Assembly Components:
- Ceiling enclosure Model 1075-AP135 assembly – 1 each
- Ceiling tile bridge – 2 each
- #8-32 X 1/4 “ screw –4 each
- #8-32 nut – 4 each
- 3/4” Trade Size Cable Clamp – 1 each
- Keys for access door lock – 2 each
- Support wire – 4 each
- Fire Block Foam – 1 each
If any of these items are missing, contact your Oberon representative.
Find a flat work surface to assemble the ceiling
enclosure, access point and antenna(s) prior to
mounting in ceiling.
Step 1 - Cut a 13” x 13” opening in the center of a
ceiling tile (not included – ref. Figure 1).
Page 2
Installation Instructions
Model Number 1075-AP135
This product is Listed by Underwriters
Laboratories Inc. Representative
samples of this product have been
evaluated by UL and meet applicable
Step 2 – Place the ceiling enclosure assembly on the
work surface. Remove one of the 1” trade size hole
cover on the side of the enclosure and install the 1”
conduit nipple (the side on which the conduit nipple is
to be installed will be determined by the location the
enclosure is to be installed and direction from which
conduit will be brought into the enclosure – ref. Figure
2).
safety standards.
File #E348543
Step 3 –Lay ceiling tile over the
enclosure assembly such that
the previously cut opening in the
ceiling tile is equally spaced
around the outside of the
enclosure (ref. Figure 3). Place
the ceiling tile bridges along
each side of the enclosure and
attach using a #8-32 screw.
Prior to tightening, be sure to
properly align the tile bridges so
the ends of the tile bridges align
with the outside edge of the
ceiling tile. Once the tile bridges
are properly aligned, press the
shoulder of the tile bridge down
firmly against the tile and then
securely tighten the screws.
This is to assure that there is
minimal gap between the
enclosure’s flange and the
ceiling tile once it is placed in
the ceiling. The four (4) holes on
the tile bridge will be used to
secure the enclosure with grid
wires.
Step 4 – Install the
mounting plate onto the
mounting bracket using
the (4) # 4-40 screws. The
tabs of the mounting plate
should be facing up
toward the cutout on the
bracket. Slide the access
point onto the mounting
plate, locking the tabs to
the underside of the
access point The door
assembly is completed by
attaching the previously
assembled mounting
plate/access point assembly
to the enclosure door by
securing it in place with four
(4) #8-32 hex nuts. Place the
slotted holes in the mounting
plate/access point assembly
over the studs located on the bottom side of the door (NOTE: the mounting plate can only be attached to the door in one direction. If the
slotted holes don’t match up with the studs in the door, rotate the mounting plate 180°). Once the mounting plate is positioned, secure it in
place by installing four (4) #8-32 hex nuts (Figure 5).
Page 3
Figure 3 - Installation to ceiling tile.
Figure 5 – Exploded door view.
Rev. A2 05/23/13 Oberon, Inc. •••• 1315 South Allen Street •••• State College, PA 16801 Copyright 2012
(877) 867-2312 • www.oberonwireless.com

Step 5 – Remove the ceiling tile
from the location where the
access point enclosure is to be
placed (if necessary) and
replace with the assembled unit
(ref. Figure 6). Use a minimum
of two separate grid wires to
attach the access point
enclosure to the ceiling. Attach
one end of the wire to the
eyebolts and the other end to a
permanent structure within the
ceiling such as a ceiling joist.
MODEL 1075-AP135
Installation Instructions
**** WARNING ****
**IMPORTANT** - This is
an important safety feature
that could prevent human
injury or damage to the
access point should the unit
become dislodged from the
ceiling grid work.
Figure 6 - Ceiling installation.
Step 6 – Once the assembly has been installed in the ceiling and secured using grid wire, open the door and run the Ethernet
cable into the enclosure through the conduit nipple located on the side of the access point enclosure and attach to the access
point prior to installing on mounting plate.
Insert foam into the conduit connector and pull the data cable through far enough to allow attachment to the access point (8" -
10"). Tighten cable clamp around foam fire block so that there are no air gaps. Be careful not to over tighten and crush the
Ethernet cable(s).
Page 4
Please thoroughly read the product warning below
before installation to provide for a safe work
environment.
1. Ceiling mounted products should be installed in accordance with National Electric Code paragraphs 300.10 (Electrical
Continuity of Metal Raceways and Enclosures) and 300.11 (Securing and Supporting). Independent support wires or
other means must be used for the installation of this product in the ceiling. Acoustical, suspended, false, drop and
concealed spline ceiling grid work is not designed to support the weight of this product. Oberon’s ceiling mounted
products have four support wire tabs on the back box. These tabs shall be used for supporting the product with
independent support wires, wire rope, threaded rod, or other secure support means of adequate gauge and fire
resistance.
2. When closing the enclosure access door, be sure that the cam lock is completely engaged to prevent the access door
from accidentally swinging open.
3. When opening the enclosure door, be sure to support the door to prevent the door from accidentally falling open.
4. This enclosure has a maximum operating ambient of 55º C (131º F), the temperature within the enclosure may not
exceed this temperature, depending on power dissipation within enclosure.
5. A minimum air clearance of 1“ between the housing of the access point and the enclosure side walls must be
maintained for the safe operation of the equipment.
6. This product is intended to be installed by trained personnel.
7. Only Listed ITE products and Listed AC Receptacles shall be installed within the enclosure.
8. This product is to be repaired by personnel trained by the manufacturer or returned to the manufacturer for repair or
replacement.
9. Maximum weight to be installed in the unit is 25 lbs.
10. All knockouts, openings, and holes shall be sealed with a plug constructed of metal, or a non-metal material that
complies with UL 2043 or UL 1479.
11. All unused mounting holes should be sealed with tape or other material that complies with UL 1479.
12. If AC power is used inside the enclosure, connect the ground wire to the green ground screw located near the
knockout in the backbox.
Page 1