLV-60BRF2
BML-80BRF2
77,000 40F3 0.60 / 60°W 120 psig 0.65 usgph 2.6 1.5
BMLV-80BRF2
BML-90BRF2
88,000 40F3 0.65 / 60°W 135 psig 0.75 usgph 3.6 2.0
BMLV-90BRF2
Table A-4 Riello Balanced Flue (40BF) Burner Set-Up
Riello 40BF Balanced Flue Series Oil Burners
(For use with sidewall vented units using outdoor combustion air)
Furnace Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
BML-60BRBU2
61,000 40BF3 0.50 / 60°W 105 psig 0.50 usgph 1.0
BMLV-60BRBU2
BML-80BRBU2
78,000 40BF3 0.60 / 60°W 120 psig 0.65 usgph 1.5
BMLV-80BRBU2
BML-90BRBU2
89,000 40BF3 0.65 / 60°W 135 psig 0.75 usgph 2.0
BMLV-90BRBU2
Pump
Pressure
Flow Rate
Turbulator
Setting
NOTE: Air gate setting may vary for sidewall vented units where air gate must be adjusted to achieve zero smoke.
A.1 OIL BURNER AIR ADJUSTMENT
Consult oil burner instructions provided in furnace
documents envelope for specic information concerning
burner adjustments, operation and troubleshooting.
Beckett AF Burner (Chimney Vent)
Adjust air shutter by loosening locking screws. Moving air shutter, and if necessary, bulk air band.
Beckett AFII Burner (Direct Vent)
Adjust burner air supply. Loosen locking screw located on black dial to right of burner. Turn black dial clockwise to
increase combustion air and counter-clockwise to decrease combustion air. Re-tighten locking screw after obtaining
proper setting.
Riello 40F3 Burner (Chimney Vent)
Combustion air is adjusted by removing burner cover. Loosen screws that secure air adjustment plate. Move adjusting plate to either increase or decrease combustion
air. When proper air setting is achieved, retighten xing
screws.
Riello 40BF3 Burner (Direct Vent)
Combustion air can be adjusted with burner cover on. Remove plastic cover on top right hand side of burner cover. With phillips head screw driver, turn adjustment
screw clockwise to increase combustion air or counter-
clockwise to decrease combustion air. When combustion air
is set, re-insert plastic cover.
14
Page 15
APPENDIX A - CHECK OUT AND ADJUSTMENTS
A.2 Burner Electrodes
Adjustment of electrode tips with respect to each other, nozzle, burner head is very important to ensure smooth
start-ups and to permit efcient combustion.
Beckett AF and AFII Burners
• Electrode gap: 5/32 inch.
Distance above horizontal center-line: 5/16 inch. Older instruction sheets specify 7/16 inch. Current
specication is 5/16 inch.
• Distance ahead of nozzle: 1/16 inch.
• “Z” dimension, distance from front of end cone
(head) to face of nozzle should be 1-1/8 inches. If
ceramic head is used, distance from end cone to
nozzle face is increased to 1-3/8 inches.
Riello 40F, & BF Burners
• Electrode gap: 5/32 inch.
Distance above horizontal center-line: 13/64 inch.
• Distance ahead of nozzle: 5/64 to 7/64 inch.
A.3 Start Up
Use following instructions to set the burner:
1.
Shut off electrical power to the furnace.
2.
Install oil pressure gauge to pressure port on oil pump.
(Refer to oil pump specication sheet included with
burner instructions).
3.
Restore electrical power to furnace.
4.
Start furnace and bleed all air from fuel oil lines.
5.
Close purge valve and re the unit.
6.
Allow furnace to warm up to normal operating temperatures. During this time, set pump pressure in
accordance with data provided in Appendix A, Table A-1 thru A-4.
7.
Chimney vented units - Drill 1/4" test port in venting between furnace ue outlet and draft regulator
(barometric damper) to take smoke readings.
8.
Sidewall vented units - Do not drill. Use test port
in the supplied appliance connector to take smoke readings.
