Ochsner AIR 7, AIR 41, AIR 11, AIR 18, AIR 23, AIR 29 Operating And Installation Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
HIGH EFFICIENCY AIR/WATER HEAT PUMPS
OPERATING AND INSTALLATION
MANUAL
AIR 7
►
AI R 11
►
AIR 18
►
AIR 23
►
AIR 29
►
AIR 41
►
CONTENTS
PLEASE NOTE
OPERATION
1. Information on documentation 4
1.1 Safety information 4
1.1.1 Arrangement of safety information 4
1.1.2 Symbols and possible dangers 4
1.1.3 Keywords 4
1.2 Other symbols 5
1.3 Units of measurement 5
1.4 Specied performance data 5
2. Safety 5
2.1 Intended use 5
2.2 General safety information 5
3. Appliance description 6
3.1 Functionality 6
3.2 Appliance components 6
3.2.1 Indoor unit 6
3.2.2 Outdoor unit 7
3.2.3 Heat pump control unit 7
3.3 Name plate 7
4. Activating settings 8
4.1 Operating costs 8
4.1.1 Flow temperatures 8
4.1. 2 Ventilation 8
4.1. 3 Heating setback program 9
5. Maintenance and care 9
6. Problem solving 9
INSTALLATION
7. Safety 10
7.1 General safety information 10
7. 2 Regulations, codes and standards 10
8. Appliance description 10
8.1 Standard delivery 10
8.2 Hydraulic variants of the indoor unit 11
9. Preparing to install the appliance 13
9.1 Indoor unit installation location 13
9.1.1 Keep minimum clearances 13
9.2 Outdoor unit installation location 13
9.2.1 Keep minimum clearances 14
9.3 Foundations for the outdoor unit 14
9.3.1 Laying spot foundations 15
9.3.2 Laying strip foundations 16
9.3.3 Installing on at roofs 16
9.4 Preparing the refrigerant lines 17
9.4.1 Line lengths 18
9.4.2 Pipe diameter 18
9.4.3 Preparing the wall outlets 19
9.4.4 Preparing refrigerant lines passing through open air
20
9.4.5 Preparing underground refrigerant lines 20
9.5 Preparing the electrical connections 22
9.5.1 Heat pumps for three-phase alternating current 22
9.5.2 Heat pumps for single phase alternating current 23
9.5.3 Cables from main distributor to indoor unit 23
9.5.4 Cables from indoor to outdoor unit 23
9.5.5 Temperature sensor 23
9.5.6 Pumps and servomotors (230 VAC) 24
9.5.7 PSU signal contact 24
9.5.8 Smart Grid 24
10. Appliance installation 25
10 .1 Installation of indoor unit 25
10 .1.1 Delivery and transportation 25
10 .1.2 Positioning the appliance 26
10 .1.3 Disassembling the appliance casing 26
10 .1.4 Assembling the appliance casing 27
10.2 Installing the outdoor unit 28
10 . 2 .1 Delivery and transportation 28
10.2.2 Positioning the appliance 29
10.2.3 Disassembling the appliance casing 29
10.2.4 Installing the snow cover 29
10.2.5 Fitting the cylindrical silencer 29
10.2.6 Installing the SSP snow cover 30
10.3 Connecting the heat sink system 31
10 . 3 .1 Connecting the heating water 31
10.3.2 Safety valve drain 32
10.3.3 Filling the heating system 32
10.3.4 Diaphragm expansion vessel (DEV) 33
10.3.5 Flow metering 33
10.3.6 Cooling version 33
10.3.7 Connecting the DHW 33
10.4 Electrical connection 34
10 . 4 .1 General 34
10.4.2 Electrical connection of the indoor unit 34
10.4.3 Electrical connection of the outdoor unit 36
10.5 Connecting heat source system 37
10 . 5 .1 Connecting the refrigerant lines 37
10.5.2 Checking for leak tightness 38
10.5.3 Filling the refrigerant circuit with refrigerant 38
10.5.4 Insulating the refrigerant lines 38
11. Commissioning 39
11.1 Before switching on for the rst time 39
11. 2 Testing the control circuit 39
11. 3 Adjusting the ow rate 39
11. 4 Heat generator pump (HGP) 42
11. 5 Necessary conditions for commissioning 43
11. 6 Commissioning the system 44
11.7 Decommissioning 45
12. Troubleshooting 46
12 .1 Fault messages on the master controller 46
12.2 Reset high limit safety cut-out 48
13. Appliance maintenance 48
13 .1 Testing safety valve 48
13.2 Maintenance contract 49
14. Specication50
14 .1 Heat pumps for three-phase alternating current 50
14 .1.1 Data table 50
14 .1.2 Output diagrams 54
14 .1.3 Details of energy consumption 60
14.2 Heat pumps for single phase alternating current 62
14 . 2 .1 Data table 62
14.2.2 Output diagrams 64
14.2.3 Details of energy consumption 66
14.3 Limits of use 67
14.4 System schematic diagrams 68
14.5 Voltage quality in island mode 84
14.6 Dimensions and connections 85
14 . 6.1 Indoor unit 85
14.6.2 Outdoor unit 86
15. Environment and recycling 90
16. Declaration of Conformity 91
17. ERP-Data 93
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 3
PLEASE NOTE | Information on documentation
i
PLEASE NOTE
f The appliance can be used by children over the age
of eight years and by people with reduced physical, sensory or mental abilities or with a lack of
experience and knowledge, if they are supervised
or instructed on the safe use of the appliance and
understand the dangers that can arise from its use.
Children must not be allowed to play with the appliance. Children must not be allowed to clean or
carry out user maintenance on the appliance without
supervision.
f Connection to the mains electricity supply must be
by means of a xed connection. It must be possible
to isolate the appliance from the mains supply with
a multi pole switch which has a gap of at least 3 mm
across all poles.
f You must not disconnect the mains supply even
outside the heating period. If the power supply is
disconnected, active frost protection of the system
cannot be guaranteed.
f You do not need to switch off the system for the
summer. The heat pump control unit changes over
automatically between summer and winter.
OPERATION
1. Information on documentation
The “Please note” and “Operation” sections are intended
for the appliance user and the qualied contractor.
The “Installation” section is intended for the qualied con-
tractor.
Unless otherwise stated, all the content of this documentation applies to the appliances listed on the title page. This
documentation describes appliances that are not always
standard items. There may therefore be differences to your
specic appliance.
Information
Read all of this documentation carefully before using the appliance and keep the documents safe.
Pass this documentation on to any new user.
1.1 Safety information
1.1.1 Arrangement of safety information
f Observe the minimum clearances in order to ensure
fault-free operation of the appliance and to allow for
maintenance work on the appliance.
f In bivalent mode, the return water from the second
heat generator can ow through the heat pump. Note
that the return water temperature must not exceed
65°C.
f Maintenance work such as checking the electrical
safety of the appliance may only be carried out by a
qualied contractor.
f We recommend an annual inspection (to assess the
appliance‘s actual condition) and if necessary maintenance (to reinstate it to its expected condition) by a
qualied contractor.
KEYWORD: Type of risk
The possible consequences of not observing the
safety information are shown here.
