C.3 Check Oil Primary Control ...................................................................................................23
Appendix D - Homeowner’s Reference Table .......................................................................... 27
Parts Listing: Chimney Vent Models BML80(B2,BRF2) and BMLV80(B2,BRF2) ....................... 28
Parts Listing: Direct Vent Models BML80(BB2U2,BRBU2) and BMLV80(BB2U2,BRBU2) .......... 30
Parts Diagram BML and BMLV ................................................................................................ 31
Check our website frequently for updates: www.ecrinternational.com
Information and specications outlined in this manual in effect at the
time of printing of this manual. Manufacturer reserves the right to
discontinue, change specications or system design at any time without
notice and without incurring any obligation, whatsoever.
3
P/N 30149, Rev. G [12/15/2016]
Page 4
1. General
Furnace installation shall be completed by qualied agency.
See glossary for additional information.
WARNING
!
Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
WARNING
!
Fire, burn, asphyxiation hazard. Do not use
gasoline, crank case oil, or any oil containing
gasoline. Failure to follow these instructions could
result in death or serious injury.
2. Safety Symbols
Become familiar with symbols identifying
potential hazards.
3. Introduction Models BML And BMLV
Models BML and BMLV are oil red forced air up-ow
furnaces with an output capacity range of 59,000 btu/hr to
89,000 btu/hr.
• BML models are equipped with 1/2 HP PSC 4 speed
blower motor.
• BMLV models are equipped with 1/2 HP ECM variable
speed blower motor.
Furnace models are either factory equipped for chimney
venting or factory equipped for direct venting.
Chimney vent models and direct vent models are not
eld convertible. Direct vent installation instructions are
included with the direct vent models.
Installation shall conform to requirements of
authority having jurisdiction or in absence of such
requirements:
• United States - National Electrical Code, NFPA31,
Standard for the Installation of Oil-Burning Equipment.
This is the safety alert symbol. Symbol alerts you to
potential personal injury hazards. Obey all safety messages
following this symbol to avoid possible injury or death.
!
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal
injury.
Models are CSA listed, (NRTL/C) for use with No. 1
(Stove) and No. 2 (Furnace) Oil.
Refer to tables in Appendix A for performance data.
4. Heat Loss
Maximum hourly heat loss for each heated space shall be
calculated in accordance with the procedures described in
the manuals of:
• Canada - The Heating, Refrigeration and Air
Conditioning Institute of Canada (HRAI), or by other
means prescribed, or approved by the local authority
having jurisdiction.
• United States - Manual J. titled, "Load Calculation"
published by the Air Conditioning Contractors of
America, describes a suitable procedure for calculating
maximum hourly heat loss.
4
P/N 30149, Rev. G [12/15/2016]
Page 5
5. Locating the Unit - [See Table 1]
• Locate furnace so ue connection to chimney is short,
direct and consists of as few elbows as possible.
• Centralize furnace location with respect to supply and
return air ductwork. Central location minimizes trunk
duct sizing.
• All models may be installed on combustible oors.
6. Furnace Used In Conjunction With Air
Conditioning
• Install furnace in parallel with or upstream from
evaporator coil to avoid condensation in heat
exchanger.
• When installed in parallel, prevent chilled air from
entering furnace by use of dampers or air controlling.
• Manually operated dampers must have a control to
prevent operation of either system unless dampers
are in full heat or full cool position.
• Air heated by the furnace shall not pass through
evaporator coil unless coil is specically approved for
such service.
Table 1: Minimum Installation Clearances
Clearance to Combustibles
Location
Top1" (26 mm)
Bottom0"
S/A Plenum1" (26 mm)
Rear6"** (152 mm)
Sides1"* (26 mm)
Front 1"** (26 mm)
4" (102 mm) measured horizontally
Flue Pipe
8" (204 mm) measured vertically or
EnclosureCloset
*18 in. (458 mm) Required from 1 side for access to rear
** 24 in. (610 mm) Service Clearance
BML and BMLV
Lowboy
or below ue pipe
above ue pipe
• Check and adjust blower speed to compensate for
pressure drop caused by evaporator coil.
• Maintain required clearance between bottom of coil
drain pan and top of heat exchanger as specied by
coil manufacturer.
5
P/N 30149, Rev. G [12/15/2016]
Page 6
7. Combustion Air
Comply with CSA B139 (Canada) or NFPA 31 (U.S.)
standards for the Installation of Oil Burning Equipment
and applicable provisions of local building codes to provide
combustion and ventilation air.
WARNING
!
Asphyxiation hazard. Chimney vented versions of furnace
must be connected to ue having sufcient draft at all
times. Failure to follow these instructions could result in
death or serious injury.
8. Chimney Venting
• Flue pipe should be as short as possible with
horizontal pipes sloping upward toward the chimney
at a rate of one-quarter inch per foot.
• Flue pipe should not be smaller in cross sectional
area than ue collar on the furnace.
• Flue pipe should connect to chimney so the ue pipe
extends into, and terminates ush with the inside
surface of chimney liner. Seal the joint between pipe
and lining.
• Chimney outlet should be at least two feet above
highest point of peaked roof.
• All unused chimney openings should be closed.
• Chimneys must conform to local, provincial or state
codes, or in the absence of local regulations, to the
requirements of the National Building Code.
NOTICE
This furnace is approved for use with Type L vent or
equivalent. Maximum vent temperature for Type L
vent is 575°F (300C).
Manufacturer recommends over re draft of -0.02 in. w.c.
See gure 2.
Flue pipe must not pass through any oor or ceiling,
may pass through a wall where suitable re protection
provisions have been installed.
• Refer to CAN/CSA B-139 for rules governing the
installation of oil burning equipment.
• United States, refer to NFPA 31 for regulations
governing the installation of oil burning equipment.
See appendix A for burner set-up.
Figure 2 - Check Over-Fire Draft
Over-re draft access port.
6
P/N 30149, Rev. G [12/15/2016]
Page 7
9. Barometric Damper Control
Barometric damper control, also known as draft regulator,
is used on conventional chimney venting only. Control
automatically maintains constant negative pressure.
Ensures proper pressures are not exceeded. If chimney
does not develop sufcient draft, draft control does not
function properly.
• Install draft regulator in same room or enclosure as
furnace. Draft regulator should not interfere with
combustion air supplied to the burner.
