Ochsner Air Eagle 717, Air Eagle 414, Multi-Tower T200 Operating And Installation Manual

BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 1 of 76
Operating and installation manual
OCHSNER AIR EAGLE 717
OCHSNER AIR EAGLE 414 OCHSNER AIR EAGLE 717 with MULTI TOWER (T200) OCHSNER AIR EAGLE 414 with MULTI TOWER (T200)
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 2 of 76
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 3 of 76
Contents
1 General ......................................................... 4
1.1 Information on documentation ...................... 4
1.2 Safety regulations ........................................... 4
2 Appliance description ................................... 5
2.1 Heat pump ...................................................... 5
2.2 CE designation ................................................. 5
2.3 Scope of delivery ............................................. 5
2.4 Function .......................................................... 6
2.5 System overview ............................................. 6
3 Outdoor unit ................................................. 7
3.1 Choosing the installation location................... 7
Minimum wall clearances ................................ 8
Dimensions ....................................................... 8
3.2 Opening the outdoor unit ............................... 9
3.3 Main components ......................................... 10
3.4 Cable entries ................................................. 10
3.5 Foundation for the outdoor unit ................... 11
Strip foundation ............................................. 12
Spot foundation ............................................. 12
Concrete plinth .............................................. 13
Installing on flat roofs .................................... 13
4 Indoor unit .................................................. 15
4.1 Golf-Midi indoor unit .................................... 15
Main components .......................................... 15
Connections ................................................... 16
Choosing the installation location.................. 16
Venting the system ........................................ 18
Safety valve .................................................... 18
Expansion vessel/system pressure................. 18
4.2 T200 (MULTI TOWER) indoor unit ................. 19
Appliance description .................................... 19
Main components .......................................... 20
Choosing the installation location.................. 20
Hydraulic and refrigerant connections .......... 22
Transport and handling .................................. 23
Safety valve .................................................... 26
DHW connection and safety assembly........... 26
Filling the system ........................................... 27
Venting the system ........................................ 28
Using T200 with a heating circuit with mixing
valve ............................................................... 28
Cooling with T200 .......................................... 28
T200 maintenance ......................................... 29
5 Connection lines ......................................... 30
5.1 Refrigerant lines ............................................ 30
5.2 Conduit to house ........................................... 31
6 Electrical connection ................................... 32
6.1 Preparation ................................................... 32
6.2 Guidelines ..................................................... 33
6.3 Power connection details.............................. 33
6.4 PSU signal contact ......................................... 34
6.5 Uninterrupted tariff ...................................... 34
6.6 Shutdown by tariff contactor ........................ 34
6.7 Night tariff ..................................................... 34
6.8 Modbus wiring .............................................. 34
6.9 Sensor wiring................................................. 34
6.10 Pumps, drives 230 VAC.............................. 35
6.11 HLSC on the heating circuit ....................... 35
6.12 DHW booster heater .................................. 35
6.13 Wiring diagram .......................................... 36
6.14 Indoor unit wiring ...................................... 37
Golf-Midi indoor unit ..................................... 37
T200 (MULTI TOWER) indoor unit ................. 38
Outdoor unit wiring .................................................. 40
6.15 Wiring diagrams ......................................... 41
EAGLE 717 with Golf-Midi indoor unit ........... 41
EAGLE 717 with T200 indoor unit .................. 42
EAGLE 414 with Golf-Midi indoor unit ........... 43
EAGLE 414 with T200 indoor unit .................. 44
7 Heating system ........................................... 45
7.1 Quality of heating water ................................ 45
7.2 Pressure maintaining system ......................... 45
8 Commissioning ............................................ 46
8.1 Before starting ............................................... 46
8.2 Persons required on site ................................ 46
8.3 Setting the flow rate ...................................... 47
9 Operation .................................................... 48
9.1 Menus ............................................................ 48
9.2 Appliance function ......................................... 49
Heating circuit ................................................ 49
DHW ............................................................... 49
Anti-legionella function ................................. 49
