718K Pipe Heating Cable 877Z De-Icing and Snow Melting Not UL Listed with XL-Trace heating cable for buried piping.
RayClic Connection System
RayClic-LE Lighted End Seal Kit Installation Instructions
DESCRIPTION
The nVent RAYCHEM RayClic-LE Lighted End Seal Kit is for use with nVent RAYCHEM IceStop, XL-Trace and HWAT heating cables. The connection is designed to be installed above the pipe insulation or mounted on the wall at the end of the heating cable circuit. These installation instructions should be used in conjunction with the IceStop, XL-Trace and HWAT System Installation and Operation Manuals.
For technical support contact your nVent representative or call
nVent (800)545‑6258.
TOOLS REQUIRED
• Utility knife • Wire cutters
®
• TORX
T20 screw driver
OPTIONAL ACCESSORIES (Not included in this kit):
• nVent RAYCHEM RayClic‑SB‑02 Wall mounting bracket
RayClic
718K Pipe Heating Cable
also Listed De-icing and
Snow Melting Equipment
®
WARNING:
Shock Hazard
Do not open while energized
-W
M
F
APPROVED
with HWAT, IceStop, and XL-Trace heating
cables.
Hazardous Locations
with GM-XT only.
-w
APPROVED
For HWAT, IceStop, and XL-Trace only Hazardous Locations: For IceStop (GM-XT) only Class I, Div. 2, Groups A,B,C,D
KIT CONTENTS
Item Qty Description
A 1 Lighted end seal
B 1 Pipe mounting bracket
C 2 Plastic cable ties
D 1 Clip
E 1 Cable lubricant
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions.
• To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent,
A B C D E
agency certifications, and national electrical codes, ground-fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers.
• Bus wires will short if they contact each other. Keep bus wires separated.
• Keep components and heating cable ends dry before and during installation.
• The black heating cable core is conductive and can short. It must be properly insulated and kept dry.
• Component approvals and performance are based on the use of nVent-specified parts only. Do not use substitute parts or vinyl electrical tape.
• Leave these instructions with end user for reference and future use.
Page 2
If you experience difficulty during installation, refer to the “Troubleshooting Guide” on page 5.
Lighted End Seal Installation
1
2
• Using the plastic cable ties, attach the bracket to the pipe. Note: For roof-mounted applications, follow steps 3 through
9 (pages 2–4), then turn to “Roof Installation” on page 4.
Do not install the end seal where it can be immersed in water.
• For the RayClic-LE lighted end seal, fold up the four outer snaps, then position the connector over the snaps and press down.
3
• Allow enough extra heating cable to make service loops as required.
• Make sure end of heating cable is cut clean.
5
• Remove the outer jacket.
• Place metal clip over the base of exposed braid.
4
• Score around and down the outer jacket of the heating cable 3 1/8 inches from the end.
Do not cut through
metal braid or
inner jacket.
2 | nVent.com
Page 3
HWAT
6A
IceStop and XL-Trace
6B
HWAT Only
• Using wire cutters, cut away 1-inch of the braid.
• Pull exposed braid back over metal clip.
IceStop and XL-Trace Only
• Pull exposed braid back over metal clip.
• Using wire cutters, cut away aluminum wrap.
7 8
• Apply a small amout of lubricant to the jacket surface near the end of the cable.
• Avoid using large amounts of lubricant on the exposed end of the cable.
• Insert prepared heating cable end into connector. Push until heating cable is fully inserted and end is visible through opening in connection cover plate.
Note: RayClic connection kits are designed to be installed only once; the heating cable cannot be removed once installed
nVent.com | 3
Page 4
9
Tighten the screws until the metal top surface is at the same height as the inner clear plastic module.
• Securely tighten the two connection screws, alternating as they are being tightened.
WARNING: Fire hazard. Loose screws can cause
excessive heating. Be sure screws are fully tightened.
Roof Installation
1
10
• Close the lid and snap the lever shut. Do not force lid closed; if lid does not close, check the connection to ensure all screws are fully tightened.
• Tighten the nuts on the heating cable entries until grommets are compressed.
2
• Position attachment clips on mounting bracket as shown.
RayClic-SB-02
• Mount flat (wall mounting) bracket under eaves by installing screws through the center holes.
Do not mount in gutter or where it may be immersed in water.
3 4
• Connect heating cable as detailed in steps 3 through 9
(pages 2–4).
Drip
loop
• Attach the connector to the mounting bracket by pressing until it snaps in place.
• Complete heating cable installation and install a drip loop as shown.
• Protect heating cable from sharp edges.
4 | nVent.com
Page 5
Troubleshooting Guide
Problem Solution
Braid clips are missing. The braid clips are attached to the cardboard packing insert
under the lid. The braid clips must be used to ensure a ground connection. If clips are missing or lost, call nVent at (800)545‑6258.
Mounting bracket is missing. A pipe mounting bracket is supplied with the Power Connection,
Powered Splice, Powered Tee and Lighted End Seal kits. A wall mounting bracket or additional pipe mounting bracket may be ordered using one of the catalog numbers listed under
“Optional Accessories” on the front page of these instructions
when you place your order.
Connector does not snap onto bracket. The bracket has two sets of attachment clips. Fold up the four
outer clips for the Power Connection and Lighted End Seal kit. Fold up only the center clips for the Powered Splice and Powered Tee kits.
Heating cable type not mentioned. RayClic connection kits are approved for use only with
RAYCHEM HWAT, XL-Trace, and IceStop heating cables. Do not use with other heating cables.
Braid clip does not fit. Be sure the clip is installed on the metal braid, not on
theouterjacket.
Heating cable does not have aluminum wrap. Only HWAT heating cables have the aluminum wrap under the
braid. Skip the aluminum wrap removal step for XL-Trace and IceStop heating cables.
Heating cable cannot be inserted into connector. Check for the following:
• Apply lubricant to heating cable primary (white) jacket.
• Outer jacket strip length is 3 1/8-inches.
• Braid clip is installed on top of the metal braid, not on the outer jacket.
• Braid is pulled back over braid clip.
• For HWAT, 1-inch of braid is removed.
• Sealing nut is loose (but not removed).
• Connection screws are loose.
Lid does not close. Be sure all screws are fully tightened before closing the lid.
Heating cable cannot be removed. The power connection and end seal are designed to be installed
only once; the heating cable cannot be removed once installed. Additional RayClic-E and RayClic-LE end seals can be ordered from nVent.
Light does not come on. • Verify there is voltage present.
• Verify the cable guide is screwed down completely.
• If the light still does not function, the RayClic-LE cannot be repaired and must be replaced.
nVent.com | 5
Page 6
North America
Tel +1.800.545.6258 Fax +1.800.527.5703
thermal.info@nvent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specications without notice.
Raychem-IM-H58082-RayClicLE-EN-1805 PN P000000801
Europe, Middle East, Africa
Tel +32.16.213.511 Fax +32.16.213.604
thermal.info@nvent.com
Asia Pacific
Tel +86.21.2412.1688 Fax +86.21.5426.3167
cn.thermal.info@nvent.com
Latin America
Tel +1.713.868.4800 Fax +1.713.868.2333
thermal.info@nvent.com
nVent.com
Loading...