Odyssey CT80-250, CT80.3F9A1, CT120.3G9A, CT215.1H9A, CT80.3P9A1 Installation And Operation Instructions Manual

...
Page 1
Odyssey
Danger Sign: Indicates a hazardous situation which, if not avoided, will result in
Warning Sign: Indicates a hazardous situation which, if not avoided, could result
bol: Indicates a hazardous situation which, if
Caution Sign without Safety Alert Symbol: Indicates a hazardous situation
es a hazardous situation which, if not avoided, could result
H
Model Numbers: CT80-250 Version Date: 2013-03-15
NEW – OUTDOOR SENSOR
Meets Sept. 2012 requirements for
“Automatic Means”
INSTALLATION AND OPERATION INSTRUCTIONS ODYSSEY OIL BOILER
TABLE OF CONTENTS
1.0 INTRODUCTION...............................................................................................................3
2.0 SPECIFICATIONS..............................................................................................................6
3.0 BOILER LOCATION..........................................................................................................8
4.0 BOILER ASSEMBLY.........................................................................................................9
5.0 GENERAL VENTING......................................................................................................14
6.0 NATURAL DRAFT APPLICATIONS.............................................................................15
7.0 DIRECT VENT APPLICATIONS....................................................................................19
8.0 BOILER PIPING...............................................................................................................26
9.0 FIELD WIRING................................................................................................................28
10.0 INSTALLATION CHECKLIST .......................................................................................34
11.0 ANNUAL MAINTENANCE AND INSPECTION ..........................................................36
12.0 PARTS LIST .....................................................................................................................39
13.0 WARRANTY....................................................................................................................43
Odyssey CT80-250
HAZARD SYMBOLS AND DEFINITIONS
serious injury or death.
in serious injury or death. Caution Sign plus Safety Alert Sym
not avoided, could result in minor or moderate injury.
which, if not avoided, could result in property damage. Notice Sign: Indicat
in property damage.
This Boiler must be installed by a licensed and trained Heating Technician or the Warranty is Void. Failure to properly install this unit may result in
property damage, serious injury to occupants, or possibly death.
NTI # 84944
Page 2
Odyssey
Read Before Proceeding
Installation and Operation Instructions CT80-250
If you do not follow these instructions exactly, a fire may result causing property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING_
BEFORE OPERATING: A. Do not start burner unless the smoke hood, clean out door, HydroStat 3250, flue breeching, and burner
door (if applicable) are secured in place and the boiler is filled with water.
B. Do not attempt to starter burner when excess oil has accumulated in combustion chamber, when unit is
full of vapour, or when combustion chamber is very hot.
C. Do not use gasoline, crankcase drainings, or any oil containing gasoline. D. Never burn garbage or paper in the unit and never leave combustible material around it. E. Always keep the oil supply valve shut off if the burner is shut down for an extended period of time. F. Do not tamper with the unit or controls - call your service personnel for service and maintenance. G. Do not use this boiler if any part has been under water. Immediately call a qualified service technician to
inspect the under water.
boiler and to replace any part of the
OPERATING INSTRUCTIONS_
control system and any oil control which has been
1. STOP! Read the safety information above very carefully.
2. Initial start-up and start-ups after periods of extended/seasonal shutdown must be performed by a
qualified service technician.
3. Check the boiler area for proper clearances.
4. Turn the thermostat(s) up.
5. Turn the emergency power isolation switch on.
6. If ignition does not occur, follow the instructions “To Turn Off Oil Boiler” and call a qualified service
technician.
TO TURN OFF OIL BOILER_
1. STOP! Read the safety information above very carefully.
2. Turn off emergency power isolation switch. Should be mounted on the wall near entrance to boiler room.
Void Warranty - This boiler must have water in it whenever the burner is on or it will damage the unit and void the warranty. Failure to follow these instructions may result in
serious injury or death.
Fuel Oil - Use only No. 2 fuel oil for boiler models listed in this manual. Failure to follow these instructions may result in severe personal injury, property damage, or death.
Low Water Cut Off (LWCO) - To take advantage of the HydroStat’s LWCO feature, the
Odyssey is equipped with a special immersion well call the Electro-well™. Failure to use the Electro-well™ provided with the boiler will over-ride the LWCO feature and allow the boiler to operate during low water conditions which may result in over heating, fire, serious injury, or death.
Oil Supply Valve - Always keep the oil supply valve shut off if the burner is shut down
for an extended period of time.
2
Page 3
CT80-250 Introduction - Installation & Operation Instructions
1.0 INTRODUCTION
Odyssey
General Installation Requirements
The installation of your NTI Odyssey oil boiler shall be in accordance with these instructions and the regulations of the authorities having jurisdiction and must comply with the following codes and standards:
United States
State and local plumbing, heating, and electrical codes NFPA 70 National Electric Code NFPA 31 Installation Code for Oil Burning Equipment Standard ANSI/ASME CSD-1, Controls and Safety Devices for Automatically Fired Boilers (if applicable)
Canada
Provincial and local plumbing, heating, and electrical codes CSA C22.1 Canadian Electrical Code Part One CSA B139 Installation Code for Oil Burning Equipment
The Odyssey is a knock-down boiler constructed of cast iron. The venting application needs to be decided in advance, either Natural Draft or Direct Vent, prior to ordering the boiler as burner packages will vary depending on the venting application. The boiler package comes in three sections and requires field assembly. Check your boiler package when it arrives and ensure it includes the following:
1. Boiler
2. Jacket
3. Burner Kit This document pertains to the correct installation and operation of NTI Odyssey oil boilers for Natural Draft and
Direct Vent models. The instructions detailed in this document supersede any and all previous instructions provided by NTI, written or otherwise. The warranty is included in the Installation and Operation manual. Each unit comes complete with the following documentation:
1. Installation and Operating Instructions
2. Users Manual
Read and understand this entire document prior to proceeding with the installation of the
Odyssey. Failure to follow the instructions outlined in this document will result in property damage, serious injury or death.
User Responsibilities
This boiler must be installed and serviced by a qualified installer or service technician. This boiler must be serviced and inspected annually. As the User/Owner of this equipment, you are responsible for ensuring the maintenance is performed at the required intervals. See “Users Manual”.
Failure to have the boiler properly serviced and inspected on a regular basis by a qualified
service technician may result in property damage, serious injury or death.
Installer Responsibilities
As the installing technician it is your responsibility to ensure the installation is performed in accordance with this instruction manual as well as any applicable local or National installation codes. It is also your responsibility to inform the User/Owner of their obligation with respect to the above description under “User Responsibilities”. Failure to follow this warning could result in fire, serious injury, or death.
3
Page 4
Odyssey
Natural Draft Applications
Installation and Operation Instructions - Introduction CT80-250
Natural Draft Applications - All Odyssey models are certified as Natural Draft boilers
which require a “Chimney System”. The exhaust gases must be vented directly to the
chimney. Failure to follow these instructions will result in serious injury or death.
Blocked Vent Switch - All Natural Draft Odyssey boilers require a Blocked Vent Switch
which is factory supplied and packaged with the burner kit and is mandatory in Canada. The Block Vent Switch must be field installed as per the instructions in this manual and the manufacturers instructions included with the switch. Failure to follow the specified instructions may result in fire, property damage, personal injury, or death.
Table 1-1 Odyssey Boiler Packages (Natural Draft)
MODEL
4
CT80
4
CT90
4
CT100
BOILER PACKAGE
BOILER PART NUMBER
Boiler
CT80.3F9A1 CT80
Burner Kit
Jacket
Natural
Draft 1
Only
Burner
82002
F3.CT
10618
Burner Kit Contents (Natural Draft)
2
Blast Tube
Nozzle
HydroStat
3250
Hydrolevel
0.65
o
60
84024
W
Tridicator
Electro-Well
OD Sensor
Relief Valve
Supply Tee
Block Vent
CT120
84654
0.85
60oB
1.5
60o W
0.75
70oB
84787
84788
81342
83604
13701
84829
CT150 CT180
Riello Burner
CT215 CT230 CT250 CT80 CT90 CT100
CT120.3G9A
1
4
CT215.1H9A1 CT215
4
4
CT80.3P9A1 CT80
4
CT120
F5.CT
3
10630
82003
F10.CT
82004
NYC601CT 81031
10632
82002
CT120 CT150 CT180
Becket Burner
CT215 CT230
CT120.3P9A1
4
CT215.3P9A1 CT215
CT120
CT250
Notes:
1
Boiler manual packaged with the Burner Kit.
2
Nozzle size included in Burner Kit. See below, “Attention: Nozzle Sizes”.
3
Burner and blast tube comes assembled c/w nozzle specified in this table. Nozzle may need to be changed depending on boiler output.
4
Models CT80-100 and CT180 are no longer offered as they do not meet new minimum efficiency regulations.
NYC602C T
82003
NYC602C T
82004
81032
81032
1.10
60oB
1.10
60oB
Nozzle Sizes - The nozzle sent with each respective boiler burner kit is for the minimum
firing rate specified for that burner. To obtain a different firing rate, replace the factory supplied nozzle with the appropriate nozzle that meets the desired output. Refer to Tables 2-1 to 2-2 in Section
2.0 for nozzle specifications and performance ratings for Natural Draft boilers.
Manufacturer’s Instructions - For complete instructions on installation and control
operations, refer to the manufacturer’s instructions included with the Fuel Smart HydroStat 3250, Burner Package, and Blocked Vent Switch.
Switch
82905
4
Page 5
CT10
0
CT80-250 Introduction - Installation & Operation Instructions
Odyssey
Direct Vent Applications
There are four Odyssey models, CT90-120, certified for installation as a Direct Vent boiler. This balanced flue system requires a special venting system in order to pressurize and essentially equalize the inlet and outlet pressure to ensure normal operation. Refer to section “General Venting” and “Specifications” for more details on Direct Vent applications and termination kits.
Balanced Flue Applications - Models CT90-120 are also certified as Direct Vent boilers
and must be ordered as such. Balance flue systems must use the NTI approved venting system. Note that the Direct Vent Terminal and Insulated Flex Pipe are sold separately (see Table 7-2 Direct Vent Kit Components for more details). This “Special Venting System” is designed for pressurized venting with NTI Direct Vent boilers. The exhaust gases must be piped directly to the outdoors using the vent materials and rules outlined in these instructions. Failure to follow these instructions will result in serious injury or death.
Table 1-2 Odyssey Boiler Packages (Direct Vent)
BOILER PACKAGE
Burner Kit Contents (Direct Vent)
Jacket
82002
82003
Burner
Kit
Direct
Vent
BF5.CT
BF5.CT
2
1
3
3
Burner
Blast Tube
Nozzle
HydroStat
3250
Hydrolevel
Electro-Well
Tridicator
OD Sensor
Relief Valve
81122
81122
0.85
60oB
0.85
60oB
84787
84788
81342
83604
13701
4
Supply Tee
Direct Vent
84829
Table 7-2
BOILER
MODEL
CT90
PART NUMBER
6
Only
Boiler
CT90.3T9A4 CT80
6
CT120
Riello Burner
Notes:
1
Boiler manual packaged with the Burner Kit.
2
Nozzle size included in the Burner Kit. See below, “Attention: Nozzle Sizes”.
3
Burner and blast tube comes assembled c/w nozzle specified in this table. Nozzle may need to be changed depending on boiler output.
4
Direct Vent Terminal not included in Kit. Refer to Table 7-2 for a list of components that must be ordered separately.
5
Riello BF5 burners are single line gravity feed. See burner manufacturers’ instructions for more details.
6
Models CT80-100 are no longer offered as they do not meet new minimum efficiency regulations.
CT120.3T9A4 CT120
Manufacturer’s Instructions - For complete instructions on installation and control operations, refer to the manufacturer’s instructions included with the Fuel Smart
HydroStat 3250, Burner Package, and Direct Vent Terminal.
Nozzle Sizes - The nozzle sent with each respective boiler burner kit is for the minimum
firing rate specified for that burner. To obtain a different firing rate, replace the factory supplied nozzle with the appropriate nozzle that meets the desired output. Refer to Table 2-3 in Section 2.0 for nozzle specifications and performance ratings for Direct Vent boilers.
