OJ-DV is a range of controllers suitable for regulating the speed of an electric motor in a wide variety
of applications.
OJ-DV is highly versatile as it can control various motor types, including:
• ACIM - asynchronous induction motors
• PMSM - permanent magnet synchronous motors
• BLDC - brushless DC motors
2. Introduction
• Read this manual thoroughly and follow the instructions it contains before taking OJ-DV into use.
• This manual contains important information and should be used when installing, connecting and
commissioning the OJ-DV as well as during maintenance, service and troubleshooting.
• If the instructions contained in this manual are not observed, the liability of the supplier and the
warranty shall be voided (see also Section 6. Prohibition on use).
• Technical descriptions, drawings and figures must not be wholly or partly copied or disclosed to
third parties without the permission of the manufacturer.
• All rights are reserved if the product is included in patent rights or other form of registration.
3. Key to symbols
Particular attention should be paid to the sections in these instructions which are marked with
symbols and warnings.
Warning
3.1. This symbol is used where there is a risk of severe or fatal personal injury.
Caution
3.2. This symbol is used where potentially dangerous situations may result in minor or moderate personal
injury. The symbol is also used to warn against unsafe and hazardous conditions.
Note
3.3. This symbol is used to indicate important information and in situations which may result in serious
damage to equipment and property.
Warning
4. Ensuring safety before installation
4.1. OJ-DV must only be installed by qualified personnel or people who have received appropriate
training and have thus become qualified to install the product.
4.2. Qualified personnel have knowledge of the installation practices used and can perform installation in
accordance with relevant local and international requirements, laws and regulations.
4.3. Qualified personnel are familiar with the instructions and safety precautions described in this manual.
4.4. OJ-DV contains dangerous high voltage when connected to the mains.
4.5. Mains voltage must always be disconnected before any installation, service or maintenance tasks are
performed on the product.
4.6. When OJ-DV is connected to the mains, there is a risk that the motor could start unintentionally,
causing a risk of dangerous situations and personal injuries.
4.7. Unintentional start during programming, service or maintenance may result in serious injury or
damage to equipment and property.
4.8. The motor/fan can be started via an external input signal, Modbus or a connected control panel.
4.9. Before connecting mains voltage to OJ-DV, all OJ-DV, motor and fan components must be properly
fitted.
4.10. Before connecting mains voltage to OJ-DV, all openings, covers and cable glands must be properly
fitted and closed. Unused cable glands must be replaced with blank glands.
4.11. OJ-DV contains capacitors which become charged during operation. These capacitors can remain
charged even after the power supply has been cut o. There is a risk of severe personal injury if
the connection terminals or wire ends are touched before these capacitors have been completely
discharged. The discharge time is about 3 minutes under normal conditions.
5. Product use
5.1. OJ-DV is especially used in ventilation applications (fans).
5.2. OJ-DV can also be used in other applications. If OJ-DV is used in applications where it cannot be
positioned directly in a flow of air, impaired OJ-DV cooling must be taken into account. This can
be countered by creating additional ventilation around the product or by reducing performance
requirements. See Section 25. Technical specifications.
5.3. OJ-DV is an electronic motor controller used to regulate fan speed. OJ-DV can be used to control AC
asynchronous motors, BLDC motors and PM motors.
5.4. Depending on what is needed, OJ-DV is suitable for stand-alone applications or as part of larger
systems/machines.
5.5. The product can be used under various environmental conditions. See Section 25. Technical
specifications.
5.6. OJ-DV can be fitted directly to the frame of the fan motor, thus saving space.
5.7. Motor operation can be regulated by commands from an external controller.
5.8. OJ-DV has built-in motor protection.
5.9. OJ-DV can be used in domestic and industrial environments and has a built-in EMC filter.
5.10. The OJ-DV is developed for use in industry and defined as professional equipment according to
EN 61000-3-2:2014, it is not intended for sales to the general public.
Warning
6. Prohibition on use
• The OJ-DV must not be taken into use until the machine or product into which it is incorporated
has in its entirety been declared to be in conformity with all relevant national and international
regulations.
• The product must not be energised until the entire installation complies with ALL relevant EU
directives.
• The product carries a manufacturer's warranty if installed in accordance with these instructions
and applicable installation regulations.
• If the product has been damaged in any way, e.g. during transport, it must be inspected and
repaired by authorised personnel before being connected to the power supply.
• If OJ-DV is built into machinery with rotating parts, e.g. a ventilation system, transport system,
etc., the entire system must comply with the Machinery Directive.
7. EMC – Electromagnetic compatibility
• OJ-DV has built-in EMC filter.
8. Approvals and certifications
CE marking
• OJ Electronics A/S hereby declares under sole responsibility that the product complies with the
following European Parliament directives:
• In accordance with EN 61800-3 – Adjustable speed electrical power drive systems. Part 3. EMC
requirements and specific test methods. See table 8.1
• The OJ-DV product line fulfils the “residential level” for emissions as per EN-61000-6-3 and the
“industrial level” for immunity as per EN-61000-6-2 with up to 5 metre shielded motor cables.
(15kW is limited to up to 4 metre motor cables).
• Longer motor cables can be used. Industrial level for both immunity and emissions can be fulfilled,
depending on the cable capacity as well as the motor capacity.
By reducing the motor cable length, it is possible to install up to 6 OJ-DVs in the same unit with EN-618003 C1 & C2 still being fulfilled.
RoHS compatible
• Contains no hazardous substances according to the RoHS Directive.
