Ochsner AIR 7, AIR 41, AIR 11, AIR 18, AIR 23 Operating And Installation Manual

...
HIGH EFFICIENCY AIR/WATER HEAT PUMPS
OPERATING AND INSTALLATION MANUAL
AIR 7
AI R 11
AIR 18
AIR 23
AIR 41
CONTENTS
PLEASE NOTE OPERATION
1. Information on documentation 4
1.1 Safety information 4
1.1.1 Arrangement of safety information 4
1.1.2 Symbols and possible dangers 4
1.1.3 Keywords 4
1.2 Other symbols 5
1.3 Units of measurement 5
1.4 Specied performance data 5
2. Safety 5
2.1 Intended use 5
2.2 General safety information 5
3. Appliance description 6
3.1 Functionality 6
3.2 Appliance components 6
3.2.1 Indoor unit 6
3.2.2 Outdoor unit 7
3.2.3 Heat pump control unit 7
3.3 Name plate 7
4. Activating settings 8
4.1 Operating costs 8
4.1.1 Flow temperatures 8
4.1. 2 Ventilation 8
4.1. 3 Heating setback program 9
5. Maintenance and care 9
6. Problem solving 9 INSTALLATION
7. Safety 10
7.1 General safety information 10
7. 2 Regulations, codes and standards 10
8. Appliance description 10
8.1 Standard delivery 10
8.2 Hydraulic variants of the indoor unit 11
9. Preparing to install the appliance 13
9.1 Indoor unit installation location 13
9.1.1 Keep minimum clearances 13
9.2 Outdoor unit installation location 13
9.2.1 Keep minimum clearances 14
9.3 Foundations for the outdoor unit 14
9.3.1 Laying spot foundations 15
9.3.2 Laying strip foundations 16
9.3.3 Installing on at roofs 16
9.4 Preparing the refrigerant lines 17
9.4.1 Line lengths 18
9.4.2 Pipe diameter 18
9.4.3 Preparing the wall outlets 19
9.4.4 Preparing refrigerant lines passing through open air 20
9.4.5 Preparing underground refrigerant lines 20
9.5 Preparing the electrical connections 22
9.5.1 Heat pumps for three-phase alternating current 22
9.5.2 Heat pumps for single phase alternating current 23
9.5.3 Cables from main distributor to indoor unit 23
9.5.4 Cables from indoor to outdoor unit 23
9.5.5 Temperature sensor 23
9.5.6 Pumps and servomotors (230 VAC) 24
9.5.7 PSU signal contact 24
9.5.8 Smart Grid 24
10. Appliance installation 25
10 .1 Installation of indoor unit 25
10 .1.1 Delivery and transportation 25 10 .1.2 Positioning the appliance 26 10 .1.3 Disassembling the appliance casing 26 10 .1.4 Assembling the appliance casing 27
10.2 Installing the outdoor unit 28 10 . 2 .1 Delivery and transportation 28
10.2.2 Positioning the appliance 29
10.2.3 Disassembling the appliance casing 29
10.2.4 Installing the snow cover 29
10.2.5 Fitting the cylindrical silencer 29
10.2.6 Installing the SSP snow cover 30
10.3 Connecting the heat sink system 31 10 . 3 .1 Connecting the heating water 31
10.3.2 Safety valve drain 32
10.3.3 Filling the heating system 32
10.3.4 Diaphragm expansion vessel (DEV) 33
10.3.5 Flow metering 33
10.3.6 Cooling version 33
10.3.7 Connecting the DHW 33
10.4 Electrical connection 34 10 . 4 .1 General 34
10.4.2 Electrical connection of the indoor unit 34
10.4.3 Electrical connection of the outdoor unit 36
10.5 Connecting heat source system 37 10 . 5 .1 Connecting the refrigerant lines 37
10.5.2 Checking for leak tightness 38
10.5.3 Filling the refrigerant circuit with refrigerant 38
10.5.4 Insulating the refrigerant lines 38
11. Commissioning 39
11.1 Before switching on for the rst time 39
11. 2 Testing the control circuit 39
11. 3 Adjusting the ow rate 39
11. 4 Heat generator pump (HGP) 42
11. 5 Necessary conditions for commissioning 43
11. 6 Commissioning the system 44
11.7 Decommissioning 45
12. Troubleshooting 46
12 .1 Fault messages on the master controller 46
12.2 Reset high limit safety cut-out 48
13. Appliance maintenance 48
13 .1 Testing safety valve 48
13.2 Maintenance contract 49
14. Specication 50
14 .1 Heat pumps for three-phase alternating current 50 14 .1.1 Data table 50 14 .1.2 Output diagrams 54 14 .1.3 Details of energy consumption 60
14.2 Heat pumps for single phase alternating current 62 14 . 2 .1 Data table 62
14.2.2 Output diagrams 64
14.2.3 Details of energy consumption 66
14.3 Limits of use 67
14.4 System schematic diagrams 68
14.5 Voltage quality in island mode 84
14.6 Dimensions and connections 85 14 . 6.1 Indoor unit 85
14.6.2 Outdoor unit 86
15. Environment and recycling 90
16. Declaration of Conformity 91
17. ERP-Data 93
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 3
PLEASE NOTE | Information on documentation
i

PLEASE NOTE

f The appliance can be used by children over the age
of eight years and by people with reduced phys­ical, sensory or mental abilities or with a lack of experience and knowledge, if they are supervised or instructed on the safe use of the appliance and understand the dangers that can arise from its use. Children must not be allowed to play with the ap­pliance. Children must not be allowed to clean or carry out user maintenance on the appliance without supervision.
f Connection to the mains electricity supply must be
by means of a xed connection. It must be possible to isolate the appliance from the mains supply with a multi pole switch which has a gap of at least 3 mm across all poles.
f You must not disconnect the mains supply even
outside the heating period. If the power supply is disconnected, active frost protection of the system cannot be guaranteed.
f You do not need to switch off the system for the
summer. The heat pump control unit changes over automatically between summer and winter.

OPERATION

1. Information on documentation

The “Please note” and “Operation” sections are intended
for the appliance user and the qualied contractor.
The “Installation” section is intended for the qualied con-
tractor.
Unless otherwise stated, all the content of this documenta­tion applies to the appliances listed on the title page. This documentation describes appliances that are not always standard items. There may therefore be differences to your
specic appliance.
Information
Read all of this documentation carefully before us­ing the appliance and keep the documents safe. Pass this documentation on to any new user.

1.1 Safety information

1.1.1 Arrangement of safety information
f Observe the minimum clearances in order to ensure
fault-free operation of the appliance and to allow for maintenance work on the appliance.
f In bivalent mode, the return water from the second
heat generator can ow through the heat pump. Note that the return water temperature must not exceed 65°C.
f Maintenance work such as checking the electrical
safety of the appliance may only be carried out by a
qualied contractor.
f We recommend an annual inspection (to assess the
appliance‘s actual condition) and if necessary main­tenance (to reinstate it to its expected condition) by a
qualied contractor.
KEYWORD: Type of risk
The possible consequences of not observing the safety information are shown here.
Instructions for action to remedy or remove
»
the source of danger are shown here.
1.1.2 Symbols and possible dangers
Symbol Type of risk
Injury
Electrocution
Burns (burns, scalding)
Material damage (appliance, consequential and environmental dam­age)
1.1.3 Keywords
Keyword Meaning
DANGER Failure to observe this information will result in seri-
WARNING Failure to observe this information may result in se-
CAUTION Failure to observe this information may result in
ous injury or death.
rious injury or death.
non-serious or minor injury.
4 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
OPERATION | Safety
i
i

1.2 Other symbols

► This triangular symbol is used as a bullet point.
These two arrows represent the symbol for an in-
»
struction. This shows that there is something you must do. The actions required are described step by step.
{{ These symbols show you the level of a software
menu. In this example, three menu levels are indicated.

1.3 Units of measurement

Information
In these documents, unless otherwise specied,
all linear measurements (e.g. in tables and illus­trations) are given in millimetres.
1.4 Specied performance data
The performance data of the appliance indicated in these documents (text, tables and diagrams) have been calcu­lated according to standardised measurement conditions. However, these measurement conditions often do not completely correspond to the plant-specic conditions ap­plicable in the respective user‘s system. System-specic factors that can affect the conditions include, for example,
the specic design of the system, the age of the system and the actual ow rates. For this reason, the stated per- formance data can differ from plant-specic performance
data.

2. Safety

2.1 Intended use

The appliance is intended for use in a domestic environ­ment. It can safely be used by persons who have received no instruction. The appliance can similarly be used in a non-domestic environment such as commercial premises, as long as it is used in the same instructed manner.
Any use of the appliance that is different from or goes beyond this is not regarded as intended use. “Intended use” also includes observing this documentation and the documentation of any accessories used.
Information
Air pressure and air humidity will affect the opera­tional reliability of the electrical components in the heat pump system (dielectric strength). The loca­tion of the heat pump system must be no more than 1000 m above sea level.

2.2 General safety information

Observe the following safety information and instructions for the appliance.
Only qualied contractors should carry out the electri-
cal work and installation of this appliance.
► Commissioning and maintenance of the appliance
may be carried out only by OCHSNER Customer Ser­vice or by customer service partners authorised by OCHSNER.
The stated performance data can be conrmed only if
the measurements taken for the appliance are carried out according to the relevant standardised measurement con­ditions.
► The authorised contractor is responsible for compli-
ance with all relevant regulations during installation and commissioning.
► Operate the appliance only when fully installed and
with all safety equipment tted.
► Protect the appliance from dust and dirt ingress dur-
ing building work. Use the plastic cover provided.
► Alterations to the appliance may be carried out only
by OCHSNER Customer Service or by customer ser­vice partners authorised by OCHSNER.
► Functions to protect the heat pump can be enabled
using the controller. However, since the controller is
not certied as a safety device, safety measures in
case of breakdown or damage to the heat pump (e.g. additional external switching of the safety devices in use) must comply with local regulations. In the case of upgrades or updates to the controller software, all function parameters of the heat pump must be checked.
► Before commencing work on electrical connections
and installation, the heat pump system must be isolat­ed and voltage-free.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 5
OPERATION | Appliance description
13_03_001
2
4
1
3
6
5
WARNING: Injury
The appliance may be used by children aged 8 and up and persons with reduced physical, sensory or mental capabilities or a lack of experience provided that they are supervised or that they have been instructed on how to use the appliance safely and have understood the possible risks. Children must not be allowed to play with the appliance. Children must not be allowed to clean or carry out user maintenance on the appliance without supervision.

3. Appliance description

The appliance is an air/water heat pump consisting of an indoor unit and an outdoor unit. The appliance can be used to heat a building and provide domestic hot water (DHW).

3.1 Functionality

An air/water heat pump extracts thermal energy from the ambient air (low temperature) and transmits it together with electrical drive energy in the form of useful heat (higher temperature) to a heating and/or DHW circuit.
The heat pump consists of separated circuits linked togeth­er via heat exchangers:
► Heat source circuit (extracting heat)
► Refrigerant circuit
► Heat sink circuit (supply of heat to the central heating
and/or DHW)
The operating principle of an air/water heat pump:
1 Evaporator (n heat exchanger) 2 Compressor 3 Condenser (plate heat exchanger) 4 Expansion valve 5 Heat sink (heating, DHW) 6 Air as heat source

3.2 Appliance components

3.2.1 Indoor unit
6 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
The indoor unit is intended to be installed only inside the building. The indoor unit contains the compressor, which in terms of sound technology is acoustically decoupled a number of times from the casing. The casing is acoustically optimised and allows particularly quiet operation.
OPERATION | Appliance description
i
11_02_200_214_01_004
Compressor
The fully hermetically sealed compressor is designed for high efciency heat pump applications. A suitable starting current limiter for the compressor is installed in the indoor unit.
Electric booster heater
The appliance is tted with an electric booster heater
(immersion heater). At low outdoor temperatures, the ap­pliance operates in bivalent-parallel mode. The appliance can also be combined with an additional heat generator.
Condenser
The condenser takes the form of a plate heat exchanger, which is built of stainless steel and insulated on all sides against condensation and heat loss.
3.2.2 Outdoor unit
The outdoor unit is intended to be installed outside. The outdoor unit is designed as a horizontal split evaporator. The indoor unit is connected to the outdoor unit with refrig­erant lines, along with electrical control and power supply cables.
► 1x direct circuit (heating and/or cooling)
► 1x mixed circuit (heating and/or cooling)
► 1x directly heated DHW cylinder (with electric booster
heater)
► 1x heat pump (heating and cooling)
► 1x additional heat generator (electric booster heater
or enable contact for external heat generator)

3.3 Name plate

Two name plates are attached to the indoor unit to identify your heat pump. In addition, a label with the serial number is attached to the right-hand casing panel of the appliance.
1
2
Evaporator
The evaporator is a part of the outdoor unit and consists
of copper pipes in a set of aluminium ns.
Information
With an air/water heat pump, frost may form on
the evaporator ns of the outdoor unit, depending
on the air temperature (below approx. +7°C), air humidity and the operating point. The evaporator
ns are automatically de-iced again in the cyclical
defrosting mode of the heat pump.
Fan
The outdoor air is blown across the evaporator by a quiet fan.
3.2.3 Heat pump control unit
The OCHSNER heat pump controller includes devices for controlling heat pump heating systems with a cooling function as well as DHW heating. In its standard version, the heat pump control unit consists of the OTE controller and the master controller, both of which are installed in the indoor unit.
1 Name plate (back of indoor unit and front of control
box)
2 Serial number (right-hand casing panel)
The OTE controller can control the following system circuits and heat generators:
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 7
OPERATION | Activating settings
i
i

4. Activating settings

Settings are activated with the master controller on the indoor unit (with graphic display or touchscreen), or via a remote controller with touchscreen that is attached to the wall.
5
Mo 09 .01.17 10:02
4
3
2
1 11
1 Button A:
Press to go back one menu step (ESC) 2 Displays function of Button A or fault message 3 Operating status 4 Outdoor temperature 5 Date 6 Time 7 DHW temperature 8 Actual room temperature 9 System temperature 10 Displays function of Button B 11 Button B:
Turn to select from menu or to change setting
Press to conrm (ENTER)
-12.5C 22°C 52.5°C
Heating mode
OCHSNER OTE
The master controller is mounted in an easily accessible plastic cover on the top of the indoor unit. Two buttons are provided for controlling the menu, with an illuminated graphic display.
6
7
32.5°C
MENU
8
9
10
11_01_200_701_01_01_001
Pressing Button B on the right calls up the main menu with a diagram of the heating system. Each heat consum­er (heating circuit, DHW circuit) and each heat generator (heat pump, electric booster heater, boiler etc.) has its own menu and corresponding submenus.
Pressing Button A takes you back one step to the previous menu.
You will nd further information on operating the heat pump
control unit in the control unit‘s operating instructions which are also supplied with the heat pump.
Information
The heat pump has no separate on/off switch. In an emergency, the system must be shut down via
the specied safety devices.
Ensure easy access to the safety devices. It
»
must be possible to perform an emergency shutdown at all times.
8 www.ochsner.com | 982000-AIR-M2-M4-EN03.1

4.1 Operating costs

In the rst two heating seasons, higher running costs are
to be expected (up to 50% more, depending on residual moisture in the building). Enabling the screed drying pro­gram will also increase operating costs further.
4.1.1 Flow temperatures
For optimum operation of your heat pump, you should aim
for the lowest possible heating ow temperatures (and also
DHW temperatures). The maximum system temperature for your heat pump should be restricted to 60°C.
Information
Increasing the room temperature by 1°C results in an increase in consumption of 5-7%.
4.1. 2 Ventilation
Any ventilation should be intermittent, especially during the heating period, and according to your own require-
OPERATION | Maintenance and care
i
i
ments. Intermittent ventilation is considerably more energy
efcient than permanent ventilation, and therefore saves
money. Avoid permanent ventilation.
4.1. 3 Heating setback program
From an energy efciency point of view, using a time pro-
gram to reduce the heating ow temperature is especially
not recommended for air/water heat pumps with low tem-
perature heating systems (such as underoor heating).
These systems are slow to respond and, due to the addi-
tional output from the system required following the end
of the setback phase, it is possible that the second heat
generator (boiler, electric immersion heater) will cut in. This
can lead to higher operating costs.

5. Maintenance and care

We recommend an annual inspection and if necessary
have your heat pump serviced by OCHSNER Customer
Service.
Material damage
Maintenance work on electrical components of the
heat pump may be carried out only by qualied
contractors.
Material damage
Abrasive tools must not be used to clean the evap-
orator ns in the outdoor unit.
Any dirt on the ns should be blown away
»
using compressed air (max. 8 bar), in the di-
rection of normal air ow. If the ns are very dirty, contact your OCHS-
»
NER system partner or OCHSNER Customer Service.
If it is necessary to clean the casing sections of the
»
indoor or outdoor unit, use only a damp cloth (with water or a weak soapy solution). Do not use any abra­sive or aggressive cleaning materials.
During the building phase, protect the indoor and
»
outdoor units from dirt and dust with a suitable cover. Use the plastic cover provided.
Ensure that the heating circuit is lled with sufcient
»
water.
Ensure that any condensation beneath the outdoor
»
unit can drain away without freezing all year round.
Information
If the outdoor unit is covered with a thick layer of snow, this can reduce system efciency.
Remove snow on and around the outdoor unit
»
as necessary. If required, install the snow cover available as
»
an accessory for the outdoor unit.
Information
Ensure that the refrigerant circuit of your heat pump is tested for leaks once a year (in acc. with Regu­lation (EU) no. 517/2014).
Ensure year-round access to soldered joints in
»
the refrigerant circuit. Document the results of the leakage test in the
»
system test report.

6. Problem solving

Problem Cause Solution
Too little DHW is available or the cen­tral heating system is too cold.
The appliance is leaking water.
If you have a problem that you cannot resolve, contact
the system installer, a qualied contractor or OCHSNER
Customer Service.
Faults are displayed as”Er XXX”on the master controller of the OTE control unit. If a fault occurs, contact your system installer. The system installer knows your hydraulic system and how it operates. The causes of faults can often be found in the settings or in the hydraulics.
Before contacting the installer, make a note of the serial number and the heat pump model. The serial number and heat pump model of your appliance are shown on the name plate. The name plates are attached to the back of the appliance on the outside and behind the front appliance casing panel (control box outer side).
Customer service hotline for Austria:
Tel: +43 (0) 504245 - 499 Email: kundendienst@ochsner.at
The power supply to the appliance has been cut off
The drain for the safe­ty valve is blocked.
Check the safety device on the main distributor board for your house. Switch the safety device back on. If the safety device trig­gers again after being switched back on, contact a qualified con­tractor or OCHSNER Customer Service.
Clean the safety valve drain. See „Safety valve drain“ on page 32.
Ensure that the outdoor unit (both the top and the un-
»
derside) is kept free from snow, leaves and twigs and other foreign bodies.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 9
Customer service hotline for Germany:
Tel: +49 (0) 69 256694 - 495 Email: kundendienst@ochsner.de
Customer service hotline for Switzerland:
Tel: +41 (0) 800 100 - 911 Email: kundendienst@ochsner.com
INSTALLATION | Safety
i

INSTALL ATION

7. Safety

Only a qualied contractor should carry out installation,
commissioning, maintenance and repair of the appliance.

7.1 General safety information

We guarantee trouble-free function and operational reliabil­ity only if the original accessories and spare parts intended for the appliance are used.

7. 2 Regulations, codes and standards

Information
Observe all applicable national and regional regu­lations and instructions.

8. Appliance description

8.1 Standard delivery

The standard delivery of your appliance includes the fol­lowing components.
1x indoor unit:
The following components are installed in the indoor unit:
AIR 7 AIR 11 AIR 18
Hydraulic variant M2-1 M2-2 M2-3 M2-4 M4-1 M4-2 M4-3 M4-4
Starting current limiter + + + + + + + +
Flow meter (heat sink side)
Circulation pump (heat sink side)
Internal flexible hose + + + + + + + + Safety valve + + + + + + + + Master control unit + + + + + + + + OTE heat pump con-
troller Diaphragm expansion
vessel 24 l 3-way switching mod-
ule (DHW) Electric booster heater
8.8 kW
+ + + + + + + +
+ + + + + + + +
+ + + + + + + +
+ + + + - - - -
+ + - - + + - -
+ - + - + - + -
AIR 23 AIR 29 AIR 41
1x outdoor unit:
Evaporator, expansion valve, fan
3x connection pipes (45°):
For vertical or horizontal connection to the heating system.
1x outdoor temperature sensor (TA)
1x contact sensor for a mixed circuit (TMK)
2x pocket sensors for a heat pump buffer tank
(TPO, TPM)
1x pocket sensor for a DHW cylinder (TB)
1xfoundationxingkitfortheoutdoorunit
10 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance description
11_02_200_202_01_019

8.2 Hydraulic variants of the indoor unit

The indoor unit is available in eight different hydraulic variants that are illustrated schematically below. Possible
system congurations for the hydraulic versions of the in­door unit are illustrated in „System schematic diagrams“ on page 68.
M2-3
43 521
43 521
M2-2M2-1
7
8
9
6
12
3 521
10
11
7
8
9
6
12
3 521
10
M2-4
7
6
12
1 Suction gas line 2 Liquid line 3 Heating water/DHW return 4 DHW ow 5 Heating water ow 6 Heat generator pump 7 Diaphragm expansion vessel 8 3-way switching module 9 Flow meter 10 Safety valve 11 Electric booster heater 12 Heat exchanger (heat sink side)
11
7
9
6
10
12
9
10
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 11
INSTALLATION | Appliance description
43 521
43 521
M4-2M4-1
6
7
8
9
10
11
21
3 5
6
7
8
9
11
3 521
M4-4M4-3
6
8
9
11
1 Suction gas line 2 Liquid line 3 Heating water/DHW return 4 DHW ow 5 Heating water ow 6 Safety valve 7 3-way switching module 8 Flow meter 9 Heat generator pump 10 Electric booster heater 11 Heat exchanger (heat sink side)
10
6
8
9
11
11_02_200_202_01_020
12 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
11_05_200_214_01_001
i
i

9. Preparing to install the appliance

Before installing the indoor and outdoor units, preparatory
work needs to be carried out by qualied contractors.