9.
When furnace has reached "steady state" (after ap­proximately 10 minutes). Set combustion air damper to get TRACE of smoke for chimney vented units and ZERO smoke for sidewall vented units.
10.
Check system temperature rise. Temperature rise is the difference between return air temperature measured at a point near return air inlet, and supply air temperature measured near furnace outlet.
System temperature rise is listed on furnace rating
plate. If temperature rise is too high, airow must
be increased. If temperature rise is too low, slow fan down.
11.
After air adjustments have been completed, recheck
the over re draft at test port on burner mounting plate shown in Figure 2. Over re draft should be adjusted to
-0.02 inches w.c.
12.
Turn burner off. Observe duct thermometer in supply air stream, note temperature blower fan stops. Fan adjustments can be made by moving dipswitch settings on timer control board for fan off delay.
13.
Check operation of limit switch. A. Shut off power to furnace.
B. Temporarily remove neutral wire from PSC blower
motor or remove 5 pin power connector from ECM blower motor. Isolate AC line voltage pins on 5 pin power connector with electrical tape to prevent
electric shock hazard. C. Restore electrical power to furnace. D. Set thermostat above room temperature. E. After three or four minutes of burner operation,
limit control should turn burner off. F. When limit function test is complete, shut off
electrical power to furnace, replace neutral wire to
PSC blower motor or 5 pin power connector to ECM
blower motor. Restore power. G. Blower fan will start up immediately. Once
temperature has dropped and limit control has
reset, fan will operate until fan off time is reached. H. Oil burner will resume operation and continue until
thermostat is satised.
I. Restore thermostat setting to comfortable
temperature.
14.
Set heat anticipator adjustment in thermostat (if so equipped), by removing "R" or "W" wire to thermostat. Read amperage draw between the two wires. Failure to remove one of the wires from thermostat while performing this test could burn out heat anticipator. Set heat anticipator to amperage measured.
15.
Run furnace through at least three full cycles before leaving the installation, to ensure all controls are operating properly.
16.
Check all joints in any positive pressure venting system for leaks before leaving the installation site
A.4 Special Instructions For Units Equipped With Riello Burners
Riello specications are listed in Tables A-1 and A-4.
Consult Riello Installation Instructions supplied with Burner
for specic information concerning burner adjustments, operation, and trouble-shooting.
15
Page 16
APPENDIX A - CHECK OUT AND ADJUSTMENTS
A.5 Final Check Out
Verify all safety devices and electrical components have been set for normal operation.
Verify all electrical connections are tight and wiring is secure.
Verify homeowner is informed and understands: Where circuit breaker or fuse is located in main electrical
panel. Where furnace switch is located, and switch "on" and "off"
positions if not obvious.
FIGURE 3: UNITED TECHNOLOGIES 1158-120 FAN TIMER BOARD (BML)
Where oil shut-off valve from oil storage tank is located.
Thermostat operation, and other related accessories. How to operate manual reset button on primary control,
and when not to push the reset button. How and where to visually inspect venting system for leaks
or other problems.
How to inspect, clean and replace air lter, and other
homeowner maintenance procedures. Who to call for emergency service and routine annual
service.
FIGURE 4: UNITED TECHNOLOGIES 1168-1 ECM TAP BOARD (BMLV)
16
Page 17
Tons Power CFM Range
APPENDIX A - CHECK OUT AND ADJUSTMENTS
CFM
External Static Pressure – Inches w.c.
Blower Set-Up Cooling Capacity
0.20 in. w.c. 0.50 in. w.c.
Speed Motor Speed Motor
0.20 0.30 0.40 0.50 0.60
High 1722 1645 1561 1462 1375
Med-High 1604 1545 1473 1383 1302
Low 747 738 720 702 669
Med-Low 1147 1133 1106 1063 1013
CFM RANGE
Heating Cooling
0.38 - 0.48 inches w.c. 0.5 inches w.c.
