OJ Electronics WLM2, WLTD, WLTP, WLCT, WLTA Installation Manual

p. 1
Installation Manual
W
LM2 WLTA WLTD WLTP WLCT
57641 01/08 (LJE)
p. 2
WLM Underfloor Heating Controller ......Page 10
Wiring diagram .......................................Page 10
Description ........................................... Page 13
Product programme .................................Page 13
Technical data ........................................ Page 13
Environment ..........................................Page 14
Recycling of obsolete appliances .................. Page 14
Configuring of the total system .................... Page 14
Installation .....................................Page 15
Electrical installation ................................. Page 15
Boiler demand ........................................ Page 15
Pump output ......................................... Page 16
Free relay function (X-OUTPUT) .................... Page 16
Thermal actuators ................................... Page 17
External switch for night setback .................. Page 18
Room sensors - Bus connection ................... Page 18
Room sensors - Wireless setup .................... Page 19
Setting up which Room sensor/controller
should work with wich thermal actuator .......... Page 20
Supply water temperature sensor
and mixing value ..................................... Page 21
Creating a Network ..........................Page 22
Using cooling function .............................. Page 23
Domestic hot water control ......................... Page 23
Radiator control ...................................... Page 24
2 step heating ........................................Page 24
Commissioning mode ...............................Page 25
Replacing equipment ................................ Page 25
Guidelines and special features .................... Page 26
Factory default settings ............................. Page 27
Error indication ....................................... Page 28
Add On Module ...............................Page 31
Configuring the Total System ....................... Page 31
Outdoor Compensation Module ...........Page 32
Introduction ........................................... Page 32
Mounting .............................................. Page 32
Bus connection - Outdoor
compensation module .............................. Page 32
Interconnection of WLM2 product .................Page 32
Waterline Wireless System .................Page 33
Product Programme ................................. Page 33
Connection of Master and Receiver ...............Page 33
Position ............................................... Page 33
Master ................................................. Page 33
To set up the system ................................Page 33
Type WLCT ....................................Page 34
Introduction ........................................... Page 34
Getting started ....................................... Page 34
Daily Use of the room sensor ....................... Page 36
Programming 4-Event Clock Time
and Temperature ..................................... Page 37
Advanced Settings and Read-out ................. Page 38
Reset to factory Settings - room controllers ...... Page 41
Waterline Room sensors ....................Page 42
Introduction ........................................... Page 42
Set-up ................................................. Page 43
Setting of Room Temperature ...................... Page 44
Setting of Room sensor Operating Mode ......... Page 44
Limit Sensor - WLTD and WLCT ...................Page 45
Quickguides ...................................................................................................... Page 3
Quick Installation Guide ............................................................................................................ Page 3
Setting up the System ..............................................................................................................Page 5
Wireless system only ...............................................................................................................Page 5
Testing the system ..................................................................................................................Page 6
Troubleshooting .....................................................................................................................Page 7
QUICKGUIDES
INSTRUCTIONS
CONTENT INSTALLATION MANUAL
B A -- +
Blue Red Brown Yellow
p. 3
We recommend the preparation of an area schedule chart on the backside of the user manual before commencing the installation. This identifies piping circuits to specific rooms and enables the correct allocation of a channel number in the WLM system.
Mount the Master and AO modules in the correct way on the wall in accordance with electrical regulations.
Connect the AO-module, using the special cable included in the box.
Mount the Room sensors/controllers in the rooms, and set the channel switches to correspond with the number of the actuator controlling that room. For hardwired Room sensors/controllers now connect the 2-wire bus to the master or the AO module, maintaining continuity of positive + and negative - connections. For wireless Room sensors/controllers now insert the batteries.
If the Room sensors/controllers are of wireless type connect the receiver (WLRC-19) using the special cable enclosed with the receiver.
NB: For Room sensors with floor temperature limiting sensors, please refer to separate instructions included with Room sensors/controllers.
QUICK INSTALLATION GUIDE
1
2
4
3
QUICKGUIDES
QUICKGUIDES
p. 4
Connect the actuators to the channel outputs on the master in accordance with the pipe manifold layout (please refer to the area schedule). Actuator no. 1 on the manifold to output no. 1 on the master. Actuator no. 2 on the manifold to output no. 2 on the master. etc.
Outdoor module WLOC-19 (FS Master only): Install on north facing wall, away from direct sunlight. Connect into 2-wire Room sensor bus or direct to master, maintaining continuity of positive + and negative - connections.
Connect 230/240Vac power, UFH circulating pump and boiler in accordance with electrical regulations. (For FS masters, connect the mixing valve and water flow temperature sensors)
6
7
5
Button learning mode
p. 5
SETTING UP THE SYSTEM
Turn on the power supply.
Set the clock on any WLCT room controller: a. If the hour digit is not flashing, press the small pinhole button with the clock symbol, otherwise.. b. Adjust the hours and press OK. c. Adjust the minutes and press OK. d. Adjust the day number (1 = Monday) and press OK.
