nvent raychem touch 1500 Installation Instructions Manual

Page 1
WARNING:
IMPORTANT:
TOUCH 1500
User Interface Terminal for Systems Installation Instructions
TOUCH 1500 installed in a panel
KIT CONTENTS
Qty Description
1 TOUCH 1500 display 10 Mounting clips 1 ADAM 4069-CID2 relay module 1 5-ft 9-pin RS-232 (null modem) cable
APPROVALS/CERTIFICATIONS
Nonhazardous Locations
E180881
I.T.F.
General
Area of use Nonhazardous, Indoors (IP65, NEMA 4) Supply voltage 10 – 30 Vdc
Amperage rating
Operating temperature Storage temperature Dimensions 449.9 mm W X 315.6 mm H X 141.7 mm D
Alarm Outputs
Relay output One Form C relay rated at 3 A @ 250 Vac.
LCD Display
Display LCD is a 15-in XGA, color TFT transective device with
Touch Screen 4-wire resistive touch screen interface for user entry
Steady state Surge current 16 A 0°C to 50°C (32°F to 122°F) w/o space heater, –30°C to 50°C (–22°F to 122°F) using space heater and screen cover –20°C to 60°C (–4°F to 140°F)
(17.74 in. W X 12.44 in. H X 5.58 in. D)
Relay is used as a common alarm.
integral CCFL backlight
1.8 A
RAYCHEM
NGC
DESCRIPTION
The nVent RAYCHEM TOUCH 1500 is a panel mounted touch screen display used in conjunction with nVent RAYCHEM NGC-40 and NGC-20 (Europe only) control and monitoring devices. The TOUCH 1500 is rated IP 65 (NEMA 4) and is approved for nonhazardous indoor locations. The TOUCH 1500 kit includes all hardware required for mounting in a suitable electrical panel. These instructions describe how to mount the TOUCH 1500 in an electrical panel and are intended only for personnel experienced in panel construction.
TOOLS REQUIRED
• Masking tape • #16 (3/16) drill bit
• Metal file • Phillips screwdriver
• Jig saw (recommend using carbon steel blade with 24TPI)
ADDITIONAL MATERIALS (TO BE ORDERED SEPARATELY)
Qty Description Manufacturer Manufacturer PN
2 Serial Communication cable L-COM "CSMN9MF-xx
11 Terminal Blocks Weidmuller 163205 1 Type ZS1 Fuse Block Weidmuller 161649 4 PE Terminal (Earth Ground) Weidmuller 1632080000 6 End plates / Partition Weidmuller 1632090000
1 End plate / Partition Weidmuller 1896330000 6 End Plate Stops Weidmuller 38356 2 Jumpers, 2 Position Weidmuller 1608950000 2 Jumpers, 3 Position Weidmuller 1608960000 1 Fuse, 1 amp, 250 V Square D MLD-1 1 Power Supply, 24 Vdc, 2.5 Amp Mean Well DR-120-24 1 Push to test alarm light; Idec 24 Vdc Idec ALW29911-D-R-24
xx=Length in Ft."
Network Connection
Local/ Remote Port
Local RS-232 A non-isolated, 9 pin D sub male Remote RS-485 2-wire isolated, 9 pin D sub male Data rate 9600 to 57600 baud
Maximum cable length Field Port RS-485, 2-wire isolated. Used to communicate with
Signals 2-wire isolated, 9 pin D sub male
Data rate To 9600 baud LAN 10/100 Base-T Ethernet port with Link and Activity Status
USB Ports USB 2.0 Host port Type A receptacle (X4)
* RS-232/RS-485 ports may be used to communicate with host computers DTS (nVent RAYCHEM Supervisor Software) or DCS
For RS-485 not to exceed 1200 m (4000 ft). Cable to be shielded twisted pair.
external devices, such as nVent RAYCHEM NGC-40-BRIDGE. Maximum cable length not to exceed
1200m (4000 ft). Cable to be shielded twisted pair.
LEDs (X2)
FIRE HAZARD: The Touch 1500 must not be used in hazardous locations. Electrical components within the unit could ignite flammable gases. Do not install the unit where it may be exposed to flammable gases.
The TOUCH 1500 is an electronic unit. During installation, take the following precautions to avoid damage to its electronic components.
• Handle with care to avoid mechanical damage.
• Keep electronics dry.
• Avoid exposure to static electricity.
• Avoid contamination with metal filings, liquids, or other foreign matter.
