Ochsner AIR 7, AIR 41, AIR 11, AIR 18, AIR 23 Operating And Installation Manual

...
HIGH EFFICIENCY AIR/WATER HEAT PUMPS
OPERATING AND INSTALLATION MANUAL
AIR 7
AI R 11
AIR 18
AIR 23
AIR 41
CONTENTS
PLEASE NOTE OPERATION
1. Information on documentation 4
1.1 Safety information 4
1.1.1 Arrangement of safety information 4
1.1.2 Symbols and possible dangers 4
1.1.3 Keywords 4
1.2 Other symbols 5
1.3 Units of measurement 5
1.4 Specied performance data 5
2. Safety 5
2.1 Intended use 5
2.2 General safety information 5
3. Appliance description 6
3.1 Functionality 6
3.2 Appliance components 6
3.2.1 Indoor unit 6
3.2.2 Outdoor unit 7
3.2.3 Heat pump control unit 7
3.3 Name plate 7
4. Activating settings 8
4.1 Operating costs 8
4.1.1 Flow temperatures 8
4.1. 2 Ventilation 8
4.1. 3 Heating setback program 9
5. Maintenance and care 9
6. Problem solving 9 INSTALLATION
7. Safety 10
7.1 General safety information 10
7. 2 Regulations, codes and standards 10
8. Appliance description 10
8.1 Standard delivery 10
8.2 Hydraulic variants of the indoor unit 11
9. Preparing to install the appliance 13
9.1 Indoor unit installation location 13
9.1.1 Keep minimum clearances 13
9.2 Outdoor unit installation location 13
9.2.1 Keep minimum clearances 14
9.3 Foundations for the outdoor unit 14
9.3.1 Laying spot foundations 15
9.3.2 Laying strip foundations 16
9.3.3 Installing on at roofs 16
9.4 Preparing the refrigerant lines 17
9.4.1 Line lengths 18
9.4.2 Pipe diameter 18
9.4.3 Preparing the wall outlets 19
9.4.4 Preparing refrigerant lines passing through open air 20
9.4.5 Preparing underground refrigerant lines 20
9.5 Preparing the electrical connections 22
9.5.1 Heat pumps for three-phase alternating current 22
9.5.2 Heat pumps for single phase alternating current 23
9.5.3 Cables from main distributor to indoor unit 23
9.5.4 Cables from indoor to outdoor unit 23
9.5.5 Temperature sensor 23
9.5.6 Pumps and servomotors (230 VAC) 24
9.5.7 PSU signal contact 24
9.5.8 Smart Grid 24
10. Appliance installation 25
10 .1 Installation of indoor unit 25
10 .1.1 Delivery and transportation 25 10 .1.2 Positioning the appliance 26 10 .1.3 Disassembling the appliance casing 26 10 .1.4 Assembling the appliance casing 27
10.2 Installing the outdoor unit 28 10 . 2 .1 Delivery and transportation 28
10.2.2 Positioning the appliance 29
10.2.3 Disassembling the appliance casing 29
10.2.4 Installing the snow cover 29
10.2.5 Fitting the cylindrical silencer 29
10.2.6 Installing the SSP snow cover 30
10.3 Connecting the heat sink system 31 10 . 3 .1 Connecting the heating water 31
10.3.2 Safety valve drain 32
10.3.3 Filling the heating system 32
10.3.4 Diaphragm expansion vessel (DEV) 33
10.3.5 Flow metering 33
10.3.6 Cooling version 33
10.3.7 Connecting the DHW 33
10.4 Electrical connection 34 10 . 4 .1 General 34
10.4.2 Electrical connection of the indoor unit 34
10.4.3 Electrical connection of the outdoor unit 36
10.5 Connecting heat source system 37 10 . 5 .1 Connecting the refrigerant lines 37
10.5.2 Checking for leak tightness 38
10.5.3 Filling the refrigerant circuit with refrigerant 38
10.5.4 Insulating the refrigerant lines 38
11. Commissioning 39
11.1 Before switching on for the rst time 39
11. 2 Testing the control circuit 39
11. 3 Adjusting the ow rate 39
11. 4 Heat generator pump (HGP) 42
11. 5 Necessary conditions for commissioning 43
11. 6 Commissioning the system 44
11.7 Decommissioning 45
12. Troubleshooting 46
12 .1 Fault messages on the master controller 46
12.2 Reset high limit safety cut-out 48
13. Appliance maintenance 48
13 .1 Testing safety valve 48
13.2 Maintenance contract 49
14. Specication 50
14 .1 Heat pumps for three-phase alternating current 50 14 .1.1 Data table 50 14 .1.2 Output diagrams 54 14 .1.3 Details of energy consumption 60
14.2 Heat pumps for single phase alternating current 62 14 . 2 .1 Data table 62
14.2.2 Output diagrams 64
14.2.3 Details of energy consumption 66
14.3 Limits of use 67
14.4 System schematic diagrams 68
14.5 Voltage quality in island mode 84
14.6 Dimensions and connections 85 14 . 6.1 Indoor unit 85
14.6.2 Outdoor unit 86
15. Environment and recycling 90
16. Declaration of Conformity 91
17. ERP-Data 93
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 3
PLEASE NOTE | Information on documentation
i

PLEASE NOTE

f The appliance can be used by children over the age
of eight years and by people with reduced phys­ical, sensory or mental abilities or with a lack of experience and knowledge, if they are supervised or instructed on the safe use of the appliance and understand the dangers that can arise from its use. Children must not be allowed to play with the ap­pliance. Children must not be allowed to clean or carry out user maintenance on the appliance without supervision.
f Connection to the mains electricity supply must be
by means of a xed connection. It must be possible to isolate the appliance from the mains supply with a multi pole switch which has a gap of at least 3 mm across all poles.
f You must not disconnect the mains supply even
outside the heating period. If the power supply is disconnected, active frost protection of the system cannot be guaranteed.
f You do not need to switch off the system for the
summer. The heat pump control unit changes over automatically between summer and winter.

OPERATION

1. Information on documentation

The “Please note” and “Operation” sections are intended
for the appliance user and the qualied contractor.
The “Installation” section is intended for the qualied con-
tractor.
Unless otherwise stated, all the content of this documenta­tion applies to the appliances listed on the title page. This documentation describes appliances that are not always standard items. There may therefore be differences to your
specic appliance.
Information
Read all of this documentation carefully before us­ing the appliance and keep the documents safe. Pass this documentation on to any new user.

1.1 Safety information

1.1.1 Arrangement of safety information
f Observe the minimum clearances in order to ensure
fault-free operation of the appliance and to allow for maintenance work on the appliance.
f In bivalent mode, the return water from the second
heat generator can ow through the heat pump. Note that the return water temperature must not exceed 65°C.
f Maintenance work such as checking the electrical
safety of the appliance may only be carried out by a
qualied contractor.
f We recommend an annual inspection (to assess the
appliance‘s actual condition) and if necessary main­tenance (to reinstate it to its expected condition) by a
qualied contractor.
KEYWORD: Type of risk
The possible consequences of not observing the safety information are shown here.
Instructions for action to remedy or remove
»
the source of danger are shown here.
1.1.2 Symbols and possible dangers
Symbol Type of risk
Injury
Electrocution
Burns (burns, scalding)
Material damage (appliance, consequential and environmental dam­age)
1.1.3 Keywords
Keyword Meaning
DANGER Failure to observe this information will result in seri-
WARNING Failure to observe this information may result in se-
CAUTION Failure to observe this information may result in
ous injury or death.
rious injury or death.
non-serious or minor injury.
4 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
OPERATION | Safety
i
i

1.2 Other symbols

► This triangular symbol is used as a bullet point.
These two arrows represent the symbol for an in-
»
struction. This shows that there is something you must do. The actions required are described step by step.
{{ These symbols show you the level of a software
menu. In this example, three menu levels are indicated.

