POLARIS SERIES Air Conditioners are designed for applications where outside air is not available
and spot cooling or air conditioning is needed. The cord connected Polaris Models range from 10500
BTU/HR to 60100 BTU/HR floor mount configuration to satisfy any space requirements. All models
are provided with casters for portability.
These models are thoroughly self-contained with the entire refrigeration system, water valve,
condensate pump, fan motor and electrical components neatly arranged in a platinum polyester powder
coated metal cabinet. Only power, condenser water supply and discharge and condensate drain piping
are required for installation. The 24 volt electronic temperature controller provides the desired comfort.
The high efficiency design of the water-cooled condenser allows the proper amount of water flow to
achieve the desired high and low refrigeration system pressures. Condenser water is regulated by a
refrigeration system head pressure actuated water regulating valve.
GENERAL REQUIREMENTS
A MINIMUM WATER PRESSURE OF 20 PSIG IS REQUIRED to actuate the water regulating valve
and allow water to flow into the condenser coil. The condenser water temperature leaving the unit
should not exceed 112° F. Ignoring this compliance will void the warranty on the refrigeration system.
IMPORTANT - Polaris Air Conditioners are designed and engineered for quiet comfort. The length
of service received can be extended by following the installation and preventive maintenance
instructions. It is important that the warranty card be filled out completely and returned to the factory
within fourteen (14) days of installation of the unit in order to receive the benefits of the warranty.
1 Nominal Capacity is total BTU/HR at 80°DB/67°WB return air or 85° EWT to
95° LWT(3GPM/Ton) high fan speed.
2 CFM with free discharge.
3 Sound Pressure, dB at 5 feet, commercial configuration.
f Size 3/8 valve used on models 10, 12, 18, 24 (with 3/8 M flare fitting)
3/4 valve used on model 36, 60 (with 5/8 M flare fitting)
gAmps & Watts at 208 volts
Ambient operating range 65° to 105°
May operate to 55° if equipped with optional
Factory installed hot gas bypass
2.20
9.0
2.0
208/230/3 208/230/1 208/230/3 460/3
26 1/4
3 1/2
6
2.20
9.0
47
42 1/2
15 1/2
520
240
560
270
21
5.50
15.0
5/8 MF
28 1/4
5.50
15.0
52 1/4
46 1/2
39
460
500
36
....
5.50
15.0
3
polarismanpg3
STANDARD FEATURES
SERVICEABILITY
All Polaris Series units are designed with removable panels to provide full service accessibility. Turn to
page 11 “Part Replacement Procedure” for removal of the correct panel when replacing a part.
AUTOMATIC WATER VALVE
All units are equipped with a direct-acting, refrigeration system head pressure actuated water regulating
valve. This valve, factory set for 94° - 100° leaving water temperature (LWT), flows only the amount of
water required to achieve the desired refrigeration system operating pressure. Units used for closed loop
operation may be ordered without the water valve. If, however, the temperature of the return water is
questionable in a closed loop, the water valve may be helpful and left in the system with little pressure
drop.
ATTRACTIVE CABINET
The Polaris Series cabinet is constructed of 18 gauge cold rolled steel with a platinum polyester powder
coated finish that will compliment any decor. The entire cabinet is insulated with a sound absorbant insulation for cool, quiet comfort. The basepan is 14 gauge galvanized steel and remains dry and free from
odor and fungal growth.
HIGH PRESSURE SAFETY SWITCH
All units incorporate a manual re-set high pressure switch for maximum protection of the refrigeration
system and compressor. The cut-out pressure setting is 375 ± 5 PSIG for all Polaris models. If the pressure exceeds this setting, the compressor stops and can be re-started by depressing the “RESET” button
located on the back panel of the unit. The high pressure control’s capillary line is attached to a schrader
valve. This allows replacement of a defective control without recovering the refrigerant.