• Use agency-approved conduit bushings, adapters, and cable glands to keep the enclosure protected from dust and fluids.
Page 2
Provide Suitable Panel Enclosure, and Determine Locations for TOUCH 1500 Assembly in Panel X
1. Provide suitable panel enclosure
To protect its electronic components, the TOUCH 1500 must be mounted in a non-hazardous location panel with a minimum IP32 (NEMA 1) enclosure. An IP52 (NEMA 12) or better enclosure is recommended. The TOUCH 1500 assembly comes with a sealing gasket and hardware to mount the enclosure.
Note: The RAYCHEM TOUCH 1500 is designed for operation in ambient temperatures from 0°C to 50°C (32°F to 122°F). If the ambient temperature is outside this range, a space heater with screen window kit and/or cooling fan will be required in the panel.
Panel door
assembly location
Alarm light
2. Determine locations for the TOUCH 1500 assembly in the electrical panel
The TOUCH 1500 should be located on the front of the panel near eye level (for convenient viewing). The TOUCH 1500 assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration.
PanelTouch 1500
C1
C2 C3 C4 C5 C6 C7 C8 C9 C10
1
3
5
7
9
11
13
15
17
19
CB1
CB2 CB4
CB3 CB5
CB6
CB7
CB8
CB9
CB10
CB11
CB12 CB14
CB13
CB16
CB15
CB18
CB17
CB20
CB19 CB21
CB22
CB23
CB24
CB25
CB26
CB27
CB28
CB29
CB30
CB31
CB32
CB33
CB34
CB35
CB36
CB37
CB38
CB39 CB40
CB42
2
4
6
8
10
12
14
16
18
20
2 | nVent.com
21
23
25
27
29
31
33
35
37
39
22
24
26
28
30
32
34
36
38
40
Page 3
Cut Opening and Mount TOUCH 1500 on Front of Panel
1. Locate the TOUCH 1500 on front of panel
Locate the TOUCH 1500 assembly on the front of the panel at a level convenient for viewing. Make sure the cover on the back of the assembly will not interfere with existing panel hardware.
Panel Door
292 mm
11.5 in.
422 mm
16.6 in.
Cutting
Area
Note: Cutting the opening for the display is a craft sensi­tive procedure; if it is not done correctly, the panel door can be damaged. The procedure for laying out and cutting the opening for the display must be undertaken with
care, and by personnel qualied and experienced in panel
construction.
2. Prepare and mark the position of the display opening and mounting holes
• Use the cut-out directions to lay out the opening for the TOUCH 1500 display.
• Apply two layers of masking tape around the outer pe­rimeter of the intended opening to prevent scratching the panel surface with the jigsaw.
3. Cut the display opening
Cut the opening for the TOUCH 1500 with a jigsaw using a 24 TPI blade. Take care not to damage the panel door. Remove all rough edges and burrs with a metal file before proceeding.
Note: The following steps are most easily accomplished if the panel door is on a horizontal surface.
4. Mount the user interface assembly onto the panel door
• Place the TOUCH 1500 assembly in position. Secure the screen to the enclosure with the 10 mounting clips.
TOUCH 1500 display
G
+–
Inside of panel door
Panel door
G
+–
TOUCH 1500 display with sealing gasket
• Place the supplied mounting clips in each slot along the sides of the TOUCH 1500. Fasten only hand tight.
TOUCH 1500 display
G
+–
Mounting clips
• Look at the front of the panel, and align the TOUCH 1500 assembly so it is level (loosen clips if necessary to reposi­tion the assembly).
• After the display is properly positioned, tighten the mounting clips. Do not overtighten and risk damage to hardware.
nVent.com | 3
Page 4
TOUCH 1500 Cut Out Dimensions
(11.5 in)
292 mm
Panel Cut Out
Panel Cut Out
422 mm (16.6 in)
Top of Display
Panel Cut Out Area
Drawing
Drawing
NOT TO SCALE
NOT TO SCALE
4 | nVent.com
Page 5
TOUCH 1500 Connection Diagram
Incoming
power
+ – G
Reset
Switch
RS-232
Com 1
Remote Port
Connect Power
Connect 10 – 30 Vdc to the male power connection tting
located on the bottom side of the TOUCH 1500. Note the polarity of the wires.