Intakes/Vents - Failure to keep the Vent and Combustion Air Intake clear of ice, snow,
and other debris may result in property damage, serious injury, or death.
which is provided primarily to permit the use of an external energy management system that serves the same function. THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE :
An external energy management system is installed that reduces the boiler water temperature as the heating load
decreases.
This boiler is not used for any space heating. This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater. This boiler is equipped with a tankless coil.
Energy Saving Feature - This boiler is equipped with a feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an override
Kit
5
Page 6
Odyssey
2.0 SPECIFICATIONS Natural Draft Application
Installation and Operation Instructions - Specifications CT80-250
Draft Settings (Natural Draft) - The Odyssey is designed to operate with -.03” w.c. draft
in the flue breaching. For proper operation, there must be enough natural or mechanical draft. Due to the design of the Odyssey, it may operate at a positive over fire pressure up to +.20 at -.03 draft. Due to installation and equipment variations, recommended air settings are a guideline and will require alteration. See Tables 2-1 and 2-2.
Insertion Depth (Natural Draft) - See General Notes section in Tables 2-1 and 2-2.
Table 2-1 Riello Burners with Odyssey Boilers (Natural Draft)
Boiler Model
CT80 CT90 CT100
8
8
Input
GPH (US)
0.65 77 67
0.75 88 77
8
0.85 99 86 CT120 1.00 121 105 CT150 1.25 149 130
8
CT180
1.50 176 153 CT215 1.75 212 184 CT230 1.85 223 194 CT250 2.00 240 209
General Notes:
1
Output is “Heating capacity” for models CT80-250.
2
Models CT80-250 use Riello 40 series burners.
3
Energy ratings for C85-250 have been confirmed by AHRI.
4
Models C80-100 - F3 burners have an insertion depth of 2.375”.
5
Models C120-180 - F5 burners come assembled with an insertion depth of 2.375”.
6
Models C215-250 - F10 burners have an insertion depth of 2.75”.
7
F10 burner heads - If head carbons on models CT215-250, reduce turbulator setting and increase air a little.
8
Models CT80-100 and CT180 are no longer offered as they do not meet new minimum efficiency regulations.
Table 2-2 Beckett Burners with Odyssey Boilers (Natural Draft)
Boiler Model
CT80 CT90 CT100
4
4
Input
GPH (US)
0.65 77 67
0.75 88 77
4
0.85 99 86 CT120 1.00 121 105 CT150 1.25 149 130
4
CT180
1.50 176 153 CT215 1.75 212 184 CT230 1.85 223 194 CT250 2.00 240 209
General Notes:
1
Models CT80-250 use Beckett AFG50 series burners.
2
Energy ratings for C85-250 have been confirmed by AHRI.
3
Models CT80-250 - MDL1 (NYC601) burners and MDV1 (NYC602) have an insertion depth of 3.75.
4
Models CT80-100 and CT180 are no longer offered as they do not meet new minimum efficiency regulations.
Heating
Capacity
MBH
Heating
Capacity
MBH
Net I=B=R
Rating Water
MBH
Net I=B=R
Rating Water
MBH
AFUE
Efficiency
%
83.6% 117
Pump
PSIG
Delevan
Nozzle
0.60 60oW
83.0% 133 0.65 60oW
82.4% 128 0.75 60oW
85.1% 138 0.85 60oW
84.0% 156 1.00 60oW
82.8% 144 1.25 60oW
85.8% 136 1.50 60oW
85.5% 152 1.50 60oW
85.0% 178 1.50 60oW
AFUE
Efficiency
%
83.6% 117
83.0% 133 0.65 60oW
82.4% 128 0.75 60oW
85.1% 138 0.85 60oW
84.0% 156 1.00 60oW
82.8% 144 1.25 60oW
85.8% 136 1.50 60oW
85.5% 152 1.50 60oW
85.0% 178 1.50 60oW
Pump
PSIG
Delevan
Nozzle
0.60 60oW
Recommended Burner Settings
Burner Air Turbulator
F3 5 0 F3 7 0 F3 7 2 F5 3 2 F5 5 2
F5 9 3.5 F10 F10
3.5 7
2 2
F10 6 3
Recommended Burner Settings
Burner
MBL1 MBL1
MBL1 MDV1 MDV1 MDV1 MDV1 MDV1 MDV1
Head Shutter
- 5 0.5
- 6 1
- 10 0 0 5 1 1 6 2 2 8 3 3 10 6 4 10 5 4 8 7
Band
6
Page 7
CT80-250 Specifications - Installation & Operation Instructions
Direct Vent Application
Odyssey
Draft Settings (Direct Vent) - Due to the design of the balanced flue system, the Odyssey
will operate at a positive draft pressure and a positive over fire pressure at all times. It is designed to operate with a maximum stack draft of 0.25” w.c. and a maximum over fire draft of 0.33” w.c. when little or no wind is present. In extreme wind conditions, the maximum stack draft is 0.35” w.c. and the maximum over fire draft is 0.45” w.c. Due to installation and equipment variations, recommended air settings are a guideline and will require alteration. See Table 2-3.
Insertion Depth (Direct Vent) - See General Notes section in Table 2-3.
Table 2-3 Riello Burners with Odyssey Boilers (Direct Vent)
Boiler Model
CT90 CT100
4
4
Input
GPH (US)
0.75 88 77
0.85 99 86
CT120 1.00 121 105
General Notes:
1
Models CT90-120 use Riello 40 series burners.
2
Energy ratings for CT90-120 have been confirmed by AHRI.
3
Models CT90-120 - BF5 burners come assembled with an insertion depth of 2.375”.
4
Models CT80-100 are no longer offered as they do not meet new minimum efficiency regulations.
Heating
Capacity
MBH
Net I=B=R
Rating Water
MBH
AFUE
Efficiency
%
83.0% 133
82.4% 128
85.1% 138
Pump
PSIG
Delevan
Nozzle
0.65 60oW
0.75 60oW
0.85 60oW
Recommended Burner Settings
Model Air Turbulator
BF5 4 BF5 BF5
5 6
0 0
1.5
Boiler Characteristics
Table 2-4 Odyssey Boiler Characteristics
Description
CT80-100 CT120-180 C215-250
Boiler Shell Weight [lbs] 260 390 500 Fuel Type No. 2 Oil Water Connections – NPT [in.] 1.25 1.25 1.25 Dimensions H x W x D [in.] Approx. Boiler Weight with Water [lbs] Approx. Boiler Water Content [usg] Stack Size Electrical Rating
30 x 17.5 x 15.5 30 x 25.5 x 15.5 30 x 33.5 x 15.5
290 435 560
3.6 5.4 7.3 5 5 5
120V / 1Ph / 60Hz / < 12A
Boiler Shell
7
Page 8
1, 2
Odyssey
3.0 BOILER LOCATION
Installation and Operation Instructions - Boiler Location CT80-250
In all cases, the Odyssey must be installed indoors in a dry location where the ambient temperature must be maintained above freezing and below 100°F [38°C]. All boiler components must be protected from dripping, spraying water, or rain during operation and servicing. Consider the proximity to the following when determining the best boiler location.
System Water Piping Oil Supply Electrical Power Combustion Air / Ventilation Air Chimney
Components - Water or flood damaged components must be replaced immediately with new components (see parts list). Failure to do so may result in fire, serious injury, or death.
Clearances - Clearances to combustibles represent the minimum clearances required for safety and service. Recommended clearances are for ease of piping installation, annual maintenance, and service access. Refer to Table 3-1 and Figure 3-1.
Table 3-1 Minimum Clearances for Installation and Service
Model Clearances
CT80-250
Notes:
1
Minimum clearances from flue pipe to combustibles is 9” for single-wall pipe; 6” for double-wall pipe (Type-L).
2
Flue pipe clearances take precedence over all other clearances.
To Combustibles 24 [610] 5 [124] 12 [305] 5 [124] 9 [228] Combustible Recommended 36 [915] 24 [610] 24 [610] 24 [610] 9 [228] Combustible
Front Rear Top Sides
Dimensions - inches [mm]
Flue Pipe
Floor
Boiler Location - Even if all installation codes are met, good judgment and common
sense must also be used when selecting a boiler location. Refer to minimum clearances in
Table 3-1 and vent clearances for chimney or direct vent applications.
Figure 3-1 Minimum Clearances to Combustibles
Flue Pipe
9” minimum
Flue pipe clearances take precedence over all clearances, refer to Table 3-1.
Rear 5”
8
Top 12”
Right Side 5”
Front 24”
Left Side 5”
Page 9
nuts and washers at
the rear of the boiler
C 85-340 Boiler Assembly - Installation & Operation Instructions
4.0 BOILER ASSEMBLY
Odyssey
The installation of the boiler shall be in accordance with the authorities having jurisdiction and must comply with Standard CSA B139 (Canada) or NFPA 31 (USA).
Fiberglass Materials - Before installing the insulation, read “Handling Instructions” in Section 11.0 and the protective measures recommended when handling fiberglass.
Assembly Procedure
The boiler assembly procedure is to be completed in sequence and in conjunction with the illustrated assembly diagrams, Figures 4-1 through 4-12.
1. Do not fully tighten screws until jacket assembly is complete.
2. Level the boiler before commencing jacket installation.
3. Install rear brackets on the boiler, secure by tightening nuts (Figures 4-1 to 4-3).
4. Install front brackets on the boiler, secure by tightening nuts (Figures 4-4 to 4-6).
5. Install fiberglass insulation on the boiler by wrapping it around the heat exchanger. Secure with factory
supplied twine (Figure 4-7).
6. Remove all protective plastic film on the jacket panels before installing.
7. Attach side panels to front and back brackets (Figure 4-8).
8. Install control panel between side panels, secure with screws provided (Figure 4-9).
9. Mount HydroStat 3250 by sliding it down over the tabs on the control panel. Secure in place with hold down
bracket as shown (Figure 4-10).
10. Mount bottom back panel to boiler (Figure 4-10); Recommend installing top back panel after flue breeching
connected, sealed, and supported. (See also Figure 6-1 Flue Breeching).
11. Fully tighten all jacket screws to secure panels in place.
12.
Insert sensor fully into the Electro-well or boiler overheating may occur (Figure 4-11). See “Danger” warning on page 11.
13. Feed the green wire, connected to the boiler ground screw, through the knockout in the back of the HydroStat.
Connect the other end of the wire to the HydroStat ground screw inside the control (green screw).
14. Installation of burner and completion of wiring must be done with front cover removed.
15. Install top cover. Align the top panel clips into the slots in the top of the side panels and slide cover forward
to lock clips in place (Figure 4-12).
HydroStat 3250 Instructions - For complete installation and operation instructions, refer to the manufacturer’s instructions included with the Fuel Smart HydroStat 3250.
Figure 4-1 Rear Brackets Figure 4-2 Mount Rear Brackets
Top
Bottom
Slide the rear brackets behind the
as shown.
9
Page 10
Tighten the nuts,
Before installing the insulation, read the
Remove protective
plastic coating from
Odyssey
Installation and Operation Instructions - General Venting CT80-250
Figure 4-3 Tighten Bracket Nuts (Rear) Figure 4-4 Front Brackets
Tighten nuts, top and bottom, to secure the rear brackets to the boiler.
Figure 4-5 Mount Front Brackets Figure 4-6 Tighten Bracket Nuts (Front)
Top
Bottom
Slide the front brackets behind the nuts and washers at the front of the boiler.
Insulation
Twine
top and bottom, to secure the front brackets to the boiler.
See Figure 4-6
Figure 4-7 Insulate Heat Exchanger Figure 4-8 Attach Side Panels To Brackets
“Handling Instructions” in Section 11.0.
all jacket pieces before installing.
Install insulation around the heat exchanger and secure in place with factory supplied twine.
Attach both side panels to brackets using sheet metal screws provided.
10
Page 11
C 85-340 Boiler Assembly - Installation & Operation Instructions
side panels, secure
the HydroStat 3250
to the control panel
Secure bottom back panel.
