OceanAire 2OAC1811 Operation Manual

2OAC6012
2OACH1211
....
6228 Oakton Street Morton Grove, IL 60053
Phone: 847-583-0311 FAX: 847-583-0312 WEB: www.oceanaire-inc.com
GENERAL DESCRIPTION
ARCTICAIRE and CONVERTIBLEAIRE SERIES Portable Air-Cooled Air Conditioners and heat pumps are designed to cool or heat an entire area by discharging air through their 12 x 5 grille (Models 2OAC12 and 2OACH12) 14 x 8 1/2 (Models 2OAC/2OACH18, 24), 18 X 10 (Model 2OAC/ OACH36) and 18 x 12 (Models 2OAC/2OACH60). These self contained units are also designed to direct air to specific areas or objects through (optional) dual 4 in. diameter nozzles (Model 2OAC/2OACH12) and 6 in. diameter nozzles (Models 2OAC/2OACH18, 24 ,36), and 8 in. diameter nozzles (2OAC/2OACH60). The cord connected Models range from 13,500 to 60,000 BTU/HR cooling and from 11,685 to 53,445 BTU/HR heating. Floor mount configuration can satisfy most space requirements. All models are provided with casters for portability.
These models are thoroughly self-contained with the entire refrigeration system, evaporator and condenser fan motors and electrical components neatly arranged in a gloss grey and blue texture polyester powder coated metal cabinet. Only power, and an opening to dispose of condenser hot air is required. The 24 volt solid state electronic controller provides the desired comfort level. The cord­connected model units are provided with heavy-duty, swivel casters for easy handling and convenient relocation.
GENERAL REQUIREMENTS IMPORTANT - ArcticAire and ConvertibleAire Air Conditioners and Heat Pumps are designed
and engineered for the comfort of the end user. The length of service received can be extended by following the installation and preventive maintenance instructions. It is important that the warranty card be filled out completely and returned to the factory within fourteen (14) days of installation of the unit in order to receive the benefits of the warranty.
UNIT MODEL CAPACITIES
CAPACITY MODEL
13500 BTU/HR COOLING 2OAC12 11685 BTU/HR HEATING 2OACH12
16500 BTU/HR COOLING 2OAC18 14850 BTU/HR HEATING 2OACH18
23500 BTU/HR COOLING 2OAC24 21380 BTU/HR HEATING 2OACH24
36000 BTU/HR COOLING 2OAC36 32445 BTU/HR HEATING 2OACH36
60000 BTU/HR COOLING 2OAC60 53445 BTU/HR HEATING 2OACH60
1
NOMENCLATURE
2 O A C H 24 1 2
2nd GENERATION
OCEANAIRE
AIR-COOLED
COOLING
CAPACITY SELECTION
NUMBER CODE 12..........13500 BTU/HR
18..........16,500 BTU/HR
24..........23,500 BTU/HR
36..........36,000 BTU/HR
60..........60,000 BTU/HR
HEAT PUMP
VOLTAGE
SINGLE PHASE
CAPACITY SELECTION
2
MODEL 2OACH1211 2OACH1811 2OACH2412 2OACH3612 2OACH3632 2OACH6012 2OACH6032 2OACH6034
Cooling Capacityc
13,500 16,500 23,500 36,000 36,000 60,000 60,000 60,000
Heating Capacityd 11,685 14,850 21,380 32,445 32,445 53,445 53,445 53,445
Voltage 208/230/3 208/230/1 208/230/3 460/3
115/60/1 or 208/230/1 208/230/1 Cooling Ampse 11.2/5.6 12.5/6.2 12.3 19.5 12.0 40.0 22.0 11.4 Heating Ampse 11.3/5.6 12.6/6.2 12.4 20.0 13.6 40.0 25.6 12.5 Cooling Wattse 1250 1440 2200 3360 3360 4992 4992 4992 Heating Wattse 1255 1460 2240 3360 3360 4992 4992 4992
E.E.R.f 12.0 11.5 10.9 10.7 10.7 12.0 12.0 12.0
C.O.P. 3.0 3.3 3.2 3.2 3.2 3.2 3.2 3.2
In Rush Current (AMPS) 92.8 114.2 79 128.8 111.8 198.0 134.2 135.6
Fuse/Breaker5 (AMPS) 15 15 20 30 20 50 40 30
Plug Type 5-15P 5-15P 6-20P 6-30P L15-20P 6-50P L15-30P L16-30P
Compressor HP 1 1 1/2 2 3 3 5 5 5 Compressor RLA 9.3 11.4 8.3 17.9 11.4 28.0 20.0 8.2 Compressor LRA 58 65 49 88 77.0 169 123.0 59.6
Evaporator CFM 400/340 600/500 810/680 1310/1100 1310/1100 2000/1600 2000/1600 2000/1600
Evap Motor HP 1/17 1/14 1/7 1/3 1/3 1/2 1/2 1/2
Evap Motor Watts 50 59 125 260 260 365 365 365
Condenser CFM 600 930 1100 1800 1800 3000 3000 3000
Condenser Motor HP 1/14 1/8 1/5 1/2 1/2 3/4 3/4 3/4 Condenser Motor Watts 59 106 160 365 365 570 570 570 Condensate Pump Head
Pump Optional on these models
Pump Standard on 5 ton
20 Feet
Sound Level6 (Hi/Low) 56/54 61/60 64/62
R-22 Charge Oz. 29 36 40
Height with Casters 36 1/2
Height without Casters 32 1/2
Width 20 Depth 25
39 1/2
24 28
30 39
65/63 66/64
77 45
48 1/2
44
52 1/2 44 1/2
48
35
Net Weight 180 245 230 350 350 470 470 490
Shipping Weight 200 285 260 390 390 520 520 550
Shipping Volume 18 34 34 37 37 40 40 40
cCooling Capacity Total 95° F at 60% RH outdoor high fan speed. dHeating Capacity Total @ 70°F DB/60°F W.B. Indoor 47°F DB/43°F W.B.
outdoor high fan speed.
eAmps & Watts at 208 volts. fEER determined with condenser discharge air ducted into another area
on high fan speed.
5Time delay fuses/circuit breakers are recommended. 6Sound pressure, dB at 5 feet, commercial configuration
(ducted condenser air) hi/lo evaporator fan speed.
Electrical ratings per U.L. 484 at 95°F DB/75°F WB on high fan speed
Ambient operating range 65° to 105° May operate to 55° if equipped with optional factory installed hot gas bypass
Specifications subject to change without notice.
