RTD4AL
3 in (76 mm)
2 in (51 mm)
4.25 in
(108 mm)
3/4-in NPT
(19 mm)
conduit
opening
RTD Temperature Sensor for Temperature Measurement up to
900°F (482°C) Installation Instructions
DESCRIPTION
The nVent RAYCHEM RTD4AL is a three-wire platinum RTD
(resistance temperature detector) typically used with monitoring
and control systems that require accurate temperature control.
The RTD4AL kit can be used with a wide variety of RAYCHEM
monitoring and control systems.
These instructions detail the installation of the RTD4AL in
conjunction with existing RAYCHEM component kits.
TOOLS REQUIRED
• 3.5 mm flat-blade screwdriver
ADDITIONAL MATERIALS REQUIRED
• Pipe straps
• Conduit with 16–22 AWG shielded instrument cable or
equivalent armored cable
APPROVALS
The RTD4AL is CSA Certified for use in North America by the
manufacturer for use in Division 2 hazardous locations as follows:
Class I, Division 2, Groups A, B, C, D
Class II, Division 2, Groups F, G
This component is an electrical device. It must be installed correctly
to ensure proper operation and to prevent shock or fire. Read
these important warnings and carefully follow all the installation
KIT CONTENTS
Qty Description
1 RTD Temperature Sensor
SPECIFICATIONS
Sensor housing Aluminum; Type 4X
Sensor sheath 316 stainless steel
Range –100°F to 900°F (–73°C to 482°C) max
Accuracy ±1°F (0.5°C) at 32°F (0°C)
Resistance 100 ohms at 0°C α =0.00385 ohms/ohm/°C
Connection 3/4 in. NPT conduit hub
instructions. Component approvals and performance are based on
the use of specified parts only. Do not use substitute parts or vinyl
electrical tape to make connections.

WIRING INFORMATION
The length of RTD extension wires is determined by the wire
gaugeused.
To reduce the likelihood that electrical noise will affect temperature
measurement, keep RTD extension wires as short as possible.
Use shielded instrument cable such as nVent RAYCHEM
MONI-RTD-WIRE (22AWG, PVC insulation, –30°F to 140°F,
–20°C to 60°C) or Belden 83553 (22 AWG, FEP insulation,
–95°F to 395°F, –70°C to 200°C).
RTD DIRECT CONNECTION
Maximum RTD extension wire length
AWG Feet (meters)
16 4500 (1400)
18 2800 (880)
20 1800 (550)
22 1100 (340)
Place strap under heating cable
INSTALLATION WITH HEATING CABLE ELECTRICAL WIRING GUIDELINES:
Electrical Wiring Notes:
Most electrical codes (such as NEC Article 725) permit Class 1
circuits to occupy the same cable, enclosure, or raceway without
regard to whether the individual circuits are alternating current
JBS-100-A
or direct current, providing all conductors are insulated for the
maximum voltage of any conductors in the cable, enclosure or
raceway.
Additional Materials Required
• JBS-100-A or other power connection kit
• Pipe straps
RTD4AL WIRING
Connect the wires as shown.
1 Note: Ground RTD extension wire shield at one
end only, preferably at RAYCHEM electronics end.
2 Note: RTD housing must be properly grounded
using the screw provided.
Electrical schematic of RTD
Field Wiring
White
White (Common return)
Red
Red (Source)
Red
Red (Compensate)
Conduit
drain
Conduit
drain
Pipe strap
Splice box
(provided by others)
Sensor
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nvent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specications without notice.
Raychem-IM-H56918-RTD4AL-EN-1805 PN 858160-000