Ground Wire
- Connect green
wire between ground screw
Installation of burner and
Figure 4-9 Attach HydroStat 3250 Bracket Figure 4-10 Attach Back Panels & Electro-well
Odyssey
Control Panel
Recommend installing top back after flue breeching connected and sealed.
Hold Down Bracket
HydroStat 3250
Attach hold down bracket
Attach the control panel between the
as shown.
Figure 4-11 Install Ground Wire and Sensor Figure 4-12 Install Top and Front Covers
to top edge of HydroStat control panel to secure it in place.
completion of wiring must be done with front cover removed.
See Figure 4 -11
Ground Screw
Electro-well
and HydroStat ground screw. Sensor - Insert fully into the
Electro-well or overheating may occur. See “Danger”.
Sensor - Insert the sensor fully into the Electro-well or the boiler may overheat resulting in fire, property damage, serious injury, or death.
11
Page 12
Odyssey
Installation and Operation Instructions - General Venting CT80-250
Burner Installation
The Odyssey boiler is designed to work with burners described in this manual. The use of other nozzles, and/or burners, may cause unsafe operation and will void any and all responsibility by NY Thermal for the safety and reliability of the system.
The burner kit should be installed in accordance with the instructions in this manual and the burner manufacturer’s instructions included with the burner. Refer to specification Tables 2-1 to 2-3 for nozzle sizes, burner settings, insertion depths, and air setting guidelines.
Fuel Oil - Odyssey boilers operate with No. 2 oil as their only approved fuel source. DO NOT USE GASOLINE, CRANKCASE DRAININGS, OR ANY OIL CONTAINING
GASOLINE. Failure to follow these instructions may result in severe personal injury, property damage, or death.
Combustion Analyzer -
capable of measuring CO
To calibrate burner operation, use a calibrated combustion analyzer
2
and O2 from oil burning boilers
Smoke Test - All tests must be done with the burner covers or air intakes in place to simulate normal operation.
Smoke Pump - A reliable, certified smoke pump is required to correctly set up this equipment.
Avoid Condensation - Due to the high combustion efficiencies and low stack gas temperatures, great care must be taken to ensure the chimney isn’t subjected to flue gas
condensation. The gas temperature where the flue pipe enters the chimney must be a minimum of 240oF.
Burner Installation Procedure:
1. Burner Package: a. Prepare the burner in accordance with the burner manufacturers instructions included with the burner. b. Refer to specification Tables 2-1 to 2-3 to determine the appropriate nozzle size for the boiler output. See
“Attention: Nozzle Sizes” in Section 2.0.
c. Riello Burners (extra step required): Mount the burner gasket and burner flange to the boiler. Secure to
the boiler using washers and nuts provided (Figure 4-5). Seal around the burner gasket and the blast tube ring with high temperature silicone (i.e. 83ml tube of silicone included in the burner kit).
d. Mount prepared burner package to the boiler. Seal around burner flange with high temperature silicone.
Combustion Air Settings - Refer to Section 10.0 Installation Checklist for instruction regarding adjusting combustion air settings.
Oil Supply Tank and Oil Piping
The oil supply tank and piping should be installed in accordance with the instructions in this manual; the burner and pump manufacturer’s instructions; National codes NFPA 31 (USA) or CSA B139 (Canada), and local codes.
General Installation Guidelines:
1. Install the oil supply tank as per tank manufacturer’s instructions.
2. Install oil supply piping from the tank to the burner.
3. Recommend installing a low pressure-drop fuel oil filter to prevent burner nozzles plugging at low flow rates.
4. Shut-off valves should be installed to control the flow during operation and to avoid spills during servicing.
5. Oil can be fed from the supply tank by gravity (single pipe system) or by transfer pump (two-pipe lift system).
6. Refer to burner manufacturer’s instructions before installing oil piping systems as some burner packages are not equipped to work with two-pipe lift systems (i.e. Riello BF5).
7. Connect oil supply piping to the fuel oil pump as per the pump manufacturer’s instructions and system type.
Pipe Dope / Teflon Tape - DO NOT use on direct oil connection to the fuel pump. Failure to follow instructions may cause valve failure and dangerous operating conditions.
12
Page 13
C 85-340 Boiler Assembly - Installation & Operation Instructions
Figure 4-5 Burner Installation
Prepare the burner as per the burner manufacturer’s instructions. Refer to Tables 2-1 to 2-3 for nozzle sizes, burner settings, insertion depths, air settings, and specifications.
Set insertion depth (Tables 2-1 to 2-3)
Blast Tube Ring
Odyssey
Burner Gasket
Burner Flange
Washers and Nuts
Blast Tube
Burner
13
Page 14
Odyssey
5.0 GENERAL VENTING
Installation and Operation Instructions - General Venting CT80-250
Natural Draft Applications
All Odyssey models are certified as Natural Draft boilers. The Natural Draft installation draws combustion air from the room and uses the stack effect and draft system to exhaust flue gases using a chimney.
Air Supply - Allowances for combustion air must be supplied to the appliance space, due to the fact that the heating appliance consumes large volumes of combustion air. In most instances, a permanent opening with an unobstructed or “free area” of 1 square inch for every 1000 BTU’s of input will provide a sufficient amount of combustion air for the boiler to operate properly. If the building is fairly new and relatively air tight, compensate for the air tightness by using a “free area” that is 15% larger that what was calculated above. Do not place the boiler in, or adjacent to, a room where an exhaust fan is operating. Refer to “Combustion Air” in Section 6.0 Natural Draft Applications for more details. Installation must comply with Standard CSA B139 (Canada) and NFPA 31 (USA).
Stack Draft - Sufficient draft by natural or mechanical means is necessary for ensuring optimal and consistent operation. The appliance should have a stack draft sufficient to support stable operation. See Draft Settings (Natural Draft).
Avoiding Condensation - Due to the high combustion efficiencies and low stack gas
temperatures, great care must be taken to ensure that the chimney isn’t subjected to gas condensation. The exhaust gas temperature where the flue pipe enters the chimney must be a minimum of 240oF or condensation may occur.
Draft Regulator - A draft regulator must be used and set to regulate the draft of the boiler. Make sure that the damper is free to operate without sticking, for this will affect the boiler’s combustion system. It is important that the draft be adequate because poor draft conditions will cause poor operation and a possible hazardous condition.
Draft Settings (Natural Draft) - The Odyssey is designed to operate with a -.03” w.c.
draft in the flue breaching; therefore, ensure there is enough natural or mechanical draft for proper operation. Due to the design of the Odyssey it may operate at a positive over fire pressure up to +.20 at a -.03 draft.
Direct Vent Applications
Odyssey models C85-150 are also certified for direct vent applications. The Direct Vent installation uses a special venting system where exhaust gases are vented directly to the outside using a special venting system which equalizes the pressure between the air inlet and the flue outlet resulting in a balanced flue system. Refer to Section
7.0 Direct Vent Applications for more details. Installation must comply with Standard CSA B139 (Canada) and NFPA 31 (USA).
Draft Settings (Direct Vent) - Due to the design of the balanced flue system, the Odyssey
will operate at a positive draft pressure and a positive over fire pressure at all times. It is designed to operate with a maximum stack draft of 0.25” w.c and a maximum over fire draft of 0.33” w.c. when little or no wind is present. In extreme wind conditions, the maximum stack draft is 0.35” w.c. and the maximum over fire draft is 0.45” w.c.
14
Page 15
CT80-250 Natural Draft - Installation & Operation Instructions
6.0 NATURAL DRAFT APPLICATIONS
Odyssey
Natural Draft Rules and Guidelines
1. Acceptable Venting Material - Use vent material approved by National Standards NFPA 31 (USA) or CSA
B139 (Canada) and local codes.
2. Venting Application - Venting must be connected to a chimney for models operating with Natural Draft.
3. Chimney Condition - Inspect existing chimney before installing new boiler. Deterioration of mortar joints
should be repaired prior to using.
4. Chimney Height - Chimney must extend 3’ above the highest point where it exits the roof and 2’ higher than
any part of the structure within 10’.
5. Cleaning - Clean chimney, if required; ensure it is clear of any blockages before connecting breeching.
6. Liner Condition - Damaged liner or pipe should be repaired before commencing installation.
7. Minimum Clearances - Observe clearances to combustibles illustrated in Figure 3-1 and Table 3-1:
8. a) Double-wall vent (Type-L) 6 "
9. b) Single-wall vent 9 "
10. Chimney Sizes - Minimum chimney sizes should be used. See Table 6-1.
11. Combustion Air - An adequate supply of combustion air must be available to ensure proper combustion.
12. Interlock - If a damper is used to provide make-up air for combustion, it must be interlocked with the burner
to prevent the burner starting before the damper is opened.
Potential Condensation - Oversized chimneys, outside masonry chimneys, and/or de-
rated inputs can result in flue gases condensing in the chimney.
Combustion Air
Natural Draft boilers require an adequate amount of combustion air to sustain proper combustion and prevent flue gas leakage. The appliance’s air-inlet draws combustion air from Indoors or Outdoors depending on whether there is a sufficient natural infiltration (air changes) occurring to sustain combustion. If the building is newer and relatively air tight, outdoor air should be considered. For recommended practice, refer to NFPA 31 (USA) or CSA B139 (Canada).
Air Circulation - The boiler shall be located so as not to interfere with proper circulation
of combustion, ventilation, and dilution air.
Make-up Air - The operation of exhaust fans, kitchen ventilation systems, clothes dryers,
and fireplaces must be considered in determining the adequacy of a space to provide combustion air requirements. Failure to ensure adequate make-up air to all appliances may result in flue gas leakage, personal injury or death.
Permanent Openings for Combustion Air
The appliance space or boiler area requires a permanent opening(s) capable of providing adequate combustion air to the boiler. If using two permanent openings, one opening must be within 12 inches of the ceiling, the other within 12 inches of the floor. The minimum dimension of air openings to the appliance space shall not be less than 3 inches in any one direction, including rectangular ducts. Round ducts are connected to the permanent air openings, duct sizes must have a minimum cross-sectional area of 3 inches. See “Sizing Combustion Air Openings” for more details.
The minimum size of permanent openings and how combustion air is supplied to them depends on three factors:
1. What is the input capacity of the boiler in Btu/hr?
2. How is the Combustion Air being supplied?
3. Is make-up air required for other appliance in the room competing for the same air?
15
Page 16
Odyssey
Installation and Operation Instructions - Natural Draft CT80-250
Sizing Combustion Air Openings
The following sections detail the three (3) methods for determining the minimum opening size and location required for providing combustion air:
1. Indoor Air - Opening Sizes: Older buildings typically have sufficient ventilation due to air leakage around
single pane windows, poorly weather-stripped doors, and non-existent vapour barrier. Indoor air can be used to supply combustion air to the boiler area if the air infiltration rate is adequate, i.e. greater than 0.4 ACH (air changes per hour) or when the boiler area and communicating spaces have a minimum volume of 50 cubic ft per 1000 Btu/hr. If the air infiltration rate is known to be less that 0.4 ACH, refer to the Installation Code for Oil-Burning Equipment for further guidance.
a. Combined spaces on the same story
minimum free area of openings = 1 in.2/1000 Btu/hr of total input rating of all appliances in the space.  not less than 100 sq. in. two openings required - one within 12 in. from ceiling, other within 12 in. from floor or bottom of the
enclosure.
minimum dimension of air openings shall be not less than 3 in.
b. Combined spaces in different stories
Volume of spaces in different stories shall be considered as communicating spaces where spaces
connected by one or more openings in doors or floors having a total minimum free area of 2 in.2/1000 Btu/hr of total input rating of all appliances.