Fan
Continuous
Blower Motor HP Motor FLA ∆T Speed
BML-60 100-10T DD Low 1/2 HP Med-Low 1/2 HP 3.5 1/2 HP 700-1400
BML-80 100-10T DD Med-Low 1/2 HP Med-Low 1/2 HP 3.5 1/2 HP 700-1400
BML-90 100-10T DD Med-Low 1/2 HP Med-High 1/2 HP 3.5 1/2 HP 700-1400
Furnace Model Blower
Table A-6 Direct Drive Blower Set-Up PSC Motor
Table A-7 Direct Drive Blower Characteristics PSC Motor
Model
Furnace
100-10T DD 1/2 HP 7.1 70°F
BML
60 – 90
1/2 HP ECM 7.7 70°F 470-635 625 - 1500 600 - 1200
Blower Motor HP Motor FLA ∆T
Model
Furnace
DD
100-10T
BMLV
60 – 90
TIP
Formulas will assist with design of duct-work and determination of air ow delivery.
CFM = Bonnet Output / (1.085 x System Temperature Rise (T)
System Temperature Rise (T) = Bonnet Output / (1.085 x CFM)
Table A-8 Direct Drive Blower Characteristics ECM Motor
17
Page 18
APPENDIX A - CHECK OUT AND ADJUSTMENTS
(TON)
AC Size
POS.
SW2 - COOL
1 2
DIP Switch Position
INPUT
OFF OFF A 3
ON OFF B 2.5
INPUT
POS.
ON ON D 1.5
OFF ON C 2
SW4 - DELAY
CFM
OFF OFF A 0.65
DIP Switch Position
1 2 USGPH
ON OFF B 0.85
OFF ON C 0.75
ON ON D 0.50
POS.
SW1 - HEAT
Dip Switch Adjustment Chart
For Input 0.50 USGPH TO 0.85 USGPH
1 2 USGPH
DIP Switch Position
OFF OFF A 0.65
ON OFF B 0.85
Table A-9 ECM Blower Set-Up (BMLV)
OFF ON C 0.75
ON ON D 0.50
POS.
SW3 - ADJUST
1 2
ON OFF B (+)15%
OFF OFF A 0%
DIP Switch Position
18
ON ON D N/A
OFF ON C (-)15%
NOTE:
SW1 (HEAT) AND SW4 (DELAY) DIP SWITCHES MUST BOTH BE ADJUSTED ACCORDING TO INPUT (NOZZLE SIZE).
SW2 (COOL): 1 TON is approximately equal to 400 CFM
SW3 (ADJUST): (Heating Mode) Increase OR decrease temperature rise respectively
(Cooling Mode) Increase OR decrease CFM respectively
Page 19
CFM
Range
Tons Motor
APPENDIX A - CHECK OUT AND ADJUSTMENTS
CFM
Belt Motor
Pulley
Blower Set-Up Cooling Capacity
Belt Motor
7 x ¾ 4L380 1/2 HP 3¼ x ½ 7 x ¾ 4L380 1/2 HP 1.5-3.5 1/2 HP 600-1400
0.20 in. w.c. 0.50 in. w.c.
Pulley
Motor Blower Motor Blower
7 x ¾ 4L380 1/2 HP 3¼ x ½ 7 x ¾ 4L380 1/2 HP 1.5-3.5 1/2 HP 600-1400
7 x ¾ 4L380 1/2 HP 3¼ x ½ 7 x ¾ 4L380 1/2 HP 1.5-3.5 1/2 HP 600-1400
0.20 0.25 0.30 0.40 0.50 0.60
External Static Pressure – Inches w.c.
Turns Out
Motor Pulley
Pulley
Blower
0 1410 1341 1272 1145 996 820
1 1277 1211 1145 970 790 598
2 1154 1077 1002 809 598 403
3 1030 929 829 630 424 178
3¼ x ½ 3 T.O.
3¼ x ½ 2 T.O.
3¼ x ½ 0 T.O.