1.3 Units of measurement

Information
In these documents, unless otherwise specied,
all linear measurements (e.g. in tables and illus­trations) are given in millimetres.
1.4 Specied performance data
The performance data of the appliance indicated in these documents (text, tables and diagrams) have been calcu­lated according to standardised measurement conditions. However, these measurement conditions often do not completely correspond to the plant-specic conditions ap­plicable in the respective user‘s system. System-specic factors that can affect the conditions include, for example,
the specic design of the system, the age of the system and the actual ow rates. For this reason, the stated per- formance data can differ from plant-specic performance
data.

2. Safety

2.1 Intended use

The appliance is intended for use in a domestic environ­ment. It can safely be used by persons who have received no instruction. The appliance can similarly be used in a non-domestic environment such as commercial premises, as long as it is used in the same instructed manner.
Any use of the appliance that is different from or goes beyond this is not regarded as intended use. “Intended use” also includes observing this documentation and the documentation of any accessories used.
Information
Air pressure and air humidity will affect the opera­tional reliability of the electrical components in the heat pump system (dielectric strength). The loca­tion of the heat pump system must be no more than 1000 m above sea level.

2.2 General safety information

Observe the following safety information and instructions for the appliance.
Only qualied contractors should carry out the electri-
cal work and installation of this appliance.
► Commissioning and maintenance of the appliance
may be carried out only by OCHSNER Customer Ser­vice or by customer service partners authorised by OCHSNER.
The stated performance data can be conrmed only if
the measurements taken for the appliance are carried out according to the relevant standardised measurement con­ditions.
► The authorised contractor is responsible for compli-
ance with all relevant regulations during installation and commissioning.
► Operate the appliance only when fully installed and
with all safety equipment tted.
► Protect the appliance from dust and dirt ingress dur-
ing building work. Use the plastic cover provided.
► Alterations to the appliance may be carried out only
by OCHSNER Customer Service or by customer ser­vice partners authorised by OCHSNER.
► Functions to protect the heat pump can be enabled
using the controller. However, since the controller is
not certied as a safety device, safety measures in
case of breakdown or damage to the heat pump (e.g. additional external switching of the safety devices in use) must comply with local regulations. In the case of upgrades or updates to the controller software, all function parameters of the heat pump must be checked.
► Before commencing work on electrical connections
and installation, the heat pump system must be isolat­ed and voltage-free.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 5
OPERATION | Appliance description
13_03_001
2
4
1
3
6
5
WARNING: Injury
The appliance may be used by children aged 8 and up and persons with reduced physical, sensory or mental capabilities or a lack of experience provided that they are supervised or that they have been instructed on how to use the appliance safely and have understood the possible risks. Children must not be allowed to play with the appliance. Children must not be allowed to clean or carry out user maintenance on the appliance without supervision.

3. Appliance description

The appliance is an air/water heat pump consisting of an indoor unit and an outdoor unit. The appliance can be used to heat a building and provide domestic hot water (DHW).

3.1 Functionality

An air/water heat pump extracts thermal energy from the ambient air (low temperature) and transmits it together with electrical drive energy in the form of useful heat (higher temperature) to a heating and/or DHW circuit.
The heat pump consists of separated circuits linked togeth­er via heat exchangers:
► Heat source circuit (extracting heat)
► Refrigerant circuit
► Heat sink circuit (supply of heat to the central heating
and/or DHW)
The operating principle of an air/water heat pump:
1 Evaporator (n heat exchanger) 2 Compressor 3 Condenser (plate heat exchanger) 4 Expansion valve 5 Heat sink (heating, DHW) 6 Air as heat source

3.2 Appliance components

3.2.1 Indoor unit
6 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
The indoor unit is intended to be installed only inside the building. The indoor unit contains the compressor, which in terms of sound technology is acoustically decoupled a number of times from the casing. The casing is acoustically optimised and allows particularly quiet operation.
OPERATION | Appliance description
i
11_02_200_214_01_004
Compressor
The fully hermetically sealed compressor is designed for high efciency heat pump applications. A suitable starting current limiter for the compressor is installed in the indoor unit.
Electric booster heater
The appliance is tted with an electric booster heater
(immersion heater). At low outdoor temperatures, the ap­pliance operates in bivalent-parallel mode. The appliance can also be combined with an additional heat generator.
Condenser
The condenser takes the form of a plate heat exchanger, which is built of stainless steel and insulated on all sides against condensation and heat loss.
3.2.2 Outdoor unit
The outdoor unit is intended to be installed outside. The outdoor unit is designed as a horizontal split evaporator. The indoor unit is connected to the outdoor unit with refrig­erant lines, along with electrical control and power supply cables.
► 1x direct circuit (heating and/or cooling)
► 1x mixed circuit (heating and/or cooling)
► 1x directly heated DHW cylinder (with electric booster
heater)
► 1x heat pump (heating and cooling)
► 1x additional heat generator (electric booster heater
or enable contact for external heat generator)

3.3 Name plate

Two name plates are attached to the indoor unit to identify your heat pump. In addition, a label with the serial number is attached to the right-hand casing panel of the appliance.
1
2
Evaporator
The evaporator is a part of the outdoor unit and consists
of copper pipes in a set of aluminium ns.
Information
With an air/water heat pump, frost may form on
the evaporator ns of the outdoor unit, depending
on the air temperature (below approx. +7°C), air humidity and the operating point. The evaporator
ns are automatically de-iced again in the cyclical
defrosting mode of the heat pump.
Fan
The outdoor air is blown across the evaporator by a quiet fan.
3.2.3 Heat pump control unit
The OCHSNER heat pump controller includes devices for controlling heat pump heating systems with a cooling function as well as DHW heating. In its standard version, the heat pump control unit consists of the OTE controller and the master controller, both of which are installed in the indoor unit.
1 Name plate (back of indoor unit and front of control
box)
2 Serial number (right-hand casing panel)
The OTE controller can control the following system circuits and heat generators:
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 7
OPERATION | Activating settings
i
i

4. Activating settings

Settings are activated with the master controller on the indoor unit (with graphic display or touchscreen), or via a remote controller with touchscreen that is attached to the wall.
5
Mo 09 .01.17 10:02
4
3
2
1 11
1 Button A:
Press to go back one menu step (ESC) 2 Displays function of Button A or fault message 3 Operating status 4 Outdoor temperature 5 Date 6 Time 7 DHW temperature 8 Actual room temperature 9 System temperature 10 Displays function of Button B 11 Button B:
Turn to select from menu or to change setting
Press to conrm (ENTER)
-12.5C 22°C 52.5°C
Heating mode
OCHSNER OTE
The master controller is mounted in an easily accessible plastic cover on the top of the indoor unit. Two buttons are provided for controlling the menu, with an illuminated graphic display.
6
7
32.5°C
MENU
8
9
10
11_01_200_701_01_01_001
Pressing Button B on the right calls up the main menu with a diagram of the heating system. Each heat consum­er (heating circuit, DHW circuit) and each heat generator (heat pump, electric booster heater, boiler etc.) has its own menu and corresponding submenus.
Pressing Button A takes you back one step to the previous menu.
You will nd further information on operating the heat pump
control unit in the control unit‘s operating instructions which are also supplied with the heat pump.
Information
The heat pump has no separate on/off switch. In an emergency, the system must be shut down via
the specied safety devices.
Ensure easy access to the safety devices. It
»
must be possible to perform an emergency shutdown at all times.
8 www.ochsner.com | 982000-AIR-M2-M4-EN03.1

