
nVent.com
Download Full EN Manual
HWAT-ECO
INSTALLATION AND OPERATION MANUAL FOR
HOT WATER TEMPERATURE MAINTENANCE
SYSTEM ELECTRONIC CONTROLLER
Raychem-IM-H57340-HWATECOcontroller-EN-1805

ii | nVent.com
Important Safeguards and Warnings
WARNING: FIRE AND SHOCK HAZARD
nVent RAYCHEM HWAT Systems must be installed correctly to ensure
proper operation and to prevent shock and fire. Read these important
warnings and carefully follow all the installation instructions.
• To minimize the danger of fire from sustained electrical arcing if the
heating cable is damaged or improperly installed, and to comply with
nVent Thermal Management requirements, agency certifications, and
national electrical codes, ground-fault equipment protection must be
used on each heating cable branch circuit. Arcing may not be stopped
by conventional circuit breakers.
• Approvals and performance are based on the use of nVent Thermal
Management parts only. Do not substitute parts or use vinyl electrical
tape.
• Bus wires will short if they contact each other. Keep bus wires
separated.
• Connection kits and heating cable ends must be kept dry before and
during installation.
• The black heating cable core is conductive and can short. They must
be properly insulated and kept dry.
• Damaged bus wires can overheat or short. Do not break bus wire
strands when preparing the cable for connection.
• Damaged heating cable can cause electrical arcing or fire. Do not use
metal attachments such as pipe straps or tie wire. Use only nVent
Thermal Management approved tapes and cable ties to secure the
cable to the pipe.
• Do not attempt to repair or energize damaged cable. Remove
damaged cable at once and replace with a new length using the
nVent RayClic-S splice kit. Replace damaged connection kits.
• Use only fire-resistant insulation which is
compatible with the application and the maximum exposure
temperature of the system to be traced.
Raychem-IM-H57340-HWATECOcontroller-EN-1805

nVent.com | iii
Table of Contents
1
General Information 1
1.1 Use of the Manual 1
1.2 Features 1
1.3 Technical Data 3
1.4 Care and Maintenance 7
1.5 HWAT Heating Cables 7
2
Installation 9
2.1 Installing the Controller 9
2.2 Wiring the Controller 13
3
Programming the Controller 26
3.1 Programming Overview 26
3.2 Initializing the Controller 27
3.3 Advanced Programming 33
4
Error/Alarms and Troubleshooting 45
5
Pre-Defined Programs 50
6
Heat-Up Cycle Graphs 52
7
Cool-Down Graph 54
Raychem-IM-H57340-HWATECOcontroller-EN-1805

iv | nVent.com
A
F
B
C
D
E
Item Qty Description
A 1 HWAT-ECO controller
B 1 Temperature sensor with 13 ft (4 m) cable
C 2 Mounting screws
D 2 Mounting washers
E 1 Aluminum tape
F 1 Manual
INSTALLATION AND OPERATION MANUAL FOR
HOT WATER TEMPERATURE MAINTENANCE
SYSTEM ELECTRONIC CONTROLLER
THERMAL MANAGEMENT SOLUTIONS
WWW.THERMAL.nVent.COM
HWAT-ECO
Figure 1: Kit contents
Raychem-IM-H57340-HWATECOcontroller-EN-1805

nVent.com | v
Power supply (green LED)
Power to heating cable (green LED)
Heat-up cycle (green LED) - increased risk of scalding
Pipe Temperature alarm (requires installed sensor) (green LED)
Alarm (red LED)
Escape, backspace; NO; or display maintain temperature setpoint
Arrow keys: to change menu selection or position the cursor
Confirm selection, new value or YES
6.5"
(165 mm)
2 ea - 1/2" conduit
entries
To water heater sensor
To HWAT-ECO network/alarm
entries
3.4"
(85 mm)
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
Figure 2: HWAT-ECO controller
Raychem-IM-H57340-HWATECOcontroller-EN-1805

vi | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805

nVent.com | 1
Raychem-IM-H57340-HWATECOcontroller-EN-1805
General Information
1
1.1 Use of the Manual
This manual covers the installation and operation of
the HWAT-ECO controller and must be used with the
following additional documents:
• HWAT System Product and Selection Design Guide
(H57538)
• HWAT System Installation and Operation Manual
(H57548)
Important: For the nVent warranty and agency
approvals to apply, the instructions included in this
manual and product packages must be followed.
1.2 Features
The Raychem HWAT-ECO controller is designed for
operation with HWAT-Y2 and HWAT-R2 self-regulating
heating cables. The HWAT-ECO controller provides
the following features:
• Flexible temperature control of hot water
temperature maintenance systems.
• Integrated function that lowers the maintain
temperature during low use hours to save energy.
• Heat-Up cycle function that increases the water
temperature in a stagnant pipe.

2 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
General Information
1
• Building Management System (BMS) interface
that receives a DC voltage to set the maintain
temperature.
• Alarm relay to signal power, temperature, or
communication problems.
• Pipe temperature monitoring, low temperature
alarm and high temperature cut-out.
• Master/slave function that allows one HWAT-ECO
to control up to eight additional HWAT-ECO
controllers.
• 9 pre-defined programs that can be customized by
the user.

