nvent Raychem NGC-40-BRIDGE Installation Instructions Manual

Page 1
WARNING:
NGC-40-BRIDGE
Control and Monitoring Modules for use with the nVent Raychem NGC-40 System Installation Instructions
DESCRIPTION
A
B
The nVent RAYCHEM NGC-40-BRIDGE module provides
C
D
APPROVALS
Hazardous Locations
3128486
Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx nC IIC T4 IP20 Ex nL IIC T4 X
–40˚C ≤ Ta ≤ +65˚C
Certified to:
CAN/CSA STD. C22.2 No. 213-M1987 (R2004) CAN/CSA STD. C22.2 No. 61010-1:2004 EN 61010-1 (2001) CAN/CSA STD. E60079-15:02 (R2006)
Shown not to scale
(Russia, Kazakhstan, Belarus) For other countries contact your local nVent representative.
Conforms to:
FM Class Number 3600 (11/98) FM Class Number 3611 (10/99) ANSI/UL STD. 60079-15-2009 UL STD. 61010-1
TOOLS REQUIRED
• Small flat-blade screwdriver
ADDITIONAL MATERIALS REQUIRED
• Power supply 24 Vdc @150 mA per NGC-40-BRIDGE
• Custom built CAN cables with RJ-45 connections
KIT CONTENTS
Item Qty Description
A 1 NGC-40-BRIDGE module B 2 CAN bus termination block PTM# 10392-043 C 2 RS-485 termination resistors 120 Ω – 1% - 1/4 watt D 1 NGC-40-BRIDGE serial cable TTC# 10332-005
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Fortechnical support, call nVent at (800) 545-6258.
Page 2
GENERAL
Supply voltage 24 Vdc ± 10% Internal power consumption < 3.6 W per NGC-40-BRIDGE Ambient operating temperature –40ºC to 65ºC (–40ºF to 149ºF) Ambient storage temperature –40ºC to 75ºC (–40ºF to 167ºF) Environment PD2, CAT III Max. altitude 2,000 m (6,562 ft) Humidity 5 – 90% noncondensing Mounting Din Rail – 35 mm
ELECTROMAGNETIC COMPATIBILITY
Emissions EN 61000-6-3Emission standard for residential, commercial and light industrial environments Immunity EN 61000-6-2Immunity standard for industrial environments
COMMUNICATIONS COM1, COM2
Type 2-wire RS-485 Cable One shielded twisted pair Length 1,200 m (4,000 ft) maximum Quantity Up to 255 devices per port Data rate 9600, 19.2K, 38.4K, 57.6K, 115.2K baud Data bits 7 or 8 Parity None, even, odd Stop bits 0, 1, 2 Tx delay 0 – 5 sec. Protocol Modbus RTU or ASCII Connection terminals Wago cage clamp terminals
COMMUNICATIONS COM3
Type RS-232 Cable Custom TTC# 10332-005 Length 15 m (50 ft) maximum Data rate 9600, 19.2K, 38.4K, 57.6K, 115.2K baud Data bits 7 or 8 Parity None, even, odd Stop bits 0, 1, 2 Tx delay 0 – 5 sec. Protocol Modbus RTU or ASCII Connection terminals RJ-11
CAN NETWORKING PORT
Type 2-wire isolated CAN-based peer-peer network. Isolated to 300 V. Connection Two 8-pin RJ-45 connectors (both may be used for Input or Output connections) Protocol Proprietary NGC-40 Topology Daisy chain Length 10 m (33 ft) maximum Quantity Up to 80 CAN nodes per network segment Address Unique, factory assigned
ETHERNET
Type 10/100 BaseT Ethernet network Length 100 m (328 ft) Data rates 10 or 100 MB/s Protocol Modbus/TCP Connection terminals Shielded 8-pin RJ-45 connector on front of module
PROGRAMMING AND SETTING
LED indicators Alarm conditions RESET, Configuration lost, CAN communications fail Configuration switch SET/RUN slide switch on front of module
CONNECTION TERMINALS
Wiring terminals Cage clamp, 0.5 to 2.5 mm² (24 to 12 AWG) CAN networking and module power Two RJ-45s, one each IN and OUT. Provides CAN bus signals and +24 Vdc power.