3
MODEL 2OAC1211 2OAC1811 2OAC2412 2OAC3612 2OAC3632 2OAC6012 2OAC6032 2OAC6034
Cooling Capacity1
Voltage 208/230/3 208/230/1 208/230/3 460/3
13,500 16,500 23,500 36,000 36,000 60,000 60,000 60,000 115/60/1 or 208/230/1
208/230/1 Cooling Amps2 11.2/5.6 12.5/6.2 12.3 19.5 12 40.0 22.0 11.4 Cooling Watts2 1250 1440 2200 3360 3360 4992 4992 4992
E.E.R.5 12.0 11.5 10.9 10.7 10.7 12.0 12.0 12.0
In Rush Current (AMPS) 92.8 114.2 79 128.8 111.8 198.0 134.2 135.6
Fuse/Breaker (Amps)4 15 15 20 30 20 50 40 30
Plug Type 5-15P 5-15P 6-20P 6-30P L15-20P 6-50P L15-30P L16-30P
Compressor HP 1 1 1/2 2 3 3 5 5 5 Compressor RLA 9.3 11.4 8.3 17.9 11.4 28.0 20.0 8.2 Compressor LRA 58 65 49 88 77 169 123 59.6
Evap CFMe Hi/Low 400/340 600/500 810/680 1310/1100 1310/1100 2000/1600 2000/1600 2000/1600
Evap Motor HP 1/17 1/14 1/7 1/3 1/3 1/2 1/2 1/2
Evap Motor Watts 50 59 125 260 260 365 365 365 Condenser CFM3 600 930 1100 1800 1800 3000 3000 3000
Condenser Motor HP 1/14 1/8 1/5 1/2 1/2 3/4 3/4 3/4 Condenser Motor Watts 59 106 160 365 365 570 570 570 Condensate Pump Head
20 Feet
Pump Optional on these units
Pump Standard on 5-Ton
Sound Level6 Hi/Low 56/54 61/60 64/62
R-22 Charge Oz. 29 36 40
Height with Casters 36 1/2
Height without Casters 32 1/2
Width 20 Depth 25
44 1/2 39 1/2 44 48
24
30
45 77
48 1/2 52 1/2
28
35
66/64 65/63
39
Net Weight 180 245 230 350 350 470 470 490
Shipping Weight 200 285 260 390 390 520 520 550
Shipping Volume 18 34 34 37 37 40 40 40
Cooling Capacity Total 95° F at 60% RH Outdoor high fan speed.
Amps & Watts at 208 Volts CFM with free discharge Hi/Low fan speed Time delay fuses/circuit breakers are recommended EER determined with condenser discharge air ducted into another area on high fan speed Sound pressure, dB at 5 feet, commercial configuration (ducted condenser air), hi/low
evaporator fan speed.
Electrical ratings per U.L 484 at 95°F DB/75°WB on high fan speed
4
Ambient operating range 65° to 105° May operate to 55° if equipped with optional factory Installed hot gas bypass
Specifications subject to change without notice.
STANDARD FEATURES
SERVICEABILITY
All 2OAC/OACH Series units are designed with quick connect removable side panels to provide full service accessibility. Only one screw needs to be removed for access to the inside of the unit. Turn to page 17 “Part Replacement Procedure” for removal of the correct panel when replacing a part. The interior is divided into two sections, front and rear. The front section contains the evaporator blower, coil, condensate bucket and thermostat. The rear section contains the condenser blower, coil, compressor, electrical control box and cord storage box.
ATTRACTIVE CABINET
The 2OAC/OACH Series cabinet is constructed of 18 gauge cold rolled steel with a gloss grey and blue texture polyester powder coated finish that will compliment any decor. The entire cabinet is insulated with a sound absorbant insulation for cool, quiet comfort.
HIGH PRESSURE SAFETY SWITCH
All units incorporate a manual re-set high pressure switch for maximum protection of the refrigeration system and compressor. The cut-out pressure setting is 375 ±5 psig or 425 ±5 psig. If the pressure exceeds this setting, the compressor stops and can be re-started by depressing the “RESET” button located on the back panel of the unit. The high pressure control’s capillary line is attached to a schrader valve. This allows replacement of a defective control without recovering the refrigerant.
Condenser Motor
Condenser Coil
Control Box
Kick Plate
Casters
Evaporator Motor
Evaporator Coil
Condensate Tank
Condensate Tank Tray
Water Level Detection Control
5
STATE-OF-THE-ART CONTROL SYSTEM This self diagnostic control system handles more than just temperature. The ConvertibleAire (2OACH) has automatic changeover from heating to cooling and cooling to heating. The ArcticAire (2OAC) does not since it is a cooling only model. The temperature setpoint range is from 55°F to 85°F. A built-in time delay prevents compressor short cycling.
The built-in 6 speed fan controller decreases the fan speed as the temperature approaches the setpoint.
The LED display will read the return and supply air temperature...as well as setpoint.
MOISTURE MODE When entering the moisture mode with the select button the fan will start within 1 minute at speed level 3. The fan will run for 30 minutes sampling the air temperature and storing it into memory. If the ambient air temperature is above 60°F, the compressor will then start. The compressor will run for a maximum of one (1) hour, or until there is a 2°F drop in ambient temperature. After the compressor shuts off, the evaporator fan will continue to run for four (4) more minutes, then turn off. This cycle will start again in four (4) hours. The right most decimal is lit while the compressor is running. If the unit is properly sized for the conditioned space, this process should maintain the relative humidity between 50-60%.
FILTERS The condenser coil filter is 1/4 inch thick washable foam located in the filter grille assembly in the back of the unit. The evaporator filter is 1/4 inch thick washable foam located in the filter grille assembly in the front of the unit. To remove filter: (1) lift and pull out the filter grille. (2) pull the filter away from the velcro attaching strip. (3) wash, and re-install in reverse order. The filter may be reinstalled damp since the air flow will dry it quickly.
SERVICE CORD All ArcticAire (2OAC) and ConvertibleAire (2OACH) Series units are equipped with a standard ten (10) foot long service cord with plug configurations and receptacle requirements as shown in the chart below.
UNIT MODEL PLUG CONFIGURATION RECEPTACLE
2OAC12 / 2OACH12 2OAC18 / 2OACH18
115 V
2OAC24
2OACH24
208/230 V
2OAC36
2OACH36
208/230
2OAC60
2OACH60
208/230
2OAC6032
2OACH6032
208/230/3
2OAC/OACH3634
460 3 PHASE
50A-250V NEMA 6-50P
NEMA L14-30P
15A-125V
NEMA 5-15P
20A-250V
NEMA 6-20P
30A-250V
NEMA 6-30P
30A-250V
20A-460 VOLT
NEMA 5-15R
NEMA 6-20R
NEMA 6-30R
NEMA 6-50R
NEMA L14-30R
NEMA L16-20R
NEMA L16-20P
2OAC/OACH6034
460 3 PHASE
30A-460 VOLT
NEMA L16-30R
NEMA L-16-30P
6
CONDENSATE RESERVOIR TANK
ArcticAire (2OAC) and ConvertibleAire (2OACH) utilize a 5.0 gallon capacity, polyethylene condensate drain tank, located in the lower, front section of the unit behind the tank door. A high water level cut-out switch is used to stop the compressor and condenser fan automatically when the tank's pre-set water level has been reached. The evaporator fan will continue to run, circulating air.