High Pressure Switch
Re-set Button
Water Cooled
Condenser
Caster
Power Cord
Electrical Box
Water
Valve
Compressor
4
Evaporator Coil
Evaporator Fan
Motor
Evaporator Drain
Pan
Evaporator Drain
Hose
Condensate Pump
polarismanpg4
STATE-OF-THE-ART CONTROLS
The electronic thermostat displays room temperature if the cooling system is on. Select the temperature
you want by pressing the ▲ or ▼ buttons. (The word COOL and the temperature setting is displayed for
5 seconds). The FAN button controls the evaporator fan motor. In the ON selection, the fan runs continuously. In the AUTO selection, the fan cycles with the compressor. The OUTDOOR button is not used in
portable air conditioning. The MODE button controls the cooling function by selecting COOL or OFF.
The DAY/NIGHT allows day and night setpoints. A built in 4 minute time delay protects the compressor
from short cycling. Pressing the ▲ and ▼ simultaneously switches the display between Celsius and
Fahrenheit.
A two position rocker switch located next to the thermostat provides high fan when depressed at the top,
low fan speed when depressed at the bottom.
BUILT-IN CONDENSATE PUMP
Every unit is equipped with a condensate pump designed as an automatic condensate removal pump for
water dripping off the evaporator coil. The pump is capable of pumping against a 20 ft. head and is controlled by a float/switch mechanism which turns the pump “on” when approximately 2 1/2 inches of water
collects in the tank, and automatically switches “off” when the tank drains to a level of approximately
1 1/4 inches. A built-in pump safety switch turns off the air conditioner if the condensate line becomes
plugged or motor/pump failure should occur. The red condensate alert light on the front panel will be on
if this condition should occur.
CONDENSER COIL
The water cooled copper/steel tube-in-tube type condenser coil is designed for a maximum water side
working pressure of 400psi. Optional cupro-nickel condenser coils are available for severe duty and saltwater/brine applications. Low pressure drop and efficient design (high SEER’s) fully utilizes the heat
transfer capability of this compact coil.
FILTER
All units are equipped with a 1/2 inch thick, washable, foam air filter located behind the return air grille
that can easily be removed and cleaned. Just pull the grille out and remove the filter.
SERVICE CORD
All Polaris Series units are equipped with the standard ten foot long service cord with UL listed plug configurations. The following page contains Oceanaire plug configurations for all units.
polarismanpg5
5
UNIT/MODEL PLUG CONFIGURATION RECEPTACLE
PWC1011, PWC1211, PWC1811
115 VOLT
PAC1011, PAC1211, OWC1211,
OWC1811, OAC1211, OACH1211
15A-125 VOLT
NEMA 5-15P
NEMA-5-15R
115 VOLT
PAC18, OAC18, OACH18
208/230 VOLT SINGLE PHASE
PAC1012,1212,1812,2412
OAC1212,1812,2412
OACH1212,1812,2412
PWC1012,1212,1812,2412,3612
OWC1212,1812,2412,3612
208/230 VOLT SINGLE PHASE
PAC3612, OAC3612, OACH3612
PWC6012, OWC6012
208/230 VOLT SINGLE PHASE
PAC6012,
OAC6012,
OACH6012
208/230 3 PHASE
OAC/PAC3632
OACH3632
OWC3632,PWC3632
208/230 3 PHASE
PAC6032
OAC6032,OACH6032
PWC6032,OWC6032
20A-125 VOLT
NEMA 5-20P
20A-250 VOLT
NEMA 6-20P
30A-250 VOLT
NEMA 6-30P
50A-250 VOLT
NEMA 6-50P
20A-250 VOLT
NEMA L15-20P
30A-250 VOLT
NEMA L15-30P
NEMA 5-20R
NEMA 6-20R
NEMA 6-30R
NEMA 6-50R
NEMA L15-20R
NEMA L15-30R
460/480 3 PHASE
OAC/PAC3634
OACH3634
PWC/OWC3634
460/480 3 PHASE
OAC6034, PAC6034
OACH6034
PWC/OWC6034
20A-460 VOLT
NEMA L16-20P
30A-460 VOLT
NEMA L16-20R
NEMA L16-30R
NEMA L-16-30P
6
polarismanpg6
OPTIONAL FEATURES
HOSE KIT
10, 25, and 40 foot hose kits with flare connectors to match fittings on units, banded 3-in-one design for
easy and convenient installation, are available. When using these hoses in applications with water pressures exceeding 50 PSIG, a water pressure reducing valve must be installed in the water supply line prior
to the hose kit; otherwise warranty on the hose kits will be void. The water out and condensate of the
three-section flexible plastic hose can be fed to a sink or permanent drain. When using a hose kit, avoid
sharp corners, hot water pipes and kinking to assure proper water flow of the supply and return lines.