Second heat generator .................................. 49
Screed drying program .................................. 49
9.3 System operation ........................................... 49
Running costs ................................................. 49
Flow temperatures ........................................ 49
10 Troubleshooting .......................................... 50
10.1 Error Codes OTE ......................................... 51
10.2 Dealing with faults ..................................... 52
10.3 Rectifying minor causes independently ..... 52
10.4 Cleaning and care ....................................... 52
11 Maintenance ............................................... 53
11.1 Customer service ....................................... 53
11.2 Maintenance contract ................................ 54
12 Environment and recycling .......................... 55
12.1 Disposal of transport packaging ................. 55
12.2 Decommissioning ....................................... 55
12.3 Disposal of the appliance ........................... 55
13 Specification ............................................... 56
13.1 Data table (with Golf-Midi indoor unit) ..... 56
13.2 Data table (T200 indoor unit) .................... 58
13.3 Pressure drop ............................................. 59
13.4 Pump curves............................................... 59
13.5 Limits of use ............................................... 59
13.6 Performance diagrams EAGLE 717............. 60
13.7 Performance diagrams EAGLE 414............. 60
13.8 Details of energy consumption .................. 61
AIR EAGLE 414 ............................................... 61
AIR EAGLE 717 ............................................... 61
13.9 Electrical wiring diagrams EAGLE 717 ........ 62
13.10 Electrical wiring diagrams EAGLE 414 ........ 67
14 List of figures ............................................... 72
15 List of tables ................................................ 72
16 Declaration of conformity ........................... 73
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 4 of 76
1 General
1.1 Information on documentation
The following information is a guideline for the complete documentation.
Please read your heat pump's operating manual carefully from beginning to end. This will help you to operate your heat pump better. This manual is to be kept readily accessible near the heat pump. The precautionary information provided below is used in this document.
WARNING Failure to observe this information poses a risk of injury or death and may lead to material damage. This information must be observed without fail.
CAUTION Failure to observe this information may lead to an appliance fault or material damage. This information should be observed.
PLEASE NOTE
CAUTION
Information for work on electrical systems. This information must be observed without fail. Caution - risk to life!
1.2 Safety regulations
Read this manual thoroughly before commissioning the heat pump or making settings!
The appliance must not be converted or modified in any way. Work on the
appliance (repairs, modifications) may only be carried out by the manufacturer or bodies authorised by them.
Turn off all mains fuses of the system before carrying out any work on plug-in strips or electrical connections (wires).
Commissioning and servicing of the
appliances may only be carried out by
specialist personnel authorised by OCHSNER.
Installation of the appliances and their wiring may only be carried out by a specialist in accordance with local regulations.
The controller can be used to enable
functions to protect the heat pump.
However, since the controller is not certified as a safety device, safety measures in case of failure of or damage to the heat pump (e.g. additional external switching of the safety devices in use) must comply with local regulations.
In order to avoid malfunctions, fitting the snow cover on the EAGLE outdoor unit is mandatory. In the event of heavy snowfall and after longer idle periods, it may be necessary to remove the snow.
WARNING
Do not use the appliance as a step or platform. Do not climb on the appliance or place any loads on it.
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 5 of 76
2 Appliance description
2.1 Heat pump
OCHSNER AIR EAGLE 717 and OCHSNER AIR EAGLE 414 are air/water heat pumps configured as split appliances.
The appliance extracts heat at a low temperature from the outdoor air and releases it to the heating water at a higher temperature. Heating water can be heated to a flow temperature of up to 65°C. The appliance is equipped with an electric booster heater (DHC). In monovalent mode, the electric booster heater is switched on when the bivalent point is not reached to ensure heating mode or the provision of high DHW temperatures.
Special features of this heat pump:
Output-dependent refrigerant circuit
Variable speed compressor
Refrigerant circuit controller
OTE heat manager
Split outdoor unit with compressor
Additional properties:
Suitable for underfloor and radiator
heating systems
Low temperature heating systems are
preferred
Heat can still be extracted from the
outdoor air at temperatures as low as ­20°C
Corrosion protected - external cladding
components are made of powder coated stainless steel
Includes all components and safety-
relevant devices required for operation
Contains non-flammable safety
refrigerant
Two different indoor units are available for the air/water heat pump:
Golf-Midi indoor unit
T200 (MULTI TOWER) indoor unit
2.2 CE designation
The product you have purchased conforms to the technical regulations valid at the time and is compliant with CE standards.