An adjustment screw is provided to vary the cut-off of the tank full switch. If a lighter (less weight) level of water is desired, turn the adjusting screw clockwise. Do not exceed 6 full turns clockwise.
CAUTION, TURN UNIT OFF: BEFORE ADJUSTING SET SCREW
BEFORE REMOVING TANK TO EMPTY CONDENSATE
Condensate Tank
*Tank Water Level Adjusting Screw
Spring
High Water Level Cut-Out Switch Condensate Tank Tray
Condensate Water From Evap Coil
Water Outlet Cap
Max Water Level 4"
Handle
Plug
Minimum
Water Level
1"
Base Pan
FRONT
* Turn screw clockwise to lower water level, which makes tank lighter in weight and easier to
handle.
NOTE: Max. and Min. water levels shown are those at which the unit will shutdown and not restart until the condensate tank has been emptied.
7
OPTIONAL FEATURES
TREATED EVAPORATOR AND CONDENSER COILS
When airborne contaminants are a problem for air conditioning applications, acrylic and heresite coated coils are recommended to guard against pitting and corrosion. Call factory for details.
CONDENSER DUCT
If a longer, 12" or 16" diameter duct is needed on the condenser discharge, 10 ft. flexible ducts may be coupled or weaved together to your desired length. The following chart
Model
Ceiling Kit
CK-12
Size/Fits
CK-16
Size/Fits
Round Flexible
Duct Size Diameter
Length
12 inch
8 feet
16 Inch
8 feet
Fits
2OAC12
2OACH12
Yes Yes Yes
No No No
Fits
2OAC18-24
2OACH18-24
Fits
2OAC36
2OACH36
Fits
2OAC60
2OACH60
No
Yes
(add 6 feet for each 90° bend)
Maximum
Equivalent Feet
(ESP)
25
(.20)
40
(.25)
80
(.50)
80
(.50)
CEILING PANEL/DUCT KIT ASSEMBLY
A 12 inch diameter (Model 2OAC/2OACH12-18-24-36) and 16" diameter (Model 2OAC/2OACH60) flexible duct kit assembly extends to vent condenser air or to draw condenser return air from the ceiling when a condenser return air plenum is used. It comes with a 2' X 2' lay in ceiling panel/collar assembly for venting into the plenum area above the false ceiling, plus a duct collar to attach the duct to the unit. Installation can be completed by following these simple steps:
1) Slip one end of the duct over the lay in ceiling panel/collar assembly and the other over the unit duct collar.
2) Clamp or screw duct to lay-in ceiling panel/collar assembly and unit duct collar.
3) Place the 2' X 2' lay-in ceiling panel in the false ceiling directly above the unit.
2x2 Lay-in ceiling panel
Flexible Duct
Duct Flange (attaches to unit)
Duct flange provided on 3 and 5 ton units.
4) Screw duct collar to unit with three screws provided.
8
DISCHARGE AIR NOZZLE KIT ASSEMBLY
The optional nozzles can be easily attached to the unit without tools to direct cold air (or warm air with heat pump) to a specific spot or area. The chart below illustrates application information for each nozzle kit.
Model
Nozzles
2NK-1
2NK-2
2NK-3
Round Duct
Number/Diameter
Compressed Length
2 x 4 inch
15 inches
2 x 6 inch
22 inches
2 x 8 inch
20 inches
OPTIONAL CONDENSATE PUMP KIT
2NK-2
Approximate
Extended
Length
21 inches Yes No No No
32 inches No Yes Yes No
29 inches No No No Yes
2OAC12
2OACH12
2OAC18-24
2OACH18-24
2OAC36
2OACH36
2NK-3
2NK-1
2OAC60
2OACH60
A condensate pump kit designed as an automatic condensate removal system for water dripping off of the evaporator coil is available. This pump kit can be used in place of the condensate collection tank, which is standard on every model except the 5-ton, where a condensate pump is standard equipment.
It is a convenience for those who do not want to empty the 5.0 gallon condensate tank. It is very convenient on units that are permanently installed.
This pump is capable of pumping against a 20 foot head and is controlled by a float/switch mechanism which turns the pump "on" when approximately 2 1/2 inches of water collects in the tank and automatically switches "off" when the tank drains to a level of approximately 1 1/4 inches. A built-in pump safety switch turns off the air conditioner if the condensate line becomes plugged or pump motor failure should occur. A built-in check valve prevents drain back and short cycling of the pump.
The pump kit in­cludes tubing, mounting bracket, hardware , wi r i ng and insulated mounting base.
Pump kit installs in place of the condensate bucket located behind the door
Pump Kit
on the front of the unit.
9
The Quick Connect Condensate Pump may be easily installed for one job, and just as easily reinstall the bucket for the next job. Our quick connect kit consists of our specially prepared and wired condensate pump, 20 feet of 3/8 plastic tubing, 2-10 inch pieces of 3/8 drain hose, 1 hose clamp, and 2 attaching screws.
Kit
TOOLS REQUIRED:
Phillips screwdriver
(for side panel & pump brackets) Slotted screwdriver (for hose clamp)
1) Unplug unit. Open low er
front door to expose condensate bucket.
Remove bucket.
Pictured 2OAC Cooling Only
7) Remove electrical tape covering pre-wired line voltage molex plug. This plug is located on the wiring harness above the condens ate pump
First hole
3) Attach 10 inch piece of 3/8 drain hose to
HEAT PUMP ONLY 3a) There is a second drain line from the rear coil on all heat pump models. Use a 10 inch piece of hose (1 of 2 supplied) and push the drain hose over the barbed fitting as shown. No hose clamp is required. Route the other end into the condensate pump tank. If this line is removed in the future, slit the plastic drain hose over the barb to release the pressure fit tension. It will then be easy to remove.
4) Slide the left side pump mounting bracket under the screw started in step 1. Install the right side pump bracket mounting screw into the predrilled hole on the bucket tray. Tighten both screws firmly, but do not over tighten.
Second hole
condensate drain using hose clamp supplied. Route other end of hose into condensate pump tank.
Low voltage molex plug (for safety switch)
Mounting brackets, One on each side
Cushion mounting pad
Line voltage molex plug (for pump motor)
2) Start the first pump bracket mounting screw into the second hole located on the left side of the bucket tray. Just turn the screw enough to catch a few threads. Later you will slide the bracket under it.
Barbed fitting from rear coil
Pictured 2OACH Heating Cooling
5) Using the Phillips screw driver, remove the right side panel (viewed from the front of the unit) and remove the plastic knock­out plug as pictured.
6) From the outside of the unit, route the drain hose into the unit through the hole. Continue through the partition panel bushing, located above the compressor. Remove or cut through the foam tape to reveal the bushing. Pull the drain through the partition and attach it to the pump discharge fitting as shown. Re-attach side panel.
8) Push large molex plug from the pump, into the pre-wired receptacle.
10
9) Disconnect molex plug from the low voltage micro switch that was used by the bucket.