9.1 Indoor unit installation location

Material damage
The indoor unit is intended to be installed only in­side the building. It must not be installed in rooms with high levels of humidity (permanently above 70%).
Information
Plan the installation sites for the outdoor and indoor units such that the pipework carrying the refriger­ant is as short, straight and simple as possible.
B
A ≥ 1000 mm B ≥ 500 mm C ≥ 500 mm D ≥ 50 mm E ≥ 500 mm
D
E
C
A
The installation location for the indoor unit must meet the following requirements:
► A dry and frost-free room
► Sound optimised environment
A horizontal, adequate load bearing oor (for weight
of indoor unit, see „Specication“ on page 50)
► Not situated directly below or above bedrooms
► Max. room temperature 30°C
► The installation room must not be subject to a risk of
explosions arising from dust, gases or vapours.
9.1.1 Keep minimum clearances
Observing the specied minimum clearances for the indoor
unit ensures:
► Correct installation of the appliance
► Fault-free operation
► Ability to carry out maintenance on the appliance.

9.2 Outdoor unit installation location

Information
Plan the installation sites for the outdoor and indoor units such that the pipework carrying the refriger­ant is as short, straight and simple as possible.
Information
When laying refrigerant lines in the ground, sched­ule the work so that the pipe liner can be laid together with the already inserted refrigerant lines in the trench between the outdoor and indoor units.
- If the pipe liner is laid empty, inserting the re-
frigerant lines afterwards will be difcult if not
impossible.
The outdoor unit is intended to be installed only out of doors. Please note the following with regard to the instal­lation location of the outdoor unit:
► Select the outdoor unit installation location such that
the appliance is safely accessible from all sides all year round.
► Avoid installing it in a hollow or ditch (a “pool” of cold
air).
► An optional snow cover is available to protect the
outdoor unit fan in case of heavy snowfall. Where necessary, ensure that a snow cover is installed (according to installation site and local weather conditions).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 13
INSTALLATION | Preparing to install the appliance
i
i
Material damage
The air ow through the evaporator must not be
obstructed by surrounding buildings. A reduced air
ow rate can lead to loss of efciency in the system.
Please note the following with regard to installation in coastal areas:
► The standard design of outdoor unit must be installed
at least 1 km from the sea.
► Outdoor units with special coating, suitable for coast-
al locations, must be installed at least 200 m from the sea.
► The installation location selected should always be on
the leeward side of the building (the side facing away from the sea).
Please note the following with regard to sound emissions from the outdoor unit:
Avoid installing on reverberant ooring.
► Avoid installing between building walls. The walls can
increase the noise level.
► Avoid installing next to bedrooms.
Information
Plants and cultivated areas around the outdoor unit, subject to minimum clearances, can reduce the noise level of the outdoor unit.
11_05_200_504_002
C
A ≥ 3000 mm (minimum clearance to roof) B ≥ 1000 mm (minimum clearance to a wall) C 100 mm or ≥ 1000 mm (minimum longitudinal clear-
ance to a wall)
Information
The minimum clearance between two outdoor units (e.g. connected in cascade) is 1000 mm on all sides.

9.3 Foundations for the outdoor unit

A
B
11_05_200_504_001
9.2.1 Keep minimum clearances
Observing the specied minimum clearances for the out­door unit ensures:
► Correct installation of the appliance
► Fault-free operation
► Ability to carry out maintenance on the appliance.
It is permissible to install the outdoor unit under a roof if the space around the unit is permanently open on three sides.
14 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
A permanent foundation is required beneath the outdoor unit. The foundations must meet the structural require-
ments of the outdoor unit (see Specication).
Provide for frost-free drainage (e.g. a gravel bed con-
»
nected to a drain) for condensation that forms on the outdoor unit.
Where refrigerant lines are to be laid in the ground,
»
ensure correct positioning of the pipe liner when lay­ing the foundations.
Use underground waste pipes (with a smooth inner
»
surface) for the pipe liner.
INSTALL ATION | Preparing to install the appliance
i
11_04_200_504_003
11_04_200_504_004
Ensure that the outdoor unit is adequately secured,
»
paying regard to the wind load occurring at the instal­lation location.
CAUTION: Risk of slipping
If drainage for condensation is inadequate, ice can build up in winter in the area around the outdoor unit.
Ensure drainage for condensation is sufcient
»
even at low temperatures.
Information
Insulation used beneath the soil must be made of a closed-cell material. Otherwise, the thermal in­sulation of the material will be impaired.
100
900
Dig out the foundation trench.
»
Place in position four underground waste pipes
»
(Ø ≥ 250 mm).
≥ 800
9.3.1 Laying spot foundations
900
4
Ø250
3
2
C
1
1 Pipe liner for the connecting lines (where installed
underground) 2 Gravel bed 3 Drainage pipe (frostproof) 4 Spot foundation (with underground waste pipe)
B
A
Ensure correct horizontal and vertical positioning of
»
the underground waste pipes.
Place a drainage pipe along the base of the trench.
»
≥ 1800
1
2
3
1 Underground waste pipe 2 Pipe liner for underground connecting lines 3 Drainage pipe (frostproof) 4 Gravel bed
In the case of underground connecting lines, allow for
»
the pipe liner.
11_04_200_504_001
Fill the foundation trench with coarse gravel. If the
»
pipe liner (with refrigerant lines) is to be installed at a later point, in the case of underground connec­tion lines, this must be allowed for in the foundation trench.
4
Fill the underground waste pipes with concrete.
A B C AIR 7 1110 270 ≥ Ø160 AIR 11 1110 270 ≥ Ø160 AIR 18 1110 270 ≥ Ø160 AIR 23 2040 300 ≥ Ø200 AIR 29 2040 300 ≥ Ø200 AIR 41 2040 330 ≥ Ø250
Use underground waste pipes when installing spot foun­dations. When installing spot foundations, we recommend the following approach:
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 15
»
INSTALLATION | Preparing to install the appliance
i
9.3.2 Laying strip foundations
4
3
2
A
C
150
200
1 Pipe liner for the connecting lines (where installed
underground) 2 Gravel bed 3 Drainage pipe (frostproof) 4 Strip foundations
AIR 7 1400 300 ≥ Ø160 AIR 11 1400 300 ≥ Ø160 AIR 18 1400 300 ≥ Ø160 AIR 23 2250 320 ≥ Ø200 AIR 29 2250 320 ≥ Ø200 AIR 41 2250 350 ≥ Ø250
When laying strip foundations we recommend the following approach:
1
1100
A B C
≥ 1600
B
1
2
3
1 Reinforced strip foundation 2 Pipe liner for underground connecting lines 3 Drainage pipe (frostproof) 4 Gravel bed
In the case of underground connecting lines, allow for
»
the pipe liner.
Fill the foundation trench with coarse gravel. If the
»
pipe liner (with refrigerant lines) is to be installed at a later point, in the case of underground connec­tion lines, this must be allowed for in the foundation
11_04_200_504_002
trench.
Construct the two reinforced strip foundations.
»
9.3.3 Installing on at roofs
WARNING: Risk of falling
Working on a at roof without fall protection con­stitutes a risk.
When working on a at roof, observe the laws
»
relating to occupational safety in your region. Always be aware of the open edge.
»
Information
Avoid installing the outdoor unit on the roof above residential buildings or on car ports attached to res­idential buildings, due to the risk of structure-borne noise transmission.
Loads and stresses on roof structure
≥ 300
4
11_04_200_504_006
Note that when outside temperatures are very low,
»
ice can form beneath the outdoor unit.
≥ 800
11_04_200_504_005
Dig out the foundation trench.
»
Place a drainage pipe along the base of the trench.
»
16 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
In terms of roof structure loads, allow for an ice load
»
of 400 kg/m² in addition to the dead weight of the
outdoor unit.
INSTALL ATION | Preparing to install the appliance
i
3
2
1
1 Flat roof
2 Refrigerant lines in open air (enclosed in thermal in-
sulation with UV protection)
3 2x concrete slabs attached with exible adhesive (per
leg of the outdoor unit). The outdoor unit is afxed to
the concrete slabs
4 Anti-vibration mounts
When installing the outdoor unit on a freestanding car port,
a garage roof or a storage space roof, please note the
following:
Ensure that the outdoor unit is adequately secured,
»
paying regard to the wind load occurring at the instal­lation location.
Take account of the concentrated load arising from
»
the dead weight of the outdoor unit (including the
roof xings) and the surface load caused by possible
build-up of ice.
Ensure suitable structure-borne sound separation be-
»
tween the outdoor unit and the installation points on the roof.
4

9.4 Preparing the refrigerant lines

Information
If the appliance, the refrigerant lines, the pipe x­ings and the wall outlets are not installed correctly, structure-borne sounds can be transmitted to the building.
Ensure that the refrigerant lines are in-
»
11_06_200_202_006
stalled in a way that ensures insulation from structure-borne noise. The system installer carrying out the work is responsible for this.
Material damage
Use only copper pipes suitable for refrigerant (D IN 12735-1). Thin-walled pipes run the risk of bursting.
Please observe the stipulated diameters and
»
wall thicknesses of the copper pipes.
Material damage
Incorrect or premature opening of the pipe connec­tions and cutting of the refrigerant lines can allow dirt and moisture to enter the refrigerant circuit.
Do not open the connections on the indoor
»
or outdoor units until just before installing the refrigerant lines. Cut the refrigerant lines with a suitable pipe
»
cutte r. Prevent swarf from contaminating the pipe
»
connections and refrigerant lines. Once cut, ll the refrigerant lines with a sub-
»
stance such as nitrogen. Keep the refrigerant lines closed until just be-
»
fore installation.
Pipe connections for the refrigerant lines (suction gas and liquid lines) are supplied soldered closed, both for the in­door unit and the outdoor unit. Appropriate copper pipes for refrigerant lines are supplied sealed at both ends and
lled with nitrogen.
Please note the following with regard to routing of the re­frigerant lines:
Keep to a minimum the distance between the indoor
»
and outdoor units, in order to minimise heat loss from the refrigerant lines.
Select the installation sites for the indoor and outdoor
»
units such that the maximum permissible line lengths and height differentials are not exceeded.
Avoid routing the lines in the vicinity of bedrooms.
»
The refrigerant in the lines can generate noise under certain operational conditions.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 17
INSTALLATION | Preparing to install the appliance
i
9.4.1 Line lengths
Observe the maximum permissible line lengths for
»
the refrigerant lines.
Where the outdoor unit is positioned higher than the
»
indoor unit, observe the maximum permissible height
differential between the two units.
C
B
A
Where a line routed along the ceiling is used in
»
conjunction with an underground connection line, observe the maximum permissible height differential between the highest and lowest points of the refriger­ant lines.
1223
D
11_06_200_202_001
≤ 3500
11_06_200_202_002
A + B + C
(sum of line lengths) AIR 7 ≤ 20 m ≤ 10 m AIR 11 ≤ 20 m ≤ 10 m
AIR 18 ≤ 20 m ≤ 10 m AIR 23 ≤ 20 m ≤ 10 m AIR 29 ≤ 20 m ≤ 10 m AIR 41 ≤ 16 m ≤ 5 m
Where the outdoor unit is positioned lower than the
»
indoor unit, observe the maximum permissible height differential between the highest and lowest points of the refrigerant lines.
1180
(max. height differential)
≤ 3500
D
9.4.2 Pipe diameter
The pipe diameter data for refrigerant lines shown below applies as long as the following are observed:
► A maximum of eight 90° pipe bends
► With pipe diameters of < 35 mm, use a suitable pipe
bending tool to create the pipe bends
With pipe diameters of ≥ 35 mm, use type 5002 pipe
bends
Bending radii of ≥ 1 m are treated as straight runs
Information
Refrigerant lines with a pipe diameter of ≥ 35 mm
are created from rigid copper pipes in 5 m lengths.
With underground refrigerant lines, provide an
»
assembly shaft at connection sites to facilitate soldering and maintenance work.
≤ 2970
18 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
650
11_06_200_202_003
INSTALL ATION | Preparing to install the appliance
Pipe diameter of the refrigerant line
Refrigerant line up to 6 m Refrigerant line up to 8 m
Liquid line Suction gas
line AIR 7 10 18 10 18 AIR 11 12 18 12 18 AIR 18 12 22 12 22 AIR 23 12 22 16 2x22 AIR 29 16 2x22 16 2x22 AIR 41 16 42 16 42 AIR 41 16 4x22 16 4x22
Pipe diameter of the refrigerant line
Refrigerant line up to 10 m
Liquid line Suction gas
line AIR 7 10 18 10 18 AIR 11 12 22 12 22 AIR 18 12 22 12 2 x18 AIR 23 16 2x22 16 2x22 AIR 29 16 2x22 16 2x22 AIR 41 16 42 16 42 AIR 41 16 4x22 16 4x22
Pipe diameter of the refrigerant line
Refrigerant line up to 14 m
Liquid line Suction gas
line AIR 7 10 18 10 18 AIR 11 12 22 12 22 AIR 18 12 2 x18 12 2x22 AIR 23 16 2x22 16 2x22 AIR 29 16 2x22 16 35 AIR 29 16 2x22 16 3x22 AIR 41 16 42 16 42 AIR 41 16 4x22 16 4x22
Liquid line Suction gas
line
Refrigerant line up to 12 m
Liquid line Suction gas
line
Refrigerant line up to 16 m
Liquid line Suction gas
line
9.4.3 Preparing the wall outlets
Whether the refrigerant lines between the indoor and outdoor units are to be routed above or below ground, ap-
propriate and plant-specic wall outlets need to be created
through the outer wall of the building.
Ensure that the wall outlets are constructed in an ap-
»
propriate, plant-specic manner.
Take the construction of the wall (tiles, concrete) into
»
account.
Take the prevailing groundwater situation into
»
account.
Material damage
Incorrectly created wall outlets can cause signi­cant damage to property, due to water (seepage, condensation, floodwater) penetrating into the building or stonework. Where the wall outlets are created below ground level, the breach must be appropriate to local conditions at the site (e.g. non-accumulating or accumulating seepage water, groundwater under pressure).
Use a suitable pipe liner or wall sleeve for the
»
wall outlet. Tie the external end of the wall outlet in to the
»
external waterproof seal of the building. Ensure that the pipe liner is arranged with a
»
slight fall (at least 2%) to the outside. On both the outside and inside edge of the
»
wall, use appropriate ring seals to seal the space between the wall sleeve and the re­frigerant lines and electrical cables passing through.
Material damage
PU foam is not suitable as a sealant for the pipe li ner.
Pipe diameter of the refrigerant line
Refrigerant line up to 18 m
Liquid line Suction gas
line AIR 7 10 18 10 18 AIR 11 12 22 12 22 AIR 18 12 2x22 12 2x22 AIR 23 16 2x22 16 2x22 AIR 29 16 35 16 35 AIR 29 16 3x22 16 3x22
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 19
Refrigerant line up to 20 m
Liquid line Suction gas
line
INSTALLATION | Preparing to install the appliance
i
i
i
i
9.4.4 Preparing refrigerant lines passing through open air
3
2
1
6
1 Appropriately sealed wall outlet (particularly where
there is a risk of ooding)
2 Appropriate sealing of the refrigerant lines as they
pass through the wall outlet
3 Refrigerant lines in open air (enclosed in thermal in-
sulation with UV protection) 4 Reinforced strip foundation 5 Drainage pipe (frostproof) 6 Foundation
Information
All solder sites on the copper pipework of the re­frigerant line must be accessible all year round for maintenance purposes (in accordance with Regu­lation (EU) no. 517/2014).
Run the refrigerant lines between the indoor and out-
»
door units.
4
5
9.4.5 Preparing underground refrigerant lines
5
3
2
1
10
11_06_200_202_005
1 Appropriately sealed wall outlet 2 Appropriate sealing of the refrigerant lines as they
pass through the pipe liner 3 Insulation 4 Gravel 5 Reinforced strip foundation 6 Appropriate sealing at the end of the pipe liner (be-
tween refrigerant lines and pipe liner) 7 Drainage pipe (frostproof) 8 Pipe liner (with min. 2% fall to outside) 9 Drain 10 Foundation
Information
All solder sites on the copper pipework of the re­frigerant line must be accessible all year round for maintenance purposes (in accordance with Regu­lation (EU) no. 517/2014).
4
~ 600
8
7
9
6
11_06_200_202_004
Allow some surplus length in the refrigerant lines
»
between the connections at the indoor and outdoor units.
Ensure that the wall outlets are sealed in an appropri-
»
ate, plant-specic manner.
Use suitable sound-insulating pipe xings to secure
»
the refrigerant lines.
Insulate the refrigerant lines with suitable insulating
»
material where they pass through open air between the indoor and outdoor units, to prevent formation of condensation. When passing through open air outside, the insulating material must also have UV protection.
Information
Where the refrigerant lines run horizontally through open air, use suitable supports. Take steps to pre­vent open refrigerant lines from being walked or driven on.
Information
When laying refrigerant lines in the ground, sched­ule the work so that the pipe liner can be laid together with the already inserted refrigerant lines in the trench between the outdoor and indoor units.
- If the pipe liner is laid empty, inserting the re-
frigerant lines afterwards will be difcult if not
impossible.
20 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
1
Ensure that the wall outlets are appropriate and
»
plant-specic, and that the pipe liner is appropriately
sealed.
Ensure that the open end of the pipe liner at the
»
outdoor unit is properly sealed. For sealing the re­frigerant lines in the pipe liner, use for example an appropriate ring seal or a UV-resistant, permanently
exible sealing compound.
Any exposed refrigerant lines outside the pipe liner
»
must also be protected from a build-up of condensa­tion with appropriate insulating material. Out of doors, the insulating material must also have UV protection.
Information
Insulation used beneath the soil must be made of a closed-cell material. Otherwise, the thermal in­sulation of the material will be impaired.
2
1 Where the pipe liner has two 90° bends, it must be
laid together with the refrigerant lines.
2 If the pipe liner is laid empty, it will not be possible to
insert the refrigerant lines afterwards.
For the underground pipe liner, use rigid waste pipes.
»
Use a pipe liner of a suitable diameter for the sys-
»
tem-specic refrigerant lines and the planned pipe
bends (see „Foundations for the outdoor unit“ on page 14).
For 90° bends in the pipes, use either 3x 30° bends
»
or 6x 15° bends (depending on the diameter of the pipe liner and the depth at which it is laid).
At the point where the refrigerant lines are connected
»
to the outdoor unit, create a suitable trench.
11_06_200_202_007
Material damage
PU foam is not suitable as a sealant for the pipe li ner.
Dig a straight trench between the wall outlet and the
»
trench at the outdoor unit.
Lay the pipe liner, with the refrigerant lines already
»
inserted, into the trench between the outdoor and in­door units.
Lay the electrical control leads and power supply
»
cables in a suitable electrical conduit. The optional OCHSNER cable harness is suitable for laying direct into the ground.
Allow some surplus length in the refrigerant lines
»
between the connections at the indoor and outdoor units.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 21
INSTALLATION | Preparing to install the appliance
i
i
i