HIGH PRESSURE WATER VALVE
High pressure water regulating valves, designed for use with up to 350 psig or 425 ±5 psig water inlet
pressure, are available.
CUPRO-NICKEL CONDENSER
When chemically treated water, salt water or brine is used in the condenser coil, it is recommended that
the air conditioner be equipped with a 90/10 Naval Spec. Cupro/Nickel condenser.
TREATED EVAPORATOR COIL
When airborne contaminants are a problem for air conditioning applications, acrylic coated evaporator
coils are recommended to guard against pitting or corroding.
HK-1
V-46 water regulating valve
installed in unit
7
polarismanpg7
UNIT CONSTRUCTION
Evaporator blower
Water valve
Evaporator blower motor
Thermostat
Evaporator coil
Fan motor capacitor
Evaporator drain
pan
Drain hose
Condensate pump
Compressor
Dry Base pan
Casters
High Pressure Switch
Condenser Water
Outlet
Condenser
Condenser Water Inlet
Condensate Outlet
Electrical Box
polarismanpg8
8
INSTALLATION INSTRUCTIONS
ELECTRICAL REQUIREMENTS
Adhere to the data plate on the back of the unit and make certain that the proper power is used. Refer to
the "Specifications" section for voltage and fuse requirements. Make sure that proper wall outlets and receptacles are used as described in "Standard Features" section of this manual. Operating the unit on improper voltage will void the warranty. CAUTION: the use of an extension cord must meet amperage
requirement and have grounding-type attachment plug and grounding-type connector (load fitting).
SEE SPECIFICATIONS FOR YOUR MODEL ELECTRICAL REQUIREMENTS
WATER FITTING LOCATION
Check the exact location of the water fittings on the unit back panel before placing the air conditioner in
the desired position. Water lines should be securely attached to the proper connections.
1"
polarismanpg9
9
PRACTICAL INSTALLATION
Proper installation can be achieved by following these simple steps:
1. Turn off cold water supply.
2. Install “T” between faucet of cold water line and supply valve.
3. Connect shut-off valve to “T” branch.
4. Insert a 3/8 pipe nipple in discharge end of water shut-off valve.
5. Thread coupling onto 3/8 pipe nipple and secure.
An alternate installation method: Drill a 5/16 diameter hole in the cold water line and attach a saddle valve
to the line. Complete installation by following above steps.
10
polarismanpg10
ACCESSORIES
Grille
Evaporator
Plenum
Evaporator
plenum attaches to unit
in place of
standard
evaporator grille.
Duct Adaptor
Model
DDA-6
DDA-10
DDA-16
Equivalent Feet
Round
Duct Size
Model
Evaporator
Plenum
EP-10
EP-12
EP-16
Maximum
(ESP)
PWC
10
Round
Duct
Size
Fits
PWC
10
Fits
PWC
12
Fits
PWC
18
10 inch Yes Yes No No No No
12 inch No No Yes Yes No No
16 Inch No No No No Yes Yes
PWC
12
25
(.15)
PWC
18
PWC
24
25
(.15)
(.25)
PWC
36
50
PWC
6 inch Yes Yes No No No No
10 inch No No Yes Yes Yes No
16 inch No No No No No Yes
Fits
PWC
24
50
(.25)
60
Fits
PWC
(.25)
Duct Adapter
36
50
Fits
PWC
60
100
(.50)
Maximum E q u i valent Feet
(add 6 feet for each 90° elbow)
Maximum E.S.P
Nozzles
Hose kit installed
on unit.
