OilGear PVM-011, PVM-014, PVM-046, PVM-022, PVM-065 Service Manual

...
Bulletin 947070-B
OILGEAR TYPE “PVM” PUMPS -
-011/-014/-022/-025/-034/-046/
-064/-065/-075/-076/-098/-130 SERVICE INSTRUCTIONS
Figure 1. Typical Oilgear “PVM” Open Loop Pump
PURPOSE OF INSTRUCTIONS
These instructions will simplify the installation, operation, maintenance and troubleshooting of Oilgear type “PVM” pumps.
REFERENCE MATERIAL
Fluid Recommendations.....................................................................................Bulletin 90000
Contamination Evaluation Guide.........................................................................Bulletin 90004
Filtration Recommendations...............................................................................Bulletin 90007
Piping Information...............................................................................................Bulletin 90011
Installation of Vertically Mounted Axial Piston Units ...........................................Bulletin 90014
PVM Open Loop Pumps Sales Brochure........................................................Bulletin 47070-B
OILG0173
Become familiar with the construction, principle of operation and characteristics of your pump to help you attain satisfactory performance, reduce shut­down and increase the pump's service life. Some pumps have been modified from those described in this bulletin and other changes may be made without notice.
Bulletin 947070-B THE OILGEAR COMPANY 1
Revised November, 2004
THE OILGEAR COMPANY
2300 South 51st Street
Milwaukee, Wisconsin 53219
Bulletin 947070-B
Safety First
Read and understand this entire instruction sheet before repairing, or adjusting your Oilgear product.
Those who use and maintain this equipment must be thoroughly trained and familiar with the product. If incorrectly used or maintained, this product and its equipment can cause severe injury.
SAFETY SYMBOLS
The following signal words are used in this instruction sheet to identify areas of concern where your safety may be involved. Carefully read the text and observe any instructions provided to ensure your safety.
DANGER
! !
THIS SIGNAL WORD INDICATES AN IMMI­NENTLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
WARNING
!
This signal word indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
This signal wor d indicate s that a pote ntiall y hazardous situation exists which, if not avoided, may result in damage to equipment or minor personal injury.
NOTE
While not directly relevant to the topic being discussed, the NOTE is used to emphasize information provided, or provide additional information which may be of benefit.
WARNING
!
This service information is designed for the maintenance of your Oilgear product. It contains the information on the correct procedures determined by Oilgear for the safe manner of servicing. Always keep this instruction sheet in a location where it is readily available for the persons who use and maintain the product. Additional copies of this instruction sheet are available through the Oilgear Company. Or visit our website: www.oilgear.com. Please contact us if you have any questions regarding the information in this instruction bulletin.
NOTE
The cleanliness of working on this pump or the hydraulic system is extremely important to the safety and reliability of the pump and the system. Always make sure the fittings are clean on the outside before removing them from their connections, are capped and plugged when removed and placed in a clean rag or container until they are reinstalled.
WARNING
!
Some service operations may require special tools or equipment. If you require information on these items, please contact Oilgear before attempting these repairs and service operations.
WARNING
!
Read, understand, and follow the safety guidelines, dangers, and warnings contained in this instruction sheet to promote reliable operation and prevent serious personal injury.
WARNING
!
DO NOT attempt to service this machinery in an environment where safety regulations are not established and in place.
WARNING
!
DO NOT operate the hydraulic system if a leak is present. Serious injury may result.
WARNING
!
Hydraulic systems operate under very high pressure. Hydraulic fluid escaping from a pressurized system can penetrate unprotected body tissue. DO NOT inspect for hydrauli c leaks with ba re hands or o ther exposed body parts. As a minimum, wear leather gloves prior to inspecting for leaks and use cardboard or wood. If leaks are present, relieve pressure and allow system to cool prior to servicing. If injured by escaping hydraulic oil, contact a physician immediately. Serious complications may arise if not treated immediately. If you have questions regarding inspecting for hydraulic leaks, please contact Oilgear prior to servicing.
2 THE OILGEAR COMPANY Bulletin 947070-B
© 1993 THE OILGEAR COMPANY - ALL RIGHTS RESERVED
Safety First
WARNING
!
Hydraulic hoses and tubing must be inspected on a daily basis for leaks, cuts, abrasions, damage and improper clearance along any mounting frame for hidden damage before the unit is put into service. Replace damaged hoses or hoses you suspect are damaged before the system is returned to service! Hoses must be replaced every two years. Failure to properly inspect and maintain the system may result in serious injury.
WARNING
!
Hydraulic systems are hot. DO NOT TOUCH! Serious personal injury may result from hot oil. When you have completed working on the hydraulic system, thoroughly clean any spilled oil from the equipment. Do not spill any hydraulic fluids on the ground. Clean any hydraulic fluids from your skin as soon as you have completed maintenance and repairs. Dispose of used oil and system filters as required by law.
WARNING
!
Hydraulic cylinders can be holding a function in a certain position when thepump is OFF. An example of this is a function being held in the lift or partial lift position by the cylinders. If a hydraulic line is removed or the hydraulic circuits or controls are being worked on, gravity may allow the function being held in position to drop. All workers and personnel must remain clear of these areas when working on or operating the hydraulic system. Block and secure all devices and functions which apply before beginning work or operation. Failure to comply with this can result in serious injury or death.
WARNING
!
Any hydraulic pipe which is replaced must conform to SAE J1065 specifications. If incorrect hydraulic pipe is installed, the hydraulic system may fail, causing serious injury. Damaged or leaking fittings, pipes or hoses must be replaced before the system is returned to service.
WARNING
!
Use correct hoses, fittings, and adapters with the correct SAE rating when replacing hoses to prevent possible serious injury. Always replace hoses, fittings, and adapters with replacements that have a proper, suitable, working pressure rating. Replacement hoses must be of the correct length and must comply with the hose manufacturer’s and Oilgear’s installation guidelines and recommendations.