4.1 Operating costs

In the rst two heating seasons, higher running costs are
to be expected (up to 50% more, depending on residual moisture in the building). Enabling the screed drying pro­gram will also increase operating costs further.
4.1.1 Flow temperatures
For optimum operation of your heat pump, you should aim
for the lowest possible heating ow temperatures (and also
DHW temperatures). The maximum system temperature for your heat pump should be restricted to 60°C.
Information
Increasing the room temperature by 1°C results in an increase in consumption of 5-7%.
4.1. 2 Ventilation
Any ventilation should be intermittent, especially during the heating period, and according to your own require-
OPERATION | Maintenance and care
i
i
ments. Intermittent ventilation is considerably more energy
efcient than permanent ventilation, and therefore saves
money. Avoid permanent ventilation.
4.1. 3 Heating setback program
From an energy efciency point of view, using a time pro-
gram to reduce the heating ow temperature is especially
not recommended for air/water heat pumps with low tem-
perature heating systems (such as underoor heating).
These systems are slow to respond and, due to the addi-
tional output from the system required following the end
of the setback phase, it is possible that the second heat
generator (boiler, electric immersion heater) will cut in. This
can lead to higher operating costs.

5. Maintenance and care

We recommend an annual inspection and if necessary
have your heat pump serviced by OCHSNER Customer
Service.
Material damage
Maintenance work on electrical components of the
heat pump may be carried out only by qualied
contractors.
Material damage
Abrasive tools must not be used to clean the evap-
orator ns in the outdoor unit.
Any dirt on the ns should be blown away
»
using compressed air (max. 8 bar), in the di-
rection of normal air ow. If the ns are very dirty, contact your OCHS-
»
NER system partner or OCHSNER Customer Service.
If it is necessary to clean the casing sections of the
»
indoor or outdoor unit, use only a damp cloth (with water or a weak soapy solution). Do not use any abra­sive or aggressive cleaning materials.
During the building phase, protect the indoor and
»
outdoor units from dirt and dust with a suitable cover. Use the plastic cover provided.
Ensure that the heating circuit is lled with sufcient
»
water.
Ensure that any condensation beneath the outdoor
»
unit can drain away without freezing all year round.
Information
If the outdoor unit is covered with a thick layer of snow, this can reduce system efciency.
Remove snow on and around the outdoor unit
»
as necessary. If required, install the snow cover available as
»
an accessory for the outdoor unit.
Information
Ensure that the refrigerant circuit of your heat pump is tested for leaks once a year (in acc. with Regu­lation (EU) no. 517/2014).
Ensure year-round access to soldered joints in
»
the refrigerant circuit. Document the results of the leakage test in the
»
system test report.

6. Problem solving

Problem Cause Solution
Too little DHW is available or the cen­tral heating system is too cold.
The appliance is leaking water.
If you have a problem that you cannot resolve, contact
the system installer, a qualied contractor or OCHSNER
Customer Service.
Faults are displayed as”Er XXX”on the master controller of the OTE control unit. If a fault occurs, contact your system installer. The system installer knows your hydraulic system and how it operates. The causes of faults can often be found in the settings or in the hydraulics.
Before contacting the installer, make a note of the serial number and the heat pump model. The serial number and heat pump model of your appliance are shown on the name plate. The name plates are attached to the back of the appliance on the outside and behind the front appliance casing panel (control box outer side).
Customer service hotline for Austria:
Tel: +43 (0) 504245 - 499 Email: kundendienst@ochsner.at
The power supply to the appliance has been cut off
The drain for the safe­ty valve is blocked.
Check the safety device on the main distributor board for your house. Switch the safety device back on. If the safety device trig­gers again after being switched back on, contact a qualified con­tractor or OCHSNER Customer Service.
Clean the safety valve drain. See „Safety valve drain“ on page 32.
Ensure that the outdoor unit (both the top and the un-
»
derside) is kept free from snow, leaves and twigs and other foreign bodies.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 9
Customer service hotline for Germany:
Tel: +49 (0) 69 256694 - 495 Email: kundendienst@ochsner.de
Customer service hotline for Switzerland:
Tel: +41 (0) 800 100 - 911 Email: kundendienst@ochsner.com
INSTALLATION | Safety
i

INSTALL ATION

7. Safety

Only a qualied contractor should carry out installation,
commissioning, maintenance and repair of the appliance.

7.1 General safety information

We guarantee trouble-free function and operational reliabil­ity only if the original accessories and spare parts intended for the appliance are used.

7. 2 Regulations, codes and standards

Information
Observe all applicable national and regional regu­lations and instructions.

8. Appliance description

8.1 Standard delivery

The standard delivery of your appliance includes the fol­lowing components.
1x indoor unit:
The following components are installed in the indoor unit:
AIR 7 AIR 11 AIR 18
Hydraulic variant M2-1 M2-2 M2-3 M2-4 M4-1 M4-2 M4-3 M4-4
Starting current limiter + + + + + + + +
Flow meter (heat sink side)
Circulation pump (heat sink side)
Internal flexible hose + + + + + + + + Safety valve + + + + + + + + Master control unit + + + + + + + + OTE heat pump con-
troller Diaphragm expansion
vessel 24 l 3-way switching mod-
ule (DHW) Electric booster heater
8.8 kW
+ + + + + + + +
+ + + + + + + +
+ + + + + + + +
+ + + + - - - -
+ + - - + + - -
+ - + - + - + -
AIR 23 AIR 29 AIR 41
1x outdoor unit:
Evaporator, expansion valve, fan
3x connection pipes (45°):
For vertical or horizontal connection to the heating system.
1x outdoor temperature sensor (TA)
1x contact sensor for a mixed circuit (TMK)
2x pocket sensors for a heat pump buffer tank
(TPO, TPM)
1x pocket sensor for a DHW cylinder (TB)
1xfoundationxingkitfortheoutdoorunit
10 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance description
11_02_200_202_01_019

8.2 Hydraulic variants of the indoor unit

The indoor unit is available in eight different hydraulic variants that are illustrated schematically below. Possible
system congurations for the hydraulic versions of the in­door unit are illustrated in „System schematic diagrams“ on page 68.
M2-3
43 521
43 521
M2-2M2-1
7
8
9
6
12
3 521
10
11
7
8
9
6
12
3 521
10
M2-4
7
6
12
1 Suction gas line 2 Liquid line 3 Heating water/DHW return 4 DHW ow 5 Heating water ow 6 Heat generator pump 7 Diaphragm expansion vessel 8 3-way switching module 9 Flow meter 10 Safety valve 11 Electric booster heater 12 Heat exchanger (heat sink side)
11
7
9
6
10
12
9
10
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 11
INSTALLATION | Appliance description
43 521
43 521
M4-2M4-1
6
7
8
9
10
11
21
3 5
6
7
8
9
11
3 521
M4-4M4-3
6
8
9
11
1 Suction gas line 2 Liquid line 3 Heating water/DHW return 4 DHW ow 5 Heating water ow 6 Safety valve 7 3-way switching module 8 Flow meter 9 Heat generator pump 10 Electric booster heater 11 Heat exchanger (heat sink side)
10
6
8
9
11
11_02_200_202_01_020
12 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
11_05_200_214_01_001
i
i

9. Preparing to install the appliance

Before installing the indoor and outdoor units, preparatory
work needs to be carried out by qualied contractors.