nVent.com | 3
Raychem-IM-H57340-HWATECOcontroller-EN-1805
General Information
1
1.3 Technical Data
Use Only for HWAT-Y2 and
HWAT-R2 heating cables
Maintain temperature
setpoint
105˚F (40˚C) to 140˚F
(60˚C)
Hot water piping
ambient temperature
60˚F (15˚C) to 80˚F (25˚C)
Controller ambient
temperature
40˚F (5˚C) to 105˚F (40˚C)
ambient
Switching capacity 24 A 208/240 Vac max.
Operating voltage 208/240 (±10%), 60 Hz
Internal power
consumption
2.5 W
Circuit protection
(not provided with
HWAT-ECO controller)
Max. 30 A with 30 mA
ground-fault protection
Power terminal block 16–10 AWG (1.5–4 mm
2
)
Use copper conductors
only
Internal temperature
alarm
150˚F (65˚C)
BMS control voltage 0–10 Vdc
BMS cable maximum
length
328 ft (100 m)

4 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
General Information
1
Alarm contacts Max. 24 Vdc or 24 Vac,
1A, SPST, voltage free,
NO/NC
Alarm events • Loss of power
• Controller reinitialized
• Internal controller
temperature too high
• Lost date and time
settings
• Internal failure
• Pipe temperature too
high (optional)
• Pipe heater temperature
too low (optional)
• Network error
Power correction factor To increase or decrease
your actual pipe maintain
temperature or adjust for
plastic pipe.
Pipe temperature sensor Thermistor with 13 ft
(4m) lead provided.
A PT100 RTD may be
optionally used. Max
length is 328 ft (100 m)

nVent.com | 5
Raychem-IM-H57340-HWATECOcontroller-EN-1805
General Information
1
Electromagnetic Complies to EN 5014-1
Compatibility (EMC) for
emission and 60730-1 for
immunity
Real time clock Leap year correction
Clock accuracy ±10 minutes per year
Enclosure rating NEMA 12 (IP54) – indoor
use only
Enclosure material ABS
Mounting Wall mount with two
screws or optional DIN rail
Conduit entries 2 ea – 1/2 in conduit entries
Cable gland 3-hole grommet
Maximum cable size:
• 2-wire: 20 AWG (0.5 mm
2
)
• 4-wire: 24 AWG (0.2 mm2)
Default programs 9 pre-defined programs
that can be customized
by user
Program settings 48 1/2-hour time blocks
of the following program
settings: Off, Economy,
Maintain and Heat-Up
cycle

6 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
General Information
1
Password 4-digit password protection
Master/slave Master is selectable in the
controller, up to 8 slaves
can be connected
Master/slave cable 2-wire, min. 24 AWG
(0.2 mm
2
) twisted pair
and insulation of 300 V,
Max length cable is 100 m
Parameters in memory All parameters are stored
in nonvolatile memory,
except time and date
Clock backup time Rechargable Lithium
battery. Battery will retain
time and date for up to 30
days when power is lost
Approvals
80BJ
Type 12
Energy Management Equipment
(for use with HWAT-R2 and HWAT-Y2 heating cables only.)
Weight 2 lbs (1 kg)
Size 6.5 in x 3.4 in x 2.8 in
(165 mm x 85 mm x
71 mm)

nVent.com | 7
Raychem-IM-H57340-HWATECOcontroller-EN-1805
General Information
1
1.4 Care and Maintenance
To clean the HWAT-ECO use a damp cloth. Do not
use solvents. Do not pour water directly on the
device. Do not use a water hose or high pressure
cleaner.
Important: In case of questions or product failure,
please contact your nVent representative, or call nVent
at 800-545-6258.
1.5 HWAT Heating Cables
Maintain temperature
Depending on the ambient temperature and voltage,
HWAT-Y2 is designed to maintain temperatures up to
125˚F (52˚C), and HWAT-R2 is designed to maintain
temperatures up to 140˚F (60˚C).
Installing the heating cables
Install the HWAT heating cable system as instructed
in the HWAT System Installation and Operation
Manual (H57548). The controller must be installed
by a professional electrical installer familiar with
electrical safety codes and practices.

8 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
General Information
1
Ground-fault protection
WARNING: To minimize the danger of fire from
sustained electrical arcing if the heating cable is
damaged or improperly installed, and to comply with
the requirements of approvals agencies, nVent and
national electrical codes, ground-fault equipment
protection must be used on each heating cable
branch circuit. Arcing may not be stopped by conventional circuit protection. The HWAT-ECO does not
include ground-fault protection.
Pre-Installation testing
Prior to installing the HWAT-ECO controller, perform
the insulation resistance (Megger) test and circuit
length verification (Capacitance) test on the heating
cable as detailed in the HWAT System Installation
and Operation Manual (H57548).

nVent.com | 9
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
2.1 Installing the Controller
Install the controller in an indoor, dry, clean,
accessible location. If using the optional pipe
temperature sensor, make sure you install the
controller within 328 ft (100 m)
of where you want to
monitor the pipe temperature.
Opening the controller
WARNING: To prevent shock, always switch off
the power supply (circuit breaker) before opening the
controller.
The HWAT-ECO has a removable front cover. Both
the cover and the box have electronic parts and are
connected to each other by a 14-pin connector. First
unscrew the four screws in the cover. Carefully pull
the cover straight out, not sideways!