2. Outdoor Air - Opening Sizes: When outdoor air is used to supply combustion air to the appliance space,
both openings must connect directly to the outdoors via ducts or connect to a crawl space or attic that connects freely to the outdoors. Outdoor combustion air provided through opening(s) to the outdoors must be made in accordance with the methods detailed below.
a. Two Permanent Openings Method - Two permanent openings shall be provided, one commencing
within 12 in. of the top, and the other within 12 in. of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as follows: vertical ducts, minimum free area = 1 in.2/4000 Btu/hr of total input rating of all appliances in the
space.
horizontal ducts, minimum free area = 1 in.2/2000 Btu/hr of total input rating of all appliances in the
space.
b. One Permanent Opening Method - One permanent opening, commencing within 12 in. of the top of
the enclosure, shall be provided. The appliance shall have clearances of at least 1 in. from the sides and back and 6 in. from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
1 in.2/3000 Btu/hr of the total input rating of all appliances located in the enclosure.  Not less than the sum of the areas of all appliances’ vent connectors in the space.
3. Combination Indoor and Outdoor Air - Opening Sizes: The use of a combination of indoor and outdoor
combustion air shall be in accordance with the following: a. Indoor Air - Where used, openings connecting the interior spaces shall comply with opening sizes
calculated in accordance with “Indoor Air Opening Sizes” described previously.
b. Outdoor Air - Outdoor opening(s) shall be located and sized in accordance with “Outdoor Air Opening
Sizes” described previously.
c. Outdoor Opening(s) - The outdoor opening(s) size shall be calculated in accordance with the following:
The ratio of interior spaces shall be the available volume of all communicating spaces divided by the
required volume (i.e. 50 cubic ft per 1000 Btu/hr if 0.4 ACH or greater).
The outdoor size reduction factor shall be 1 minus the ratio of interior spaces. The minimum size of outdoor opening(s) shall be the full size of outdoor opening(s) calculated in
accordance with “Outdoor Air Opening Sizes” described previously, multiplied by the reduction factor. The minimum dimension of air openings shall not be less than 3 in.
16
Page 17
CT80-250 Natural Draft - Installation & Operation Instructions
Connect Breeching & Blocked Vent Switch
Odyssey
Restrictions - Use the minimum vent length and number of elbows possible to ensure
flow of combustion gases are not restricted. Failure to follow instructions may result in severe personal injury or death.
Blocked Vent Switch - For complete installation details, refer to the manufacturer’s
instructions included with the Blocked Vent Switch. The steps for connecting breeching to a chimney are illustrated in Figure 6-1 and should be read in conjunction
with the sizes specified in Table 6-1. Restricted flow can result in condensation, flue gas leakage, and/or carbon monoxide emissions.
Breeching Installation:
1. Chimney Clearances - Observe clearances to combustibles for breeching and chimney connections.
2. Supports - Install flue pipe brackets according to local codes or as needed.
3. Breeching Sizes- Connect breeching to the boiler flue collar. Use full size breeching when possible. Refer to
Table 6-1 for minimum sizes.
4. Potential Restrictions - Keep breeching lengths and elbow-tee combinations to a minimum to avoid
restricting the flow of combustion gases. See warning titled “Restrictions”.
5. Chimney Connections - Use thimble or slip joint where breeching enters chimney to allow for removal for
cleaning and servicing.
6. Avoiding Obstructions - Ensure breeching does not protrude so far into the chimney that it will cause
obstruction. Avoid connecting near the bottom of chimney as blockages may result.
7. Draft Regulator - Ensure damper is level. See instructions included with regulator.
8. Normal Draft Settings - When properly installed, Odyssey models are designed to operate with -.03” w.c.
draft in the flue breaching. For proper operation, there must be enough natural or mechanical draft. Due to the design of the Odyssey, it may operate at a positive over fire pressure up to +.20 at -.03 draft.
9. Draft Gauge (if applicable) - A barometric control can be used to adjust the draft opening by installing it in
the breeching. This is optional and typically only done when excessive draft conditions exist which must be relieved or to comply with applicable codes or regulations.
10. Sealing - Seal all vent joints.
11. Blocked Vent Switch - Install switch 6-8” from boiler breeching (Canada). See manufacturer’s instructions.
12. Interlock Set-up - Interlock burner with fan operation before start-up if using a motorized damper to supply
outdoor combustion air or induced draft.
17
Page 18
Blocked Vent Switch
8” from the boiler
breeching, refer to instructions included
Top Back Panel
-
with high temperature silicone.
Odyssey
Table 6-1 Minimum Chimney Sizes
Model
Installation and Operation Instructions - Natural Draft CT80-250
Minimum Breaching
Diameter
Minimum I=B=R Chimney
Rectangular Round
Minimum
Chimney
Height
Boiler Flue Collar Size
C80 C90
C100
6 "
15 ' C120 C150
5 "
8 " x 8 " C180 C215 C230 C250
Notes:
1
6-3/4" x 6-3/4" inside liner.
2
Excessive breeching length or too many elbows and/or tee will cause restriction.
1
7 "
8 "
15 '
15 '
Figure 6-1 Breeching & Blocked Vent Switch
5"
Recommend installing top back after flue breeching connected and sealed
Secure breeching using a minimum of two screws, equally spaced. These two screws must past through the support tabs on either side of the breeching.
Draft Regulator
Support Tabs
Blocked Vent Switch
Install the switch 6-
18
with kit (mandatory in Canada).
Page 19
CT80-250 Direct Vent - Installation & Operation Instructions
7.0 DIRECT VENT APPLICATIONS
Direct Vent Rules and Guidelines
1. Vent Material: Use approved venting material. Refer to Direct Vent Termination Kit in this section.
2. Continuous Vent: The vent must be in one continuous piece with no joints.
3. Balance: Combustion air intake and vent must be installed on the same wall using the specified vent terminal
to ensure the system is balanced.
4. Prevailing Winds: Ensure the vent is located where it will not be exposed to normal prevailing winds.
5. Combustion Air-inlet Contamination: Air for combustion must be drawn from an area free of dust and
contaminants. Combustion air containing chemicals such as chloride, fluoride, bromine, iodine, or dust and debris will cause corrosion damage of the heat exchanger voiding your NTI warranty.
6. Snow Level Allowance: 24” is the recommended snow level allowance above grade or any surface that will
support snow, debris, or ice required for air-inlet / vents in balanced flue systems. If living in a snowfall region, consult your local weather office for the maximum typical snowfall in your area.
Example: New Brunswick Canada - typical maximum snowfall is 19”, thus the inlet must be (12”+19”) = 31”
above grade.
7. Wall Flashing: Under normal operating conditions this boiler will produce a plume of white gases, and
should be taken into consideration when selecting an adequate location. A 36” [915 mm] diameter stainless, plastic, or vinyl shield can be used to flash the exterior of the residence.
8. Flue Gas Hazard: Position the vent termination where vapors cannot make accidental contact with people
and pets, damage property, or adjacent buildings.
9. Condensate Hazard: Do not locate vent over public walkways, driveways or parking lots. Condensate could
drip and freeze resulting in a slip hazard or damage to vehicles and machinery.
10. Wall Thickness: Direct Vent terminations are designed to work with any standard wall thickness.
Installation guidelines for min/max wall thickness are as follows: Min.= 1” [25mm], Max.= 20” [0.5m]. Standard Vent Terminal is 8” long (p/n 81522-1) and Extended Vent Terminal is 20” long (p/n 81522-2).
11. Venting Options: Due to potential moisture loading (build-up) along the exterior wall, sidewall venting may
not be the preferred venting option.
Odyssey
19
Page 20
Odyssey
Direct Vent Clearances
Installation and Operation Instructions - Direct Vent CT80-250
Table 7-1 is a quick reference table that is to be read in conjunction with the numbered
notes in the table, the Direct Venting Rules and Guidelines, and Figure 7-1. The instructions detailed in this section are a combination of Odyssey specific and National Code restrictions. Compliance alone doesn’t ensure a satisfactory installation as good common sense must also be applied. Failure to follow these instructions may result in fire, property damage, serious injury or death.
Table 7-1 Termination Clearances Quick Reference Table
Clearances to Vent Termination
A Vent Terminal above grade, snow level, or an object that can support snow/ice 3 12 in. 305 mm 12 in. 305 mm B Flue gases directed toward / causing damage to masonry, siding, or construction 6 C To exhaust from any other appliance 4 6 ft. 1.8 m 12 in. 305 mm D
From combustible materials, surrounding building openings, or property lines 9
E Below / adjacent operable window or building opening 6 ft. 1.8 m 4 ft. 1.2 m
F Above window, door, or building opening. 6 ft. 1.8 m 12 in. 305 mm G To combustion air inlet from any other appliance 6 ft. 1.8 m 12 in. 305 mm H Under a veranda, porch, deck, or balcony 8 6 ft. 1.8 m
I Mechanical air supply inlet to building 5 6 ft. 1.8 m 3 ft. 1.0 m
J Soffit, overhang, eave or parapet 2 ft. 610 mm 12 in. 305 mm K Soffit vent; vent opening in overhang 6 ft. 1.8 m 12 in. 305 mm L Inside corner of an L-shaped structure (including walls and fences) 3 ft. 1.0 m 3 ft. 1.0 m
Minimum distance from the oil supply tank’s vent or fill pipe (inlet)
M
N Above a gas meter, gas meter / regulator assembly 4 3 ft. 1.0 m
P Each side of center line above or below meters, regulators and vent/relief devices 4 6 ft. 1.8 m Q Above or adjacent to a paved sidewalk /driveway, or parking lot
7
7 ft. 2.1 m 7 ft. 2.1 m
R Above a sidewalk, driveway, or parking lot on public property
S Above a sidewalk, driveway on private property between / serving both dwellings T Into a canopy or carport U Above, under or near exterior stairs
Notes:
1 - Canadian installations must comply with the current CSA B139 Natural Oil Installation Code and local codes. 2 - US installations must comply with current Standard NFPA 31 Installation of Oil Burning Equipment and local codes.
3 - 24” is the recommended snow level allowance above grade or any surface that will support snow, debris, or ice (i.e.
deck). Minimum distance is 12” above grade or above snow level (which ever is greater). If living in a snowfall region,
consult your local weather office for the maximum typical snowfall for your area. 4 - Within 3’ of the vertical centerline. 5 - For US installations, an exhaust vent may be 3 ft above a mechanical air supply inlet if within 10 ft. [3 m] horizontally. 6 - The vent terminal shall not terminate where flue gases are directed toward brickwork, siding, or construction in such a
manner that can cause damage from heat or condensate from the flue gases. 7 - Exit terminals of mechanical draft systems must maintain this minimum distance when located above or adjacent public
walkways, driveways or parking lots. Flue gases cannot drip, freeze, or create a hazard. 8 - Only permitted if a minimum of two sides are fully open beneath.
9 - Vent terminal must terminate so flue gases maintain the stated clearances from combustibles, property line, and
surrounding building openings.
X
- Not permitted by National code(s) and/or recommended by boiler manufacturer.
Canada 1 USA 2
Min. Distance Min. Distance
X X X X
6 ft. 1.8 m
- -
- -
3 ft. 1.0 m
5 ft. 1.5 m
- -
- -
X X X X X X X X X X X X X X X X
20
Page 21
CT80-250 Direct Vent - Installation & Operation Instructions
Figure 7-1 Termination Clearance Quick Reference Diagram
Odyssey
21
Page 22
1
,3
DV Burner Kit.
3
5
Odyssey
Installation and Operation Instructions - Direct Vent CT80-250
Direct Vent Termination Kit
When installed as a Direct Vent boiler the combustion air-inlet must also be piped directly to the outdoors using the methods described in this section and in accordance with the CSA B139 (Canada) or NFPA 31 (USA) and local code requirements.
Venting Options - Due to potential moisture loading (build-up) along the exterior wall, sidewall venting may not be the preferred venting option.
The majority of the balance flue components required for Direct Vent installations are included with the Burner Kit. Remaining components must be ordered separately. Refer to the components listed in Table 7-2 and illustrated in Figure 7-2.