9.5 Preparing the electrical connections

WARNING: Electrocution
All electrical connection and installation work must be carried out according to the applicable national and regional regulations.
WARNING: Electrocution
Before commencing work on electrical connections and installation, the heat pump system must be isolated and voltage-free.
WARNING: Electrocution
Work on electrical connections and installation may
be conducted only by qualied contractors.
Material damage
This appliance contains frequency converters (e.g. EC circulation pumps, EC fan motors). Leakage currents may arise in normal operation. In the event of faults, these components may cause DC fault currents. An incorrectly selected RCD may trip dur­ing normal operation or, in the event of a fault, may not trip at all or only trip after a delay.
Make sure that the power supply for this
»
appliance is separate from the domestic in­stallation. If local conditions require the installation of an
»
RCD, use type B AC/DC-sensitive RCDs.
► For the integral electric booster heater (8.8 kW), a
suitable high limit safety cut-out (HLSC) is installed in
the indoor unit.
Information
The main power circuit for the compressor has no upstream power contactor on the machine side. Control devices and equipment to discon­nect and shut down all supply voltages across all poles, which must be provided on the system side, must meet the technical safety requirements of EN 60204-1 sections 5 and 13.4.5, as well as the international regulations in the IEC 60947 series.
Material damage
Protect the main power circuit (compressor), the control circuit (control unit) and the electric booster heater separately from one another.
9.5.1 Heat pumps for three-phase alternating current
1
3 4 5 6
2
C13A B16A
Information
It is essential that the regulations of the responsible power supply utility (PSU) and the applicable EN standards be observed.
Information
The values specied in this documentation for
circuit protectors and cable cross-sections are standard values. The contractor carrying out the work is responsible for plant-specic sizing of safe­ty equipment and cable cross-sections.
► For the electrical connection, use the system principle
schematic appropriate to your heat pump system from section „System schematic diagrams“ on page 68.
► The outdoor unit takes its power supply from the in-
door unit. The supply cable for the fan in the outdoor unit is protected by an internal C10A circuit breaker in the indoor unit.
► In the case of a fault, the protection on the main pow-
er circuit (compressor) and electric booster heater must break the circuit across all poles.
3 x 400 VAC 1 x 230 VAC 3 x 400 VAC
1 Heat pump indoor unit control box 2 Main system distributor board 3 Supply to main power circuit (compressor) 4 PSU signal contact 5 Supply to control circuit (OTE controller) 6 Supply to electric booster heater
Description Typ e Max.
Main power cir­cuit (compressor and fan)
Electric booster heater
Control circuit (control unit)
AIR 7 C11A 13.5 5.4 C10A AIR 11 C 11A 20.0 7.9 C10A AIR 18 C11A 32.0 11. 4 C16A
AIR 23 C12A 50.5 16.8 C20A AIR 29 C12A 49.5 21.1 C25A AIR 41 C12A 63.5 24.8 C25A
AIR 7 C11A
AIR 41 C12A
AIR 7 C11A
AIR 41 C12A
starting current [A]
Max. op­erating current [A]
14 B16A
6 C13A
11_02_200_202_01_010
Fuse
► All power supply cables must be protected against
surges and short circuits.
22 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Preparing to install the appliance
i
i
Material damage
Operating a three-phase motor (compressor, pumps, fans) for long periods using an incorrectly phased three-phase supply will damage the motor.
Ensure that all three-phase motors are
»
connected to a three-phase supply with a clockwise rotating eld.
9.5.2 Heat pumps for single phase alternating current
1
3 4 5 6
2
C13A B16A
1 x 230 VAC 1 x 230 VAC 3 x 230 VAC
1 Heat pump indoor unit control box 2 Main system distributor board 3 Supply to main power circuit (compressor) 4 PSU signal contact 5 Supply to control circuit (OTE controller) 6 Supply to electric booster heater
Description Typ e Max.
Main power cir­cuit (compressor and fan) Electric booster heater
Control circuit (control unit)
AIR 11 C 11B 48.5 20.8 C25A
AIR 18 C11B 80.0 30.0 C40A
AIR 11 C 11B 12.8 B16A AIR 18 C11B AIR 11 C 11B 6 C13A AIR 18 C11B
starting current [A]
Max. op­erating current [A]
Fuse
9.5.3 Cables from main distributor to indoor unit
Description Wires Min. cable
Supply to electric booster heater
(8.8 kW electric immersion heater)
Control circuit supply 1x 2 30 VAC
Supply to pumps and ser­vomotors Sensor leads (system temperature sen­sors) Bus leads (eBus connections from OTE controller to remote controllers or auxiliary modules and in cascades)
3x 400 VAC (L1/L2/L3/N/PE) or 3x 230 VAC (L/L/L/N/PE)
(L/N/PE) 1x 23 0 VAC (L/N/PE) 2x (shielding recommend­ed) Example: Y(ST)Y 2x2x0.8 (shielded cable design and twisted cable pairs)
9.5.4 Cables from indoor to outdoor unit
Description Wires Min. cable
11_02_200_202_01_024
Fan power supply 1x 23 0 VAC
Fan alarm (TK) 2x 230 VAC 1.5 mm² Fan speed (0-10 VDC)
Defrost sensor (TQE, TQA) 4x
Pulse lead (for stepper motor on elec­tronic expansion valve)
Suction gas sensor S2
(for expansion valve control­ler)
(L/N/PE)
2x (shielding recom­mended)
(shielding recom­mended) 4x (shielding recom­mended)
Example: ÖLFLEX® CLASSIC 100 CY
2x (shielding recom­mended)
9.5.5 Temperature sensor
cross-sec­tion
2.5 mm²
1.5 mm²
1.0 mm²
1.0 mm²
0.8 mm²
cross-sec­tion
1.5 mm²
1 mm²
1 mm²
0.8 mm²
1 mm²
Information
The maximum line length for sensor leads is 50 m.
Information
Sensor leads must be routed separately from 230 V and 400 V cables. If a minimum distance of 20 cm cannot be maintained, then shielded cables should be used. The shielding should be connected to the earth rail of the heat pump.
Defrost sensors (TQA, TQE):
The two defrost sensors are factory-installed in the evap­orator on the outdoor unit.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 23
INSTALLATION | Preparing to install the appliance
i
i
Outdoor temperature sensor (TA):
nected directly to the OTE controller (1x 230 VAC power supply).
Fit the outdoor temperature sensor at a height of ap-
»
prox. 2.5 m to the outside wall of the building (on the north-west side). Make sure that the outdoor temper­ature sensor is not exposed to direct sunlight or wind, as this will impair the control characteristics.
Information
Avoid tting the outside temperature sensor to the casing of the outdoor unit or in the air ow from
the outdoor unit.
Buffer sensor (TPO, TPM):
In heat pump buffer tank, two buffer sensors are required. The heat pump is switched on on the basis of readings from the TPO and switched off on the basis of those from the TPM.
Install a sensor pocket in the female socket provided
»
for the upper buffer sensor (TPO)
Install a sensor pocket in the female socket provided
»
for the lower buffer sensor (TPM)
DHW sensor (TB):
Material damage
A test run of the pumps and servomotors may be conducted only on a system that has been pre­pared for commissioning. The hydraulics must be fully connected.
9.5.7 PSU signal contact
Tariff switching on the heat pump system
In the case of tariff switching (with interrupted power deliv­ery), the heat pump is temporarily shut down by the power supply utility (PSU).
Uninterrupted tariff
In the case of tariff switching with uninterrupted power delivery, the heat pump is temporarily shut down by the power supply utility. A PSU signal contact is provided for this purpose on the indoor unit. To activate the function, remove a cable bridge in the control box and connect the PSU signal contact cable (see „Electrical connection of the indoor unit“ on page 34).
OCHSNER DHW cylinders are tted with appropriate fe­male sockets for installing the sensor.
Install the DHW sensor in the top one-third of the
»
DHW cylinder (or at the very least in the top half). The lower the selected position of the DHW sensor, the larger the switching hysteresis (5-15 K) will need to be.
Information
Ensure that the DHW sensor is correctly positioned and extends beyond the cylinder insulation into the interior of the DHW cylinder. This is the only way in which the temperature can be captured correctly.
Mixer sensor (TMK):
If, in addition to a direct heating circuit, your system also has a heating circuit with mixing valve, then a mixer sensor must be installed. The mixer sensor is supplied with the heat pump, as a contact sensor including band clamp and heat conducting paste.
Install the mixer sensor immediately downstream
»
of heating circuit circulation pump 2 for the heating circuit with mixing valve, on a (metal) pipe made of a good heat-conducting material.
Shutdown by means of a tariff contactor
In the case of shutdown by means of a tariff contactor in­stalled on behalf of the customer (sealed by the PSU), the power supply to the heat pump compressor is disconnect­ed. Here, it is essential to connect an auxiliary contact to the tariff contactor (N/C contact) of the PSU signal contact on the indoor unit.
Night tariff
Where tariff switching takes place within the meter (night tariff), the PSU signal contact is not connected.
9.5.8 Smart Grid
For the Smart Grid function, special descriptions are avail­able on request from your OCHSNER Customer Service department.
9.5.6 Pumps and servomotors (230 VAC)
Pumps (heating circuit pumps, DHW charging pump) and servomotors (switching module, mixing valve) are con-
24 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance installation
i
i
11_02_200_214_01_005
11_02_200_214_01_001
10. Appliance installation
10.1 Installation of indoor unit
10 .1.1 Delivery and transportation
The appliance is delivered on a one-way pallet, wrapped in lm. The appliance casing is assembled on delivery.
Information
Should you notice any transportation damage to the appliance, you must report such damaged im­mediately when the delivery is unloaded. Claims for transportation damage cannot be made sub­sequently.
Material damage
Protect the appliance from damage by using
»
transport belts. When transporting, protect the appliance from
»
impact.
► The appliance is secured to the one-way (recyclable)
pallet of the transport packaging with screws.
► The transport packaging or one-way pallet is suitable
for transportation using a forklift truck.
► For level transportation to the installation location, the
appliance may remain in the transport packaging.
► Leave the appliance in the transport packaging or on
the one-way pallet for lifting and moving by crane or forklift.
► The standard packaging of the appliance does not
provide protection against the weather or sea water.
► The appliance may be stored and transported only at
temperatures of between -20°C and +45°C.
► The appliance must be stored in its transport
packaging.
Information
If the route to the installation location is difcult,
the transport packaging should be removed and the appliance casing disassembled.
Please note the following when removing the transport packaging:
Remove the transport packaging.
»
Undo and remove the eight woodscrews on the two
»
transport xing brackets (left and right) securing the
appliance to the one-way pallet.
Use the pre-installed transport aids (2 lifting slings at
»
the front and 2 lifting handles at the rear) to lift and transport the appliance.
Transport the appliance in an upright position. Over
»
short distances, you may transport the appliance carefully at an angle of up to 30°.
Material damage
Note the following points when carrying the appli­ance with the pre-installed transport aids:
- When lifting and carrying the appliance, make sure that all 4 transport aids are pulled evenly and at the same time.
- Ensure that the appliance casing is not dam­aged during transport.
- The transport aids are not suitable for lifting by crane.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 25
INSTALLATION | Appliance installation
i
Material damage
When being transported with the appliance cas­ing disassembled, sensitive components will be exposed.
Take care transporting the appliance.
»
10 .1.2 Positioning the appliance
After the appliance has been placed in position,
»
remove the two lifting slings at the front of the appliance.
Undo and remove the two mounting bolts and remove
»
the two lifting slings.
Then screw the two mounting bolts back into the ap-
»
pliance frame.
10 .1.3 Disassembling the appliance casing
11_02_200_214_01_002
Position the appliance at the intended installation
»
location.
Use the pre-installed transport aids (2 lifting slings at
»
the front and 2 lifting handles at the rear) to slide and tilt the appliance.
Observe minimum clearances.
»
Ensure the appliance is horizontal. To compen-
»
sate for minor unevenness in the oor, use the four
height-adjusting plastic glides on the underside of the appliance.
Information
On the underside of the indoor unit, there are four plastic glides with rubber mounted threaded pins (without nuts). Discrepancies in oor height of up to 6 mm can be compensated for.
1
2 3
Undo and remove the four knurled screws for the ap-
»
pliance casing panel at the rear of the appliance.
Undo and remove the two xing screws for the control
»
box cover, on the rear of the appliance.
11_02_200_214_01_006
Slide back the control box cover. Lift the control box
»
cover up and away.
11_02_200_214_01_003
1 Lifting sling 2 Mounting bolt 3 Appliance frame
26 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_02_200_214_01_007
INSTALL ATION | Appliance installation
11_02_200_214_01_012
Undo and remove the two xing screws for the left-
»
hand appliance casing panel, inside the control box.
Lift the left-hand appliance casing panel up and away.
»
Material damage
When the appliance casing has been disassem­bled, sensitive components are fully exposed.
Assemble the appliance casing as soon as
»
there is nothing that needs doing inside the appliance. During the building phase, provide the appli-
»
ance with additional protection from dirt and dust with a suitable covering.
10 .1.4 Assembling the appliance casing
11_02_200_214_01_008
Undo and remove the three xing screws for the front
»
appliance panel, inside the control box.
Lift the front appliance casing panel up and away.
»
Undo and remove the two xing screws for the right-
»
hand appliance casing panel, inside the control box.
Lift the right-hand appliance casing panel up and
»
away.
11_02_200_214_01_009
Slide the left-hand and front appliance casing panels
»
down from the top along the frame of the appliance, until the panels click into place at the bottom.
Ensure that both panels are fully engaged at the ve
»
positions along the bottom.
Secure both of these appliance casing panels with
»
screws at the xing points provided, inside the control
box.
11_02_200_214_01_010
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 27
INSTALLATION | Appliance installation
i
Slide the right-hand appliance casing panel down
»
from the top along the frame of the appliance, until the panel clicks into place at the bottom.
10.2 Installing the outdoor unit
10 . 2 .1 Delivery and transportation
The appliance is delivered on a one-way pallet, wrapped in lm. The appliance casing is assembled on delivery.
Information
Should you notice any transportation damage to the appliance, you must report such damaged im­mediately when the delivery is unloaded. Claims for transportation damage cannot be made sub­sequently.
Material damage
Protect the appliance from damage by using
»
transport belts. When transporting, protect the appliance from
»
impact.
11_02_200_214_01_011
► The appliance is secured to the one-way (recyclable)
pallet of the transport packaging with screws.
► The transport packaging or one-way pallet is suitable
for transportation using a forklift truck.
Ensure that the panel is fully engaged at the three
»
points along the bottom.
Secure the appliance casing with screws at the xing
»
points provided, inside the control box.
Secure the appliance casing with screws at the rear
»
of the indoor unit.
► For level transportation to the installation location, the
appliance may remain in the transport packaging.
► Leave the appliance in the transport packaging or on
the one-way pallet for lifting and moving by crane or forklift.
► The standard packaging of the appliance does not
provide protection against the weather or sea water.
► The appliance may be stored and transported only at
temperatures of between -20°C and +45°C.
► The appliance must be stored in its transport
packaging.
Please note the following when removing the transport packaging:
11_02_200_214_01_006
Remove the transport packaging.
»
28 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_02_200_504_01_007
INSTALL ATION | Appliance installation
11_02_200_504_01_006
i
Undo and remove the four woodscrews securing the
»
appliance to the one-way pallet.
10.2.2 Positioning the appliance
Position the appliance on the prepared foundations.
»
Secure the four legs of the outdoor unit on the foun-
»
dations, using four xing screws.
10.2.3 Disassembling the appliance casing
By removing the side casing panels on the outdoor unit, you can gain access to the connection points for the re­frigerant lines and to the terminal boxes for the electrical control leads and power supply cables.
Undo and remove the two xing screws on the
»
underside.
Pull the side appliance casing panel down and away.
»
1
2
1 Round stainless steel plate 2 Mounting foot with threaded pin (4 pce, M5)
Attach the four mounting feet of the snow cover to the
»
outdoor unit, by screwing the threaded pins into the four free screw holes in the ring-shaped casing part.
Attach the round stainless steel plate of the snow
»
cover to the four positioning feet (M5x12 mm, stain­less steel).
10.2.4 Installing the snow cover
The snow cover for an outdoor unit fan can be retrotted.
10.2.5 Fitting the cylindrical silencer
Information
The Super Silent Paket (SSP) exclusively available ex works for a VHS-M outdoor unit reduces noise by up to 3 dB. The Super Silent Paket consists of:
11_02_200_504_01_009
The cylindrical silencer from the super silent package (SSP) can be retrotted. A retrotted cylindrical silencer alone will reduce noise by about 1.5 dB.
11_02_200_504_01_005
- One cylindrical silencer per fan
- Reinforced casing insulation
- Shielded refrigeration technology
Undo and remove four of the eight xing screws on
»
the ring-shaped casing part for the fan (M5x12 mm, stainless steel).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 29
INSTALLATION | Appliance installation
1
10.2.6 Installing the SSP snow cover
The SSP snow cover can be retrotted to an existing cy- lindrical silencer on the outdoor unit.
Secure the four mounting feet to the round stainless
»
steel plate with screws (M5x12, 8 pcs).
Screw the safety bolt (M6x12, 1 pce) for the sound
»
absorbing mat into the centre of the stainless steel plate.
1 Casing section for the fan
Undo and remove the eight xing screws (M5x12 mm,
»
stainless steel) on the ring-shaped casing part of the fan.
Remove the ring-shaped casing part.
»
4
3
11_02_200_504_01_003
1 Round stainless steel plate with attached sound ab-
sorbing mat 2 Mounting foot with threaded rivet (4 pcs) 3 Safety bolt (M6x12, 1 pce) with washer and retaining
nut 4 Fixing screw (M5x12, 8 pcs) with plastic washer
Position the SSP snow cover on the upper edge of
»
the cylindrical silencer.
Ensure that the SSP snow cover is correctly aligned.
»
The cylindrical silencer has just one predrilled screw
hole for each mounting foot.
1
2
11_02_200_504_01_008
First, secure the four mounting feet of the SSP
»
snow cover to the cylindrical silencer, using the four
1
11_02_200_504_01_002
1 Cylindrical silencer
Position the cylindrical silencer over the fan. Ensure
»
that the assembly holes are correctly aligned.
Attach the cylindrical silencer to the casing panel of
»
the outdoor unit, using the eight xing screws (M5x12, stainless steel).
30 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
pre-drilled holes. Use self-tapping xing screws
(4.8x19 mm, stainless steel).
Secure the SSP snow cover through the remaining
»
four screw holes in the mounting feet that do not have
pre-drilled receiving holes. Use self-tapping xing
screws (4.8x19 mm, stainless steel).
INSTALL ATION | Appliance installation
i
i
i
i
11_02_200_202_01_016
1
Information
Ensure that the guard is easy to clean for mainte­nance purposes. A heavily soiled strainer can lead to a high pressure safety shutdown or to a malfunc-
tion shutdown based on ow metering (heat sink).
Information
Ensure that the ow velocity in the pipe network
does not exceed 0.8 m/s, as this can cause in­creased noise emissions.
10 . 3 .1 Connecting the heating water
Before connecting the heat pump, ush the pipework
»
through with ltered ushing water in accordance with
standard procedures. Foreign bodies such as rust, sealing material and swarf will impair the operational reliability of the heat pump.
12
1 SSP snow cover
10.3 Connecting the heat sink system
Information
The hydraulic connection from the heat sink system (WNA) to the heat pump may be made only by a
qualied contractor.
Information
For maintenance purposes, a cut-off valve should be tted to every hydraulic line close to the con­nection point on the heat pump.
In the case of air/water heat pumps, an appropriately di­mensioned heat pump buffer tank is essential, in order to provide the necessary energy for defrosting the outdoor unit.
► The pipe network and the pumps should be correctly
dimensioned for your heating system and according to the technical data for your heat pump.
A (manual) air vent valve must be tted at the highest
point in the pipework.
At the lowest point in the pipework, t a drain pipe to
allow the system to be drained.
11_02_200_504_01_004
1 Heating water ow
2 Heating water/DHW return
Make the appropriate connections from the indoor
»
unit heating ow and heating return to the heating
system.
Ensure that the connection is tight.
»
When installing pipework, take care to prevent trans-
»
mission of vibration noise.
Quality of heating water
Use the corre ct ll water that is suit able for the compone nts
of your heating system. We recommend ll water prepared
according to Guideline VDI 2035-2.
A high pH value and low electrical conductivity in the ll
water will reduce to a minimum the risk of corrosion to iron
and copper materials, as long as there is also low oxygen
content. This will also minimise scaling (calcication).
► Ensure that no foreign bodies (dust, dirt etc.) can en-
ter the pipework.
► A guard (strainer) can be installed in the return line of
the heat pump to catch dirt.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 31
Fill water characteristics
pH value at 25°C 8.5 -10
Electrical conductivity at 25°C < 100 μS/cm
Oxygen content < 0.05 mg/l
Chloride < 30 mg/l
INSTALLATION | Appliance installation
i
i
i
Material damage
Unsuitable ll water can damage your system due
to scaling and corrosion.
If necessary, ensure that the ll water is pro-
»
fessionally softened and demineralised.
10.3.2 Safety valve drain
Information
The indoor unit has an internal safety valve (DHW, heating).