25 25 50 50 50 100
.15 .15 .25 .25 .25 .50
Model
Nozzles
NK-1
NK-2
NK-3
Round Duct
Number/Diameter
Compressed Length
2 x 4 inch
15 inches
2 x 6 inch
22 inches
2 x 8 inch
Approximate
Extended
PWC
Length
21 inches Yes Yes No No No No
32 inches No No Yes Yes Yes No
29 inches No No No No No Yes
20 inches
Hose kits are available in
10, 25 and 40 foot lengths.
Check specifications for
correct size and application.
10
PWC
12
PWC
18
PWC
24
PWC
36
PWC
60
11
11
HOSE KIT
polarismanpg11
FAN ONLY
Plug unit in and push FAN button once. This turns the evaporator fan blower on. To turn the blower off,
push the FAN button once again. This turns the fan blower off.
To change fan speeds, push the fan speed rocker switch up for high speed or down for low speed.
COOLING CYCLE
To operate unit for cooling, push MODE button to display COOL in the window.
72
Push down arrow button multiple times to lower set
point to desired temperature.
MODE
OUTDOOR
FAN
DAY/NIGHT
The display will show the setpoint temperature for 5 seconds, then it will return to room temperature display.
After a slight pause, the fan motor and compressor will
start, beginning the cooling cycle.
Remember, the setpoint must be lower than the room
temperature for the unit to start.
WAIT 4 MINUTES
BEFORE RE-STARTING
Robertshaw
The OUTDOOR and DAY/NIGHT buttons are not used and do not apply to portable air conditioning.
GENERAL INFORMATION
This is a cooling only thermostat. Select the temperature you want by
pressing the ▲ or ▼ buttons. The word COOL and the temperature setpoint is displayed for 5 seconds.
To change display to Celsius, simultaneously press the ▲ and ▼ buttons. Press them again to change back to Fahrenheit.
No batteries are required. In the event of a power failure, when the
power is restored the thermostat will continue operating as if the power
had never been off.
Compressor short cycle protection is built-in to the thermostat. A 4 minute time delay will protect the unit.
Electrical rating 24 to 30VAC
Control Range 60° to 88°
Temperature differential ± 1°
Anticipation Electronic
Manufacturer Robertshaw
12
polarismanpg12
REPLACEMENT PROCEDURE FOR PARTS
A. FAN MOTOR
1. Remove cabinet's left-hand (when looking at the front of the unit) side panel.
2. Disconnect motor wires from evaporator contactor and fan speed rocker switch.
3. Remove screws securing motor and O-ring to blower housing. All screws are external and visible.
4. Loosen clamp around motor and remove motor.
5. Install new motor, reversing the removal procedure.
B. THERMOSTAT AND BATTERIES
1. No batteries are used in the thermostat.
C. PANEL INDICATOR LIGHT
1. To replace pilot light on all models, disconnect wire from control panel, bend tinnerman clip retaining
light and pull out. Install new light, reversing the procedure.
D. CONDENSATE PUMP
1. Remove cabinet's left hand side panel.
2. Remove front bracket securing condensate pump in base pan by removing nut from weld stud.
3. Disconnect pump wire leads from terminal block. Remove retainer clamp and tubing. Replace pump,
install by reversing procedure.
E. PRESSURE ACTUATED WATER VALVE
1. Remove back panel.
2. Remove nut that secures sensing capillary to the refrigeration system's high pressure side. A built in
schrader valve allows removal without need to remove refrigerant charge..
3. Remove two screws that retain valve to right side panel.
13
polarismanpg13
4. Disconnect valve from "water in" line.
5. Install new valve, reversing the procedure.
F. HIGH PRESSURE CONTROL
1. Follow the first two steps in "E".
2. Remove two screws that retain switch to right side panel.
3. Disconnect wire leads from compressor contactor and condensate pump safety switch.
4. Install new High Pressure Control, reversing the procedure.
To gain access to compressor and compressor run capacitor, remove left hand side panel.
TROUBLESHOOTING GUIDE
The following steps and procedures are recommended for correcting the problems indicated. Service, other
than routine maintenance, should be performed only by a qualified refrigeration serviceman.