Instructions for action to remedy or remove
»
the source of danger are shown here.
1.1.2 Symbols and possible dangers
SymbolType of risk
Injury
Electrocution
Burns
(burns, scalding)
Material damage
(appliance, consequential and environmental damage)
1.1.3 Keywords
KeywordMeaning
DANGER Failure to observe this information will result in seri-
WARNING Failure to observe this information may result in se-
CAUTION Failure to observe this information may result in
ous injury or death.
rious injury or death.
non-serious or minor injury.
4 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
OPERATION | Safety
i
i
1.2 Other symbols
► This triangular symbol is used as a bullet point.
These two arrows represent the symbol for an in-
»
struction. This shows that there is something you
must do. The actions required are described step by
step.
{{These symbols show you the level of a software
menu. In this example, three menu levels are
indicated.
1.3 Units of measurement
Information
In these documents, unless otherwise specied,
all linear measurements (e.g. in tables and illustrations) are given in millimetres.
1.4 Specied performance data
The performance data of the appliance indicated in these
documents (text, tables and diagrams) have been calculated according to standardised measurement conditions.
However, these measurement conditions often do not
completely correspond to the plant-specic conditions applicable in the respective user‘s system. System-specic
factors that can affect the conditions include, for example,
the specic design of the system, the age of the system
and the actual ow rates. For this reason, the stated per-
formance data can differ from plant-specic performance
data.
2. Safety
2.1 Intended use
The appliance is intended for use in a domestic environment. It can safely be used by persons who have received
no instruction. The appliance can similarly be used in a
non-domestic environment such as commercial premises,
as long as it is used in the same instructed manner.
Any use of the appliance that is different from or goes
beyond this is not regarded as intended use. “Intended
use” also includes observing this documentation and the
documentation of any accessories used.
Information
Air pressure and air humidity will affect the operational reliability of the electrical components in the
heat pump system (dielectric strength). The location of the heat pump system must be no more than
1000 m above sea level.
2.2 General safety information
Observe the following safety information and instructions
for the appliance.
► Only qualied contractors should carry out the electri-
cal work and installation of this appliance.
► Commissioning and maintenance of the appliance
may be carried out only by OCHSNER Customer Service or by customer service partners authorised by
OCHSNER.
The stated performance data can be conrmed only if
the measurements taken for the appliance are carried out
according to the relevant standardised measurement conditions.
► The authorised contractor is responsible for compli-
ance with all relevant regulations during installation
and commissioning.
► Operate the appliance only when fully installed and
with all safety equipment tted.
► Protect the appliance from dust and dirt ingress dur-
ing building work. Use the plastic cover provided.
► Alterations to the appliance may be carried out only
by OCHSNER Customer Service or by customer service partners authorised by OCHSNER.
► Functions to protect the heat pump can be enabled
using the controller. However, since the controller is
not certied as a safety device, safety measures in
case of breakdown or damage to the heat pump (e.g.
additional external switching of the safety devices in
use) must comply with local regulations. In the case
of upgrades or updates to the controller software,
all function parameters of the heat pump must be
checked.
► Before commencing work on electrical connections
and installation, the heat pump system must be isolated and voltage-free.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 5
OPERATION | Appliance description
13_03_001
2
4
1
3
6
5
WARNING: Injury
The appliance may be used by children aged 8 and
up and persons with reduced physical, sensory or
mental capabilities or a lack of experience provided
that they are supervised or that they have been
instructed on how to use the appliance safely and
have understood the possible risks. Children must
not be allowed to play with the appliance. Children
must not be allowed to clean or carry out user
maintenance on the appliance without supervision.
3. Appliance description
The appliance is an air/water heat pump consisting of an
indoor unit and an outdoor unit. The appliance can be used
to heat a building and provide domestic hot water (DHW).
3.1 Functionality
An air/water heat pump extracts thermal energy from the
ambient air (low temperature) and transmits it together with
electrical drive energy in the form of useful heat (higher
temperature) to a heating and/or DHW circuit.
The heat pump consists of separated circuits linked together via heat exchangers:
► Heat source circuit (extracting heat)
► Refrigerant circuit
► Heat sink circuit (supply of heat to the central heating
and/or DHW)
The operating principle of an air/water heat pump:
The indoor unit is intended to be installed only inside the
building. The indoor unit contains the compressor, which
in terms of sound technology is acoustically decoupled a
number of times from the casing. The casing is acoustically
optimised and allows particularly quiet operation.
OPERATION | Appliance description
i
11_02_200_214_01_004
Compressor
The fully hermetically sealed compressor is designed for
high efciency heat pump applications. A suitable starting
current limiter for the compressor is installed in the indoor
unit.
Electric booster heater
The appliance is tted with an electric booster heater
(immersion heater). At low outdoor temperatures, the appliance operates in bivalent-parallel mode. The appliance
can also be combined with an additional heat generator.
Condenser
The condenser takes the form of a plate heat exchanger,
which is built of stainless steel and insulated on all sides
against condensation and heat loss.
3.2.2 Outdoor unit
The outdoor unit is intended to be installed outside. The
outdoor unit is designed as a horizontal split evaporator.
The indoor unit is connected to the outdoor unit with refrigerant lines, along with electrical control and power supply
cables.
► 1x direct circuit (heating and/or cooling)
► 1x mixed circuit (heating and/or cooling)
► 1x directly heated DHW cylinder (with electric booster
Two name plates are attached to the indoor unit to identify
your heat pump. In addition, a label with the serial number
is attached to the right-hand casing panel of the appliance.
1
2
Evaporator
The evaporator is a part of the outdoor unit and consists
of copper pipes in a set of aluminium ns.
Information
With an air/water heat pump, frost may form on
the evaporator ns of the outdoor unit, depending
on the air temperature (below approx. +7°C), air
humidity and the operating point. The evaporator
ns are automatically de-iced again in the cyclical
defrosting mode of the heat pump.
Fan
The outdoor air is blown across the evaporator by a quiet
fan.
3.2.3 Heat pump control unit
The OCHSNER heat pump controller includes devices
for controlling heat pump heating systems with a cooling
function as well as DHW heating. In its standard version,
the heat pump control unit consists of the OTE controller
and the master controller, both of which are installed in
the indoor unit.
1 Name plate (back of indoor unit and front of control
box)
2 Serial number (right-hand casing panel)
The OTE controller can control the following system circuits
and heat generators:
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 7
OPERATION | Activating settings
i
i
4. Activating settings
Settings are activated with the master controller on the
indoor unit (with graphic display or touchscreen), or via
a remote controller with touchscreen that is attached to
the wall.
5
Mo 09 .01.1710:02
4
3
2
111
1 Button A:
Press to go back one menu step (ESC)
2 Displays function of Button A or fault message
3 Operating status
4 Outdoor temperature
5 Date
6 Time
7 DHW temperature
8 Actual room temperature
9 System temperature
10 Displays function of Button B
11 Button B:
Turn to select from menu or to change setting
Press to conrm (ENTER)
-12.5C22°C52.5°C
Heating mode
OCHSNER OTE
The master controller is mounted in an easily accessible
plastic cover on the top of the indoor unit. Two buttons
are provided for controlling the menu, with an illuminated
graphic display.