Table 7-2 Direct Vent Components
Item Part # Description
Included with Direct Vent Burner Kit
1 81764 2 81098 3 81138
5” to 3” Ported Adapter 3” Insulated Flex to Pipe Adapter 3” Flex, 10’ long 3
4 81625 Hose Clamps, 3” (2)
6
2
4
Direct Vent Terminal 1
5 81522-1 Direct Vent Terminal, 8”
Insulated Flex
1
81109 5’ Insulated Flex 81097 10’ Insulated Flex
6
81110 15’ Insulated Flex 81111 20’ Insulated Flex
Optional Components 2
- 81522-2 Extended Direct Vent Terminal, 20”
- 81453 Silicone, High Temp., 302 (83ml)
- 81847 3” Direct Vent 90o Elbow
- 81633 Adapter3” x 20’ Flex Aluminum
- 83026
Notes:
1
Required for Direct Vent installation but not included with boiler package; therefore, must be ordered separately.
2
Optional components available from NTI. Must be ordered separately.
3
The vent and air intake maximum length is 20’ (6m).
5” to 3” 90o Elbow Ported
Components required for Direct Vent installation:
Items 1-4 included with the boiler’s Items 5-6 must be ordered separately.
Figure 7- 2
4
22
Page 23
Connection
Flange
CT80-250 Direct Vent - Installation & Operation Instructions
Direct Vent Installation Instructions
Odyssey
Vent Location - Under normal operating conditions, the boiler will vent plumes of white
flue gases; therefore, code restrictions and potential hazards associated with thru-wall
installations should be considered before selecting a location for the Direct Vent terminal. To install the Direct Vent Termination Kit for the balanced flue system, complete the steps listed below in
sequence. Note there are two parts to the install, outside prep work and inside connections:
PART A: Outside
1. Vent Location - Select a suitable location for the
vent terminal. It is highly recommended that the vent terminal be located where it will not be
Support Bracket
Heat Shield
exposed to normal prevailing winds. See NFPA 31 (USA), CSA B139 (Canada) for code clearances.
2. Exterior Surface - Ensure that the outside wall
Mounting Tabs
surface is flat and meets the installation clearances. See Table 7-1 and Figure 7-1.
3” Hole
3. Vent Hole - Cut a rectangular hole, 5.5” wide, and
6.5” in height in the exterior wall.
4. Orientation - Insert the vent terminal through the
rectangular hole into the building so that the 3” diameter hole for the air intake is facing downward. See Figure 7-3.
5. Slope - When installed correctly, the vent terminal
pipe should point slightly uphill in order to drain
Figure 7- 3
water to the outside. If it is not sloped to the outside, flue gases will condense and drain back into the boiler.
6. Mounting Tabs - Secure the mounting tabs on either side of the vent terminal to the outside of the structure
using 4 x #10 stainless steel screws (field supplied).
7. Sealing - Using a suitable silicone sealant, seal the gap between the structure and the vent terminal.
PART B: Inside
8. Bend Bracket Support - Using a screwdriver, bend up the support
bracket located on the top of the unit as shown in Figure 7-4.
9. Support - Support the back end of the vent terminal by connecting
the support bracket to a joist, or other solid structure, by means of metal strapping or wire.
10. Air Inlet Connections - Using the screws provided, attach the air
inlet connection flange to the bottom of the vent terminal. Figure 7-4.
11. Heat Shield - The back of the vent terminal is equipped with a
flexible heat shield, bend the flaps to the side, and then bend the heat
Air Inlet
Connection
shield up, and out of the way as shown in Figure 7-5.
12. Silicone - Seal the space between the vent terminal and the structure.
Refer to “Sealing” section for more detailed instructions.
13. Flex Piping - Install air inlet flex piping (3” flex 10’) over air inlet
connection (Figure 7-5). Secure with a 3”gear clamp included in the
Figure 7- 4
burner kit. Connect other end of flex piping directly to the Riello burner (or increaser if using a Beckett burner). See Figure 7-7.
14. Insulated Flex - The boiler can now be connected to the vent
terminal with the help of insulated flex piping. The flex piping is available in lengths of 5 ft, 10 ft, 15ft, and 20 ft. Ensure the flex piping is long enough to form long radius bends (no smaller than 1 ft in radius). If the flex is too long, it can be cut with a hacksaw.
15. Direct Vent - Assemble Direct Vent as detailed in following section
titled “Sealing”. Use only high temperature silicone provided or referenced in instructions.
Air Inlet
Figure 7- 5
23
Page 24
Odyssey
Sealing
Installation and Operation Instructions - Direct Vent CT80-250
Proper Sealing - This Balanced Flue system will leak if the following sealing procedures
are not followed. It’s easier to seal the entire system properly the first time than return at a
later date and have to remove the connections to reseal it.
The adapters are multi-start, left hand thread, with one thread twice the width of the others. Therefore, care must be taken to ensure that the correct threads are engaged before
tightening in a counter clockwise direction. Clearances to Combustibles - The vent must have 9” clearance to combustible within 36” of the appliance
breech. The remaining section of the vent to the terminal can have a minimum of 1” clearance. The terminal is rated for 0” clearance.
Recommended Sealing Method - Because the balanced flue system operates with a positive pressure in the exhaust at all times, the sealing has to be done properly to prevent leaks at the joints. The type of sealant used throughout this installation is critical to the operation of the balanced flue system. A tube of high temperature silicone is provided with the installation kit (#81453). This tube should be sufficient for the whole installation, but if more sealant is needed buy one of the following: GE 106, Dow Corning 736 Heat Resistant Sealant, Perimeter 248 High Temp or RTV Silicone Gasket.
It’s the installer’s responsibility to ensure that combustion products do not enter the home.
To obtain a good seal between the Vent Terminal and the building wall, follow Steps “A” through “J” illustrated in Figure 7-6:
PART 1: Boiler
A. Seal the 5” smoke collar to the smoke hood on the boiler with the high temperature silicone. Inspect all boiler
openings (sight door, burner connection, pipe joints, Etc) during initial operation, to verify there are no leaks.
Flex Pipe - Make sure that it’s long enough to form long radius bends (no smaller than 1 ft in radius). If the flex is too long, it can be cut with a hacksaw.
Flex Adapter Collar - It is recommended to remove the collar on the 81098 & 81112 flex adapters that secure the insulation and outer foil of the flex pipe. This can be accomplished by removing the pop rivet at the base of the collar, and backing off the gear clamp completely. After removing the collar, you will get an unobstructed view of the pipe joint. To reinstall, put the collar back into place and install a #8 x ½” screw in rivet hole, and re­thread the gear clamp.
PART 2: Flex Pipe
B. Pull the outer foil sheathing and insulation back to give an unobstructed view of the pipe joints. Put 1 bead of
silicone on both inside ends of the insulated flex pipe, approximately 1” wide and ½” from the end. Put 1 bead of silicone on both outside ends of 81098 & 81112 connectors, approximately 1” wide and 1” from the bottom of the threads. Screw in part number 81089 & 81112 adapters into the insulated flex and pull the insulation and the outside flex over the collar and tighten the gear clamp.
C. Apply a wide bead on top of the flex joint. D. Reinstall the collars on the vent connectors using a #8 x ½” screw in rivet hole, and re-thread the gear clamp E. Apply silicone between the vertical overlap joint of the 5” to 3” adapter. F. Apply silicone on inside surface of the 5” to 3” adapter. G. Apply silicone on outside surface of the boiler cast collar, and slide 5” to 3” adapter over the smoke hood and
tighten the gear clamp.
H. Perform steps D-G to install the 3” adapter #81098 over the 3” vent terminal, and tighten gear clamp. I. Fold the vent terminal heat shield flaps back into position. J. Refer to Figure 7-7 for an illustration of a typical balanced flue installation for an Odyssey boiler (CT90-120).
24
Page 25
CT80-250 Direct Vent - Installation & Operation Instructions
Vacuum
Secure
Odyssey
Seal with silicone where shown.
Step G
Smoke Hood
Step B
5” to 3”
Ported Adapter
Insulated Flex
Step D
Step E
Step F
Step C
Important Warning - It is the responsibility of the installing contractor to ensure that:
1. The boiler and venting system are totally sealed from products of combustion.
2. The homeowner is advised of their responsibility of keeping the vent terminal clear of snow and ice.
3. That the home is equipped with a carbon monoxide detector.
Figure 7 -6
Insulated Flex
5” to3” Ported
Adapter
Typical Balanced Flue Installation for CT90-120
3” Insulated Flex to Pipe Adapter
Seal
Hose Clamp
using Tabs
Hose Clamp
3” Flex (10’)
Hose Clamp
Direct Vent Terminal
Breaker
Air Inlet Piping 3” Flex (10’)
Figure 7 -7
Tilt down after sealing
Direct Vent Terminal Installation
Seal with silicone where shown.
25
Page 26
Odyssey
8.0 BOILER PIPING
Installation and Operation Instructions - Field Wiring CT80-250
Boiler Water
Pressure - Odyssey boilers are intended to solely for use in pressurized closed-loop heating systems operating with a “fill pressure” between 12-15 psi at the boiler outlet and a Relief Valve pressure of 30 psi (maximum working pressure of the boiler).
Oxygen Elimination - The Odyssey boiler is designed to operate in a pressurized closed-loop heating system, free of air and other impurities. To avoid the presence of oxygen, ensure all of the air is removed from the system during commissioning via strategically placed, adequately sized air-removal devices located throughout the heating system and the boiler piping (Figure 8-1). Immediately repair any leaks in the system plumbing to avoid the addition of make-up water; make-up water provides a source of oxygen and minerals that may lead to heat exchanger failure, poor performance, unnecessary wear of system components, and premature failure.
Closed System - The Odyssey is not approved for operation in an “open system”, thus it cannot be used for direct potable water heating or process heating of any kind.
Antifreeze - If using antifreeze, use an inhibited propylene glycol specifically designed for hydronic systems. NTI recommends against exceeding 35% concentration of glycol.
Near Boiler Plumbing
Install boiler piping for central heat and domestic hot water as shown in Figure 8-1. Gauges - The temperature and pressure gauges (Ttridicator) is factory supplied and must be field installed in the
front of the boiler or on the coil plate.
Relief Valve - A 30 psi relief valve is factory supplied and must be field installed. Piping - The closed loop piping system must be in accordance with the central heat piping illustration. All piping
joints must be secure and water tight or the boiler warranty is void.
Water Supply - Pressure regulating “fill valve” (12-15 psi) and back flow preventer are required (Figure 8-1). Boiler Venting - Hot waters boilers are designed to operate with the airless water in the system. The NY Thermal
boilers are designed with a built-in air trap, to purge air at the ¾” relief valve nipple. An air vent must be installed here or the boiler warranty is void.
Low Water Cut Off (LWCO) - To take advantage of the HydroStat’s LWCO feature, the
Odyssey is equipped with a special immersion well call the Electro-well™. Failure to use the Electro-well™ provided with the boiler will over-ride the LWCO feature and allow the boiler to operation during low water conditions which may result in over heating, fire, serious injury, or death.
Verify LWCO is Active - Ensure the LWCO active light is illuminated on the HyrdroStat
3250 when using the Electro-well™. If the indicator light is not illuminated than the LWCO feature is not active. Refer to manufacturer’s instructions included with the HydroStat 3250.
Removing Air - Do not fill the boiler with water until you are ready to fire the burner.
Once filled with water, bring the boiler up to temperature and remove the air.
Removing Air from the Boiler:
1. Open automatic air vent 1 turn.
2. Bleed air from system. Starting at the lowest point in the building, open air vents one at a time and leave them
open until water comes out. Close all air vents, except the automatic air vent.
3. Refill to correct pressure, 12-15 psi.
26
Page 27
CT80-250 Field Wiring - Installation & Operation Instructions
Tee
(below
Figure 8-1 Near Boiler Piping
Central Heat
Relief Valve
Outlet
Tridicator
Odyssey
Heating
Supply
Heating
Return
Bypass Line
(optional)
* Circulator location may vary from one application to another.
Pump *
Automatic Air Vent
Air Eliminator (mandatory)
Isolation/Throttle Valve
Water
Supply
Expansion Tank
Boiler Drain
burner)
Inlet
27
Page 28
Odyssey
9.0 FIELD WIRING
Installation and Operation Instructions - Field Wiring CT80-250
All wiring and electrical grounding must be in accordance with local codes and the applicable National Electrical Code, NFPA 70 (USA) or CSA C22.2 (Canada). Ensure that the wiring complies with this manual.