• Locate control near furnace ue outlet.
• Install per instructions supplied with regulator.
• Set over re draft, measured at oil burner mounting
plate over-re draft access port, to -0.02 in. w.c. See
Figure 2 page 6.
10. Optional Side Wall Venting
Certain BML and BMLV furnace models are manufactured
as sidewall vented units. Refer to Direct Venting Instructions,
P/N 240006979 included with Vent Kit for details.
Sidewall Venting (Direct Venting) requires use of specic oil
burners; Beckett AFII, or Riello 40BF.
Refer to Appendix A, Tables A2, and A4.
11a. Fan Timer Board And Limit Control (BML)
See Figure 3, page 15.
Electronic Fan Timer integrates control of burner and
circulator fan operations. Control is central wiring point for
most of furnace electrical components.
• United Technologies 1158-120 (BML) has an
adjustable fan on time set by selecting dipswitch
combination displayed in Chart 1. Fan on delay can
be set at 30, 60, 90 or 120 seconds. Provides a
delay between burner ignition and blower start-up
to eliminate excessive ow of cold air when blower
comes on.
• United Technologies 1158-120 (BML) has an
adjustable fan off time of 2, 3, 4 or 6 minutes as
displayed in Chart 1. Fan off delay time starts when
burner motor is de-energized at end of call for heat.
Blower shutdown is delayed to remove any residual
heat from heat exchanger.
• Electronic fan timer board works in conjunction with
snap disc limit controls, performing a safety function,
and breaks power to oil burner primary control,
shutting off burner if furnace over-heats.
• Limit control is thermally operated and automatically
resets. Limit control is factory installed, pre-set and
is not adjustable.
• If limit control opens with United Technologies 1158-
120 (BML) electronic fan control, circulating fan will
energize. When limit closes, fan off timer begins.
At the end of fan off time cycle burner is energized,
initiating normal burner cycle.
Chart 1- United Technologies 1158-120 (BML)
Dip Switch PositionBlower Delay Times
1234On SecondsOff Minutes
OffOff30
OnOff60
OffOn90
OnOn120
OffOff2
OnOff3
OffOn4
OnOn6
11b. Fan Timer Board And Limit Control (BMLV)
[See Figure 4, page 15]
United Technologies 1168-1 ECM (BMLV) tap board has an
adjustable fan on/off delay and airow settings that must
be adjusted in accordance with furnace input rating (nozzle
size). Refer to Table A-9, page 17 for ECM blower set-up.
12. Electrical Connections
• Furnace is listed by Canadian Standards Association
under NRTL (North American) Standard.
• All eld wiring shall conform to CAN/CSA C22.1
Canadian Electrical Code, Part 1, and by local codes,
where they prevail.
• United States, wiring shall conform to National Fire
Protection Association NFPA-70, National Electrical
Code, and with local codes and regulations.
• Wire furnace to separate dedicated circuit in main
electrical panel.
• Suitably located circuit breaker can be used as
service switch, separate service switch is advisable.
• Service switch is necessary if circuit breaker is close
to the furnace, or furnace is located between circuit
breaker and entry to furnace room.
• Clearly mark service switch. Install in accessible area
between furnace and furnace room entry. Locate so
as to reduce possibility it can be mistaken as light
switch or similar device.
• Power requirement for BML and BMLV models is: 115
VAC, 1 Ø, 60 Hz., 12A.
• Accessory equipment such as electronic air cleaners
and humidiers may be included on furnace circuit.
• Accessories requiring 115 VAC power sources such
as electronic air cleaners and humidier transformers
may be powered from electronic fan timer board
where provisions have been made for connections,
but should have their own controls.
• Do not use direct drive motor connections as a power
source, there is risk of damaging accessories.
7
P/N 30149, Rev. G [12/15/2016]
Page 8
• Thermostat wiring connections are shown in wiring
diagrams in Appendix B. Some micro-electronic
thermostats require additional controls and wiring.
Refer to thermostat manufacturer's instructions.
• Locate thermostat approximately 5 feet above oor,
on inside wall, and where thermostat is exposed to
average room temperatures. Avoid locations where
thermostat is exposed to cold drafts, heat from
nearby lamps and appliances, exposure to sunlight,
heat from inside wall stacks, etc.
• Adjust thermostat heat anticipator to amperage
draw of heating control circuit as measured at "R"
and "W" terminals of thermostat. Do not measure
current with thermostat connected to the circuit.
Measure amperage by connecting ammeter between
two wires which connect to thermostat "R" and "W"
terminals.
13. Humidier
• Humidier is optional accessory available through
most heating supplies outlets.
• Protect furnace heat exchanger from water or water
droplets from humidier.
• Do not use direct drive motor connections as source
of power for 115 VAC humidiers and humidier
transformers.
16. Oil Burner Nozzles
BML and BMLV are certied for multiple ring rates, ranging
from 59,000 to 89,000 Btu/h output. Furnace may be red
at ideal rate for wide range of structures by manipulating
oil burner nozzle, ame retention head, and temperature
rise. Refer to Table A-1 thru A-4, and furnace rating plate
to determine proper combinations.
17. Oil Burner Adjustment
• Adjust burner air supply to maintain fuel to air ratio
to obtain ideal combustion conditions.
• Lack of air causes "soft" and "sooty" ames, resulting
in soot build-up throughout heat exchanger passages.
• Excess combustion air causes bright roaring re
and high stack temperatures resulting in poor fuel
efciency.
• BML and BMLV operate most efciently with No. 1
smoke spot on Bacharach Scale. Dust will eventually
build up on air moving components of oil burner
assembly resulting in decreased air supply with
potential soot build up in ue gas passageways
of heat exchanger. Soot behaves as insulator and
impairs good heat transfer. Stack temperature
increases, and efciency decreases. To avoid this
problem, adjust the air supply to provide no more
than trace smoke spot on Bacharach Scale.
• See Venting Instructions included in Vent Kits for set-
up details for sidewall vented furnaces.
14. Piping Installation
• Install fuel system in accordance with requirements
of CAN/CSA B-139, and local regulations.
• United States installation shall conform to NFPA No.
31 and local codes and authorities.
• Use only approved fuel oil tanks, piping, ttings and
oil lter.
• Install oil lter as close to burner as possible.
