Appendix A – Replacement Component Ordering Guide .......................................................... 23
Appendix B – Panel Specications.............................................................................................24
Appendix C – NGC-30-CRM/-CRMS Specications ................................................................... 27
Appendix D – NGC-UIT2 Specications ..................................................................................... 28
Appendix E – Device Address ..................................................................................................... 29
Appendix F – RAYCHEM RMM-DI Technical Specication ....................................................... 30
2 | nVent.com
Page 3
SECTION I – OVERVIEW
1.1 INTRODUCTION
The nVent RAYCHEM NGC-30 is a fully wired and tested control and monitoring system used
with electric heat tracing. This manual provides information pertaining to the installation,
operation, testing, adjustment, and maintenance of all components of the RAYCHEM NGC-30
System. For information about how to program the RAYCHEM NGC-30, see the RAYCHEM
NGC-30 Programming Guide (H58186)
A typical RAYCHEM NGC-30 is made up of at least a User Interface Terminal (NGC-UIT2),
one Card Rack (NGC-30-CR), one Card Rack Module with connectors
(NGC-30-CRM or NGC-30-CRMS), and one Current Transformer Module (NGC-30-CTM).
Optional Remote Monitoring Module for Temperatures (RMM2), Power Line Carrier Interface
(PLI), RMC modules, Remote Monitoring Module for Digital Inputs (RMM-DI) and Voltage
Monitoring Module (NGC-30-CVM) may be used.
The information in this document coincides with the specific releases of firmware
(listed in Table 1.1) for the User Interface Terminal (NGC-UIT2) and Card Rack Module
(NGC-30-CRM/-CRMS) components. As nVent releases new firmware to significantly modify
or enhance any of these components, new documentation will accompany these releases.
To ensure that the correct documentation is being used for your particular version of the
RAYCHEM User Interface Terminal (NGC-UIT2), compare the firmware version number of
each component against the number listed in the table below. As subsequent changes are
made, supplements to this document will be included in manuals shipped after the firmware is
released. Supplements will make specific reference to the operation or functional change.
Copies of this manual and updates may be downloaded from the Literature section of
nVent.com.
Table 1.1 Component versions
Component versions
ComponentVersion number
NGC-CRM/CRMSV1.0X
NGC-UIT2-EXV2.1.X or V4.X
RMM2V1.0X
RMM-DIV1.0
IMPORTANT WARNINGS AND NOTES
The following icons are used extensively throughout this manual to alert you to important
warnings
the unit. Be sure to read and follow them carefully.
that affect safety and to important notes that affect the proper operation of
nVent.com | 3
Page 4
SECTION2 – INSTALLATION AND WIRING
2.1 INTRODUCTION
WARNING:
Electrical Hazard! Ensure all personnel involved in installation, servicing, and programming are
qualified and familiar with electrical equipment, its ratings, and proper practices and codes.
Multiple voltages and signal levels may be present during the installation, operation, and
servicing of this product. Do not power the product until the safety provisions outlined in this
section have been observed.
This section includes information regarding the initial inspection, preparation for use,
and wiring instructions for the components of the RAYCHEM NGC-30.
2.2 INITIAL INSPECTION
Inspect the shipping container for damage. If the shipping container or cushioning material
is damaged, it should be kept until the contents of the shipment have been verified for
completeness and the equipment has been checked mechanically and electrically. Procedures
for installing the RAYCHEM NGC-30 are given in this section. If the shipment is incomplete,
mechanically damaged, defective in any way, or does not pass the electrical performance tests,
notify the nearest nVent representative. If the shipping container is damaged, or the cushioning
material shows signs of stress, notify the carrier as well as your nVent representative. Keep the
shipping materials for the carrier’s inspection.
2.3 OPERATING ENVIRONMENT
There are three types of User Interface Terminals (UIT2s) available with the RAYCHEM
NGC-30 panel, as shown in Table 2.1. The term “NGC-UIT2” in this document refers to any of
the available NGC-UIT2s, regardless of which model is actually installed.
NGC-30 User Interface Terminals (UIT2s)
UIT2 typeArea classificationUsage
NGC-UIT2-EXNonhazardous (Unclassified) Locations
Hazardous Locations
Class 1 Div. 2, Groups A, B, C & D
The NGC-UIT2-ORD-R must be installed in a
nonhazardous, indoor or outdoor location.
The NGC-UIT2-ORD-R connects to NGC-30
panels using RS-485 communication wiring.
TYPE 4
(Indoors or
Outdoors)
TYPE 4
(Indoors or
Outdoors)
WARNING:
Some wiring configurations will use more than one power source. All power sources must be
de-energized prior to performing any maintenance on a card rack module or its heating circuit.