Observe national and regional regulations re-
»
garding the design of the drain and prescribed regular operational tests.
Information
The maximum operating pressure of the heat transfer medium is 3 bar. However, due to closing pressure differences, the safety valve may begin to open from a pressure of 2.4 bar.
If the valve is triggered, the water exits via a hose on the rear of the indoor unit.
The safety valve drain should be dimensioned such
»
that the water can drain unobstructed via an open and readily visible waste water drain.
1
1 Drain and ll valve with hose screw connector (spe-
cial thread M21x1.5)
Information
The drain and fill valve has a special thread (M21x1.5) for the hose screw connector.
Take care of the hose screw connector provid-
»
ed and keep it close to the heat pump.
2
1
3
11_02_200_202_01_027
Install the hose with a consistent fall to the drain.
»
Avoid kinking the hose.
10.3.3 Filling the heating system
On delivery, the 3-way switching module will be in the “heating mode” position.
4
1 Drain and ll valve 2 Locking ring for closing and opening the drain and ll
valve 3 Hose screw connector (special thread M21x1.5) 4 Cover
Venting the heating system
On the AIR 7, AIR 11 and AIR 18 (M2 hydraulic variant) indoor units, the multifunctional assembly (MFA) has a quick-action air vent valve for venting the heating system.
Before venting, open the quick-action air vent valve
»
on the multifunctional assembly (MFA). Do this by
11_02_200_202_01_023
pulling the red cover on the valve.
Material damage
During venting, water can escape from the air out­let on the quick-action air vent valve.
Ensure that the electronics in the indoor unit
»
do not become wet.
11_02_200_202_01_028
You can nd information on subsequent manual switching
of the 3-way switching module in the controller operating instructions (DHW circuit/relay test).
Fill the heating system with suitable ll water using
»
the drain and ll valve.
32 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance installation
i
i
11_02_200_202_01_017
1
1 Quick-action air vent valve on the multifunctional as-
sembly (AIR 7, AIR 11 and AIR 18)
Material damage
Close the quick-action air vent valve again
»
after venting by pressing the red cover on the valve.
10.3.6 Cooling version
When used for cooling, all system components (pipes,
ttings) must be insulated against condensation build-up
using appropriate insulating materials. This is particularly
important on the ow line from the heat pump to the heat
pump buffer tank.
Especially in relation to cooling mode and defrost
»
mode, ensure adequate sizing of the hydraulic safety devices.
Allow for a pressure maintaining device with appro-
»
priate charge pressure, adjusted for the operating conditions.
Ensure that in cooling mode the appliance casing on
»
the indoor unit is fully and correctly installed (see „As­sembling the appliance casing“ on page 27).
10.3.7 Connecting the DHW
11_02_200_202_01_029
The indoor unit is tted with a 3-way switching module for
switching between the DHW circuit and the heating circuit.
When conguring a DHW charging pump, take into account
the internal pressure differences in the plate heat exchang-
er (see „Specication“ on page 50).
10.3.4 Diaphragm expansion vessel (DEV)
► The indoor units for the AIR 7, AIR 11 and AIR 18
heat pumps are factory-tted with a 24 l diaphragm
expansion vessel for the heat sink system.
► The factory-set pre-charge pressure on the DEV is
1.5 bar.
Information
The set charge pressure on the DEV must not be taken as correct but must be adjusted for the par­ticular system.
Set the charge pressure on the DEV accord-
»
ing to the height of your system and the lling
pressure of your heating system.
10.3.5 Flow metering
A ow meter is installed on the heat sink side inside the
indoor unit of your heat pump. This unit measures the ow rate in your heating system. Too low a ow rate will lead to a safety shutdown of the heat pump.
12
1 DHW ow
2 Heating water/DHW return
Make the appropriate connections from the DHW
»
ow and DHW return on the indoor unit to the DHW
cylinder.
Information
The nominal ow rates for the heat sink system (WNA) should be determined. Different ow rates can lead to a reduction in the efciency of the heat
pump.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 33
INSTALLATION | Appliance installation
i
i
i
i
i
10.4 Electrical connection
10 . 4 .1 General
WARNING: Electrocution
Before commencing work on electrical connections and installation, the heat pump system must be isolated and voltage-free.
WARNING: Electrocution
Work on electrical connections and installation may
be conducted only by qualied contractors.
WARNING: Electrocution
Before commissioning, the necessary fault pro­tection measures on the system and the earth connection must be checked by an authorised contractor.
Information
It is essential that the regulations of the responsible power supply utility (PSU) and the applicable EN standards be observed.
► Before commencing work to connect up the power
supply, the necessary activities dened in „Preparing
the electrical connections“ on page 22 must have been completed.
► For the electrical connection, use the system principle
schematic appropriate to your heat pump system from section „System schematic diagrams“ on page 68.
Undo and remove the four nuts on the two metal
»
plates at the cable entries.
Remove the two metal plates at the cable entries to
»
gain access to the cable strain reliefs.
Information
When tting the cables in the indoor unit, ensure
that subsequent connection work and soldering on the refrigerant lines will not be obstructed by the cables.
Information
For the shielded cables between the outdoor and indoor units, use the shielding clamps provided on the control box panel.
Information
For the cables inside the control box on the indoor unit, use the cable strain reliefs provided.
Connect the lead for suction gas sensor S2 (coming
»
from the outdoor unit) to the terminal provided.
Connect the cable for the stepper motor of expansion
»
valve A (located in the outdoor unit) directly to the
free terminal on the expansion valve controller (EVD).
Be sure that each wire is connected correctly accord-
ing to its colour.
Connect the leads for defrost sensors TQE and TQA
»
directly to the OTE controller.
Connect the fan speed lead (0-10 VDC) directly to the
»
OTE controller.
10.4.2 Electrical connection of the indoor unit
Remove the control box cover (see „Disassembling
»
the appliance casing“ on page 26).
Connect the temperature sensors required by your
»
system (TA, TPO, TPM, TMK, TB) directly to the OTE
controller.
Connect the external pumps and servomotors re-
»
quired by your system (switching module, mixing
valve) directly to the OTE controller.
Information
For external pumps and servomotors, use the PE terminals on the relevant OTE plug.
11_02_200_202_01_011
34 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance installation
11_02_200_202_01_014
1
2
1 X5 terminal for suction gas sensor S2 2 Terminal on expansion valve controller for the stepper
motor of expansion valve A 1: green 3: brown 2: yellow 4: white
11_02_200_202_01_013
OTE pin Description
7 Heating circuit circulation pump 1, direct (HCP 1)
8 Heating circuit circulation pump 2, mixed (HCP 2)
10 DHW auxiliary heater, only on M4 (DHWAH)
13/14 DHW charging pump ON/OFF (WWL)
15/16 Heating circuit mixing valve (MVH)
25/26 Buzzer fault output
40 0-10 VDC fan speed
41/4 2 Control elements (eBus)
43 Mixer sensor (TMK)
44 Outdoor temperature sensor (TA)
45 Top buffer sensor (TPO)
46 DHW sensor (TB)
49 Defrost sensor 1 (TQE)
50 Defrost sensor 2 (TQ A)
52 Bottom buffer sensor (TPM)
55 Building management system input
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 35
INSTALLATION | Appliance installation
i
i
Information
For the cables inside the control box on the indoor unit, use the cable strain reliefs provided.
Material damage
An external source of voltage at the sensor termi­nals can destroy the OTE controller.
Ensure that no 230 VAC or 400 VAC cables
»
are touching the sensor terminals on the OTE controller.
Connect the power supply cable for the control circuit
»
(X3).
Connect the power supply for the main power circuit
»
(X1).
Connect the power supply for the electric booster
»
heater, if present (KM2, X8).
Information
Connect the PE conductor from the power cables to the earth rail in the control box.
WARNING: Electrocution
When the appliance power supply is on, there will always be 230 VAC at the PSU signal contact.
When using the PSU signal contact („PSU signal contact“ on page 24), please note the following:
Remove the factory-tted clamp on X3 (LS/21).
»
Connect the cable for the PSU signal contact to X3
»
(L S/21).
KM2
Terminal Description
X1 L1/L2/L3/N Connection from main power circuit (compres-
L/N/PE Connection from main power circuit (compres-
X2 L1/ N Connection for fan power supply (for outdoor
X2 TK1/TK2 Fan fault message
X3 L/N Mains connection for control circuit (OTE)
X3 LS/21 PSU signal contact
KM2 L1/L2/L3 Mains connection for the electric booster
X8 N/N/N
sor and fan) to three -phase alternating current
sor and fan) to single phase alternating current
unit)
heater (comprising three individual heating elements)
10.4.3 Electrical connection of the outdoor unit
The outdoor unit receives its power supply via the indoor unit.
Remove the side casing panel from the outdoor unit
11_02_200_202_01_012
»
to gain access to the terminal box (see „Disassem-
bling the appliance casing“ on page 26).
Connect the fan power supply in the terminal box.
»
Connect the lead for the defrost sensors (TQE, TQA).
»
Connect the fan speed lead (0-10 VDC). Make sure
»
that the polarity of the lead is correct.
Connect the lead for suction gas sensor S2 to the ter-
»
minal provided.
Connect the cable for the stepper motor of expan-
»
sion valve A (located in the outdoor unit). Be sure
that each wire is connected correctly according to its
colour.
11_02_200_202_01_015
36 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance installation
i
7
6
5
4
3
1 Fan fault message (TK1/TK2) 2 Fan power supply (L/N/PE) 3 Stepper motor of expansion valve A (1/2/3/4) 4 Suction gas sensor S2 5 Defrost sensor TQE (OTE pin 49/GND) 6 Defrost sensor TQA (OTE pin 50/GND) 7 Fan speed (0-10 VDC/GND) 8 Earth rail
8
1
2
10.5 Connecting heat source system
WARNING: Burns
Work on the refrigerant circuit may be carried out only by an authorised and suitably qualied con­tractor. Refrigerant can cause burns to the skin.
When handling refrigerant, wear appropriate
»
gloves and protective glasses.
The following activities on air/water heat pumps must be
carried out by OCHSNER Customer Service or by a cus-
tomer service partner authorised by OCHSNER.
► Connecting the previously laid refrigerant lines.
► Conducting leakage tests on the refrigerant lines.
► Emptying the refrigerant lines.
► Insulating the refrigerant lines around the connection
points on the indoor and outdoor units.
► Filling the system with the correct refrigerant accord-
ing to OCHSNER guidelines.
Information
The system installer must ensure that noise insu-
lating pipe xings for the refrigerant lines and the
11_02_200_504_01_001
10 . 5 .1 Connecting the refrigerant lines
seals on the wall outlets are correctly tted.
Material damage
Incorrect or premature opening of the pipe connec­tions and cutting of the refrigerant lines can allow dirt and moisture to enter the refrigerant circuit.
Do not open the connections on the indoor
»
or outdoor units until just before installing the refrigerant lines. Cut the refrigerant lines with a suitable pipe
»
cutte r. Prevent swarf from contaminating the pipe
»
connections and refrigerant lines. Flush the refrigerant lines fully with nitrogen.
»
The refrigerant circuits on both the outdoor and indoor
units are lled with nitrogen at the factory. Please note the
following when installing the refrigerant lines:
Use the largest possible pipe bends to avoid high
»
pressure losses.
Use suitable sound-insulating pipe xings to secure
»
the refrigerant lines.
Do not install the pipe xings in the vicinity of bends
»
in the pipes.
Ensure that no strain can be exerted on soldered
»
joints.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 37
INSTALLATION | Appliance installation
i
i
2
1 Liquid line (refrigerant) 2 Suction gas line (refrigerant)
Ensure that the necessary preparatory work on refrig-
»
erant lines underground or in open air has been fully completed.
Open up the connections for the liquid and suction
»
gas lines on the indoor and outdoor units using a suit­able pipe cutter.
Connect the liquid and suction gas lines to the indoor
»
and outdoor units of the heat pump system.
1
10.5.3 Filling the refrigerant circuit with refrigerant
Empty the refrigerant lines.
»
Allow the refrigerant to ow into the refrigerant circuit.
»
Material damage
Operating the heat pump with too little or no refrig­erant will damage the appliance.
10.5.4 Insulating the refrigerant lines
11_02_200_202_01_018
Insulate refrigerant lines with suitable insulating mate-
»
rial wherever they are still exposed to the air between
the indoor and outdoor units, to prevent formation
of condensation. When passing through open air
outside, the insulating material must also have UV
protection.
Information
Insulation used beneath the soil must be made of a closed-cell material. Otherwise, the thermal in­sulation of the material will be impaired.
When soldering, ensure that neither moisture nor dirt
»
can penetrate into the refrigerant lines. When solder­ing, always use forming gas.
Ensure that soldered joints are properly sealed.
»
10.5.2 Checking for leak tightness
After the refrigerant lines have been installed, the leakage test on the refrigerant circuit is carried out.
Information
Nitrogen can become trapped in magnetic valves and expansion valves in the refrigerant circuit.
Before carrying out the leakage test, open all
»
magnetic valves and expansion valves in the refrigerant circuit.
Evacuate the refrigerant lines.
»
Use a suitable medium to carry out the leakage test
»
according to standard regulations.
38 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Commissioning
11_02_200_202_01_022
i
11. Commissioning
OCHSNER Customer Service or an authorised custom­er service partner must be requested to commission the system. In order to be allocated an appointment, a com­pleted and signed commissioning form must be provided. Commissioning appointments must be requested at least two weeks in advance.
11.1 Before switching on for the rst time
The heat pump has no separate on/off switch. In an emer-
gency, the system must be shut down via the specied
safety equipment. The safety equipment must be acces­sible so that an emergency shutdown can be performed at any time.
WARNING: Electrocution
First-time start-up of electrical systems is permitted
only in the presence of a qualied contractor.
Make sure that no persons can be put at risk during
»
the rst start-up.
Make sure that the heat sink system (heating and
»
DHW production) has been connected to the heat pump.
11.3 Adjusting the ow rate
The nominal ow rate of the heat sink system must be
determined in each operating mode (DHW charging, heat-
ing, cooling mode via separate cooling heat pump buffer
tanks etc.). The ow rate is measured using the installed
ow met er. The measured values can be read off from the
master controller display on the indoor unit.
The ow rate of the heat sink system is adjusted using the
adjusting screw on the heat generator pump (HGP). To
enable correct hydraulic adjustment, in particular during
combined heating or heating/cooling and DHW heating
modes, the appropriate balancing valves must be installed
and the system regulated accordingly.
Make sure that the hydraulic system is lled with
»
water.
Make sure that the system has been fully vented.
»
Make sure that the electrical installation has been
»
carried out and completed professionally.
Material damage
Operating the circulation pumps without water in the system will destroy the pumps.
The power supply to the main power circuit (compressor) must not be switched on until the refrigerant circuit has
been lled with refrigerant and the hydraulic system with
the correct medium.
11. 2 Testing the control circuit
Once all the above conditions have been checked, the pow­er supply to the control circuit (OTE controller, 230 VAC) can be switched on so that the individual functions can be tested.
Check all of the sensors and their values for
»
plausibility.
1
1 Heat generator pump (HGP)
Information
To be able to change the ow rate in the heat sink
system, you will have to turn the adjusting screw on the heat generator pump.
Remove the front casing panel from the indoor
»
unit to gain access to the heat generator pump (see „Disassembling the appliance casing“ on page 26).
Switch on the heat generator pump via the relay test
»
menu on the master controller.
Check all of the controller outputs used on your hy-
»
draulic system for correct function.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 39
INSTALLATION | Commissioning
HEIZKREIS 1
ESC
HEIZKREIS 2
WARMWASSERKREIS
WAERMEPUMPE
ENTER
Einstellungen
Relaistest
ESC
ENTER
Betriebswahl
Betriebsdaten
MENUE
ESC
Umlenkventil Kü
0
ESC
Wärmeerzeugerpu
0
0
SOLL Verdichter
ENTER
Wärmequellenpu
0
ESC
ENTER
100%
Wärmeerzeugerpumpe
MENUE
ESC
HEIZKREIS 1
ESC
HEIZKREIS 2
WARMWASSERKREIS
WAERMEPUMPE
ENTER
Betriebswahl
Betriebsdaten
Einstellungen
Relaistest
ESC
ENTER
ESC
ENTER
Heizenergie MWh
0
Heizleistung
0
Heizenergie kWh
0
Volumenstrom Wä
27
Volumenstrom Wärmenut-
zung
27.4 l / min
ESC
Mo 09 .01.17 10:02
-12.5C 22°C 52.5°C
32.5°C
Betriebsbereit
Ready for operation
OCHSNER OTE
HEATING CIRCUIT 1 HEATING CIRCUIT 2 DHW CIRCUIT
HEAT PUMP
ESC
WAERMEPUMPE
ESC
MENU
Hauptmenü
Main menu
HE AT PUMP
ENTER
MENU
Mo 09 .01.17 10:02
-12.5C 22°C 52.5°C
32.5°C
Betriebsbereit
Ready for operation
OCHSNER OTE
HEATING CIRCUIT 1 HEATING CIRCUIT 2 DHW CIRCUIT
HEAT PUMP
ESC
WAERMEPUMPE
ESC
MENU
Hauptmenü
Main menu
HE AT PUMP
ENTER
MENU
WARMWASSERKREIS
HE AT PUMP
Operation mode Operating data Settings
Relay test
ESC
HE AT PUMP
WAERMEPUMPE
01-022
01-022 Heat generator 0
01-076
01-076 TARGET compres
01-077
01-077 Heat source pump/ 0
01-078
01-078 Refrigerant circuit 0
ESC
01-022 H EAT PUMP
01-022 WAERMEPUMPE
Heat generator pump
ENTER
- 0
ENTER
100%
ESC
ENTER
11_01_200_701_01_01_002
WAERMEPUMPE
HE AT PUMP
Operation mode
Operating data
Settings Relay test
ESC
HE AT PUMP
WAERMEPUMPE
21-002
21-002 Flow rate heat sink 27
23-001
23-001 Heating energy 0
23-010
23-010 Heating energy 0
23-003
23-003 Heating output 0
ESC
21-002 H EAT PUMP
21-002 WAERMEPUMPE
Flow rate heat sink
ENTER
ENTER
27.4 l/m in
ESC
ENTER
11_01_200_701_01_01_003
Read off the measured ow rate on the master con-
»
troller display.
40 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
Adjust the ow rate to its correct level by turning the
»
adjusting screw on the heat generator pump.
INSTALL ATION | Commissioning
AIR 7 AIR 11 AIR 18
Hydraulic variant M2 M2 M2 Connection dimension DN 32 (1 1/4”) male DN 32 (1 1/4”) male DN 32 (1 1/4”) male Heat sink system circulation pump
(heat generator pump)
Pump head [mbar] 776 776 783 6 51 762 774 499 611 690 766 Spread at L2/W35 [K] 5 7 10 5 7 10 5 6 7 10 Flow rate [m
Internal pressure loss (M2-1) [mbar] 109 56 27 205 104 51 324 225 165 81 Residual head I (M2-1) [mbar] 657 720 756 446 658 722 175 386 525 685
Addnl 3-way switching module [mbar] external DN32 kvs16 external DN32 kvs16 external DN32 kvs16 Pressure loss [mbar] 5 2 1 11 6 3 19 13 10 5 Residual head II (M2-1) [mbar] 652 718 754 435 652 719 156 372 515 680
Yonos Para HPS 25/7.5 Yonos Para HPS 25/7.5 Yonos Para HPS 25/7.5
internal internal internal
3
/h] 1 .1 0.79 0.55 1.7 1.21 0.85 2.2 1.83 1.57 1.1
100% 70% 50% 100% 70% 50% 10 0% 83% 70% 50%
External plate heat exchanger (PHE) for DHW
Primary pressure loss, side A (HP) [mbar] 64 33 16 65 33 16 20 14 10 5 Primary pressure loss, side B
(DHW) Residual head III: heating [mbar] 586 684 738 374 621 704 149 368 512 678 Residual head III: heating/cooling
incl. additional external 3-way switching module (M2-1)
Hydraulic variant M4 M4 M4 Connection dimension DN 40 (1 1/2”) male DN 40 (1 1/2”) male DN 50 (2”) male Heat sink system circulation pump
(heat generator pump)
Pump head [mbar] 686 728 726 577 714 727 929 1052 113 9 1124 Spread at L2/W35 [K] 5 7 10 5 7 10 5 6 7 10 Flow rate [m
Internal pressure loss (M4-1) [mbar] 330 168 82 464 237 116 820 569 418 205 Internal pressure loss (M4-4) [mbar] 234 120 59 304 155 76 523 363 267 131 Residual head I (M4-1) [mbar] 356 560 643 113 478 611 109 482 721 931 Residual head (M4-4 for cascade) [mbar] 452 609 667 273 559 651 406 689 873 10 05
Addnl 3-way switching module [mbar] External DN 40 kvs25 External DN 40 kvs25 External DN 50 kvs40 Pressure loss [mbar] 18 9 5 31 16 8 23 16 11 6 Residual head II (M4-1) [mbar] 338 551 638 82 462 603 87 466 710 925 Residual head (M4-4 for cascade) [mbar] 434 600 662 242 543 643 384 673 862 999
[mbar] 71 36 18 72 37 18 26 18 13 7
[mbar] 588 685 738 370 619 703 136 359 505 675
3
PHE 2007, A=1”, B=1” PHE 2007, A=1”, B=1” PHE 5007, A=1 1/4”, B=1”
AIR 23 AIR 29 AIR 41
Stratos Para 25/1-8 Stratos Para 25/1-8 Stratos Para 25/1-12
internal internal internal
/h] 3.4 2.43 1.7 4.4 3.14 2.2 6 5.00 4.29 3
100% 70% 50% 100% 70% 50% 10 0% 83% 70% 50%
External plate heat exchanger (PHE) for DHW
Primary pressure loss, side A (HP) [mbar] 37 19 9 62 32 16 65 45 33 16 Primary pressure loss, side B
(DHW) Residual head III: heating [mbar] 308 536 631 33 437 591 19 420 675 909 Residual head III: heating/cooling
incl. additional external 3-way switching module (M4-1)
Residual head III (M4-4) [mbar] 397 5 81 653 180 512 628 319 628 828 983
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 41
[mbar] 48 24 12 80 41 20 90 63 46 23
[mbar] 301 532 629 20 431 588 22 421 676 909
PHE 5007, A=1 1/4”, B=1” PHE 5007, A=1 1/4”, B=1” PHE 9507, A=2”, B=2”
INSTALLATION | Commissioning
11. 4 Heat generator pump (HGP)
Yonos Para HPS 25/7.5 (AIR 7, AIR 11, AIR 18)
Stratos Para 25/1-8 (AIR 23, AIR 29)
12_05_908_01_001
Stratos Para 25/1-12 (AIR 41)
12_05_908_02_001
42 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
12_05_908_03_001
INSTALL ATION | Commissioning
i
i
11.5 Necessary conditions for commissioning
Before commissioning, the system installer must ensure the following points:
► The design and installation of the system have been
approved by OCHSNER.
► The OCHSNER guidelines have been observed
(system installed according to OCHSNER standard hydraulic schemes or a special OCHSNER hydraulic system).
► The system datasheet is available and has been fully
and correctly completed.
1. The heat sink system is fully ready (heating and DHW heating).
► The hydraulic pipework has been correctly di-
mensioned and installed such that the required
nominal ow rates can be set.
The heat sink system has been ushed, lled and
vented according to the required standards.
The quality of the system ll water is assured to
meet the required standards (VDI 2035).
► Operating pressure has been set and the system
temperature and buffer temperature lie between 20°C and 30°C at the time of commissioning.