PROBLEM: THE ENTIRE UNIT DOES NOT RUN.
1. CAUSE: POWER INTERRUPTION
REMEDY: Check external power supply. Look for blown fuses or tripped circuit breakers. Reset or
replace if needed.
2. (REASON) THERMOSTAT INOPERABLE.
REMEDY: Setting may be too high; check and reset. Thermostat may be out of calibration or otherwise
defective...remove and replace.
3. (CAUSE) ELECTRICAL PANEL:
a) 24 volt transformer defective; (b) contactor coil defective, contacts stuck open, burned or dirty; (c) loose
wires.
(REMEDY) Correct as follows: (a) Replace; (b) Correct or change; (c) Tighten connections
PROBLEM: FAN RUNS BUT COMPRESSOR DOES NOT START
1. (REASON) Low Voltage.
(FIXING) Check power supply for voltage outside the range of 106-126 volts on the 115 volt unit and
187-253 volts on the 208/230 volt unit.
polarismanpg14
14
2. (CAUSE) Thermostat
(REMEDY) Examine the control unit for loose wires. Tighten any loose connections. Wait 4-minutes
before re-start.
3. (REASON) High Pressure Control cutting turning unit off
(FIXING) Check for loose wire connections, broken or burned contacts. If switch is defective, replace.
Not enough water flow to unit or water is too warm.
4. (CAUSE) Compressor contactor open or burned.
(CURE) Replace
5. (REASON) Refrigerant leak no freon.
(REMEDY) Locate leak and repair. Evacuate unit and recharge.
6. (CAUSE) Loose or defective wires.
(FIXING) Tug on wires to see if they will separate from connections.
7. (REASON) Defective compressor
(REMEDY) Check for shorts, opens and grounds. Remove and replace compressor.
8. CAUSE) Shorted or open run capacitor
(FIXING) Remove and replace.
PROBLEM: COMPRESSOR STARTS AND RUNS, BUT, FAN DOES NOT RUN.
1. (CAUSE) Faulty rocker switch
(REMEDY) Replace
2. (REASON) Open fan motor coil circuit
(FIXING) Replace fan motor.
3. (CAUSE) Shorted or open fan motor capacitor
(REMEDY) Replace capacitor.
4. (REASON) Loose or defective wires
(REMEDY) Trace and repair
15
polarismanpg15
PROBLEM: INSUFFICIENT COOLING
1. (CAUSE) Insufficient air flow through evaporator coil due to:
A. Dirty air filter in unit B. Dirty evaporator coil
C. Ice on evaporator coil D. Obstructed air intake
(REMEDY) Correct as noted:
A. Clean filter (see "Preventive Maintenance" section of this manual)
B. Clean filter with a vacuum cleaner & hose.
C. Defrost; turn on fan only.
D. Remove obstruction
2. (REASON) IMPROPER SIZING OF UNIT
(FIXING) Check to make sure unit is properly sized for load. Add supplemental unit if required.
PROBLEM: NOISY OPERATION
1.(CAUSE) Copper tubing vibrating
(REMEDY) Adjust by bending slightly to firm position. Segregate tubes touching cabinet or each other.
2.(REASON) Loose cabinet or internal component
(FIXING) check and tighten loose screws.
3.(CAUSE) Machine vibrating out of level
(CURE) Level unit base.
4.(REASON) Loose blower wheel
(REMEDY) Tighten screws on blower wheel to motor shaft.
5.(CAUSE) Blower wheel hitting housing.
(REMEDY) Adjust wheel position on motor shaft.
6. (CAUSE) Blower motor bearing defective.
(REMEDY) Replace blower motor.
polarismanpg16
16
PROBLEM: WATER LEAKING FROM PAN
1. (CAUSE) Leaky drain pan
(REMEDY) Locate leak and repair pan.
2. (CAUSE) Loose evaporator, drain or condensate pump hose
(REMEDY) Tighten connections.
3. (CAUSE) Defective condensate pump or excessive lift on pump
(REMEDY) Examine to see if elevation exceeds 20 ft. (if it does, a larger pump will be required).