WARNING
!
Hydraulic hoses have the SAE ratings marked on the hose to assist you in selecting the correct hose. The same manu­facturer must supply any replacement hydraulic hoses and fitting assemblies. As an example: Brand “X” hose and brand “Y” fitting will not normally be compatible. No “Twist” is allowed in the hydraulic hoses. “Twist” may result in premature hose failure. This can cause serious injury. Please contact Oilgear for assistance when required.
WARNING
!
DO NOT heat hydraulic pipe. The carbon content of this steel tube is such that if heated for bending, and either water or air quenched, the pipe may lose its ductility and thereby be subject to failure under high pressure or hydraulic chock conditions. Serious injury can result. Damaged or leaking pipes must be replaced before the system is returned to service. Please contact Oilgear if you require assistance or have questions.
WARNING
!
All hydraulic pressure must be relieved from the hydraulic system prior to re moving any components from the system. To relieve the hydraulic pressure from the hydraulic system, turn off the motor and operate the control panel with the key in the ON position. Failure to comply can result in serious injury. If you have any questions concerning relieving the hydraulic pressure from the system, please contact Oilgear.
Bulletin 947070-B THE OILGEAR COMPANY 3
Safety First
WARNING
!
Hydraulic components can be heavy. Use caution while lifting these components. Serious personal injury can be avoided with proper handling of the components.
WARNING
!
Please contact Oilgear if you require assistance, when performing hydraulic test procedures, use the proper hydraulic gauges. Installing an incorrect test gauge could result in serious injury if the gauge fails. Use properly rated hydraulic hoses to allow the test gauge to be read away from moving parts and functions.
WARNING
!
Increasing hydraulic pressure beyond the recommendations may result in serious damage to the pump and system or serious personal injury and may void the Oilgear Warranty. If you have questions concerning hydraulic pressures or testing procedures, please contact Oilgear before attempting the test procedures or making adjustments.
WARNING
!
Any Oilgear pump safety decals must be replaced anytime they are damaged, missing, or cannot be read clearly. Failure to have proper decals in place can result in serious injury or death. (If you require safety decals, please contact Oilgear for replacement safety decals, at no charge.)
WARNING
!
Be sure everyone is clear of the area around the hydraulic system before operating after servicing. Remain attentive at all times when operating to check your work until you are completely sure it is safe to return to service. Failure to heed this warning may result in serious personal injury or death.
WARNING
!
Wear the proper protective clothing when operating, servicing or maintaining the hydraulic system or the Oilgear pump. Wear the correct protective gear, safety glasses, gloves, and safety shoes. Serious injury can result without proper protective gear.
WARNING
!
An Oilgear pump must not be modified in any way without authorization from Oilgear. Modifications may not comply with safety standards, including ANSI safety standards, and may result in serious personal injury. Please contact Oilgear if you require assistance.
WARNING
!
DO NOT enter under hydraulic supported equipment unless they are fully supported or blocked. F ailure to follow this procedure can result in serious injury or death.
WARNING
!
Make sure to keep hands and feet and other parts of your body clear of revolving or moving parts. Failure to comply can cause serious injury.
WARNING
!
DO NOT wear watches, rings, or jewelry while working with electrical and mechani­cal equipment. These items can be hazard­ous and can cause serious and painful injuries if they come into contact with elec­trical wires, moving parts, or hydraulic equipment.
4 THE OILGEAR COMPANY Bulletin 947070-B
Service Instructions
PREPARATION AND INSTALLATION
MOUNTING
Pump Without Reservoir - The pump can be mounted in any position. But, the recommended mounting position is with the driveshaft on a horizontal plane. Secure the pump to a rigid mounting surface.
Pump With Reservoir - These pumps are usually fully piped and equipped. It may be necessary to connect to a super-charge circuit when used. Mount reservoir on level foundation with the reservoir bottom at least six inches above floor level to facilitate fluid changes.
PIPING AND FITTINGS
Refer to the referenced Oilgear Piping Information Bulletin 90011 and individual circuit diagram before connecting the pump to the system. Inlet velocity must not exceed 5 fps (1,5 mps). Inlet should be unrestricted and have a minimum of fittings.
NOTE
Horizontal Mounting - Arrange line from the highest “case drain” or “alternate case drain” so the case remains full of fluid (non-siphoning). Case pressure must be less than 25 psi (1,7 bar). For higher case pressures and the special shaft seals required, contact our Customer Service. Each drain line must be a separate line, unrestricted, full sized and connected directly to the reservoir below the lowest fluid level. Make provisions for opening this line without draining (siphoning) reservoir.
Vertical Mounting - Refer to referenced Oilgear “Installation of Vertically Mounted Axial Piston Units,” Bulletin 90014.
DO NOT use an inlet strainer.
WARNING
!
Running the pump in NEUTRAL position (zero delivery) for extended periods without a supercharge circuit can damage the pump. The system and pump must be protected against overloads by separate high pressure relief valves. Install bleed valve(s) at the highest point(s) in system.
POWER
Power is required in proportion to volume and pressure used. Motor size recommendations for specific applications can be obtained from The Oilgear Company. Standard low starting torque motors are suitable for most applications.
CAUTION
DO NOT start or stop unit under load unless system is approved by Oilgear. It may be necessary to provide delivery bypass in some circuits.
DRIVE
V erify rotation direction plate on the pump 's housing. Clockwise pumps must be driven clockwise and counterclockwise pumps must be driven counterclockwise. Use direct drive coupling. Size and install coupling per manufacturer's instructions.
CAUTION
DO NOT drive the coupling onto the pump driveshaft. If it is too tight, it may be necessary to heat coupling for installation. Refer to manufacturer's instructions.