Avoid Shocks - To Avoid Electrical Shock, turn off electrical power to the boiler prior to
opening any electrical box within the unit. Ensure the power remains off while any wiring connections are being made. Failure to follow these instructions may result in component failure, serious injury or death.
Wire Protection - When passing any wiring through the casing of any component or
electrical box, the installer must use wire grommets suitable for securing the wiring and preventing chafing. Failure to follow instructions may result in component failure, serious injury or death.
Burner Primary Safety - Blocked Vent Switch and any other limit device must break
power to the burner primary (B1). Failure to follow these instructions may result in serious injury or death.
Labeling - Label all wires prior to disconnecting them when servicing controls. Wiring
errors can cause improper and dangerous operation. Failure to follow instructions may result in property damage or personal injury.
Connection Description
T-T
WWSD
Heat Demand Input (Dry Contact) - from heating thermostat or zone controller. Contact closure indicates to the controller that there is a heating demand, controller will apply Thermal Targeting
Outdoor Temperature Sensor (Factory Supplied) – Connecting the OD Sensor to WWSD and C enables the Warm Weather Shutdown feature of the controller. Control will not respond to T-T demands when the
C
outdoor temperature is above the WWSD setting. Outdoor Temperature Sensor (Factory Supplied) – Connecting the Outdoor Sensor to OR and C
OR
disables Thermal Targeting and enables full Outdoor Reset functionality, including Warm Weather Shutdown.
Table 9-2 Electrical Field Connections - Line Voltage
Connection Description
Power Supply Hot – 120VAC input for the controller. Installation codes require the installation of a
L1
service switch to break line voltage to the appliance. Power supply must be protected with 15 Amp circuit breaker or fuse.
L2 Power Supply Neutral – Location for connecting the Neutral of the power supply. C2 Circulator Neutral – Location for connecting the Neutral to the circulator. C1 Circulator Hot – 120VAC output to circulator (5.8 FLA max.)
B1
Burner Hot – 120VAC output to burner (7.4 FLA max.). Additional safety limits, i.e. LWCO and/or Blocked Vent Switch, must be installed in series with this circuit. B1 is the Burner Primary.
B2 Burner Neutral – Location for connecting the Neutral to the burner.
ZC
Priority Zone Output (120VAC) – Power supply for priority zone, power is always present at ZC unless the LO TEMP temperature is not attained.
Priority Zone Input (120VAC) – When power is applied to ZR from ZC, via a contact closure of an Indirect Tank Thermostat, when Zone/Indirect Switch is set to “I”, the control overrides Thermal Targeting
ZR
and Outdoor Reset functions, and operates to the HI TEMP setting. When Zone/Indirect Switch is set to “Z”, the control interprets the call as an end switch from Priority Zone relay, and operates as a central heat demand performing Thermal Targeting or Outdoor Reset functions.
28
Page 29
CT80-250 Field Wiring - Installation & Operation Instructions
Figure 9-1 Odyssey Wiring Diagram
Odyssey
Burner Primary Safety - The Blocked Vent Switch and any other limit device must
break power to the burner primary (B1). Failure to follow these instructions may result in serious injury or death.
29
Page 30
Odyssey
Installation and Operation Instructions - Field Wiring CT80-250
Fuel Smart HydroStat Model 3250
The Fuel Smart HydroStat 3250-Plus is manufactured by HydroLevel Company. It is a Temperature Limit and Reset Control for oil and gas fired boilers. It meets the September 2012 requirements for “Automatic Means” of adjusting boiler temperature. The HydroStat provides only temperature and reset functionality when installed on a standard immersion well used on Caprice models.
Temperature Limit – In lieu of the HydroStat 3250 the Honeywell Aquastat models L7248A, L7224U or L8148A can be used on Odyssey boilers.
Low Water Cut Off (LWCO) - To take advantage of the HydroStat’s LWCO feature, the
Odyssey is equipped with a special immersion well call the Electro-well™. Failure to use
the Electro-well™ provided with the boiler will over-ride the LWCO feature and allow the boiler to operation during low water conditions which may result in over heating, fire, serious injury, or death.
Verify LWCO is Active - Ensure the LWCO active light is illuminated on the HyrdroStat
3250 when using the Electro-well™. If the indicator light is not illuminated than the LWCO feature is not active. Refer to manufacturer’s instructions included with the HydroStat 3250.
Infloor Radiant Heating Applications - When the heating system incorporates low
temperature radiant heating, external mixing controls must be used to regulate the temperature. Failure to follow these instructions may result in property damage.
HydroStat 3250 - For complete installation details and instructions on controls operation,
refer to the manufacturer’s instructions included with the Fuel Smart HydroStat 3250.
Table 9-3 HydroStat 3250 Control Settings
Parameter Default Recommended Settings
HI TEMP 190ºF 140-210ºF LO TEMP OFF OFF ECONOMY (Thermal Targeting) 1 See Thermal Targeting Method ECONOMY (Outdoor Reset) 1.00 See Outdoor Reset Method Thermal Pre-Purge OFF ON Warm Weather Shutdown (WWSD) 70ºF 70ºF Zone/Indirect Switch I See Zone/Indirect Switch
General Notes:
1 – LO TEMP must be set at least 10ºF below the HI TEMP. 2 - Set HI TEMP according to temperature demands of the heating system, high for fined-tube
baseboard or low for infloor radiant.
Control Settings
HI TEMP:
o
Setting establishes the maximum boiler operating temperature for safety (burner will not operate above this setting).
o Do not set greater than 210ºF. o With Zone/Indirect Switch set to “I”, boiler operates to the HI TEMP setting during a ZC-ZR demand
(DHW- Indirect Tank)
30
Page 31
CT80-250 Field Wiring - Installation & Operation Instructions
Odyssey
LO TEMP:
o Minimum permissible boiler temperature, burner will fire without demand when temperature drops below
the LO TEMP setting.
o Controller inhibits circulator operation (120V outputs at C1 and ZC are deactivated) until the temperature
exceeds the LO TEMP setting.
o Set LO TEMP at least 10ºF below HI TEMP setting. o See “Setting the Low Limit” in the Hydrolevel installation instructions included with the HydroStat 3250.
ECONOMY
o Establishes the Boost Interval and Subtractive Differential settings for Thermal Targeting; see Thermal
Targeting Method below.
o Establishes the Reset Ratio setting for Outdoor Reset operation: see Outdoor Reset Method below o The higher the setting the greater the reduction in boiler operating temperature and fuel consumption.
Thermal Pre-Purge
o When set to ON, the control will purge the boiler temperature down to 135oF at the start of any thermostat
call before firing the burner. Display indicates "Pur" when control is in Thermal Pre-Purge mode.
o To set Thermal Pre-Purge ON, perform the following steps:
1. Turn the LO TEMP dial to “Pro”.
2. Turn the HI TEMP dial to select feature 1.
3. Push the Test/Settings Button to turn Thermal Pre-Purge ON or OFF.
4. Reset LO TEMP and HI TEMP settings to desired temperatures.
Zone / Indirect Switch
Determines the function of the ZC-ZR input.
o Switch = "Z" (Zone) – ZC-ZR demands are treated as central heat/thermostat demands; Thermal
Targeting and Pre-purge features are active.
o Switch = “I” (Indirect) – ZC-ZR demands are treated as DHW demands; Thermal Targeting and Pre-
purge features are overridden, boiler operates to the HI TEMP Setting.
o If ZC-ZR input is not used (i.e. nothing is wired to it), the Zone/Indirect Switch setting is irrelevant.
Outdoor Sensor - The outdoor sensor (p/n: 83604) is included in the burner kit, it must be
connected to the Fuel Smart HydroStat Control 3250 prior to setting up the control.
Warm Weather Shutdown (WWSD) The Warm Weather Shutdown feature prevents the boiler from providing central heating when the outside temperature reaches a level that you select. The boiler will still operate to satisfy a call for domestic hot water.
Available settings range from OFF or 40°- 70°F (factory default = 70°F). To adjust the WWSD setting, press and hold the Test/Setting Button and simultaneously adjust the Economy
dial to the desired setting.
To turn the feature off (allows space heating regardless of outdoor temperature), press and hold the Test/Setting
Button and simultaneously turn the Economy dial fully counter-clockwise. Release the Test/Setting Button.
31
Page 32
Boost
Odyssey
Installation and Operation Instructions - Field Wiring CT80-250
Inferring Heat Load (“Automatic Means” of Adjusting Boiler Temperature)
The HydroStat control incorporates two (2) options for Inferring Heat Load:
1) Thermal Targeting Method – default method
2) Outdoor Reset Method – method used when outdoor sensor is connected to OR and C
1) Thermal Targeting Method:
Default method for satisfying central heat demands. For the duration of a central heat demand, the target temperature is boosted by 10ºF every Boost Interval. For each new central heat demand, the control reduces the target temperature established in the previous cycle
by 5ºF.
For every 30 minutes of no central heat demand, the control will reduce the target temperature by 5ºF. The Subtractive Differential establishes how much the boiler temperature must drop below the target
temperature, before the burner will fire for a central heat demand.
The Economy Feature setting determines the Boost Interval and Subtractive Differential values; see Table 9-4. Thermal Targeting is overridden when Economy Feature is set to OFF, i.e. central heat demands operate to the
HI TEMP setting.
A central heat demand is activated by a T-T demand or ZC-ZR demand when the Zone / Indirect switch is set to
"Z".
With an Outdoor Sensor connected to WWSD and C, the control will perform Warm Weather Shutdown and
Thermal Targeting.
With an Outdoor Sensor connected to OR and C, the control will override Thermal Targeting and instead
function as an Outdoor Reset control with Warm Weather Shutdown – see 2) Outdoor Reset Method below.
Table 9-4 Economy Feature Setting (for Thermal Targeting)
1 2 3 4 5
Subtractive Differential
10oF 20oF
20oF 20oF 20oF 20oF 20oF 20oF
Interval
N/A
10 min Lowest level of fuel savings. Use only if other settings can’t meet the demand load. 15 min 1 zone heating system. 20 min 2 zone heating system. 25 min 3 zone heating system. 30 min 4 zone heating system. 35 min 5 zone heating system. 40 min Maximum efficiency. Highest level of fuel savings.
Setting1
OFF
LO
HI
Notes:
1 - Do not include Indirect Water Heaters in the number of heating zones.
Recommended Settings and Applications
Disables Thermal Targeting. Applications where a boiler must fire to the High Limit (HI TEMP setting)
32
Page 33
CT80-250 Field Wiring - Installation & Operation Instructions
Odyssey
2) Outdoor Reset Method:
Automatically active when the Outdoor Sensor is connected to the OR and C spade connects on the Fuel Smart
HydroStat.
Outdoor Reset overrides Thermal Targeting Method. The Reset Ratio setting dictates the influence the outdoor temperature has on the boiler target temperature
during a central heat demand. The boiler target temperature increases by the Reset Ratio setting for every 1ºF decrease in outdoor temperature. Inversely, the boiler target temperature decreases by the Reset Ratio setting for every 1ºF increase in outdoor temperature.
The Reset Ratio is set using the Economy Feature Dial. Use Table 9-5 to aid in setting the Reset Ratio for your
application.
o Example: if the outdoor design temperature is 0ºF (typical for the Northeast), and the design heating
water is 180ºF (typical for baseboard heating), then set Reset Ratio = 1.50.
The display will toggle between boiler temperature (8 seconds) and outdoor temperature (2 seconds). To check the current target temperature, press the Test/Settings button in 4 short intervals. If the Outdoor Sensor becomes damaged or disconnected, the control will automatically revert back to the
Thermal Targeting Method. The display will no longer toggle outdoor temperature.