• Refer to instructions and illustrations in oil burner and
oil pump instructions shipped with the furnace.
15. Oil Filter
Install oil lter between fuel oil storage tank and oil burner.
When using oil burner nozzle smaller than 0.65 U.S.
Gallons Per Hour, install additional 7 to 10 micron lter as
close as possible to oil burner.
NOTICE
Set up sidewall vented models to deliver zero (0)
smoke.
NOTICE
Before operating furnace check burner alignment
with combustion chamber. End cone of air tube must
be centred to accommodating ring of combustion
chamber. Adjust as necessary.
18. Burner Electrodes
Correct positioning of electrode tips with respect to each
other, fuel oil nozzle, and burners is essential for smooth
light ups and proper operation.
Refer to oil burner instructions provided with furnace
and Appendix A Section A.2 in this manual for electrode
specications.
8
P/N 30149, Rev. G [12/15/2016]
Page 9
NOTICE
Do not tamper with furnace controls they are
sensitive. If problems persist, call your service
contractor.
19. Burner Primary (Safety) Control
Furnace is equipped with primary combustion control, also
referred to as burner relay or burner protector relay, which
uses a cad cell located in burner housing, to monitor and
control combustion.
Dust or combustion residuals can build up on lens of cad
cell impairing its response to ame. Check cad cell for
cleanliness and proper alignment if primary control frequently shuts down combustion.
20. Combustion Chamber
Furnace is equipped with cerafelt combustion chamber, held
in place by a retaining bracket.
Check the alignment of the combustion chamber
and oil burner before ring. It is possible for the
combustion chamber to shift if subjected to rough
handling during transit.
Inspect combustion chamber for damage or carbon build
up whenever oil burner is removed for repairs or routine
maintenance.
WARNING
!
Fire, burn, asphyxiation hazard. Do not start the
burner unless blower access door is secured in
place. Failure to follow these instructions could
result in death or serious injury.
• Some older duct systems were not designed to
provide static pressure. They typically feature special
reducing ttings at each branch run and lack block
ends on the trunk ducts. These systems may require
modication to provide some resistance to the airow
to prevent over-amping of direct drive blower motor.
Selecting a lower blower speed may correct this
problem.
• Direct drive blower speeds are adjusted by changing
"hot" wires to motor winding connections. Refer to
wiring diagrams in Appendix B or wiring diagram
label afxed to furnace.
• Do not move neutral wire (normally white
wire) to adjust blower speed.
• Single blower speed for both heating and cooling
modes may be used. Use a "piggy-back connector"
accommodating both wires on a single motor tap.
• It is also acceptable to connect selected motor speed
with a pigtail joined to both heating and cooling
speed wires with a wire nut.
• Safety precaution against accidental disconnection of
wires by vibration, secure wire nut and wires with few
wraps of electricians tape.
• Do not connect power leads between motor
speeds. Always connect neutral wire to motor's
designated neutral terminal.
• If joining blower speed wiring is done in furnace
junction box, tape off both ends of unused wire.
• Do not use blower speed wires as source of
power to accessories as electronic air cleaners
and humidier transformers. Unused motor
taps auto-generate sufciently high voltages to
damage accessory equipment.
21a. CIRCULATING AIR BLOWER (BML/BMLV)
• BML furnace models may be equipped with either
direct drive or belt drive blower systems.
• BMLV furnace models are equipped with direct drive
blower systems.
• BML models are equipped with PSC motors.
• BMLV models are equipped with electronically
commutated motors (ECM).
Direct Drive Blower Systems
• Direct drive blower speed adjustments are not
normally required in properly sized extended plenum
duct systems. Motor RPM and air CFM delivery will
vary automatically to accommodate conditions within
usual range of external static pressures typical of
residential duct systems.
• Under-sized duct systems may require higher blower
speed to obtain system temperature rise.
Belt Drive Blower Systems
WARNING
!
Improper installation could result in death or serious
injury. Belt drive components operate at high speeds
and may snag loose clothing resulting in injury or
death. Have a trained service professional preform
the following instructions. Failure to follow these
instructions could result in death or serious injury.
Belt drive blower systems can be modied for speed and
air delivery by adjusting variable speed motor pulley and
changing blower pulley.
• Adjust variable speed motor pulley by loosening 5/32
allen set screw in outer sheave. Turn outer sheave
clockwise to increase blower speed, counter clockwise
to reduce speed.
9
P/N 30149, Rev. G [12/15/2016]
Page 10
• Verify setscrew is tightened at one of the at spots,
failure to do so will convert the variable speed pulley
to a xed speed pulley by ruining the threads.
• Modify blower speed by changing the blower pulley.
Smaller blower pulley will cause the blower to turn
faster. Large pulley reduces blower speed.
!
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before opening blower
access door. Failure to do so could result in death or
serious injury.
• Large increases in the blower speed may increase
power requirements.
• Check amperage draw of the blower motor after
making changes. If amperage draw is greater than
the value listed on the motor rating plate, replace
with motor of higher horsepower.
• Deection of 3/4 of an inch to 1 inch fan belt tension
is necessary. Less deection places a strain on the
blower bearings and increases start up amperage
draw.
• More deection allows excess slippage and causes
premature motor pulley wear.
• Automotive belt dressings are not recommended.
• Bar soap will work as belt dressing to reduce belt
squeaks, etc. If using soap apply to the sides of belt
only.
If operating belt drive blower at speeds above 1100
RPM, replace sintered bronze blower bearings with roller
bearings.
21b. Circulating Air Blower (BMLV)
BMLV furnace models are equipped with electronically
commutated motors (ECM).
Setting Blower Speed and “ON” and “OFF” Timings
Blower speed and on/off time delays are handled by ECM
motor programming and are set via dipswitches per Table
A-9 on page 17. Heating airow rate is SW1 and on/off
delay is SW4, both are set according to ring rate. Cooling
airow rate is SW2 and if used is set according to installed
cooling capacity. SW3 can be used to adjust airow rate by
(+) or (-) 15%. Features of this ECM variable speed motor
are that it will deliver a constant airow within a wide range
of external static pressures, and also includes:
• Soft Start: ECM will slowly ramp up to required
operating speed. In heating cycle allows heat
exchanger to reach operating temperature before set
heat speed, minimizes noise and increases comfort.