10 | nVent.com
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
Figure 3: Opening the controller
Wall mounting the controller
Mount the controller using either of the options
below:
1. You can mount the controller to the wall using
the two supplied screws and sealing rings in the
two holes located inside the bottom part of the
controller.

nVent.com | 11
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
5.9" (148 mm)
1.7"
(43 mm)
TEMP BMS
B A
Figure 4: Hole locations for mounting with screws

12 | nVent.com
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
2. Optionally you can mount the controller using DIN
35 Rail mounting.
Optional Din Rail Mount
(Rail not provided)
Mounting
Removing
Press tab to remove box
Figure 5: Mounting with DIN 35 Rail

nVent.com | 13
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
2.2 Wiring the Controller
The diagram below shows the arrangement of the
terminal blocks for power, alarm, pipe temperature
sensor, BMS and network.
Ground
HWAT-ECO
General Arrangement
Power
terminal block
Sensor, BMS,
and network
terminal block
Alarm
terminal block
Ø
1Ø2
HWAT Line
Ø
1Ø2
TEMP BMS
B A
Figure 6: General arrangement for terminal blocks

14 | nVent.com
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
The diagram below shows the connection of a single
controller (without optional water heater sensor,
BMS, network and alarm connections).
Important: Tighten the terminal screws to 6 inch-
lbs. (0.68 N-m)
Ø
Ø
G
1/2"
Conduits
HWAT
heating
cable
RayClic-PC
Max. 30 A
ground fault
circuit breaker
208-240 Vac
Ground
Incoming power
208/240 Vac Max
Wiring diagram
for HWAT-ECO
To
HWAT
heating
cable
TEMP BMS
B A
Figure 7: Connecting a single controller
(w/o sensor, BMS, network and alarm connections)

nVent.com | 15
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
For controlling multiple HWAT circuits with the same
programming parameters (i.e. voltage, maintain
temperature, ambient temperature, economy
temperature), connect the heating cable output
relay to an external contactor coil(s).
N
ø
1
HWAT-ECO internal switch
ø3ø
2
HWAT heating cable
HWAT heating cable
Braid/pipe
Two-pole with 30-mA ground-fault trip (208/240 Vac)
Two-pole with 30-mA ground-fault trip (208/240 Vac)
Three-pole
main CB
HWAT-ECO
internal
relay
Power connection
Panel energized light
*Contactor coil
(208 or 240 V)
Heating cable
End seal
Three-pole
main contactor
Ground
Line voltage
208 V or 240 V
Install contactor
manufacturer’s recommended
snubber circuit across the coil
*
Figure 8: Multiple HWAT circuits connection
Pipe temperature sensor (optional usage)
Installation of the pipe temperature sensor is optional.
If installed, the HWAT-ECO provides low temperature
alarm and high temperature cut-out.
The temperature sensor should be connected to a
single or master controller only. Connect both wires

16 | nVent.com
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
of the temperature sensor to the TEMP terminal in
the controller (PL4). The sensor wires do not have a
special polarity. To connect a wire, use a screwdriver
to push down the orange tab on the side of the
terminal. Put the wire into the hole and release the
orange tab.
PL4PL3
PL5
Standard temperature sensor
PT100 sensor (2 wire)
short
for
PT100
TEMP BMS
B A
PL4PL3
PL5
TEMP BMS
B A
Alarm,
Sensor,
and BMS
terminals
PL6
Alarm contact
TEMP BMS
B A
Figure 9: TEMP terminal location and sensor wiring
Optionally, PT100 RTDs from the water heater can
be used. To install a PT100 sensor first connect a
jumper between the terminals indicated in Figure 9,
then connect the two wires from the RTD. If you are
using a three wire sensor, remove the compensation
lead and only connect the two measurement wires.

nVent.com | 17
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
The pipe temperature sensor must be placed on
1-inch diameter pipes or larger, installed opposite
from the HWAT heating cable to accurately measure
the pipe temperature.
The temperature sensor cable is 13 ft 3 in (4 m) in
length, however the user can extend the cable up to
328 ft (100 m) by splicing a length of 300 volt, 18 AWG
(0.75mm
2
) cable.
Cold water in
mixing
valve
Tempered water out
Hot water out
Hot water in
HWAT-Y2
HWAT-R2
Water
heater
A
B
Temperature
sensor
Insulation
180°
Heating
cable
Figure 10: Positioning temperature sensor (optional)

18 | nVent.com
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
Alarm wiring (optional)
The alarm contact (24 Vac, 24 Vdc, 1A) inside the
controller can be used to switch an external device.
The contact is closed during operation and open during
an alarm or during loss of power. In a network, all alarm
contacts should be connected in series.
Alarm,
Sensor,
and BMS
terminals
PL6
Alarm contact
TEMP BMS
B A
NC O NO
Figure 11: Connecting the alarm contact
The alarm terminal (PL6) is located in the upper
right corner of the controller and has the text
“alarm contact” next to it. To connect a wire, use a
screwdriver to push down the orange tab on the side
of the terminal. Put the wire into the hole and release
the orange tab. The wires used for the alarm contact
should be rated for 300 V. See “Chapter 4, Error/

nVent.com | 19
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
Alarms and Troubleshooting” for more information
about alarm conditions.
The alarm contact is designed as a fail safe
mode and can be wired for normally open (NO) or
normally closed (NC) operation. The following table
summarizes the relay positions in the different
controller states:
Position NC NO
Power Off Open Closed
Power On Closed Open
Alarm Mode Open Closed
Network
The Master/slave function allows one HWAT-ECO to
control up to eight additional HWAT-ECO controllers.
Connect all HWAT-ECO controllers to each other in
parallel using the A and B inputs on terminal (PL3).
This means that several controllers will have two
wires in one hole. The wire should be a twisted pair
and be rated for 300 V. The total maximum length of
this cable between all controllers is 328 ft (100m).
Be careful not to mix A and B connections. To
connect a wire, use a screwdriver to push down the
orange tab on the side of the terminal. Put the wire
into the hole and release the orange tab.