Table 9-5 Economy Feature Setting (for Outdoor Reset)
Reset Ratio Chart
200
1.25 1.25 1.25 1.50 1.50 1.50 1.50 1.75 1.75 2.00 2.00 2.25 2.50 2.50 2.50 2.50 2.50 2.50
195
1.00 1.25 1.25 1.25 1.50 1.50 1.50 1.50 1.75 1.75 2.00 2.25 2.25 2.50 2.50 2.50 2.50 2.50
190
Boiler Temperature ºF
1.00 1.00 1.25 1.25 1.25 1.50 1.50 1.50 1.75 1.75 2.00 2.00 2.25 2.50 2.50 2.50 2.50 2.50
185
1.00 1.00 1.00 1.25 1.25 1.25 1.25 1.50 1.50 1.75 1.75 2.00 2.25 2.50 2.50 2.50 2.50 2.50
180
1.00 1.00 1.00 1.00 1.25 1.25 1.25 1.50 1.50 1.50 1.75 2.00 2.00 2.25 2.50 2.50 2.50 2.50
175
1.00 1.00 1.00 1.00 1.25 1.25 1.25 1.50 1.50 1.50 1.75 1.75 2.00 2.25 2.50 2.50 2.50 2.50
170
1.00 1.00 1.00 1.00 1.00 1.25 1.25 1.25 1.50 1.50 1.50 1.75 1.75 2.00 2.25 2.50 2.50 2.50
165
0.75 1.00 1.00 1.00 1.00 1.00 1.00 1.25 1.25 1.50 1.50 1.50 1.75 2.00 2.25 2.50 2.50 2.50
160
0.75 0.75 0.75 1.00 1.00 1.00 1.00 1.25 1.25 1.25 1.50 1.50 1.75 1.75 2.00 2.25 2.50 2.50
155
0.75 0.75 0.75 0.75 1.00 1.00 1.00 1.00 1.25 1.25 1.25 1.50 1.50 1.75 2.00 2.25 2.50 2.50
150
0.75 0.75 0.75 0.75 0.75 1.00 1.00 1.00 1.00 1.25 1.25 1.50 1.50 1.75 1.75 2.00 2.50 2.50
145
0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.00 1.00 1.00 1.25 1.25 1.50 1.50 1.75 2.00 2.25 2.50
140
0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 1.00 1.00 1.00 1.25 1.25 1.50 1.50 1.75 2.00 2.50
-40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
Outdoor Design Temperature
Outdoor Sensor - The outdoor sensor (p/n: 83604) is included in the burner kit, it must be
connected to the Fuel Smart HydroStat Control 3250 prior to setting up the control.
33
Page 34
Odyssey
10.0 INSTALLATION CHECKLIST
Installation and Operation Instructions - Installation Checklist CT80-250
Start-up
1. Close automatic air vent and boiler drain cock.
2. Boiler water pH range should be 7.0 - 8.5. If conditions are above 7, contact local water treatment company.
3. Fill boiler with water until gauge reads 12-15 psi using auto fill device. Check for leaks.
4. Open automatic air vent 1 turn.
5. Bleed air from system. Starting at the lowest point in the building, open air vents one at a time and leave them
open until water comes out. Close all air vents, except the automatic air vent(s).
6. Refill to correct pressure, 12-15 psi.
Purging the System - Ensure all air is purged from the heating system as it can result in
uneven heat distribution, water circulation problems, and shorten the life of the boiler.
Antifreeze - If using antifreeze, use an inhibited propylene glycol specifically designed
for hydronic systems.
Avoiding Corrosion - Two things that contribute to boiler corrosion are air in the system,
and boiler water with pH levels outside the recommended range. Be sure to check the pH level of the water before filling the boiler and bleed the system of air before firing the burner.
Pump Shaft Seals - Do not activate the burner until proper oil line connections have been
made or failure of the pump shaft seal may occur.
Check-out
1. Boiler heating system is filled with water and pressurized to 12-15 psi.
2. Bring the boiler up to temperature, once at temperature purge air from the boiler.
3. Purge air from the heating system piping.
4. Check that heating system piping and boiler are free from leaks.
5. Ensure Oil Supply tank is properly installed and vented as per applicable standards.
6. Oil line is secured to the burner in accordance with the burner manufacturers instructions.
7. Oil line is purged and free from leaks.
8. Do not start burner unless smoke hood, clean out door, HydroStat 3250, breeching, and burner door are
secured.
9. Burner has power and burner switch is turned on.
10. Verify sufficient combustion air is provided and applicable dampers are interlocked with burner.
11. Set burner flame by eye during initial start up. Make final adjustments with combustion test equipment.
12. Use the recommended air settings in Tables 2-1 to 2-3 as a starting point for the burner set-up.
13. Test HydroStat 3250 operation via the following methods: a) Adjust HI TEMP setting down until below
boiler water temperature, burner should go out, circulator should continue pumping; b) adjust HI TEMP setting up until above boiler water temperature, burner should ignite.
14. Test field installed controls (i.e. external low water cut off or high limit) as per the control manufacturer’s
instructions included with the device. Burner should be operating when testing is conducted to verify that the burner changes state (on, off, on) when the controls are tested.
15. HydroStat 3250 settings are to the recommended settings defined in this manual.
16. Verify the boiler cycles with thermostat(s) demand (high temperature / low temperature).
17. Set thermostat to desired room temperature.
18. Allow boiler to complete at least one heating cycle to verify correct operation (minimum 15 minutes).
19. Review owner’s responsibilities (Section 1.0) and annual maintenance (Section 11.0) with owner.
20. Leave this manual with the owner and affix the instructions close to the boiler.
34
Page 35
CT80-250 Installation Checklist - Installation & Operation Instructions
Adjusting Combustion Air
Odyssey
Smoke Pump - A reliable, certified smoke pump is required to correctly set up this
equipment.
Combustion Analyzer -
capable of measuring CO
To calibrate burner operation, use a calibrated combustion analyzer
2
and O2 from oil burning boilers.
Smoke Test - All tests must be done with the burner covers or air intakes in place to
simulate normal operation.
Avoid Condensation - Due to the high combustion efficiencies and low stack gas
temperatures, great care must be taken to ensure the chimney isn’t subjected to gas condensation. The gas temperature where the flue pipe enters the chimney must be a minimum of 240oF.
Air Settings:
1. Install applicable “burner package” as per burner installation instructions in Section 4.0.
2. Use the recommended air settings in Table 2-1 to 2-4 as a guideline.
3. Final adjustments should be made using test equipment and by verifying the CO2 is between 11-13%.
4. To accurately set the combustion system, first establish a stable firing condition with a #1 smoke.
5. Increase the air setting slightly until a #0 smoke is obtained.
6. Establish a minimum of three 5 minute burner cycles.
7. With boiler operating, measure the CO2 and O
Adjust pump pressure as necessary until the CO2 is within the
2.
acceptable range of 11-13%.
8. Repeat the smoke test - #0 smoke should be detected.
Instructions to Installing Contractor
1. Ensure that the customer receives the Warranty Documentation included with the installation manual.
2. Leave the manual with the customer so they know when to call for annual maintenance and inspection.
This boiler must have water in it whenever the burner is firing. Failure to comply may damage the unit, void the warranty, and cause serious injury or death.
35
Page 36
Odyssey
11.0 ANNUAL MAINTENANCE AND INSPECTION
Installation and Operation Instructions - Maintenance CT80-250
The building owner is responsible for scheduling boiler routine maintenance as described in this section. The boiler unit must be inspected at the beginning of every heating season by a Qualified Technician.
Annual Inspection Checklist
1. Make sure boiler is filled with water and fill valve is operating properly.
2. Inspect the condition of the combustion chamber.
3. Clean flue passages and combustion chamber at the end of each heating season.
4. Replace the oil filter.
5. Inspect the condition of the chimney and make recommendations for cleaning, if necessary.
6. Check heating system and boiler piping for leaks, make repairs as necessary.
7. Verify proper combustion air supply.
8. Verify proper draft.
9. Verify proper burner operation and combustion settings, including CO2 and “smoke” tests. Records of annual
testing and cleaning are required for any warranty consideration.
10. Verify proper control settings.
11. Verify proper operation of external controls on the boiler (i.e. low water cut off, high limit).
12. Verify proper operation of the hydronic system circulator, pressure relief valve, pressure regulating “fill
valve”, expansion tank, air vents, etc.
13. Verify proper operation of the HydroStat 3250.
14. Test Low Water Cut-Off. Press and hold the Test/Settings button for 5 seconds. The display will read LCO.
See instructions included with HydroStat for more details.
15. Clean Electro-Well every five years. To clean, remove scale or sediment deposits from areas in contact with
boiler water. Reinstall well using pipe sealing compound. DO NOT use Teflon tape.
16. Refer to the manufacturer’s instructions included with the Fuel Smart HydroStat 3250 for more information
on maintenance and operational procedures.
Close down for extended shutdown period
1. Turn off the thermostat(s) or set as low as it will go.
2. Close the oil supply valve (tank shutoff valve).
3. Turn the emergency power isolation switch off.
4. Clean the boiler to avoid premature aging.
Start-up after extended shutdown period
1. Check the boiler area for proper clearances to combustibles.
2. Inspect the boiler before preparing for start up.
3. Ensure there is oil in the oil tank.
4. Open the oil supply valve and ensure are no leaks.
5. Turn the thermostat(s) up.
6. Turn the emergency power isolation switch on.
If the burner has shut down on safety locate the red reset button on the burner and depress
it, the burner should restart. If it fails to restart, or if it shuts down a second time, contact your service technician.
Annual Cleaning Instructions
Annually, before the heating season begins (fall) or immediately after it ends (spring), the Odyssey is to be cleaned and serviced by a licensed burner technician. If the burner is not used for an extended period of time, it must also be cleaned before being put back into service (start-up).
Handling Instructions - Accidental contact with potentially carcinogenic insulating
materials can occur when cleaning the boiler. Read and follow the handling instructions in Section 11.0 regarding recommended personal protective equipment before commencing service on the boiler.
36
Page 37
CT80-250 Maintenance - Installation & Operation Instructions
Cleaning the Flue Passages:
1. Remove power from boiler before servicing.
2. Close oil supply valves.
3. Remove the front cover and the burner door (see Figure 12-1 for boiler parts breakout).
4. Remove baffles.
5. Carefully clean flue passages with a fire tube brush.
6. Vacuum debris out of the burner and combustion chamber.
7. Reinstall the baffles and secure the burner door.
8. Open valves and restore power once reassembled.
9. Verify proper operation once the cleaning is completed.
Odyssey
37
Page 38
Odyssey
Installation and Operation Instructions - Maintenance CT80-250
Handling Instructions
Fiberglass and Ceramic Fiber Materials - Odyssey boilers use insulating materials to reduce heat exchanger losses and clearances to combustibles. It is important for installers and service personnel to know what these materials are, where they are located on the boiler, and how they should be handled. Refer to Table 11-1 for recommended handling instructions and Figure 12-1 for location of insulating materials.
Personal Protective Equipment Recommended - Read the following warnings and
handling instructions carefully before commencing any service work.
Fiberglass (Potential Carcinogen) - Inhalation of airborne fibers from fiberglass
materials have been listed as a possible cause of cancer in California.
Ceramic Fiber (Potential Carcinogen) - Use of Ceramic Fibers in high temperature
applications (above 1000oC) can result in the formation of Crystalline Silica (cristobalite), a respirable silica dust. Repeated airborne exposure to crystalline silica dust may result in chronic lung infections, acute respiratory illness, or death. Crystalline silica is listed as a (potential) occupational carcinogen by the following regulatory organizations: International Agency for Research on Cancer (IARC), Canadian Centre for Occupational Health and Safety (CCOHS), Occupational Safety and Health Administration (OSHA), and National Institute for Occupational Safety and Health (NIOSH). Failure to comply with handling instructions in Table 11-1 may result in serious injury, long term health problems, or death.
Table 11-1 Handling Instructions for Fiberglass and Ceramic Fiber Materials
Reduce the Risk of Exposure Precautions and Recommended Personal Protective Equipment
Avoid contact with skin and eyes Avoid breathing in silica dust
Avoid transferring contamination
First Aid Measures
Notes:
1
Respirator recommendations based on CCOHS and OSHA requirements at the time this document was written. Consult
your local regulatory authority regarding current requirements for respirators, personal protective equipment, handling, and disposal of RCFs.