Blower
Fur-
nace
Model
BML-60 100-10T
BML-80 100-10T
Table A-10 Belt Drive Blower Set-Up
BML-90 100-10T
Table A-10 ECM Blower Set-Up (BMLV)
Motor HP Motor FLA ∆T Blower
Model
Furnace
Table A-11 Airow Characteristics - Belt Drive
19
1/2 HP 7.8 70°F 100-10T 7 x ¾
BML 60-90
Page 20
APPENDIX B - WIRING DIAGRAMS
Chimney Vent Furnace Wiring Diagram BML/BMLV
20
Page 21
APPENDIX B - WIRING DIAGRAMS
Direct Vent Furnace Wiring Diagram BML/BMLV
21
Page 22
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-1: 1158-120 Electronic Fan Timer Board (EFT) Detailed Sequence Of Operation (BML)
Mode Action System Response
EFT closes the oil primary control T - T connections. Ignition system and the oil primary control start the furnace. Oil ows as long as the oil primary control senses ame.
Burner motor is energized and heat "fan on" delay timing begins. When timing is complete, the circulator fan is energized at heat speed.
The oil primary control is de-energized, terminating the burner cycle.
Heat "fan off" delay timing begins. Length of delay depends on EFT dipswitch settings. When
timing is complete, the circulator fan is de-energized.
EFT returns to standby mode, (Oil primary control and circulator fan are off, unless continuous fan operation is selected at the thermostat).
HEAT
Thermostat calls for heat. ("W" terminal is energized).
Thermostat ends call for heat.
("W" terminal is de-energized).
COOL
FAN
LIMIT
FAN
Burner fails to light.
Established ame fails.
Thermostat begins call for cool. (G and Y terminals are ener­gized).
Thermostat ends call for cool.
(G and Y terminals are de-ener-
gized).
Thermostat begins call for fan. (G terminal is energized).
Thermostat ends call for fan. (G
terminal is de-energized).
Limit switch string opens.
Limit switch string closes (with existing call for heat).
Limit switch string closes (with­out existing call for heat).
Continuous circulating fan is con­nected.
Oil primary control locks out within lockout timing, (15 seconds).
Burner motor is de-energized. (Even though thermostat is still calling for heat).
If circulator fan has started, it continues through the selected heat “fan off” delay period.
Burner motor is de-energized and oil primary control goes into recycle mode.
If the selected heat “fan off” delay timing is longer than the recycle delay timing, the circulator fan continues to run through the next trial for ignition.
Cooling contactor is energized immediately. Circulator fan is energized at cool speed.
Cooling contactor is de-energized immediately.
Circulator fan turns off immediately.
Circulator fan is energized immediately at cooling speed.
Circulator fan is de-energized immediately.
Oil primary control shuts off burner. Circulator fan is energized immediately at heat speed.
EFT opens the oil primary control T - T connections. Circulating fan runs as long as limit string
stays open. If there is a call for cooling or fan, the circulating fan switches from heating to cooling speed.
EFT begins heat “fan off” delay sequence. Circulating fan turns off after the selected heat “fan off” timing.
EFT re-closes the oil primary control T - T connections.
Oil primary control is energized, initiating burner light off.
Circulator fan turns off when heat “fan off” delay time is complete. Normal operation resumes; EFT control is in standby mode awaiting next thermostat com­mand.
Circulating fan is energized when there is no call for heat, cool, or fan. If fan operation is required by a call for heat, cool, or fan, the EFT switches off the continuous fan speed tap before energizing the other fan speed.
EAC
HUM Humidity control is connected. Humidier connections are energized when the oil burner motor is energized.
Electronic Air Cleaner is con­nected.
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of the cir­culator fan is energized. EAC connections are not energized when the optional continuous fan terminal is energized.
1168-1 Electronic Fan Timer Board (EFT) Detailed Sequence Of Operation (BMLV)
Thermostat Input LEDs (LED1-5, LED8)
Six green LEDs are placed behind their respective thermostat connections (Y1, Y/Y2, G, DH, O, and W) and operate whenever a call is present.
