OJ Electronics PTH, PTH-3202 Series Manual

INSTRUCTIONS
Type PTH
57433B 03/14 (OSH)
English
PTH is a series of electronic pressure transmit­ters designed primarily to measure total and differential air pressures in ventilation systems. The resulting measurements are used for monitoring, control and regulation purposes via a regulator, PLC or monitoring system. The re­sulting measurements are used for monitoring, control and regulation purposes via a regulator, PLC or monitoring system.
Typical applications include:
- The maintenance/control of constant pressure at a given position within the duct system.
- The maintenance/control of desired under­pressure within the duct system.
- The measurement of pressure differentials across filters to determine optimum filter replacement time.
- Flow determination via differential pressure measurements across a standard aperture.
PRODUCT PROGRAMME
Type Product
PTH-3202 Pressure transmitter, 0-2500 Pa, 1 channel, IP54
FUNCTION
PTH is a pressure transmitter for comfort ventilation systems. It provides an active current or voltage signal proportional to the measured air pressure. PTH consists of semiconduc­tor elements. There is no air throughput and the unit is thus protected against dust in the ventilation system. The pressure element is temperature compensated to provide accurate pressure measurement throughout the specified temperature range. The required measuring range of the pres­sure transmitter is set with DIP switches. The output signal can be changed from voltage [V] to current [mA] by setting a jumper. A DIP switch allows two different damping times to be selected so that pressure fluctuations within the ventilation system are attenuated in the trans­mitter output signal. A green LED indicates that supply voltage has been connected correctly. If the actual pressure is outside the selected measuring range, the green LED flashes.
CE MARKING
OJ Electronics A/S hereby declares that the product is manufactured in accordance with Council Directive 92/31/EEC on electromagne­tic compatibility (and subsequent amendments) and Council Directive 73/23/EEC on electrical equipment designed for use within certain voltage limits.
Applied standards
EN 61000-6-2 and EN 61000-6-3 Electromagnetic compatibility (EMC)
TECHNICAL DATA
Full scale pressure range PTH-3202 / 0-2500 Pa
Pressure ranges ................ PTH-3202 (see fig. 5)
Supply voltage ............24 V AC ±15%, 50/60 Hz
13.5-28 V DC
Own consumption (-20/+40°C) ...... max. 0,5 VA
Output signal (selectable) ................. 0-10 V DC,
2-10 V DC 4-20 mA, 0-20 mA
Accuracy output signal ........................................
1.5 %xMV+0.3 %xSR+2.5 Pa
(MV = measured value / SR = set measuring range)
Dampening (selectable) ................. 0.4 s or 10 s
Max. pressure .......................................... 20 kPa
Ambient temperature ......................... -20/+40 °C
(constant operation)
-30/+50 °C (transient)
Dimensions .............75 x 36 x 91 mm (see fig. 1)
Cable dimensions ................. 4 x max. 1.5 mm2
Pressure connector ........................ 2 x ø6.2 mm
Enclosure ..................................................... IP54
MOUNTING
PTH must be securely mounted on a level surfa­ce using screws. PTH is insensitive to mounting orientation. However, in order to maintain the specified enclosure, tubes should be attached to both tube connectors if the connectors point upwards. The enclosure is equipped with screw holes, see fig. 1. Pressure is connected by means of tubes. The higher pressure must be connected to the “+ connector” and the lower pressure to the “- connector”. If the tubes are unintentional­ly exchanged, or the pressure is outside the measuring range, the green LED flashes. See table 1. The pressure tubes must be as short as possible and must be secured in position to prevent vibration. To obtain the best possible results, pressure must be measured where there is least risk of turbulence, i.e. in the centre of the ventilation duct and at a suitable distance from bends and branches. See fig. 2. The enclosure is opened without the use of tools by pressing the snap lock at the side of the connectors. The transmitter cable may be up to 50 m in length and must be connected as shown in fig. 3. The transmitter cable must be kept separate from mains-carrying cables as voltage signals from these may affect transmit­ter function.
SETTINGS
Pressure range is set by turning the dial, SW2 (see fig. 3) PTH types in this product series, pressure range can be set to 8 different intervals, ranging from
-50/+50 Pa to 0-2500 Pa (see fig. 5). If the dial is set to values other than the speci­fied positions (0-7), the pressure transmitter will interpret the setting as position 7 corresponding to the highest pressure range. If the pressure transmitter is inadvertently set to a pressure range lower than the pressure encountered in the connectors, the green LED will light constantly (see table 1).
The screw terminals of the pressure transmitter can provide a 0/2 - 10 V output signal and/or a 0/4 - 20 mA output signal (see fig. 4). The 0-10 V output signal is provided by terminal 2 with DIP 1 of SW1 in position “Off”. The 2-10 V output signal is provided by terminal 2 with DIP 1 of SW1 in position “On”. The 0-20 mA output signal is provided by termi­nal 4 with DIP 1 of SW1 in position “Off”. The 4-20 mA output signal is provided by terminal 4 with DIP 1 of SW1 in position “On” (see figs 4 & 7).
Output signal damping time can be set to 0.4 s or 10 s using DIP2 of SW1 (see figs 3 & 8). The transmitter measures the pressure several times within the set time and the output signal consists of the average of these measurements. This allows any pressure fluctuations within the ventilation system to be dampened in the transmitter output signal.
ZEROING
The transmitter can be zeroed after it has been mounted and the power supply con­nected. Before zeroing the transmitter, it is
important to ensure that the pressure on the + and - connectors is equal (e.g. by stopping the ventilation system). If the yellow LED is constantly lit, the transmitter is measuring a differential pressure of more than 50 Pa. This may be caused by unintended pressure within the system (draughts or compressed tubing). It is recommended that tubes be removed from the + and - connectors during zeroing. Zeroing is activated by pressing the integrated zero-set switch (see fig. 3), after which the yellow LED will continue to flash until zeroing has been completed.
LED INDICATION
The green LED is lit when the power supply has been connected correctly and flashes when the actual pressure is above or below the selected measuring range. The yellow LED is lit if pres­sure exceeds 50 Pa and flashes for approx. 3 seconds during zeroing.
Table 1
LED on
On Flashing Off
Green OK
Yellow >0,5 mbar Zeroing in progress <0,5 mbar
FIGURES
Fig. 1: Dimensioned sketch Fig. 2: Transmitter position in relation to bends
and branches Fig. 3: PCB component positions Fig. 4: Wiring diagram Fig. 5: Selection of pressure range: PTH-3202 Fig. 6: Selection of output voltage/current Fig. 7: Selection of damping time Fig. 8: Free DIP switch
Bailey & Mackey Ltd
Baltimore Road Birmingham B42 1DE Tel: 0121-357 5351 · Fax: 0121-357 8319 www.baileymackey.com
Pressure outside set range
No supply
© 2012 OJ Electronics A/S
1
Fig. 1
BR-0996-A07 © 2011 OJ Electronics A/S
Output DIP1 Terminal
0-10 V O Terminal 2
2-10 V On
0-20 mA O Te rminal 4
4-20 mA On
BR-0996-A08
Fig. 2
Fig. 4
BR956A02bBR956A03aBR996A03
BR996A06
Fig. 3
Fig. 5
Fig. 6
2
Fig. 7
Fig. 8
Damping DIP2
0,4 Sec O
10 Sec On
BR996A07
The trademark is registered and belongs to OJ Electronics A/S · © 2014 OJ Electronics A/S
BR996A08
BR996A09 BR996B04
Loading...