9.1 Indoor unit installation location

Material damage
The indoor unit is intended to be installed only in­side the building. It must not be installed in rooms with high levels of humidity (permanently above 70%).
Information
Plan the installation sites for the outdoor and indoor units such that the pipework carrying the refriger­ant is as short, straight and simple as possible.
B
A ≥ 1000 mm B ≥ 500 mm C ≥ 500 mm D ≥ 50 mm E ≥ 500 mm
D
E
C
A
The installation location for the indoor unit must meet the following requirements:
► A dry and frost-free room
► Sound optimised environment
A horizontal, adequate load bearing oor (for weight
of indoor unit, see „Specication“ on page 50)
► Not situated directly below or above bedrooms
► Max. room temperature 30°C
► The installation room must not be subject to a risk of
explosions arising from dust, gases or vapours.
9.1.1 Keep minimum clearances
Observing the specied minimum clearances for the indoor
unit ensures:
► Correct installation of the appliance
► Fault-free operation
► Ability to carry out maintenance on the appliance.

9.2 Outdoor unit installation location

Information
Plan the installation sites for the outdoor and indoor units such that the pipework carrying the refriger­ant is as short, straight and simple as possible.
Information
When laying refrigerant lines in the ground, sched­ule the work so that the pipe liner can be laid together with the already inserted refrigerant lines in the trench between the outdoor and indoor units.
- If the pipe liner is laid empty, inserting the re-
frigerant lines afterwards will be difcult if not
impossible.
The outdoor unit is intended to be installed only out of doors. Please note the following with regard to the instal­lation location of the outdoor unit:
► Select the outdoor unit installation location such that
the appliance is safely accessible from all sides all year round.
► Avoid installing it in a hollow or ditch (a “pool” of cold
air).
► An optional snow cover is available to protect the
outdoor unit fan in case of heavy snowfall. Where necessary, ensure that a snow cover is installed (according to installation site and local weather conditions).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 13
INSTALLATION | Preparing to install the appliance
i
i
Material damage
The air ow through the evaporator must not be
obstructed by surrounding buildings. A reduced air
ow rate can lead to loss of efciency in the system.
Please note the following with regard to installation in coastal areas:
► The standard design of outdoor unit must be installed
at least 1 km from the sea.
► Outdoor units with special coating, suitable for coast-
al locations, must be installed at least 200 m from the sea.
► The installation location selected should always be on
the leeward side of the building (the side facing away from the sea).
Please note the following with regard to sound emissions from the outdoor unit:
Avoid installing on reverberant ooring.
► Avoid installing between building walls. The walls can
increase the noise level.
► Avoid installing next to bedrooms.
Information
Plants and cultivated areas around the outdoor unit, subject to minimum clearances, can reduce the noise level of the outdoor unit.
11_05_200_504_002
C
A ≥ 3000 mm (minimum clearance to roof) B ≥ 1000 mm (minimum clearance to a wall) C 100 mm or ≥ 1000 mm (minimum longitudinal clear-
ance to a wall)
Information
The minimum clearance between two outdoor units (e.g. connected in cascade) is 1000 mm on all sides.

9.3 Foundations for the outdoor unit

A
B
11_05_200_504_001
9.2.1 Keep minimum clearances
Observing the specied minimum clearances for the out­door unit ensures:
► Correct installation of the appliance
► Fault-free operation
► Ability to carry out maintenance on the appliance.
It is permissible to install the outdoor unit under a roof if the space around the unit is permanently open on three sides.
14 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
A permanent foundation is required beneath the outdoor unit. The foundations must meet the structural require-
ments of the outdoor unit (see Specication).
Provide for frost-free drainage (e.g. a gravel bed con-
»
nected to a drain) for condensation that forms on the outdoor unit.
Where refrigerant lines are to be laid in the ground,
»
ensure correct positioning of the pipe liner when lay­ing the foundations.
Use underground waste pipes (with a smooth inner
»
surface) for the pipe liner.
INSTALL ATION | Preparing to install the appliance
i
11_04_200_504_003
11_04_200_504_004
Ensure that the outdoor unit is adequately secured,
»
paying regard to the wind load occurring at the instal­lation location.
CAUTION: Risk of slipping
If drainage for condensation is inadequate, ice can build up in winter in the area around the outdoor unit.
Ensure drainage for condensation is sufcient
»
even at low temperatures.
Information
Insulation used beneath the soil must be made of a closed-cell material. Otherwise, the thermal in­sulation of the material will be impaired.
100
900
Dig out the foundation trench.
»
Place in position four underground waste pipes
»
(Ø ≥ 250 mm).
≥ 800
9.3.1 Laying spot foundations
900
4
Ø250
3
2
C
1
1 Pipe liner for the connecting lines (where installed
underground) 2 Gravel bed 3 Drainage pipe (frostproof) 4 Spot foundation (with underground waste pipe)
B
A
Ensure correct horizontal and vertical positioning of
»
the underground waste pipes.
Place a drainage pipe along the base of the trench.
»
≥ 1800
1
2
3
1 Underground waste pipe 2 Pipe liner for underground connecting lines 3 Drainage pipe (frostproof) 4 Gravel bed
In the case of underground connecting lines, allow for
»
the pipe liner.
11_04_200_504_001
Fill the foundation trench with coarse gravel. If the
»
pipe liner (with refrigerant lines) is to be installed at a later point, in the case of underground connec­tion lines, this must be allowed for in the foundation trench.
4
Fill the underground waste pipes with concrete.
A B C AIR 7 1110 270 ≥ Ø160 AIR 11 1110 270 ≥ Ø160 AIR 18 1110 270 ≥ Ø160 AIR 23 2040 300 ≥ Ø200 AIR 29 2040 300 ≥ Ø200 AIR 41 2040 330 ≥ Ø250
Use underground waste pipes when installing spot foun­dations. When installing spot foundations, we recommend the following approach:
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 15
»
INSTALLATION | Preparing to install the appliance
i
9.3.2 Laying strip foundations
4
3
2
A
C
150
200
1 Pipe liner for the connecting lines (where installed
underground) 2 Gravel bed 3 Drainage pipe (frostproof) 4 Strip foundations
AIR 7 1400 300 ≥ Ø160 AIR 11 1400 300 ≥ Ø160 AIR 18 1400 300 ≥ Ø160 AIR 23 2250 320 ≥ Ø200 AIR 29 2250 320 ≥ Ø200 AIR 41 2250 350 ≥ Ø250
When laying strip foundations we recommend the following approach:
1
1100
A B C
≥ 1600
B
1
2
3
1 Reinforced strip foundation 2 Pipe liner for underground connecting lines 3 Drainage pipe (frostproof) 4 Gravel bed
In the case of underground connecting lines, allow for
»
the pipe liner.
Fill the foundation trench with coarse gravel. If the
»
pipe liner (with refrigerant lines) is to be installed at a later point, in the case of underground connec­tion lines, this must be allowed for in the foundation
11_04_200_504_002
trench.
Construct the two reinforced strip foundations.
»
9.3.3 Installing on at roofs
WARNING: Risk of falling
Working on a at roof without fall protection con­stitutes a risk.
When working on a at roof, observe the laws
»
relating to occupational safety in your region. Always be aware of the open edge.
»
Information
Avoid installing the outdoor unit on the roof above residential buildings or on car ports attached to res­idential buildings, due to the risk of structure-borne noise transmission.
Loads and stresses on roof structure
≥ 300
4
11_04_200_504_006
Note that when outside temperatures are very low,
»
ice can form beneath the outdoor unit.
≥ 800
11_04_200_504_005
Dig out the foundation trench.
»
Place a drainage pipe along the base of the trench.
»
16 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
In terms of roof structure loads, allow for an ice load
»
of 400 kg/m² in addition to the dead weight of the
outdoor unit.
INSTALL ATION | Preparing to install the appliance
i
3
2
1
1 Flat roof
2 Refrigerant lines in open air (enclosed in thermal in-
sulation with UV protection)
3 2x concrete slabs attached with exible adhesive (per
leg of the outdoor unit). The outdoor unit is afxed to
the concrete slabs
4 Anti-vibration mounts
When installing the outdoor unit on a freestanding car port,
a garage roof or a storage space roof, please note the
following:
Ensure that the outdoor unit is adequately secured,
»
paying regard to the wind load occurring at the instal­lation location.
Take account of the concentrated load arising from
»
the dead weight of the outdoor unit (including the
roof xings) and the surface load caused by possible
build-up of ice.
Ensure suitable structure-borne sound separation be-
»
tween the outdoor unit and the installation points on the roof.
4