The operating environment should be within the limitations specified for the RAYCHEM
NGC-30 components as outlined in Appendices B, C, and D.
4 | nVent.com
Page 5
2.4 INSTALLATION LOCATION
Power wiring diagram
Incomming service
2.5 MOUNTING PROCEDURES
2.6 WIRING PROCEDURES
The wide Operating Temperature range of the RAYCHEM NGC-30 permits installation in almost
any convenient location. Considerations should include: expected atmospheric conditions
(weather), accessibility for maintenance and testing, the location of existing conduits, and
hazardous location rating. Ambient temperature conditions may affect load current ratings
.
CAUTION:
Always be sure that the intended location is classified as an area that the product is approved
for use in as defined by Article 500 of the National Electrical Code and/or Part I, Section 18 of
the Canadian Electrical Code.
Each RAYCHEM NGC-30 panel includes a set of “As Built” drawings that have been engineered,
designed, and drafted based upon the model number and any special requirements that
were requested when ordering. The “As Built” drawings include an elevation/layout (with
bill of materials) and schematics. If these drawings are not included, contact your nVent
Representative and request the “As Built” drawings for your panel. Upon request, an electronic
copy of these drawings can be provided.
For mounting the panel, locate the elevation and layout drawing which includes a bill of
materials. The enclosure mounting information will be provided on the “As Built” drawings.
Refer to the “As Built” drawings for wiring of incoming/outgoing power and incoming RTD
connections. The RAYCHEM NGC-30 panel can be purchased with, or without, a distribution
panel board.
2.6.1 INCOMING POWER WITH DISTRIBUTION SYSTEM
Main Circuit Breaker
Locate the main circuit breaker in the panel by using the supplied elevation/layout drawing,
and connect per the associated schematic drawings. Depending upon the size and type of
main circuit breaker and voltage loss calculations, use the appropriate size and number of
wires to connect directly to the main circuit breaker, and panel board neutral and ground bus in
thepanel.
Three phase, 4 wire, 60 Hz
ØA ØB
ØC
Main circuit
breaker
3-pole
Panelboard
neutral bus
Panelboard
ground bus
Fig. 2.1 Main circuit breaker wiring
Branch Circuit Breakers
The branch circuit breakers are pre-wired to the contactors or solid- state relays in the panel,
sono further incoming power wiring is required.
nVent.com | 5
Page 6
2.6.2 OUTGOING POWER WITH DISTRIBUTION SYSTEM
e
EMR or
Branch
Load Power
Heat trace
** Represents HTC circuit number 1-40
Single pole C.B.
Tw
* Reference panel drawing for terminal block number
Load Power Terminal Blocks
Locate the outgoing heater terminal blocks using the supplied elevation/layout drawing, and
connect per the associated schematic drawings. Depending upon the size of the branch circuit
breaker and voltage loss calculations, use the appropriate size and number of wires to connect
from the panel’s Load Power Terminal Blocks to the heat-trace power junction box.
LCGF
CTM
connector
SSR
contacts
Terminal
TB- (Y)
13
14
15
16
17
Block
TB*
CRM
junction
box
Heat trace cabl
circuit
breaker
X
Cable-CT**
* Reference panel drawing for terminal block number
Fig. 2.2 Heat trace power wiring diagram
2.6.3 INCOMING/OUTGOING POWER WITHOUT DISTRIBUTION PANEL BOARD
Line Power Terminal Blocks
Locate the incoming power terminal blocks in the panel using the supplied elevation/layout
drawings and connect per the associated schematic drawing. Depending upon size and type of
the remotely located branch circuit breakers, use the appropriate size and number of wires to
connect directly to the Line Power Terminal Blocks.
Load Power Terminal Blocks
Locate the outgoing power terminal blocks in the panel using the supplied elevation/layout
drawings and connect per the associated schematic drawing. Depending upon size and type of
the remotely located branch circuit breakers, use the appropriate size and number of wires to
connect from the Load Power Terminal Blocks to the heater’s power connection box.
Line Power
Terminal Blocks
CB
LP
*
N
TB*
L1
C
–L1
–N
*
*
*
*
N
*
–T1
–N
CTM–
CT GF CT
Terminal Blocks
*
Load Power
TB*
T1
N
Heat trace cable
Fig. 2.3 Single pole and two pole circuit breaker wiring diagrams
6 | nVent.com
o pole C.B.