► The necessary safety devices are in place and
have been adjusted and checked according to sys­tem requirements.
A DHW cylinder is present and has been lled for
commissioning.
► All shut-off valves have been opened, adjusted
and checked.
The ow meter has been checked for correct
functioning.
► The system has been hydraulically balanced.
2. The heat source system has been prepared.
► The hydraulic pipework has been correctly di-
mensioned and installed such that the required
nominal ow rates can be set.
In the case of air/water and direct evaporation/
water heat pumps, if the routing of the con­nection lines by the system installer has been contractually agreed:
Ensure that the refrigerant lines between the indoor and outdoor units have been correctly routed in accordance with refrigeration engineer­ing guidelines. The refrigerant lines have been correctly channelled through the wall outlets with some surplus length between the connections at the indoor and outdoor units.
In the case of brine/water heat pumps:
The system pressure and addition of frost pro­tection additive (between -12°C and -15°C) have been assured. The heat source system has been
ushed, lled and vented according to standards.
In the case of water/water heat pumps:
All lters have been checked and cleaned. The
water quality is in accordance with OCHSNER guidelines.
Information
OCHSNER will accept no liability for damage (e.g. to plate heat exchangers) caused by poor water quality.
3. The electrical installation has been completed.
Information
Provisional electrical installations are not permissi­ble and will lead to commissioning being cancelled.
► Electrical connection and installation work has
been carried out, checked and completed in ac­cordance with national and regional regulations.
► A safety device that will shut down across all poles
has been provided on every supply (compressor, heat source pump and controller). Every additional heat generator is also provided with its own safety device.
► The three-phase supply has been checked to en-
sure a clockwise rotating eld.
4. On site requirements
► An authorised and technically competent repre-
sentative of the system installer (the heating or electrical contractor) is present along with the sys­tem user during the commissioning.
► The necessary safety devices are in place and
have been adjusted and checked according to sys­tem requirements.
► The wall outlet has been properly sealed.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 43
Customer-specic controller settings are available
(heating curve and functional logic, according to system datasheet).
► Where connections are in a duct or on the roof, an
assistant has been provided by the customer.
► Climbing aids and/or fall protection (compliant
attachment points) have been provided on site in accordance with the required standards.
INSTALLATION | Commissioning
i
i
i
► Vehicle access to the heat pump system is
available.
Information
OCHSNER Customer Service or its customer ser-
vice partner carries out customer-specic settings
according to the details on the system datasheet. If the system installer is not present during com­missioning or if a fully completed system datasheet is not available, the system is put into operation using the control factory settings. OCHSNER will accept no responsibility for any faulty operation (too low a heating curve, too high a bivalent point, etc.). Any additional work required will be charged to the system installer.
11. 6 Commissioning the system
Before commissioning, the requirements set out in section
11.5 “Necessary conditions for commissioning” must be met.
Commissioning is carried out by OCHSNER Customer Service or by a customer service partner authorised by OCHSNER. The OCHSNER commissioning guidelines apply.
Information
If the system is operated without technically correct commissioning in accordance with the OCHSNER guidelines, all warranty claims will be invalid.
Information
Special work such as system venting, connecting electrical cables, additional training etc., which is not included in OCHSNER‘s scope of delivery, will be invoiced separately.
Activities carried out by OCHSNER:
► Checking that the system has been installed accord-
ing to OCHSNER guidelines. In commissioning the system, OCHSNER offers no warranty regarding the ability to meet the heat demand of the building to be heated.
► Functional testing of the heating circuit (system
pressure, function of diaphragm expansion vessel, quantity settings). Responsibility for the system re­mains with the system installer.
Checking ow rates.
► Checking that all shut-off valves are open.
► Checking the electrical connections to the system
components including all required safety devices.
► In the case of air/water and direct evaporation/water
heat pumps (depending on contractual terms):
► Version 1:
Where connecting lines have been laid as contrac­tually agreed by the system installer. OCHSNER Customer Service is responsible for:
- Connecting the previously laid refrigerant lines.
- Conducting leakage tests on the refrigerant lines.
- Emptying the refrigerant lines.
- Insulating the refrigerant lines around the con­nection points on the indoor and outdoor units.
- Filling the system with the correct refrigerant according to OCHSNER guidelines.
► Version 2:
Where connection lines have been laid and the technical installation of the refrigerant circuit car­ried out by OCHSNER Customer Service.
44 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Commissioning
i
Checking that the 3-phase supply is correctly phased
with a clockwise rotating eld.
► Switching on the main power circuit (3-phase supply
to heat pump).
► Switching on the power supply to the control circuit.
Conguring the system using the commissioning
assistant.
Checking the sensor conguration.
► Conducting a relay test on the outputs.
Making customer-specic settings on the heat pump
system.
► Producing a commissioning report and completing
the entries in the service book.
► Handing the system over to the system user or end
customer.
► Explanation of the basic functions of the heat pump
system (controller operation, etc.).
11.7 Decommissioning
You do not need to switch off your heat pump system in the summer. The heat pump control unit changes over au­tomatically between summer and winter.
Material damage
If the power supply to your heat pump system is switched off, frost protection of the system cannot be guaranteed.
You should not switch off the power supply
»
to your heat pump, even outside the heating period.
Should you wish to deactivate your heat pump system, then switch off the system using the master controller. This way, safety functions such as frost protection remain enabled.
Material damage
If the power supply to the heat pump system is interrupted and there is a risk of frost, drain the system on the water side.
Information
OCHSNER Customer Service will provide an ex­planation of the basic functions of the heat pump system (controller operation, etc.). If the system user is not present on commissioning, the system installer will assume responsibility for this explana­tion. Instruction on the functionality of the overall system is the responsibility of the system installer.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 45
INSTALLATION | Troubleshooting
i
12. Troubleshooting
Information
Resolving faults and making changes to settings on the heat pump system may only be carried out by qualied contractors. Standard settings for the controller are set by OCHSNER Customer Service as part of the commissioning process. The system user and contractual partner is responsible for any further corrections and settings to programs.
Problem Cause Solution
Too little DHW is available or the central heating system is too cold.
The appliance is leaking water.
The heating system does not heat up, no fault message.
The heat pump is only producing DHW and is not providing heating, or is doing so too late.
DHW temperature is not or is no longer being reached.
Heat pump runs continuously but yields only low tempera­tures, and there are traces of oil in the appliance.
Flow rate too low The minimum flow rate at the heat
The power supply to the appliance has been cut off.
The drain for the safety valve is blocked.
PSU shutdown Check individual room controls, vent the heating circuit, open valves, Energy transfer to the heating circuits
is interrupted or too low Power failure DHW priority DHW target temperature is too high Check the DHW target temperature Pasteurisation mode Use time program, install electric immersion heater for DHW DHW circulation line Reduce flow rate and use time clock DHW heat exchanger scaled up Notify heating contractor, clean heat exchanger, descale Heat exchanger for DHW is too small. Increase size of heat exchanger Heat exchanger is scaled up Descale heat exchanger Sensor incorrectly positioned Correctly position sensor Pipework too small Install pipes with larger diameters Faulty DHW sensor Replace DHW sensor DHW charging pump is faulty Replace DHW charging pump DHW charging pump output level set
too low 3-way switching module is faulty Replace 3-way switching module Refrigerant leak, refrigerant line not
leak tight
pump is not being reached.
Check the safety device on the main distributor board for your house. Switch the safety device back on. If the safety device triggers again after being switched back on, contact a qualified contractor or OCHSNER Customer Service.
Clean the safety valve drain.
check heating circuit circulation pump, increase the output level of the heating circuit circulation pump, check fuses
Set higher output levels
Switch off heat pump, notif y OCHSNER Customer Service
System pressure too low: check pressure maintenance equipment. Buffer charging pump is faulty, 3-way switching module is faulty
12 .1 Fault messages on the master controller
► In the event of a fault, the relevant fault messages will
be displayed on the controller as “Er XXX”.
► If the high limit safety cut-out is triggered, this will
not be displayed with a fault message on the master controller.
In the following table, the possible fault messages are listed together with the associated code or fault history code. Fault messages with an associated fault history code are stored and can be read off again later, even when no fault is present. Stored fault messages are listed in the “Service Report” menu under the “Error data” submenu.
46 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Troubleshooting
Code Fault code
history
115 Er 01: DHW sensor faulty Replace sensor 116 Er 10: Outside sensor faulty Replace sensor 117 Er 14: Mixer sensor faulty Replace sensor 124 Er 20: TWR sensor faulty Replace sensor 120 Er 22: TPM or TWR shutdown sensor faulty Replace sensor 136 Er 23: TPV sensor faulty Replace sensor 118 Er 24: Buf fer sensor faulty Replace sensor 114 Er 29: TWV sensor faulty Replace sensor 11 11 Er 30: Phase monitor Check power supply 134 Er 32: THG sensor faulty Replace sensor 138 Er 33: High pressure sensor faulty Check sensor 137 Er 34: Low pressure sensor faulty Check sensor 5 5 Er 36: High pressure Deficient heat distribution, faulty circulation pump, valve closed or air in the
18 18 Er 37: Low pressure Lack of source energy, lack of refrigerant, expansion valve, check refrigerant
16 16 Er 38: Hot gas Expansion valve, lack of refrigerant, target temperature too high, check re-
10 10 Er 39: Compressor motor protection Motor overload relay, phase fault/overload, source temperature too high,
8 8 Er 42: Heat sink frost protection Deficient heat distribution, faulty circulation pump, valve closed or air in the
Er 46: TSG sensor faulty Replace sensor 9 9 Er 47: Defrost fault Too little de-icing energy, evaporator/sensor, check refrigerant circuit (by
129 129 Er 48: TQE sensor/Evaporator 1 is faulty Replace sensor 130 130 Er 49: TQA sensor/Evaporator 2 is faulty Replace sensor 12 12 Er 50: Expansion valve Check function of electronic expansion valve (by OCHSNER) 1 1 Er 56: Heat source flow rate Lack of source energy, heat source pump/filter, flow rate at heat source too
2 2 Er 57: Heat source frost protection Lack of source energy, source temperature too low, check heat source,
3 3 Er 58: Heat source motor protection Check motor protection, check wiring to motor, motor overload relay, phase
143 143 Er 59: TW V + TWR sensor break Check sensor 144 144 Er 60: TQA + TQE sensor break Check sensor 42 42 Er 71: Bus fault, room remote control Check eBus wiring 30 30 Er 80: Heat generator 1 address Check addressing 31 31 Er 81: Heat generator 2 address Check addressing 32 32 Er 82: HG 3 address Check addressing 33 33 Er 83: HG 4 address Check addressing 34 34 Er 84: HG 5 address Check addressing 35 35 Er 85: HG 6 address Check addressing 36 36 Er 86: HG 7 address Check addressing 37 37 Er 87: HG 8 address Check addressing 20 20 Er 91: Heat sink flow rate Water pressure too low, circulation pump faulty, valve closed/air in system,
21 21 Er 90: Overheating Check refrigerant circuit (by OCHSNER Customer Service) 98 98 Er 98: Auxiliary heat generator running as
104 10 4 Er104: Sum fault, heat pump OCHSNER Customer Service 108 10 8 Er108: Outdoor unit, general Check wiring 109 10 9 Er109: Compressor overheating Automatic acknowledgement 100 10 0 Er200: Condensation temperature too low Check refrigerant circuit (by OCHSNER Customer Service) 102 102 Er 202: Evaporation temp. too low Check refrigerant circuit (by OCHSNER Customer Service) 103 103 Er 203: Evaporation temp. too high Check refrigerant circuit (by OCHSNER Customer Ser vice) 240 240 Er240: OTE cannot recognise a Modbus
241 241 Er241: Modbus communication error Power shutdown? Check the wiring of the Modbus cable between indoor and
242 242 Er242: CAN bus communication fault Check wiring of CAN bus cable and Modbus cable (possible consequential
Display message Possible cause and solution
system, check hydraulics
circuit (by OCHSNER Customer Service)
frigerant circuit (by OCHSNER Customer Service)
check compressor in refrigerant circuit (by OCHSNER Customer Service)
system, check buffer charging pump or hydraulics
OCHSNER Customer Service)
low
check heat source pump/filter, clean water filter, submersible pump faulty
fault/overload, thermal cutout
check hydraulics
Check operation mode of heat pump
only heat generator
Check by OCHSNER Customer Service
PCB
outdoor units. Otherwise check by OCHSNER Customer Service
fault of Er 241), otherwise check by OCHSNER Customer Service
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 47
INSTALLATION | Appliance maintenance
i
i
12.2 Reset high limit safety cut-out
If the temperature sensor of the high limit safety cut-out registers a heating water temperature of over 85°C, the power supply to the internal electric booster heater is cut off.
Check whether the high limit safety cut-out has
»
triggered.
Check the ow rate of the heating water.
»
Remedy the source of the fault.
»
Press the reset button on the rear of the appliance to
»
reset the high limit safety cut-out. The reset button can be reached by hand from the left-hand side.
1
13. Appliance maintenance
WARNING: Electrocution
For maintenance work, cut off the power supply to the indoor and outdoor units of your heat pump.
Information
Ensure that the refrigerant circuit of your heat pump is tested for leaks once a year (in acc. with Regu­lation (EU) no. 517/2014).
Ensure year-round access to soldered joints in
»
the refrigerant circuit. Document the results of the leakage test in the
»
system test report.
We recommend arranging for an inspection and if neces­sary a service on the heat pump to be conducted once a year. We draw your attention to the fact that statutory regulations require regular testing of heating systems by the system user.
The refrigerants used in OCHSNER heat pumps are non-ammable, non-toxic and ozone neutral. Heat pumps are refrigeration equipment and are subject to the pro­visions of the F-gas Regulations (Regulation (EU) no. 517/2014). OCHSNER Customer Service will be pleased to help in carrying out maintenance and testing, in particular as required by the F-gas Regulations. You can nd more information at www.ochsner.com.
1 Reset button for high limit safety cut-out on rear of
appliance
We recommend testing the heating water system pressure and correcting it if necessary (pressure too high/low).
We recommend adjusting the charge pressure in the dia­phragm expansion vessel (DEV) on the system accordingly (system height).
We recommend monitoring the ow rate of the heat sink
system (WNA) and if necessary the heat source system
(WQA) using the ow meters specied by OCHSNER.
We recommend that when non-routine work takes place
requiring relling (e.g. system alteration or pipe breakage),
a current water assessment be prepared and the heat sink
system be relled on the basis of this.
13 .1 Testing safety valve
11_02_200_202_01_021
Information
The indoor unit has an internal safety valve (DHW, heating).
Observe the national and regional regulations
»
regarding the prescribed regular operational tests.
Remove the left-hand appliance casing panel to gain
»
access to the internal safety valve (see „Disassem­bling the appliance casing“ on page 26).
To test, turn the red knob on the safety valve until wa-
»
ter emerges from the safety valve drain.
48 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Appliance maintenance
11_02_200_202_01_025
Ensure that the safety valve is closed again after the
»
test.
1
1
1 Internal safety valve on AIR 7, AIR 11 and AIR 18
1 Internal safety valve on AIR 23, AIR 29 and AIR 41.
11_02_200_202_01_026
13. 2 Maintenance contract
OCHSNER offers a wide range of maintenance contracts.
You can nd more information at www.ochsner.com.
Benetsofamaintenancecontract
Annual inspection fulls the statutory requirements
(of, for example, the F-gas Regulations).
► A correctly performed service not only helps to save
energy but also protects the environment.
► In addition, correct care of the heating system is
necessary to ensure many years of service life and indeed to extend the service life of the system.
► For the system user, this reduces the risk of system
failure.
You can nd further information on customer service and
on the services offered under the maintenance contracts at www.ochsner.com.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 49
INSTALLATION | Specication
14. Specication
14 .1 Heat pumps for three-phase alternating
current
14 .1.1 Data table
AIR 7 C11A AIR 11 C11A AIR 18 C11A
INDOOR UNIT:
Hydraulic variant M2-1/M2-2/M2-3/M2-4 M2-1/M2-2/M2-3/M2- 4 M2-1/M2-2 /M2-3/M2-4 Dimensions HxWxD [mm] 1286x600x680 1286x600x680 1286x600x680 Hydraulic connection DN 32 (1 1/4”) male DN 32 (1 1/4”) male DN 32 (1 1/4”) male Weight [kg] 114 124 13 5 Casing colour Tiger white 29/11289/
grey RAL 7016
HEATING MODE PERFORMANCE DATA:
Standard point L10/W35 Heating output [kW] 6.8 11 16 Total power consumption / operating current [kW]/[A] 1.33 / 2.65 2.3 / 4.7 3 / 6.2 Coefficient of per formance EN 14511/EN 255 5.1 / 5.6 4.9 / 5.2 5.3 / 5.6
Operating point L7/W35 Heating output [kW] 6.4 10.2 15 .1 Total power consumption / operating current [kW]/[A] 1.33 / 2.65 2.3 / 4.5 3 / 6.2 Coefficient of per formance EN 14511/EN 255 4.8 / 5.3 4.5 / 4.7 5 / 5.3
Tiger white 29/11289/
grey RAL 7016
Tiger white 29/11289/
grey RAL 7016
Standard point A2/W35 Heating output [kW] 5.4 8.8 13. 2 Total power consumption / operating current [kW]/[A] 1.32 / 2.64 2.2 / 4.4 3 / 6.2 Coefficient of per formance EN 14511/EN 255 4.1 / 4.5 4 / 4.3 4.4 / 4.7
Standard point L-7/W35 Heating output [kW] 4.1 6.8 10.6 Total power consumption / operating current [kW]/[A] 1.28 / 2.6 2 / 4.2 3 / 6.1 Coefficient of per formance EN 14511/EN 255 3.2 / 3.5 3.3 / 3.6 3.6 / 3.8
Operating point L-10/W35 Heating output [kW] 3.7 6.2 9.9 Total power consumption / operating current [kW]/[A] 1.25 / 2.55 2 / 4.1 2.9 / 6 Coefficient of per formance EN 14511/EN 255 3 / 3.3 3.1 / 3.3 3.4 / 3.6
Operating point A2/W50 Heating output kW 4.7 7.9 12.3 Total power consumption / operating current [kW]/[A] 1.75 / 3.4 2.8 / 5.8 4 / 8.2 Coefficient of per formance EN 14511/EN 255 2.7 / 2.9 2.8 / 3 3.1 / 3.2
Operating point A2/W60 Heating output [kW] 4.3 7. 6 12.1 Total power consumption / operating current [kW]/[A] 1.95 / 3.6 3.2 / 6.6 4.4 / 9.1 Coefficient of per formance EN 14511/EN 255 2.2 / 2.4 2.4 / 2.5 2.8 / 2.9
COOLING MODE PERFORMANCE DATA:
Operating point A30/ W18 Cooling capacity [kW] 4.4 9.6 11.2 Total power consumption / operating current [kW]/[A] 1.34 / 2.8 3 / 6.2 3.3 / 6.8 Energy efficiency ratio EER 3.3 3.2 3.4
Operating point A30/ W7 Cooling capacity [kW] 3 .1 8.7 10.7 Total power consumption / operating current [kW]/[A] 1.39 / 2.9 2.9 / 6 3.3 / 6.8 Energy efficiency ratio EER 2.2 3 3.2
SPECIFICATION:
Phases/nominal voltage/frequency [~]/[V]/[Hz] 3/400/50 3/400/50 3/400/50 Output factor cos ϕ 0.7 0.7 0.76 Fuse C10A C10A C16A Max. operating current [A] 5.4 7. 9 11.4
50 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
i
i
AIR 7 C11A AIR 11 C11A AIR 18 C11A
Max. starting current/max. with soft start [A] 27 / 13.5 40 / 20 64 / 32 Sound power level/sound pressure level (at 1 m distance) [dBA] 40.9 / 32.9 44.5 / 36.5 47.5 / 39.5
ELECTRIC BOOSTER HEATER (M2-1, M2-3):
Phases/nominal voltage/frequency [~]/[V]/[Hz] 3/400/50 3/400/50 3/400/50 Max. output [kW] 8.8 (2.9 / 2.9 / 2.9) 8.8 (2.9 / 2.9 / 2.9) 8.8 (2.9 / 2.9 / 2.9) Max. operating current [A] 12.8 12.8 12.8
CONDENSER:
Type Plate heat exchanger Plate heat exchanger Plate heat exchanger Material Stainless steel 1.4301 Stainless steel 1.4301 Stainless steel 1.4301 Quantity [pcs] 1 1 1 Max. refrigerant operating pressure [bar] 30 30 30 Max. heat transfer medium operating pressure [bar] 3 3 3 Heat transfer medium temperature differential [K] 5 5 5 Application range [°C] 65 65 65 Heat transfer medium Water Water Water Test pressure [bar] 45 45 45 Heat transfer medium flow rate [m³/h] 1.1 1.7 2.2 Internal pressure differential [mbar] 109 205 324 Flow meter built-in built-in built-in Heat sink circulation pump (heat generator pump) internal Yonos Para 25/7.5 Yonos Para 25/7.5 Yonos Para 25/7.5 Residual head I heat sink system, external, incl. flow me­ter
REFRIGERANT CIRCUIT:
No. of refrigerant circuits [pcs] 1 1 1 Heat transfer medium R407C R407C R407C Refrigerant full charge [kg] 5.0 9.0 9.0 Defrost technology Hot gas Hot gas Hot gas
[mbar] 657 446 175
COMPRESSOR:
Type Fully hermetic/scroll Fully hermetic/scroll Fully hermetic/scroll Quantity [pcs] 1 1 1 Output levels 1 1 1 Speed [rpm] 2900 2900 2900 Voltage/frequency [V ]/[Hz] 400 / 50 400 / 50 400 / 50 Max. operating current [A] 4 6.5 10
FAN (OUTDOOR UNIT):
Type Axial Axial Axial Quantity [pcs] 1 1 1 Voltage/frequency [V ]/[Hz] 230 / 50 230 / 50 230 / 50 Power consumption [W] 23 40 68 Max. operating current [A] 1.40 1.40 1.40
EVAPORATOR (OUTDOOR UNIT):