2.3 Scope of delivery
The OCHSNER AIR EAGLE heat pump is delivered in 2 sections.
Golf-Midi indoor unit:
The indoor unit is delivered without its casing installed. The casing sections are in a separate package on the same pallet.
Contents of packages:
Name plate
Cowl for outdoor installation
Front panel
Rear panel
Side panels, left/right
OTE controller sensor set
Operating manual
Optional accessories:
OTE sensor set for buffer
T200 (MULTI TOWER) indoor unit:
The following components are packed inside the MULTI TOWER, next to the two pumps:
Outside temperature sensor
Adjustable feet
Drain hose
Operating manual
Gaskets for the hydraulic connection (heating circuit flow/return, cold water, DHW) are attached directly at the connections.
Outdoor unit:
The outdoor unit is shipped fully assembled. It is transported on a pallet.
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 6 of 76
2.4 Function
Heat is extracted from the outdoor air via the heat exchanger (evaporator) on the air side. The refrigerant is evaporated and compressed by a compressor. This requires electrical energy. The refrigerant is now at a higher temperature level and releases the heat from the air to the heating system via another heat exchanger (condenser). During this, the refrigerant expands and the process begins again. At air temperatures below
approx. + 7 °C air humidity condenses as ice on the evaporator fins. This ice is automatically removed (defrosting). In the defrost phase, the fan shuts down and the heat pump circuit is reversed. The heat required for defrosting is drawn from the buffer tank or the heating circuit. At the end of the defrost phase the heat pump automatically returns to heating mode.
2.5 System overview
The heat pump consists of a split outdoor unit and an indoor unit which is installed in the boiler room. The connection to the heating system is made via
the flow and return of the heat sink side of the heat pump.
Figure 1: System overview
EAGLE indoor
Primary/secondary
distribution
EAGLE outdoor unit
Heating return
Heating flow
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 7 of 76
3 Outdoor unit
Figure 2: EAGLE outdoor unit
The EAGLE outdoor unit is installed outdoors on a plinth provided on site. The outdoor unit consists of a sound-insulated casing for the horizontal fan and refrigerant circuit components, such as the evaporator, compressor, expansion valves and others. It should be installed as closely as possible to the indoor unit. The minimum clearances to walls and recesses should be observed for installation.
CAUTION Risk of injury!
Never remove the grille from the fan.
3.1 Choosing the installation location
The heat pump can be installed at altitudes of up to 1000 m above sea level.
High wind loads on the outdoor unit can cause problems with defrosting in defrosting mode.
Avoid installation in an open and exposed location with high expected wind loads (e.g. flat roof of a house in a raised location).
Select an installation location where the appliance is on the side of the building facing away from the wind (leeward side).
Avoid acoustic reflections when installing the EAGLE outdoor unit:
Avoid installation on reverberant floors.
Installation between two walls can lead to
increased sound levels.
Avoid installation next to bedrooms.
Plants and planted areas can reduce sound
levels.
Provide a frost-free drain for any condensate to drain away. A gravel bed with drainage connection underneath the evaporator is sufficient. In winter, ice may form around the drain.
Please note the following with regard to installation in coastal areas:
The outdoor unit must be installed at least
1 km away from the sea.
The installation location selected should
always be on the leeward side of the building (the side facing away from the sea).
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 8 of 76
Minimum wall clearances
Do not place the outdoor unit in a recess. The diagram shows the minimum wall clearances.
Figure 3: Outdoor unit minimum clearances (in mm)
Dimensions
Figure 4: Outdoor unit dimensions (in mm)
min. 1000
min. 500
min. 1000
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 9 of 76
3.2 Opening the outdoor unit
The EAGLE outdoor unit is delivered as a closed unit. It has to be opened for the connection of the refrigeration and electric system. We recommend securing the outdoor unit before removing the casing cover.
Procedure:
1. Secure the outdoor unit
2. Undo screws on the cover
3. Lift cover out
4. Remove cover
Cover can now be
removed
4
3
Slide cover upwards out
of the bracket
2
Undo 2 hexagon
socket 6 screws
M8x200
Release cover
Secure the
outdoor unit
1
Casing cover
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 10 of 76
3.3 Main components
Figure 5: Outdoor unit main components
3.4 Cable entries
Remove the mounting plate to pass through the hot gas and liquid pipes as well as the 3 supply cables. After the outdoor unit has been positioned, the pipes can be aligned and cables
passed through. When everything is ready, re­align the mounting plate and tighten the cable entries.