10) Push the low voltage molex from the pump into the pre wired molex receptacle.
Installation complete
CONDENSER INLET AIR PLENUM
2DCP, Condenser Plenums are used to duct condenser air into the unit. The plenum easily
attaches with speed screws (supplied) to the back of the unit. The plenum transitions the
condenser inlet air opening to 12 inch round on Size 12, 18, 24 and 36. The Size 60 transitions
into 2, 12 inch round inlet ducts.
To calculate “equivalent feet”, add the length of the condenser inlet air duct run and the length of
the condenser air discharge duct run...allowing for elbows( adding 6 equivalent feet per 90°
(elbow). This is total equivalent feet. At any rate, do not exceed the rated E.S.P.(External Static
Pressure).
Condenser air plenums can substantially reduce air noise and increase the number of options for
solving difficult cooling problems.
All 2OAC/2OACH units have a dedicated blower for the condenser section and a dedicated
blower for the evaporator section. So, the “equivalent feet” may be applied to either or both
sections of the unit at the same time.
Model
Evaporator
Plenum 2DCP-1
Size/Fits
2DCP-2
Size/Fits
2DCP-3
Size/Fits
2DCP-4
Size/Fits
Maximum
Equivalent Feet
(ESP)
Round
Duct
Size
12 inch Yes No No No
12 inch No Yes No No
12 inch No No Yes No
2-12 Inch No No No Yes
-
2OAC12
2OACH12
25
(.20)
2OAC18-24
2OACH18-24
40
(.25)
2OAC36
2OACH36
80
(.50)
2OAC60
2OACH60
80
(.50)
Plenums may be easily attached to the back of unit. Since it adds no width to the unit, it can be moved through doorways or elevators without removing it.
Mounting screw
t
n
o
r
t
i
F
n
u
f
o
11
Close-up view of plenum access door for high pressure switch.
UNIT CONSTRUCTION
Condenser Discharge Air Opening
Reverse Curved Motorized Impeller For Condenser
Condenser Coil
Condensate Pan For Coil
Compressor
Electrical control box
Reverse Curved Motorized Impe ller For Evaporator
Electronic control Panel
Evaporator Coil
Condensate Pan For Coil
5 gallon condensate bucket
Quick connect plugs for optional condensate pump
Microswitch for “full”
Reversing Valve
Kick Plate
Internal side view of 2OACH1211 ConvertibleAire Air Conditioner Heat Pump
Casters
Bucket shut-off
Hot gas bypass
Pictured above are the key internal components that are included with the unit. Note the re­verse curved motorized impellers that are used rather than conventional blowers. The result are units that are more energy efficient and much more quiet.
12
APPLICATIONS
ROOM AIR CONDITIONER/HEAT PUMP
OceanAire ArcticAire and ConvertibleAire units can be used as a room air conditioner to cool the entire enclosed space. In this application, condenser hot exhaust air venting and condenser air intake ducting is required. Use the optional "Flexible Duct" and the "Condenser Inlet Air Plenum" as specified in the optional features section. ConvertibleAire units can be used to heat a space to a desired temperature, but, not warmer than 85° F. If a condenser inlet air plenum is not used, negative pressure created in the space by the condenser blower may cause a net temperature increase in the room. Please consult your Oceanaire distributor or factory for assistance.
SPOT COOLER/HEATER
ArcticAire/ConvertibleAire units can be used in an open environment to cool specific objects or "spots" through the evaporator grille, the optional nozzles or the optional duct adapter. Spot Cooling is a convenient and economical way to provide air conditioning where cooling the entire space is impractical. In this application, ducts for condenser air intake and hot air exhaust are not often not required. If heating cool spots are required, ConvertibleAire units may be used in the “heating” mode.
AREA COOLER/HEATER
When ArcticAire or ConvertibleAire is installed in an area that is not totally enclosed, the (optional) condenser hot air exhaust duct directs condenser air out of the area, allowing the evaporator air to cool the specific space.
INSTALLATION INSTRUCTIONS
BEFORE INSTALLING: Check the air conditioner/spot cooler for any damage. Air conditioners are thoroughly inspected at the factory and carefully packaged. If any damage is evident, file a claim with the delivering carrier immediately.
ELECTRICAL REQUIREMENTS: Check the data plate on the back of the unit to make certain that the proper power is available. Refer to "Specifications" section for voltage and fuse/circuit breaker requirement. For proper NEMA receptacles, refer to "Electrical service plug configuration". Operating the unit on improper voltage will void the warranty. Caution: An
extension cord can be used provided it is rated at least 20 amps@ 120 volts, or 20 amps@ 250 volts with grounding-type attachment plug and grounding type connector (load fitting). For Models 2OAC/2OACH6012 at least 50 amps@ 250 volts and for Models 2OAC/2OACH6032 at least 30 amps@ 250 volts 3 phase.
OceanAire ArcticAire/ConvertibleAire portable air conditioner/spot cooler/heater requires minimal installation. Plug unit in proper NEMA receptacle and it immediately begins to cool or heat. The entire system is built into one compact unit which can be moved and installed with ease.
DO NOT INSTALL UNIT AGAINST A WALL. A MINIMUM OF 8 INCHES OF CLEARANCE IS REQUIRED BETWEEN THE WALL AND THE BACK OF THE UNIT.
13
CHECKOUT OF UNIT OPERATION
POWER BUTTON: Press the power
button once to toggle the unit to the on mode. Press the power button again to toggle the unit to the off mode. FAN BUTTON: Press and release the fan button to advance from auto to manual fan. Press and release to increase the manual fan speeds, 1 through 6. Press and release again returns to the auto fan
INSIDE OUTSIDE
SETPOINT
temperature display. The set point increases one degree each time the up button is pressed and released.
DOWN BUTTON: Momentarily press and release to display the set point. The set point is decreased one degree each time the button is pressed and released.
MODE BUTTON: The Mode Button is used to select one of 2 Operating Modes. Press and release to advance to the next mode. Continue to press and release until the desired Operating Mode is reached. The mode selected is indicated by the Mode LED.
TEMP SELECT BUTTON: Press and release to view inside (return) air temperature, outside (discharge) air temperature or set point. The appropriate LED will be lit indicating which temperature is displayed.
THREE DIGIT DISPLAY: The inside (return) temperature is displayed whenever the control is turned on. The display also provides a readout of the outside (discharge) air temperature which is located in the supply airflow.
COOL MODE LED: The Cool Mode LED is lit when Cooling is selected.
MOISTURE CONTROL LED: The Moisture LED is lit when the Moisture Control is selected.
MANUAL FAN LED: The Manual Fan LED is lit when a manual fan speed is selected.
AUTO FAN LED: The Auto Fan LED is lit when automatic fan speed operation is selected.
FAN SPEED BAR GRAPH: There are six(6) individual fan speed LED’s. Each LED represents
one (1) fan speed. Low fan (1) is indicated by illuminating the first LED. High fan speed is indicated by illuminating all six (6) LED’s.