CB
*
LP
LP
Line Power
Terminal Blocks
TB*
L1
L2
Load Power
CTM–
C
–L1
–L2
*
*
*
*
*
–T1
–T2
CT GF CT
Terminal Blocks
*
TB*
T1
T2
Heat trace cable
Page 7
2.6.4 INCOMING RTD WIRING
DR
* Reference panel drawing for terminal block number
Device must be mounted in series.
Branching of the network is not allowed.
Nonhazardous and Hazardous Location Installations Wired to Terminal Block in Panel
The RTD wiring from the NGC-30-CRM/-CRMS have been pre-wired to RTD terminals. The field
RTD wiring (3-wire with shield) will be terminated by the installer at the RTD terminal blocks.
Refer to the Installation Drawings for the RTD Termination Schedule.
See Fig. 2.4 on page 8 for a typical RTD installation.
IMPORTANT: To meet the requirements for hazardous location installations, a separate RTD
terminal block must be installed and wired to the NGC-30-CRM/-CRMS RTD terminal connector.
NGC-30-CRM/-CRMSNGC-30-CRM/-CRMSPanel Rear
Card Rack ModuleCard Rack Module
CRMCRM
11
22
33
44
WHWH
REDRED
REDRED
OPENOPEN
(+)(+)
(–)(–)
Panel Rear
Terminal Block
Terminal Block
RTD-RTD-
TB*TB*
WHWH
REDRED
REDRED
SHLDSHLD
WHWH
REDRE
REDRED
SHLDSHLD
RTD-RTD-
Field
Field
Wiring
Wiring
EDRED
(+)(+)(–)(–)
REDREDWHWH
CHASSIS GRDCHASSIS GRD
Fig. 2.4 Typical RTD installation
2.6.5 CONNECTING THE RS-485 DEVICE NETWORK
The NGC-UIT2 display is typically linked to a network of RAYCHEM NGC-30-CRMs/-CRMSs and
optional nVent RAYCHEM RMM2s and PLIs. These are connected to the RAYCHEM NGC-UIT2
using an RS-485 communication cable (shielded, two conductor, twisted pair). The following
illustration shows how the RS-485 network for the NGC-UIT2 system may be configured.
(Terminated devices are shown in gray)
NGC-UIT2-EX
NGC-CRM/-CRMS
MSBLSB
TB 12
TB 7TB 6
NGC-CRM/-CRMS
MSBLSB
TB 12
TB 7TB 6
PLI
HN/HGABCN
RMM2
Jumper
RMM-DI
TB 19
TB 19
110
.
220
.
0
TB 1TB 2TB 3TB 4TB 5
1 2 3
TB 13 TB 14 TB 15 TB 16 TB 17
TB 1TB 2TB 3TB 4TB 5
1 2 3
TB 13 TB 14 TB 15 TB 16 TB 17
Norm
Mixed
S
6
S2 S1
6
S
Connect no more than two RS-485 cables to any device.
RMM-DI
RMM2
0
PLI
HN/HGABCN
NGC-UIT2-EX
NGC-CRM/-CRMS
TB 12
NGC-CRM/-CRMS
0
0-9
+
S+
36
TB 12
NGC-CRM/-CRMS
TB 12
MSB LSB
TB 7TB 6
MSB LSB
TB 7TB 6
MSB LSB
TB 7TB 6
110
.
220
.
TB 19
TB 19
TB 19
Norm
Mixed
TB 1TB 2TB 3TB 4TB 5
1 2 3
TB 13 TB 14 TB 15 TB 16 TB 17
TB 1TB 2TB 3TB 4TB 5
1 2 3
TB 13 TB 14 TB 15 TB 16 TB 17
TB 1TB 2TB 3TB 4TB 5
1 2 3
TB 13 TB 14 TB 15 TB 16 TB 17
S
6
S2 S1
6
S
0
0-9
+
S+
36
NGC-UIT2-EX
Fig. 2.5 RS-485 network configuration for the NGC-UIT2 system
nVent.com | 7
Page 8
In order for the RS-485 network to work properly, you must enable the termination resistor for
the first and last device. The devices shown in gray in Fig. 2.5 represent the devices for which
you must enable the termination resistors. The devices that are not grayed out represent the
devices for which you should not enable the termination resistors.
Optional RMM2 Installed in the Field
Refer to the RMM2 Installation Instructions (H56848) for field installation instructions.
You must connect a RS-485 connection from the RMM2 to an open RS-485 connector on the
NGC-30-CRM/-CRMS board in the RAYCHEM NGC-30 panel. To make this connection, a
pre-wired terminal block has been provided in the RAYCHEM NGC-30 panel. Connect the
RS-485 wire from the RMM2 to TB (per the panel drawing) while maintaining the correct
polarity. If the RMM2 is the first or last device in the RS-485 network, connect the
J17 termination jumper to pins 1 and 2. If the RMM2 is not the first or last device in the
RS-485 network, connect the J17 termination jumper to pins 2 and 3.