Misalignment of pump shaft to driver's shaft should not exceed 0.005 inches (0,13 mm) Total Indicator Readout (TIR) in any plane.
Bulletin 947070-B THE OILGEAR COMPANY 5
FILTRATION
Keep the fluid clean at all times to ensure long life from your hydr aulic system. Ref er to the ref erenced Oilgear Filtration Recommendations bulletin 90007 and Oilgear Contamination Evaluation Guide Bulletin 90004. Oilgear recommends use of a filter in the pressure or return line. Replace filter element(s) when the filter condition indicator reaches change area at normal fluid temperature. Drain and thoroughly clean filter case. Use replacement element(s) of same beta 10 ratio (normally a ratio of 4 with hydraulic oils).
FLUID COOLING
When the pump is operated continuously at the rated pressure or frequently at peak load, auxiliary cooling of the fluid may be necessary. Fluid temperature should not exceed limits specified in the referenced Oilgear Fluid Recommendations Bulletin 90000.
AIR BREATHER
FLUID, FILLING AND STARTING RECOMMENDATIONS
Refer to instruction plate on the unit, reservoir, machine and/or reference, Fluid Recommendations bulletin. Fire resistant fluids and phosphate ester fluids can be used in accordance with fluid manufacturer's recommendations .
1. Pump all fluid into reservoir through a clean (beta 10 ratio of 4 or more) filter. Fill reservoir to, but not above, “high level” mark on the sight gauge.
2. Remove case drain line and fill pump case
with hydraulic fluid.
3. Turn driveshaft a few times by hand with a spanner wrench to make sure parts rotate.
With pump under “no load” or with pump control at NEUTRAL:
4. Turn drive unit ON and OFF several times before allowing pump to reach full speed. The system can usually be filled by running the pump and operating the control.
5. The fluid level in the reservoir should decrease. Stop the pump. DO NOT allow the fluid level to go beyond the “low level.” If the level reaches “low level” mark, add fluid and repeat step.
NOTE
With differential (cylinder) systems, the fluid must not be above “high level” when the ram is retracted or below “low level” when extended. Bleed air from the system by loosening connections or opening petcocks at the highest point in the system. Close connections or petcocks tightly when solid stream of fluid appears.
Unit PVM-011/-014/-022 PVM-025/-034/-046/-065/-075 PVM-064/-076/-098/-130
Approximate torque
to turn driveshaft
15-25 in•lb
(1,7-2,8 N•m)
6 THE OILGEAR COMPANY Bulletin 947070-B
120-180 in•lb
(13,7-20,5 Nm)
Table 1. Torque to Turn Shaft
180-260 in•lb
(20,5-29,6 N•m)
CONSTRUCTION
See Figures 11, 12 and 13.
1. A driveshaft (21) runs through the center line of pump housing and valve plate (45) with the pump cylinder barrel (38) splined to it.
2. A bearing (26) supports the outboard end of the driveshaft and a bushing supports the inboard end. (The bushing is part of valve pla te assembly.)
3. The pump cylinder barrel is carried in a hydrodynamic (journal type) cylinder bearing (35).
4. The port plate (43) has two crescent shaped ports and is located on a valve plate (45) that has matching crescent shaped ports.
5. The pumping piston/shoe assemblies (39) in the cylinder barrel are held against a swashblock (29) by a shoe retainer (40).
6. The shoe retainer is held in position by the fulcrum ball (41) which is forced outward by the shoe retainer spring (42).
7. The spring acts against the pump cylinder barrel, forcing it against the valve plate while also forcing the piston shoes against the swashblock.
8. The semi-cylindrical shaped swashblock limits the piston stroke and can be swiveled in arc shaped saddle bearings (30).
9. The swashblock is swiveled by a control piston
(19). Refer to PRINCIPLE OF OPERATION.
SPECIFICATIONS
NOTE
Refer to reference material, pump control material and individual application circuit for exceptions.
FLOW RATE
THEORETICAL
UNIT
011 0.66 10,8 3750 258,6 4250 293,1 4.3 16,3 5.6 (0,39) 8.1 (0,56) 17.2 (1,19) 3600 12.8 9,5 014 0.86 14,1 3750 258,6 4250 293,1 5.8 22,0 5.5 (0,38) 7.8 (0,54) 17.2 (1,19) 3600 16.4 12,1 022 1.35 22,1 3750 258,6 4250 293,1 9.5 36,0 8.6 (0,60) 11.4 (0,79) 23.7 (1,63) 3600 26.1 19,5 025 1.55 25,4 3750 258,6 4250 293,1 10.1 38,2 6.5 (0,45) 11.5 (0,80) - 2700 28.8 21,5
0342.06 33,8 3750 258,6 4250 293,1 14.1 53,4 5.7 (0,40) 11.0 (0,76) - 2700 37.7 28,1 046 2.83 46,4 3750 258,6 4250 293,1 19 .7 74,6 5.7 (0,40) 8.1 (0,56) - 2400 51.9 38,7 064 3.88 63,6 3750 258,6 4250 293,1 2 6 .6 100,7 7.3 (0,50) 11.4 (0,79) - 2400 70.2 52,4 065 4.00 65,5 3750 258,6 4250 293,1 27 .9 105,6 6.2 (0,43) 1 0.2 (0,70) - 3000 71.0 53,0 075 4.61 75,5 3750 258,6 4250 293 076 4.67 76,5 3750 258,6 4250 293,1 32.4 122,6 8.2 (0,57) 13.4 (0,92) - 2400 85.7 63,9 098 6.00 98,33750 258,6 4250 293,1 41.2 156,0 8.3 (0,57) 12.1 (0,83) - 2400 109.2 81,4
1307.94130,2 3750 258,6 4250 293,1 57.8 218,8 8.7 (0,60) 14.9 (1,03) - 2400 150.8 112,5
Case pressure should be less than 25 psi (1,7 bar). For hi gh er pressure, consult factory. Higher speeds availab le - consult factory.