LED: The system operating status (Compressor On or Off) is indicated by turning On the right most decimal point in the 3 Digit Display.
mode. The selected fan mode is indicated by the Auto and Manual fan LED’s.
UP BUTTON: Momentarily press and the set point will appear in the
14
These are not default values, they are OceanAire factory values.
MODEL CODE SETTINGS
TO CHECK THE NUMBER OF HOURS ON THE UNIT
1) Unplug unit.
2) Plug in unit.
3) When “888” appears in display, push and release DOWN button.
4) The first set of numbers displayed reads thousands of hours. 02 would be 2000 hours. 04 would be 4000 hours. 00 would be no thousand of hours.
5) The second set of numbers read hours directly. 58 would be 58 hours. 742 would be 742 hours.
6) Add the 2 number sets together for total hours. 03 and 486 would be 3486 hours. 01 and 59 would be 1059 hours. HOURS REPRESENT COMPRESSOR “ON” TIME.
2OWC12
2OAC/2OACH12
2OWC18
2OAC/2OACH18
2OWC24
2OAC/2OACH24
2OWC36
2OAC/2OACH36
2OWC60
2OAC/2OACH60
P1 = 85 P2 = 35
P1 = 80 P2 = 50
P1 = 70 P2 = 50
P1 = 85 P2 = 35
P1 = 85
P2 = 45
1) Plug in the power supply cord to power outlet.
2) Unit must be in the “OFF” mode.
3) Press these buttons on the thermostat in this sequence: S TEMP SELECT U UP D DOWN S TEMP SELECT
4) As the TEMP SELECT button is released, the display
will begin flashing P and a number. To adjust P
numeric settings press the UP or DOWN button until the proper value is displayed.
5 Use the “MODE” button to scroll through the programmable parameters P
6) If no buttons are pushed, the display will then return to the “OFF” position after about 50 seconds.
2 through P16.
1 and other
15
7) To cycle the evaporator fan with the compressor, access code P-13. Press the up or down button to switch to “CYC”, which means cycle the fan with the compressor. The factory default setting is “CON”, which means continuous fan operation.
LAC…….. Low AC line power
HPF…….. High Pressure Fault (does not apply)
AAA…….Failed Air Sensor (unit will not run)
CON……. Empty Condensate Bucket or High Pressure Switch needs re-setting
REPLACEMENT PROCEDURE FOR PARTS
A. BLOWER MOTOR ASSEMBLY (REVERSE CURVED BLOWER)
1. Disconnect power from unit
2. Remove cabinet's left-hand (when looking at the front of the unit) side panel for condenser blower and right hand side panel for evaporator blower.
3. Disconnect evaporator blower motor wires from evaporator contactor and motor capacitor.
4. Disconnect condenser motor wires from condenser contactor and motor capacitor.
5. Remove 4 hex head bolts securing motor to motor mounting center panel.
6. Remove blower motor.
6. Install new blower assemblies, reversing the removal procedure.
B. THERMOSTAT
1. Remove left hand side panel.Remove 2 nuts securing to front panel and pull out. Pry thermostat from frame by pulling it out. Disconnect display cable and replace thermostat .
2. Reverse procedure to re-install.
C. CONDENSATE PUMP (3 & 5-Ton Only)
1. Remove cabinet's left front side panel.
2. Remove front bracket securing condensate pump in base pan by removing nut from weld stud.
3. Disconnect pump wire leads from terminal block. Remove retainer clamp and tubing. Replace pump, install by reversing procedure.
D. HIGH PRESSURE CONTROL
1. Remove the right hand side panel (when looking at the unit). Remove the right rear side panel on the 3 and 5 ton unit.
2. Remove the flare nut that secures the capillary to the refrigeration system high pressure side. A built-in Schrader valve permits removal without recovering the refrigerant charge.
3. Remove two the screws that secures the high pressure switch to the unit.
4. Disconnect lead wires.
5. Install new high pressure switch, reversing the procedure.
16
TROUBLESHOOTING GUIDE
The following steps and procedures are recommended for correcting the problems indicated. Service, other than routine maintenance, should be performed only by a qualified refrigeration serviceman.
PROBLEM: THE ENTIRE UNIT DOES NOT RUN.
1. CAUSE: POWER INTERRUPTION
REMEDY: Check external power supply. Look for blown fuses or tripped circuit breakers. Reset or replace if needed.
2. (REASON) THERMOSTAT INOPERABLE.
REMEDY: Setting may be too high or to low; check and reset. Thermostat may be out of calibration or otherwise defective...remove and replace.
3. (CAUSE) POWER MODULE:
(REMEDY) Correct as follows: (a) Replace;
PROBLEM: EVAPORATOR FAN RUNS BUT COMPRESSOR AND CONDENSER FAN DO NOT START
1. (REASON) Low Voltage.
(FIXING) Check power supply for voltage outside the range of 106-126 volts on the 115volt unit and 187-253 volts on the 208/230 volt unit.
2. (CAUSE) Thermostat
(REMEDY) Examine the control unit for loose display cable and tighten.
3. (REASON) High Pressure Control cutting turning unit off
(FIXING) Depress high pressure switch red button, check for loose wire connections, broken or burned contacts. If switch is defective, replace.
4. (CAUSE) Defective Power Module. (CURE) Replace
5. (REASON) Refrigerant leak-no freon. (REMEDY) Locate leak and repair. Evacuate unit and recharge.
6. (CAUSE) Loose or defective wires. (FIXING) Tug on wires to see if they will separate from connections.
7. (REASON) Defective compressor (REMEDY) Check for shorts, opens and grounds. Remove and replace compressor.
17
8. CAUSE) Shorted or open run capacitor (FIXING) Remove and replace.
9. (CAUSE) Defective tank full unit cut-out switch. (REMEDY) Check and replace.
10 (CAUSE) Condensate tank could be full, but, red con display not appearing in display window. (REMEDY) Check tank and replace red light if defective.
PROBLEM: COMPRESSOR STARTS AND RUNS, BUT, EVAPORATOR FAN DOES NOT RUN.
1. (CAUSE) Faulty power module (REMEDY) Replace
2. (REASON) Open fan motor coil circuit (FIXING) Replace fan motor.
3. (CAUSE) Shorted or open fan motor capacitor (REMEDY) Replace capacitor.
4. (REASON) Loose or defective wires (REMEDY) Trace and repair
PROBLEM: INSUFFICIENT COOLING/HEATING
1. (CAUSE) Insufficient air flow through evaporator coil due to:
A. Dirty air filter in unit B. Dirty evaporator coil
C. Ice on evaporator coil D. Obstructed air intake
(REMEDY) Correct as noted:
A. Clean filter (see "Preventive Maintenance" section of this manual)
B. Clean coil with a vacuum cleaner & hose.
C. Defrost; turn on fan only.
D. Remove obstruction
2. (REASON) IMPROPER SIZING OF UNIT (FIXING) Check to make sure unit is properly sized for load. Add supplemental unit if required.