In addition to its own room, the WLCT room controller can be used to set the operating times and temperatures of other Room sensors (channels). To achieve this, do the following on the WLCT room controller: a. Enter the “InFo” menu by pressing the up and down button simultaneously for 4 seconds. b. Find the “ArEA” menu with the down button and press OK. c. The display shows “CH 1” (channel 1).
- Press OK button.
- Select “On” if this channel (Room sensor) should be controlled by the WLCT room controller, or “OFF” if not.
- Now press OK button to get to the next channel (CH 2) and repeat this step until all required channels have been selected “On”. d. After all channels are set up, find the “ESC” menu entry and press OK.
NB: If different times and temperatures are required for other channels (Room sensors) within the system, more than one WLCT room controller can
be used. Care must be taken to ensure that the action of selecting a channel “On” is not made on more than one
WLCT room controller.
Switch on DIP-3 to activate learn mode:
All wireless Room sensors now have to be initialized:
- Analogue Room sensor (TA,TD,TM,TP) by pressing the internal init button (Button learning mode) until a beep is heard.
- Digital Room sensor (CT) by pressing the pin hole button with the clock symbol until a beep is heard.
Switch off DIP-3 to de-activate learn mode:
1.
2.
3.
WIRELESS SYSTEM ONLY:
QUICKGUIDES
1.
2.
3.
p. 6
TESTING THE SYSTEM:
1. Switch on DIP-3 to activate learn mode: - power light will blink quickly
2. Each red channel light on the master should now be lit if a Room sensor is present on that
channel.
3. Switch off DIP-3 to de-activate learn mode again – power light stops blinking.
4. Turn all adjustable temperature settings on the Room sensors to minimum.
5. Switch on DIP-1 on the master to activate install mode (Install mode will be active for 2 hours
- Pumps, boiler, mixing valve and actuators should now be off)
6. Turn the temperature setting on the adjustable Room sensor in room 1 to maximum. The red
channel 1 light should be lit and the actuator on output nr. 1 will be activated, and will open after 1-3 minutes, depending on the type of actuator. Important: If the Room sensor is of a wireless type a delay of up to 5 minutes may occur before the channel light becomes illuminated .
7. Check that the UHF pump is running and the mixing valve (only FS master) opens .
8. Repeat step 6 on all rooms.
9. Boiler test function:
Switch on DIP-2. This closes the boiler start relay contacts for 1 minute.
10. To end all tests:
- Switch off DIP-1 to deactivate install mode. Switch off DIP-2 to deactivate boiler test.
- Set all temperature knobs to default positions Room sensors (TA,TD,TM,TP) to zero (center position). Room controllers (CT) recommended to 21˚C.
- Set all override switches on TM and TD Room sensors to automatic position (clock symbol).
11. The system is now operating automatically.
NB: Other important settings can be found in the User manual on the pages shown bellow:
Off temperature (frost protection) page 7 Minimum & Maximum floor temperatures page 7 Maximum supply water temperature page 8 Weather compensation page 8
p. 7
Problem Possible cause & solution
Make sure the power light is fast blinking. If not then put DIP-3 to ON position.
2-wire bus may be incorrectly connected. Voltage at each Room sensor should not be lower than 4.0V (check for + & - continuity and short circuits)
For wireless Room sensors, please check that the batteries have been inserted correctly.
Has the init button been pressed ?
For wireless Room sensor check that the WLRC-19 (receiver) is correctly connected.
For channel 9-14, is the AO module correctly connected to the Master.
Make sure the Room sensor in that room is set to the correct channel number.
The channel selector on the Room sensor may be slightly out of position, try rotating and the set it again.
Channel light is not coming on.
(When in Learn mode)
(When in Install mode, when the Room sensor is activated (set to maximum))
Master is not in install mode – after 2 hours the master automatically de-activates install mode – please reset the DIP-1.
Make sure the Room sensor in that room is set to the correct channel number. (two Room sensors could be crossed over)
The actuator on the manifold has not opened after 3 minutes.
Check the red channel light is illuminated.
The actuator for the room is not connected to the correct output on the master.
Bad electrical connection between actuator and terminals.
Actuator may be faulty or manually locked.
UFH Pump not starting in install mode Bad electrical connection between pump and terminals.
Install mode is not activated.
Pump may be faulty.
TROUBLESHOOTING:
QUICKGUIDES
p. 8
Output relay for Main pump, Cooling, High limit valve or other attached device.
Incorrect connection to device (output relay has volt free contacts, see master wiring diagram for correct connection)
Bad electrical connection between terminals and attached device.
Install mode is not activated.
Attached device may be faulty.
Boiler does not fi re
(LED lit)
Incorrect connection to device (output relay has volt free contacts, see master wiring diagram for correct connection)
Bad electrical connection between terminals and attached device.
Install mode is not activated.