20 | nVent.com
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
MASTER
TEMP BMS
B A
TEMP BMS
B A
SLAVE 1
OPTIONAL BMS
Figure 12: Networking controllers together
The diagram below shows the connection of multiple
controllers (with optional RS-485 connections).

nVent.com | 21
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
HWAT
heating
cable
L
L
208/240V
HWAT
heating
cable
Master Slave 1 Slave 2
RS-485 RS-485
Sensor
BMS
Alarm
L
L
208/240V
L
L
208/240V
HWAT
heating
cable
Figure 13: Connecting multiple controllers (with
RS-485)
When multiple controllers
are networked and you are
using BMS and Alarm
functions, you must use a
4-wire conductor.
max. 20 AWG
(0.5 mm
2
)
max. 24 AWG
(0.2 mm2)
Figure 14: Combine alarm and BMS wire in 4-wire
cable
Important: For master/slave combination with
alarm function, the alarms are connected in series by a
RS485 wire. Since the cable gland grommet has only
3holes, you must combine the alarm wire and the BMS
wire in a 4-wire cable.

22 | nVent.com
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
Building Management System (BMS) (optional)
See Table 5 on page 39.
The BMS input of the HWAT-ECO is a 0 to 10-Vdc
input. If the controller is programmed to have a
BMS connection, the BMS controls the temperature
setpoint. Using 300-V rated cable, connect the BMS
signal wire to terminal (PL5). Connect the ground
wire to the “–” and the 0-10 V output to the “+”
terminal.
Alarm,
Sensor,
and BMS
terminals
0-10v
ground
BMS
PL3 PL5PL4
PL6
Alarm contact
TEMP BMS
B A
Figure 15: Connecting the BMS

nVent.com | 23
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
Figure 16 shows the connection of a single controller
(with optional sensor, BMS and alarm connections).
Master
H WAT
heating
cable
Sensor
BMS
Alarm
L
L
208/240V
RayClic-PC
Figure 16: Single controller connection
(with sensor, BMS, and alarm connections)

24 | nVent.com
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
Closing the controller
Position the cover in front of the wall-mounted box.
The separation sheet inside the controller will help
guide the cover and the connector. Push the cover
onto the box. Note that the connector pins will offer
some resistance. Put the screws in place and tighten
to 10 inch-lbs (1.13 N-m).
Figure 17: Closing the controller

nVent.com | 25
Installation
Raychem-IM-H57340-HWATECOcontroller-EN-1805
2
Power supply (green LED)
Power to heating cable (green LED)
Heat-up cycle (green LED) - increased risk of scalding
Pipe temperature alarm (requires installed sensor) (green LED)
Alarm (red LED)
Escape, backspace; NO; or display maintain temperature setpoint
Arrow keys: to change menu selection or position the cursor
Confirm selection, new value or YES
02-11-2012 09:30
Maintain *
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
Figure 18: Controller display

Programming the Controller
3
26 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
3.1 Programming Overview
Display functions
Quickstart
Any key to start
The display has two lines with 16 characters each.
The display shows the following text on start up:
The HWAT-ECO has six buttons:
Up/Down/Left/Right arrows
Escape (ESC) button
Enter button
You can program the HWAT-ECO by simply executing
the Quickstart program which is suitable for normal
operations. In addition, advanced programming can
be used to modify initial settings, set additional
features such as BMS and Network Master, reinitialize
the entire controller, or customize the pre-defined
programs.

Programming the Controller
3
nVent.com | 27
Raychem-IM-H57340-HWATECOcontroller-EN-1805
3.2 Initializing the Controller
The first time you power up the controller, you
must execute the Quickstart program to set the
initial settings. Once initialized continue to power
the controller for at least 6 hours to charge the
internal battery.
QUICKSTART MENU
Time and date Year
Month
Day
Hour
Minutes
Select Year
Select Month
Select Day
Select Hour
Select Minutes
Cable type HWAT-R2
“Press Enter for this cable type.”
HWAT-Y2
“Press Enter for this cable type.”
Voltage select 208 Vac
“Press Enter for this voltage
type.”
240 Vac
“Press Enter for this voltage
type.”
Units English
“Press Enter for this unit type.”
Metric
“Press Enter for this unit type.”
Ambient temp.
Maintain temp.
Economy temp.
“Enter ambient temp.”
“Enter maintain temp. setpoint”
“Enter economy temp. setpoint”

Programming the Controller
3
28 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
QUICKSTART MENU
Default program Constant
Apartments
Family home
Prison
Hospital
Nursing home
Hotel
Sports center
Convales. home
“Scroll to program and press
Enter.”
During the Quickstart you can press the ESC button
to go back to a previous menu. On startup the
display will show the following text:
Quickstart
Any key to start
Press a key to start, and the following menus
appear:
Time and Date
Use the up/down arrows to select the year and press
Enter. Then, select and enter the month, day, hour, and
minutes. The time and date is contained in volatile
memory, and is maintained during power outages by
an internal rechargeable battery. Power the HWAT-ECO
for at least 6 hours to charge the battery.

Programming the Controller
3
nVent.com | 29
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Cable type
Use the up/down arrows to select HWAT-Y2 or
HWAT-R2 cable used in your installation. Press Enter.
Voltage
Use the up/down arrows to select 208 V or 240 V
(applied voltage to the cable). Press Enter.
Units
Use the up/down arrows to select English or Metric
units. Press Enter.
Ambient temperature
The ambient temperature is the air temperature
surrounding the hot water piping where the heating
cable is installed. Use the up/down arrow keys to
select from 60˚F (15˚C) to 80˚F (25˚C). Press Enter.
If your design requires that the ambient temperature
is significantly different from one location to another,
you will need an HWAT-ECO controller for each
ambient condition.
Maintain temperature
The maintain temperature setpoint is the water
temperature that you set for normal use. Use the up/
down arrow keys to select the temperature.