6
7
32.5°C
MENU
8
9
10
11_01_200_701_01_01_001
Pressing Button B on the right calls up the main menu
with a diagram of the heating system. Each heat consumer (heating circuit, DHW circuit) and each heat generator
(heat pump, electric booster heater, boiler etc.) has its own
menu and corresponding submenus.
Pressing Button A takes you back one step to the previous
menu.
You will nd further information on operating the heat pump
control unit in the control unit‘s operating instructions which
are also supplied with the heat pump.
Information
The heat pump has no separate on/off switch. In
an emergency, the system must be shut down via
the specied safety devices.
Ensure easy access to the safety devices. It
»
must be possible to perform an emergency
shutdown at all times.
8 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
4.1 Operating costs
In the rst two heating seasons, higher running costs are
to be expected (up to 50% more, depending on residual
moisture in the building). Enabling the screed drying program will also increase operating costs further.
4.1.1 Flow temperatures
For optimum operation of your heat pump, you should aim
for the lowest possible heating ow temperatures (and also
DHW temperatures). The maximum system temperature
for your heat pump should be restricted to 60°C.
Information
Increasing the room temperature by 1°C results in
an increase in consumption of 5-7%.
4.1. 2 Ventilation
Any ventilation should be intermittent, especially during
the heating period, and according to your own require-
OPERATION | Maintenance and care
i
i
ments. Intermittent ventilation is considerably more energy
efcient than permanent ventilation, and therefore saves
money. Avoid permanent ventilation.
4.1. 3 Heating setback program
From an energy efciency point of view, using a time pro-
gram to reduce the heating ow temperature is especially
not recommended for air/water heat pumps with low tem-
perature heating systems (such as underoor heating).
These systems are slow to respond and, due to the addi-
tional output from the system required following the end
of the setback phase, it is possible that the second heat
generator (boiler, electric immersion heater) will cut in. This
can lead to higher operating costs.
5. Maintenance and care
We recommend an annual inspection and if necessary
have your heat pump serviced by OCHSNER Customer
Service.
Material damage
Maintenance work on electrical components of the
heat pump may be carried out only by qualied
contractors.
Material damage
Abrasive tools must not be used to clean the evap-
orator ns in the outdoor unit.
Any dirt on the ns should be blown away
»
using compressed air (max. 8 bar), in the di-
rection of normal air ow.
If the ns are very dirty, contact your OCHS-
»
NER system partner or OCHSNER Customer
Service.
If it is necessary to clean the casing sections of the
»
indoor or outdoor unit, use only a damp cloth (with
water or a weak soapy solution). Do not use any abrasive or aggressive cleaning materials.
During the building phase, protect the indoor and
»
outdoor units from dirt and dust with a suitable cover.
Use the plastic cover provided.
Ensure that the heating circuit is lled with sufcient
»
water.
Ensure that any condensation beneath the outdoor
»
unit can drain away without freezing all year round.
Information
If the outdoor unit is covered with a thick layer of
snow, this can reduce system efciency.
Remove snow on and around the outdoor unit
»
as necessary.
If required, install the snow cover available as
»
an accessory for the outdoor unit.
Information
Ensure that the refrigerant circuit of your heat pump
is tested for leaks once a year (in acc. with Regulation (EU) no. 517/2014).
Ensure year-round access to soldered joints in
»
the refrigerant circuit.
Document the results of the leakage test in the
»
system test report.
6. Problem solving
ProblemCauseSolution
Too little DHW
is available
or the central heating
system is too
cold.
The appliance
is leaking
water.
If you have a problem that you cannot resolve, contact
the system installer, a qualied contractor or OCHSNER
Customer Service.
Faults are displayed as”Er XXX”on the master controller of
the OTE control unit. If a fault occurs, contact your system
installer. The system installer knows your hydraulic system
and how it operates. The causes of faults can often be
found in the settings or in the hydraulics.
Before contacting the installer, make a note of the serial
number and the heat pump model. The serial number and
heat pump model of your appliance are shown on the name
plate. The name plates are attached to the back of the
appliance on the outside and behind the front appliance
casing panel (control box outer side).
The power
supply to the
appliance has
been cut off
The drain
for the safety valve is
blocked.
Check the safety device on the
main distributor board for your
house. Switch the safety device
back on. If the safety device triggers again after being switched
back on, contact a qualified contractor or OCHSNER Customer
Service.
Clean the safety valve drain. See
„Safety valve drain“ on page 32.
Ensure that the outdoor unit (both the top and the un-
»
derside) is kept free from snow, leaves and twigs and
other foreign bodies.
For vertical or horizontal connection to the heating
system.
► 1x outdoor temperature sensor (TA)
► 1x contact sensor for a mixed circuit (TMK)
► 2x pocket sensors for a heat pump buffer tank
(TPO, TPM)
► 1x pocket sensor for a DHW cylinder (TB)
► 1xfoundationxingkitfortheoutdoorunit
10 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance description
11_02_200_202_01_019
8.2 Hydraulic variants of the indoor unit
The indoor unit is available in eight different hydraulic
variants that are illustrated schematically below. Possible
system congurations for the hydraulic versions of the indoor unit are illustrated in „System schematic diagrams“
on page 68.
M2-3
43521
43521
M2-2M2-1
7
8
9
6
12
3521
10
11
7
8
9
6
12
3521
10
M2-4
7
6
12
1 Suction gas line
2 Liquid line
3 Heating water/DHW return
4 DHW ow
5 Heating water ow
6 Heat generator pump
7 Diaphragm expansion vessel
8 3-way switching module
9 Flow meter
10 Safety valve
11 Electric booster heater
12 Heat exchanger (heat sink side)
11
7
9
6
10
12
9
10
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 11
INSTALLATION | Appliance description
43521
43521
M4-2M4-1
6
7
8
9
10
11
21
35
6
7
8
9
11
3521
M4-4M4-3
6
8
9
11
1 Suction gas line
2 Liquid line
3 Heating water/DHW return
4 DHW ow
5 Heating water ow
6 Safety valve
7 3-way switching module
8 Flow meter
9 Heat generator pump
10 Electric booster heater
11 Heat exchanger (heat sink side)
10
6
8
9
11
11_02_200_202_01_020
12 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
11_05_200_214_01_001
i
i
9. Preparing to install the
appliance
Before installing the indoor and outdoor units, preparatory
work needs to be carried out by qualied contractors.
9.1 Indoor unit installation location
Material damage
The indoor unit is intended to be installed only inside the building. It must not be installed in rooms
with high levels of humidity (permanently above
70%).
Information
Plan the installation sites for the outdoor and indoor
units such that the pipework carrying the refrigerant is as short, straight and simple as possible.
B
A ≥ 1000 mm
B ≥ 500 mm
C ≥ 500 mm
D ≥ 50 mm
E ≥ 500 mm
D
E
C
A
The installation location for the indoor unit must meet the
following requirements:
► A dry and frost-free room
► Sound optimised environment
► A horizontal, adequate load bearing oor (for weight
of indoor unit, see „Specication“ on page 50)
► Not situated directly below or above bedrooms
► Max. room temperature 30°C
► The installation room must not be subject to a risk of
explosions arising from dust, gases or vapours.