9.4 Preparing the refrigerant lines

Information
If the appliance, the refrigerant lines, the pipe x­ings and the wall outlets are not installed correctly, structure-borne sounds can be transmitted to the building.
Ensure that the refrigerant lines are in-
»
11_06_200_202_006
stalled in a way that ensures insulation from structure-borne noise. The system installer carrying out the work is responsible for this.
Material damage
Use only copper pipes suitable for refrigerant (D IN 12735-1). Thin-walled pipes run the risk of bursting.
Please observe the stipulated diameters and
»
wall thicknesses of the copper pipes.
Material damage
Incorrect or premature opening of the pipe connec­tions and cutting of the refrigerant lines can allow dirt and moisture to enter the refrigerant circuit.
Do not open the connections on the indoor
»
or outdoor units until just before installing the refrigerant lines. Cut the refrigerant lines with a suitable pipe
»
cutte r. Prevent swarf from contaminating the pipe
»
connections and refrigerant lines. Once cut, ll the refrigerant lines with a sub-
»
stance such as nitrogen. Keep the refrigerant lines closed until just be-
»
fore installation.
Pipe connections for the refrigerant lines (suction gas and liquid lines) are supplied soldered closed, both for the in­door unit and the outdoor unit. Appropriate copper pipes for refrigerant lines are supplied sealed at both ends and
lled with nitrogen.
Please note the following with regard to routing of the re­frigerant lines:
Keep to a minimum the distance between the indoor
»
and outdoor units, in order to minimise heat loss from the refrigerant lines.
Select the installation sites for the indoor and outdoor
»
units such that the maximum permissible line lengths and height differentials are not exceeded.
Avoid routing the lines in the vicinity of bedrooms.
»
The refrigerant in the lines can generate noise under certain operational conditions.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 17
INSTALLATION | Preparing to install the appliance
i
9.4.1 Line lengths
Observe the maximum permissible line lengths for
»
the refrigerant lines.
Where the outdoor unit is positioned higher than the
»
indoor unit, observe the maximum permissible height
differential between the two units.
C
B
A
Where a line routed along the ceiling is used in
»
conjunction with an underground connection line, observe the maximum permissible height differential between the highest and lowest points of the refriger­ant lines.
1223
D
11_06_200_202_001
≤ 3500
11_06_200_202_002
A + B + C
(sum of line lengths) AIR 7 ≤ 20 m ≤ 10 m AIR 11 ≤ 20 m ≤ 10 m
AIR 18 ≤ 20 m ≤ 10 m AIR 23 ≤ 20 m ≤ 10 m AIR 29 ≤ 20 m ≤ 10 m AIR 41 ≤ 16 m ≤ 5 m
Where the outdoor unit is positioned lower than the
»
indoor unit, observe the maximum permissible height differential between the highest and lowest points of the refrigerant lines.
1180
(max. height differential)
≤ 3500
D
9.4.2 Pipe diameter
The pipe diameter data for refrigerant lines shown below applies as long as the following are observed:
► A maximum of eight 90° pipe bends
► With pipe diameters of < 35 mm, use a suitable pipe
bending tool to create the pipe bends
With pipe diameters of ≥ 35 mm, use type 5002 pipe
bends
Bending radii of ≥ 1 m are treated as straight runs
Information
Refrigerant lines with a pipe diameter of ≥ 35 mm
are created from rigid copper pipes in 5 m lengths.
With underground refrigerant lines, provide an
»
assembly shaft at connection sites to facilitate soldering and maintenance work.
≤ 2970
18 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
650
11_06_200_202_003
INSTALL ATION | Preparing to install the appliance
Pipe diameter of the refrigerant line
Refrigerant line up to 6 m Refrigerant line up to 8 m
Liquid line Suction gas
line AIR 7 10 18 10 18 AIR 11 12 18 12 18 AIR 18 12 22 12 22 AIR 23 12 22 16 2x22 AIR 29 16 2x22 16 2x22 AIR 41 16 42 16 42 AIR 41 16 4x22 16 4x22
Pipe diameter of the refrigerant line
Refrigerant line up to 10 m
Liquid line Suction gas
line AIR 7 10 18 10 18 AIR 11 12 22 12 22 AIR 18 12 22 12 2 x18 AIR 23 16 2x22 16 2x22 AIR 29 16 2x22 16 2x22 AIR 41 16 42 16 42 AIR 41 16 4x22 16 4x22
Pipe diameter of the refrigerant line
Refrigerant line up to 14 m
Liquid line Suction gas
line AIR 7 10 18 10 18 AIR 11 12 22 12 22 AIR 18 12 2 x18 12 2x22 AIR 23 16 2x22 16 2x22 AIR 29 16 2x22 16 35 AIR 29 16 2x22 16 3x22 AIR 41 16 42 16 42 AIR 41 16 4x22 16 4x22
Liquid line Suction gas
line
Refrigerant line up to 12 m
Liquid line Suction gas
line
Refrigerant line up to 16 m
Liquid line Suction gas
line
9.4.3 Preparing the wall outlets
Whether the refrigerant lines between the indoor and outdoor units are to be routed above or below ground, ap-
propriate and plant-specic wall outlets need to be created
through the outer wall of the building.
Ensure that the wall outlets are constructed in an ap-
»
propriate, plant-specic manner.
Take the construction of the wall (tiles, concrete) into
»
account.
Take the prevailing groundwater situation into
»
account.
Material damage
Incorrectly created wall outlets can cause signi­cant damage to property, due to water (seepage, condensation, floodwater) penetrating into the building or stonework. Where the wall outlets are created below ground level, the breach must be appropriate to local conditions at the site (e.g. non-accumulating or accumulating seepage water, groundwater under pressure).
Use a suitable pipe liner or wall sleeve for the
»
wall outlet. Tie the external end of the wall outlet in to the
»
external waterproof seal of the building. Ensure that the pipe liner is arranged with a
»
slight fall (at least 2%) to the outside. On both the outside and inside edge of the
»
wall, use appropriate ring seals to seal the space between the wall sleeve and the re­frigerant lines and electrical cables passing through.
Material damage
PU foam is not suitable as a sealant for the pipe li ner.
Pipe diameter of the refrigerant line
Refrigerant line up to 18 m
Liquid line Suction gas
line AIR 7 10 18 10 18 AIR 11 12 22 12 22 AIR 18 12 2x22 12 2x22 AIR 23 16 2x22 16 2x22 AIR 29 16 35 16 35 AIR 29 16 3x22 16 3x22
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 19
Refrigerant line up to 20 m
Liquid line Suction gas
line
INSTALLATION | Preparing to install the appliance
i
i
i
i
9.4.4 Preparing refrigerant lines passing through open air
3
2
1
6
1 Appropriately sealed wall outlet (particularly where
there is a risk of ooding)
2 Appropriate sealing of the refrigerant lines as they
pass through the wall outlet
3 Refrigerant lines in open air (enclosed in thermal in-
sulation with UV protection) 4 Reinforced strip foundation 5 Drainage pipe (frostproof) 6 Foundation
Information
All solder sites on the copper pipework of the re­frigerant line must be accessible all year round for maintenance purposes (in accordance with Regu­lation (EU) no. 517/2014).
Run the refrigerant lines between the indoor and out-
»
door units.
4
5
9.4.5 Preparing underground refrigerant lines
5
3
2
1
10
11_06_200_202_005
1 Appropriately sealed wall outlet 2 Appropriate sealing of the refrigerant lines as they
pass through the pipe liner 3 Insulation 4 Gravel 5 Reinforced strip foundation 6 Appropriate sealing at the end of the pipe liner (be-
tween refrigerant lines and pipe liner) 7 Drainage pipe (frostproof) 8 Pipe liner (with min. 2% fall to outside) 9 Drain 10 Foundation
Information
All solder sites on the copper pipework of the re­frigerant line must be accessible all year round for maintenance purposes (in accordance with Regu­lation (EU) no. 517/2014).
4
~ 600
8
7
9
6
11_06_200_202_004
Allow some surplus length in the refrigerant lines
»
between the connections at the indoor and outdoor units.
Ensure that the wall outlets are sealed in an appropri-
»
ate, plant-specic manner.
Use suitable sound-insulating pipe xings to secure
»
the refrigerant lines.
Insulate the refrigerant lines with suitable insulating
»
material where they pass through open air between the indoor and outdoor units, to prevent formation of condensation. When passing through open air outside, the insulating material must also have UV protection.
Information
Where the refrigerant lines run horizontally through open air, use suitable supports. Take steps to pre­vent open refrigerant lines from being walked or driven on.
Information
When laying refrigerant lines in the ground, sched­ule the work so that the pipe liner can be laid together with the already inserted refrigerant lines in the trench between the outdoor and indoor units.
- If the pipe liner is laid empty, inserting the re-
frigerant lines afterwards will be difcult if not
impossible.
20 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
1
Ensure that the wall outlets are appropriate and
»
plant-specic, and that the pipe liner is appropriately
sealed.
Ensure that the open end of the pipe liner at the
»
outdoor unit is properly sealed. For sealing the re­frigerant lines in the pipe liner, use for example an appropriate ring seal or a UV-resistant, permanently
exible sealing compound.
Any exposed refrigerant lines outside the pipe liner
»
must also be protected from a build-up of condensa­tion with appropriate insulating material. Out of doors, the insulating material must also have UV protection.
Information
Insulation used beneath the soil must be made of a closed-cell material. Otherwise, the thermal in­sulation of the material will be impaired.
2
1 Where the pipe liner has two 90° bends, it must be
laid together with the refrigerant lines.
2 If the pipe liner is laid empty, it will not be possible to
insert the refrigerant lines afterwards.
For the underground pipe liner, use rigid waste pipes.
»
Use a pipe liner of a suitable diameter for the sys-
»
tem-specic refrigerant lines and the planned pipe
bends (see „Foundations for the outdoor unit“ on page 14).
For 90° bends in the pipes, use either 3x 30° bends
»
or 6x 15° bends (depending on the diameter of the pipe liner and the depth at which it is laid).
At the point where the refrigerant lines are connected
»
to the outdoor unit, create a suitable trench.
11_06_200_202_007
Material damage
PU foam is not suitable as a sealant for the pipe li ner.
Dig a straight trench between the wall outlet and the
»
trench at the outdoor unit.
Lay the pipe liner, with the refrigerant lines already
»
inserted, into the trench between the outdoor and in­door units.
Lay the electrical control leads and power supply
»
cables in a suitable electrical conduit. The optional OCHSNER cable harness is suitable for laying direct into the ground.
Allow some surplus length in the refrigerant lines
»
between the connections at the indoor and outdoor units.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 21
INSTALLATION | Preparing to install the appliance
i
i
i