HOUSING
Size 45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep
2 | nVent.com
Page 3
System Components
45.1 mm (1.78 in) 45.1 mm (1.78 in)
45.1 mm (1.78 in)
NGC-40 BRIDGE MODULE
Front Top Bottom Back
RESET
87 mm (3.43 in)
A. Wiring Terminals
Terminals Function
1 COM 1 (485) + in 2 COM 1 (485) + out 3 COM 2 (485) + in 4 COM 2 (485) + out 5 COM 1 (485) – in 6 COM 1 (485) – out 7 COM 2 (485) – in 8 COM 2 (485) – out 9 – 12 Not used
B. Status LEDs
Status: Indicates status of the module
Off No power Green OK/Normal Yellow (flashing) Configuration mode Red (flashing) Internal fault
Network: Indicates CAN network activity
Off No link detected Green Link OK, receive data packets Yellow Transmit data packets Red (flashing) Network error
COM: Indicates COM1 & 2 (RS-485) activity
Off No activity Green (flashing) Receipt of data packet Yellow (flashing) Transmit of data packet
45.1 mm (1.78 in)
106.4 mm (4.2 in)
87 mm (3.43 in)
C. Communication Slide Switch
D. RS-232 Port
Status: Indicates status of RS-232 port
Top LED
Off No activity Green (flashing) Receipt of data packet
Bottom LED
Off No activity Yellow (flashing) Transmit of data packet
E. Ethernet Port
Status: Indicates status of the LAN
Top LED
Off No LAN detected Green ON, LAN detected
Bottom LED
Off No LAN activity Yellow (flashing) LAN activity (data packet)
F. CAN Bus/Module Power
G. Reset Button
nVent.com | 3
Page 4
Mounting the NGC-40-BRIDGE
Each NGC-40-BRIDGE mounts on a DIN 35 rail. MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up
and inwards to engage the clip.
2
1
RS-485 Connection Diagrams – North American Installation Technique
COM 1&2 Connections (In)
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground.
RESET
NGC-40 BRIDGE MODULE
COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown.
REMOVAL: Push the module upwards to disengage the clip, then rotate the module toward you.
2
1
RESET
NGC-40 BRIDGE MODULE
COM 1 InCOM 1 In
11 55 99
++ ––
Field
Field
terminal
terminal
block
block
++ –– ++ ––
To upstream
To upstream
device
device
COM 2 InCOM 2 In
33 77 1111
++ ––
To upstream
To upstream
device
device
Field
Field
terminal
terminal
block
block
COM 1 OutCOM 1 Out
1010
66
22
++ ––
120 ohm
120 ohm
termination
termination
resistor
resistor
COM 2 OutCOM 2 Out
44 88 1212
++ ––
120 ohm
120 ohm
termination
termination
resistor
resistor
4 | nVent.com
Page 5
RS-485 Connection Diagrams – European Installation Technique
COM 1&2 Connections (In)
COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. TheCom cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar.
Earth grounding
Earth grounding bar located at the
bar located at the bridge module
bridge module
Field
Field terminal
terminal block
block
Earth grounding
Earth grounding bar located at the
bar located at the bridge module
bridge module
NGC-40 BRIDGE MODULE
RESET
COM 1 InCOM 1 In
11 55 99
++ ––
++ ––
To upstream
To upstream
device
device
COM 2 InCOM 2 In
33 77 1111
++ ––
++ ––
To upstream
To upstream
device
device
Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar.
