• Main Connect Port: To connect the bus line and the electronic locks.
• BUS: Connect to the bus line, no polarity.
• PL: External lock power input, connect to the power positive(power +).
• S+: Lock power(+) output.
• S-: Lock power(-) output, connect to the power(-) input of locks(only when using the door
station to power the locks, if using the external power supply for the locks, the S- will not be
connected).
3.Door Station Mounting
DT601/KP/FE Mounting
12
Drill holes in the wall to match the size of
screws and attach the rainy cover to the wall.
Attach the panel to the rainy coverUse the screwdriver and the screw
Connect the cable correctly
43
to fix the panel
-2-
DT601F/KP/FE Mounting
12
Drill a hole in the wall to match the size of the
mounting box and attach to the wall.
Attach the panel to the mounting box and
use screws supplied to fix the panel
Connect the cable correctly
43
Placing Name Label
Use a screwdriver to unscrew the screw, and cock the host , then Placing Name Label.
-3-
AcDbMLeader (ACDB_MLEADER_CLASS)
AcDbMLeader (ACDB_MLEADER_CLASS)
4.System Wiring and Connections
Switch
Basic Connection
AC~
Code=00, DIP6=on
PC6A
L1
L2
DIP Switches
ON DIP
1 2 3 4 5 6
Doorbell Button
Electric Lock Connection
Door Lock Controlled with Internal Power
Note:
1. Electronic lock of Power-on-to-unlock type
should be used.
2. The door lock is limited to 12V, and holding
current must be less than 250mA.
3. The door lock control is not timed from Exit
Button(EB).
4. The Unlock Mode Parameter of Monitor
must be set to 0 (by default).
BUS(IM) BUS(DS)
1 2 3
Jumper position in 2-3
BUSPLS+S-
EB
*
L1 L2 PL S+ S-
-
+
LOCK
-4-
Door Lock Controlled with Dry Contact
Note:
1. The external power supply must be used according
to the lock.
2. The inside relay contact is restricted to AC or DC
24V/1A.
3. The jumper must be taken off before connecting.
4. Setup the Unlock Mode of Monitor for different
lock types.
• Power-on-to-unlock type:Unlock Mode=0
(by default)
• Power-off-to-unlock type:Unlock Mode=1
Unlock parameter setting(set in monitor)
• On main menu page, touch [Logo] icon to enter About page.
Take off the Jumper
BUSPLS+S-
POWER
SUPPLY
LOCK
• When the screen stay in About page, press
UNLOCK button on front panel and hold for 2
seconds.
• A keypad is shown.
Refer to the followings:
00:10 DS-1
About
Local Address 00.00
Video Standard
System Verson 00.01.00
Display Driver 1.0
Font 1.0
UI 1.0
AUTO
INSTALLER SETUP
_
? + OK: Help Menu
@ + OK: Address Setting Menu
Note:
1.must connect DT601(F)/KP/FE correctly before setting.
2.the parameter will be saved in DT601(F)/KP/FE automatically,so you need only set on one monitor.
3.Here we take DT47MG(the monitor) for example, please refer to the corresponding user manual.
-5-
123
Multi Door Stations Connection
4# Camera
(Device Address:3)
L1 L2 PL S+ S-
3# Camera
(Device Address:2)
L1 L2 PL S+ S-
2# Camera
(Device Address:1)
L1 L2 PL S+ S-
(Device Address:0)
A B C D
DBC4A1
OFF
ON
Impedance
switch
Multi Monitors Connection
Basic IN-OUT Wiring Mode
Code=14Code=15
1# Camera
L1 L2 PL S+ S-
AC~
100~240VAC
PC6A
BUS(IM) BUS(DS)
Code=0
AC~
100~240VAC
PC6A
BUS(IM) BUS(DS)
2 3
1
4 5 6
98
7
0 #
*
(Device Address:0)
NOTE:Here we take DT47MG(the monitor) for example.
-6-
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.