NGC-30 Panel
6
5
4
3
S
S
(+)
2
BK
(–)
1
WH
RS-485
1
S
+
2
BK
–
3
WH
TB*
NGC-30-CRM/-CRMS #1NGC-UIT2
* Reference panel drawing for terminal block number
1
S
2
BK
3
WH
TB*
RS-485RS-485
1
S
+
2
BK
–
3
WH
TB*
NGC-30-CRM/-CRMS #8
1
S
2
BK
3
WH
TB*
TB*
4
S
S
+
+
5
BK
BK
–
–
6
WH
WH
RMM2
Jumper
0
Default position (for all RMM2
units in network except first or last one)
J17
123
LNLN
Out
DI Wiring: Output: min 12V @ 10mA
DI -1
Termination mode
(first or last RMM2/RMM-DI in network)
J17
123
230V:
IN
115V:
~
1.5 VA
DI -2 DI -3 DI -4 DI -5 DI -6 DI -7 DI -8 DI -9 DI -10DI -11DI -12
Fig. 2.6 RMM2 RS-485 field wiring and termination jumper setting
DI-13 DI-14 DI-15
ADDR
H
ADDR
L
RS 485
8 | nVent.com
Page 9
Last PLI in network
NGC-30 Panel
6
5
4
3
S
(+)
2
(–)
1
Optional PLI Installed in the Panel
Refer to the PLI Installation Instructions (H56850). You must connect a RS-485 connection
from the PLI to an open RS-485 connector on the NGC-30-CRM/-CRMS board in the RAYCHEM
NGC-30 panel. IF the PLI is the first or last device in the RS-485 network, remove the shorting
block jumper location J2 from 1 and 2 and place it across pins 2 and 3.
9
S2S1
* Reference panel drawing for terminal block number
110
.
220
.
1
1
S
BK
WH
RS-485
S
+
BK
–
WH
NGC-30-CRM/-CRMS #1NGC-UIT
Default position (for all PLI
units in network except first or last one)
J2
2
3
TB*
123
S
2
BK
3
WH
TB*
RS-485RS-485
1
1
S
+
BK
–
WH
S
2
2
BK
3
3
WH
TB*
TB*
NGC-30-CRM/-CRMS #8
Termination mode
(first or last PLIin network)
J2
123
HN/H GABCN
Norm
Mixed
S
J2
123
5
6
5
RS-485 connections
+ ––
+
S
S
36
Fig. 2.7 PLI RS-485 panel wiring and termination jumper setting
NGC-UIT2 Installation
The NGC-UIT2-EX will come pre-wired into any NGC-30 panel. Exceptions exist when a remote
mount NGC-UIT2 (NGC-UIT2-ORD-R) is used or the NGC-30 panel is wired to the NGC-UIT2
in another panel. Fig. 2.8 shows the wiring for the NGC-UIT2-ORD-R and Fig. 2.10 shows the
wiring between a separate panel and the NGC-UIT2.
nVent.com | 9
Page 10
NGC-UIT2-ORD-R Installation
NGC-30-CRM/-CRMS
Normal
position
End of Line
position
3
2
1
3
2
1
You must make an RS-485 connection from the NGC-UIT2-ORD-R to the NGC-30-CRM/-CRMS
board in the NGC-30 panel. To make this connection, a pre-wired terminal block has been
provided in the NGC-UIT2-ORD-R and in the NGC-30 panel. Connect the RS-485 wire from TB3
in the NGC-UIT2-ORD-R and the other end to TB* in the NGC-30 panel maintaining the correct
polarity. If the NGC-UIT2-ORD-R and/or the NGC-30-CRM/-CRMS is the first or last device in the
RS-485 network, see Fig. 2.9 and Table 3.1 for details on how to terminate the RS-485 network.
* Reference panel drawing for terminal block numbers.
NGC-UIT2-ORD-R
SR 9 876
43521
RS-485+
RS-485–
Field
Remote
RS-485 Ports
RS-485
NGC-30 Panel #1
TB*
3
S
S
+
+
2
BK
BK
–
–
1
WH
WH
* Reference panel drawing for terminal block number
1
1
S
+
BK
–
WH
NGC-30-CRM/-CRMS #1
S
2
2
BK
3
3
WH
TB*
TB*
RS-485
S
+
BK
–
WH
TB*
NGC-30-CRM/-CRMS #8
1
1
2
2
3
3
TB*
Fig. 2.8 NGC-UIT2 RS-485 field wiring
The following figure shows the RS-485 termination options for the NGC-30-CRM/-CRMS.