9.1.1 Keep minimum clearances
Observing the specied minimum clearances for the indoor
unit ensures:
► Correct installation of the appliance
► Fault-free operation
► Ability to carry out maintenance on the appliance.
9.2 Outdoor unit installation location
Information
Plan the installation sites for the outdoor and indoor
units such that the pipework carrying the refrigerant is as short, straight and simple as possible.
Information
When laying refrigerant lines in the ground, schedule the work so that the pipe liner can be laid
together with the already inserted refrigerant lines
in the trench between the outdoor and indoor units.
- If the pipe liner is laid empty, inserting the re-
frigerant lines afterwards will be difcult if not
impossible.
The outdoor unit is intended to be installed only out of
doors. Please note the following with regard to the installation location of the outdoor unit:
► Select the outdoor unit installation location such that
the appliance is safely accessible from all sides all
year round.
► Avoid installing it in a hollow or ditch (a “pool” of cold
air).
► An optional snow cover is available to protect the
outdoor unit fan in case of heavy snowfall. Where
necessary, ensure that a snow cover is installed
(according to installation site and local weather
conditions).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 13
INSTALLATION | Preparing to install the appliance
i
i
Material damage
The air ow through the evaporator must not be
obstructed by surrounding buildings. A reduced air
ow rate can lead to loss of efciency in the system.
Please note the following with regard to installation in
coastal areas:
► The standard design of outdoor unit must be installed
at least 1 km from the sea.
► Outdoor units with special coating, suitable for coast-
al locations, must be installed at least 200 m from the
sea.
► The installation location selected should always be on
the leeward side of the building (the side facing away
from the sea).
Please note the following with regard to sound emissions
from the outdoor unit:
► Avoid installing on reverberant ooring.
► Avoid installing between building walls. The walls can
increase the noise level.
► Avoid installing next to bedrooms.
Information
Plants and cultivated areas around the outdoor
unit, subject to minimum clearances, can reduce
the noise level of the outdoor unit.
11_05_200_504_002
C
A ≥ 3000 mm (minimum clearance to roof)
B ≥ 1000 mm (minimum clearance to a wall)
C 100 mm or ≥ 1000 mm (minimum longitudinal clear-
ance to a wall)
Information
The minimum clearance between two outdoor
units (e.g. connected in cascade) is 1000 mm on
all sides.
9.3 Foundations for the outdoor unit
A
B
11_05_200_504_001
9.2.1 Keep minimum clearances
Observing the specied minimum clearances for the outdoor unit ensures:
► Correct installation of the appliance
► Fault-free operation
► Ability to carry out maintenance on the appliance.
It is permissible to install the outdoor unit under a roof if the
space around the unit is permanently open on three sides.
14 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
A permanent foundation is required beneath the outdoor
unit. The foundations must meet the structural require-
ments of the outdoor unit (see Specication).
Provide for frost-free drainage (e.g. a gravel bed con-
»
nected to a drain) for condensation that forms on the
outdoor unit.
Where refrigerant lines are to be laid in the ground,
»
ensure correct positioning of the pipe liner when laying the foundations.
Use underground waste pipes (with a smooth inner
»
surface) for the pipe liner.
INSTALL ATION | Preparing to install the appliance
i
11_04_200_504_003
11_04_200_504_004
Ensure that the outdoor unit is adequately secured,
»
paying regard to the wind load occurring at the installation location.
CAUTION: Risk of slipping
If drainage for condensation is inadequate, ice can
build up in winter in the area around the outdoor
unit.
Ensure drainage for condensation is sufcient
»
even at low temperatures.
Information
Insulation used beneath the soil must be made of
a closed-cell material. Otherwise, the thermal insulation of the material will be impaired.
100
900
Dig out the foundation trench.
»
Place in position four underground waste pipes
»
(Ø ≥ 250 mm).
≥ 800
9.3.1 Laying spot foundations
900
4
Ø250
3
2
C
1
1 Pipe liner for the connecting lines (where installed
underground)
2 Gravel bed
3 Drainage pipe (frostproof)
4 Spot foundation (with underground waste pipe)
B
A
Ensure correct horizontal and vertical positioning of
»
the underground waste pipes.
Place a drainage pipe along the base of the trench.
»
≥ 1800
1
2
3
1 Underground waste pipe
2 Pipe liner for underground connecting lines
3 Drainage pipe (frostproof)
4 Gravel bed
In the case of underground connecting lines, allow for
»
the pipe liner.
11_04_200_504_001
Fill the foundation trench with coarse gravel. If the
»
pipe liner (with refrigerant lines) is to be installed at
a later point, in the case of underground connection lines, this must be allowed for in the foundation
trench.
4
Fill the underground waste pipes with concrete.
ABC
AIR 71110270≥ Ø160
AIR 111110270≥ Ø160
AIR 181110270≥ Ø160
AIR 232040300≥ Ø200
AIR 292040300≥ Ø200
AIR 412040330≥ Ø250
Use underground waste pipes when installing spot foundations. When installing spot foundations, we recommend
the following approach:
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 15
»
INSTALLATION | Preparing to install the appliance
i
9.3.2 Laying strip foundations
4
3
2
A
C
150
200
1 Pipe liner for the connecting lines (where installed
AIR 71400300≥ Ø160
AIR 111400300≥ Ø160
AIR 181400300≥ Ø160
AIR 232250320≥ Ø200
AIR 292250320≥ Ø200
AIR 412250350≥ Ø250
When laying strip foundations we recommend the following
approach:
1
1100
ABC
≥ 1600
B
1
2
3
1 Reinforced strip foundation
2 Pipe liner for underground connecting lines
3 Drainage pipe (frostproof)
4 Gravel bed
In the case of underground connecting lines, allow for
»
the pipe liner.
Fill the foundation trench with coarse gravel. If the
»
pipe liner (with refrigerant lines) is to be installed at
a later point, in the case of underground connection lines, this must be allowed for in the foundation
11_04_200_504_002
trench.
Construct the two reinforced strip foundations.
»
9.3.3 Installing on at roofs
WARNING: Risk of falling
Working on a at roof without fall protection constitutes a risk.
When working on a at roof, observe the laws
»
relating to occupational safety in your region.
Always be aware of the open edge.
»
Information
Avoid installing the outdoor unit on the roof above
residential buildings or on car ports attached to residential buildings, due to the risk of structure-borne
noise transmission.
Loads and stresses on roof structure
≥ 300
4
11_04_200_504_006
Note that when outside temperatures are very low,
»
ice can form beneath the outdoor unit.
≥ 800
11_04_200_504_005
Dig out the foundation trench.
»
Place a drainage pipe along the base of the trench.
»
16 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
In terms of roof structure loads, allow for an ice load
»
of 400 kg/m² in addition to the dead weight of the
outdoor unit.
INSTALL ATION | Preparing to install the appliance
i
3
2
1
1 Flat roof
2 Refrigerant lines in open air (enclosed in thermal in-
sulation with UV protection)
3 2x concrete slabs attached with exible adhesive (per
leg of the outdoor unit). The outdoor unit is afxed to
the concrete slabs
4 Anti-vibration mounts
When installing the outdoor unit on a freestanding car port,
a garage roof or a storage space roof, please note the
following:
Ensure that the outdoor unit is adequately secured,
»
paying regard to the wind load occurring at the installation location.