• Soft Stop: At end of heating cycle, ECM will slowly
ramp down. Allows increased energy efciency and
reduced noise levels.
• Dehumidication: Dehumidication feature is
programmed into the variable speed motor. At start
of each cooling cycle, variable speed motor will run
at 82% of rated airow for 7.5 minutes. After 7.5
minutes has elapsed, motor will increase to 100% of
rated airow. Used to provide dehumidication and
improve system efciency.
10
• Continuous Fan Operation: When thermostat
continuous fan (G) switch is on without call for
heating or cooling, indoor fan is immediately
energized up to 50% of cooling speed. Allows
continuous circulation of air between calls for heating
or cooling. If call for heat (W) or cool (Y) occurs
during continuous fan, blower remains energized.
P/N 30149, Rev. G [12/15/2016]
Page 11
22. Maintenance And Service
Routine Maintenance By Home Owner
• Arrange for professional servicing of furnace by the
service or installation contractor annually.
• Homeowner is to maintain air lter or lters. A dirty
lter can cause furnace to over-heat, fail to maintain
indoor temperature during cold weather, increase fuel
consumption and cause component failure.
• Inspect, clean or replace lter monthly.
• Furnace is supplied with semi-permanent type lter.
If lter is damaged, replace with lters of same size
and type.
• During monthly lter inspection, inspect general
condition of furnace. Watch for signs of oil leaks in
vicinity of oil burner, soot forming on any external
part of furnace, soot forming around joints in vent
pipe, etc. If any of these conditions are present,
please advise your service or installation contractor.
Annual Service By Contractor
NOTICE
Combustion chamber (repot) is fragile. Use care
when inspecting and cleaning this area
• If cleaning is necessary, shut off oil supply, shut off
power to the furnace and remove burner.
• Use stiff brush with wire handle, brush off scale and
soot from inside drum and ue pipe.
• Clean radiator, remove clean-out cap screws.
Remove caps carefully to avoid tearing gaskets.
• Wire brush can be used to loosen dirt and debris
on the inside surfaces of radiator. Clean out all
accumulated dirt, soot and debris with a wire handled
brush and an industrial vacuum cleaner.
• Before replacing clean-out caps, inspect gaskets. If
gaskets are broken, remove remnants and replace
with new gaskets.
• Blower motor is factory oiled and permanently
sealed. Do not lubricate. Excess oil causes
premature electric motor failure.
• Change oil burner nozzle and oil lter annually.
• Clean and inspect venting system for signs of
deterioration. Replace pitted or perforated vent pipe
and ttings.
• Inspect heat exchanger periodically and clean if
necessary.
!
WARNING
Electrical shock hazard. Turn OFF electrical
power supply at service panel before service or
maintenance Failure to do so could result in death or
serious injury.
• Barometric damper should open and close freely.
• Check electrical connections to ensure tight
connections. Safety controls such as the high limit
controls should be tested for functionality.
• Check fan control to ensure fan on and off delay
function continues to start and stop blower fan at
optimal settings.
11
P/N 30149, Rev. G [12/15/2016]
Page 12
WARNING
!
Fire, burn, explosion, asphyxiation hazard.
• Do not start burner when excess oil has
accumulated, furnace is full of vapor, or
combustion chamber is very hot.
• Do not burn garbage or paper in furnace.
• Do not leave paper or rags around furnace.
Failure to follow these instructions could result in
death or serious injury.
23. OPERATING INSTRUCTIONS (BML)
Before Lighting
1.
Open all supply and return air registers and grilles.
2.
Open all valves in oil pipes.
3.
Turn on electric power supply
To Light Unit
1.
Set thermostat above room temperature to call for
heat. Burner should start. It may be necessary to
press RESET button on primary combustion control
relay.
2.
There is a fan on time delay before circulating fan
is energized. United Technologies 1158-120 has
adjustable fan on time set by selecting dipswitch
combination displayed in Chart 1. Fan on delay can be
set at 30, 60, 90 or 120 seconds.
3.
Set the thermostat below room temperature. Oil burner
stops.
4.
Air circulation blower continues to operate until time off
setting selected on electronic fan timer control times
out. United Technologies 1158-120 has adjustable
fan off time of
adjustments may be altered if air at room registers is
high upon blower start up or shutdown.
5.
Restore thermostat setting to comfortable temperature.
2, 3, 4 or 6 minutes.
Fan timer control
24. Operating Instructions (BMLV)
Before Lighting
1.
Open all supply and return air registers and grilles.
2.
Open all valves in oil pipes.
3.
Turn on electric power supply.
To Light Unit
1.
Set thermostat above room temperature to call for
heat. Burner should start. It may be necessary to
press RESET button on primary combustion control
relay.
2.
There is a fan on time delay before circulating fan is
energized. United Technologies 1168-1 has adjustable
fan on/off time delay programmed into ECM motor,
and is set by selecting SW4 DIP switch combination
displayed in Table A-9 page 17. Adjust Fan on/off
delay according to input (nozzle size).
3.
Set thermostat below room temperature. Oil burner
stops.
4.
Air circulation blower continues to operate until blower
off delay setting programmed into ECM motor times
out.
5.
Restore thermostat setting to comfortable temperature.
NOTICE
If furnace is to be shut down for extended period of
time, close oil supply valve to burner.
To Shut Down Unit
1.
Set thermostat to lowest possible setting.
2.
Set manual switch (if installed) in electrical power
supply line to "OFF".
12
P/N 30149, Rev. G [12/15/2016]
Page 13
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Check out and adjustments
BML and BMLV furnaces may be used with following oil burners.
Beckett AF, and Riello 40F oil burners are for applications using indoor air for combustion only.
Sidewall venting applications utilizing outdoor air for combustion, use Beckett AFII or Riello 40BF (Balanced Flue) oil burners
only.
Table A-1 Beckett AF Oil Burner Set-Up
Beckett AF Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
BML-60B2
2
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
59,000AF76BNHS0.50 / 80°A100 psig0.50 usgphF33- ⅜ in.
BMLV-60B2²
BML-80B2
76,000AF76BNHS0.65 / 80°A100 psig0.65 usgphF33- ⅜ in.
BMLV-80B2
BML-90B2
85,000AF76BNHS0.75 / 80°A100 psig0.75 usgphF33- ⅜ in.