MSB LSB
TB 1TB 2TB 3TB 4TB 5
1 2 3
TB 12
TB 7TB 6
TB 19
TB 13TB 14TB 15TB 16TB 17
Fig. 2.9 Termination of RS-485 network for NGC-30-CRM/-CRMS
10 | nVent.com
End of Line (EOL) Jumper
If this device (NGC-30-CRM/-CRMS) is
the first or last device in the RS-485
network, move the J1 jumper from
terminals 2 & 3 to terminals 1 & 2.
Page 11
NGC-30 Panel with NGC-UIT2 Connected to an NGC-30 Panel without NGC-UIT2
This wiring is used when a single UIT2 in one panel is the central point for multiple
NGC-30 panels. Because the NGC-UIT2 can handle up to 260 heat tracing circuits, it can be
cost effective to use one NGC-UIT2 for multiple panels. An RS-485 connection must be made
from the panel that has the NGC-UIT2 (panel #1) installed to the NGC-30-CRM/-CRMS board
in NGC-30 (panel #2) that does not have the NGC-UIT2 installed (see Fig. 2.10). To make this
connection, a pre-wired terminal block has been provided in the panel #1 and in panel #2.
Connect the RS-485 wire from TB* in panel #1 and the other end to TB* in panel #2 maintaining
the correct polarity. If the NGC-30-CRM/-CRMS is the first or last device in the RS-485 network,
see Fig. 2.9 and Table 3.1 for details on how to terminate the RS-485 network.
* Reference panel drawing for terminal block numbers.
NGC-30 Panel #1
6
* Reference panel drawing for terminal block number
5
4
1
3
S
S
(+)
2
BK
(–)
1
WH
RS-485
NGC-30-CRM/-CRMS #1NGC-UIT2
1
S
+
BK
–
WH
S
2
2
BK
3
3
WH
TB6
TB6
RS-485RS-485
1
1
S
+
BK
–
WH
S
2
2
BK
3
3
WH
TB6
TB6
NGC-30-CRM/-CRMS #8
RS-485
NGC-30 Panel #2
without UIT installed
TB*
1
S
S
+
+
2
BK
BK
–
–
3
WH
WH
RS-485
1
1
S
+
BK
–
WH
S
2
2
BK
3
3
WH
TB6
TB6
NGC-30-CRM/-CRMS #1
RS-485
NGC-30-CRM/-CRMS #8
Fig. 2.10 RS-485 field wiring between two RAYCHEM NGC-30 panels
TB*
4
S
S
+
+
5
BK
BK
–
–
6
WH
WH
1
1
S
+
2
2
BK
–
3
3
WH
TB6
TB6
nVent.com | 11
Page 12
2.7 CONNECTIONS FOR REMOTE ANNUNCIATION — NGC-UIT2-EX
NGC-UIT2 Relay 1
To
n
NGC-UI
n
NGC-UIT2 Relay 2
n
Relay 1 on the NGC-UIT2-EX has been factory-configured and wired for “Any Alarms” unless
otherwise specified. It is powered by 12 Vdc and will energize a light on the front of the panel
if any alarm occurs. Relay 1 was also wired to a common alarm relay/terminal block for
remote annunciation of any alarms. Please see below the NGC-UIT2 Relay 1 in non-energized,
energized and in alarm condition.
Non-energized
alarm
light
Energized without an alarm conditionEnergized with an alarm conditio
To alarm
light
To alarm
light
NC
C
NO
NC
NO
NC
C
C
NO
Fig. 2.11 Relay 1 wiring
The NGC-UIT2 has two other Form C alarm relays (configurable through the NGC-UIT2 program)
for external alarms. Each relay can be connected to an annunciator light or distributed control
system. Each relay’s contacts have been wired from the NGC-UIT2 to a terminal block in the
panel.
Non-energizedEnergized without an alarm conditionEnergized with an alarm conditio
NC
C
NO
NC
NO
NC
C
C
NO
T2 Relay 3
Non-energizedEnergized without an alarm conditionEnergized with an alarm conditio
Fig. 2.12 Relays 2 and 3 wiring
IMPORTANT: An energized relay with no alarm condition will change state with loss of power
or an alarm condition.