Otherwise, change pump if defective. Pump will operate properly against 20 ft. of water total head pressure
on pump. If combination of vertical height and horizontal drain line exceeds 20 ft. of water pressure drop,
problems will occur.
PROBLEM: THERMOSTAT (LCD) LIQUID CRYSTAL DISPLAY WINDOW DOES NOT
ILLUMINATE.
1. (CAUSE) Weak or dead batteries.
(REMEDY) Replace batteries.
PREVENTIVE MAINTENANCE
Polaris Series air conditioners are designed to last a long time and to give maximum performance and
reliability with minimum maintenance. To prolong the life of the unit, regular maintenance must be
performed as specified below:
1. BLOWER MOTOR
The motors for all 208/230 volt models are sealed bearings and require no oiling. The 115 volt motors have
oil ports and should be oiled annually.
17
polarismanpg17
2. FILTER
A clogged filter will cause the unit to operate at greatly reduced efficiencies. We recommend that the
filter be inspected on a regular bases every six weeks or more often depending on the environment. The
foam filter is located behind the return air grille and can be easily removed by pulling the grille out. The
filter must be washed periodically as needed by placing it in a dishwasher or soaking it in a solution of
warm water and detergent for 10 minutes. Then rinsing it clean with hot water and shaking excess
moisture from filter.
3. CONDENSATE PUMP
When servicing pump follow these steps;
1. Make certain that the unit is disconnected from the power source before attempting to service or
remove any component.
2. Be sure the floats move freely. Clean as necessary.
3. Remove the volute and check for obstructions. Clean as needed.
4. Clean the tank with warm water and mild soap when mineral deposits are visible.
5. Check the inlet and outlet piping. Clean as necessary. Be sure there are no kinks in the lines that would
inhibit flow.
GENERAL
When necessary maintenance steps outlined above are followed, the air conditioner will provide long and
reliable service. The refrigeration and electrical circuits of the system should only be serviced by a fully
qualified service technician.
18
polarismanpg18
PIPING SCHEMATIC
WATER COOLED AIR-CONDITIONER
19
polarismanpg19
May 1, 2002
G
W
Y
C
Y
EVAPORATOR MOTOR
CONTACTOR
L1
L2
24 Volt Coil
COMPRESSOR
CONTACTOR
L1
L2
24 Volt Coil
RHB
G
T1
T2
T1
T2
TRANSFORMER
R
O
TERMINAL
BLOCK
RC
THERMOSTAT
COOLING ONLY
24 Volt
120 or 230
Volt
HIGH-LO EVAPORATOR
FAN SWITCH
HIGH
LOW
RUN
CAP
S
R
RUN
CAP
EVAPORATOR
FAN
MOTOR
HARD START
KIT
STANDARD ON
ONLY PWC1811
C
TERMINAL
BLOCK
G
N
L1
L2 FOR
208/230
120/1/60
208/230/1/60
POWER CORD
CONDENSATE
PUMP
120 or 230 VOLT
LINE VOLTAGE
24 VOLT
Oceanaire, Inc.
SAFETY
SWITCH
NC
NO
COM
R
Hard Start Kit is factory installed
only on the PWC1811.
COMPRESSOR
HIGH PRESSURE SWITCH
RED LIGHT ON
CONTROL PANEL
POLARIS, (WATER COOLED) MODELS
MODELS PWC10, 12, 18, 24, 36, 60
01pwcwiredia
120/1/60208/230/1/60
20
Polarismanpg20
YWRHB
G
C
YGR
T2
JUMPER
O
RC
TERMINAL
COOLING
THERMOSTAT
BLOCK
24v CONTROL
TRANSFORMER
24
VOLT
230
VOLT
HIGH
COM
LOW
HI-LO FAN
SWITCH
EVAP
FAN
MOTOR
230 VOLT
T1
May 1, 2002
RUN
CAP
T2
T1
COMPRESSOR
T1
L1
24 Volt Coil
COMPRESSOR CONTACTOR
T3
T2
L2
T3
L3
230v POWER
TRANSFORMER
230
VOLT
460
VOLT
HIGH PRESSURE
SWITCH
L1
24 Volt Coil
EVAP MOTOR CONTACTOR
L2
TERMINAL BLOCK
L1
L2L3
G
24 VOLT
LINE VOLTAGE
N.C.