Appliance type VHS-M 5 VHS-M 9 VHS-M 14 Dimensions HxWxD [mm] 1080x1290x960 1080x1290x960 1080x1290x960 Type Finned pipe Finned pipe Finned pipe Quantity [pcs] 1 1 1 Weight [kg] 93 93 93 Fin pack material Copper/aluminium Copper/aluminium Copper/aluminium Casing material Stainless steel, coated Stainless steel, coated Stainless steel, coated Max. refrigerant operating pressure [bar] 30 30 30 Relative humidity [%] 80 80 80 Heat transfer medium temperature differential [K] 3.7 5.7 5.7 Air flow rate [m³/h] 2100 3000 4000 Application range min./max [°C] -24 / +40 -24 / +40 -24 / +40 Sound power level/sound pressure level [dBA] 48/20 52/23 54/26 Sound power level/sound pressure level (in silent mode) [dBA] 46/18 49/20 51/ 23
Information
Data on sound pressure levels refer to operation at full load at a distance of 10 m (free space). Sound pressure and sound power levels are given +/-3 dB(A).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 51
Information
Silent mode offers four separate time windows during which the outdoor unit can be operated with reduced sound levels. It is set via the OTE controller.
INSTALLATION | Specication
AIR 23 C12A AIR 29 C12A AIR 41 C12A
INDOOR UNIT:
Hydraulic variant M4-1/M4-2/M4-3/M4-4 M4-1/M4-2/M4-3/M4-4 M4-1/M4-2/M4-3/M4-4 Dimensions HxWxD [mm] 1286x600x680 1286x600x680 1286x600x680 Hydraulic connection DN 40 (1 1/2”) male DN 40 (1 1/2”) male DN 50 (2”) male Weight [kg] 148 160 164 Casing colour Tiger white 29/11289/
grey RAL 7016
HEATING MODE PERFORMANCE DATA:
Standard point L10/W35 Heating output [kW] 23.4 28.4 40 Total power consumption / operating current [kW]/[A] 4.6 / 9 5.8 / 11.8 8.2 / 16.7 Coefficient of per formance EN 14511/EN 255 5.1 / 5.4 4.9 / 5.2 4.9 / 5.1
Operating point L7/W35 Heating output [kW] 20.7 25.8 37. 2 Total power consumption / operating current [kW]/[A] 4.5 / 8.8 5.6 / 11.4 8.1 / 16.5 Coefficient of per formance EN 14511/EN 255 4.6 / 4.9 4.6 / 4.9 4.6 / 4.8
Standard point A2/W35 Heating output [kW] 17. 2 21.8 30.3 Total power consumption / operating current [kW]/[A] 4.1 / 8 5.2 / 10.6 7.4 / 15 Coefficient of per formance EN 14511/EN 255 4.2 / 4.4 4.2 / 4.4 4.1 / 4.4
Standard point L-7/W35 Heating output [kW] 13.7 17.5 25.1 Total power consumption / operating current [kW]/[A] 3.9 / 7.6 5 / 10.2 7.4 / 15 Coefficient of per formance EN 14511/EN 255 3.5 / 3.8 3.5 / 3.8 3.4 / 3.6
Tiger white 29/11289/
grey RAL 7016
Tiger white 29/11289/
grey RAL 7016
Operating point L-10/W35 Heating output [kW] 12 .8 16.3 23.4 Total power consumption / operating current [kW]/[A] 3.9 / 7.6 5 / 10.2 7.4 / 15 Coefficient of per formance EN 14511/EN 255 3.3 / 3.6 3.3 / 3.6 3.2 / 3.4
Operating point A2/W50 Heating output kW 16.8 21. 2 27.4 Total power consumption / operating current [kW]/[A] 5.3 / 10.3 6.6 / 13.4 8.8 / 17.9 Coefficient of per formance EN 14511/EN 255 3.2 / 3.4 3.2 / 3.4 3.1 / 3.3
Operating point A2/W60 Heating output [kW] 16.4 20.8 26.4 Total power consumption / operating current [kW]/[A] 5.8 / 11.3 7.3 / 14.8 9.3 / 18.9 Coefficient of per formance EN 14511/EN 255 2.8 / 3 2.8 / 3 2.8 / 3
COOLING MODE PERFORMANCE DATA:
Operating point A30/ W18 Cooling capacity [kW] 15.6 17.9 2 7. 2 Total power consumption / operating current [kW]/[A] 5.1 / 9.9 5.7 / 11.6 8.4 / 17.1 Energy efficiency ratio EER 3 .1 3 .1 3.2
Operating point A30/ W7 Cooling capacity [kW] 15.2 17.2 25.9 Total power consumption / operating current [kW]/[A] 5 / 9.8 5.6 / 11.4 8.3 / 16.9 Energy efficiency ratio EER 3 3.1 3.1
SPECIFICATION:
Phases/nominal voltage/frequency [~]/[V]/[Hz] 3/400/50 3/400/50 3/400/50 Output factor cos ϕ 0 .74 0.71 0.71 Fuse C20A C25A C25A Max. operating current [A] 16.8 21.1 24.8 Max. starting current/max. with soft start [A] 101 / 50.5 99 / 49.5 127 / 63.5 Sound power level/sound pressure level (at 1 m distance) [dBA] 49.5 / 41.5 55.5 / 47.5 55.5 / 47.5
52 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
i
i
AIR 23 C12A AIR 29 C12A AIR 41 C12A
ELECTRIC BOOSTER HEATER (M4-1, M4-3):
Phases/nominal voltage/frequency [~]/[V]/[Hz] 3/400/50 3/400/50 3/400/50 Max. output [kW] 8.8 (2.6 / 3.0 / 3.2) 8.8 (2.6 / 3.0 / 3.2) 8.8 (2.6 / 3.0 / 3.2) Max. operating current [A] 14 14 14
CONDENSER:
Type Plate heat exchanger Plate heat exchanger Plate heat exchanger Material Stainless steel 1.4301 Stainless steel 1.4301 Stainless steel 1.4301 Quantity [pcs] 1 1 1 Max. refrigerant operating pressure [bar] 30 30 30 Max. heat transfer medium operating pressure [bar] 3 3 3 Heat transfer medium temperature differential [K] 5 5 5 Application range [°C] 65 65 65 Heat transfer medium Water Water Water Test pressure [bar] 45 45 45 Heat transfer medium flow rate [m³/h] 3.4 4.4 6 Internal pressure differential [mbar] 330 464 820 Flow meter built-in built-in built-in Heat sink circulation pump (heat generator pump) internal Stratos Para 25/1-8 Stratos Para 25/1-8 Stratos Para 25/1-12 Residual head I heat sink system, external, incl. flow me­ter
REFRIGERANT CIRCUIT:
No. of refrigerant circuits [pcs] 1 1 1 Heat transfer medium R407C R407C R407C Refrigerant full charge [kg] 10.0 15.0 16.0 Defrost technology Hot gas Hot gas Hot gas
[mbar] 356 (M4-1)
452 (M4- 4)
113 (M4-1), 273 (M4- 4)
109 (M4-1), 40 6 (M 4-4)
COMPRESSOR:
Type Fully hermetic/scroll Fully hermetic/scroll Fully hermetic/scroll Quantity [pcs] 1 1 1 Output levels 1 1 1 Speed [rpm] 2900 2900 2900 Voltage/frequency [V ]/[Hz] 400 / 50 400 / 50 400 / 50 Max. operating current [A] 14 18.3 22
FAN (OUTDOOR UNIT):
Type Axial Axial Axial Quantity [pcs] 2 2 2 Voltage/frequency [V ]/[Hz] 230 / 50 230 / 50 230 / 50 Power consumption [W] 111 201 337 Max. operating current [A] 2.80 2.80 2.80
EVAPORATOR (OUTDOOR UNIT):
Appliance type VHS-M 19 VHS-M 25 VHS-M 35 Dimensions HxWxD [mm] 1080x2220x960 1080x2220x960 1080x2220x960 Type Finned pipe Finned pipe Finned pipe Quantity [pcs] 1 1 1 Weight [kg] 136 175 180 Fin pack material Copper/aluminium Copper/aluminium Copper/aluminium Casing material Stainless steel, coated Stainless steel, coated Stainless steel, coated Max. refrigerant operating pressure [bar] 30 30 30 Relative humidity [%] 80 80 80 Heat transfer medium temperature differential [K] 4 5.9 5.9 Air flow rate [m³/h] 8000 8000 9800 Application range min./max [°C] -24 / +40 -24 / +40 -24 / +40 Sound power level/sound pressure level [dBA] 54/26 58/30 61/33 Sound power level/sound pressure level (in silent mode) [dBA] 52 / 24 54/26 57/2 8
Information
Data on sound pressure levels refer to a distance of 10 m (free space). Sound pressure and sound power levels are given +/-3 dB(A).
Information
Silent mode offers four separate time windows during which the outdoor unit can be operated with reduced sound levels. It is set via the OTE controller.
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 53
INSTALLATION | Specication
14 .1.2 Output diagrams
AIR 7 C11A
9
Y
8
7
6
5
4
3
2
1
0
-25 -23 -21 -19 -17 -15 -13 -11 -9 -7 -5 -3 -1 1357 9 11 13 15 17 19 21 23 25
X Air temperature [°C] Y Heating output [kW], component tolerance/output tolerance ±10%
7
Y
6
5
4
3
4
Y
3
2
35°C
45°C
50°C
60°C
X
12_01_200_202_01_001 AIR_7_ C11A
2
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23
X
12_02_200_202_01_001 AIR_7_C11A
X Air temperature [°C] Y Coefcient of performance (COP), component toler-
ance/output tolerance ±10%
54 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23
X
X Air temperature [°C] Y Power consumption [kW], component tolerance/out-
put tolerance ±10%
12_03_200_202_01_001 AIR_7_C11A
INSTALL ATION | Specication
12_01_200_202_01_002 AIR_11_C11A
35°C
45°C
50°C 60°C
12_03_200_202_01_002 AIR_11_C11A
AIR 11 C 11A
15
Y
14
13
12
11
10
9
8
7
6
5
4
3
-25 -23 -21 -19 -17 -15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
X Air temperature [°C] Y Heating output [kW], component tolerance/output tolerance ±10%
Y
6
5
4
3
2
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23
X
X Air temperature [°C] Y Coefcient of performance (COP), component toler-
ance/output tolerance ±10%
12_02_200_202_01_002 AIR_11_C11A
4
Y
3
2
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23
X Air temperature [°C] Y Power consumption [kW], component tolerance/out-
put tolerance ±10%
X
X
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 55
INSTALLATION | Specication
35°C
45°C
50°C
60°C
AIR 18 C11A
21
Y
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
-25 -23 -21 -19 -17 -15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
X Air temperature [°C] Y Heating output [kW], component tolerance/output tolerance ±10%
7
Y
6
5
4
5
Y
4
3
X
12_01_200_202_01_003 AIR_18_C11A
3
2
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23 27
X
12_02_200_202_01_003 AIR_18_C11A
X Air temperature [°C] Y Coefcient of performance (COP), component toler-
ance/output tolerance ±10%
56 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
2
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23 27
X Air temperature [°C] Y Power consumption [kW], component tolerance/out-
put tolerance ±10%
X
12_03_200_202_01_003 AIR_18_C11A
INSTALL ATION | Specication
12_01_200_202_01_004 AIR_23_C12A
35°C
45°C
50°C
60°C
12_03_200_202_01_004 AIR_23_C12A
AIR 23 C12A
30
Y
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
-25 -23 -21 -19 -17 -15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
X
X Air temperature [°C] Y Heating output [kW], component tolerance/output tolerance ±10%
7
Y
6
5
4
3
2
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23 27
X
X Air temperature [°C] Y Coefcient of performance (COP), component toler-
ance/output tolerance ±10%
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 57
Y
7
6
5
4
3
2
1
0
12_02_200_202_01_004 AIR_23_C12A
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23 27
X Air temperature [°C] Y Power consumption [kW], component tolerance/out-
put tolerance ±10%
X
INSTALLATION | Specication
35°C
45°C
50°C 60°C
AIR 29 C12A
Y
37
36 35 34 33
32
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
16
15 14 13 12
11
10
9 8
-25-23-21-19-17-15-13-11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
X Air temperature [°C] Y Heating output [kW], component tolerance/output tolerance ±10%
X
12_01_200_202_01_005 AIR_29_C12A
7
Y
6
5
4
3
2
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23 27
X
X Air temperature [°C] Y Coefcient of performance (COP), component toler-
ance/output tolerance ±10%
58 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
Y
9
8
7
6
5
4
3
2
1
0
12_02_200_202_01_005 AIR_29_C12A
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23 27
X Air temperature [°C] Y Power consumption [kW], component tolerance/out-
put tolerance ±10%
X
12_03_200_202_01_005 AIR_29_C12A
INSTALL ATION | Specication
12_01_200_202_01_006 AIR_41_C12A
35°C
45°C
50°C
12_03_200_202_01_006 AIR_41_C12A
AIR 41 C12A
Y
56
54
52
50
48
46
44
42
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
-25 -23 -21 -19 -17 -15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25
60°C
X
X Air temperature [°C] Y Heating output [kW], component tolerance/output tolerance ±10%
Y
7
6
5
4
3
2
1
0
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23 27
X
X Air temperature [°C] Y Coefcient of performance (COP), component toler-
ance/output tolerance ±10%
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 59
Y
11 10
9 8 7 6 5 4 3 2 1 0
12_02_200_202_01_006 AIR_41_C12A
-25 -21 -17 -13 -9 -5 -1 3 7 11 15 19 23 27
X Air temperature [°C] Y Power consumption [kW], component tolerance/out-
put tolerance ±10%
X
INSTALLATION | Specication
14 .1.3 Details of energy consumption
Product data conform to EU Regulations on the Ecodesign of Energy Related Products (ErP).
AIR 7 C11A
LOW TEMPERATURE 35°C
A++ cooler medium warmer
ηs 151 169 196 Energy consumption [kWh] 2164 2237 1450 P rated [kW] 3 5 5 SCOP [-] 3.84 4.30 4.98
MEDIUM TEMPER ATURE 55 °C
A+ cooler medium warmer
ηs 109 124 143 Energy consumption [kWh] 3779 3293 179 6 P rated [kW] 4 5 5 SCOP [-] 2.80 3.17 3.65
DHW SP300
A cooler medium warmer
ηWH 85 93 107 Energy consumption [kWh] 1682 1537 13 34 Tap profile XL Cylinder loss [W] 94
AIR 18 C11A
LOW TEMPERATURE 35°C
A++ cooler medium warmer
ηs 168 185 215 Energy consumption [kWh] 5192 5289 3241 P rated [kW] 9 12 13 SCOP [-] 4.27 4.70 5.44
MEDIUM TEMPER ATURE 55 °C
A++ cooler medium warmer
ηs 122 136 158 Energy consumption [kWh] 7367 7683 4048 P rated [kW] 9 13 12 SCOP [-] 3.11 3.48 4.03
DHW SP500
A cooler medium warmer
ηWH 93 102 118 Energy consumption [kWh] 1486 1359 1179 Tap profile XL Cylinder loss [W] 117
indoor outdoor Sound power level [dBA] 4 7.5 54.0 Controller class, with remote
controller Controller class, without re-
mote controller
VII Controller contribu-
tion [%]
III Controller contribu-
tion [%]
3.5
1.5
indoor outdoor Sound power level [dBA] 40.9 48.0 Controller class, with remote
controller Controller class, without re-
mote controller
VII Controller contribu-
tion [%]
III Controller contribu-
tion [%]
3.5
1.5
AIR 11 C 11A
LOW TEMPERATURE 35°C
A++ cooler medium warmer
ηs 153 166 185 Energy consumption [kWh] 3239 3757 2509 P rated [kW] 5 8 9 SCOP [-] 3.90 4.21 4.69
MEDIUM TEMPER ATURE 55 °C
A++ cooler medium warmer
ηs 122 129 138 Energy consumption [kWh] 5589 5 412 3229 P rated [kW] 7 9 9 SCOP [-] 3.12 3.38 3.54
DHW SP300
A cooler medium warmer
ηWH 82 90 10 4 Energy consumption [kWh] 17 28 1580 1371 Tap profile XL Cylinder loss [W] 94
AIR 23 C12A
LOW TEMPERATURE 35°C
A++ cooler medium warmer
ηs 161 174 199 Energy consumption [kWh] 6821 7236 4558 P rated [kW] 11 16 17 SCOP [-] 4.11 4.43 5.04
MEDIUM TEMPER ATURE 55 °C
A++ cooler medium warmer
ηs 123 136 157 Energy consumption [kWh] 9 740 9600 5563 P rated [kW] 12 16 17 SCOP [-] 3.15 3.53 3.99
DHW SP500
A cooler medium warmer
ηWH 94 103 119 Energy consumption [kWh] 1478 13 51 117 2 Tap profile XL Cylinder loss [W] 117
indoor outdoor Sound power level [dBA] 49.5 54.0 Controller class, with remote
controller Controller class, without re-
mote controller
VII Controller contribu-
tion [%]
III Controller contribu-
tion [%]
3.5
1.5
indoor outdoor Sound power level [dBA] 44.5 52.0 Controller class, with remote
controller Controller class, without re-
mote controller
60 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
VII Controller contribu-
tion [%]
III Controller contribu-
tion [%]
3.5
1.5
INSTALL ATION | Specication
AIR 29 C12A
LOW TEMPERATURE 35°C
A++ cooler medium warmer
ηs 160 174 196 Energy consumption [kWh] 8791 8617 58 51 P rated [kW] 15 18 22 SCOP [-] 4.08 4.42 4.98
MEDIUM TEMPER ATURE 55 °C
A++ cooler medium warmer
ηs 128 138 156 Energy consumption [kWh] 13133 11613 7073 P rated [kW] 17 20 21 SCOP [-] 3.26 3.56 3.97
DHW SP500
A cooler medium warmer
ηWH 95 103 11 9 Energy consumption [kWh] 1469 1343 1165 Tap profile XL Cylinder loss [W] 117
indoor outdoor Sound power level [dBA] 55.5 58.0 Controller class, with remote
controller Controller class, without re-
mote controller
VII Controller contribu-
tion [%]
III Controller contribu-
tion [%]
3.5
1.5
AIR 41 C12A
LOW TEMPERATURE 35°C
A++ cooler medium warmer
ηs 156 170 195 Energy consumption [kWh] 140 62 1273 6 8163 P rated [kW] 23 27 30 SCOP [-] 3.97 4.33 4.96
MEDIUM TEMPER ATURE 55 °C
A++ cooler medium warmer
ηs 123 136 158 Energy consumption [kWh] 17392 14962 8927 P rated [kW] 22 25 27 SCOP [-] 3.14 3. 51 4.03
indoor outdoor Sound power level [dBA] 55.5 61.0 Controller class, with remote
controller Controller class, without re-
mote controller
VII Controller contribu-
tion [%]
III Controller contribu-
tion [%]
3.5
1.5
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 61
INSTALLATION | Specication
14.2 Heat pumps for single phase alternating current
14 . 2 .1 Data table
AI R 11 C11B AIR 18 C11B
INDOOR UNIT:
Hydraulic variant M2-1/M2-2/M2-3/M2-4 M2-1/M2-2/M2-3/M2- 4 Dimensions HxWxD [mm] 1286x600x680 1286x600x680 Hydraulic connection DN 32 (1 1/4”) male DN 32 (1 1/4”) male Weight [kg] 124 135 Casing colour Tiger white 29/11289/grey RAL
7016
HEATING MODE PERFORMANCE DATA:
Standard point L10/W35 Heating output [kW] 11.1 16.1 Total power consumption / operating current [kW]/[A] 2.5 / 12.9 3.4 / 20.8 Coefficient of per formance EN 14511/EN 255 4.4 / 4.7 4.8 / 5
Operating point L7/W35 Heating output [kW] 10.2 14.8 Total power consumption / operating current [kW]/[A] 2.4 / 12.4 3.3 / 20.5 Coefficient of per formance EN 14511/EN 255 4.3 / 4.5 4.5 / 4.8
Tiger white 29/11289/grey RAL
7016
Standard point A2/W35 Heating output [kW] 8.9 13 Total power consumption / operating current [kW]/[A] 2.3 / 11.6 3.2 / 19.9 Coefficient of per formance EN 14511/EN 255 4 / 4.2 4 / 4.3
Standard point L-7/W35 Heating output [kW] 6.9 10 .1 Total power consumption / operating current [kW]/[A] 2.2 / 11.5 3.2 / 19.9 Coefficient of per formance EN 14511/EN 255 3.1 / 3.3 3.1 / 3.3
Operating point L-10/W35 Heating output [kW] 6.3 9.2 Total power consumption / operating current [kW]/[A] 2.1 / 10.9 3.1 / 19.5 Coefficient of per formance EN 14511/EN 255 3 / 3.3 2.9 / 3.1
Operating point A2/W50 Heating output kW 8.5 12.3 Total power consumption / operating current [kW]/[A] 3 / 15.5 4.3 / 26.1 Coefficient of per formance EN 14511/EN 255 2.8 / 2.9 2.9 / 3.1
Operating point A2/W60 Heating output [kW] 8.4 11.5 Total power consumption / operating current [kW]/[A] 3.3 / 17.1 4.5 / 27.4 Coefficient of per formance EN 14511/EN 255 2.5 / 2.6 2.6 / 2.8
COOLING MODE PERFORMANCE DATA:
Operating point A30/ W18 Cooling capacity [kW] 9.5 9.9 Total power consumption / operating current [kW]/[A] 3.2 / 16.6 3.4 / 21.1 Energy efficiency ratio EER 3 2.9
Operating point A30/ W7 Cooling capacity [kW] 8.6 9.3 Total power consumption / operating current [kW]/[A] 3.1 / 16 3.4 / 21.1 Energy efficiency ratio EER 2.8 2.7
SPECIFICATION:
Phases/nominal voltage/frequency [~]/[V]/[Hz] 1/230/50 1/230/50 Output factor cos ϕ 0.84 0.71 Fuse C25A C40A Max. operating current [A] 20.8 30 Max. starting current/max. with soft start [A] 97 / 48.5 160/80 Sound power level/sound pressure level (at 1 m distance) [dBA] 44.5 / 36.5 47.5 / 39.5
62 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
i
i
AI R 11 C11B AIR 18 C11B
ELECTRIC BOOSTER HEATER (M2-1, M2-3):
Phases/nominal voltage/frequency [~]/[V]/[Hz] 1/230/50 1/230/50 Max. output [kW] 8.8 (2.9 / 2.9 / 2.9) 8.8 (2.9 / 2.9 / 2.9) Max. operating current [A] 38.3 (12.8 / 12.8 / 12.8) 38.3 (12.8 / 12.8 / 12.8)
CONDENSER:
Type Plate heat exchanger Plate heat exchanger Material Stainless steel 1.4301 Stainless steel 1.4301 Quantity [pcs] 1 1 Max. refrigerant operating pressure [bar] 30 30 Max. heat transfer medium operating pressure [bar] 3 3 Heat transfer medium temperature differential [K] 5 5 Application range [°C] 65 65 Heat transfer medium Water Water Test pressure [bar] 45 45 Heat transfer medium flow rate [m³/h] 1.7 2.2 Internal pressure differential [mbar] 205 324 Flow meter built-in built-in Heat sink circulation pump (heat generator pump) internal Yonos Para 25/7.5 Yonos Para 25/7.5 Residual head I heat sink system, external, incl. flow me­ter
REFRIGERANT CIRCUIT:
No. of refrigerant circuits [pcs] 1 1 Heat transfer medium R407C R407C Refrigerant full charge [kg] 9.0 9.0 Defrost technology Hot gas Hot gas
[mbar] 446 175
COMPRESSOR:
Type Fully hermetic/scroll Fully hermetic/scroll Quantity [pcs] 1 1 Output levels 1 1 Speed [rpm] 2900 2900 Voltage/frequency [V ]/[Hz] 230 / 50 230 / 50 Max. operating current [A] 19.4 28.6
FAN (OUTDOOR UNIT):
Type Axial Axial Quantity [pcs] 1 1 Voltage/frequency [V ]/[Hz] 230 / 50 230 / 50 Power consumption [W] 40 68 Max. operating current [A] 1.40 1.40
EVAPORATOR (OUTDOOR UNIT):
Appliance type VHS-M 9 VHS-M 14 Dimensions HxWxD [mm] 1080x1290x960 1080x1290x960 Type Finned pipe Finned pipe Quantity [pcs] 1 1 Weight [kg] 93 93 Fin pack material Copper/aluminium Copper/aluminium Casing material Stainless steel, coated Stainless steel, coated Max. refrigerant operating pressure [bar] 30 30 Relative humidity [%] 80 80 Heat transfer medium temperature differential [K] 5.7 5.7 Air flow rate [m³/h] 3000 4000 Application range min./max [°C] -24 / +40 -24 / +40 Sound power level/sound pressure level [dBA] 52/23 54/26 Sound power level/sound pressure level (in silent mode) [dBA] 49/20 51/23
Information
Data on sound pressure levels refer to operation at full load at a distance of 10 m (free space). Sound pressure and sound power levels are given +/-3 dB(A).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 63
Information
Silent mode offers four separate time windows during which the outdoor unit can be operated with reduced sound levels. It is set via the OTE controller.
INSTALLATION | Specication
14.2.2 Output diagrams
AIR 11 C 11B
15
Y
14
13
12
11
10
9
8
7
6
5
4
3
-23 -19 -15 -11 -7 -3 1 5 9 13 17 21 25
X Air temperature [°C] Y Heating output [kW], component tolerance/output tolerance ±10%
6
Y
4
Y
5
3
4
35°C
45°C
50°C
60°C
X
12_01_200_202_01_007 AIR_11_C11B
3
2
2
1
1
0
-25 -17 -9 -1 7 15 23
X
12_02_200_202_01_007 AIR_11_C11B
X Air temperature [°C] Y Coefcient of performance (COP), component toler-
ance/output tolerance ±10%
64 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
0
-25 -17 -9 -1 7 15 23
X
X Air temperature [°C] Y Power consumption [kW], component tolerance/out-
put tolerance ±10%
12_03_200_202_01_007 AIR_11_C11B
INSTALL ATION | Specication
12_01_200_202_01_008 AIR_18_C11B
12_03_200_202_01_008 AIR_18_C11B
AIR 18 C11B
21
Y
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
-23 -19 -15 -11 -7 -3 1 5 9 13 17 21 25
X Air temperature [°C] Y Heating output [kW], component tolerance/output tolerance ±10%
5
7
Y
6
Y
4
5
4
3
35°C
45°C
50°C
60°C
X
3
2
2
1
1
0
-21 -13 -5 3 11 19
27
X
12_02_200_202_01_008 AIR_18_C11B
X Air temperature [°C] Y Coefcient of performance (COP), component toler-
ance/output tolerance ±10%
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 65
0
-21 -13 -5 3 11 19 27
X Air temperature [°C] Y Power consumption [kW], component tolerance/out-
put tolerance ±10%
X
INSTALLATION | Specication
14.2.3 Details of energy consumption
Product data conform to EU Regulations on the Ecodesign of Energy Related Products (ErP).
AIR 11 C 11B
LOW TEMPERATURE 35°C
A++ cooler medium warmer
ηs 138 151 176 Energy consumption [kWh] 6228 6242 2654 P rated [kW] 9 12 9 SCOP [-] 3.52 3.84 4.48
MEDIUM TEMPER ATURE 55 °C
A+ cooler medium warmer
ηs 116 121 134 Energy consumption [kWh] 8045 7685 3267 P rated [kW] 10 11 8 SCOP [-] 2.96 3.30 3.44
DHW SP300
A cooler medium warmer
ηWH 83 90 104 Energy consumption [kWh] 1722 1574 1366 Tap profile XL Cylinder loss [W] 94
indoor outdoor Sound power level [dBA] 44.5 52.0 Controller class, with remote
controller Controller class, without re-
mote controller
VII Controller contribu-
tion [%]
III Controller contribu-
tion [%]
3.5
1.5
AIR 18 C11B
LOW TEMPERATURE 35°C
A++ cooler medium warmer
ηs 140 154 187 Energy consumption [kWh] 9140 8970 3649 P rated [kW] 13 17 13 SCOP [-] 3.59 3.93 4.76
MEDIUM TEMPER ATURE 55 °C
A++ cooler medium warmer
ηs 113 122 140 Energy consumption [kWh] 11 467 10910 4 514 P rated [kW] 13 16 12 SCOP [-] 2.90 3.34 3.58
DHW SP500
A cooler medium warmer
ηWH 83 91 105 Energy consumption [kWh] 1665 1522 1321 Tap profile XL Cylinder loss [W] 117
indoor outdoor Sound power level [dBA] 4 7.5 54.0 Controller class, with remote
controller Controller class, without re-
mote controller
66 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
VII Controller contribu-
tion [%]
III Controller contribu-
tion [%]
3.5
1.5
INSTALL ATION | Specication
12_04_200_202_01_001 AIR_7
12_04_200_202_01_001 AIR_11-41
14.3 Limits of use