12 | nVent.com
NC
NO
NC
C
C
NO
NC
C
NO
Page 13
2.8 RS-232, RS-485, OR ETHERNET REMOTE PORT CONNECTIONS TO A HOST COMPUTER
NGC-UIT2-EX
The NGC-UIT2 can communicate with a distributed control system (DCS) or other host
computer through the NGC-UIT2 external communication ports. The NGC-UIT2 provides ports
for RS-232,
RS-485, and Ethernet communication. All of these communication ports provide data read
access. However, only one port can be assigned read/write access. This is done using
theNGC-UIT2.
2.8.1 RS-232 SERIAL CONNECTIONS
The RS-232 port can be used as a direct connection to a single PC located within 50 feet of the
panel. (Refer to Fig. 2.14 on page 16). For an RS-232 connection, a 5-foot long 9-pin female D
connector to 9-pin female D-connector null modem cable has been provided with the
NGC-UIT2. Using the supplied cable, plug one end into the RS-232 port on the NGC-UIT2 and
the other end into the 9-pin male connector on the user’s computer.
9-pin
female
RS-232
5-foot 9-pin female D connector
to 9-pin female D connector
null modem cable supplied with
NGC-UIT2-ORD
9-pin
female
PC Laptop
9-pin
male
Side view
Fig. 2.13 RS-232 connection
2.8.2 RS-485 SERIAL CONNECTIONS
Use the RS-485 port when multiple NGC-UIT2 units are to be connected to a host computer or
the connection is longer than 50 feet. An RS-485 to RS-232 or RS-485 to USB converter may be
required to make the connection to the user’s PC.
NGC-30 Panel
6
5
4
3
S
(+)
2
(–)
1
NGC-UIT2
RS-485
S
BK
WH
To NGC-30-CRM/-CRMS
Fig. 2.14 RS-485 connection
TB*
3
S
S
++
2
BK
BK
––
1
WH
WH
RS-485 Converter
* Reference panel drawing
for terminal block number
9-pin
female
PC
9-pin
male
nVent.com | 13
Page 14
2.8.3 ETHERNET CONNECTIONS
e
The Ethernet port can be used to connect multiple NGC-UIT2 units to a host computer by
connecting to the user’s LAN system.
NGC-UIT2-EX
Fig. 2.15 Ethernet connection (NGC-UIT2-EX)
2.9 TESTING THE NGC-30 SYSTEM
Once the wiring to the panel has been finished, confirm that it was done properly by completing
the following steps:
1. Turn the power on to all network devices (NGC-30-CRMs/-CRMSs and optional RMM2s &
2. Once the NGC-UIT2 has booted up to the Main screen, Go to the Network | Device Screen
Bottom view
PLI modules) and the NGC-UIT2.
and press “Update Network.”
Ethernet
Ethernet cable
Network nod
Fig. 2.16 Network|Devices screen
3. Confirm all modules have been scanned into the Network database.
4. If a device or an RTD is installed but does not show up in the Network | Devices Screen,
For Devices:
For RTDs:
Turn the power on to all devices (NGC-30-CRMs/-CRMSs and optional RMM2s & PLI) and the
NGC-UIT2. Once the NGC-UIT2 has booted up to the Main screen, Go to the Network | Device
Screen and press “Update Network.” Confirm all NGC-30-CRM s/ -CRMSs, RTDs, and/or RMM2s
and PLI modules have been scanned into the Network database.
14 | nVent.com
turn the power off to the system and:
a. Confirm the device has a unique address (refer to section 3.2 on page 24)
b. Confirm the device is being powered
c. Confirm the RS-485 connection is in place with the correct polarity (refer to section 2.6.5)
a. Confirm the RTD connection is in place with the correct polarity
b. Perform a resistance check of the RTD. The resistance should be in a range of 70–250
ohms
Page 15
SECTION 3 – RAYCHEM NGC-30 COMPONENTS AND OPERATION
The RAYCHEM NGC-30 heat-trace system is comprised of a number of modular components,
allowing the ultimate in design flexibility. This section describes the NGC-30 control and
monitoring components (excluding the optional distribution section). Appendix B, C, and D
includes the specifications for these components.
3.1 USER INTERFACE TERMINAL (NGC-UIT2)
The NGC-UIT2 is a panel mounted color LCD display with touch-screen overlay. The NGC-UIT2
includes software that interfaces with the Card Rack Modules (NGC-30-CRM and NGC-30-CRMS)
and the Remote Monitoring Module for temperatures (RMM2), Remote Monitoring Module for
Digital Inputs (RMM-DI) and Power Line Carrier Interface (PLI) module.
The NGC-UIT2 is used as a control panel, setup device and user display.