BMLV-90B2
1
Head is shielded by ceramic insulator.
2
Low Firing Rate Bafe required when using 0.50-gallon nozzle.
Table A-2 Beckett AFII Oil Burner Set-Up
Beckett AFII Series Oil Burners
(For use with sidewall vented units with outdoor combustion air,
or chimney vented units with indoor air for combustion)
(For use with sidewall vented units using outdoor combustion air)
Furnace Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
BML-60BRBU2
61,00040BF30.50 / 60°W105 psig0.50 usgph1.0
BMLV-60BRBU2
BML-80BRBU2
78,00040BF30.60 / 60°W120 psig0.65 usgph1.5
BMLV-80BRBU2
BML-90BRBU2
89,00040BF30.65 / 60°W135 psig0.75 usgph2.0
BMLV-90BRBU2
Pump
Pressure
Flow Rate
Turbulator
Setting
NOTE: Air gate setting may vary for sidewall vented units where air gate must be adjusted to achieve zero smoke.
A.1 OIL BURNER AIR ADJUSTMENT
Consult oil burner instructions provided in furnace
documents envelope for specic information concerning
burner adjustments, operation and troubleshooting.
Beckett AF Burner (Chimney Vent)
Adjust air shutter by loosening locking screws. Moving air
shutter, and if necessary, bulk air band.
Beckett AFII Burner (Direct Vent)
Adjust burner air supply. Loosen locking screw located on
black dial to right of burner. Turn black dial clockwise to
increase combustion air and counter-clockwise to decrease
combustion air. Re-tighten locking screw after obtaining
proper setting.
Riello 40F3 Burner (Chimney Vent)
Combustion air is adjusted by removing burner cover.
Loosen screws that secure air adjustment plate. Move
adjusting plate to either increase or decrease combustion
air. When proper air setting is achieved, retighten xing
screws.
Riello 40BF3 Burner (Direct Vent)
Combustion air can be adjusted with burner cover on.
Remove plastic cover on top right hand side of burner
cover. With phillips head screw driver, turn adjustment
screw clockwise to increase combustion air or counter-
clockwise to decrease combustion air. When combustion air
is set, re-insert plastic cover.
14
P/N 30149, Rev. G [12/15/2016]
Page 15
APPENDIX A - CHECK OUT AND ADJUSTMENTS
A.2 Burner Electrodes
Adjustment of electrode tips with respect to each other,
nozzle, burner head is very important to ensure smooth
Install oil pressure gauge to pressure port on oil pump.
(Refer to oil pump specication sheet included with
burner instructions).
3.
Restore electrical power to furnace.
4.
Start furnace and bleed all air from fuel oil lines.
5.
Close purge valve and re the unit.
6.
Allow furnace to warm up to normal operating
temperatures. During this time, set pump pressure in
accordance with data provided in Appendix A, Table A-1
thru A-4.
7.
Chimney vented units - Drill 1/4" test port in
venting between furnace ue outlet and draft regulator
(barometric damper) to take smoke readings.
8.
Sidewall vented units - Do not drill. Use test port
in the supplied appliance connector to take smoke
readings.
9.
When furnace has reached "steady state" (after approximately 10 minutes). Set combustion air damper
to get TRACE of smoke for chimney vented units and
ZERO smoke for sidewall vented units.
10.
Check system temperature rise. Temperature rise is the
difference between return air temperature measured at
a point near return air inlet, and supply air temperature
measured near furnace outlet.
System temperature rise is listed on furnace rating
plate. If temperature rise is too high, airow must
be increased. If temperature rise is too low, slow fan
down.
11.
After air adjustments have been completed, recheck
the over re draft at test port on burner mounting plate
shown in Figure 2. Over re draft should be adjusted to
-0.02 inches w.c.
12.
Turn burner off. Observe duct thermometer in supply
air stream, note temperature blower fan stops. Fan
adjustments can be made by moving dipswitch settings
on timer control board for fan off delay.
13.
Check operation of limit switch.
A. Shut off power to furnace.
B. Temporarily remove neutral wire from PSC blower
motor or remove 5 pin power connector from ECM
blower motor. Isolate AC line voltage pins on 5 pin
power connector with electrical tape to prevent
electric shock hazard.
C. Restore electrical power to furnace.
D. Set thermostat above room temperature.
E. After three or four minutes of burner operation,
limit control should turn burner off.
F. When limit function test is complete, shut off
electrical power to furnace, replace neutral wire to
PSC blower motor or 5 pin power connector to ECM
blower motor. Restore power.
G. Blower fan will start up immediately. Once
temperature has dropped and limit control has
reset, fan will operate until fan off time is reached.
H. Oil burner will resume operation and continue until
thermostat is satised.
I. Restore thermostat setting to comfortable
temperature.
14.
Set heat anticipator adjustment in thermostat (if so
equipped), by removing "R" or "W" wire to thermostat.
Read amperage draw between the two wires. Failure
to remove one of the wires from thermostat while
performing this test could burn out heat anticipator.
Set heat anticipator to amperage measured.
15.
Run furnace through at least three full cycles before
leaving the installation, to ensure all controls are
operating properly.
16.
Check all joints in any positive pressure venting system
for leaks before leaving the installation site
A.4 Special Instructions For Units Equipped With
Riello Burners
Riello specications are listed in Tables A-1 and A-4.
Consult Riello Installation Instructions supplied with Burner
for specic information concerning burner adjustments,
operation, and trouble-shooting.
15
P/N 30149, Rev. G [12/15/2016]
Page 16
APPENDIX A - CHECK OUT AND ADJUSTMENTS
A.5 Final Check Out
Verify all safety devices and electrical components have
been set for normal operation.
Verify all electrical connections are tight and wiring is
secure.
Verify homeowner is informed and understands:
Where circuit breaker or fuse is located in main electrical
panel.
Where furnace switch is located, and switch "on" and "off"
positions if not obvious.
FIGURE 3: UNITED TECHNOLOGIES 1158-120 FAN
TIMER BOARD (BML)
Where oil shut-off valve from oil storage tank is located.
Thermostat operation, and other related accessories.
How to operate manual reset button on primary control,
and when not to push the reset button.
How and where to visually inspect venting system for leaks
or other problems.