Problem: Unit does not switch from heating to cooling or cooling to heating . Fixing: a) Check reversing valve. b) Check reversing valve coil.
PROBLEM: NOISY OPERATION
1.(CAUSE) Copper tubing vibrating
(REMEDY) Adjust by bending slightly to firm position. Segregate tubes touching cabinet or each other.
18
2.(REASON) Loose cabinet or internal component
(FIXING) check and tighten loose screws.
3.(CAUSE) Machine vibrating out of level
(CURE) Level unit base.
4.(REASON) Loose blower assembly.
(REMEDY) Tighten bolts on blower assembly to blower mounting panel.
5.(CAUSE) Blower wheel hitting coil partition. (Unit probably received rough handling or was dropped).
(REMEDY) Adjust coil partition to clear motor.
6. (CAUSE) Blower motor bearing defective.
(REMEDY) Replace blower motor.
PROBLEM: WATER LEAKING FROM PAN
1. (CAUSE) Leaky drain pan
(REMEDY) Locate leak and repair pan.
2. (CAUSE) Loose evaporator, drain or condensate pump hose
(REMEDY) Tighten connections.
3. (CAUSE) Defective condensate pump or excessive lift on pump
(REMEDY) Examine to see if elevation exceeds 20 ft. (if it does, a larger pump will be required). Otherwise, change pump if defective. Pump will operate properly against 20 ft. of water total head pressure on pump. If combination of vertical height and horizontal drain line exceeds 20 ft. of water pressure drop, problems will occur.
PROBLEM: THERMOSTAT (LCD) LIQUID CRYSTAL DISPLAY WINDOW DOES NOT ILLUMINATE.
1. (CAUSE) Check discharge air and return air sensers.
(REMEDY) Replace
19
PREVENTIVE MAINTENANCE
2OAC/OACH Series air conditioners are designed to last a long time and to give maximum performance and reliability with minimum maintenance. To prolong the life of the unit, regular maintenance must be performed as specified below:
1. BLOWER MOTOR ASSEMBLY
The motors for all models are sealed and require no oiling. Dust and dirt may be removed from the motor vanes by washing, blowing with an air hose or with a vacuum.
2. FILTERS
A clogged filter will cause the unit to operate at greatly reduced efficiencies. We recommend that the filter be inspected on a regular bases every six weeks or more often depending on the environment. The Evaporator washable foam filter is located behind the return air grille and can be easily removed by pulling the grille out. The condenser washable foam filter is located in the grille on the back of the unit. Remove the grille by lifting it out. The filter can then be removed for washing. The filters must be washed periodically or as needed.
3. CONDENSATE PUMP
When servicing pump follow these steps;
1. Make certain that the unit is disconnected from the power source before attempting to service or remove any component.
2. Be sure the floats move freely. Clean as necessary.
3. Remove the volute and check for obstructions. Clean as needed.
4. Clean the tank with warm water and mild soap when mineral deposits are visible.
5. Check the inlet and outlet piping. Clean as necessary. Be sure there are no kinks in the lines that would inhibit flow.
GENERAL
When necessary maintenance steps outlined above are followed, the air conditioner will provide long and reliable service. The refrigeration and electrical circuits of the system should only be serviced by a fully qualified service technician.
20
AIR COOLED-AIR CONDITIONER
EVAPORATOR BLOWER
SUCTION LINE
MODELS 2OAC/OACH12, 18, 24, 36, 60
PIPING SCHEMATIC
AIR FLOW
HOT GAS BYPASS
ACCESS VALVES
DISCHARGE LINE
CONDENSER BLOWER
MANUAL RE-SET HIGH PRESSURE SWITCH
CONDENSER COIL
CAPILLARY TUBES
STRAINER
COMPRESSOR WITH INTEGRAL ACCUMULATOR
REVERSING VALVE (HEAT PUMP ONLY)
21
MODELS: 2OACH12, 18, 24, 36, 60
OCEANAIRE EXCLUSIVE PORTABLE AIR -COOLED
HEAT PUMP SCHEMATIC
FLOW DURING HEATING MODE
-COOLER AMBIENT TEMPERATURE
AMBIENT AIR TO HEAT EXCHANGER TO EVAPORATE REFRIGERANT
COLD AIR REJECTED TO
AMBIENT
CONDENSER BLOWER
WARM AIR TO
CONDITIONED SPACE
EVAPORATOR BLOWER
FRONT COIL
AMBIENT AIR TO HEAT EXCHANGER TO BE HEATED TO CONDENSE REFRIGERANT
REAR COIL
REVERSING VALVE
HOT GAS BYPASS
ACCUMULATOR COMPRESSOR
CONDENSATE PUMP
2OACH6012
Side View
22
HIGH PRESSURE SWITCH
TANK FULL CUT-OUT SWITCH
COM
N.O.
N.C.
DISPLAY
COMP
DAT/H2O
X
COMP
COM
X
COMP
RUN
5
LOW
FREON
JP
JP
6
X
PUMP
HIGH
X X
PUMP
VAL V E
L-2
L-1
X X
AC
AC L-1
L-2
ALT AIR
FAN
X
FAN
L-2
2
X
FAN
VAL V E
JP
L-1
JP
3
Hard Start
Kit
C
S
R
COMPRESSOR
RUN CAP
CONDENSER
FAN
MOTOR
RUN CAP
HIGH
L1
L2
G
EVAPORATOR
FAN
MOTOR
Oceanaire, Inc.
AIR-COOLED COOLING ONLY
MODELS 2OAC12, 18, 24
115 and 230 Volt
Hard Start Kit Applies to 2OAC1811 Only
23
ArcticAire
Wireoac121824
DISPLAY
COMP
HIGH PRESSURE SWITCH
JP
DAT/H2O
5
LOW
FREON
JP
6
HIGH
TANK FULL CUT-OUT SWITCH
COM
ALT AIR
FAN
JP
3
VA LV E
JP
2
N.O.
N.C.
RUN CAP
S
R
62K 3W
T1
T2
COMPRESSOR
CONTACTOR
230 Volt
Coil
C
X
X X
COMP
COMP
RUN
COM
L1
L2
PUMP
X
PUMP
L-2
X
VA LV E
L-1
X X
AC
AC L-1
L-2
FAN
X
L-2
X
FAN
L-1
RUN CAP
RUN CAP
HIGH
EVAPORATOR
FAN
MOTOR
CONDENSER
FAN
MOTOR
208/230/1
COMPRESSOR
L1
Oceanaire, Inc.
AIR-COOLED COOLING ONLY
MODEL 2OAC3612
208/230/1 Volt
24
L2
G
ArcticAire
Wir2oac3612
COMP
DISPLAY
HIGH PRESSURE SWITCH
JP
DAT/H2O
5
LOW
FREON
JP
6
HIGH
TANK FULL CUT-OUT SWITCH
COM
ALT AIR
FAN
JP
3
VAL V E
JP
2
N.O.