3.1.1 MULTIPLE NGC-UIT2 MODELS
There are two versions of User Interface Terminals (UITs) available as specified in Table 2.1,
“NGC-30 User Interface Terminals (UIT2s),” on page 4. The term “NGC-UIT2” in this document
refers to any of the available NGC-UITs, regardless of which model is actually installed.
Fig. 3.1 Typical NGC-UIT2 model showing NGC-UIT2-ORD-R remote user interface terminal
The physical dimensions of each NGC-UIT2 model vary; the dimensions of the
NGC-UIT2-ORD-R shown in the figure are the largest of all NGC-UITs:
• Width: 15.21” (386 mm)
• Height: 13.21” (336 mm)
• Depth: 7.09” (180 mm)
NGC-UIT2 LCD Touch-Screen Display
The NGC-UIT2-EX and NGC-UIT2-ORD-R have a 7 inch wide x 5 ¼ inch high LCD
(17.5 cm X 13.3 cm) LCD color display. All NGC-UIT2 have touch-screen technology that
provides an user interface easy and efficient programming with no keyboards or cryptic labels.
nVent.com | 15
Page 16
3.1.2 NGC-UIT2 LOCAL AND REMOTE NETWORK CONNECTIONS
Bottom view
NGC-UIT2-EX
The NGC-UIT2 communicates to both a local field network and optionally to a remote
monitoring and control network.
Local Field Network Connection
The local field network always uses an RS-485 serial connection running over shielded
twisted-pair cable. This network is used to connect the NGC-UIT2 to its control and monitoring
modules:
• RAYCHEM Solid State Relay Controller - NGC-30-CRMS
• RAYCHEM Current Transformer Module Controller - NGC-30-CTM
• RAYCHEM Voltage Monitoring Module - NGC-30-CVM
• RAYCHEM Remote Monitoring Module for Temperature Measurement - RMM2
• RAYCHEM Remote Monitoring Module for Digital Inputs - RMM-DI
• RAYCHEM Power Line Carrier Interface Module - PLI
The local field network must follow configuration rules about topology and termination of
network end devices.
Remote Monitoring and Control Network Connection
The remote monitoring and control network communicates via a selectable network
connection port using either RS-485, RS-232, or 10/100Base-T Ethernet. This network is
used to connect to multiple NGC-UIT2 systems and communicate with a central PC running
RAYCHEM Supervisor software. The RAYCHEM Supervisor software provides centralized
status and alarm monitoring, data logging, and remote configuration control over all attached
NGC-UIT2 systems in the network. The remote monitoring and control network must also
follow configuration rules about topology and termination of the network end devices.
16 | nVent.com
CAN
(not used)
RS-485
(not used)
Reset
RS-485
Side view
(not used)
USBPower
Front view
Open Collector Outputs
RS-485 2
Debug Port (not used)
RS-485 1
Fig. 3.2 NGC-UIT2-EX touch-screen display, controls, and connections
USB device port
(not used)
Ethernet
Termination
RS-485-1
RS-232
Side view
Termination
RS-485-2
Page 17
3.1.3 RS-485 CONFIGURATION SWITCHES
321
Reset
The configuration switches are found on the right side of the NGC-UIT2-ORD. Refer to table 3.1
for settings.
(As-shipped default) RS-485
network “–” signal is forced
to a determinate state when
idle.
(As-shipped default)
RS-485 network “+” signal
is forced to a determinate
state when idle.
(As-shipped default) RS-485
network is terminated with
120-ohm resistor.
RS-485 network “–” signal
is not forced to a determinate
state when idle.
RS-485 network “+” signal
is not forced to a determinate
state when idle.
RS-485 network is not terminated.
One and only one device (typically
this NGC-UIT2-ORD) on the RS-485
network should force the network “-“
signal to a determinate state.
One and only one device (typically
this NGC-UIT2-ORD) on the RS-485
network should force the network
“+“ signal to a determinate state.
Terminate the device (NGC-UIT2-ORD
or other) that is at each end of the
RS-485 network, for a total of two
terminated devices. No other devices
on the network should be terminated.
3.1.4 NGC-UIT2-EX RESET SWITCH
The reset switch is located on the side of the NGC-UIT2-EX panel. A pointed object is required
to press the restart switch and restart the UIT2 software.
Fig. 3.3 Reset switch
nVent.com | 17
Page 18
3.2 CARD RACK MODULE (NGC-30-CRM/-CRMS) AND CURRENT TRANSFORMER MODULE (NGC-30-CTM)
12 Vdc Inputs (2x)
Address Switches
NGC-30-CRM/-CRMS
5
10
Each Card Rack Module (NGC-30-CRM and NGC-30-CRMS) and Current Transformer Module
(NGC-30-CTM) provide ground-fault and line current sensing, alarming, switching, and RTD
input for five Loops. The NGC-30-CRM is used with electromechanical relays. The NGC-30CRMS is used with solid-state relays. The NGC-30-CRM/-CRMS may be connected to one
User Interface Terminal (NGC-UIT2).
