nvent Raychem NGC-UIT-OUT, Raychem NGC-UIT2-HAZ Conversion Instructions

WARNING:
NGC-UIT-OUT to NGC-UIT2-HAZ
CONVERSION INSTRUCTIONS
DESCRIPTION
These instructions will guide the installer on how to convert from nVent RAYCHEM NGC-UIT-OUT to nVent RAYCHEM NGC-UIT2-HAZ and are intended only for personnel experienced in panel construction.
TOOLS REQUIRED
• Masking tape • #7 (.201) drill bit
• 11/32 in. Nut Driver • 3/8 in. drill bit
• In-line torque wrench with 3/8 socket
• Zipcut Disc for cutting Stainless Steel panels (5.0 in x 0.45 in x 7/8 in) Note: the Zipcut disc is used to cut the opening in the door for the NGC-UIT2-HAZ display. Other cutting type tools can be used.
General
Area of Use Nonhazardous or hazardous locations,
Supply Voltage 90–240 Vac
Operating Temperature 32°F to 140°F (0°C to 60°C) without
Min. Storage Temperature –40°F to 149°F (–40°C to 65°C)
Dimensions 13.43 in W X 10.87 in H X 3.63 in D
Alarm Outputs
Via External Alarm Module Three relay outputs, Form C contacts,
User to Drive External Relays
LCD Display
Display LCD is a 10.4 in SVGA, color TFT
The NGC-UIT2-HAZ is an electronic unit. During installation, take the following precautions to avoid damage to its electronic components.
indoors or outdoors (Type 4X, IP66)
space heater –22°F to 140°F (–30°C to 60°C) with space heater
(341 mm W X 276 mm H X 92 mm D)
switching module up to 250 Vac/5 A Relays may be assigned for alarm
outputs
transflective device with integral LED backlight
• Handle with care to avoid mechanical damage.
• Keep electronics dry.
• Avoid exposure to static electricity.
• Avoid contamination with metal filings, liquids, or other foreign matter.
Network Connection Local/Remote Port RS-232/RS-485 (via external converter)
Local RS-232 A non-isolated, 9 pin D sub male Remote RS-232 to RS-485
using external converter #2 Data Rate 9600 to 57600 baud Maximum cable length For RS-485 not to exceed 4000 ft
Field Port RS-232/RS-485 (via external converter)
Field RS-232 to RS-485 using external converter #1
Data Rate 9600 Maximum Cable Length For RS-485 not to exceed 4000 ft
LAN 10/100 Base-T Ethernet port with Link
ports may be used to communicate with host computer (RAYCHEM Supervisor software) or DCS
2 wire isolated,, Using a standard 9 pin D sub female to 9 pin D sub male cable.
(1200 m). Cable to be shielded twisted pair.
port used to communicate with external devices, such as NGC-30-CRM, CRMs and RMM2.
2 wire isolated,, Using a standard 9 pin D sub female to 9 pin D sub male cable.
(1200 m). Cable to be shielded twisted pair.
and Activity Status LEDs
• Take care to protect the user interface board on the enclosure door.
• Use agency-approved conduit bushings, adapters, and cable glands to keep the enclosure protected from dust and fluids.
KIT CONTENTS
Qty Description Manufacturer Part Number
1 NGC-UIT2-HAZ TTC 10332-022
1 Din 35 Rail 15 inches any
2 Ilinx RS-232 to RS-485
converters
1
ADAM 4069 relay module
TTC 10332-023
TTC 10332-024
Qty Description Manufacturer Part Number
2 Grounding terminal Phoenix 3044128
4 Terminal blocks Phoenix 3044102
2 Serial comm cables M-F L-Com CSMN9MF-2.5
1 UIT2-HAZ SS window kit TTC T1200033
2 Two position jumpers Phoenix 3030336
1
Removing the Existing NGC-UIT-OUT
WARNING: Power to the Electrical panel that is
housing the NGC-UIT-OUT must be turned OFF before proceeding.
• Disconnect the cables from the NGC-UIT-OUT by loosening the retaining screws that secure the Phoenix connectors to the mating terminals on the NGC-UIT-OUT. This includes the serial communications (RS-485), Relay outputs and AC Input.
NGC-UIT display
Inside of panel door
2
Removing the Existing NGC-UIT-OUT
• Loosen and remove all 10 nuts and remove the NGC-UIT-OUT from the panel door.
11/32 Nut Driver
3
Removing the Existing NGC-UIT-OUT
• Disconnect the wires from the Phoenix connectors. Undo all the cable ties for the wiring bundle to the NGC-UIT-OUT. These wires will be used for the NGC-UIT2-HAZ once it is installed.
2 | nVent.com
Cable ties
4
Enlarging the NGC-UIT Opening
Use the foldout template as a guide for enlarging the cutout.