MAXIMUM
DISPLACEMENT
in 3/rev ml/rev psi bar psi bar gpm l/mi 1800 rpm 2400 rpm 3600 rpm rpm hp kw
RATED
CONTINUOUS
PRESSURE
MAXIMUM
PRESSURE
1800 rpm rated
continuous
pressure and
14,7 psia (bar abs)
inlet condition
,1 31.3 118,5 6.5 (0,45) 10.6 (0,73)- 3000 83.8 62,5
at
MINIMUM INLET PRESSURE
psia (bar abs)
MAXIMUM
SPEED
POWER
INPUT at
rated continuous pressure &
1800 rpm
Table 2. All data is for ISO 46 mineral-based oil at 125°F (160 SSU).
Bulletin 947070-B THE OILGEAR COMPANY 7
Unit
PVM-011
PVM-022 PVM-025
PVM-046 PVM-065 PVM-075 PVM-064 PVM-076 PVM-098 PVM-130
Length Width Height Weight*
inches mm inches mm inches mm lbs. kg
7.95 201,9 7.28 184,9 6.63 168,4 37.5 17,0 SAE "A" 2 BoltPVM-014
9.51 241,5 9.00 228,6 8.88 225,6 73.0 33,1 SAE "B" 2/4 BoltPVM-034
10.00 254,0 9.03 229,4 8.88 225,6 75.0 34,0 SAE "B" 2/4 Bolt
11.91 302,5 10.73 272,5 10.45 265,4 136.0 61,7 SAE "C" 2/4 Bolt
For detailed dimensions, contact your Oilgear Representative. * Weight with rear port valve plate and without maximum volume stop.
Table 3. Nominal Dimensions and Weights.
Refer to installation drawings for more detailed dimensions and port configurations.
TROUBLESHOOTING
PROBLEM CAUSES REMEDY
Plugged stability orifice (OP2). Inspect. Clean out if contaminated. PC control cartridge (55) damaged.
Unresponsive or Sluggish Control
Insufficient Pump Volume
Swashblock saddle bearings (30) worn or damaged. Control piston (19) or sequence spool (54) binding in bore. Control piston spring (20) broken, sequence valve spool spring
(53) broken. High load sense differential pressure.
PC control cartridge damaged, stuck open. Delivery limited by stroke limiter screw (70). Adjust stroke limiter CCW.
Obstructed suction circuit or insufficient supercharge volume. Inspect for obstruction and verify supercharge. Insufficient drive motor speed. Check drive speed. Worn or grooved cylinder barrel (38) and/or port plate (43) mating
surfaces. Worn or damaged piston shoe or swashblock (29). Worn or sticking control piston (19). Port plate not seated against valve plate. Worn hydrobearing (35). Worn or broken saddle bearing (30). O-rings leaking on plug (84) or control cartridges (55) or (83). Worn or damaged piston and shoe assemblies (39) or piston
bores in cylinder (38).
Inspect components. Replace.
Verify that load sense differential pressure is less than pump control setting.
Inspect. Clean out if contaminated. Replace if necessary.
Inspect components. Replace.
Face Mounting
8 THE OILGEAR COMPANY Bulletin 947070-B
TROUBLESHOOTING
PROBLEM CAUSES REMEDY
Fluctuating load sense differential pressure. Check system flow control valve/orifice.
Irregular or Unsteady Operation
Loss of Pressure
Excessive or High Peak Pressure
Excessive Noise
Excessive Heating
Faulty control piston (19), sequence valve (54) or PC control cartridge (55) operation.
Fluid level in reservoir is low or supercharge is insufficient. Verify fluid level and/or supercharge. Air entering hydraulic system. Inspect system for leak. Low viscosity fluid used. Increase size of OP2. Refer to Table 4. Remote PC setting close to pump PC setting. Increase pump PC setting. Worn axial piston pump. Inspect components. Replace. Faulty output circuit components (cylinder, motors, valves or
other related components). Worn piston pump. Worn hydrobearing. Worn or grooved cylinder barrel (38) and/or port plate (43)
mating surfaces. Worn piston/shoe assemblies (39) or piston bores in cylinder. Worn or broken saddle bearing (30). Faulty output circuit components. Faulty output circuit components. Check the relief valves. Faulty PC control cartridge (55) operation. Seized control piston (19). Worn or broken saddle bearing (30). Inspect components. Replace. Pump stopped or started incorrectly under load. Verify operation procedure of pump. Low fluid level in reservoir or insufficient supercharge causing
cavitation. Air entering hydraulic system. Inspect system for leak. Fluid too cold or viscosity too high. Verify fluid temperature and/or type. Suction line problem i.e.; obstructions in line, line too long, line
diameter too small or too many bends and/or loops in line. Broken or worn piston/shoe assembly (39). Inspect components. Replace. Pump rotating in wrong direction. Inspect operation direction of pump. Operating pump above rated or peak pressure. Verify pump limitations. Low fluid level in reservoir or insufficient supercharge. Verify fluid level and/or supercharge. Air entering hydraulic system. Inspect system for leak. Worn piston pump. Worn or grooved cylinder barrel (38) and/or port plate (43)
mating surfaces. Faulty output circuit components (continuous blowing relief v alves
or "slip" through valves, cylinder or other components. Insufficient cooling provision or clogged coolers. Inspect for obstruction. Insufficient case fluid level (wrong drain port). Use highest drain port. OP2 too big or missing causing excessive case drain. Decrease size of OP2. Sequence spool seized. Sequence spool leaking (if heating occurring during
compensating).