Take account of the concentrated load arising from
»
the dead weight of the outdoor unit (including the
roof xings) and the surface load caused by possible
tween the outdoor unit and the installation points on
the roof.
4
9.4 Preparing the refrigerant lines
Information
If the appliance, the refrigerant lines, the pipe xings and the wall outlets are not installed correctly,
structure-borne sounds can be transmitted to the
building.
Ensure that the refrigerant lines are in-
»
11_06_200_202_006
stalled in a way that ensures insulation from
structure-borne noise. The system installer
carrying out the work is responsible for this.
Material damage
Use only copper pipes suitable for refrigerant
(D IN 12735-1). Thin-walled pipes run the risk of
bursting.
Please observe the stipulated diameters and
»
wall thicknesses of the copper pipes.
Material damage
Incorrect or premature opening of the pipe connections and cutting of the refrigerant lines can allow
dirt and moisture to enter the refrigerant circuit.
Do not open the connections on the indoor
»
or outdoor units until just before installing the
refrigerant lines.
Cut the refrigerant lines with a suitable pipe
»
cutte r.
Prevent swarf from contaminating the pipe
»
connections and refrigerant lines.
Once cut, ll the refrigerant lines with a sub-
»
stance such as nitrogen.
Keep the refrigerant lines closed until just be-
»
fore installation.
Pipe connections for the refrigerant lines (suction gas and
liquid lines) are supplied soldered closed, both for the indoor unit and the outdoor unit. Appropriate copper pipes
for refrigerant lines are supplied sealed at both ends and
lled with nitrogen.
Please note the following with regard to routing of the refrigerant lines:
Keep to a minimum the distance between the indoor
»
and outdoor units, in order to minimise heat loss from
the refrigerant lines.
Select the installation sites for the indoor and outdoor
»
units such that the maximum permissible line lengths
and height differentials are not exceeded.
Avoid routing the lines in the vicinity of bedrooms.
»
The refrigerant in the lines can generate noise under
certain operational conditions.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 17
INSTALLATION | Preparing to install the appliance
i
9.4.1 Line lengths
Observe the maximum permissible line lengths for
»
the refrigerant lines.
Where the outdoor unit is positioned higher than the
»
indoor unit, observe the maximum permissible height
differential between the two units.
C
B
A
Where a line routed along the ceiling is used in
»
conjunction with an underground connection line,
observe the maximum permissible height differential
between the highest and lowest points of the refrigerant lines.
1223
D
11_06_200_202_001
≤ 3500
11_06_200_202_002
A + B + C
(sum of line lengths)
AIR 7≤ 20 m≤ 10 m
AIR 11≤ 20 m≤ 10 m
AIR 18≤ 20 m≤ 10 m
AIR 23≤ 20 m≤ 10 m
AIR 29≤ 20 m≤ 10 m
AIR 41≤ 16 m≤ 5 m
Where the outdoor unit is positioned lower than the
»
indoor unit, observe the maximum permissible height
differential between the highest and lowest points of
the refrigerant lines.
1180
(max. height differential)
≤ 3500
D
9.4.2 Pipe diameter
The pipe diameter data for refrigerant lines shown below
applies as long as the following are observed:
► A maximum of eight 90° pipe bends
► With pipe diameters of < 35 mm, use a suitable pipe
bending tool to create the pipe bends
► With pipe diameters of ≥ 35 mm, use type 5002 pipe
bends
► Bending radii of ≥ 1 m are treated as straight runs
Information
Refrigerant lines with a pipe diameter of ≥ 35 mm
are created from rigid copper pipes in 5 m lengths.
With underground refrigerant lines, provide an
»
assembly shaft at connection sites to facilitate
soldering and maintenance work.
≤ 2970
18 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
650
11_06_200_202_003
INSTALL ATION | Preparing to install the appliance
Pipe diameter of the refrigerant line
Refrigerant line up to 6 mRefrigerant line up to 8 m
Liquid lineSuction gas
line
AIR 710181018
AIR 1112181218
AIR 1812221222
AIR 231222162x22
AIR 29162x22162x22
AIR 4116421642
AIR 41164x22164x22
Pipe diameter of the refrigerant line
Refrigerant line up to
10 m
Liquid lineSuction gas
line
AIR 710181018
AIR 1112221222
AIR 181222122 x18
AIR 23162x22162x22
AIR 29162x22162x22
AIR 4116421642
AIR 41164x22164x22
Pipe diameter of the refrigerant line
Refrigerant line up to
14 m
Liquid lineSuction gas
line
AIR 710181018
AIR 1112221222
AIR 18122 x18122x22
AIR 23162x22162x22
AIR 29162x221635
AIR 29162x22163x22
AIR 4116421642
AIR 41164x22164x22
Liquid lineSuction gas
line
Refrigerant line up to
12 m
Liquid lineSuction gas
line
Refrigerant line up to
16 m
Liquid lineSuction gas
line
9.4.3 Preparing the wall outlets
Whether the refrigerant lines between the indoor and
outdoor units are to be routed above or below ground, ap-
propriate and plant-specic wall outlets need to be created
through the outer wall of the building.
Ensure that the wall outlets are constructed in an ap-
»
propriate, plant-specic manner.
Take the construction of the wall (tiles, concrete) into
»
account.
Take the prevailing groundwater situation into
»
account.
Material damage
Incorrectly created wall outlets can cause signicant damage to property, due to water (seepage,
condensation, floodwater) penetrating into the
building or stonework. Where the wall outlets are
created below ground level, the breach must be
appropriate to local conditions at the site (e.g.
non-accumulating or accumulating seepage water,
groundwater under pressure).
Use a suitable pipe liner or wall sleeve for the
»
wall outlet.
Tie the external end of the wall outlet in to the
»
external waterproof seal of the building.
Ensure that the pipe liner is arranged with a
»
slight fall (at least 2%) to the outside.
On both the outside and inside edge of the
»
wall, use appropriate ring seals to seal the
space between the wall sleeve and the refrigerant lines and electrical cables passing
through.
Material damage
PU foam is not suitable as a sealant for the pipe
li ner.
Pipe diameter of the refrigerant line
Refrigerant line up to
18 m
Liquid lineSuction gas
line
AIR 710181018
AIR 1112221222
AIR 18122x22122x22
AIR 23162x22162x22
AIR 2916351635
AIR 29163x22163x22
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 19
Refrigerant line up to
20 m
Liquid lineSuction gas
line
INSTALLATION | Preparing to install the appliance
i
i
i
i
9.4.4 Preparing refrigerant lines passing through open
air
3
2
1
6
1 Appropriately sealed wall outlet (particularly where
there is a risk of ooding)
2 Appropriate sealing of the refrigerant lines as they
pass through the wall outlet
3 Refrigerant lines in open air (enclosed in thermal in-
sulation with UV protection)
4 Reinforced strip foundation
5 Drainage pipe (frostproof)
6 Foundation
Information
All solder sites on the copper pipework of the refrigerant line must be accessible all year round for
maintenance purposes (in accordance with Regulation (EU) no. 517/2014).