Programming the Controller
3
30 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
The minimum temperature is 105˚F (40˚C) or the
economy temperature, whichever is higher. The
maximum temperature depends on cable type,
voltage and ambient temperature. The programmed
maintain temperature will display if you press the
ESC button once the system is in operation.
MAXIMUM MAINTAIN TEMPERATURE (208-VOLT)
Ambient temperature
HWAT-Y2 120˚F (49˚C) 125˚F (52˚C) 125˚F (52˚C)
HWAT-R2 140˚F (60˚C) 140˚F (60˚C) 140˚F (60˚C)
MAXIMUM MAINTAIN TEMPERATURE (240-VOLT)
Ambient temperature
HWAT-Y2 120˚F (49˚C) 125˚F (52˚C) 125˚F (52˚C)
HWAT-R2 140˚F (60˚C) 140˚F (60˚C) 140˚F (60˚C)
Economy temperature
The economy temperature setpoint is the water
temperature for periods during which hot water is not
usually used (at night) or when a lot of hot water is
used (peak period). Use the up/down arrows to select

Programming the Controller
3
nVent.com | 31
Raychem-IM-H57340-HWATECOcontroller-EN-1805
the temperature. The minimum temperature is 105˚F
(40˚C) and the maximum temperature is the selected
maintain temperature.
Default programs
The HWAT-ECO has 9 pre-defined programs.
(See “Chapter 5, Pre-Defined Programs” for more
information.) Use the up/down arrows to select a
pre-defined program. Press Enter. HWAT-ECO takes a
few seconds to copy the pre-defined program to the
internal memory. During this time a row of dots will
show in the display.
Pipe temperature
This function also ensures that the delivered water
temperature is not lower than the desired maintain
temperature.
Completing initialization
The controller will start automatically when you
finish selecting your Quickstart options. Additional
settings are available in the Setup menu for advanced
installations. See section 3.3 on page 33 for more
information.
Press Enter to start the controller. If you press the
ESC button, you can retrace all menu items to check
the settings. After starting the controller the display
shows date, time, temperature setting and a “*” to

Programming the Controller
3
32 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
indicate that the controller is unlocked. If you wish
to lock (password protect) the controller, see section
3.3.2.6 for instructions.
Displaying Maintain Temperature Setpoint
After finishing the Quickstart, the display will show
the date, time, temperature mode and a star to
indicate that the controller is unlocked.
02-11-2013
Maintain
09:13
While in operating mode, press ESC to view a bar
graph that shows the maintain temperature setpoint.
To enter the programming menu, press any other
key. The controller will exit the menu automatically
after five seconds of key inactivity.
Figure 19: Bar graph
Displaying Pipe Temperature
When the optional pipe temperature sensor is
connected, the controller will display date and time
as above and alternate between temperature mode
and pipe temperature.

Programming the Controller
3
nVent.com | 33
Raychem-IM-H57340-HWATECOcontroller-EN-1805
02-11-2013
Pipe T: 110°F
09:13
*
3.3 Advanced Programming
Advanced programming options are also available.
Table 4 and the remainder of this section outline the
advanced programming options that include modifying
initial settings, setting additional features such as BMS
and Network Master, reinitializing the entire controller,
or customizing the pre-defined programs.

Programming the Controller
3
34 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
ADVANCED PROGRAMMING MENU
1 Time and
Date
1 Year
2 Month
3 Day
4 Hour
Select Year
Select Month
Select Day
Select Hour
Select Minutes
2 Setup
(enter password if Lock
is ON)
1 Main Temp “Enter maintain temp. setpoint”
2 Economy Temp “Enter economy temp. setpoint”
3 Ambient Temp “Enter ambient temp.”
4 Power Correction Selectable
Lock/unlock Setup and Timer
menus
6 BMS Select Yes/No
7 Network Master Select Yes/No
8 Reinitialize Select Yes/No
9 Short heater Select Yes/No
10 LTA
(Low Temp Alarm)
1. Set Status
2. Set Temperature
3. Set Alarm Filter Time
4. Set Deadband
Select Yes/No
Enabled or Disabled
95°F (35°C) min
5-30 Minutes
4-18°F (2-10°C)
11 HTC
(High Tem. Cut Out)
1. Set Status
2. Set Temperature
3. Set Alarm Filter Time
4. Set Deadband
Enabled or Disabled
Maximum 205°F
10-30 Minutes
4-18°F (2-10°C)

Programming the Controller
3
nVent.com | 35
Raychem-IM-H57340-HWATECOcontroller-EN-1805
ADVANCED PROGRAMMING MENU
3 Timer
(enter password if Lock
is ON)
1 Default program Constant
Apartments
Family home
Prison
Hospital
Nursing home
Hotel
Sports Center
Convalesc. home
2. Edit program
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Edit timer for Monday
Edit timer for Tuesday
Edit timer for Wednesday
Edit timer for Thursday
Edit timer for Friday
Edit timer for Saturday
Edit timer for Sunday
4 Holiday On
Off
xxDays off
Show firmware version number + Cable type + Sensor temp.
Time and Date
Use the up/down arrows to select the year and press
Enter. Then select and set the month, day, hour and
minutes.