Inspect components. Replace.
Inspect components. Replace.
Inspect components. Replace.
Inspect components. Replace.
Verify fluid level and/or supercharge.
Inspect line and for obstruction.
Inspect components. Replace.
Inspect, replace spool and valve plate if necessary.
Bulletin 947070-B THE OILGEAR COMPANY 9
Table shows the orifice plugs OP2 (item 68).
Unit Application
PVM-011 PVM-014 PVM-022
PVM-025 PVM-034 PVM-046 PVM-065 PVM-075
PVM-064 PVM-076 PVM-098 PVM-130
Standard (fluid viscosity of 100 SSU or
greater)
High Temperature or thin oil (fluid
viscosity less than 100 SSU)
Standard (fluid viscosity of 100 SSU or
greater)
High Temperature or thin oil (fluid
viscosity less than 100 SSU)
Standard (fluid viscosity of 100 SSU or
greater)
High Temperature or thin oil (fluid
viscosity less than 100 SSU)
Standard
Orifice Size*
0.032 dia. 240971-018
0.040 dia. 240971-002
0.047 dia. 240971-022
0.062 dia. 240971-003
0.062 dia. 240971-003
0.076 dia. 240971-004
Oilgear Part Number
* Pumps delivered from the factory are equipped with the standard application orifice unless specified for high temperature
or thin oil.
Table 4. PVM Stability Orifice Sizing
10 THE OILGEAR COMPANY Bulletin 947070-B
PRINCIPLE OF OPERATION
OILG0020
Figure 2. Cut-a-way of a Typical “PVM”
Pump (01010)
Full Stroke Operation - Figure 3
NOTE
The control piston (19) positions the control pin (31) and pump swashblock (29) so the pump will
deliver maximum volume to raise pressure in the system.
Raising Pressure
Pump delivery (and resultant pressure) is fed to both sides of the control piston (19). Pressure to the unloading side (C) of the control piston is direct. Pressure to the bias side (D) of the control piston is maintained by the respective control.
Numbers in parentheses represent item number in parts list and drawings.
The areas on either end of the control piston are the same and the pressure acting on either end is the same. The resultant hydraulic forces on the ends of the control piston cancel each other out (the control piston is balanced), and the force of the control piston spring (20) controls the control piston position (19).
Rotating the driveshaft turns the splined cylinder (38), which contains the pumping pistons (39). When the cylinder rotates, the pistons move in and out within their bores as the shoes ride against the angled swashblock (29).
As the cylinder rotates, the individual piston bores are connected, alternately, to the crescent shaped upper (P) and lower (S) in the valve plate. While connected to the lower side (suction) S, each piston moves outward OUT, drawing fluid from S into the piston bore until its outermost stroke is reached. At this point, the piston bore passes from the lower crescent S to the upper crescent P.
While rotating across the upper crescent port, each piston moves across the angled swashblock face and then each piston is forced inward IN. Each piston then displaces fluid through the upper crescent to P until its inner most stroke is reached. At this point, the piston bore passes from the upper to the lower crescent again and the cycle is repeated.
The angle of the swashblock determines the length of the piston stroke, (the difference between outermost and innermost position) which determines the amount of delivery from the pump. If the stroke angle is one-half of the stroke, the piston stroke is one-half and the pump delivery is one-half.
Note that the flow through the PC control cartridge (3-1) is blocked.
Bulletin 947070-B THE OILGEAR COMPANY 11
3-1
HP
RP
3-3
D
LS
P
54
S
68
3-2
19
C
20
29
39
38
OUT
(3-1) PC Control Cartridge (3-2) Stability Orifice (3-3) Into Case
Figure 3. Full Stroke Operation
31
IN
OILG0119
12 THE OILGEAR COMPANY Bulletin 947070-B
4-1
Relatively small variations in system flow
LS
P
requirements can be accommodated for in the mentioned operational mode. When pump outlet
54
HP
RP
4-3
53
S
68
4-2
19
pressure decreases below the preset pressure setting of the PC Control Cartridge, the PC Control Cartridge closes. The sequence spool spring (53) repositions the sequence spool to open the flow path. This provides for an unobstructed flow path to the bias side of the control piston so the pump will be responsive to increased system flow demand.
20
D
(4-1) PC Control Cartridge (4-2) Stability Orifice (4-3) Into Case
OILG0115
Figure 4. Pressure Compensating
Pressure Compensating - Figure 4
When pump outlet pressure reaches the preset pressure setting of the PC Control Cartridge, bias pressure D (pressure on the spring side of the control piston) is relieved by the PC Control Cartridge. Exhaust flow from the PC Control Cartridge is ported to the pump case via the sequence spool (54). The resulting pressure drop across the sequence spool due to the exhaust flow moves the spool to block the flow path. All flow to the PC Control Cartridge is now provided via the stability orifice OP2 (68).
Blocking the flow path and requiring all control flow to pass through OP2 minimizes case drain leakage and provides a means of stability adjustment for a wide range of system requirements. The decrease in bias pressure results in a pressure differential across the control piston (19). The control piston is no longer balanced and the pressure on the unloading side of the control piston forces the control piston to compress the control piston spring (20). The control piston moves the control pin and shifts the swashblock to a position that provides less flow output from the pump. Flow output from the pump is then controlled to maintain the preset pressure setting of the PC Control Cartridge. When the outlet port of the pump is blocked, the swashblock is positioned so the pump delivers just enough volume to provide for internal losses and required control flow.
5-1
5-2
HP
RP
(5-1) PC Control Cartridge (5-2) Remote Pressure Control Valve (5-3) Stability Orifice (5-4) Into Case
5-4
LS
54
D
5-3
68
20
P
S
19
OILG0116
Figure 5. Remote Pressure Compensating
Remote Pressure Compensating - Figure 5
Principal of operation for remote pressure compensating is the same as the integral pressure compensating except another pressure control valve is placed in parallel with the PC Control Cartridge.