Limits of use AIR 7 AIR 11/AIR 18/AIR 23/AIR 29/AIR 41

Outdoor temperature/max. heat pump flow temperature A 0 / W 65°C
Underfloor heating (-15°C / 35°C) Yes Yes
Radiators (-15°C / 55°C) Yes
(size the booster heater for 100%
Radiators (-15°C / 65°C) Yes
(size the booster heater for 100%
Domestic hot water Yes Ye s
A -5 / W 60°C
A -15 / W 50°C
of the heat load)
(size the booster heater for 100% of the heat
of the heat load)
AIR 7
A -10 / W 65°C A -15 / W 60°C A -20 / W 55°C
Yes
Yes
load)
Y
65
60
55
50
40
-23
-20 -15 -10
X Outdoor temperature [°C] Y Flow temperature [°C] 1 Flow temperature application limit for heat pump 2 Maximum ow temperature for conguration
AIR 11, AIR 18, AIR 23, AIR 29, AIR 41
Y
65
60
55
-5
1
2
5
0
10 15
20
X
1
2
50
40
-23
-20 -15 -10
-5
5
0
10 15
20
X
X Outdoor temperature [°C] Y Flow temperature [°C] 1 Flow temperature application limit for heat pump 2 Maximum ow temperature for conguration
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 67
INSTALLATION | Specication
14.4 System schematic diagrams
AIR 7, AIR 11, AIR 18 (M2-1)
I
19
16 17 18
15
3x1.5 4x1.5 3x1.5
2x1
EVU EVU
PE N L3 L2 L1
PE N L1
C
4242
NPE 16 15
N PE
8
43
7 NPE
X3
X1
X3
A
50 Hz
3x400V/N/PE
50Hz
230 V
EVU EVU
43
X3
PE N L
X1
PE N
21
L
X3
B
50 Hz
1x230V/N/PE
50Hz
230 V
50Hz
KM2
2x1
46
52
G
H
2x1 2x1 2x1 2x1
45
TK TK
X2
PE N L
X2
49 5040
GND
S2
3x400V/N/PE
KM2
9
8
7
50Hz
3x230V/N/PE
10
6
EVO
1 3 2 4
F
11 12 13 14
E
GN BN YE WH
2x1
44
GND
D
4-WH 2-YE 3-BN
1-GN
GND
S2
GND
50
GND
49
PE N L
TK TK
0-10VDC
5
4x1 2x1 4x1 2x1
3x1.5 2x1.5
03_200_202_01_000 M2-1
68 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
Key to system principle schematic for AIR 7, AIR 11 and AIR 18 (M2-1)
A Main distributor for 3-phase alternating current B Main distributor for single phase alternating current C Indoor unit control box D Outdoor unit terminal box E Outdoor unit F Indoor unit G DHW cylinder H Heat pump separating cylinders I Remote controller
1 Electric booster heater 2 Control circuit (OTE controller) 3 Main power circuit (compressor and fan) 4 PSU signal contact 5 0-10 VDC fan speed 6 Stepper motor of expansion valve A 7 Suction gas sensor S2 8 Defrost sensor (TQE, TQA) 9 Fan power supply 10 Fan fault message 11 Outdoor temperature sensor (TA) 12 Top buffer sensor (TPO) 13 Bottom buffer sensor (TPM) 14 DHW sensor (TB) 15 Heating circuit circulation pump 1, direct (HCP 1) 16 Mixer sensor (TMK) 17 Heating circuit circulation pump 2, mixed (HCP 2)
Power supply via high limit safety cut-out 18 Heating circuit mixing valve (MVH) 19 Control elements (eBus)
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 69
INSTALLATION | Specication
AIR 7, AIR 11, AIR 18 (M2-2)
I
19
16 17 18
15
3x1.5 4x1.5 3x1.5
2x1
EVU EVU
PE N L3 L2 L1
PE N L1
C
4242
NPE 16 15
N PE
8
43
7 NPE
X3
X1
X3
A
50 Hz
3x400V/N/PE
50Hz
230 V
EVU EVU
43
X3
PE N L
X1
PE N
21
L
X3
B
50 Hz
1x230V/N/PE
50Hz
230 V
50Hz
KM2
2x1
46
52
G
H
2x1 2x1 2x1 2x1
45
TK TK
X2
PE N L
X2
49 5040
GND
S2
3x400V/N/PE
KM2
9
8
7
50Hz
3x230V/N/PE
10
6
EVO
1 3 2 4
F
11 12 13 14
E
GN BN YE WH
2x1
44
GND
D
4-WH 2-YE 3-BN
1-GN
GND
S2
GND
50
GND
49
PE N L
TK TK
0-10VDC
5
4x1 2x1 4x1 2x1
3x1.5 2x1.5
03_200_202_01_006 M2-2
70 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
Key to system principle schematic for AIR 7, AIR 11 and AIR 18 (M2-2)
A Main distributor for 3-phase alternating current B Main distributor for single phase alternating current C Indoor unit control box D Outdoor unit terminal box E Outdoor unit F Indoor unit G DHW cylinder H Heat pump separating cylinders I Remote controller
1 Electric booster heater 2 Control circuit (OTE controller) 3 Main power circuit (compressor and fan) 4 PSU signal contact 5 0-10 VDC fan speed 6 Stepper motor of expansion valve A 7 Suction gas sensor S2 8 Defrost sensor (TQE, TQA) 9 Fan power supply 10 Fan fault message 11 Outdoor temperature sensor (TA) 12 Top buffer sensor (TPO) 13 Bottom buffer sensor (TPM) 14 DHW sensor (TB) 15 Heating circuit circulation pump 1, direct (HCP 1) 16 Mixer sensor (TMK) 17 Heating circuit circulation pump 2, mixed (HCP 2)
Power supply via high limit safety cut-out 18 Heating circuit mixing valve (MVH) 19 Control elements (eBus)
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 71
INSTALLATION | Specication
AIR 7, AIR 11, AIR 18 (M2-3)
I
19
16 17 18
15
3x1.5 4x1.5 3x1.5
2x1
EVU EVU
PE N L3 L2 L1
PE N L1
C
4242
NPE 16 15
N PE
8
43
7 NPE
X3
X1
X3
A
50 Hz
3x400V/N/PE
50Hz
230 V
EVU EVU
43
X3
PE N L
X1
PE N
21
L
X3
B
50 Hz
1x230V/N/PE
50Hz
230 V
50Hz
KM2
14
2x1
46
52
G
H
2x1 2x1 2x1 2x1
3x1.5
45
NPE 14 13
TK TK
X2
PE N L
X2
49 5040
GND
S2
3x400V/N/PE
KM2
9
8
7
50Hz
3x230V/N/PE
10
6
EVO
1 3 2 4
F
11 12 13
E
GN BN YE WH
2x1
44
GND
D
4-WH 2-YE 3-BN
1-GN
GND
S2
GND
50
GND
49
PE N L
TK TK
0-10VDC
5
4x1 2x1 4x1 2x1
3x1.5 2x1.5
03_200_202_01_005 AIR_M2-3
72 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
Key to system principle schematic for AIR 7, AIR 11 and AIR 18 (M2-3)
A Main distributor for 3-phase alternating current B Main distributor for single phase alternating current C Indoor unit control box D Outdoor unit terminal box E Outdoor unit F Indoor unit G DHW cylinder H Heat pump separating cylinders I Remote controller
1 Electric booster heater 2 Control circuit (OTE controller) 3 Main power circuit (compressor and fan) 4 PSU signal contact 5 0-10 VDC fan speed 6 Stepper motor of expansion valve A 7 Suction gas sensor S2 8 Defrost sensor (TQE, TQA) 9 Fan power supply 10 Fan fault message 11 Outdoor temperature sensor (TA) 12 Top buffer sensor (TPO) 13 Bottom buffer sensor (TPM) 14 DHW sensor (TB) 15 Heating circuit circulation pump 1, direct (HCP 1) 16 Mixer sensor (TMK) 17 Heating circuit circulation pump 2, mixed (HCP 2)
Power supply via high limit safety cut-out 18 Heating circuit mixing valve (MVH) 19 Control elements (eBus)
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 73
INSTALLATION | Specication
AIR 7, AIR 11, AIR 18 (M2-4)
I
19
16 17 18
15
3x1.5 4x1.5 3x1.5
2x1
EVU EVU
PE N L3 L2 L1
PE N L1
C
4242
NPE 16 15
N PE
8
43
7 NPE
X3
X1
X3
A
50 Hz
3x400V/N/PE
50Hz
230 V
EVU EVU
43
X3
PE N L
X1
PE N
21
L
X3
B
50 Hz
1x230V/N/PE
50Hz
230 V
50Hz
KM2
2x1
46
52
G
H
2x1 2x1 2x1 2x1
3x1.5
45
NPE 14 13
TK TK
X2
PE N L
X2
49 5040
GND
S2
3x400V/N/PE
KM2
9
8
7
50Hz
3x230V/N/PE
10
6
EVO
1 3 2 4
F
11 12 13 14
E
GN BN YE WH
2x1
44
GND
D
4-WH 2-YE 3-BN
1-GN
GND
S2
GND
50
GND
49
PE N L
TK TK
0-10VDC
5
4x1 2x1 4x1 2x1
3x1.5 2x1.5
03_200_202_01_007 M2-4
74 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
Key to system principle schematic for AIR 7, AIR 11 and AIR 18 (M2-4)
A Main distributor for 3-phase alternating current B Main distributor for single phase alternating current C Indoor unit control box D Outdoor unit terminal box E Outdoor unit F Indoor unit G DHW cylinder H Heat pump separating cylinders I Remote controller
1 Electric booster heater 2 Control circuit (OTE controller) 3 Main power circuit (compressor and fan) 4 PSU signal contact 5 0-10 VDC fan speed 6 Stepper motor of expansion valve A 7 Suction gas sensor S2 8 Defrost sensor (TQE, TQA) 9 Fan power supply 10 Fan fault message 11 Outdoor temperature sensor (TA) 12 Top buffer sensor (TPO) 13 Bottom buffer sensor (TPM) 14 DHW sensor (TB) 15 Heating circuit circulation pump 1, direct (HCP 1) 16 Mixer sensor (TMK) 17 Heating circuit circulation pump 2, mixed (HCP 2)
Power supply via high limit safety cut-out 18 Heating circuit mixing valve (MVH) 19 Control elements (eBus)
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 75
INSTALLATION | Specication
AIR 23, AIR 29, AIR 41 (M4-1)
I
19
16 17 18
15
3x1.5 4x1.5 3x1.5
2x1
EVU EVU
PE N L3 L2 L1
PE N L1
C
4242
NPE 16 15
N PE
8
43
7 NPE
X3
X1
X3
A
50 Hz
3x400V/N/PE
50Hz
230 V
EVU EVU
43
X3
PE N L
X1
PE N
21
L
X3
B
50 Hz
1x230V/N/PE
50Hz
230 V
50Hz
KM2
14
2x1
46
52
G
H
2x1 2x1 2x1 2x1
45
TK TK
X2
PE N L
X2
49 5040
GND
S2
3x400V/N/PE
KM2
9
8
7
50Hz
3x230V/N/PE
10
6
EVO
1 3 2 4
F
11 12 13
E
GN BN YE WH
2x1
44
GND
D
4-WH 2-YE 3-BN
1-GN
GND
S2
GND
50
GND
49
PE N L
TK TK
0-10VDC
5
4x1 2x1 4x1 2x1
3x1.5 2x1.5
03_200_202_01_001 M4-1
76 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
Key to system principle schematic for AIR 23, AIR 29 and AIR 41 (M4-1)
A Main distributor for 3-phase alternating current B Main distributor for single phase alternating current C Indoor unit control box D Outdoor unit terminal box E Outdoor unit F Indoor unit G DHW cylinder H Heat pump separating cylinders I Remote controller
1 Electric booster heater 2 Control circuit (OTE controller) 3 Main power circuit (compressor and fan) 4 PSU signal contact 5 0-10 VDC fan speed 6 Stepper motor of expansion valve A 7 Suction gas sensor S2 8 Defrost sensor (TQE, TQA) 9 Fan power supply 10 Fan fault message 11 Outdoor temperature sensor (TA) 12 Top buffer sensor (TPO) 13 Bottom buffer sensor (TPM) 14 DHW sensor (TB) 15 Heating circuit circulation pump 1, direct (HCP 1) 16 Mixer sensor (TMK) 17 Heating circuit circulation pump 2, mixed (HCP 2)
Power supply via high limit safety cut-out 18 Heating circuit mixing valve (MVH) 19 Control elements (eBus)
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 77
INSTALLATION | Specication
AIR 23, AIR 29, AIR 41 (M4-2)
I
19
16 17 18
15
20
3x1.5 4x1.5 3x1.5
2x1
KM4
EVU EVU
PE N L3 L2 L1
PE N L1
X3
X1
X3
N
KM2
C
4242
NPE 16 15
N PE
8
43
7 NPE
10
A
50 Hz
3x400V/N/PE
50Hz
230 V
50Hz
3x400V/N/PE
EVU EVU
43
X3
PE N L
X1
PE N
21
L
X3
KM2
B
50 Hz
1x230V/N/PE
50Hz
230 V
50Hz
3x230V/N/PE
2x1
46
13 14
52
G
H
2x1 2x1 2x1 2x1
45
TK TK
X2
PE N L
X2
49 5040
GND
S2
7
10
9
8
6
EVO
1 3 2 4
F
11 12
E
GN BN YE WH
2x1
44
GND
D
4-WH 2-YE 3-BN
1-GN
GND
S2
GND
50
GND
49
PE N L
TK TK
0-10VDC
5
2x1
4x1 2x1 4x1
3x1.5 2x1.5
03_200_202_01_002 M4-2
78 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
Key to system principle schematic for AIR 23, AIR 29 and AIR 41 (M4-2)
A Main distributor for 3-phase alternating current B Main distributor for single phase alternating current C Indoor unit control box D Outdoor unit terminal box E Outdoor unit F Indoor unit G DHW cylinder H Heat pump separating cylinders I Remote controller
1 Electric booster heater 2 Control circuit (OTE controller) 3 Main power circuit (compressor and fan) 4 PSU signal contact 5 0-10 VDC fan speed 6 Stepper motor of expansion valve A 7 Suction gas sensor S2 8 Defrost sensor (TQE, TQA) 9 Fan power supply 10 Fan fault message 11 Outdoor temperature sensor (TA) 12 Top buffer sensor (TPO) 13 Bottom buffer sensor (TPM) 14 DHW sensor (TB) 15 Heating circuit circulation pump 1, direct (HCP 1) 16 Mixer sensor (TMK) 17 Heating circuit circulation pump 2, mixed (HCP 2)
Power supply via high limit safety cut-out 18 Heating circuit mixing valve (MVH) 19 Control elements (eBus) 20 DHW auxiliary heater
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 79
INSTALLATION | Specication
AIR 23, AIR 29, AIR 41 (M4-3)
I
19
16 17 18
15
3x1.5 4x1.5 3x1.5
2x1
EVU EVU
PE N L3 L2 L1
PE N L1
C
4242
NPE 16 15
N PE
8
43
7 NPE
X3
X1
X3
A
50 Hz
3x400V/N/PE
50Hz
230 V
EVU EVU
43
X3
PE N L
X1
PE N
21
L
X3
B
50 Hz
1x230V/N/PE
50Hz
230 V
50Hz
KM2
14
2x1
46
52
G
H
2x1 2x1 2x1 2x1
3x1.5
45
NPE 14 13
TK TK
X2
PE N L
X2
49 5040
GND
S2
3x400V/N/PE
KM2
9
8
7
50Hz
3x230V/N/PE
10
6
EVO
1 3 2 4
F
11 12 13
E
GN BN YE WH
2x1
44
GND
D
4-WH 2-YE 3-BN
1-GN
GND
S2
GND
50
GND
49
PE N L
TK TK
0-10VDC
5
4x1 2x1 4x1 2x1
3x1.5 2x1.5
03_200_202_01_003 M4-3
80 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
Key to system principle schematic for AIR 23, AIR 29 and AIR 41 (M4-3)
A Main distributor for 3-phase alternating current B Main distributor for single phase alternating current C Indoor unit control box D Outdoor unit terminal box E Outdoor unit F Indoor unit G DHW cylinder H Heat pump separating cylinders I Remote controller
1 Electric booster heater 2 Control circuit (OTE controller) 3 Main power circuit (compressor and fan) 4 PSU signal contact 5 0-10 VDC fan speed 6 Stepper motor of expansion valve A 7 Suction gas sensor S2 8 Defrost sensor (TQE, TQA) 9 Fan power supply 10 Fan fault message 11 Outdoor temperature sensor (TA) 12 Top buffer sensor (TPO) 13 Bottom buffer sensor (TPM) 14 DHW sensor (TB) 15 Heating circuit circulation pump 1, direct (HCP 1) 16 Mixer sensor (TMK) 17 Heating circuit circulation pump 2, mixed (HCP 2)
Power supply via high limit safety cut-out 18 Heating circuit mixing valve (MVH) 19 Control elements (eBus)
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 81
INSTALLATION | Specication
AIR 23, AIR 29, AIR 41 (M4-4)
I
19
16 17 18
15
20
14
3x1.5 4x1.5 3x1.5
2x1
KM4
2x1
EVU EVU
PE N L3 L2 L1
PE N L1
X3
X1
X3
N
KM2
C
4242
NPE 16 15
N PE
8
43
7 NPE
10
46
A
50 Hz
3x400V/N/PE
50Hz
230 V
50Hz
3x400V/N/PE
EVU EVU
43
X3
PE N L
X1
PE N
21
L
X3
KM2
B
50 Hz
1x230V/N/PE
50Hz
230 V
50Hz
3x230V/N/PE
52
G
H
2x1 2x1 2x1 2x1
3x1.5
45
NPE 14 13
TK TK
X2
PE N L
X2
49 5040
GND
S2
7
10
9
8
6
EVO
1 3 2 4
F
11 12 13
E
GN BN YE WH
2x1
44
GND
D
4-WH 2-YE 3-BN
1-GN
GND
S2
GND
50
GND
49
PE N L
TK TK
0-10VDC
5
4x1 2x1 4x1 2x1
3x1.5 2x1.5
03_200_202_01_004 M4-4
82 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
Key to system principle schematic for AIR 23, AIR 29 and AIR 41 (M4-4)
A Main distributor for 3-phase alternating current B Main distributor for single phase alternating current C Indoor unit control box D Outdoor unit terminal box E Outdoor unit F Indoor unit G DHW cylinder H Heat pump separating cylinders I Remote controller
1 Electric booster heater 2 Control circuit (OTE controller) 3 Main power circuit (compressor and fan) 4 PSU signal contact 5 0-10 VDC fan speed 6 Stepper motor of expansion valve A 7 Suction gas sensor S2 8 Defrost sensor (TQE, TQA) 9 Fan power supply 10 Fan fault message 11 Outdoor temperature sensor (TA) 12 Top buffer sensor (TPO) 13 Bottom buffer sensor (TPM) 14 DHW sensor (TB) 15 Heating circuit circulation pump 1, direct (HCP 1) 16 Mixer sensor (TMK) 17 Heating circuit circulation pump 2, mixed (HCP 2)
Power supply via high limit safety cut-out 18 Heating circuit mixing valve (MVH) 19 Control elements (eBus) 20 DHW auxiliary heater
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 83
INSTALLATION | Specication
14.5 Voltage quality in island mode
The following table shows voltage quality requirements in island mode (in mains mode, the relevant standards apply):
Harmonic Maximum proportion
2 2.00%
3 5.00%
4 1.00%
5 6.00%
6 0.50%
7 5.00%
8 0.50%
9 1.50%
10 0.50%
11 3.50%
12 0.50%
13 3.00%
14 0.50%
15 0.50%
16 0.50%
17 2.00%
18 0.50%
19 1.50%
20 0.50%
21 0.50%
22 0.50%
23 1.5 0%
25 1.50%
>25 0.50%
► Total harmonic content (THC) 8%
► Frequency 49.5 Hz to 50.5 Hz
► Slow voltage changes 230 VAC ± 10% (integration
interval 10 min)
► Rapid voltage changes 230 VAC ± 5% (integration
interval 10 ms)
► Voltage asymmetry 2%
84 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Specication
11_03_200_202_01_001
14.6 Dimensions and connections
14 . 6.1 Indoor unit
1
1286
1200
2
3
60
4
5
130
105
105
90
6 7 8
1344
1223
9
717
588,7
60
248
430 600
541 680 721
10
~9cm²
32,5
1 Carrying handles (removable) 2 Cable entries 3 Connections (optionally vertical with exit at top or horizontal with exit at rear) 4 Liquid line (refrigerant) 5 Suction gas line (refrigerant) 6 Heating water/DHW return 7 DHW ow 8 Heating water ow 9 Safety valve drain 10 Plastic glide (height-adjustable, 4 pcs)
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 85
INSTALLATION | Specication
14.6.2 Outdoor unit
Outdoor unit for AIR 7, AIR 11 and AIR 18
80
70
A
1112
905
10,5
19,5
Ø14
19,5
30
47,8
10,5
90
140,3
A
1261
45±5
Ø850
1
2
951,5
180
1292
232±5
320±5
645±5
VHS-M 5, VHS-M 9, VHS-M 14
965
1 Suction gas line 2 Liquid line
86 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_03_200_504_01_001
INSTALL ATION | Specication
11_03_200_504_01_002
Outdoor unit for AIR 23
85
50
A
2040
A
905
1261
951,5
19,5
10,5
1
35±5
14
Ø
90
140,3
Ø850
30
19,5
10,5
47,8
2
180
2224
207±5
360±5
595±5
VHS-M 19
965
1 Suction gas line 2 Liquid line
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 87
INSTALLATION | Specication
Outdoor unit for AIR 29 and AIR 41
70
60
A
2040
A
951,5
905
1261
19,5
1
10,5
14
Ø
90
140,3
Ø850
2
30
19,5
10,5
47,8
180
2224
210±5
370±5
440±5
520±5
590±5
VHS-M 25, VHS-M 35
965
1 Suction gas line 2 Liquid line
88 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_03_200_504_01_003
INSTALL ATION | Specication
11_03_200_504_01_004
Outdoor unit with Super Silent Paket (SSP)
Ø 840
Ø 809,50
965
1 Cylindrical silencer 2 SSP snow cover
2
1
1696
1406,5
952
2224
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 89
INSTALLATION | Environment and recycling
i
15. Environment and recycling
Disposal of transport packaging
Your appliance has been carefully packed for transporta­tion. Please help to protect the environment by ensuring that transport packaging is disposed of properly and pro­fessionally. The transport packaging for this appliance consists of recyclable raw materials. Waste transport packaging should be sorted and recycled. Leave disposal of transport packaging to the contractor or system installer who has installed the appliance.
Disposal of the appliance
Dispose of the appliance properly and professionally at a regional waste collection facility. Observe environmental regulations and standards applicable to your region.
Information
The heat pump must not be put into the household waste.
The appliance is not covered by the Electrical and Electron­ic Appliances Act [Austria]. The appliance is not intended for disposal free of charge at a local collection facility.
R407C refrigerant
The refrigerant circuit of this appliance is lled with R407C
refrigerant. R407C refrigerant is a uorinated greenhouse gas listed in the Kyoto Protocol. R407C refrigerant may not be discharged into the atmosphere.
90 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | Declaration of Conformity
16. Declaration of Conformity
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 91
INSTALLATION | Declaration of Conformity
92 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | ERP-Data

