GYROFOCUS:
INSTALLATION AND
USER MANUAL
1. TECHNICAL DATA 2
2. PRE-INSTALLATION 3
3. INSTALLATION 5
4. OPERATION 11
5. TESTING 12
Keep for future use
OBLICA
200 Argyle St
Fitzroy VIC 3065
03 9416 0400
OBLICA | GYROFOCUS INSTALLATION AND USER MANUAL
1. TECHNICAL DATA
DETERMINED UNDER TEST CONDITIONS:
Nominal thermal output 6kW
Efficiency 57,8%
WEIGHT AND DIMENSIONS:
Firebox diameter 1250mm
Firebox weight 92Kg
Flue diameter 219mm
Flue weight 16Kg/meter
Standard bracket weight 20Kg
External flue kit Triple skin 200/250/300mm
ø219 mm
FLUE
ø1250 mm
500 mm
FIREBOX
OBLICA | GYROFOCUS INSTALLATION AND USER MANUAL
2. PRE-INSTALLATION
Congratulations on your purchase of the GyroFocus. This appliance should be installed and checked by a qualified
professional. Ensure you have read the operation guidelines thoroughly prior to first use. For any questions or concerns
please contact Oblica on 03 9416 0400.
The installation process is outlined below:
– Determine position of firebox and flue carefully observing the clearances described within this section
– Install the suspension bracket
– Install the external flue
– Install the internal flue and engage the firebox
– Ensure the floor has adequate protection
CAUTION:
Using components or parts other than those provided by the manufacturer or modifying the specification of components
may result in inferior or unsafe operation. If such action is necessary, consult the manufacturer in the first instance.
WARNING:
• The appliance and flue-system must be installed in accordance with AS/NZS 2918 and the
relevant building code or codes.
• Any modification of the appliance that has not been approved in writing by the testing authority
will be in breach of the approval granted for compliance with AS/NZS 4013.
• Once the flue has been installed and approved by a professional installer, the flue must not be
modified in any way.
OBLICA | GYROFOCUS INSTALLATION AND USER MANUAL
MINIMUM CLEARANCE – INTERNAL
2.1 Clearance from non-combustible surfaces
(eg masonry)
100mm minimum clearance is required from fully
non-combustible surfaces.
100
100
1200
1200
Combustible
FULLY ROTATING
Combustible
Combustible
FIXED
Combustible
2.2 Clearance from glass
500mm minimum clearance is required from normal
non-combustible glass.
350mm minimum clearance is required from
toughened glass.
100
100
520
520
Non Combustible
Non Combustible
1200
1200
Combustible
FULLY ROTATING
Combustible
Combustible
FIXED
Combustible
(frameless or aluminium frame)
Glass
(frameless or aluminium frame)
2.3 Clearance from combustible surfaces
(eg timber joist & plasterboard)
1200mm minimum clearance is required on all sides
when the GyroFocus can rotate 360˚ .
1200
1200
Combustible
FULLY ROTATING
Combustible
Combustible
FIXED
Combustible
520mm minimum clearance is required if the rotation
of the GyroFocus is locked at 120˚ or 90˚ away from the
wall. Locking the GyroFocus so that the opening is fixed
is an option available on purchase.
Combustible
FIXED
Combustible
Clearances may be reduced with the application of
heat shielding to walls in accordance to the Australian
Building Code.
For information on heat shielding please contact our
office on 03 9416 0400 or email info@oblica.com.au.
IMPORTANT:
Frames must also be considered. Timber window
frames must be treated as combustible surfaces
(see 2.3). Aluminium frames can be treated as
non-combustible surfaces (see 2.2).
2. PRE-INSTALLATION (CONTINUED)