The supply port of the remote pressure control valve needs to be ported to the RP port on the valve plate (43). The exhaust from the remote pressure control valve needs to be ported to the HP port on the valve plate. When pump outlet pressure reaches the preset pressure setting of the remote control valve, bias pressure D [pressure on the spring side of the control piston (19)] is relieved by the remote control valve. Exhaust flow from the remote control valve is ported to the pump case via the sequence spool (54). The resulting pressure drop across the sequence spool due to the exhaust flow mov es th e spool to block the flow path. All flow to the remote control valve is now provided via the stability orifice OP2 (68). Blocking the flow path and requiring all control flow to pass through OP2
Bulletin 947070-B THE OILGEAR COMPANY 13
minimizes case drain leakage and provides a means of stability adjustment for a wide range of system requirements.
6-1
6-6
69
LS
P
The decrease in bias pressure results in a pressure differential across the control piston (19). The control piston is no longer balanced and the pressure on the unloading side of the control piston forces the control piston to compress the control piston spring (20). The control piston moves the control pin and shifts the swashblock to a position that provides less flow output from the pump. Flow output from the pump is then controlled to maintain the preset pressure setting of the remote pressure control valve. When the outlet port of the pump is blocked, the swashblock is positioned so the pump delivers just enough volume to provide for internal losses and required control flow.
Relatively small variations in system flow requirements can be accommodated for in the mentioned operational mode, but, when pump outlet pressure decreases below the preset pressure setting of the remote control valve, the remote control valve closes. The sequence spool spring (53) repositions the sequence spool to open the flow path. This provides for an unobstructed flow path to the bias side of the control piston so the pump will be responsive to increased system flow demand. If the setting of the remote pressure control valve exceeds the setting of the PC Control Cartridge, the pump will control to the setting of the PC Control Cartridge.
NOTE
Failure to port the exhaust of the remote pressure control valve to the HP port will result in significantly higher case drain leakage.
6-2
68
20
S
19
OILG0118
HP
RP
6-5
(6-1) PC Control Cartridge (6-2) Stability Orifice (6-3) Bias D (6-4) Outlet C (6-5) Into Case (6-6) Load Sense Port
Figure 6. Standard Load Sensing with Pressure
Compensating Override
6-3 6-4
Standard Load Sensing with Pressure Compensator Override - Figure 6
The parts configuration for the Standard Load Sense control is similar to the Pressure Compensator control except for the installation of a plug. All other components are unchanged. A 1/16 inch pipe plug is supplied with all new pumps. The plug is installed in a blind hole next to the LS port for all pumps originally shipped as a Pressure Compensator control or Adjustable Load Sense control. The plug (69) is already installed in the correct location (and the blind hole is empty), if the pump was originally shipped as a Standard Load Sense.
NOTE
The RP lines of multiple pumps cannot be tied together for unloading or controlling with a common remote pressure control valve. Each pump requires a dedicated valve.
14 THE OILGEAR COMPANY Bulletin 947070-B
To convert to a Standard Load Sense from a Pressure Compensator control, install the pipe plug (69) deep into the LS port of the valve plate as shown in Figure 6.
NOTE
The pipe plug threads start approximately
1.7 inch (0.043 mm) from the port spotface.
Standard Load Sense control requires the load sense line (pressure signal from downstream of an orifice or flow control valve) be attached at the LS port on the valve plate assembly. Load sense pressure is ported via the sequence spool and stability orifice to the bias side of the control piston (19). The pressure differential across the system
flow control is therefore equal to the pressure differential across the control piston; when the pressure differential reaches the non-adjustable preload force of the control spring, the control piston moves toward the neutral position. The control piston moves the control pin and shifts the swashblock to a position that reduces pump delivery to maintain a constant, preset pressure differential across the flow control v alv e . The preset pressure differential is 150 to 210 psi (10,3 to 14,5 bar). If the pressure differential across the flow control valve is decreased, t he control piston spring (20) moves the control piston in the full stroke direction until pump delivery is increased sufficiently to reach the preset load sense differential pressure. When the pump outlet is blocked and the load sense pressure is allowed to go to drain pressure, the swash is positioned so that the pump delivers just enough volume to provide for internal losses and required control flow at a standby pressure equal to the preset pressure differential of 150 to 210 psi (10,3 to 14,5 bar).
The pressure compensating function will override the load sense control and, if necessary, further reduce pump delivery when the load sense pressure reaches the preset pressure of the PC Control Cartridge.
7-1
7-4
7-5
Figure 7. Adjustable Load Sensing with Pressure
LS
HP
RP
(7-1) PC Control Cartridge (7-2) Stability Orifice (7-3) Into Case (7-4) Load Sense Port (7-5) Adjustable Load Sense Cartridge
LS
54
53
7-3
D
Compensating Override
68
7-2
20
P
S
19
OILG0117
Adjustable Load Sensing w/ Pressure Compensator Override - Figure 7
The Adjustable Load Sense control functions similar to the Standard Load Sense control except it is adjustable from 150 to 600 psi (10,3 to 41,4 bar).
The Adjustable Load Sense Cartridge is located adjacent to the PC Control Cartridge on the valve plate. The Adjustable Load Sense does not require the installation of the 1/16 inch pipe plug in the standard load sense port as previously described. The standard load sense port should be plugged with an SAE #4 plug. Adjustable Load Sense control requires the load sense line [pressure signal from downstream of an orifice or flow control valve] be attached to the end of the Adjustable Load Sense Cartridge.