9.5 Preparing the electrical connections

WARNING: Electrocution
All electrical connection and installation work must be carried out according to the applicable national and regional regulations.
WARNING: Electrocution
Before commencing work on electrical connections and installation, the heat pump system must be isolated and voltage-free.
WARNING: Electrocution
Work on electrical connections and installation may
be conducted only by qualied contractors.
Material damage
This appliance contains frequency converters (e.g. EC circulation pumps, EC fan motors). Leakage currents may arise in normal operation. In the event of faults, these components may cause DC fault currents. An incorrectly selected RCD may trip dur­ing normal operation or, in the event of a fault, may not trip at all or only trip after a delay.
Make sure that the power supply for this
»
appliance is separate from the domestic in­stallation. If local conditions require the installation of an
»
RCD, use type B AC/DC-sensitive RCDs.
► For the integral electric booster heater (8.8 kW), a
suitable high limit safety cut-out (HLSC) is installed in
the indoor unit.
Information
The main power circuit for the compressor has no upstream power contactor on the machine side. Control devices and equipment to discon­nect and shut down all supply voltages across all poles, which must be provided on the system side, must meet the technical safety requirements of EN 60204-1 sections 5 and 13.4.5, as well as the international regulations in the IEC 60947 series.
Material damage
Protect the main power circuit (compressor), the control circuit (control unit) and the electric booster heater separately from one another.
9.5.1 Heat pumps for three-phase alternating current
1
3 4 5 6
2
C13A B16A
Information
It is essential that the regulations of the responsible power supply utility (PSU) and the applicable EN standards be observed.
Information
The values specied in this documentation for
circuit protectors and cable cross-sections are standard values. The contractor carrying out the work is responsible for plant-specic sizing of safe­ty equipment and cable cross-sections.
► For the electrical connection, use the system principle
schematic appropriate to your heat pump system from section „System schematic diagrams“ on page 68.
► The outdoor unit takes its power supply from the in-
door unit. The supply cable for the fan in the outdoor unit is protected by an internal C10A circuit breaker in the indoor unit.
► In the case of a fault, the protection on the main pow-
er circuit (compressor) and electric booster heater must break the circuit across all poles.
3 x 400 VAC 1 x 230 VAC 3 x 400 VAC
1 Heat pump indoor unit control box 2 Main system distributor board 3 Supply to main power circuit (compressor) 4 PSU signal contact 5 Supply to control circuit (OTE controller) 6 Supply to electric booster heater
Description Typ e Max.
Main power cir­cuit (compressor and fan)
Electric booster heater
Control circuit (control unit)
AIR 7 C11A 13.5 5.4 C10A AIR 11 C 11A 20.0 7.9 C10A AIR 18 C11A 32.0 11. 4 C16A
AIR 23 C12A 50.5 16.8 C20A AIR 29 C12A 49.5 21.1 C25A AIR 41 C12A 63.5 24.8 C25A
AIR 7 C11A
AIR 41 C12A
AIR 7 C11A
AIR 41 C12A
starting current [A]
Max. op­erating current [A]
14 B16A
6 C13A
11_02_200_202_01_010
Fuse
► All power supply cables must be protected against
surges and short circuits.
22 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
i
Material damage
Operating a three-phase motor (compressor, pumps, fans) for long periods using an incorrectly phased three-phase supply will damage the motor.
Ensure that all three-phase motors are
»
connected to a three-phase supply with a clockwise rotating eld.
9.5.2 Heat pumps for single phase alternating current
1
3 4 5 6
2
C13A B16A
1 x 230 VAC 1 x 230 VAC 3 x 230 VAC
1 Heat pump indoor unit control box 2 Main system distributor board 3 Supply to main power circuit (compressor) 4 PSU signal contact 5 Supply to control circuit (OTE controller) 6 Supply to electric booster heater
Description Typ e Max.
Main power cir­cuit (compressor and fan) Electric booster heater
Control circuit (control unit)
AIR 11 C 11B 48.5 20.8 C25A
AIR 18 C11B 80.0 30.0 C40A
AIR 11 C 11B 12.8 B16A AIR 18 C11B AIR 11 C 11B 6 C13A AIR 18 C11B
starting current [A]
Max. op­erating current [A]
Fuse
9.5.3 Cables from main distributor to indoor unit
Description Wires Min. cable
Supply to electric booster heater
(8.8 kW electric immersion heater)
Control circuit supply 1x 2 30 VAC
Supply to pumps and ser­vomotors Sensor leads (system temperature sen­sors) Bus leads (eBus connections from OTE controller to remote controllers or auxiliary modules and in cascades)
3x 400 VAC (L1/L2/L3/N/PE) or 3x 230 VAC (L/L/L/N/PE)
(L/N/PE) 1x 23 0 VAC (L/N/PE) 2x (shielding recommend­ed) Example: Y(ST)Y 2x2x0.8 (shielded cable design and twisted cable pairs)
9.5.4 Cables from indoor to outdoor unit
Description Wires Min. cable
11_02_200_202_01_024
Fan power supply 1x 23 0 VAC
Fan alarm (TK) 2x 230 VAC 1.5 mm² Fan speed (0-10 VDC)
Defrost sensor (TQE, TQA) 4x
Pulse lead (for stepper motor on elec­tronic expansion valve)
Suction gas sensor S2
(for expansion valve control­ler)
(L/N/PE)
2x (shielding recom­mended)
(shielding recom­mended) 4x (shielding recom­mended)
Example: ÖLFLEX® CLASSIC 100 CY
2x (shielding recom­mended)
9.5.5 Temperature sensor
cross-sec­tion
2.5 mm²
1.5 mm²
1.0 mm²
1.0 mm²
0.8 mm²
cross-sec­tion
1.5 mm²
1 mm²
1 mm²
0.8 mm²
1 mm²
Information
The maximum line length for sensor leads is 50 m.
Information
Sensor leads must be routed separately from 230 V and 400 V cables. If a minimum distance of 20 cm cannot be maintained, then shielded cables should be used. The shielding should be connected to the earth rail of the heat pump.
Defrost sensors (TQA, TQE):
The two defrost sensors are factory-installed in the evap­orator on the outdoor unit.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 23
INSTALLATION | Preparing to install the appliance
i
i
Outdoor temperature sensor (TA):
nected directly to the OTE controller (1x 230 VAC power supply).
Fit the outdoor temperature sensor at a height of ap-
»
prox. 2.5 m to the outside wall of the building (on the north-west side). Make sure that the outdoor temper­ature sensor is not exposed to direct sunlight or wind, as this will impair the control characteristics.
Information
Avoid tting the outside temperature sensor to the casing of the outdoor unit or in the air ow from
the outdoor unit.
Buffer sensor (TPO, TPM):
In heat pump buffer tank, two buffer sensors are required. The heat pump is switched on on the basis of readings from the TPO and switched off on the basis of those from the TPM.
Install a sensor pocket in the female socket provided
»