Run the refrigerant lines between the indoor and out-
»
door units.
4
5
9.4.5 Preparing underground refrigerant lines
5
3
2
1
10
11_06_200_202_005
1 Appropriately sealed wall outlet
2 Appropriate sealing of the refrigerant lines as they
pass through the pipe liner
3 Insulation
4 Gravel
5 Reinforced strip foundation
6 Appropriate sealing at the end of the pipe liner (be-
tween refrigerant lines and pipe liner)
7 Drainage pipe (frostproof)
8 Pipe liner (with min. 2% fall to outside)
9 Drain
10 Foundation
Information
All solder sites on the copper pipework of the refrigerant line must be accessible all year round for
maintenance purposes (in accordance with Regulation (EU) no. 517/2014).
4
~ 600
8
7
9
6
11_06_200_202_004
Allow some surplus length in the refrigerant lines
»
between the connections at the indoor and outdoor
units.
Ensure that the wall outlets are sealed in an appropri-
»
ate, plant-specic manner.
Use suitable sound-insulating pipe xings to secure
»
the refrigerant lines.
Insulate the refrigerant lines with suitable insulating
»
material where they pass through open air between
the indoor and outdoor units, to prevent formation
of condensation. When passing through open air
outside, the insulating material must also have UV
protection.
Information
Where the refrigerant lines run horizontally through
open air, use suitable supports. Take steps to prevent open refrigerant lines from being walked or
driven on.
Information
When laying refrigerant lines in the ground, schedule the work so that the pipe liner can be laid
together with the already inserted refrigerant lines
in the trench between the outdoor and indoor units.
- If the pipe liner is laid empty, inserting the re-
frigerant lines afterwards will be difcult if not
impossible.
20 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
1
Ensure that the wall outlets are appropriate and
»
plant-specic, and that the pipe liner is appropriately
sealed.
Ensure that the open end of the pipe liner at the
»
outdoor unit is properly sealed. For sealing the refrigerant lines in the pipe liner, use for example an
appropriate ring seal or a UV-resistant, permanently
exible sealing compound.
Any exposed refrigerant lines outside the pipe liner
»
must also be protected from a build-up of condensation with appropriate insulating material. Out of doors,
the insulating material must also have UV protection.
Information
Insulation used beneath the soil must be made of
a closed-cell material. Otherwise, the thermal insulation of the material will be impaired.
2
1 Where the pipe liner has two 90° bends, it must be
laid together with the refrigerant lines.
2 If the pipe liner is laid empty, it will not be possible to
insert the refrigerant lines afterwards.
For the underground pipe liner, use rigid waste pipes.
»
Use a pipe liner of a suitable diameter for the sys-
»
tem-specic refrigerant lines and the planned pipe
bends (see „Foundations for the outdoor unit“ on
page 14).
For 90° bends in the pipes, use either 3x 30° bends
»
or 6x 15° bends (depending on the diameter of the
pipe liner and the depth at which it is laid).
At the point where the refrigerant lines are connected
»
to the outdoor unit, create a suitable trench.
11_06_200_202_007
Material damage
PU foam is not suitable as a sealant for the pipe
li ner.
Dig a straight trench between the wall outlet and the
»
trench at the outdoor unit.
Lay the pipe liner, with the refrigerant lines already
»
inserted, into the trench between the outdoor and indoor units.
Lay the electrical control leads and power supply
»
cables in a suitable electrical conduit. The optional
OCHSNER cable harness is suitable for laying direct
into the ground.
Allow some surplus length in the refrigerant lines
»
between the connections at the indoor and outdoor
units.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 21
INSTALLATION | Preparing to install the appliance
i
i
i
9.5 Preparing the electrical connections
WARNING: Electrocution
All electrical connection and installation work must
be carried out according to the applicable national
and regional regulations.
WARNING: Electrocution
Before commencing work on electrical connections
and installation, the heat pump system must be
isolated and voltage-free.
WARNING: Electrocution
Work on electrical connections and installation may
be conducted only by qualied contractors.
Material damage
This appliance contains frequency converters (e.g.
EC circulation pumps, EC fan motors). Leakage
currents may arise in normal operation. In the event
of faults, these components may cause DC fault
currents. An incorrectly selected RCD may trip during normal operation or, in the event of a fault, may
not trip at all or only trip after a delay.
Make sure that the power supply for this
»
appliance is separate from the domestic installation.
If local conditions require the installation of an
»
RCD, use type B AC/DC-sensitive RCDs.
► For the integral electric booster heater (8.8 kW), a
suitable high limit safety cut-out (HLSC) is installed in
the indoor unit.
Information
The main power circuit for the compressor has
no upstream power contactor on the machine
side. Control devices and equipment to disconnect and shut down all supply voltages across
all poles, which must be provided on the system
side, must meet the technical safety requirements
of EN 60204-1 sections 5 and 13.4.5, as well as the
international regulations in the IEC 60947 series.
Material damage
Protect the main power circuit (compressor), the
control circuit (control unit) and the electric booster
heater separately from one another.
9.5.1 Heat pumps for three-phase alternating current
1
3456
2
C13AB16A
Information
It is essential that the regulations of the responsible
power supply utility (PSU) and the applicable EN
standards be observed.
Information
The values specied in this documentation for
circuit protectors and cable cross-sections are
standard values. The contractor carrying out the
work is responsible for plant-specic sizing of safety equipment and cable cross-sections.
► For the electrical connection, use the system principle
schematic appropriate to your heat pump system from
section „System schematic diagrams“ on page 68.
► The outdoor unit takes its power supply from the in-
door unit. The supply cable for the fan in the outdoor
unit is protected by an internal C10A circuit breaker in
the indoor unit.
► In the case of a fault, the protection on the main pow-
er circuit (compressor) and electric booster heater
must break the circuit across all poles.
3 x 400 VAC1 x 230 VAC 3 x 400 VAC
1 Heat pump indoor unit control box
2 Main system distributor board
3 Supply to main power circuit (compressor)
4 PSU signal contact
5 Supply to control circuit (OTE controller)
6 Supply to electric booster heater
DescriptionTyp eMax.
Main power circuit
(compressor and
fan)
Electric booster
heater
Control circuit
(control unit)
AIR 7 C11A13.55.4C10A
AIR 11 C 11A20.07.9C10A
AIR 18 C11A32.011. 4C16A
AIR 23 C12A50.516.8C20A
AIR 29 C12A49.521.1C25A
AIR 41 C12A63.524.8C25A
AIR 7 C11A
–
AIR 41 C12A
AIR 7 C11A
–
AIR 41 C12A
starting
current
[A]
Max. operating
current
[A]
–14B16A
–6C13A
11_02_200_202_01_010
Fuse
► All power supply cables must be protected against
surges and short circuits.
22 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
i
Material damage
Operating a three-phase motor (compressor,
pumps, fans) for long periods using an incorrectly
phased three-phase supply will damage the motor.
Ensure that all three-phase motors are
»
connected to a three-phase supply with a
clockwise rotating eld.