Thermostat calls for heat “W”. The 24VAC input signal is passed to pin 2 of P1 and will drive the K1 relay that provides dedicated
contacts to the T-T input of the Oil Primary Control. Thermostat calls for cool “Y1”. The 24VAC input signal is passed to pin 6 of P1. Thermostat calls for fan “G”. The 24VAC input signal is passed to pin 15 of P1. Thermostat calls for dehumidication “DH”.
The 24VAC input signal is passed to pin 10 of P1. Thermostat calls for reversing valve “O”. The 24VAC input signal is passed to pin 9 of P1.
22
Page 23
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
C.1 Troubleshooting
!
WARNING
Electrical shock hazard. Only a trained, experienced service technician should perform troubleshooting procedure. Failure to do so could result in death or serious injury.
C.2 Preliminary Steps:
Consult Beckett or Riello instruction manuals provided
with oil burner for specic information regarding oil burner
primary control sequence of operation, diagnostics and troubleshooting.
Check diagnostic light for indications of burner condition.
NOTICE
When simulating call for heat at oil primary control, disconnect at least one thermostat lead
wire from T - T terminals to prevent damage to
thermostat. Neglecting this procedure may burn out heat anticipator of standard 24 vac thermostat, or
cause harm to components within micro-electronic
thermostat.
Before checking oil primary control, perform these preliminary checks, repair or replace controls as necessary:
• Check power supply, fuse box or breaker, any service switches, all wiring connections, and burner motor reset button (if equipped).
• Check limit switches to ensure switch contacts are closed.
• Check electrode gap and position.
• Check contacts between oil primary control and electrodes.
• Check oil supply (tank gauge).
Check oil nozzle, oil lter, and oil valves.
• Check piping or tubing to oil tank.
• Check oil pump pressure.
C.3 Check Oil Primary Control
If the trouble does not appear to be in the burner or ignition hardware, check the oil primary control per manufacturer's instructions inlcuded with oil burner.
23
Page 24
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
!
WARNING
Electrical shock hazard. Only a trained, experienced service technician should perform troubleshooting procedure. Failure to do so could result in death or serious injury.
Table C2: System and General Troubleshooting
Problem Possible Cause Remedy
Furnace will not start.
Thermostat not calling for heat
No power to furnace
Thermostat faulty
Oil primary control faulty
Photo Cell wiring shorted or room light leaking into photo cell compartment
Open safety switch
No fuel oil
Check thermostat and adjust. Check thermostat for accuracy; if mercury switch type, it might be off level.
Check furnace switch, main electrical panel furnace fuse or circuit breaker. Look for any other hand operated switch, such as old poorly located furnace switch, which was not removed during furnace replacement.
Remove thermostat wires from oil primary control terminals T-T. Place a jumper across T-T. If furnace starts, replace thermostat, thermostat sub-base
(if equipped), or both.
Check reset button on oil primary control.
Remove thermostat wires from oil primary control terminals T - T. Check for 24V across T -T. If no voltage is present, check for 115V to oil
primary control. If 115V is present, refer to oil primary control documentation provided with oil burner.
Check photo cell (cad cell) wiring for short circuits. Check for room light leaking into cad cell compartment. Repair light leak if necessary.
Check for open limit or auxiliary limit. Check internal wiring connections; loose connectors, etc.
Check fuel oil supply. Check all hand operated fuel oil valves are in open position. Fill oil storage tank if necessary.
Clogged nozzle
Furnace will not start
without rst pushing oil
primary control reset
button.
(Happens on frequent
basis)
Clogged oil lter Replace oil tank lter or in-line lter if used.
Low oil pump pressure
Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective
Defective burner motor
Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Verify erratic pressure readings are not caused by defective fuel oil line.
Check fuel oil lines.
Replace any compression ttings found with high quality ared ttings.
Check for signs of oil leaks. Any oil leak is potential source of air or contaminants.