for the upper buffer sensor (TPO)
Install a sensor pocket in the female socket provided
»
for the lower buffer sensor (TPM)
DHW sensor (TB):
Material damage
A test run of the pumps and servomotors may be conducted only on a system that has been pre­pared for commissioning. The hydraulics must be fully connected.
9.5.7 PSU signal contact
Tariff switching on the heat pump system
In the case of tariff switching (with interrupted power deliv­ery), the heat pump is temporarily shut down by the power supply utility (PSU).
Uninterrupted tariff
In the case of tariff switching with uninterrupted power delivery, the heat pump is temporarily shut down by the power supply utility. A PSU signal contact is provided for this purpose on the indoor unit. To activate the function, remove a cable bridge in the control box and connect the PSU signal contact cable (see „Electrical connection of the indoor unit“ on page 34).
OCHSNER DHW cylinders are tted with appropriate fe­male sockets for installing the sensor.
Install the DHW sensor in the top one-third of the
»
DHW cylinder (or at the very least in the top half). The lower the selected position of the DHW sensor, the larger the switching hysteresis (5-15 K) will need to be.
Information
Ensure that the DHW sensor is correctly positioned and extends beyond the cylinder insulation into the interior of the DHW cylinder. This is the only way in which the temperature can be captured correctly.
Mixer sensor (TMK):
If, in addition to a direct heating circuit, your system also has a heating circuit with mixing valve, then a mixer sensor must be installed. The mixer sensor is supplied with the heat pump, as a contact sensor including band clamp and heat conducting paste.
Install the mixer sensor immediately downstream
»
of heating circuit circulation pump 2 for the heating circuit with mixing valve, on a (metal) pipe made of a good heat-conducting material.
Shutdown by means of a tariff contactor
In the case of shutdown by means of a tariff contactor in­stalled on behalf of the customer (sealed by the PSU), the power supply to the heat pump compressor is disconnect­ed. Here, it is essential to connect an auxiliary contact to the tariff contactor (N/C contact) of the PSU signal contact on the indoor unit.
Night tariff
Where tariff switching takes place within the meter (night tariff), the PSU signal contact is not connected.
9.5.8 Smart Grid
For the Smart Grid function, special descriptions are avail­able on request from your OCHSNER Customer Service department.
9.5.6 Pumps and servomotors (230 VAC)
Pumps (heating circuit pumps, DHW charging pump) and servomotors (switching module, mixing valve) are con-
24 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance installation
i
i
11_02_200_214_01_005
11_02_200_214_01_001
10. Appliance installation
10.1 Installation of indoor unit
10 .1.1 Delivery and transportation
The appliance is delivered on a one-way pallet, wrapped in lm. The appliance casing is assembled on delivery.
Information
Should you notice any transportation damage to the appliance, you must report such damaged im­mediately when the delivery is unloaded. Claims for transportation damage cannot be made sub­sequently.
Material damage
Protect the appliance from damage by using
»
transport belts. When transporting, protect the appliance from
»
impact.
► The appliance is secured to the one-way (recyclable)
pallet of the transport packaging with screws.
► The transport packaging or one-way pallet is suitable
for transportation using a forklift truck.
► For level transportation to the installation location, the
appliance may remain in the transport packaging.
► Leave the appliance in the transport packaging or on
the one-way pallet for lifting and moving by crane or forklift.
► The standard packaging of the appliance does not
provide protection against the weather or sea water.
► The appliance may be stored and transported only at
temperatures of between -20°C and +45°C.
► The appliance must be stored in its transport
packaging.
Information
If the route to the installation location is difcult,
the transport packaging should be removed and the appliance casing disassembled.
Please note the following when removing the transport packaging:
Remove the transport packaging.
»
Undo and remove the eight woodscrews on the two
»
transport xing brackets (left and right) securing the
appliance to the one-way pallet.
Use the pre-installed transport aids (2 lifting slings at
»
the front and 2 lifting handles at the rear) to lift and transport the appliance.
Transport the appliance in an upright position. Over
»
short distances, you may transport the appliance carefully at an angle of up to 30°.
Material damage
Note the following points when carrying the appli­ance with the pre-installed transport aids:
- When lifting and carrying the appliance, make sure that all 4 transport aids are pulled evenly and at the same time.
- Ensure that the appliance casing is not dam­aged during transport.
- The transport aids are not suitable for lifting by crane.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 25
INSTALLATION | Appliance installation
i
Material damage
When being transported with the appliance cas­ing disassembled, sensitive components will be exposed.
Take care transporting the appliance.
»
10 .1.2 Positioning the appliance
After the appliance has been placed in position,
»
remove the two lifting slings at the front of the appliance.
Undo and remove the two mounting bolts and remove
»
the two lifting slings.
Then screw the two mounting bolts back into the ap-
»
pliance frame.
10 .1.3 Disassembling the appliance casing
11_02_200_214_01_002
Position the appliance at the intended installation
»
location.
Use the pre-installed transport aids (2 lifting slings at
»
the front and 2 lifting handles at the rear) to slide and tilt the appliance.
Observe minimum clearances.
»
Ensure the appliance is horizontal. To compen-
»
sate for minor unevenness in the oor, use the four
height-adjusting plastic glides on the underside of the appliance.
Information
On the underside of the indoor unit, there are four plastic glides with rubber mounted threaded pins (without nuts). Discrepancies in oor height of up to 6 mm can be compensated for.
1
2 3
Undo and remove the four knurled screws for the ap-
»
pliance casing panel at the rear of the appliance.
Undo and remove the two xing screws for the control
»
box cover, on the rear of the appliance.
11_02_200_214_01_006
Slide back the control box cover. Lift the control box
»
cover up and away.
11_02_200_214_01_003
1 Lifting sling 2 Mounting bolt 3 Appliance frame
26 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_02_200_214_01_007
INSTALL ATION | Appliance installation
11_02_200_214_01_012