9.5.2 Heat pumps for single phase alternating current
1
3456
2
C13AB16A
1 x 230 VAC1 x 230 VAC 3 x 230 VAC
1 Heat pump indoor unit control box
2 Main system distributor board
3 Supply to main power circuit (compressor)
4 PSU signal contact
5 Supply to control circuit (OTE controller)
6 Supply to electric booster heater
DescriptionTyp eMax.
Main power circuit
(compressor and
fan)
Electric booster
heater
Control circuit
(control unit)
AIR 11 C 11B48.520.8C25A
AIR 18 C11B80.030.0C40A
AIR 11 C 11B–12.8B16A
AIR 18 C11B
AIR 11 C 11B–6C13A
AIR 18 C11B
starting
current
[A]
Max. operating
current
[A]
Fuse
9.5.3 Cables from main distributor to indoor unit
DescriptionWiresMin. cable
Supply to electric booster
heater
(8.8 kW electric immersion
heater)
Control circuit supply1x 2 30 VAC
Supply to pumps and servomotors
Sensor leads
(system temperature sensors)
Bus leads
(eBus connections from
OTE controller to remote
controllers or auxiliary
modules and in cascades)
3x 400 VAC
(L1/L2/L3/N/PE)
or
3x 230 VAC
(L/L/L/N/PE)
Sensor leads must be routed separately from 230 V
and 400 V cables. If a minimum distance of 20 cm
cannot be maintained, then shielded cables should
be used. The shielding should be connected to the
earth rail of the heat pump.
Defrost sensors (TQA, TQE):
The two defrost sensors are factory-installed in the evaporator on the outdoor unit.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 23
INSTALLATION | Preparing to install the appliance
i
i
Outdoor temperature sensor (TA):
nected directly to the OTE controller (1x 230 VAC power
supply).
Fit the outdoor temperature sensor at a height of ap-
»
prox. 2.5 m to the outside wall of the building (on the
north-west side). Make sure that the outdoor temperature sensor is not exposed to direct sunlight or wind,
as this will impair the control characteristics.
Information
Avoid tting the outside temperature sensor to the
casing of the outdoor unit or in the air ow from
the outdoor unit.
Buffer sensor (TPO, TPM):
In heat pump buffer tank, two buffer sensors are required.
The heat pump is switched on on the basis of readings
from the TPO and switched off on the basis of those from
the TPM.
Install a sensor pocket in the female socket provided
»
for the upper buffer sensor (TPO)
Install a sensor pocket in the female socket provided
»
for the lower buffer sensor (TPM)
DHW sensor (TB):
Material damage
A test run of the pumps and servomotors may be
conducted only on a system that has been prepared for commissioning. The hydraulics must be
fully connected.
9.5.7 PSU signal contact
Tariff switching on the heat pump system
In the case of tariff switching (with interrupted power delivery), the heat pump is temporarily shut down by the power
supply utility (PSU).
Uninterrupted tariff
In the case of tariff switching with uninterrupted power
delivery, the heat pump is temporarily shut down by the
power supply utility. A PSU signal contact is provided for
this purpose on the indoor unit. To activate the function,
remove a cable bridge in the control box and connect the
PSU signal contact cable (see „Electrical connection of the
indoor unit“ on page 34).
OCHSNER DHW cylinders are tted with appropriate female sockets for installing the sensor.
Install the DHW sensor in the top one-third of the
»
DHW cylinder (or at the very least in the top half). The
lower the selected position of the DHW sensor, the
larger the switching hysteresis (5-15 K) will need to
be.
Information
Ensure that the DHW sensor is correctly positioned
and extends beyond the cylinder insulation into the
interior of the DHW cylinder. This is the only way in
which the temperature can be captured correctly.
Mixer sensor (TMK):
If, in addition to a direct heating circuit, your system also
has a heating circuit with mixing valve, then a mixer sensor
must be installed. The mixer sensor is supplied with the
heat pump, as a contact sensor including band clamp and
heat conducting paste.
Install the mixer sensor immediately downstream
»
of heating circuit circulation pump 2 for the heating
circuit with mixing valve, on a (metal) pipe made of a
good heat-conducting material.
Shutdown by means of a tariff contactor
In the case of shutdown by means of a tariff contactor installed on behalf of the customer (sealed by the PSU), the
power supply to the heat pump compressor is disconnected. Here, it is essential to connect an auxiliary contact to
the tariff contactor (N/C contact) of the PSU signal contact
on the indoor unit.
Night tariff
Where tariff switching takes place within the meter (night
tariff), the PSU signal contact is not connected.
9.5.8 Smart Grid
For the Smart Grid function, special descriptions are available on request from your OCHSNER Customer Service
department.
9.5.6 Pumps and servomotors (230 VAC)
Pumps (heating circuit pumps, DHW charging pump) and
servomotors (switching module, mixing valve) are con-
24 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance installation
i
i
11_02_200_214_01_005
11_02_200_214_01_001
10. Appliance installation
10.1 Installation of indoor unit
10 .1.1 Delivery and transportation
The appliance is delivered on a one-way pallet, wrapped
in lm. The appliance casing is assembled on delivery.
Information
Should you notice any transportation damage to
the appliance, you must report such damaged immediately when the delivery is unloaded. Claims
for transportation damage cannot be made subsequently.
Material damage
Protect the appliance from damage by using
»
transport belts.
When transporting, protect the appliance from
»
impact.
► The appliance is secured to the one-way (recyclable)
pallet of the transport packaging with screws.
► The transport packaging or one-way pallet is suitable
for transportation using a forklift truck.
► For level transportation to the installation location, the
appliance may remain in the transport packaging.
► Leave the appliance in the transport packaging or on
the one-way pallet for lifting and moving by crane or
forklift.
► The standard packaging of the appliance does not
provide protection against the weather or sea water.
► The appliance may be stored and transported only at
temperatures of between -20°C and +45°C.
► The appliance must be stored in its transport
packaging.
Information
If the route to the installation location is difcult,
the transport packaging should be removed and
the appliance casing disassembled.
Please note the following when removing the transport
packaging:
Remove the transport packaging.
»
Undo and remove the eight woodscrews on the two
»
transport xing brackets (left and right) securing the
appliance to the one-way pallet.
Use the pre-installed transport aids (2 lifting slings at
»
the front and 2 lifting handles at the rear) to lift and
transport the appliance.
Transport the appliance in an upright position. Over
»
short distances, you may transport the appliance
carefully at an angle of up to 30°.
Material damage
Note the following points when carrying the appliance with the pre-installed transport aids:
- When lifting and carrying the appliance, make
sure that all 4 transport aids are pulled evenly
and at the same time.
- Ensure that the appliance casing is not damaged during transport.
- The transport aids are not suitable for lifting by
crane.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 25
INSTALLATION | Appliance installation
i
Material damage
When being transported with the appliance casing disassembled, sensitive components will be
exposed.
Take care transporting the appliance.
»
10 .1.2 Positioning the appliance
After the appliance has been placed in position,
»
remove the two lifting slings at the front of the
appliance.
Undo and remove the two mounting bolts and remove
»
the two lifting slings.
Then screw the two mounting bolts back into the ap-
»
pliance frame.
10 .1.3 Disassembling the appliance casing
11_02_200_214_01_002
Position the appliance at the intended installation
»
location.