17. ERP-Data

Model: AIR 7
Air-to-water heat pump: yes
Water-to-water heat pump: no
Brine-to-water heat pump: no
Low-temperature heat pump: no
Equipped with a supplementary heater: no
Heat pump combination heater: no
Temperature application: medium
Climate conditions: average
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Praded 5 kW
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature T
j
Seasonal space heating energy effi­ciency
η
s
Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature T
Tj = -7 °C Pdh 3.8 kW Tj = -7 °C COPd 2 .18
T
= +2 °C Pdh 5 .1 kW Tj = +2 °C COPd 3.22
j
T
= +7 °C Pdh 6 .1 kW Tj = +7 °C COPd 4.07
j
T
= +12 °C Pdh 6.9 kW Tj = +12 °C COPd 4.81
j
T
= bivalent temperature Pdh 4.1 kW Tj = bivalent temperature COPd 2.43
j
T
=
j
For air-to-water heat pumps:
T
= -15 °C (if TOL < - 20 ºC) Tj = -15 °C (if TOL < - 20 ºC)
j
Bivalent temperature T
Power input „compressor off“ 0 W
operation limit tempe­rature
Pdh 3.3 kW Tj =
For air-to-water heat pumps:For air-
Pdh 2.6 kW
biv
-5 °C
to-water heat pumps:
For air-to-water heat pumps:
Operation limit temperature
Heating water operating limit temperature
operation limit tempe­rature
COPd 1. 85
COPd 1. 36
TOL -14 °C
WTOL 65 °C
Power consumption in modes other than active mode Supplementary heater
Off mode P
Thermostat-off mode P
Crankcase heater mode P
OFF
TO
SB
CK
20 kW Rated heat output (*) Psup 1.75 kW
20 kW
20 kW
Type of energy input electricityStandby mode P
0 kW
Other items
Capacity control fixed For air-to-water heat pumps:
Sound power level
indoors
outdoors 48
Annual energy consumption Q
L
WA
HE
40.9 dB
3293 kWh
Rated air flow rate, outdoors
For water-/brine-to-water heat pumps:
Rated brine or water flow rate, out­door heat exchanger
2100 m
m
For heat pump combination heater:
Declared load profile Water heating energy effi ciency η
Daily electricity consumption Q
elec
kWh Daily fuel consumption Q
wh
fuel
124 %
j
%
kWh
3
/h
3
/h
Contact details: OCHSNER Wärmepumpen GmbH, Ochsner-Straße 1, A-3350 Haag
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heatingPde­signh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 93
INSTALLATION | ERP-Data
Model: AIR 11
Air-to-water heat pump: yes
Water-to-water heat pump: no
Brine-to-water heat pump: no
Low-temperature heat pump: no
Equipped with a supplementary heater: no
Heat pump combination heater: no
Temperature application: medium
Climate conditions: average
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Praded 9 kW
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature T
j
Seasonal space heating energy effi­ciency
η
s
Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature T
Tj = -7 °C Pdh 7. 2 kW Tj = -7 °C COPd 2.60
T
= +2 °C Pdh 8.7 kW Tj = +2 °C COPd 3.32
j
T
= +7 °C Pdh 9.9 kW Tj = +7 °C COPd 3.81
j
T
= +12 °C Pdh 11.3 kW Tj = +12 °C COPd 4.44
j
T
= bivalent temperature Pdh 7.3 kW Tj = bivalent temperature COPd 2.68
j
T
=
j
For air-to-water heat pumps:
T
= -15 °C (if TOL < - 20 ºC) Tj = -15 °C (if TOL < - 20 ºC)
j
Bivalent temperature T
Power input „compressor off“ 0 W
operation limit tempe­rature
Pdh 6.8 kW Tj =
For air-to-water heat pumps:For air-
Pdh 6.4 kW
biv
-6 °C
to-water heat pumps:
For air-to-water heat pumps:
Operation limit temperature
Heating water operating limit temperature
operation limit tempe­rature
COPd 2.38
COPd 2.08
TOL -15 °C
WTOL 65 °C
Power consumption in modes other than active mode Supplementary heater
Off mode P
Thermostat-off mode P
Crankcase heater mode P
OFF
TO
SB
CK
20 kW Rated heat output (*) Psup 1.83 kW
20 kW
20 kW
Type of energy input electricityStandby mode P
0 kW
Other items
Capacity control fixed For air-to-water heat pumps:
Sound power level
indoors
outdoors 50.4
Annual energy consumption Q
L
WA
HE
44.5 dB
5412 kWh
Rated air flow rate, outdoors
For water-/brine-to-water heat pumps:
Rated brine or water flow rate, out­door heat exchanger
5700 m
m
For heat pump combination heater:
Declared load profile Water heating energy effi ciency η
Daily electricity consumption Q
elec
kWh Daily fuel consumption Q
wh
fuel
129 %
j
%
kWh
3
/h
3
/h
Contact details: OCHSNER Wärmepumpen GmbH, Ochsner-Straße 1, A-3350 Haag
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heatingPde­signh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
94 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | ERP-Data
Model: AIR 18
Air-to-water heat pump: yes
Water-to-water heat pump: no
Brine-to-water heat pump: no
Low-temperature heat pump: no
Equipped with a supplementary heater: no
Heat pump combination heater: no
Temperature application: medium
Climate conditions: average
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Praded 13 kW
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature T
j
Seasonal space heating energy effi­ciency
η
s
Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature T
Tj = -7 °C Pdh 9.8 kW Tj = -7 °C COPd 2.43
T
= +2 °C Pdh 12.7 kW Tj = +2 °C COPd 3.50
j
T
= +7 °C Pdh 14.8 kW Tj = +7 °C COPd 4.32
j
T
= +12 °C Pdh 16.3 kW Tj = +12 °C COPd 5 .11
j
T
= bivalent temperature Pdh 10.4 kW Tj = bivalent temperature COPd 2.69
j
T
=
j
For air-to-water heat pumps:
T
= -15 °C (if TOL < - 20 ºC) Tj = -15 °C (if TOL < - 20 ºC)
j
Bivalent temperature T
Power input „compressor off“ 0 W
operation limit tempe­rature
Pdh 8.7 kW Tj =
For air-to-water heat pumps:For air-
Pdh 7. 0 kW
biv
-5 °C
to-water heat pumps:
For air-to-water heat pumps:
Operation limit temperature
Heating water operating limit temperature
operation limit tempe­rature
COPd 2.08
COPd 1. 56
TOL -15 °C
WTOL 65 °C
Power consumption in modes other than active mode Supplementary heater
Off mode P
Thermostat-off mode P
Crankcase heater mode P
OFF
TO
SB
CK
20 kW Rated heat output (*) Psup 4.19 kW
20 kW
20 kW
Type of energy input electricityStandby mode P
0 kW
Other items
Capacity control fixed For air-to-water heat pumps:
Sound power level
indoors
outdoors 54
Annual energy consumption Q
L
WA
HE
47. 5 dB
7683 kWh
Rated air flow rate, outdoors
For water-/brine-to-water heat pumps:
Rated brine or water flow rate, out­door heat exchanger
4000 m
m
For heat pump combination heater:
Declared load profile Water heating energy effi ciency η
Daily electricity consumption Q
elec
kWh Daily fuel consumption Q
wh
fuel
136 %
j
%
kWh
3
/h
3
/h
Contact details: OCHSNER Wärmepumpen GmbH, Ochsner-Straße 1, A-3350 Haag
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heatingPde­signh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 95
INSTALLATION | ERP-Data
Model: AIR 23
Air-to-water heat pump: yes
Water-to-water heat pump: no
Brine-to-water heat pump: no
Low-temperature heat pump: no
Equipped with a supplementary heater: no
Heat pump combination heater: no
Temperature application: medium
Climate conditions: average
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Praded 16 kW
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature T
j
Seasonal space heating energy effi­ciency
η
s
Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature T
Tj = -7 °C Pdh 13.2 kW Tj = -7 °C COPd 2.55
T
= +2 °C Pdh 16.9 kW Tj = +2 °C COPd 3. 47
j
T
= +7 °C Pdh 20.5 kW Tj = +7 °C COPd 4.08
j
T
= +12 °C Pdh 2 4.1 kW Tj = +12 °C COPd 4.94
j
T
= bivalent temperature Pdh 13.6 kW Tj = bivalent temperature COPd 2.66
j
T
=
j
For air-to-water heat pumps:
T
= -15 °C (if TOL < - 20 ºC) Tj = -15 °C (if TOL < - 20 ºC)
j
Bivalent temperature T
Power input „compressor off“ 0 W
operation limit tempe­rature
Pdh 11.9 kW Tj =
For air-to-water heat pumps:For air-
Pdh 9.8 kW
biv
-6 °C
to-water heat pumps:
For air-to-water heat pumps:
Operation limit temperature
Heating water operating limit temperature
operation limit tempe­rature
COPd 2.24
COPd 1.76
TOL -15 °C
WTOL 65 °C
Power consumption in modes other than active mode Supplementary heater
Off mode P
Thermostat-off mode P
Crankcase heater mode P
OFF
TO
SB
CK
20 kW Rated heat output (*) Psup 4.15 kW
20 kW
20 kW
Type of energy input electricityStandby mode P
0 kW
Other items
Capacity control fixed For air-to-water heat pumps:
Sound power level
indoors
outdoors 54
Annual energy consumption Q
L
WA
HE
49.5 dB
9600 kWh
Rated air flow rate, outdoors
For water-/brine-to-water heat pumps:
Rated brine or water flow rate, out­door heat exchanger
8000 m
m
For heat pump combination heater:
Declared load profile Water heating energy effi ciency η
Daily electricity consumption Q
elec
kWh Daily fuel consumption Q
wh
fuel
136 %
j
%
kWh
3
/h
3
/h
Contact details: OCHSNER Wärmepumpen GmbH, Ochsner-Straße 1, A-3350 Haag
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heatingPde­signh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
96 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
INSTALL ATION | ERP-Data
Model: AIR 29
Air-to-water heat pump: yes
Water-to-water heat pump: no
Brine-to-water heat pump: no
Low-temperature heat pump: no
Equipped with a supplementary heater: no
Heat pump combination heater: no
Temperature application: medium
Climate conditions: average
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Praded 20 kW
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature T
j
Seasonal space heating energy effi­ciency
η
s
Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature T
Tj = -7 °C Pdh 17. 5 kW Tj = -7 °C COPd 2.68
T
= +2 °C Pdh 21.4 kW Tj = +2 °C COPd 3.48
j
T
= +7 °C Pdh 25.6 kW Tj = +7 °C COPd 4.10
j
T
= +12 °C Pdh 29.2 kW Tj = +12 °C COPd 4.79
j
T
= bivalent temperature Pdh 17.5 kW Tj = bivalent temperature COPd 2.68
j
T
=
j
For air-to-water heat pumps:
T
= -15 °C (if TOL < - 20 ºC) Tj = -15 °C (if TOL < - 20 ºC)
j
Bivalent temperature T
Power input „compressor off“ 0 W
operation limit tempe­rature
Pdh 16.3 kW Tj =
For air-to-water heat pumps:For air-
Pdh 14.6 kW
biv
-7 °C
to-water heat pumps:
For air-to-water heat pumps:
Operation limit temperature
Heating water operating limit temperature
operation limit tempe­rature
COPd 2.43
COPd 2.06
TOL -15 °C
WTOL 65 °C
Power consumption in modes other than active mode Supplementary heater
Off mode P
Thermostat-off mode P
Crankcase heater mode P
OFF
TO
SB
CK
20 kW Rated heat output (*) Psup 3.45 kW
20 kW
20 kW
Type of energy input electricityStandby mode P
0 kW
Other items
Capacity control fixed For air-to-water heat pumps:
Sound power level
indoors
outdoors 58
Annual energy consumption Q
L
WA
HE
55.5 dB
11613 kWh
Rated air flow rate, outdoors
For water-/brine-to-water heat pumps:
Rated brine or water flow rate, out­door heat exchanger
8000 m
m
For heat pump combination heater:
Declared load profile Water heating energy effi ciency η
Daily electricity consumption Q
elec
kWh Daily fuel consumption Q
wh
fuel
138 %
j
%
kWh
3
/h
3
/h
Contact details: OCHSNER Wärmepumpen GmbH, Ochsner-Straße 1, A-3350 Haag
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heatingPde­signh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 97
INSTALLATION | ERP-Data
Model: AI R 41
Air-to-water heat pump: yes
Water-to-water heat pump: no
Brine-to-water heat pump: no
Low-temperature heat pump: no
Equipped with a supplementary heater: no
Heat pump combination heater: no
Temperature application: medium
Climate conditions: average
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output (*) Praded 25 kW
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature T
j
Seasonal space heating energy effi­ciency
η
s
Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature T
Tj = -7 °C Pdh 22.2 kW Tj = -7 °C COPd 2.54
T
= +2 °C Pdh 28.5 kW Tj = +2 °C COPd 3.44
j
T
= +7 °C Pdh 35.9 kW Tj = +7 °C COPd 4.11
j
T
= +12 °C Pdh 41.2 kW Tj = +12 °C COPd 4.84
j
T
= bivalent temperature Pdh 22.2 kW Tj = bivalent temperature COPd 2.54
j
T
=
j
For air-to-water heat pumps:
T
= -15 °C (if TOL < - 20 ºC) Tj = -15 °C (if TOL < - 20 ºC)
j
Bivalent temperature T
Power input „compressor off“ 0 W
operation limit tempe­rature
Pdh 20.0 kW Tj =
For air-to-water heat pumps:For air-
Pdh 16.2 kW
biv
-7 °C
to-water heat pumps:
For air-to-water heat pumps:
Operation limit temperature
Heating water operating limit temperature
operation limit tempe­rature
COPd 2.23
COPd 1.75
TOL -15 °C
WTOL 65 °C
Power consumption in modes other than active mode Supplementary heater
Off mode P
Thermostat-off mode P
Crankcase heater mode P
OFF
TO
SB
CK
20 kW Rated heat output (*) Psup 5.14 kW
20 kW
20 kW
Type of energy input electricityStandby mode P
0 kW
Other items
Capacity control fixed For air-to-water heat pumps:
Sound power level
indoors
outdoors 61
Annual energy consumption Q
L
WA
HE
55.5 dB
14962 kWh
Rated air flow rate, outdoors
For water-/brine-to-water heat pumps:
Rated brine or water flow rate, out­door heat exchanger
9800 m
m
For heat pump combination heater:
Declared load profile Water heating energy effi ciency η
Daily electricity consumption Q
elec
kWh Daily fuel consumption Q
wh
fuel
136 %
j
%
kWh
3
/h
3
/h
Contact details: OCHSNER Wärmepumpen GmbH, Ochsner-Straße 1, A-3350 Haag
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heatingPde­signh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
98 www.ochsner.com | 982000-AIR-M2-M4-EN03.1
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 99
System installer:
Company
Address
Tel . n o.
Service engineer:
OCHSNER Wärmepumpen GmbH Austria
(Commercial register) A-4020 Linz Krackowizerstrasse 4 kontakt@ochsner.at www.ochsner.com
HeadOfce/Factory A-3350 Haag Ochsner-Strasse 1 Hotline for system partners: +43 (0) 820 201020 Customer service hotline: +43 (0) 5 04245-499 kontakt@ochsner.at www.ochsner.com
Subject to technical modications.
OCHSNER Wärmepumpen GmbH Deutschland
D-10719 Berlin Kurfürstendamm 11 Hotline for system partners: +49 (0) 1805 832840 Customer service hotline: +49 (0) 69 256694 -495 kontakt@ochsner.de www.ochsner.com
OCHSNER East PL 31-302 Kraków ul. Pod Fortem Nr. 19 Tel .: +48 (0)12 4214527 kontakt@ochsner.pl www.ochsner.com
OCHSNER Wärmepumpen GmbH Switzerland
CH- 8001 Zurich Uraniastrasse 18 Customer service hotline: +41 (0) 800 100 911 kontakt@ochsner.com www.ochsner.com
*982000-AIR-M2-M4-EN03.1*
Loading...