Check burner motor.
If burner motor is cutting out on over-load, determine why. Replace if neces-
sary.
24
Page 25
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-2: System and General Troubleshooting continued
Problem Possible Cause Remedy
Furnace starts, but cuts out requiring manually re­setting oil protector reset button.
Furnace starts, but cuts out requiring manually re­setting oil protector reset button.
If cad cell is dirty, clean it. Determine why cad cell is getting dirty. If cad cell is poorly aimed, realign it.
Photo Cell (Cad Cell) defective.
No fuel oil.
Clogged nozzle.
Clogged oil lter. Replace oil tank lter or in-line lter if used.
Low oil pump pressure.
Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.
Defective burner motor.
Water or contaminants in oil. Drain fuel oil storage tank; replace fuel oil. (Consult with fuel oil supplier).
NOTE: Photocell should have resistance of 100 KΩ in absence of light; maximum of 1500 Ω in presence of light.
Verify room light is not leaking into the cad cell compartment. (See diag­nostic light section).
Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide.
Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Verify erratic pressure readings are not caused by defective fuel oil line.
Check fuel oil lines. Replace any compression ttings found with high qual­ity ared ttings.
Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants.
Check burner motor.
If burner motor is cutting out on over-load, determine why.
Replace if necessary.
Oil burner sputtering at nozzle
Excessive fuel oil consumption.
Frozen oil line.
Electrodes out of adjustment or defective.
Poor igniter connections or defective igniter.
Fuel oil lter clogged. Replace fuel oil storage tank lter and / or fuel oil in-line lter.
Defective oil pump.
Fuel oil line partially clogged or contains air.
System temperature rise too high.
Poor “fan off” delay timing se­lection, (fan stops too soon).
Fuel oil leak. Check fuel oil line for leaks. Repair or replace if necessary.
Gently warm oil line. Insulate oil line. (Outdoor piping size may require increased diameter).
Check electrode settings.
Check electrodes for dirt build-up or cracks in porcelain.
Check contacts between the igniter and electrodes. If OK, replace the igniter
Check burner motor and / or fuel oil pump coupling. Check oil pump pressure. Replace fuel oil pump if necessary.
Bleed air from oil line. If problem persists, replace oil line.
System temperature rise should not exceed 75°F. Check for clogged air l­ters. Check blower fan for excess dirt build-up or debris. Speed up blower
fan if necessary.
Check “fan off” delay timing setting. Use duct thermometer in supply air
plenum take-off or rst few inches of supply air trunk duct. Fan should shut off at 90° - 100°F. Manipulate dip switch settings to come as close as
possible to this “fan off” temperature.
Stack temperature too high.
Thermostat improperly adjusted or in poor location.
Check stack temperature. Stack temperatures will normally range from
400° to 500°F. Check draft regulator. Draft should be set to -0.02 in. w.c.
Check thermostat heat anticipator setting against measured amperage draw. Increase heat anticipator setting if necessary. If thermostat is being
inuenced by drafts, sunlight, duct work, etc., relocate to suitable location.
25
Page 26
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-2: System and General Troubleshooting continued
Problem Possible Cause Remedy
Too much smoke.
Soot building up on blast tube (end coning).
Furnace will not warm home to desired temperature.
Insufcient combustion air
adjustment at oil burner, or improper draft pressure.
Heat exchanger partially clogged.
Poor alignment between oil
burner blast tube and re pot.
Flame impingement caused by Incorrect nozzle angle.
Defective re-pot Check re-pot. Repair or replace.
Airow blocked or dirty air lter. Clean or replace air lter.
Thermostat adjustments or location.
Insufcient airow.
Defective high limit control.
Adjust oil burner combustion air band and draft regulator to gain highest
practical CO2 or lowest practical O2 content in ue gases.
See Burner Set Up.
Check for soot build-up in heat exchanger ue passages, especially in
outer radiator.