Use the pre-installed transport aids (2 lifting slings at
»
the front and 2 lifting handles at the rear) to slide and
tilt the appliance.
Observe minimum clearances.
»
Ensure the appliance is horizontal. To compen-
»
sate for minor unevenness in the oor, use the four
height-adjusting plastic glides on the underside of the
appliance.
Information
On the underside of the indoor unit, there are four
plastic glides with rubber mounted threaded pins
(without nuts). Discrepancies in oor height of up
to 6 mm can be compensated for.
1
23
Undo and remove the four knurled screws for the ap-
»
pliance casing panel at the rear of the appliance.
Undo and remove the two xing screws for the control
»
box cover, on the rear of the appliance.
11_02_200_214_01_006
Slide back the control box cover. Lift the control box
»
cover up and away.
11_02_200_214_01_003
1 Lifting sling
2 Mounting bolt
3 Appliance frame
26 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_02_200_214_01_007
INSTALL ATION | Appliance installation
11_02_200_214_01_012
Undo and remove the two xing screws for the left-
»
hand appliance casing panel, inside the control box.
Lift the left-hand appliance casing panel up and away.
»
Material damage
When the appliance casing has been disassembled, sensitive components are fully exposed.
Assemble the appliance casing as soon as
»
there is nothing that needs doing inside the
appliance.
During the building phase, provide the appli-
»
ance with additional protection from dirt and
dust with a suitable covering.
10 .1.4 Assembling the appliance casing
11_02_200_214_01_008
Undo and remove the three xing screws for the front
»
appliance panel, inside the control box.
Lift the front appliance casing panel up and away.
»
Undo and remove the two xing screws for the right-
»
hand appliance casing panel, inside the control box.
Lift the right-hand appliance casing panel up and
»
away.
11_02_200_214_01_009
Slide the left-hand and front appliance casing panels
»
down from the top along the frame of the appliance,
until the panels click into place at the bottom.
Ensure that both panels are fully engaged at the ve
»
positions along the bottom.
Secure both of these appliance casing panels with
»
screws at the xing points provided, inside the control
box.
11_02_200_214_01_010
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 27
INSTALLATION | Appliance installation
i
Slide the right-hand appliance casing panel down
»
from the top along the frame of the appliance, until
the panel clicks into place at the bottom.
10.2 Installing the outdoor unit
10 . 2 .1 Delivery and transportation
The appliance is delivered on a one-way pallet, wrapped
in lm. The appliance casing is assembled on delivery.
Information
Should you notice any transportation damage to
the appliance, you must report such damaged immediately when the delivery is unloaded. Claims
for transportation damage cannot be made subsequently.
Material damage
Protect the appliance from damage by using
»
transport belts.
When transporting, protect the appliance from
»
impact.
11_02_200_214_01_011
► The appliance is secured to the one-way (recyclable)
pallet of the transport packaging with screws.
► The transport packaging or one-way pallet is suitable
for transportation using a forklift truck.
Ensure that the panel is fully engaged at the three
»
points along the bottom.
Secure the appliance casing with screws at the xing
»
points provided, inside the control box.
Secure the appliance casing with screws at the rear
»
of the indoor unit.
► For level transportation to the installation location, the
appliance may remain in the transport packaging.
► Leave the appliance in the transport packaging or on
the one-way pallet for lifting and moving by crane or
forklift.
► The standard packaging of the appliance does not
provide protection against the weather or sea water.
► The appliance may be stored and transported only at
temperatures of between -20°C and +45°C.
► The appliance must be stored in its transport
packaging.
Please note the following when removing the transport
packaging:
11_02_200_214_01_006
Remove the transport packaging.
»
28 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_02_200_504_01_007
INSTALL ATION | Appliance installation
11_02_200_504_01_006
i
Undo and remove the four woodscrews securing the
»
appliance to the one-way pallet.
10.2.2 Positioning the appliance
Position the appliance on the prepared foundations.
»
Secure the four legs of the outdoor unit on the foun-
»
dations, using four xing screws.
10.2.3 Disassembling the appliance casing
By removing the side casing panels on the outdoor unit,
you can gain access to the connection points for the refrigerant lines and to the terminal boxes for the electrical
control leads and power supply cables.
Undo and remove the two xing screws on the
»
underside.
Pull the side appliance casing panel down and away.
Attach the four mounting feet of the snow cover to the
»
outdoor unit, by screwing the threaded pins into the
four free screw holes in the ring-shaped casing part.
Attach the round stainless steel plate of the snow
»
cover to the four positioning feet (M5x12 mm, stainless steel).
10.2.4 Installing the snow cover
The snow cover for an outdoor unit fan can be retrotted.
10.2.5 Fitting the cylindrical silencer
Information
The Super Silent Paket (SSP) exclusively available
ex works for a VHS-M outdoor unit reduces noise
by up to 3 dB. The Super Silent Paket consists of:
11_02_200_504_01_009
The cylindrical silencer from the super silent package
(SSP) can be retrotted.A retrotted cylindrical silencer
alone will reduce noise by about 1.5 dB.
11_02_200_504_01_005
- One cylindrical silencer per fan
- Reinforced casing insulation
- Shielded refrigeration technology
Undo and remove four of the eight xing screws on
»
the ring-shaped casing part for the fan (M5x12 mm,
stainless steel).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 29
INSTALLATION | Appliance installation
1
10.2.6 Installing the SSP snow cover
The SSP snow cover can be retrotted to an existing cy-
lindrical silencer on the outdoor unit.
Secure the four mounting feet to the round stainless
»
steel plate with screws (M5x12, 8 pcs).
Screw the safety bolt (M6x12, 1 pce) for the sound
»
absorbing mat into the centre of the stainless steel
plate.
1 Casing section for the fan
Undo and remove the eight xing screws (M5x12 mm,
»
stainless steel) on the ring-shaped casing part of the
fan.
Remove the ring-shaped casing part.
»
4
3
11_02_200_504_01_003
1 Round stainless steel plate with attached sound ab-
sorbing mat
2 Mounting foot with threaded rivet (4 pcs)
3 Safety bolt (M6x12, 1 pce) with washer and retaining
nut
4 Fixing screw (M5x12, 8 pcs) with plastic washer
Position the SSP snow cover on the upper edge of
»
the cylindrical silencer.
Ensure that the SSP snow cover is correctly aligned.
»
The cylindrical silencer has just one predrilled screw
hole for each mounting foot.
1
2
11_02_200_504_01_008
First, secure the four mounting feet of the SSP
»
snow cover to the cylindrical silencer, using the four
1
11_02_200_504_01_002
1 Cylindrical silencer
Position the cylindrical silencer over the fan. Ensure
»
that the assembly holes are correctly aligned.
Attach the cylindrical silencer to the casing panel of
»
the outdoor unit, using the eight xing screws (M5x12,
stainless steel).
30 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
pre-drilled holes. Use self-tapping xing screws
(4.8x19 mm, stainless steel).
Secure the SSP snow cover through the remaining
»
four screw holes in the mounting feet that do not have
pre-drilled receiving holes. Use self-tapping xing
screws (4.8x19 mm, stainless steel).