How to inspect, clean and replace air lter, and other
homeowner maintenance procedures.
Who to call for emergency service and routine annual
service.
FIGURE 4: UNITED TECHNOLOGIES 1168-1 ECM
TAP BOARD (BMLV)
Table A-7 Direct Drive Blower Characteristics PSC Motor
Model
Furnace
100-10T DD1/2 HP7.170°F
BML
60 – 90
1/2 HP ECM7.770°F470-635625 - 1500600 - 1200
BlowerMotor HP Motor FLA∆T
Model
Furnace
DD
100-10T
BMLV
60 – 90
TIP
Formulas will assist with design of duct-work and determination of air ow delivery.
CFM = Bonnet Output / (1.085 x System Temperature Rise (∆T)
System Temperature Rise (∆T) = Bonnet Output / (1.085 x CFM)
Table A-8 Direct Drive Blower Characteristics ECM Motor
17
P/N 30149, Rev. G [12/15/2016]
Page 18
APPENDIX A - CHECK OUT AND ADJUSTMENTS
(TON)
AC Size
POS.
SW2 - COOL
12
DIP Switch Position
INPUT
OFFOFFA3
ONOFFB2.5
INPUT
POS.
ONOND1.5
OFFONC2
SW4 - DELAY
CFM
OFFOFFA0.65
DIP Switch Position
12USGPH
ONOFFB0.85
OFFONC0.75
ONOND0.50
POS.
SW1 - HEAT
Dip Switch Adjustment Chart
For Input 0.50 USGPH TO 0.85 USGPH
12USGPH
DIP Switch Position
OFFOFFA0.65
ONOFFB0.85
Table A-9 ECM Blower Set-Up (BMLV)
OFFONC0.75
ONOND0.50
POS.
SW3 - ADJUST
12
ONOFFB (+)15%
OFFOFFA 0%
DIP Switch Position
18
ONOND N/A
OFFONC (-)15%
NOTE:
SW1 (HEAT) AND SW4 (DELAY) DIP SWITCHES MUST BOTH BE ADJUSTED ACCORDING TO INPUT (NOZZLE SIZE).
SW2 (COOL): 1 TON is approximately equal to 400 CFM
SW3 (ADJUST): (Heating Mode) Increase OR decrease temperature rise respectively
(Cooling Mode) Increase OR decrease CFM respectively
P/N 30149, Rev. G [12/15/2016]
Page 19
CFM
Range
TonsMotor
APPENDIX A - CHECK OUT AND ADJUSTMENTS
CFM
BeltMotor
Pulley
Blower Set-UpCooling Capacity
BeltMotor
7 x ¾4L3801/2 HP3¼ x ½7 x ¾4L3801/2 HP1.5-3.51/2 HP600-1400
0.20 in. w.c.0.50 in. w.c.
Pulley
MotorBlowerMotorBlower
7 x ¾4L3801/2 HP3¼ x ½7 x ¾4L3801/2 HP1.5-3.51/2 HP600-1400
7 x ¾4L3801/2 HP3¼ x ½7 x ¾4L3801/2 HP1.5-3.51/2 HP600-1400
0.200.250.300.400.500.60
External Static Pressure – Inches w.c.
Turns Out
Motor Pulley
Pulley
Blower
01410134112721145996820
1127712111145970790598
2115410771002809598403
31030929829630424178
3¼ x ½ 3 T.O.
3¼ x ½ 2 T.O.
3¼ x ½ 0 T.O.
Blower
Fur-
nace
Model
BML-60100-10T
BML-80100-10T
Table A-10 Belt Drive Blower Set-Up
BML-90100-10T
Table A-10 ECM Blower Set-Up (BMLV)
Motor HP Motor FLA∆TBlower
Model
Furnace
Table A-11 Airow Characteristics - Belt Drive
19
1/2 HP7.870°F100-10T7 x ¾
BML 60-90
P/N 30149, Rev. G [12/15/2016]
Page 20
APPENDIX B - WIRING DIAGRAMS
Chimney Vent Furnace Wiring Diagram BML/BMLV
20
P/N 30149, Rev. G [12/15/2016]
Page 21
APPENDIX B - WIRING DIAGRAMS
Direct Vent Furnace Wiring Diagram BML/BMLV
21
P/N 30149, Rev. G [12/15/2016]
Page 22
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-1: 1158-120 Electronic Fan Timer Board (EFT) Detailed Sequence Of Operation (BML)
ModeActionSystem Response
EFT closes the oil primary control T - T connections.
Ignition system and the oil primary control start the furnace. Oil ows as long as the oil
primary control senses ame.
Burner motor is energized and heat "fan on" delay timing begins. When timing is complete, the
circulator fan is energized at heat speed.
The oil primary control is de-energized, terminating the burner cycle.
Heat "fan off" delay timing begins. Length of delay depends on EFT dipswitch settings. When
timing is complete, the circulator fan is de-energized.
EFT returns to standby mode, (Oil primary control and circulator fan are off, unless continuous
fan operation is selected at the thermostat).
HEAT
Thermostat calls for heat. ("W"
terminal is energized).
Thermostat ends call for heat.
("W" terminal is de-energized).
COOL
FAN
LIMIT
FAN
Burner fails to light.
Established ame fails.
Thermostat begins call for cool.
(G and Y terminals are energized).
Thermostat ends call for cool.
(G and Y terminals are de-ener-
gized).
Thermostat begins call for fan. (G
terminal is energized).
Thermostat ends call for fan. (G
terminal is de-energized).
Limit switch string opens.
Limit switch string closes (with
existing call for heat).
Limit switch string closes (without existing call for heat).
Continuous circulating fan is connected.
Oil primary control locks out within lockout timing, (15 seconds).
Burner motor is de-energized. (Even though thermostat is still calling for heat).
If circulator fan has started, it continues through the selected heat “fan off” delay period.
Burner motor is de-energized and oil primary control goes into recycle mode.
If the selected heat “fan off” delay timing is longer than the recycle delay timing, the circulator
fan continues to run through the next trial for ignition.
Cooling contactor is energized immediately.
Circulator fan is energized at cool speed.
Cooling contactor is de-energized immediately.
Circulator fan turns off immediately.
Circulator fan is energized immediately at cooling speed.
Circulator fan is de-energized immediately.
Oil primary control shuts off burner.