When load sense pressure differential reaches the preset pressure setting of the Adjustable Load Sense Cartridge, bias pressure D [pressure on the spring side of the control piston (19)] is relieved by the Adjustable Load Sense Cartridge. Exhaust flow from the Adjustable Load Sense Cartridge is ported to the pump case via the sequence spool. The resulting pressure drop across the sequence spool (54) due to the exhaust flow moves the spool to block the flow path. All flow to the Adjustable Load Sense Cartridge is now provided via the stability orifice OP2 (68). Blocking the flow path and requiring all control flow to pass through OP2 minimizes case drain leakage and provides a means of stability adjustment for a wide range of system requirements.
The decrease in bias pressure results in a pressure differential across the control piston (19). The control piston is no longer balanced and the pressure on the unloading side of the control piston forces the control piston to compress the control piston spring (20). The control piston moves the control pin and shifts the swashblock to a position that provides less flow output from the pump. Flow output from the pump is then controlled to maintain the preset pressure differential setting of the Adjustable Load Sense Cartridge. When the outlet port of the pump is blocked, the swashblock is positioned so the pump delivers just enough volume to provide for internal losses and required control flow at a standby pressure equal to the differential pressure setting of the Adjustable Load Sense Cartridge.
Bulletin 947070-B THE OILGEAR COMPANY 15
Relatively small variations in system flow requirements can be accommodated for in the mentioned operational mode, but, when pump outlet pressure decreases below the preset differential pressure setting of the Adjustable Load Sensing Cartridge, the Adjustable Load Sensing Cartridge closes. The sequence spool spring (53) repositions the sequence spool to open up the flow path. This provides for an unobstructed flo w path to the bias side of the control piston so the pump will be responsive to increased system flow demand. The pressure compensating function will override the load sense control and, if necessary, further reduce pump delivery when the load sense pressure reaches the preset pressure of the PC Control Cartridge.
Electronic Proportional Pressure Compensator with Override - Figure 8
The Electronic Proportional Pressure Compensator functions the same as the Pressure Compensating Control (refer to Figure 4) except the PC Control Cartridge is electrically controlled. An electrical signal is used to proportionally increase or decrease the pressure compensator setting with increasing current. A manually adjustable PC Override Valve enables the user to set the maximum desired pressure compensator setting.
NOTE
An Adjustable Load Sense control is also available with a bleed-off feature. This cartridge internally vents load sensing pressure to case via an orifice in the cartridge and the sequence spool when the control is not active or the system is shutdown.
8-2
8-1
LS
HP
RP
LS
8-8
8-9
8-7
8-3
P
S
8-4
8-5
8-6
(8-1) PC Override Cartridge (8-2) Electronic Proportional Control Cartridge (8-3) Sequence Spool (8-4) Stability Orifice (OP2) (8-5) Control Piston (8-6) Control Pin (8-7) Cylinder Barrel (8-8) Piston (8-9) Swashblock (8-10) Into Case
Figure 8. Electronic Proportional Pressure
16 THE OILGEAR COMPANY Bulletin 947070-B
OILG0170
Compensator with Override
TESTING AND ADJUSTING
WARNING
!
Shut the pump OFF and release pressure from the system before disassembling components. Failure to comply with these instructions could result in personal injury or death. Blocking the pressure line between the pump and the system (or pump) high pressure relief valve will result in damage and could result in serious personal injury.
PISTON PUMP
To check for a worn piston pump, make a leak measurement test from the case drain while the pump is under pressure. After the unit is warm, either install a flow meter in the drain line or have the flow from the drain line directed into a large container or reservoir. The pump case must remain full of fluid during this test.
CAUTION
DO NOT run a pump on stroke against a blocked output unless it is protected by a high pressure relief valve and then run no longer than necessary to check slip. Limit discharge to prevent dropping reservoir fluid below low level.
With an accurate high pressure gauge in the pressure line, start the pump and stall (or block) output device to raise system pressure to maximum (as set by system relief valve). Read the measurement on the flow meter or time and measure the case drain flow used to fill a known size container and calculate the flow rate in terms of cubic inches per minute (cipm). The leakage should conform to Table 5.
NOTE
Additional leakage indicates wear, but does not become critical until it impairs performance.
DISASSEMBLY
Refer to pump.
NOTE
DO NOT attempt to remove or install any components or assembly while the pump and system is running. Always stop the pump, shut OFF the power and release pressure from the system before servicing or testing. Be sure provisions have been made so the case drain line can be disconnected from the unit without causing the line to drain (siphon) the reservoir.
1. Disconnect case drain line(s).
2. Drain pump case. If drain pump case plugs are
Figures 9 through 15
The cleanliness of working on this pump or the hydraulic system is extremely important to the safety and reliability of the pump and the system.
When disassembling or assembling the pump, choose a clean, dry, dust and sand free area where no traces of abrasive particles are in the air which can damage the pump and system. DO NOT work near welding, sandblasting, grinding benches or similar conditions.
Always make sure the fittings are clean on the outside before removing them from their connections. Make sure they are capped and plugged when removed. Place them on a clean surface and in a clean rag or container until they are reinstalled. When cleaning parts which have been disassembled, it is important to use CLEAN cleaning solvents and parts are allowed to dry. All tools and gauges should be clean prior to working with the system and use new, CLEAN lint free rags to handle and dry parts.
WARNING
!
inaccessible, it may be necessary to remove the pump from the mounting and drive motor before draining it.
for your series of
Bulletin 947070-B THE OILGEAR COMPANY 17
(continued)
DISASSEMBLY (Continued)
CAUTION
WARNING
!
Seek assistance from others and use of a hoist and/or proper lifting techniques to prevent personal injury.
NOTE
3. After removing the pump from the mounting
NOTE
VALVE PLATE GROUP
If another pump is coupled with a thru-shaft pump or other device coupled to the rear of the pump, it will be necessary to remove that unit and O-ring (59). If thru-shaft convertible cover (63) is used, remove the socket head cap screws (64) and O-ring (62). Also remove screw (61) and thru-shaft coupling spacer (60).