Figure 6: Outdoor unit conduits
Outdoor unit
control box
Compressor
Fan motor
Inverter
Refrigerant
circuit
Connection
line conduit
Cable entries
Liquid line
Hot gas line
Cable entries for control
cables
M25 x 1.5
Liquid line
Hot gas line
Conduits
Hot gas line
M25 x 1.5
Mounting plate
removed
Cable entry for BUS
cable
M16 x 1.5
Cable entry for power
supply
M25 x 1.5
Conduit
Liquid line
M25 x 1.5
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 11 of 76
3.5 Foundation for the outdoor unit
A permanent foundation is required beneath the outdoor unit. The foundation must meet the load bearing requirements of the outdoor unit (see section 13, Specification).
Provide for frost-free drainage (e.g. a gravel
bed with a frost-free connection to a drain) for condensation that forms on the outdoor unit.
Where refrigerant lines are to be laid in the
ground, ensure correct positioning of the pipe liner when laying the foundations.
Use rigid underground sewage pipes or
flexible, double-skinned cable ducts (smooth on the inside) for the pipe liner.
This must be done in accordance with the
relevant Building Codes of Practice and regulations.
Take the expected wind loads at the installation site into consideration. Ensure that the outdoor unit is adequately secured to the foundation to prevent it from tipping over due to wind loads.
CAUTION: Slipping hazard
If drainage for condensation is inadequate, ice can build up in winter in the area around the outdoor unit.
- Ensure drainage for
condensation is sufficient even at low temperatures.
- Ensure that no ice is formed,
especially around walking surfaces and entrances around the outdoor unit.
NOTE
Insulation used beneath the soil must be made of a closed-cell material. Otherwise, the thermal insulation of the material will be impaired.
Figure 7: EAGLE outdoor unit (view from below), fixing holes in the outdoor unit legs (dimensions in mm)
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 12 of 76
Strip foundation
1
Strip foundation
2
Pipe liner for the connecting lines (where installed underground)
3
Gravel bed
4
Drainage pipe (frostproof)
Figure 8: Strip foundation (dimensions in mm)
Spot foundation
1
Spot foundation
2
Pipe liner for the connecting lines (where installed underground)
3
Gravel bed
4
Drainage pipe (frostproof)
Figure 9: Spot foundation (dimensions in mm)
2
1
3
4
min. 800
2
1
3
4
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 13 of 76
Concrete plinth
Figure 10: Installation on concrete plinth (dimensions in mm)
Installing on flat roofs
NOTE
Avoid installing the EAGLE outdoor unit on roofs over living spaces or car ports attached to living spaces due to the risk of structure-borne noise transmission.
WARNING Risk of falling
Working on a flat roof without fall protection constitutes a risk.
When working on a flat roof,
observe the laws relating to occupational safety in your region.
Always be aware of the open
edge.
Loads and stresses on roof structure
Note that when outside temperatures are very low, ice can form beneath the outdoor unit.
In terms of roof structure loads, allow for an ice load of 400 kg/m² in addition to the dead weight of the outdoor unit.
When installing the EAGLE outdoor unit on top of a freestanding car port, a garage or a storage space, please note the following:
Provide a suitable plinth for roof installation.
Take the concentrated load arising from the
dead weight of the outdoor unit (subject to the type of plinth) and the surface load caused by possible build-up of ice into consideration.
Ensure suitable sound insulation between the
outdoor unit and the installation points on the plinth.
Use suitable anti-vibration pads between the
plinth and the outdoor unit legs (OCHSNER accessory no. 290698) – see Figure 11.
Provide sound insulation between the
outdoor unit legs and the plinth – see Figure 11.
Use suitable sound-insulating pipe fixings to
secure the refrigerant lines.