Programming the Controller
3
36 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Setup
When Lock is on (no star in the lower right corner)
enter a password to access the setup menu. The
controller locks again after 60 seconds of inactivity.
When Lock is off the following menus are directly
accessible.
1. Maintain temperature
The maintain temperature setpoint is the water
temperature that you set for normal use. Use the
up/down arrows to select the temperature. The
minimum temperature is 105˚F (40˚C) or the economy
temperature, whichever is higher. The maximum
temperature depends on cable type, pipe diameter,
insulation thickness and ambient temperature.
2. Economy temperature
The economy temperature setpoint is the water
temperature for periods during which hot water is
not usually used (at night) or when a lot of hot water
is used (peak period). Use the up/down arrows to
select the temperature. The minimum temperature
is 105˚F (40˚C) and the maximum temperature is the
selected maintain temperature. Press Enter.
3. Ambient temperature
The ambient temperature is the air temperature
surrounding the pipes where the heating cable is

Programming the Controller
3
nVent.com | 37
Raychem-IM-H57340-HWATECOcontroller-EN-1805
installed. Use the up/down arrows to select from
60˚F (15˚C) to 80˚F (25˚C). Press Enter to confirm.
If your design requires that the ambient temperature is
significantly different from one location to another, you
will need an HWAT-ECO controller for each ambient
condition.
4. Power correction
The power correction factor can be selected to
increase or decrease your actual pipe maintain
temperature or to adjust for using HWAT heating
cables on rigid plastic pipes.
The power correction factor can be adjusted from
0.6 to 1.40, increasing or decreasing the percent
time the heating cable is powered during the duty
cycle.
For installation on rigid plastic pipe set the power
factor at:
HWAT-Y2: 1.20
HWAT-R2: 1.25
Lock (password)
Use the up/down arrows to select Lock On/Off and
press Enter. If you select ‘On’, you must enter a
password using the left/right and up/down arrow
buttons to select a 4-digit password. Press Enter.
You will need to remember your 4-digit password
whenever you wish to unlock the controller for

Programming the Controller
3
38 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
reprogramming. Once you unlock and reprogram,
you will need to relock by entering your password.
If Lock is On, the Setup and Timer menus are protected
by the password. After you enter the password, the
controller remains unlocked until five minutes of key
inactivity or until you select Lock ‘On’ again.
6. Building Management System (BMS)
You can activate the Building Management System
option using this menu. When set to “Yes” the
controller responds only to the voltage applied to the
BMS terminal. For voltages ≤ 4 Vdc: heating cable
is OFF. For voltages between 4.1 Vdc and 6.4 Vdc:
maintain temperatures are set as indicated in Table
5. For voltages > 6.4 Vdc: 100% power is applied
to the heating cable. See "Building Management
System (BMS) (optional)" on page 22 for
installation information. If Water heater is ON, it
overrules the BMS temperature setting if necessary.

Programming the Controller
3
nVent.com | 39
Raychem-IM-H57340-HWATECOcontroller-EN-1805
BMS VOLTAGE INPUT
>147 (>64) X >6.4
147 (64) X 6.4
140 (60) X 6
131 (55) X X 5.5
122 (50) X X 5
113 (45) X X
4.5
106 (41) X X
4.1
Off X X
0
7. Network Master
In large installations where more than one
HWAT-ECO controllers are connected to each other,
you must select one controller as the Master. This
controller should be fully programmed and all slave
controllers will use the Master settings.
The master controller sends commands to all slave
controllers to switch them ON or OFF. The master
program is used for all controllers as follows:
Slave controllers on the same phase (max. three
controllers) will have a delayed ON and OFF. This
way the start-up current of the cable will never occur
at the same moment for these controllers (A, B and
C). Slave controllers connected to a different phase
will switch at the same time (1, 2 and 3).

Programming the Controller
3
40 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
After selecting “Master: Yes”, the slave controllers
will initialize and show:
:Slave: “x y” x= phase number (1 to 3)
y= slave identification (A, B and C)
The master controller is always 1 A, the slave
controllers will get their number and identification
automatically. Always check afterwards if all
controllers have unique id-numbers, if not, check
the RS485 cables and repeat this procedure.
8. Reinitialize
To Reinitialize all settings back to the factory
settings (except time and date), set the “Reinitialize”
menu to “Yes.”
9. Short Heater
This feature allows you to activate a low current
alarm:
Yes: Allows low current such as when used as a
demonstration, or to control a contactor. In this
mode there is no low current alarm.
No: Generates low current alarm when measured
current is less that 300 mA.
10. LTA (Low Pipe Temperature Alarm)
When the optional pipe temperature sensor option
is installed, the HWAT-ECO controller monitors the
temperature of the hot water distribution pipes

Programming the Controller
3
nVent.com | 41
Raychem-IM-H57340-HWATECOcontroller-EN-1805
where the sensor is installed and can generate a low
pipe temperature alarm.
1. Set Status: Enabled or Disabled
2. Set temperature:
– Minimum: 95°F (35°C)
– Maximum: < Maintain (or Economy)
3. Set Alarm filter time: 5–30 minutes
4. Set deadband: 4–18°F (2–10°C), 9°F
(5°C default)
11. HTC (High Temperature Cut-Out)
When the optional pipe temperature sensor option
is installed, the HWAT-ECO controller monitors the
temperature of the hot water distribution pipes
where the sensor is installed and a high temperature
cut-out can be set.
High Temperature Cut-out:
Minimum: > set point
Maximum: 205°F (96°C)
Alarm filter: 5–30 minutes (default 10)
Dead band: > 5°F (3°C) default 0°F(6°C)
Timer
The Timer feature lets you re-program any of the
pre-defined programs to suit your personnel
requirements. Reprogramming is done graphically in
½ hour time blocks. A block can be set to Heat-Up

Programming the Controller
3
42 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
cycle, Maintain temperature, Economy temperature,
or Off. See “Chapter 6, Heat-Up Cycle Graphs” for
more information.
Edit pre-defined programs
To edit a program, switch Lock to Off. If password
protected, you will need to enter the password to
unlock the controller. After you enter the password,
the controller remains unlocked until five minutes of
key inactivity or the Lock ‘On’ is selected again
Select temperature
Use the up/down arrows to select the temperature:
= Maintain temperature= Heat-up cycle
= Economy temperature = Off
Figure 20: Timer block options
Select time block
Use the left/right arrows to select the time block.
Timer programming example from 00:00 to 08:00:

Programming the Controller
3
nVent.com | 43
Raychem-IM-H57340-HWATECOcontroller-EN-1805
.......... 04:00 – 04:30: Off
00:00 – 00:30: Heat-up cycle 04:30 – 05:00: Economy
00:30 – 01:00: Heat-up cycle 05:00 – 05:30: Economy
01:00 – 01:30: Heat-up cycle 05:30 – 06:00: Economy
01:30 – 02:00: Heat-up cycle 06:00 – 06:30: Economy
02:00 – 02:30: Off 06:30 – 07:00: Maintain
02:30 – 03:00: Off 07:00 – 07:30: Maintain
03:00 – 03:30: Off 07:30 – 08:00: Maintain
03:30 – 04:00: Off ...........
Figure 21: Timer programming example
Heat-Up cycle
The HWAT-ECO can be programmed to power
HWAT-Y2 or HWAT-R2 at full power for any selected
number of hours. When hot water is not being used
and the pipes are stagnant, the HWAT-ECO can
raise the temperature of the water in the stagnant
pipes. To determine the amount of time that is
required to reach a desired temperature, refer to
“Chapter 6, Heat-Up Cycle Graphs.” You must know
the programmed maintain temperature, pipe sizes,
system voltage and the type of heating cable to
determine the amount of time that is required
to reach a desired temperature. If the desired
temperature can be reached in a timeframe that is
less than when the pipes will be flowing again, the
Heat-Up cycle can be programmed for the number of
hours that are required and the desired temperature
will be reached. To determine the amount of time

Programming the Controller
3
44 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
that is required to return back to the maintain
temperature after the Heat-Up cycle is complete
and the heating cable is off, refer to “Chapter 7,
Cool-Down Graph.”
Holiday
This menu is used to set the controller to Off,
timed-off, or to resume your timer program.
On: The controller uses the normal operation the
timer program.
Off: The controller will not power the system until
you select “Use timer”.
xx Days off: You can select a number of days. The
controller automatically returns to timer mode when
the selected number of days have passed.
Info
The display shows the firmware version number,
selected cable type and the current sensor
temperature. Press Enter twice to update the
sensor temperature on the display.

Error/Alarms and
Troubleshooting
4
nVent.com | 45
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Please ensure that the unit is correctly connected to
the power supply and the heating cable is connected
to the HWAT-ECO unit.
Error code
Definitions
Error 1: Internal temperature
alarm;
Temperature is too
high. (> 65°C)
Turn off power and allow the
controller to cool and then
re-energize. The controller
will lock out after three
occurrences. If this does not
restore the controller, replace
the HWAT-ECO.
Error 2: Pipe Sensor failure
(Only when
temperature alarm
“enabled” selected)
• Sensor or sensor
cable defect
• Low temp alarm or
High temperature
cut-out selected
and sensor is not
installed.
Connect sensor to HWAT-ECO or
turn off temperature alarm.
Check sensor connections;
replace sensor, check
temperature sensor mounting
Error 3: Network failure
Two or more
HWAT-ECO’s are set as
Master
Reinitialize MASTER
(see "Setup" on page 36)

Error/Alarms and
Troubleshooting
4
46 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Error 4: Internal Error Controller needs to be replaced.
Contact nVent representative
Error 5: No/Low current alarm Ensure that the heating circuit
is connected to power output of
the HWAT-ECO.
If controlling a contactor, ensure
that the Short Heater Alarm is
enabled.
Error 6: Configuration Error Refer to "Short Heater" menu.
• If heating cable is longer
that 15 ft. (4.5 m) then, Short
heater = No
• If heating cable is shorter
than 15 ft. (4.5 m) then, Short
heater = Yes
Error 7: Pipe temperature too
high
(Only when HTC is
enabled)
• Boiler temperature is
too high.
• Pipe temperature
too hot
• Verify High Temperature
Cut-out (HTC) is set correctly.
• Correct boiler or mixing valve
setting.
• Verify HWAT-ECO
programming.
• Verify that pipe insulation
schedule is correct.

Error/Alarms and
Troubleshooting
4
nVent.com | 47
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Error 8: Time is lost
Battery is drained due
to not being powered
for a long time.
Input time again (will be asked
by the unit when a button is
pressed)
Error 9: Pipe temperature is
too low
(Only when temperature
alarm “yes” selected)
Pipe temperature too
low
• Correct boiler/mixing valve
temperature setting
• Ensure that the sensor is tight
to pipe and insulated.
• Verify power is connected to
heating cable.
• Confirm Low Temperature
Alarm (LTA) setting
Confirm HWAT-ECO settings
Confirm insulation schedule

Error/Alarms and
Troubleshooting
4
48 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Indications/Trouble
shooting
Water temperature
too low
Too low water
temperature
• Boiler temperature is
too low
• Cold water entering
system
• Heater used is
different type than
entered in program.
• Entered value of
ambient temperature
is too high.
• Insulation thickness
is different than standard thickness.
• Check boiler
temperature and
timer program
• Mixing valves and
janitor sinks may be
allowing cold water to
cross over to the hot
water side.
• Change heater type
in HWAT-ECO (can
only be done in
quick install "Setup"
on page 36
- Reinitialize)
• Change value of
ambient temperature
• Adjust power
correction factor if
possible (see "Timer"
on page 41)
• Change insulation
to match required
schedule in HWAT
installation manual.