Wear long-sleeved loose fitting clothing, gloves, and safety glasses (or goggles).
Wear a respirator with a N95-rated filter efficiency or better. 1
Do not dry sweep silica dust. Pre-wet or use a vacuum with a high efficiency filter.
When installing or removing place the material in a sealable plastic bag.
Remove contaminated clothing after use. Store in sealable container until cleaned.
Wash contaminated clothing separately from other laundry.
If irritation persists after implementing first aid measures consult a physician.
Skin - Wash with luke-warm soap and water.
Eyes - Do not rub eyes; flush with water immediately.
Inhalation – Breathe in fresh air; drink water, sneeze or cough to clear irritated
passage ways.
* For more information on Fiberglass and Ceramic Fiber Materials contact CCOHS or OSHA. Canada (CCOHS): Telephone directory listing
under Government Blue Pages Canada—Health and Safety—Canadian Centre for Occupational Health and Safety; or website http://www.ccohs.ca.
38
United States (OSHA): Telephone directory listing under United States Government—Department of Labor—Occupational Safety and Health Administration; or website http://www.osha.gov.
Page 39
Item 1
0:
CT80-250 Parts List - Installation & Operation Instructions
12.0 PARTS LIST
Odyssey
For a list of parts that corresponds to the item numbers in the callouts, refer to Table 12-1. Note that some item numbers may appear more than once in the parts list depending on which model number is being referenced.
Building Owners - Replacement parts are available from your stocking wholesaler. Contact your local Installer or Wholesaler for assistance with parts.
Wholesalers - Contact NY Thermal Inc. directly when ordering replacement parts, 1-506-657-6000. Installers - Contact NY Thermal Inc. directly if technical assistance required, 1-800-688-2575.
Figure 12-1 Boiler and Jacket
15
13
18
8
16
11
9
39
38
34
37
35
6
33
1
7
12
2
3
4 5
36
46
14
47
48
Blocked Vent Switch is applicable to Natural Draft models, mandatory in Canada.
10
39
Page 40
Items
27
- 28
:
ordered
Item
26:
connects the 3” Flex to the Vent
Items 19 & 20:
Item
21
:
Burner Mounting Hardware:
Odyssey
Installation and Operation Instructions - Parts List CT80 -180
Figure 12-2 Burner Package
Included with Burner Kit
Burner
Gasket
Burner
Flange
Riello burners and blast tubes are ordered separately, field assembled.
Burner and blast tube are sold as a fully assembled unit.
21
20
19
M8 bolts, washers, and nuts used to mount the burner to the boiler
Figure 12-3 Direct Vent Components
are included with the jacket kit.
28
22
23
24
26
26
27
Vent Terminal and Insulated Flex not included with Burner Kit, must be separately. See Table 7-2.
3” Hose Clamps (x 2)
Terminal and Burner.
40
Page 41
CT80-250 Parts List - Installation & Operation Instructions
Table 12-1 Odyssey Parts List:
Item Part # Models Description
1 CT80. 1 CT120. 1 CT215. 2 82390 3 82391 4 82727 5 82728 6 84787 7 84788 8 81342
9 13701 10 82905 11 ­12 ­13 ­13 ­13 ­14 ­14 ­14 ­15 ­15 ­15 ­16 ­17 82894 17 82895 17 82896 18
84829
19 F3.CT 19 F10.CT 20 84024 21 F5.CT 21
81032 21 81032 21 BF5.CT 22 81764 23 81098 24 81138 25
83026 26 81625 27 81522-1 28 81109 28 81097 28 81110 28 81111 29 81522-2 30 81453 31 81847
32 81633 33 84797 34 84828 35 -
CT80-100 CT120-180 CT215-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 Jacket Common, Back-Bottom, HydroStat CT80-250 Jacket Common, Front Cover, HydroStat CT80-100 Jacket 82002, Right Side, HydroStat CT120-180 Jacket 82003, Right Side, HydroStat CT215-250 Jacket 82004, Right Side, HydroStat CT80-100 CT120-180 CT215-250 CT80-100 CT120-180 CT215-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-100 CT215-250 CT80-100 Blast Tube, Riello F3 Natural Draft CT120-180 CT80-100 CT120-250 CT90-120 CT90-120 CT90-120 CT90-120 CT90-120 CT90-120 CT90-120 CT90-120 CT90-120 Insulated Flex, 10 ' CT90-120 Insulated Flex, 15 ' CT90-120 Insulated Flex, 20 ' CT90-120 CT90-120 CT90-120 CT80-250 CT80-250 CT80-250 CT80-250
Boiler Only, CT80 (3 section) Boiler Only, CT120 (5 section) Boiler Only, CT215 (7 section) Site Glass, Round, #R100385 Site Glass Gasket, #R100934 Site Glass Retainer Site Glass Retaining Bolts Fuel Smart HydroStat Model 3250 Electro-Well , Hydrolevel Tridicator Relief Valve, 30 psi Blocked Vent Switch (Natural Draft models only)
Jacket 82002, Left Side, HydroStat Jacket 82003, Left Side, HydroStat Jacket 82004, Left side, HydroStat Jacket 82002, Top Cover, HydroStat Jacket 82003, Top Cover, HydroStat Jacket 82004, Top Cover, HydroStat Jacket Common, Back-Top, HydroStat Baffle, MPS 9 (1/unit) Baffle, MPS 10 (1/unit) Baffle, MPS 11 (1+1/unit) Outlet Tee, HydraStat Burner, Riello F3, Natural Draft Burner, Riello F10, Natural Draft
Burner & Blast Tube, Riello F5, Natural Draft Burner & Blast Tube, Beckett, NYC601CT, Natural Draft Burner & Blast Tube, Beckett, NYC602CT, Natural Draft Burner & Blast Tube, Riello BF5, Direct Vent 5"- 3" Ported Adapter 3" Insulated Flex to Pipe Adapter 3" Flex, 10 ' 5"x 3" 90 Degree Elbow Ported Adapter (optional) Hose Clamps, 3" Direct Vent Terminal, 8” Wall Insulated Flex, 5 '
Extended Direct Vent Terminal, 20" Wall (optional) Silicone, High Temperature, Nu Flex 302, Red (83ml) 3" Direct Vent 90 Degree Elbow (optional) 3" x 20 ' Flex Aluminum (optional) Grommet, Electro-well Odyssey, Ground Wire, HydraStat Brackets, Rear - Left
Odyssey
41
Page 42
Odyssey
Installation and Operation Instructions - Parts List CT80 -180
Item Part # Models Description
36 ­37 ­38 ­39 ­40 ­41 82893 42 82892 43 82726 44 82982 45 82897 46 82490 47 76023 48 82350 49 82133 50 82975 51
81671
CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250 CT80-250
Brackets, Rear - Right Brackets, Front - Left Brackets, Front - Right Control Panel, HydraStat Hold Down Bracket, HydraStat Boiler Heat Exchanger Insulation, Fiberglass (White) Door Insulation Boiler Drain Bushing, Boiler Drain Ring Gasket, Boiler Drain Stud, M8 x 30mm (included with jacket kit) Washer, 5/16” Flat, Zinc Plated (included with jacket kit) Nut, brass, M8 (included with jacket kit) Ball Stud Retaining Clips, #R102017 (10 pcs/bag) Insulation Singe Unfaced, Duct Wrap DM225 Plastic Bailer Twine
42
Page 43
13.0 WARRANTY
A licensed and trained Heating Technician must install this appliance, otherwise the Warranty is VOID.
FREE extended coverage Option C, only IF you register your boiler and installation with NY Thermal Inc. within the first year of purchase.
What Is Covered We, the manufacturer, warrant that any parts or components of each new Boiler or Water Heater, will be supplied free of defects in material or workmanship. This warranty replaces any other warranty implied or expressed. All the durations, terms and conditions mentioned hereafter are for manufacturer defects due to material or workmanship only, and do not include misuse or normal wear of the equipment. Equipment returned for warranty consideration, will be evaluated upon the condition of the part when examined by NY Thermal Inc. or an authorized service representative. Improper handling and/or installation practices may VOID the warranty. See silver rating plate label on unit exterior for appliance type, model number, and serial number information.
Warranty only valid to the original owner and location and is not transferrable.
Models Covered:
Application Model Numbers Options
Natural Draft
CT80, CT90, CT100, CT120, CT150, CT180, CT215, CT230, CT250
A,B,C
Direct Vent CT90, CT100, CT120 A,B,C
Owner’s Warranty Record:
Appliance Model No.
Serial No. Date Installed Contractor
Basic Coverage A - We will repair or replace any component, supplied or manufactured by NY Thermal Inc.,
that is found to be defective, for a period of twelve (12) months from date of installation, if it is within the "Terms and Conditions" of this warranty, and in compliance with the original manufacturer’s warranty.
Extended Coverage B - We will repair or replace the pressure vessel, if found to be defective, for a period of five (5) years for Boilers, from the original date of installation, and if found to be in compliance with the recommended installation and "Terms and Conditions" of this warranty.
Extended Residential Coverage C - We are so confident in the quality of our product, that we offer an extended warranty plan for the pressure vessel, if found to be defective, for a period of twenty (20) years from the date of installation, if found to be in compliance with the recommended installation and "Terms and Conditions" of this warranty. This extended plan will credit the costs of repair or replacement of the unit from six (6) to ten (10) years, and on a pro-rated schedule ranging from 100% in year eleven (11) to a fraction of the selling price effective at that time, in year twenty (20). To receive this warranty, the boiler and installation must be registered with NY Thermal. The registration card must be filled out and returned to NY Thermal Corporation within one (1) year of purchase of the unit.
Terms and Conditions
1. This warranty is VOID if: a. The appliance is not installed and serviced by a licensed and trained Heating Technician. b. The installation is not in accordance with this manufacturer’s manuals, local codes, and regulations. c. The heating system does not provide and ensure required flow through the heat exchanger when the
burner is on.
d. Deformation occurs due to freezing; improper storage or handling; improper firing or firing without water.
2. Any repairs or replacements made without authorization by or notification to the manufacturer.
3. This warranty does not cover the labour and shipping costs associated with installing a repaired or replaced boiler.
4. Installations determined to have any leaks in the entire heating system causing make up water to enter the system (eg. Solder leaks, coil gasket leaks, frequent system drainage).
5. Decision of warranty repairs or replacements to appliances will be at the discretion of the manufacturer or authorized service representative.
6. This warranty is to the original owner only.
Page 44
Odyssey
Installation and Operation Instructions - Parts List CT80 -180
What To Do In The Case of A Warranty Service Problem
1. Contact your installing contractor or service provider. Do not call NTI.
2. If your contractor or service representative requires further help, they will contact us directly.
3. If you cannot contact your contractor or service representative, contact us at 1-506-657-6000 to the attention of the Service Department.
NOTE: NTI cannot provide technical assistance to homeowners unless they are a licensed and trained
Heating Technician.
4. We as the appliance manufacturer will replace or credit the parts under warranty; credits are issued to the authorized wholesaler at their cost, so do not purchase replacement parts from suppliers with hopes of receiving 100% credit; it is recommended to receive all your warranty parts from your authorized service representative or us directly, at no charge (if under the warranty coverage).
5. We care about the quality of service you receive, so please let us know if you have complaints concerning your authorized service representative.
For Service Contact:
Name: ____________________________________
Owner’s Name Address City Province / State Boiler Model Serial Number Installer’s Name Date of Installation
Warranty Registration Form
Odyssey Oil Boiler
Complete this form, photocopy, and return to:
NY Thermal Inc. 65 Drury Cove Road Saint John, N.B. E2H 2Z8 Canada
NY Thermal Inc. 65 Drury Cove Road Saint John, NB E2H 2Z8 Canada
44
Technical Assistance: 1-800-688-2575
Website: www.nythermal.com
Fax: 1-506-432-1135
Loading...