700
min. 1600
1100
200
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 14 of 76
1
Base
2
Anti-vibration mount
3
Rubber grommet
4
Washer
5
Fixing screw
Figure 11: EAGLE outdoor unit secured with structure-borne noise attenuating fixings
1
Flat roof
2
Refrigerant lines in open air with thermal insulation and UV protection
3
Base
4
Anti-vibration mount
Figure 12: Flat roof installation of EAGLE outdoor unit (dimensions in mm)
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 15 of 76
4 Indoor unit
The indoor unit is installed in the heating distribution room or any other suitable room. The indoor unit contains the condenser and all hydraulic components required for operation with a water-filled heating system. Observe the minimum clearances to the wall and recesses when installing the unit and ensure the maximum room temperature does not exceed 30°C.
4.1 Golf-Midi indoor unit
Main components
Figure 13: Indoor unit detailed view
Indoor unit control box
OTE controller
MFA module with
3-way switching valve
Safety valve
Electric auxiliary heater
8.8 kW
Flow sensor
Air vent
Circulation pump
Plate heat ex-
changer
Condenser
Expansion vessel
Service valve for expansion vessel
Valve for filling and
draining
DHW
flow
Heating
flow
Heating
return
DHW
return
Bypass connection
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 16 of 76
Connections
Figure 14: View from above
Choosing the installation location
4.1.3.1 Minimum wall clearances
Figure 15: Minimum wall clearances
Room temperature <30°C
Controller voltage
230 V~
Booster heater
400 VAC
Sensors <12 V
Liquid line
DHW heating
return
Heating
return
DHW heating
flow
Heating
flow
Hot gas line
Pressure gauge
b
bar
40 cm
min 40 cm
min 40 cm
min 100 cm
65 cm
min 5 cm
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 17 of 76
4.1.3.2 Dimensions
Figure 16: Indoor unit dimensions
Figure 17: Indoor unit tilt height
Figure 18: Indoor unit connection dimensions
min. 50 mm
1150 mm
400 mm
650 mm
approx. 132 cm
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 18 of 76
Venting the system
Figure 19: Indoor unit air vent valve
CAUTION Close the valve cap after venting.
Safety valve
NOTE
Water will escape when the safety valve is opened. Route the drain hose into the sewage drain at the rear of the indoor unit. The drain must not be permanently connected to the sewage drain! A funnel with a siphon must be provided.
- Size the drain hose to ensure water can drain
freely when the safety valve is fully open.
- Ensure that the safety valve drain hose is open
to the atmosphere.
- Route the safety valve drain hose with a
continuous slope to the drain.
- Secure the drain hose to prevent movement
when water is running out.
Expansion vessel/system pressure
Preparation for filling:
A 24 l expansion vessel is installed in the heat pump Golf-Midi indoor unit. In buffer systems or systems with higher capacity, this expansion vessel should be checked. If required, install an additional expansion vessel in the system (externally, not inside the appliance).
Figure 20: Draining and filling detailed view
Before filling the system, check the pre-charge pressure in the expansion vessel. This must be matched to the building height.
- Static head: Difference between highest and
lowest points in the system.
- Pre-charge pressure = static head + 0.3 bar
- System charge pressure = pre-charge pressure
+0.5 bar (when cold)
- Max. permissible operating pressure: 2.6 bar.
Select a safety valve with 3.0 bar.
See EN ISO 4126-1:2013-10-15, part 1: Safety valves.
- Flush the heating system thoroughly before
filling.
- Only fill with water of potable quality.
CAUTION!
Replace plastic closures with suitable plugs.
Air vent valve
Drain and fill opening Expansion vessel
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 19 of 76
4.2 T200 (MULTI TOWER) indoor unit
Appliance description
The buffer tank and the DHW tank with heat exchanger are arranged on top of each other and can be separated for handling.
1
Heat pump
2
Hot gas
3
Liquid
4
Buffer charging pump
5
Multifunctional assembly (MFA)
6
Magnesium anode
7
Cable grommet
8
Drain stopcock
9
Heating circuit
10
DHW circulation
11
Cold water
12
DHW
13
Connecting hoses
14
Buffer tank
15
DHW tank
Figure 21: T200 hydraulic schematic
The appliance is fitted with a plastic foam outer casing and a removable front panel. The appliance is connected hydraulically and electrically to the heat pump. All hydraulic connections are at the top.