Error/Alarms and
Troubleshooting
4
nVent.com | 49
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Indications/Trouble
shooting
Water temperature
too high
Too high water
temperature
• Heater used is
different type than
entered in program.
• Insulation thickness
is different than standard thickness.
• Entered value of
ambient temperature
is too low
• Change heater type
in HWAT-ECO (can
only be done in
quick install "Setup"
on page 36
- Reinitialize)
• Adjust power
correction factor if
possible (see "Timer"
on page41)
• Change value of
ambient temperature
No display
Loss of power Restore power
Can’t access
programming
mode
Controller is
password-protected
Enter your 4-digit
password. If you
forgot your password,
enter the backup
password: 6922 to
unlock the controller

50 | nVent.com
5
Pre-Defined Programs
Constant
I-0
Monday-Sunday
Apartments
I-1
Monday-Friday
Saturday-Sunday
Family home
I-2
Monday-Sunday
Prison
I-3
Monday-Sunday
I-4
Monday-Sunday
I-5
Monday-Sunday
I-6
Monday-Sunday
I-7
Monday-Sunday
I-8
Monday-Sunday
00
02 04 16
00
02 04 16
00
02 04 16
00
06
12
18
24
02 04 16
14
1008
20 22
00
06
12
18
24
02 04 16
14
1008
20 22
00
06
12
18
24
02 04 16
14
1008
20 22
Heat-up
Economy
Maintain
Heat-up
Economy
Maintain
Heat-up
Economy
Maintain
00
06
12
18
24
02 04 16
14
1008
20 22
Heat-up
Economy
Maintain
00
06
12
18
24
02 04 16
14
1008
20 22
Heat-up
Off
Economy
Maintain
= Maintain temperature= Heat-up cycle
= Economy temperature = Off
= Economy temperature = Off
Heat-up
Economy
Maintain
Heat-up
Economy
Maintain
Heat-up
Economy
Maintain
00
02 04 16
Heat-up
Economy
Maintain
00
02 04 16
Heat-up
Economy
Maintain
Raychem-IM-H57340-HWATECOcontroller-EN_1805

nVent.com | 51
5
Pre-Defined Programs
Hospital
I-4
Monday-Sunday
Nursing home
I-5
Monday-Sunday
Hotel
I-6
Monday-Sunday
Sports center
I-7
Monday-Sunday
Convalescent home
I-8
Monday-Sunday
00
06
12
18
24
02 04 16
14
1008
20 22
00
06
12
18
24
02 04 16
14
1008
20 22
00
06
12
18
24
02 04 16
14
1008
20 22
= Maintain temperature= Heat-up cycle
= Economy temperature = Off
Heat-up
Economy
Maintain
Heat-up
Economy
Maintain
Heat-up
Economy
Maintain
00
06
12
18
24
02 04 16
14
1008
20 22
Heat-up
Economy
Maintain
00
06
12
18
24
02 04 16
14
1008
20 22
Heat-up
Economy
Maintain
Off
Off
Off
Off
Off
Raychem-IM-H57340-HWATECOcontroller-EN_1805

Heat-Up Cycle Graphs
6
52 | nVent.com
Raychem-IM-H57340-HWATECOcontroller-EN-1805
To calculate heat-up and cooldown times when heat cycle is
used.
Heat-Up HWAT-Y2
125
(52)
120
(49)
115
(46)
110
(43)
Time (hours)
Pipe Temperature °F (°C)
105
(41)
0 2 4 6 8 10 12 14 16 18 22 2420
70°F (21°C) ambient
1/2-inch pipe
1-inch pipe
2-inch pipe
208V
0 2 4 6 8 10 12 14 16 18 22 2420
Time (hours)
125
(52)
120
(49)
115
(46)
110
(43)
105
(41)
240V
1/2-inch pipe
1-inch pipe
2-inch pipe
70°F (21°C) ambient

Heat-Up Cycle Graphs
6
nVent.com | 53
Raychem-IM-H57340-HWATECOcontroller-EN-1805
Heat-Up HWAT-R2
0 2 4 6 8 10 12 14 16 18 22 2420
Time (hours)
150
(66)
140
(60)
130
(54)
120
(49)
110
(43)
105
(41)
240V
1/2-inch pipe
1-inch pipe
2-inch pipe
70°F (21°C) ambient
150
(66)
140
(60)
130
(54)
120
(49)
110
(43)
105
(41)
Time (hours)
Pipe Temperature °F (°C)
0 2 4 6 8 10 12 14 16 18 22 2420
70°F (21°C) ambient
1/2-inch pipe
1-inch pipe
2-inch pipe
208V

7
Cool-Down Graph
54 | nVent.com
Raychem-IM-H59181-HWATECO16controller-EN-1805
These cool down curves represent when the heating
cable is turned off.
0 1 2 3 4 5 6 7 8 9 11 1210
Cool-Down
150
(66)
140
(60)
130
(54)
120
(49)
110
(43)
145
(63)
135
(57)
125
(52)
115
(46)
105
(40)
Pipe Temperature °F (°C)
1/2-inch pipe
1-inch pipe
2-inch pipe
70°F (21°C) ambient

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates.
All other trademarks are the property of their respective owners. nVent reserves the right to change
specications without notice.
Raychem-IM-H57340-HWATECOcontroller-EN-1805
nVent.com
North America
Tel. +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nvent.com
Asia Pacific
Tel. +86.21.2412.1688
Fax +86.21.5426.3167
cn.thermal.info@nvent.com
Europe, Middle East, Africa
Tel. +32.16.213.511
Fax +32.16.213.604
thermal.info@nvent.com
Latin America
Tel. +1.713.868.4800
Fax +1.713.868.2333
thermal.info@nvent.com