Circulator fan is energized immediately at heat speed.
EFT opens the oil primary control T - T connections. Circulating fan runs as long as limit string
stays open.
If there is a call for cooling or fan, the circulating fan switches from heating to cooling speed.
EFT begins heat “fan off” delay sequence.
Circulating fan turns off after the selected heat “fan off” timing.
EFT re-closes the oil primary control T - T connections.
Oil primary control is energized, initiating burner light off.
Circulator fan turns off when heat “fan off” delay time is complete.
Normal operation resumes; EFT control is in standby mode awaiting next thermostat command.
Circulating fan is energized when there is no call for heat, cool, or fan.
If fan operation is required by a call for heat, cool, or fan, the EFT switches off the continuous
fan speed tap before energizing the other fan speed.
EAC
HUMHumidity control is connected.Humidier connections are energized when the oil burner motor is energized.
Electronic Air Cleaner is connected.
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of the circulator fan is energized. EAC connections are not energized when the optional continuous fan
terminal is energized.
1168-1 Electronic Fan Timer Board (EFT) Detailed Sequence Of Operation (BMLV)
Thermostat Input LEDs (LED1-5, LED8)
Six green LEDs are placed behind their respective thermostat connections (Y1, Y/Y2, G, DH, O, and W) and operate whenever a call is
present.
Thermostat calls for heat “W”. The 24VAC input signal is passed to pin 2 of P1 and will drive the K1 relay that provides dedicated
contacts to the T-T input of the Oil Primary Control. Thermostat calls for cool “Y1”. The 24VAC input signal is passed to pin 6 of P1.
Thermostat calls for fan “G”. The 24VAC input signal is passed to pin 15 of P1. Thermostat calls for dehumidication “DH”.
The 24VAC input signal is passed to pin 10 of P1. Thermostat calls for reversing valve “O”. The 24VAC input signal is passed to
pin 9 of P1.
22
P/N 30149, Rev. G [12/15/2016]
Page 23
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
C.1 Troubleshooting
!
WARNING
Electrical shock hazard. Only a trained, experienced
service technician should perform troubleshooting
procedure. Failure to do so could result in death or
serious injury.
C.2 Preliminary Steps:
Consult Beckett or Riello instruction manuals provided
with oil burner for specic information regarding oil burner
primary control sequence of operation, diagnostics and
troubleshooting.
Check diagnostic light for indications of burner condition.
NOTICE
When simulating call for heat at oil primary
control, disconnect at least one thermostat lead
wire from T - T terminals to prevent damage to
thermostat. Neglecting this procedure may burn out
heat anticipator of standard 24 vac thermostat, or
cause harm to components within micro-electronic
thermostat.
Before checking oil primary control, perform these
preliminary checks, repair or replace controls as necessary:
• Check power supply, fuse box or breaker, any service
switches, all wiring connections, and burner motor
reset button (if equipped).
• Check limit switches to ensure switch contacts are
closed.
• Check electrode gap and position.
• Check contacts between oil primary control and
electrodes.
• Check oil supply (tank gauge).
• Check oil nozzle, oil lter, and oil valves.
• Check piping or tubing to oil tank.
• Check oil pump pressure.
C.3 Check Oil Primary Control
If the trouble does not appear to be in the burner or ignition
hardware, check the oil primary control per manufacturer's
instructions inlcuded with oil burner.
23
P/N 30149, Rev. G [12/15/2016]
Page 24
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
!
WARNING
Electrical shock hazard. Only a trained, experienced
service technician should perform troubleshooting
procedure. Failure to do so could result in death or
serious injury.
Table C2: System and General Troubleshooting
ProblemPossible CauseRemedy
Furnace will not start.
Thermostat not calling for heat
No power to furnace
Thermostat faulty
Oil primary control faulty
Photo Cell wiring shorted or
room light leaking into photo
cell compartment
Open safety switch
No fuel oil
Check thermostat and adjust.
Check thermostat for accuracy; if mercury switch type, it might be off level.
Check furnace switch, main electrical panel furnace fuse or circuit breaker.
Look for any other hand operated switch, such as old poorly located furnace
switch, which was not removed during furnace replacement.
Remove thermostat wires from oil primary control terminals T-T. Place a
jumper across T-T. If furnace starts, replace thermostat, thermostat sub-base
(if equipped), or both.
Check reset button on oil primary control.
Remove thermostat wires from oil primary control terminals T - T.
Check for 24V across T -T. If no voltage is present, check for 115V to oil
primary control.
If 115V is present, refer to oil primary control documentation provided with
oil burner.
Check photo cell (cad cell) wiring for short circuits.
Check for room light leaking into cad cell compartment. Repair light leak if
necessary.
Check for open limit or auxiliary limit.
Check internal wiring connections; loose connectors, etc.
Check fuel oil supply.
Check all hand operated fuel oil valves are in open position. Fill oil storage
tank if necessary.
Clogged nozzle
Furnace will not start
without rst pushing oil
primary control reset
button.
(Happens on frequent
basis)
Clogged oil lterReplace oil tank lter or in-line lter if used.
Low oil pump pressure
Air getting into fuel oil lines, or
fuel oil line dirty, clogged, or in
some manner defective
Defective burner motor
Replace nozzle with high quality replacement.
Use rating plate or Tables in Appendix A as a guide.
Connect pressure gauge to oil pump.
Adjust pump pressure, or replace oil pump if necessary.
Verify erratic pressure readings are not caused by defective fuel oil line.
Check fuel oil lines.
Replace any compression ttings found with high quality ared ttings.
Check for signs of oil leaks. Any oil leak is potential source of air or
contaminants.
Check burner motor.
If burner motor is cutting out on over-load, determine why. Replace if neces-
sary.
24
P/N 30149, Rev. G [12/15/2016]
Page 25
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-2: System and General Troubleshooting continued
ProblemPossible CauseRemedy
Furnace starts, but cuts
out requiring manually resetting oil protector reset
button.
Furnace starts, but cuts
out requiring manually resetting oil protector reset
button.
If cad cell is dirty, clean it. Determine why cad cell is getting dirty. If cad
cell is poorly aimed, realign it.
Photo Cell (Cad Cell) defective.
No fuel oil.
Clogged nozzle.
Clogged oil lter.Replace oil tank lter or in-line lter if used.