Template is actual size (see attached at back of booklet)
Instructions
• Line up the upper edge of the template with the existing cutout. Use masking tape to secure the template to the panel door. The dashed lines indicate the areas that must be removed. To minimize the amount of cutting, it may be desired to align the area to be removed with the upper left corner of the existing cutout (as pictured)
• Using a center punch, mark the 12 mounting holes. M1 – M12
• Remove the template after making the center punch marks.
• Using a straight edge and marking pen draw a line starting from the upper left hand corner of the existing cutout to the center of H1 to H2 and H3.
• Use a #7 (.201) drill bit, drill all 12 mounting holes. M1 – M12
• Using the Zipcut disc or equivalent, start the cut from the bottom left corner of the existing cutout and follow the marked line to the center of H1. Continue the cut to H2 and H3. End the cut at the upper right hand corner of the existing cutout.
• Deburr all cut edges before installing the new NGC-UIT2-HAZ.
• Do not install NGC-UIT2-HAZ until the holes for the UIT2-HAZ Window Kit have been drilled.
Inside of panel door
HAZ cutout pattern
Masking tape
Upper left
hand corner
M2
M3
M1 M12 M11 M10
H3
Original Panel
Cutout Area
9.25 in.
Drawing
UIT2 Panel
Cutout Area
11.75 in.
H1 H2
Not to Scale
M9
M8
M4 M5 M6 M7
nVent.com | 3
Drilling the Hole Pattern for the UIT2-HAZ Window Kit
5
• Refer to the drawing shown below for the hole pattern for the UIT2-HAZ Window Kit.
• Start by referencing the first hole of the window kit as shown in the drawing below. (X=1.225 in. and Y=1.225 in.). Use the Reference point shown in the drawing below as your starting point.
• Use masking tape to outline the mounting holes for the window kit.
• Measure each hole location from the first hole in the upper left hand corner and continue around the perimeter until all twelve holes are marked.
• Using a center punch mark all 12 holes.
• Drill all 12 holes using a #7 (.201) drill bit.
• Remove the masking tape.
NGC-UIT2-HAZ cutout
Masking tape
5.06 in.
1.225 in.
1.225 in.
4.21 in.
8.41 in.
12.62 in.
6
Installing the NGC-UIT2-HAZ
• Insert the NGC-UIT2-HAZ into the panel door opening. Verify that the gasket that came with the NGC-UIT2-HAZ is properly installed. Secure the NGC-UIT2-HAZ using the twelve 10-32 nuts and hardware.
• After the display is properly positioned, tighten the nuts to
0.9 newton-meters (8 inch-pounds) of torque using a 3/8 inch wrench. Tighten Kep nuts in the sequence shown for proper sealing.
Reference point
10.11 in.
15.18 in.
Cutout
1
5
9
11
3
8
4 | nVent.com
7
6
Not to Scale
4
12
10
2
7
Installing the UIT2-HAZ Window Kit
• Insert the UIT2-HAZ Window Kit onto the panel door. Verify that the gasket that came with the UIT2-HAZ Window Kit is properly installed. Secure the UIT2-HAZ Window Kit using the twelve 10-32 nuts and hardware.
Neoprene gasket
• After the UIT2-HAZ Window Kit is properly positioned, tighten the nuts to 0.9 newton-meters (8 inch-pounds) of torque using a 3/8 inch wrench. Tighten Kep nuts in the sequence shown for the NGC-UIT2-HAZ.
UIT2-HAZ Window Kit
Panel door
8
Installing the DIN Rail Components
• If there is DIN rail space available, mount the components shown on the available space.
• If there is no DIN rail space available, use the DIN rail that comes with the kit to mount the components shown.
1/4-20 x 1/2 in. studs
RL4NO
RL3NO
RL4COM
RL2N0
RL2NC
RL1NC
RL3COM
RL2COM
ADAM 4069
Relay Output
Module
8 Outputs
Two position jumpers
RL0NC
RL1NO
RL0NO
RL1COM
RL0COM
A B C D E
RD
TD Power
A B C D E
RD
TD Power
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NCNCINT+
(Y) D ATA +
(G) DATA –
(R) +Vs
(B) GND 10
nVent.com | 5
Connect Power
9
• Connect an AC power cord (120–240 V) to the NGC-UIT2­HAZ AC input.
NGC-UIT2-HAZ mounted on panel door
120 – 240 Vac
Back of NGC-UIT-OUT
• The Adam 4069 Relay module and the two RS-232 – RS-485 converters require +12 Vdc to operate. These devices can be powered by the same power supply used to power the CRM(s) boards.