NGC-40 BRIDGE MODULE
RESET
COM 1 OutCOM 1 Out
22
++ ––
120 ohm
120 ohm
termination
termination
resistor
resistor
COM 2 OutCOM 2 Out
44 88 1212
++ ––
120 ohm
120 ohm
termination
termination
resistor
resistor
1010
66
Earth grounding
Earth grounding bar located at the
bar located at the bridge module
bridge module
Field
Field terminal
terminal block
block
Earth grounding
Earth grounding bar located at the
bar located at the bridge module
bridge module
Local RS-232 (COM 3) & Ethernet Switch Setting RS-232
User Interface – Configuration Switch A slide switch is provided on the front of the module to allow
the user to set the bridge into a known state for configuration of the communication ports, as shown in the following table:
NGC-40 BRIDGE MODULE
RESET
RS-232RS-232
Local RS-232
Local RS-232
to Laptop
to Laptop
EthernetEthernet
To upstream
To upstream
device
device
Bridge Module Settings
Modbus address 1
Local RS-232
Protocol RTU
Data rate 9600 baud
Data bits 8
Stop bits 2
Parity No parity
Switch Position
SET Configuration mode
RUN Normal operating mode
Settings based on the user configuration parameters
nVent.com | 5
Page 6
RMM2 Connection – Optional
When using the field mounted RMM2 for RTD input, it must be connected to the COM 2 In as shown below.
PanelPanel
To next
To next RMM2
RMM2
NGC-40 BRIDGE MODULE
RESET
COM 2 InCOM 2 In
33 77 1111
++ ––
++ ––
++ ––
~~ ~~
RS-485 Shielded
RS-485 Shielded Twisted Pair
Twisted Pair
~~ ~~
++ ––
++ ––++ ––
Earth grounding
Earth grounding bar located at the
bar located at the bridge module
bridge module
Panel Terminal BlockPanel Terminal Block
FieldField
6 | nVent.com
Page 7
++
Power/
Termination
Module
Power/
Termination
Module
Primary Supply*
24 Vdc
Primary Supply*
24 Vdc
20 Modules
per Power Supply
20 Modules
per Power Supply
Termination
Block
Termination
Block
CAN/TermCAN/Term
CAN / 24 VdcCAN / 24 Vdc
100-240 Vac In100-240 Vac In
Optional redundant supplyOptional redundant supply
100-240 Vac In100-240 Vac In
++
NGC-40 CAN Bus Connections for Up to 10 Modules
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
Termination
Termination
Block
Block
ININ OUTOUT
CAN / 24 Vdc
Bridge
Module
80 Modules
per Bridge
Redundant Supply*
Redundant Supply*
24 Vdc
24 Vdc
20 Modules
20 Modules
per Power Supply
per Power Supply
Module 1
* Power supply shall have a means for disconnect from line voltage* Power supply shall have a means for disconnect from line voltage
NGC-40 CAN Bus Connections for Up to 20 Modules
Termination
100-240 Vac In100-240 Vac In
Primary Supply*
Primary Supply*
24 Vdc
24 Vdc
20 Modules
20 Modules
per Power Supply
per Power Supply
Termination
Block
Block
CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc
Power/
Power/
Termination
Termination
Module
Module
++
––
CAN / 24 Vdc
100-240 Vac In100-240 Vac In
Redundant Supply*
Redundant Supply*
24 Vdc
24 Vdc
20 Modules
20 Modules
per Power Supply
per Power Supply
Optional redundant supplyOptional redundant supply
CAN / 24 Vdc
++
––
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
Bridge
Module
80 Modules
per Bridge
Module 1
CAN / 24 Vdc CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 2
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 2
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 3
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 3
CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 4
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 4
CAN / 24 Vdc CAN / 24 Vdc
ININ OUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 10
ININ OUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 10
Termination
Termination
Block
Block
Power/
Power/
Termination
Termination
Module
Module
* Power supply shall have a means for disconnect from line voltage* Power supply shall have a means for disconnect from line voltage
ININ
OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 11
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 12
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 13
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 14
ININ OUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 20
nVent.com | 7
Page 8
CAN Bus Termination Block
A termination block (included) is required at each end of the CAN/24 Vdc bus. See NGC-40 CAN bus connection wiring diagram for more details.
Termination block
CAN / TERM CAN / 24 VDC
Termination block
CAN / TERM CAN / 24 VDC
PTM
PTM
Provide Suitable Panel Enclosure and Determine Locations for NGC-40-BRIDGE Assembly in Panel*
1. Provide suitable panel enclosure
The NGC-40-BRIDGE must be mounted in an enclosure
door
to protect its electronic components. For indoor applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X enclosure depending on the requirements.