N.C.
COMPRESSOR
CONTACTOR
208/230/3 VOLT COMPRESSOR
x x x
COMP
COMP
RUN
COM
62K 3Watt
T1
T2
T3
T1
L1
L2
L3
T2
T3
PUMP
x
x x x x
PUMP
VAL V E
L-2
L-1
FAN
x
FAN
L-2
L-1
AC
AC L-1
L-2
RUN CAP
HIGH
230 VOLT
EVAPORATOR
FAN
MOTOR
RUN CAP
NOTE:
Compressor has only one proper rotation direction. If compressor is unusually noisy and does not cool, it may be running backwards. This is not unusual for 3 phase equipment.
TO CORRECT THIS:
Unplug power cord from outlet, remove side panel at electrical box and reverse any two of the power leads on the compressor contactor. Example, move L1 wire to L2. And move L2 wire to L1. Re­install side panel, plug unit in and re-start.
230 VOLT
CONDENSER
FAN
MOTOR
L1
L2
L3
G
Plug for 2OAC3632 L15-20P
Oceanaire, Inc.
AIR-COOLED COOLING ONLY
ArcticAire
MODEL 2OAC3632
208/230 VOLT 3 PHASE
25
Wire2oac3632
COMP
DISPLAY
HIGH PRESSURE SWITCH
JP
DAT/H2O
5
LOW
FREON
JP
6
HIGH
N.C.
SAFETY SWITCH
ALT AIR
FAN
JP
3
VA LV E
JP
2
N.O.
COM
CONDENSATE
PUMP
RUN CAP
S
R
62K 3W
T1
T2
COMPRESSOR
CONTACTOR
230 Volt
Coil
C
X
X X
COMP
COMP
RUN
COM
L1
L2
PUMP
X
PUMP
L-2
X
VA LV E
L-1
X X
AC
AC L-1
L-2
X
FAN
L-2
X
FAN
L-1
RUN CAP
RUN CAP
HIGH
EVAPORATOR
FAN
MOTOR
CONDENSER
FAN
MOTOR
208/230/1
COMPRESSOR
L1
L2
G
Oceanaire, Inc.
AIR-COOLED COOLING ONLY
MODEL 2OAC6012
208/230/1 Volt
26
ArcticAire
Wirdia2oac6012
HIGH PRESSURE SWITCH
COMPRESSOR
CONTACTOR
DISPLAY
COMP
62K 3Watt
T1
DAT/H2O
x
COMP
COM
L1
x
COMP
RUN
5
LOW
FREON
JP
JP
6
x
PUMP
HIGH
x
PUMP
L-2
x
VAL V E
L-1
x
AC L-1
x
AC L-2
ALT AIR
FAN
FAN
x
L-2
2
x
FAN
L-1
VAL V E
JP
JP
3
T1
208/230/3
COMPRESSOR
NOTE:
Compressor has only one proper rotation direction. If compressor is unusually noisy and does not cool, it may be running backwards. This is not unusual for 3 phase equipment.
TO CORRECT THIS:
Unplug power cord from outlet, remove side panel at electrical box and reverse any two of the power leads on the compressor contactor. Example, move L1 wire to L2. And move L2 wire to L1. Re­install side panel, plug unit in and re-start.
T2
T3
L2
L3
T2
T3
L1
L3
L2
Plug for 2OAC6032 L15-30P
AIR-COOLED COOLING ONLY
G
Oceanaire, Inc.
MODEL 2OAC6032
208/230 VOLT 3 PHASE
27
HIGH
RUN CAP
230 VOLT
EVAPORATOR
FAN
MOTOR
230 VOLT
CONDENSER
FAN
MOTOR
ArcticAire
S. SW
230 VOLT
CONDENSATE
PUMP
RUN CAP
Model 2 is factory
OAC6032
equipped with a condensate pump. A condensate bucket is an option.
Wire2oac6032
NC
NO
COM
not
HIGH PRESSURE SWITCH
COMPRESSOR
CONTACTOR
DISPLAY
COMP
62K 3Watt
T1
DAT/H2O
X
COMP
COM
L1
JP
5
JP
6
HIGH
LOW
FREON
X X X
COMP
PUMP
RUN
PUMP
L-2
X X X
AC
VAL V E
L-1
L-1
AC L-2
ALT AIR
FAN
JP
3
X X
FAN
L-2
VAL V E
JP
2
FAN
L-1
T1
460 VOLT
COMPRESSOR
2KVA
TRANSFORMER
230 VOLT
460 VOLT
NOTE:
Compressor has only one proper rotation direction. If compressor is unusually noisy and does not cool, it may be running backwards. This is not unusual for 3 phase equipment.
TO CORRECT THIS:
Unplug power cord from outlet, remove side panel at electrical box and reverse any two of the power leads on the compressor contactor. Example, move L1 wire to L2. And move L2 wire to L1. Re­install side panel, plug unit in and re-start.
T2
T3
L2
L3
T2
T3
L1
L2
L3
Plug for 2OACH6034 L16-30P
AIR-COOLED COOLING ONLY
G
Oceanaire, Inc.
MODELS 2OAC6034 460 VOLT 3 PHASE
28
HIGH
230 VOLT
EVAPORATOR
FAN
MOTOR
230 VOLT
CONDENSER
FAN
MOTOR
ArcticAire
RUN CAP
S. SW
230 VOLT
CONDENSATE
PUMP
RUN CAP
Model is factory
2OAC6034
equipped with a condensate pump. A condensate bucket is not an option.
NC
NO
COM
Wireoac6034
HIGH PRESSURE SWITCH
TANK FULL CUT-OUT SWITCH
COM
N.O.
N.C.
DISPLAY
COMP
JP
DAT/H2O
X
COMP
COM
5
6
LOW
FREON
X X X X
COMP
PUMP
RUN
JP
HIGH
PUMP
L-2
X X X X
AC
VAL V E
L-1
L-1
ALT AIR
FAN
FAN
L-2
2
FAN
VAL V E
JP
L-1
JP
3
AC L-2
Hard Start
Kit
S
R
COMPRESSOR
RUN CAP
RUN CAP
C
CONDENSER
FAN
MOTOR
L1
L2
HIGH
EVAPORATOR
FAN
MOTOR
REVERSING VALVE
110 Volt or 230 Volt
G
HEAT PUMP
Oceanaire, Inc.
AIR-COOLED HEATING/COOLING
MODELS 2OACH12, 18, 24
115 and 230 Volt
Hard Start Kit Applies to 2OACH1811 Only
29
ConvertibleAire
wireoach121824
DISPLAY
COMP
HIGH PRESSURE SWITCH
JP
DAT/H2O
5
LOW
FREON
JP
6
HIGH
TANK FULL CUT-OUT SWITCH
COM
ALT AIR
FAN
JP
3
VA LV E
JP
2
N.O.
N.C.