RS-485 PORTS
FIELD REMOTE
SIG+
SIG–
WH
SIG–
SHLD
S
WH
BK
FAIL SAFE RELAY OUTPUTS AC INPUT
RELAY 1 RELAY 2 RELAY 3
N/L2
SIG+
SHLD
S
BK
1 2 3 4 8
5 6 7 9 10 111 2 3 4 5 6
Line/L1
1 2 3
Connect to + 12 Vdc power supply used to power the CRM(S) boards
RL2NC
RL4NO
RL3NO
RL4COM
RL3COM
ADAM 4069
Relay Output
Module
8 Outputs
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL2COM
RL7COM
RL2N0
RL7NCNCINT+
Power Supply
Connections
RL1NC
RL0NC
RL1NO
RL0NO
RL1COM
RL0COM
(Y) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
+ –
A B C D E
Field
Port
RD
TD Power
+ –
RD
A B C D
E
TD Power
Remote
Port
6 | nVent.com
10
Connecting the Alarm Relays
• The illustration below shows the wiring for the alarm relays from NGC-UIT-HAZ (dashed lines) to NGC-UIT2­HAZ. TB-X’s are the field terminals. Refer to the panel wiring for location of the field terminals.
NGC-UIT2-HAZ mounted on panel door
Back of NGC-UIT-OUT
RS-485 PORTS
FIELD REMOTE
SIG+
SIG–
WH
SIG–
SHLD
S
WH
BK
SIG+
SHLD
S
BK
RL4NO
RL4COM
RL5NO
RL5COM
FAIL SAFE RELAY OUTPUTS AC INPUT
RELAY 1 RELAY 2 RELAY 3
1 2 3 4 8
RL2N0
RL2NC
RL1NC
RL3COM
RL2COM
Module
8 Outputs
RL6COM
RL7NO
RL7COM
RL7NCNCINT+
RL1COM
RL0NC
RL1NO
RL0COM
(Y) DATA +
(G) DATA –
(R) +Vs
RL3NO
ADAM 4069
Relay Output
RL6NO
RL0NO
(B) GND 10
5 6 7 9 10 111 2 3 4 5 6
A = Gnd B = Data + C = Data –
RD
A B C D E
TD Power
Field
Port
RD
A B C D E
TD Power
Remote
Port
N/L2
Line/L1
1 2 3
AR
Fuse
TB-X
Refer to panel drawings
TB-X TB-X
for location of Terminal Block (TB) for landing relay
TB-X TB-X
wires from ADAM Module
TB-X
To Alarm Lamp/Switch
N
Mounted on Panel Door
Line
nVent.com | 7
11
Communications
• The illustration below shows the wiring for RS-485 ports from NGC-UIT-HAZ (dashed lines) to NGC-UIT2-HAZ. Refer to the panel wiring for location of the field terminals.
NGC-UIT2-HAZ mounted on panel door
• Connect the RS-232 serial cables to the appropriate comm port on the NGC-UIT2-HAZ as shown in the illustration.
Back of NGC-UIT-OUT
RL2N0
RL2NC
RL1NC
RL4NO
RL3NO
RL4COM
RL3COM
RL2COM
ADAM 4069
Relay Output
Module
8 Outputs
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NCNCINT+
RS-485 PORTS
FIELD REMOTE
SIG+
SIG–
SIG–
SHLD
S
WH
WH
BK
Wh Bk G Wh Bk G
3 2 1
A = Gnd B = Data +
RL0NC
RL1NO
RL0NO
RL1COM
RL0COM
C = Data –
(Y) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
RD
A B C D E
TD Power
Field Port
RD
A B C D E
TD Power
Remote
Port
3 2 1
CRM(S)
To other CRM(S) RMM2 PLI
FAIL SAFE RELAY OUTPUTS AC INPUT
RELAY 1 RELAY 2 RELAY 3
SIG+
SHLD
1 2 3 4 8
S
BK
5 6 7 9 10 111 2 3 4 5 6
3 2 1
Remote
N/L2
Line/L1
1 2 3
8 | nVent.com
Not to Scale
NGC-UIT2-HAZ Cut Out Dimensions
12.7 mm (0.5 in)
107.7 mm (4.24 in)
Ø 5.08 mm (0.2 in) X12
179.58 mm
(7.07)
77.98 mm
(3.07 in)
12.7 mm
(0.5 in)
310.64 mm
215.65 mm (8.49)
(12.73 in)
243.54 mm (11.73 in)
Top of Display
mm
(10.17 in)
Panel Cut Out Area
(9.17 in)
232.92 mm
Drawing
nVent.com | 9
North America
Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nvent.com
Europe, Middle East, Africa
Tel +32.16.213.511 Fax +32.16.213.604 thermal.info@nvent.com
Asia Pacific
Tel +86.21.2412.1688 Fax +86.21.5426.3167 cn.thermal.info@nvent.com
Latin America
Tel +1.713.868.4800 Fax +1.713.868.2333 thermal.info@nvent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specications without notice.
Raychem-IM-H58812-NGCUIT1OUTtoUIT2HAZ-EN-1805