Attached device may be faulty.
Timing sequence delay is activated
FS master only - mixing valve not open above 20%
No heat demand from Room sensors.
Master is in cooling mode.
(LED not lit)
Mixing valve does not operate correctly
(When in install mode)
Incorrect connection, see master wiring diagram for correct connection.
Valve/actuator assembly is incorrect.
Actuator is faulty.
Check what happens if sensor and/or outdoor module is missing.
(Valve cycles between open and closed in normal operating mode)
Valve may be oversized.
Supply Limit sensor may be subject to heat migration.
Upstream water temperature is excessively high. (these problems may be corrected by changing PI settings – please refer to the main manual)
p. 9
QUICKGUIDES
Room is too hot
(After running for at least 48 hours)
This could be caused by draughts within the wall cavities.
The Room sensor is placed in a position that does not represent the general temperature in the room.
If the room is controlled by a CT Room sensor, check that the time and temperatures are set correctly.
If the Room sensor has got an override switch (TM or TD), the switch may be set in the “day” position.
For rooms with fl oor sensors, the minimum fl oor limit setting could be increasing the room temperature above the desired setting.
Solar gain or extraneous heat source.
Room is too cold.
(After running for at least 48 hours)
The Room sensor is placed in a position that does not represent the general temperature in the room. E.g. mounted on external wall or near an extraneous heat source.
If the room is controlled by a CT Room sensor, check that the time and temperatures are set correctly.
If the Room sensor has got an override switch (TM or TD), the switch may be set in the “off” or “night” position.
For rooms with fl oor sensors, the maximum fl oor limit setting could be preventing the room reaching the desired temperature.
Insuffi cient heating capacity of the system.
Bad insulation creating large heat loss.
INSTRUCTIONS
WLM Underfloor Heating Controller
BR965A30b
p. 10
p. 11
p. 12
p. 13
Type WLM underfloor heating controller is suitable for connecting multiple room Room sensors and electric actuators (thermoheads) for an underfloor or radiator based heating system.
Room sensors requiring a 230 V or 24V live & neutral must NOT be connected. Only OJ Room sensors type WLxx that are prepared for 2 wire or wireless communication can be used.
Description
Product Programme
Technical Data
Product Thermo Heads Type
Master for 8 zones 230V AC WLM2-1BA (basic system) Master for 8 zones with display 230V AC WLM2-1FS (full system) Master for 8 zones 24V WLM2-3BA (basic system) Master for 8 zones with display 24V WLM2-3FS (full system) Add-on module for 6 zones 230V AC WLM2-1AO Add-on module for 6 zones 24V WLM2-3AO
TECHNICAL DATA
Power Supply ............................................................................................. 230V AC +10/-15%, 50 HZ
Max load pumps and Thermal actuators .......................................................................................
10A
Boiler relay ........................................................................................................Volt free signal. Max 4A
Main pump (free relay) .....................................................................................Volt free signal. Max 4A
Secondary pump .............................................................................................230V AC, 50Hz Max. 4A
Thermal actuators:
WLM2-1BA ........................................................................................................................ 8 x 230V
WLM2-1FS ........................................................................................................................ 8 x 230V
Max. 2A per output. Max. 5A in total
WLM2-3BA .......................................................................................................................... 8 x 24V
WLM2-3FS ...........................................................................................................................8 x 24V
Max. 10VA per output. Max. 35VA in total
Optional External Switch (Timer) for night setback ......................................... Open terminals for NSB
Closed terminals for day operation
Room sensor Bus 2 wire low voltage . . . . . . . . . . . . . . . . . . . . . . . . . . bus signal from Room sensors
Additional data for WLM2-1FS & WLM2-3FS (not applicable to the basic version)
Application sensor and Limit sensor ............................... NTC type ETF-1899A for water temperature
Control signal for mixing valve actuator .................................................................................0-10V DC
Power supply for mixing valve actuator ....................................................................24V AC. Max 6VA
WLM underfloor heating controller
p. 14
Please help us to protect the environment by disposing of the packaging in accordance with the national regulations for waste processing.
Environment
Appliances with this label must not be disposed off with the general waste. They must be collected separately and disposed off according to local regulations.
Recycling of obsolete appliances
Each master module is capable of controlling 8 heating zones, each of which may use one or more loops of piping, with one or more thermal actuators. These zones are referred to later in this instruction as channels 1 to 8. If you wish to control more than 8 zones, it is necessary to install ADD ON (AO) modules, each of which can provide another 6 outputs. The first AO module then controls channels 9 to 14,
Configuring the Total System
Green: Power supply connected Red: Night setback active Red flashing: Indicates error
Main boiler (primary) pump is running (if installed)
Secondary UFH pump is running
Boiler enable signal is activated
Zone 1 to 8 indicating heating is on
1..8
Type WLM-1BA and WLM-3BA
Type WLM-1FS and WLM-3FS
Loading...
+ 32 hidden pages