Check alignment. Blast tube should be centered with re pot burner opening. Oil burner head should be ¼ inch back from inside surface of re
pot.
Check nozzle size and angle. (See Appendix A).
Check distance from head to inside surface of re pot.
Check thermostat heat anticipator setting against measured amperage draw. Increase heat anticipator setting if necessary. If thermostat is being
inuenced by drafts, sunlight, duct work, etc., relocate to suitable location.
Check all dampers. Open closed dampers including registers in unused rooms. Check system temperature rise. If temperature rise is too high, speed up blower fan.
Test high limit function of all limit switches. Use duct thermometer to verify accuracy of limit control.
Check for obstructions to airow around limit switch bimetal elements.
Replace control if necessary.
Home does not heat evenly
Supply air temperature too hot.
Supply air temperature too cool.
Supply air temperature
too cool during rst
moments of furnace cycle.
Under-sized nozzle.
Blower fan motor stopping intermittently on overload.
Burner motor stopping intermittently on overload.
Improper distribution of heat. This is not likely to be a furnace problem. Balance duct system.
Airow blocked or dirty air lter. Clean or replace air lter.
Insufcient airow.
Excess airow. Check system temperature rise. Slow down blower fan if necessary.
Excessive duct losses.
Fan control "fan on" setting too low.
Excessive duct losses.
Check nozzle. If problem is not caused by air ow problems, use larger
nozzle, if permitted by rating plate.
Check blower fan motor amperage draw. Check motor ventilation ports, clean if necessary. Replace motor if necessary.
Check burner motor. Replace if necessary.
Check all dampers. Open closed dampers including registers in unused rooms. Check system temperature rise. If temperature rise is too high, speed up blower fan.
Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork if necessary.
Increase "fan on” dipswitch settings on EFT if control has this option.
Register air deectors may help.
Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork if necessary.
26
Page 27
APPENDIX D - HOMEOWNER’S REFERENCE TABLE
Model No.
Serial No.
Date Installed
Contractor
Contact
Address
Postal Code
Telephone No.
After Hours No.
Fuel Supplier
Fuel Oil Supplier
Contact
Telephone No.
After Hours No.
27
Page 28
PARTS LISTING
Parts Listing: Chimney Vent Models BML80(B2,BRF2) and BMLV80(B2,BRF2)
Ref. No. Description Part No.
1 Left Side Panel Assembly 29631AD
2 Right Side Panel Assembly 29630AD 3 Rear Panel 29638AD
4 Blower Division Assembly 29676 5 Base Panel Assembly 28459
6 Inner Front Panel 30154 7 Blower Access Panel 27367AD
Front Door Panel 30157AD
8
9 Top Front Panel 26017AD
10 Heat Exchanger Assembly 550001635
11 Firepot Bracket Assembly 27068 12 Replacement Combustion Chamber 27000WP 13 Bafe 30152
14
15 Pouch Gasket 2080175
16
17 Flue Pipe Collar 27476 18 Air Filter - 20 x 20 x 1 (Permanent) 2180032 19 Control Panel 30010 20 Control Panel Cover 29654
21
22 Wire Harness Fan Timer Board Chimney Vent 29364
23 Wire Harness Transformer and Supply 29751
24
25 Transformer, 120/24V, 40a 240005330 26 Limit Control 60T11 (L260°F) BOF (Black Oxide Finish) 30153 27 Draft Regulator 27494
28
Logo Bezel 28479 Logo Label 28563
Clean-out Gasket Retainer (2 per unit) 29161 Clean-out Gasket (2 per unit) 29163
Oil Burner Mounting Plate Assembly
Oil Burner Mounting Plate Sight Glass Cover Plate Sight Glass Gasket (2 per unit) Sight Glass
Wire Harness Blower Motor Direct Drive 29690 Wire Harness Blower Motor Belt Drive 29691
Fan Timer Control 1158-120 UTEC
Fan Timer Control 1168-1 ECM UTEC 240007048
Beckett AF Oil Burner Assembly, Beckett AF76BNHS 30067
Burner Motor 1/7 HP 3450 RPM PSC 29689
Oil Pump, Clean-Cut A2EA6520 29688 Solid State Ignitor 29522
Oil Primary Combustion Control 7505P1515 240008818 Flame Retention Head 1050002
Low Fire Kit 29880 Low Firing Rate Bafe 25521101
Oil Burner, Riello 40F3 29568
109007674 109007675 29850 29870 29876
29388
28
Page 29
PARTS LISTING
Parts Listing: Chimney Vent Models BML80(B2,BRF2) and BMLV80(B2,BRF2)
Ref. No. Description Part No.