RUN CAP
S
R
62K 3W
T1
T2
COMPRESSOR
CONTACTOR
230 Volt
Coil
C
X
X X
COMP
COMP
RUN
COM
L1
L2
PUMP
X
PUMP
L-2
X
VA LV E
L-1
X X
AC L-1
L-2
AC
FAN
FAN
L-2
L-1
X
X
RUN CAP
RUN CAP
HIGH
EVAPORATOR
FAN
MOTOR
CONDENSER
FAN
MOTOR
208/230/1
COMPRESSOR
HEAT PUMP
ConvertibleAire
REVERSING
VA LV E
L1
L2
Oceanaire, Inc.
AIR-COOLED HEATING/COOLING
MODEL 2OACH3612
208/230/1 Volt
30
G
Wir2oach3612
COMP
DISPLAY
HIGH PRESSURE SWITCH
JP
DAT/H2O
5
LOW
FREON
JP
6
HIGH
TANK FULL CUT-OUT SWITCH
COM
ALT AIR
FAN
JP
3
VAL V E
JP
2
N.O.
N.C.
COMPRESSOR
CONTACTOR
208/230/3
COMPRESSOR
T1
62K 3Watt
T1
T2
T3
x
x
COMP
COMP
RUN
COM
L1
L2
L3
T2
T3
x
PUMP
x
PUMP
L-2
x
VAL V E
L-1
x
AC L-1
x
AC L-2
FAN
x
L-2
x
FAN
L-1
HIGH
230 VOLT
EVAPORATOR
FAN
MOTOR
RUN CAP
RUN CAP
NOTE:
Compressor has only one proper rotation direction. If compressor is unusually noisy and does not cool, it may be running backwards. This is not unusual for 3 phase equipment.
TO CORRECT THIS:
Unplug power cord from outlet, remove side panel at electrical box and reverse any two of the power leads on the compressor contactor. Example, move L1 wire to L2. And move L2 wire to L1. Re­install side panel, plug unit in and re-start.
L1
L3
L2
G
Plug for 2OACH3632 L15-20P
Oceanaire, Inc.
AIR-COOLED HEATING/COOLING
MODEL 2OACH3632
208/230 VOLT 3 PHASE
31
Reversing Valve 230 volt
230 VOLT
CONDENSER
FAN
MOTOR
Model is factory equipped with a condensate bucket. However, a condensate pump may be added as an option.
HEAT PUMP
ConvertibleAire
2OACH3632
Wire2oach3632
DISPLAY
COMP
HIGH PRESSURE SWITCH
JP
DAT/H2O
5
LOW
FREON
JP
6
HIGH
N.C.
SAFETY SWITCH
ALT AIR
FAN
JP
3
VAL V E
JP
2
N.O.
COM
CONDENSATE
PUMP
RUN CAP
S
R
62K 3W
T1
T2
COMPRESSOR
CONTACTOR
230 Volt
Coil
C
X
X X
COMP
COMP
RUN
COM
L1
L2
PUMP
X
PUMP
L-2
X
VAL V E
L-1
X X
AC L-1
L-2
AC
FAN
FAN
L-2
L-1
X
X
RUN CAP
RUN CAP
HIGH
EVAPORATOR
FAN
MOTOR
CONDENSER
FAN
MOTOR
REVERSING VALVE
230 Volt
208/230/1
COMPRESSOR
HEAT PUMP
ConvertibleAire
L1
L2
G
Oceanaire, Inc.
AIR-COOLED HEATING/COOLING
MODEL 2OACH6012
208/230 Volt
32
Wirdia2oach6012
HIGH PRESSURE SWITCH
COMPRESSOR
CONTACTOR
DISPLAY
COMP
62K 3Watt
T1
DAT/H2O
x
COMP
COM
L1
x
COMP
RUN
5
LOW
FREON
JP
JP
6
x
PUMP
HIGH
x
PUMP
L-2
x
VAL V E
L-1
x
AC L-1
x
AC L-2
ALT AIR
FAN
x
FAN
VAL V E
JP
2
x
FAN
L-2
L-1
JP
3
T1
208/230/3
COMPRESSOR
NOTE:
Compressor has only one proper rotation direction. If compressor is unusually noisy and does not cool, it may be running backwards. This is not unusual for 3 phase equipment.
TO CORRECT THIS:
Unplug power cord from outlet, remove side panel at electrical box and reverse any two of the power leads on the compressor contactor. Example, move L1 wire to L2. And move L2 wire to L1. Re­install side panel, plug unit in and re-start.
T2
T3
L2
L3
T2
T3
L1
L3
L2
Plug for 2OACH6032 L15-30P
AIR-COOLED HEATING/COOLING
G
Valve 230 volt
Oceanaire, Inc.
MODEL 2OACH6032
208/230 VOLT 3 PHASE
33
Reversing
HIGH
RUN CAP
230 VOLT
EVAPORATOR
FAN
MOTOR
230 VOLT
CONDENSATE
RUN CAP
230 VOLT
CONDENSER
FAN
MOTOR
Model is factory equipped with a condensate pump. A condensate bucket is an option.
HEAT PUMP
ConvertibleAire
S. SW
PUMP
2OACH6032
NC
NO
COM
not
Wire2oach6032
HIGH PRESSURE SWITCH
COMPRESSOR
CONTACTOR
DISPLAY
COMP
62K 3Watt
T1
DAT/H2O
X
COMP
COM
L1
JP
5
JP
6
HIGH
LOW
FREON
X X X
COMP
PUMP
RUN
PUMP
L-2
X X X
AC
VAL V E
L-1
L-1
AC L-2
ALT AIR
FAN
JP
3
X X
FAN
L-2
VAL V E
JP
2
FAN
L-1
T1
460 VOLT
COMPRESSOR
2KVA
TRANSFORMER
230 VOLT
460 VOLT
NOTE:
Compressor has only one proper rotation direction. If compressor is unusually noisy and does not cool, it may be running backwards. This is not unusual for 3 phase equipment.
TO CORRECT THIS:
Unplug power cord from outlet, remove side panel at electrical box and reverse any two of the power leads on the compressor contactor. Example, move L1 wire to L2. And move L2 wire to L1. Re­install side panel, plug unit in and re-start.
T2
T3
L2
L3
T2
T3
L1
L2
L3
Plug for 2OACH6034 L16-30P
AIR-COOLED HEATING/COOLING
G
Oceanaire, Inc.
MODELS 2OACH6034
460 VOLT 3 PHASE
34
HIGH
Reversing Valve 230 volt
RUN CAP
230 VOLT
EVAPORATOR
FAN
MOTOR
RUN CAP
230 VOLT
CONDENSER
FAN
MOTOR
Model is factory equipped with a condensate pump. A condensate bucket is not an option.
HEAT PUMP
ConvertibleAire
230 VOLT
CONDENSATE
PUMP
2OACH6034
S. SW
NC
NO
COM
Wireoach6034
Manufacturers of Portable Air Conditioning and Heating Units
Form 2OAC/2OACH-SM-9/15/03