Tag similar par ts (particularly screws, plugs and O-rings) during disassembly to make sure they don't become confused with similar parts and to ensure they will be returned to their original location. Do not remove (locator) roll pins unless they are deformed or need to be replaced.
and before disassembly, cap or plug all ports and clean the outside of unit thoroughly to prevent dust from entering the system.
Depending on what part or par ts are to be inspected, it may not be necessary to completely take apart all assemblies.
Do not damage the faces of the port plate and the matching faces of both the valve plate and cylinder barrel.
1. Block the unit on bench with driveshaft horizontal.
2. Remove valve plate assembly (45) by removing four socket head cap screws (50 and 56) and the valve plate assembly. When used, shaft coupling (57) with retaining rings (58), if used, will come with valve plate assembly. The port plate (43) is located on the valve plate assembly by a dowel pin. Remove the port plate from the valve plate assembly.
The control sequence valve can be removed, if necessary by:
(A) Removing the sequence valve spool plug
(51) with the O-ring (52).
(B) Withdrawing sequence valve spool spring
(53) and sequence valve spool (54).
The PC control cartridge (55) can also be unscrewed from the valve plate if necessary. The rear shaft bearing (67 or 77) is pressed into the valve plate.
18 THE OILGEAR COMPANY Bulletin 947070-B
Frame Unit - Size
SAE “A” PVM-011
SAE “A” PVM-014
SAE “A” PVM-022
SAE “B” PVM-025
SAE “B” PVM-034
SAE “B” PVM-046
SAE “B” PVM-065
SAE “B” PVM-075
SAE “C” PVM-064
SAE “C” PVM-076
SAE “C” PVM-098
SAE “C” PVM-130
Case Slip at Full Stroke and Indicated Pressure
500 psi 1000 psi 2000 psi 3000 psi 3750 psi
cipm 25.0 40.0 75.0 110.0 160.0
lpm0,410,661,23 1,80 2,62
cipm 35.0 50.0 80.0 120.0 170.0
lpm0,570,821,31 1,97 2,79
cipm 55.0 90.0 145.0 210.0 300.0
lpm0,901,472,38 3,44 4,92
cipm 75.0 115.0 185.0 270.0 360.0
lpm 1,23 1,88 3,03 4,42 5,90
cipm 70.0 105.0 175.0 255.0 340.0
lpm 1,15 1,72 2,87 4,18 5,57
cipm 70.0 105.0 180.0 280.0 365.0
lpm 1,15 1,72 2,95 4,59 5,98
cipm 95.0 135.0 205.0 300.0 400.0
lpm 1,56 2,21 3,36 4,92 6,55
cipm 140.0 190.0 290.0 450.0 650.0
lpm 2,29 3,11 4,75 7,37 10,65
cipm 90.0 135.0 230.0 345.0 460.0
lpm 1,47 2,21 3,77 5,65 7,54
cipm 90.0 145.0 245.0 390.0 580.0
lpm 1,47 2,384,016,399,50
cipm 125.0 180.0 280.0 560.0 860.0
lpm2,082,954,599,1814,09
cipm 135.0 210.0 370.0 580.0 810.0
lpm 2,21 3,44 6,06 9,50 13,27
Table 5. NOMINAL CASE SLIP versus High Pressure at 1800 rpm
[All data is for ISO 46 mineral-based oil at 125°F (160 SSU)]
Bulletin 947070-B THE OILGEAR COMPANY 19
ROTATING GROUP
WARNING
!
The rotating group may be heavy. Be careful not to damage cylinder wear surface which mates against the valve plate, bearing diameters or piston shoes. Use proper lifting techniques and assistance from others to prevent personal injury.
-011/-014/-022
5. Remove cylinder barrel retaining ring (37) and pull the hydrodynamic cylinder bearing (35) and roll pins, if necessary, from the housing.
-025/-034/-046/-064/-065/-075/
-076/-098/-130
5. Remove the hydro-bearing retaining ring (37).
1. Remove O-rings (13 and 14) from the pump housing (1). Do not remov e roll pins (12) unless they are damaged.
2. Remove the rotating group by turning the driveshaft (21) slowly, while pulling the cylinder barrel (38) from the housing.
3. Identify (number) each pump piston shoe assembly (39) and its respective bore in the cylinder barrel (38) and shoe retainer plate (40) for easy reassembly.
4. See Figure 9. Lift out shoe retainer (40) with pistons (39) and remove the fulcrum ball (41) and shoe retainer spring (42).
40
39
41
42
38
6. Remove socket head screw (36) and lock washer (5).
7. Pull hydrodynamic cylinder bearing (35) from housing.
DRIVESHAFT GROUP
1. Remove the drive key (22 or 23), if used and the driveshaft bearing retainer ring (28).
2. Grasp outboard end of driveshaft (21) and pull it out of the pump housing.
3. Remove shaft seal retainer (25). Remove driveshaft seal (24) from housing ONLY if necessary.
NOTE
If the seal is removed it can not be reused. It must be replaced.
SWASHBLOCK GROUP
1. Remove the socket head cap screws (34), the housing cover (33) and O-ring (32).
2. Reach into the housing through the opening and pull out the swashblock (29), along with control pin (31).
The saddle bearing (30) is seated in the housing by an integral pintle that engages a hole in the housing.
Figure 9. Rotating Group Disassembly
20 THE OILGEAR COMPANY Bulletin 947070-B
OILG0023
3. Pull the saddle bearing (30) back (parallel to
driveshaft axis) until the pintle disengages from the housing, then pull the saddle bearing out in the same manner the swashblock was removed.
Loading...
+ 44 hidden pages