Ethernet
Ethernet
Field Port
USB port (X4)
RS-485
Com 4
Remote Port
Compact flashKeyboardMouse
RS-485
Com 3
Field Port
G
10 – 30 Vdc
+
Incoming
power
+ – G
Communication
The TOUCH 1500 has two isolated RS-485 ports located at the bottom.
Field Side Port (RS-485)
The RS-485 port labeled “Com 3” is the eld side port that
is used to communicate with ModBus devices (ie. NGC-40­BRIDGE and NGC-20).
*Remote Port (RS-485) – Optional
The RS-485 port labeled “Com 4” is the Remote side port that is used to communicate with to a host computer DTS (using RAYCHEM Supervisory Software) or to a DCS.
*Local Host Port (RS-232) – Optional
The RS-232 port can be used as local Host port that is used to communicate with to a host computer (using RAYCHEM Supervisory Software).
nVent.com | 5
Page 6
Field Port Communication RS-485 Common Alarm Light and Alarm Relay
Mount the supplied ADAM 4069-CID2 module, 9-pin D sub to 10 pin terminal block and 4 terminal block (with 2 position jumpers) on a DIN rail inside the panel enclosure. Mount the alarm light on the panel's door below the touch screen.
Wire per the schematic below.
Shield
Data +
Field port (to Bridge, NGC-20)
Data –
2
1
RL4NO
RL4COM
ADAM-4069-CID2
RL5NO
RL5COM
Alarm Lamp
3
24 V Lamp
4
Idec Switch/Lamp
Alarm Lamp
RL2NC
RL2NC
RL1NC
RL3NO
RL3COM
RL2COM
RL1COM
RL6NO
RL6COM
RL7NC
RL7COM
RL7NCNCINT+
Jumpers
RL0NO
RL1NO
RL0NC
RL0COM
(Y) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
5 4 3 2 1
T 9 8 7 6
Field
Port
Com 3
+
Ground
120/230 Vac
+ – G
5 4 3 2 1
T 9 8 7 6
Remote
Port
Com 4
(See wiring below)
Serial communication
cable to Field Port/Com 3
(RS-485)
TOUCH 1500
Jumpers
RS-485
RS-485
To Remote Port/Com 4 (RS-485)
Door mounted
Data +
To host computer
Shield
Data –
Remote Port Connection
* Mount the supplied 9-pin D sub to 10-pin terminal block on a
DIN rail inside the panel enclosure.
Wire per schematic to the right.
6 | nVent.com
5 4 3 2 1
T 9 8 7 6
Remote
Port
Com 4
Page 7
Overview of Wiring
Common alarm relay
Shield
Data + Data –
Data + Data –
Field Port
Remote Port
Ø or N
G Ø
RL2NC
RL2NC
RL1NC
RL4NO
RL3NO
RL3COM
RL2COM
RL1COM
RL1NO
RL4COM
ADAM-4069-CID2
RL5NO
RL5COM
RL6NO
RL6COM
RL7NC
RL7COM
RL7NCNCINT+
(Y) D ATA +
2
1
RL0NC
RL0NO
RL0COM
(G) DATA –
(R) +Vs
(B) GND 10
Jumpers
Alarm Lamp
3
24 V Lamp
4
Idec Switch/Lamp
Alarm Lamp
5 4 3 2 1
T 9 8 7 6
Field Port
Com 3
5 4 3 2 1
T 9 8 7 6
Remote
Port
Com 4
Ground
Jumpers
Incoming
Power Terminal
Block
+
+ – G
TOUCH 1500
Door mounted
nVent.com | 7
Page 8
Servicing
The TOUCH 1500 contains no user-serviceable parts. Contact your
nVent representative for service and an authorization number if
required.
Cleaning
The touch screen area of the TOUCH 1500 may be cleaned with a damp or dry cloth. Typical window cleaning agents may be applied to aid in the removal of dirt, dust and grease. Do not use abrasive cleaners.
Reset Switch
The Reset switch can be found on the bottom of the TOUCH 1500.
North America
Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nvent.com
Reset
Switch
+ – G
Europe, Middle East, Africa
Tel +32.16.213.511 Fax +32.16.213.604 thermal.info@nvent.com
Asia Pacific
Tel +86.21.2412.1688 Fax +86.21.5426.3167 cn.thermal.info@nvent.com
Latin America
Tel +1.713.868.4800 Fax +1.713.868.2333 thermal.info@nvent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specications without notice.
Raychem-IM-H58559-INSTALL170-Touch1500-EN-1805
nVent.com