Undo and remove the two xing screws for the left-
»
hand appliance casing panel, inside the control box.
Lift the left-hand appliance casing panel up and away.
»
Material damage
When the appliance casing has been disassem­bled, sensitive components are fully exposed.
Assemble the appliance casing as soon as
»
there is nothing that needs doing inside the appliance. During the building phase, provide the appli-
»
ance with additional protection from dirt and dust with a suitable covering.
10 .1.4 Assembling the appliance casing
11_02_200_214_01_008
Undo and remove the three xing screws for the front
»
appliance panel, inside the control box.
Lift the front appliance casing panel up and away.
»
Undo and remove the two xing screws for the right-
»
hand appliance casing panel, inside the control box.
Lift the right-hand appliance casing panel up and
»
away.
11_02_200_214_01_009
Slide the left-hand and front appliance casing panels
»
down from the top along the frame of the appliance, until the panels click into place at the bottom.
Ensure that both panels are fully engaged at the ve
»
positions along the bottom.
Secure both of these appliance casing panels with
»
screws at the xing points provided, inside the control
box.
11_02_200_214_01_010
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 27
INSTALLATION | Appliance installation
i
Slide the right-hand appliance casing panel down
»
from the top along the frame of the appliance, until the panel clicks into place at the bottom.
10.2 Installing the outdoor unit
10 . 2 .1 Delivery and transportation
The appliance is delivered on a one-way pallet, wrapped in lm. The appliance casing is assembled on delivery.
Information
Should you notice any transportation damage to the appliance, you must report such damaged im­mediately when the delivery is unloaded. Claims for transportation damage cannot be made sub­sequently.
Material damage
Protect the appliance from damage by using
»
transport belts. When transporting, protect the appliance from
»
impact.
11_02_200_214_01_011
► The appliance is secured to the one-way (recyclable)
pallet of the transport packaging with screws.
► The transport packaging or one-way pallet is suitable
for transportation using a forklift truck.
Ensure that the panel is fully engaged at the three
»
points along the bottom.
Secure the appliance casing with screws at the xing
»
points provided, inside the control box.
Secure the appliance casing with screws at the rear
»
of the indoor unit.
► For level transportation to the installation location, the
appliance may remain in the transport packaging.
► Leave the appliance in the transport packaging or on
the one-way pallet for lifting and moving by crane or forklift.
► The standard packaging of the appliance does not
provide protection against the weather or sea water.
► The appliance may be stored and transported only at
temperatures of between -20°C and +45°C.
► The appliance must be stored in its transport
packaging.
Please note the following when removing the transport packaging:
11_02_200_214_01_006
Remove the transport packaging.
»
28 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_02_200_504_01_007
INSTALL ATION | Appliance installation
11_02_200_504_01_006
i
Undo and remove the four woodscrews securing the
»
appliance to the one-way pallet.
10.2.2 Positioning the appliance
Position the appliance on the prepared foundations.
»
Secure the four legs of the outdoor unit on the foun-
»
dations, using four xing screws.
10.2.3 Disassembling the appliance casing
By removing the side casing panels on the outdoor unit, you can gain access to the connection points for the re­frigerant lines and to the terminal boxes for the electrical control leads and power supply cables.
Undo and remove the two xing screws on the
»
underside.
Pull the side appliance casing panel down and away.
»
1
2
1 Round stainless steel plate 2 Mounting foot with threaded pin (4 pce, M5)
Attach the four mounting feet of the snow cover to the
»
outdoor unit, by screwing the threaded pins into the four free screw holes in the ring-shaped casing part.
Attach the round stainless steel plate of the snow
»
cover to the four positioning feet (M5x12 mm, stain­less steel).
10.2.4 Installing the snow cover
The snow cover for an outdoor unit fan can be retrotted.
10.2.5 Fitting the cylindrical silencer
Information
The Super Silent Paket (SSP) exclusively available ex works for a VHS-M outdoor unit reduces noise by up to 3 dB. The Super Silent Paket consists of:
11_02_200_504_01_009
The cylindrical silencer from the super silent package (SSP) can be retrotted. A retrotted cylindrical silencer alone will reduce noise by about 1.5 dB.
11_02_200_504_01_005
- One cylindrical silencer per fan
- Reinforced casing insulation
- Shielded refrigeration technology
Undo and remove four of the eight xing screws on
»
the ring-shaped casing part for the fan (M5x12 mm, stainless steel).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 29
INSTALLATION | Appliance installation
1
10.2.6 Installing the SSP snow cover
The SSP snow cover can be retrotted to an existing cy- lindrical silencer on the outdoor unit.
Secure the four mounting feet to the round stainless
»
steel plate with screws (M5x12, 8 pcs).
Screw the safety bolt (M6x12, 1 pce) for the sound
»
absorbing mat into the centre of the stainless steel plate.
1 Casing section for the fan
Undo and remove the eight xing screws (M5x12 mm,
»
stainless steel) on the ring-shaped casing part of the fan.
Remove the ring-shaped casing part.
»
4
3
11_02_200_504_01_003
1 Round stainless steel plate with attached sound ab-
sorbing mat 2 Mounting foot with threaded rivet (4 pcs) 3 Safety bolt (M6x12, 1 pce) with washer and retaining
nut 4 Fixing screw (M5x12, 8 pcs) with plastic washer
Position the SSP snow cover on the upper edge of
»
the cylindrical silencer.
Ensure that the SSP snow cover is correctly aligned.
»
The cylindrical silencer has just one predrilled screw
hole for each mounting foot.
1
2
11_02_200_504_01_008
First, secure the four mounting feet of the SSP
»
snow cover to the cylindrical silencer, using the four
1
11_02_200_504_01_002
1 Cylindrical silencer
Position the cylindrical silencer over the fan. Ensure
»
that the assembly holes are correctly aligned.
Attach the cylindrical silencer to the casing panel of
»
the outdoor unit, using the eight xing screws (M5x12, stainless steel).
30 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
pre-drilled holes. Use self-tapping xing screws
(4.8x19 mm, stainless steel).
Secure the SSP snow cover through the remaining
»
four screw holes in the mounting feet that do not have
pre-drilled receiving holes. Use self-tapping xing
screws (4.8x19 mm, stainless steel).
Loading...
+ 70 hidden pages