Low oil pump pressure.
Air getting into fuel oil lines, or
fuel oil line dirty, clogged, or in
some manner defective.
Defective burner motor.
Water or contaminants in oil.Drain fuel oil storage tank; replace fuel oil. (Consult with fuel oil supplier).
NOTE: Photocell should have resistance of 100 KΩ in absence of light;
maximum of 1500 Ω in presence of light.
Verify room light is not leaking into the cad cell compartment. (See diagnostic light section).
Check fuel oil supply.
Check that all hand operated fuel oil valves are in the open position.
Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate or Tables in
Appendix A as a guide.
Connect pressure gauge to oil pump.
Adjust pump pressure, or replace oil pump if necessary.
Verify erratic pressure readings are not caused by defective fuel oil line.
Check fuel oil lines. Replace any compression ttings found with high quality ared ttings.
Check for any signs of oil leaks. Any oil leak is a potential source of air or
contaminants.
Check burner motor.
If burner motor is cutting out on over-load, determine why.
Replace if necessary.
Oil burner sputtering at
nozzle
Excessive fuel oil
consumption.
Frozen oil line.
Electrodes out of adjustment or
defective.
Poor igniter connections or
defective igniter.
Fuel oil lter clogged.Replace fuel oil storage tank lter and / or fuel oil in-line lter.
Defective oil pump.
Fuel oil line partially clogged or
contains air.
System temperature rise too
high.
Poor “fan off” delay timing selection, (fan stops too soon).
Fuel oil leak.Check fuel oil line for leaks. Repair or replace if necessary.
Check electrodes for dirt build-up or cracks in porcelain.
Check contacts between the igniter and electrodes. If OK, replace the
igniter
Check burner motor and / or fuel oil pump coupling.
Check oil pump pressure. Replace fuel oil pump if necessary.
Bleed air from oil line.
If problem persists, replace oil line.
System temperature rise should not exceed 75°F. Check for clogged air lters. Check blower fan for excess dirt build-up or debris. Speed up blower
fan if necessary.
Check “fan off” delay timing setting. Use duct thermometer in supply air
plenum take-off or rst few inches of supply air trunk duct. Fan should
shut off at 90° - 100°F. Manipulate dip switch settings to come as close as
possible to this “fan off” temperature.
Stack temperature too high.
Thermostat improperly adjusted
or in poor location.
Check stack temperature. Stack temperatures will normally range from
400° to 500°F. Check draft regulator. Draft should be set to -0.02 in. w.c.
Check thermostat heat anticipator setting against measured amperage
draw. Increase heat anticipator setting if necessary. If thermostat is being
inuenced by drafts, sunlight, duct work, etc., relocate to suitable location.
25
P/N 30149, Rev. G [12/15/2016]
Page 26
APPENDIX C - SEQUENCE OF OPERATION AND TROUBLESHOOTING
Table C-2: System and General Troubleshooting continued
ProblemPossible CauseRemedy
Too much smoke.
Soot building up on blast
tube (end coning).
Furnace will not warm
home to desired
temperature.
Insufcient combustion air
adjustment at oil burner, or
improper draft pressure.
Heat exchanger partially
clogged.
Poor alignment between oil
burner blast tube and re pot.
Flame impingement caused by
Incorrect nozzle angle.
Defective re-potCheck re-pot. Repair or replace.
Airow blocked or dirty air lter.Clean or replace air lter.
Thermostat adjustments or
location.
Insufcient airow.
Defective high limit control.
Adjust oil burner combustion air band and draft regulator to gain highest
practical CO2 or lowest practical O2 content in ue gases.
See Burner Set Up.
Check for soot build-up in heat exchanger ue passages, especially in
outer radiator.
Check alignment. Blast tube should be centered with re pot burner
opening. Oil burner head should be ¼ inch back from inside surface of re
pot.
Check nozzle size and angle. (See Appendix A).
Check distance from head to inside surface of re pot.
Check thermostat heat anticipator setting against measured amperage
draw. Increase heat anticipator setting if necessary. If thermostat is being
inuenced by drafts, sunlight, duct work, etc., relocate to suitable location.
Check all dampers. Open closed dampers including registers in unused
rooms.
Check system temperature rise. If temperature rise is too high, speed up
blower fan.
Test high limit function of all limit switches. Use duct thermometer to verify
accuracy of limit control.
Check for obstructions to airow around limit switch bimetal elements.
Replace control if necessary.
Home does not heat
evenly
Supply air temperature
too hot.
Supply air temperature
too cool.
Supply air temperature
too cool during rst
moments of furnace cycle.
Under-sized nozzle.
Blower fan motor stopping
intermittently on overload.
Burner motor stopping
intermittently on overload.
Improper distribution of heat.This is not likely to be a furnace problem. Balance duct system.
Airow blocked or dirty air lter.Clean or replace air lter.
Insufcient airow.
Excess airow.Check system temperature rise. Slow down blower fan if necessary.
Excessive duct losses.
Fan control "fan on" setting too
low.
Excessive duct losses.
Check nozzle. If problem is not caused by air ow problems, use larger
nozzle, if permitted by rating plate.
Check blower fan motor amperage draw.
Check motor ventilation ports, clean if necessary. Replace motor if
necessary.
Check burner motor. Replace if necessary.
Check all dampers. Open closed dampers including registers in unused
rooms.
Check system temperature rise. If temperature rise is too high, speed up
blower fan.
Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork
if necessary.
Increase "fan on” dipswitch settings on EFT if control has this option.
Register air deectors may help.
Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork
if necessary.
26
P/N 30149, Rev. G [12/15/2016]
Page 27
APPENDIX D - HOMEOWNER’S REFERENCE TABLE
Model No.
Serial No.
Date Installed
Contractor
Contact
Address
Postal Code
Telephone No.
After Hours No.
Fuel Supplier
Fuel Oil Supplier
Contact
Telephone No.
After Hours No.
27
P/N 30149, Rev. G [12/15/2016]
Page 28
PARTS LISTING
Parts Listing: Chimney Vent Models BML80(B2,BRF2) and BMLV80(B2,BRF2)
Ref. No.DescriptionPart No.
1Left Side Panel Assembly29631AD
2Right Side Panel Assembly29630AD
3Rear Panel29638AD