Further system components are integrated alongside the DHW tank and the buffer tank: Heat pump manager, tank charging pump, high efficiency circulation pump for one direct heating circuit, multifunctional assembly with safety valve and 3-way switching valve, emergency/booster heater for mono energetic operation.
4.2.1.1 DHW tank
The steel tank is fitted internally with a special direct enamel and a sacrificial anode. The anode with wear indicator protects the inside of the tank against corrosion.
The heating water heated by the heat pump is pumped through an internal indirect coil in the DHW tank. The internal indirect coil transfers the absorbed heat to the DHW. The integral heat pump manager controls DHW heating to the required temperature.
4.2.1.2 Buffer tank
The steel tank serves to hydraulically separate the flow rates of the heat pump and the heating circuit. The heating water heated by the heat pump is transported to the buffer tank by the tank charging pump. When there is a demand, the heating water is supplied to the heating circuit by the integral heating circuit circulation pump.
4.2.1.3 Heat pump manager (OTE)
The system is controlled via the integral OTE3 heat pump manager. For adjustment options, see the controller operating manual.
4.2.1.4 Multifunctional assembly (MFA)
The multifunctional assembly switches between heating circuit and DHW heating.
10
11
12 9 2
1 3 5
6
8
7
13
8
4
14
15
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 20 of 76
Main components
1
Magnesium anode
2
Air vent valve (MFA)
3
Electric booster heater 8.8 kW (MFA)
4
Safety valve (MFA)
5
3-way switching valve (MFA)
6
Electrical connection
7
Cable entries
8
Maintenance flange
9
Drain stopcock
10
Buffer tank (100 l)
11
Drain stopcock
12
Heating circuit pump
13
Buffer charging pump
14
DHW tank (168 l)
15
Condenser (plate heat exchanger)
16
High limit safety cut-out (MFA)
17
Air vent valve
Figure 22: Main components in T200 indoor unit
Choosing the installation location
CAUTION Do not install the appliance in damp rooms!
Install the appliance in a frost free and dry room near the draw-off point. In order to reduce line losses, keep the distance between the indoor unit and the outdoor unit small.
Ensure that the floor has adequate load bearing capacity and is sufficiently level (for weight, see section 13, Specification). The room must not be endangered by explosive dust, gases or vapours.
If installing the appliance in a boiler room with other heating appliances, ensure that their operation is not affected.
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 21 of 76
4.2.3.1 Minimum wall clearances
Figure 23: Minimum clearances (in mm)
Minimum clearances to the side can be either to the right or the left.
4.2.3.2 Dimensions
Figure 24: Dimensions (in mm)
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 22 of 76
Hydraulic and refrigerant connections
e01
Heating circuit flow 1" union nut with flat gasket
e02
Heating return 1" union nut with flat gasket
e50
Hot gas line
e51
Liquid line
c01
Cold water inlet 1" union nut with flat gasket
c06
DHW outlet 1" union nut with flat gasket
c10
DHW circulation 12 mm copper
c12
Safety valve drain
Figure 25: Hydraulic connections and labels, T200 refrigeration
BA_OCHSNER AIR EAGLE_414_717_V06_EN.docx Page 23 of 76
Transport and handling
- Remove the 4 screws from the non-
returnable pallet.
Figure 26: Removing the fixing screw
- Slightly tilt the appliance and screw in the
4 adjustable feet supplied.
- Lift the appliance from the pallet.
Should narrow doors or corridors impede handling, the top and bottom sections of the appliance can be separated as described in the following sections.
Removing the front cladding:
- Remove the screw from the top centre of the
appliance.
- Unhook the front cladding towards the top.
- Disconnect the control panel plug and the
front panel earth wire.
Installing the front cladding
Install the front cladding in reverse order.
Separating the appliance sections:
Figure 27: Pull the sensor from the buffer tank.
- Pull out the sensor on the buffer tank.
- Remove the sensor cable from the guiding
groove in the insulation element.
Figure 28: Undoing the plug-in connectors
- Undo the plug-in connectors of the 4 hydraulic
connections. Pull out the spring clips fully using a screwdriver.
- Pull off the hydraulic connections towards the
front.
Loading...
+ 53 hidden pages