Note: The RAYCHEM NGC-40-BRIDGE is designed for
operation in ambient temperatures from –40°C to 65°C (–40°F to 149°F ). If the ambient temperature is outside
Alarm light
this range, a space heater and/or cooling fan will be required in the panel.
2. Determine locations for the NGC-40-BRIDGE assembly in the electrical panel.
The NGC-40-BRIDGE should be located in the rear of the
panel. The NGC-40-BRIDGE assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration.
*North American panel installation techniques
HTC/HTC3/IO
PS1
CBM
PTM1
PS2
HTC1
HTC2
HTC3
PTM2
C1C2C3C4C5C6C7
PS3
PTM3
HTC12
HTC11
HTC13
C4
C11
C12
C113
PS4
PTM4
HTC22
HTC21
HTC23
C24
C21
C23
C22
HTC/HTC3/IO
PanelPanel
I/O1
I/O3
I/O2
I/O4
I/O5
HTC8
HTC9
HTC5
HTC6
HTC4
HTC7
C8
C9
C10
HTC18
HTC19
HTC15
HTC16
HTC14
HTC17
C5
C17
C18
C16
C19
C20
HTC28
HTC29
HTC25
HTC26
HTC24
HTC27
C27
C28
C25
C26
C29
C30
TB
HTC10
HTC20
HTC30
8 | nVent.com
Page 9
++
20 Modules
per Power Supply
20 Modules
per Power Supply
100-240 Vac In100-240 Vac In
20 Modules
per Power Supply
20 Modules
per Power Supply
100-240 Vac In100-240 Vac In
Optional redundant supplyOptional redundant supply
++
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
NGC-40 CAN Bus Connections for Up to 40 Modules
Termination
100-240 Vac In100-240 Vac In
Primary Supply*
Primary Supply*
24 Vdc
24 Vdc
20 Modules
20 Modules
per Power Supply
per Power Supply
Termination
Block
Block
CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc
Power/
Power/
Termination
Termination
Modules
Modules
++
––
CAN / 24 Vdc
100-240 Vac In100-240 Vac In
Redundant Supply*
Redundant Supply*
24 Vdc
24 Vdc
20 Modules
20 Modules
per Power Supply
per Power Supply
Optional redundant supplyOptional redundant supply
CAN / 24 Vdc
CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc
Power/
Power/
Termination
Termination
Module
Module
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
Bridge
Module
80 Modules
per Bridge
Module 1
++
––
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
Bridge
Module
80 Modules
per Bridge
Module 11
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 2
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 12
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 3
CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 13
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 4
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 14
ININ OUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 10
ININ OUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 20
Primary Supply*
Primary Supply*
24 Vdc
24 Vdc
* Power supply shall have a means for disconnect from line voltage
CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc
Power/
Power/
Termination
Termination
Board
Board
Redundant Supply*
Redundant Supply*
CAN/TermCAN/TermCAN / 24 VdcCAN / 24 Vdc
Termination
Termination
24 Vdc
24 Vdc
Power/
Power/
Module
Module
CAN / 24 Vdc CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
CAN / 24 Vdc
Module 21
ININ OUTOUT
HTC/HTC3
or
I/O
Module 22
CAN / 24 Vdc CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
CAN / 24 Vdc
Module 23
CAN / 24 Vdc
CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 31
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 32
ININ OUTOUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 33
CAN / 24 Vdc
ININ OUTOUT
HTC/HTC3)
or
I/O
Module 24
ININ OUTOUT
HTC/HTC3
or
I/O
Module 34
ININ OUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 30
Termination
Termination
Block
Block
ININ OUT
CAN / 24 Vdc
HTC/HTC3
or
I/O
Module 40
nVent.com | 9
Page 10
North America
Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nvent.com
©2018 nVent. Al l nVent marks and logos a re owned or license d by nVent Service s GmbH or its affi liates. All other tr ademarks are the p roperty of the ir respective own ers. nVent reser ves the right to chang e specificat ions without noti ce.
Raychem- IM-H58089-NGC40Bridge- EN-1805