OJ Electronics OCC3, OCD3 User Manual

English
Type OCC3 / OCD3
USER MANUAL
57695 05/08 - (BJ)
Type: OCC3 / OCD3
Buttons
Display symbols
M
L
K
I
J
A: B: C: D:
E: F: G:
Pin button adjust of clock
On/off Reset to
factory setting
Adjustment down
OK ­accept
Adjustment upDisplay
H: I: J: K:
L: M: N:
Clock function
Manual mode
Time and temperature
Day number
Heating on %
Monitoring of switch-on time
4-event symbol
1. Getting started
Introduction
The thermostat is capable of switching on your heating system at pre determined times on different days of the week. It is possible to set 4 periods called events each day with different temperatures. From factory a default schedule is programmed suitable for most installations. Unless you change these settings the thermostat will operate to this default program.
Working with lower temperatures during times that the room is unoccupied will lower your energy costs without reducing the comfort. The thermostat has an adaptive function that automatically changes the start time of a heating period so that the desired temperature is reached at the time that you set. After 3 days the adaptive function has learned when the heating must be switched on.
The thermostat has a built-in temperature sensor and an externally temperature sensor. In this configuration the thermostat controls the temperature within the room and use the externally temperature sensor as limit sensor avoiding too high or too low temperatures in the floor construction.
The thermostat has a pin button marked R, allowing you to reset the thermostat to factory settings. These are listed at the end of this manual with space for you to record your own weekly schedule.
The display is backlit when operating the buttons. The heating element is switched off when the light is on in the display.
The heating system can be switched off on the built-in interrupter. The Microprocessor taking care of the time will still be supplied with power whereby time and day will be maintained. When the heating is required and the thermostat is switched on, it will continue the 4-event programme based on present time and day.
Setting the thermostat into operation
1-7
Press the UP ( ) or DOWN ( ) buttons to select the correct time and press OK button ( ).
Then press the UP ( ) or DOWN ( ) button to select the correct day and press OK ( ) button.
First time power is connected the clock and day will be flashing and must be set. If you need to adjust the time of the thermostat at a later date, insert a pin into the hole for setting of time and day. Adjustment must be made for summer and winter time.
Wake Night
Out Home
1
2. Daily use of the thermostat 4-event clock mode
The day has been split into 4 events describing a typical day. When the thermostat is in 4-event mode it will automatically adjust the temperature according to the required temperature to the required time. As standard the thermostat has 5 days with 4 events, and 2 days with 2 events. Programming see 3.
4-event clock mode:
Comfort mode:
Manual mode:
Temporary override
To temporarily override the temperature in the 4-event schedule program, press the UP ( ) or DOWN ( ) button once, to show the temperature, and press again to increase or decrease the temperature. The display will flash for 5 seconds, and will then revert to the time. The override will operate until the next programmed event when the unit will resume the automatic programme.
The clock function symbol ( ) and one of the 4-event symbols ( ) will be indicated. Programming see 3.
Cancel comfort mode
To cancel the override state, press the OK ( ) button twice.
Permanent override:
During holidays, the scheduled 4-event program can be overridden. Press the OK ( ) button, and then the UP ( ) or DOWN ( ) button until the override temperature is set. The unit will now operate to this temperature permanently.
Cancel manual mode
To cancel the permanent override state press the OK ( ) button once, and the unit will resume automatic function.
5 secs.
5 secs.
Press OK ( ) button for 3 secs. to begin programming
: Time and temperature
: Time and temperature
: Time and temperature
: Time and temperature
Day 1 - 5
Day 6 - 7
: Time and temperature
: Time and temperature
3. Programming 4-event time and temperature
For each event, the start time and required temperature must be set.
For example, in the morning you wish the heating to start at 07:00 and the temperature to rise to 21˚C. Press OK ( ) button for 3 seconds and the start time is displayed. Change this to 07:00 with the UP ( ) or DOWN ( ) button. Press OK ( ) to confirm. The temperature is now displayed. Change this to 21˚C with the UP ( ) or DOWN ( ) button. Press OK ( ) button to confirm. This action can now be repeated for the second event.
These settings will be valid with days 1-5 showing on the display. To program the days 6 and 7, repeat the above. Days 6 and 7 are usually Saturday and Sunday, and only have two events.
The temperature can be set within the range of +5 to +40˚C. It is also possible to select the heating OFF at that event by reducing the setting to 5˚C, and then pressing the ( ) once more.
2
Monitoring of energy consumption
The thermostat calculates average time it has been switched on allowing you to monitor your energy consumption. In the thermostat you can read out:. Total switch-on time in percentage in the latest 2 days, 30 days or 365 days.
Calculation of operational costs per day: (switch-on time:100) x kW x kWh-price x 24 h per day Example: Read-out: 30 % in the latest 365 days
Size of heating system: 1,2 kW (ask the installer) Cost of power: 0,2 EUR / kWh Calculation: (30:100) x 1,2 kW x 0,2 EUR / kWh x 24 h = 1,7 EUR per day
4. Advanced settings and read-out
4-event sequence
The present event sequence flashes: Days 1-5, followed by days 6-7. To change, press the UP ( ) button until you have days 1-6 and then day 7 flashing, or all 7 days are flashing. Select the required sequence with the OK ( ) button.
5-2: 4 events in 5 days +
2 events in 2 days.
6-1: 4 events in 6 days +
2 events in 1 day
7-0: 4 events in 7 days
}
2 days 30 days 365 days
Software version
Regulation sensor Limit sensor
(visible if configurated as OCD3)
}
Max and min allowed temperature range. The temperature setting range of +5˚ to +40˚C can be limited to prevent a too high or too low temperature being selected under manual or comfort mode. For OCD3 with limit sensor the max. and min. temperature range refer to the temperature of the limit sensor. For example: A wood floor covering should not be allowed to exceed a maximum of 27˚C. Low limitation is used where the temperature of the floor is required never to fall below the minimum set temperature.
Time and temperature scale selection
Maximum allowed temperature setting. Use the UP ( ) or DOWN ( ) button to increase or reduce, and OK ( ) button to accept.
Next is displayed LoLi. Press OK ( ) button to continue.
Minimum allowed temperature setting. Use the UP ( ) or DOWN ( ) button to increase or reduce and OK ( ) button to accept.
You can select either ˚C or ˚F scale, and 12 or 24 hour clock as follows:
Press UP ( ) or DOWN ( ) button to change settings. Confirm the required scale with the OK button ( ) button.
}
Press both UP ( ) and DOWN ( ) buttons together for 3 seconds. INFO is displayed. Press UP( ) button until you reach the desired sub menu. Select the sub menu with the OK ( ) button.
Press UP ( ) or DOWN ( ) button to show the different readouts.
No changes can be made here. Use the OK ( ) button to end.
Selection of type (only visible in type OCD3)
Type OCD3-1999 has a built-in temperature sensor and an externally temperature sensor. In this configuration the thermostat controls the temperature within the room and use the externally temperature sensor as limit sensor Type OCD3 can be changed into type OCC3-1991 with an external temperature sensor that normally is placed in the floor construction. In this configuration the thermostat controls the temperature of the floor and not the temperature within the room. OCD3 can also be changed into type OCC3-1999 with a built-in temperature sensor. In this configuration the thermostat controls the temperature of the room, and the external temperature sensor should not be installed.
OCD3-1999 With 2 sensors;
built-in room sensor and incl. floor sensor 3m
OCC3-1991 Incl. floor sensor 3m
OCC3-1999 With built-in room sensor
}
3
Loading...
+ 5 hidden pages