CONDENSATE
PUMP
230 Volt
N.O.
C
OceanAire, Inc.
POLARIS (WATER COOLED)
MODEL PWC6034
460 VOLT 3 PHASE
21
RTANK FULL
LIGHT
Polarismanpg21
May 1, 2002
G
COMPRESSOR CONTACTOR
W
Y
C
Y
G
EVAPORATOR MOTOR
CONTACTOR
L1
L2
24 Volt Coil
L1
L2
L3
24 Volt Coil
T1
T2
T3
RHB
R
T1
T2
TERMINAL
BLOCK
O
RC
THERMOSTAT
COOLING ONLY
HIGH-LO EVAPORATOR
FAN SWITCH
HIGH
RUN
CAP
LOW
EVAPORATOR
FAN
MOTOR
24 Volt
T1
TRANSFORMER
T2
230 Volt
T3
COMPRESSOR
SAFETY
CONDENSATE
PUMP
230 VOLT
SWITCH
NC
NO
HIGH PRESSURE SWITCH
COM
G
L1
208/230/3/60
POWER CORD
L2
L3
LINE VOLTAGE
24 VOLT
RED LIGHT ON
R
CONTROL PANEL
POLARIS, (WATER COOLED) MODELS
MODEL PWC6032 and PWC3632
Oceanaire, Inc.
208/230/3/60
22
Polarismanpg22
The Manufacturer (OceanAire, Inc.) warrants to the
original owner that the Product will be free from defects
in material or workmanship for a period not to exceed
one (1) year from date of installation. If upon
examination by the Manufacturer the Product is shown
to have a defect in material or workmanship during the
warranty period, the Manufacturer will repair or replace,
at its option, that part of the Product which is shown to
be defective.
The Manufacturer further warrants that the product's
compressor-motor will be free from defects in materials
and workmanship for five (5) years from the date of
installation. If upon examination by the Manufacturer
the Product is shown to have a defect in materials or
workmanship during the warranty period, the
Manufacturer will repair or replace, at its option, that
Part of the Product which is shown to be defective.
Electrical parts (such as relays, overloads, capacitors,
etc...) and the sealed refrigeration system (condenser
and evaporator) are included in the one year limited
warranty , but not with the five year limited warranty of
the compressor. This limited warranty does not apply:
a) if the Product has been subjected to
misuse or neglect, has been accidentally
or intentionally damaged, has not been
installed, maintained or operated in
accordance with the furnished
written instructions, or has been altered or
modified in any way.
b) to any expenses, including labor or
material, incurred during removal or
reinstallation of the Product.
c) to any workmanship of the installer of
the Product.
This limited warranty is conditional upon:
(a) shipment, to the Manufacturer,
of that part of the Product thought
to be defective. Goods can only
be returned with prior written
approval from the Manufacturer.
All returns must be freight prepaid.
(b) determination, in the reasonable
opinion of the Manufacturer
that there exists a defect in
material or workmanship.
Repair or replacement of any part under this Limited
Warranty shall not extend the duration of the warranty with
respect to such repaired or replaced part beyond the stated
warranty period.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER
WARRANTIES, EITHER EXPRESS OR IMPLIED, AND
ALL SUCH OTHER WARRANTIES, INCLUDING
WITHOUT LIMITATION IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED
AND EXCLUDED FROM THIS LIMITED WARRANTY.
IN NO EVENT SHALL THE MANUFACTURER BE
LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL,
SPECIAL, OR INCIDENTAL DAMAGES OF ANY
NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN
EXCESS OF THE SELLING PRICE OF THE PRODUCT OR
ANY PARTS THEREOF FOUND TO BE DEFECTIVE.
THIS LIMITED WARRANTY GIVES THE ORIGINAL
OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS.
YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY
VARY BY EACH JURISDICTION.
Form PWC-ESM-5/02
23
polarismanpg23
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.