Blower Assembly, Complete, Direct Drive, 1/2 HP, 4-Speed 29668
Blower Assembly, Complete, Direct Drive, 1/2 HP, ECM 109007377
Blower Housing and Wheel, 100-10T Direct Drive 30626
Blower Motor, ½ HP, 4-Speed 102000131
Blower Motor ½ HP ECM Programmed 109007380
Motor Mounting Band – TR6884B 17811
Motor Mount Arms – 10-10 DD Blower (3 per unit) 26251
Motor Run Capacitor, 10 mfd @ 370 VAC 27743
Capacitor Strap 27760
29
30 Insulation/Limit Disc Retainer 20602
31
32 Filter Side Rail (2 per unit) 27370
33 Filter Blower Division Rail 27369
35 Wire Harness ECM Motor Control (from Fan Timer) 240007276
36 Wire Harness ECM Motor Control (from Motor) 240007272
* Wire Harness ECM Motor Power 240007273
37 Flue Pipe 3002356
* Flue Pipe Insulator 29713
* Flue Pipe Gasket 21994
* Blocked Vent Safety Switch Kit Complete 30690
* Blocked Vent Safety Switch - Replacement Switch Only 30660
* Flue Pipe for Blocked Vent Safety Switch 30655
* Door Handle (2 per unit) 28673
Blower Base ( 2 per unit) 109005826
Grommet, Blower Feet (4 per Unit) 26415
Blower Assembly Complete, Belt Drive, 1/2 HP, One Speed 109006191
Blower Housing and Wheel, 100-10T Belt Drive 30627
Blower Motor, 1/2 HP, One Speed 102000154
Motor Pulley, 3-1/4" x 1/2" 2240001
Blower Pulley, 7" x 3/4" 2240008
Belt, 4L380 2240017
Blower Base (2 per unit) 109005826
Grommet, Blower Feet (4 per unit) 26415
Radiator Clean-out Pipe Cover (2 per unit) 240007841
Radiator Clean-out Cap Gasket (2 per unit) 240006333
29
Page 30
PARTS LISTING
Parts Listing: Direct Vent Models BML80(BB2U2,BRBU2) and BMLV80(BB2U2,BRBU2)
Ref. No. Description Part No.
All parts are the same as listed on previous pages for chimney vent Model BML-80B and BMLV-
15 Pouch Gasket (Second gasket required for Direct Vent) 2080175
22
28
34 Appliance Vent Adapter 5" x 3" 240006904
* Pressure Switch -0.28" WC 30700
* 10 Second Bypass Timer GPS00C9X10 (Use with Beckett AFII) 30699
* 25 Second Bypass Timer GPS00C9X25 (Use with Riello 40BF3) 240005182
Wire Harness Fan Timer Board Direct Vent 30745
Beckett Oil Burner AFII 85 30069
Burner Motor 1/7 HP 3450 RPM PSC 28907
Beckett Clean-cut Oil Pump A2EA6520 29688
Solid State Ignitor 28558
Oil Primary Combustion Control 7505P1530
Air Tube Combination FBX80HGXS 28561
Flame Retention Head (FB3) 28533
Riello Oil Burner 40BF3 30427
80B except where noted below.
30
Page 31
Model BML and BMLV Diagram
Direct Drive Model Shown
37
31
Page 32
ECR International
2210 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
Loading...