ImmunityEmission
9. Product programme
• OJ-DV is available in four dierent enclosures, whose size depends on the rated power of the
OJ-DV.
• The product programme contains 12 power sizes ranging from 0.55 kW to 15.0 kW, see table 9.
• Enclosures are designated ”H1”…”H5”, where ”H1” is the smallest and ”H5” is the largest.
• All enclosures are made of die-cast aluminium.
Table 9
Product nameEnclosure PowerSupply voltageDimensions (w, h, d)
OJ-DV-1005H10.55 kW1 x 230 V185 x 230.5 x 90 mm
OJ-DV-1007H10.75 kW1 x 230 V185 x 230.5 x 90 mm
OJ-DV-1011H11.1 kW1 x 230 V185 x 230.5 x 90 mm
OJ-DV-1013H1x1.3 kW1 x 230 V185 x 265 x 125 mm
OJ-DV-3016H31.6 kW3 x 400 V185 x 265 x 100 mm
OJ-DV-3024H32.4 kW3 x 400 V185 x 265 x 100 mm
OJ-DV-3030H33.0 kW3 x 400 V185 x 265 x 100 mm
OJ-DV-3040H44.0 kW3 x 400 V220 x 294 x 107 mm
OJ-DV-3055H45.5 kW3 x 400 V220 x 294 x 107 mm
OJ-DV-3065H46.5 kW3 x 400 V220 x 294 x 107 mm
OJ-DV-3075H47.5 kW3 x 400 V220 x 294 x 107 mm
OJ-DV-3110H511.0 kW3 x 400 V244 x 399 x 144 mm
OJ-DV-3150H515.0 kW3 x 400 V244 x 399 x 144 mm
All 3x400V versions can also be connected to 3x230V. The power output (kW) will, however, be limited to
max. 58% (1/√3) of the rated power output at 3x400V.
With enclosure sizes H3 ... H5, OJ-DV operating and motor parameters are set for connection to a supply
voltage of 3x400V.
If these types are connected to a 3x230V power supply, operating and motor parameters must therefore be
changed for optimum operation.
Motor parameters can be changed by the installer via the hand terminal (OJ-DV Hterm), OJ-Drives-Tool or
OJ-DV PCTool. Configuration parameters can only be changed by the manufacturer.
10. Rating plate
10.1. OJ-DV is equipped with a silver-coloured rating
plate.
See the example in fig. 10.1 and explanation in
table 10.2.
Check that the information specified on the rating
plate is as expected.
10.2. Rating plate, information and explanation
10.3. Explanation of product code
Each and every OJ-DV is given its own product
code during manufacture.
The product code (see table 10.3) gives precise
information on the specific OJ-DV.
The product code contains the following
information:
Table 10.3
Week number
W WB B B B BS S S S SY Y
Week of
production
BatchSerial no. Year
Manufacturer's order
number
Unit
number
Year of
manufacture
Figure 10.1
Table 10.2
1Product ID = see table 10.4.
2Shaft power at nominal voltage
3Max. input voltage, Hz/A
4Max. output voltage/Hz/A
5Product code = see table 10.3.
6Enclosure rating
7Weight
8Temperature range, operating
9Manufacturer's logo
10Manufacturer's web address
11Manufacturer's postal address
12Country of manufacture
13CE approved, logo
14Disposal, logo
15Bar code
16EAC approved, logo
10.4. The product ID consists of a combination of 14
numbers and letters, each of which provides
information about the specific product, see fig.
No.Description No.Description
1Motor connection terminals5RJ12 Modbus connectro (2 x xslave/1 x Master)
2Connections for future use63-point stain relief for Modbus connector cable (ribbon cable)
3Connector for optional modules7Power terminals (H1=L, N, PE); (H3, H4, H5=L1, L2, L3, PE)
4Terminal strip for Modbus and A/D control signals8Connector for the earth (PE) protective conductor
Incorrect mechanical installation may cause overheating and impaired performance.
Warning
• OJ-DV must only be installed by trained/experienced personnel.
• To ensure proper cooling of the OJ-DV, it must be positioned in such a way that the passing air
flow (> 3 m/s turbulent air speed) can cool the OJ-DV cooling fins. (3 m/s turbulent air speed is
equivalent to 6.5 m/s laminar air speed). If the OJ-DV is installed in a reduced air flow (< 3 m/s
turbulent air speed) or mounted outside a direct airstream, the output power (kW) will be reduced.
External on-board cooling fan can be added.
• Only OJ-DV-1013 can be installed without considering the above requirements for sucient air
flow over the cooling fins. OJ-DV-1013 is supplied with extra large cooling fins and can therefore
be mounted in still air with an air temperature of max. 40°C.
See Section 25: Technical Specifications.
• To facilitate future service and maintenance tasks, ensure that there is sucient space around the
unit after it has been installed.
• To achieve the specified enclosure rating, the cable glands must not point upwards (see fig. 12.4).
• To prevent water from entering OJ-DV via cables and cable glands, ensure that connection is
performed in such a way that water is prevented from accumulating around the cable in the gland.
See fig. 12.5.
• Check that the surface to which OJ-DV is attached is capable of supporting the entire weight of
the unit.
• OJ-DV can be mounted vertically, horizontally or at an incline. See fig. 12.4.
• OJ-DV must be installed on a flat solid surface.
• To avoid unnecessarily long motor cables (max. 5 m), OJ-DV should be installed as close to the
motor as possible.
• Use only the pre-cut installation holes/screw holes to secure OJ-DV in place.