Each NGC-30-CRM/-CRMS must have a unique communication address. The valid address
switch range for the NGC-UIT2 is 1–99. SW1 is the ones digit (0–9) and SW2 is the tens digit
(0–9). See Fig. 3.6.
IMPORTANT: RMM2s use ModBus addresses 32 through 47 and PLIs use Modbus addresses
1-99. When using RMM2s and PLI modules in an NGC-30 system, care must be taken to not
assign the same addresses to an RMM2, PLI module or an NGC-30-CRM/-CRMS board.
LSBMSB
8
Fig. 3.4 Communication address switch
IMPORTANT: When adding an NGC-30-CRM/-CRMS to the system, power must be cycled to
the board and a network update on the NGC-UIT2 must be performed.
Each NGC-30-CRM/-CRMS has a cluster of nine LED lights to advise the status of the board.
Number 3 in Fig. 3.7 shows the location of the LED lights.
3.3 CARD RACK (NGC-30-CR)
Power
Relay 1
Relay 3
Tx
Alarm
Rx
Relay 2
Relay 4
Alarm Energized upon AlarmRed
PowerEnergizes upon power to unit Green
Relays 1, 2, 3, 4, 5Energizes upon relay closedRed
RX & TXEnergizes upon received and
transmit of RS-485 data
Relay 5
Amber
LED functions
Table 3.2 LED Display
The Card Rack (NGC-30-CR) has the capability to house one to four Card Rack Modules (CRMs).
Fig. 3.6 NGC-30 card rack
3.4 VOLTAGE MONITORING MODULE (NGC-30-CVM) – OPTIONAL
The optional voltage sensor can monitor 80–290 Vac. This voltage sensor connects to one of
the five line current/ground-fault inputs of the NGC-30-CRM/-CRMS
(IMPORTANT: By using the optional voltage sensors, the NGC-30-CRM/-CRMS board looses
one circuit).
Fig. 3.7 NGC-30 voltage monitoring module
nVent.com | 19
Page 20
3.5 REMOTE MONITORING MODULE (RMM2) – OPTIONAL
The RAYCHEM Remote Monitoring Module (RMM2) provides additional temperature
monitoring capabilities. Each RMM2 accepts up to eight RTDs that measure pipe, vessel,
or ambient temperatures. The RMM2 can be installed in the RAYCHEM NGC-30 enclosure or
can be located in the field to reduce RTD field wiring.The RAYCHEM NGC-30 system supports
260 temperature inputs via the CRM/CRMs boards. Sixteen (16) RMM2s can be connected
via a single, twisted pair RS-485 cable to provide up to 128 additional RTD inputs into the
RAYCHEM NGC-30 system.
Fig. 3.8 RMM2 module
Set the RS-485 address for the RMM2 using the rotary switch provided. Note the orientation of
the clear plastic cover, then remove the cover. Use a slotted screwdriver to rotate the selector
switches to the appropriate positions to select the RS-485 address. The single character visible
on the switch indicates the RS-485 address assigned.
0
0
6
Fig. 3.9 RMM2 rotary switch
Table 3.3 RMM2 Switch Settings
RMM2 Switch Settings
Switch Settings0123456789ABCDEF
Device Address32333435363738394041424344454647
20 | nVent.com
Page 21
3.6 POWER LINE CARRIER INTERFACE MODULE (PLI) – OPTIONAL
RAYCHEM PLI modules (Power Line Carrier Interface) together with RAYCHEM temperature
transmitters provide remote temperature-monitoring capability for heat-tracing control and
monitoring systems by communicating the temperature data to the control system over the
heat-tracing bus wires and the AC power line, eliminating the need for RTD wiring. Typical
savings on the installation costs of a heat-tracing system can be as much as 30% with PLI
technology, depending on the specifics of each application.
The PLI module typically resides in the NGC-30 panel and receives input from special
transmitters connected to the heat-tracing. The transmitters provide pipe temperatures from
RTDs and continuity confirmation; they are typically located at the front and/or end of the
heat-tracing circuit. The PLI special transmitters are: RAYCHEM SES (Smart End Seal),
RAYCHEM SPC (Smart Power Connection) and RAYCHEM 700-TT.
The NGC-30 system can accept up to 127 temperature inputs from SES/SPC transmitters or
255 temperature inputs from 700-TT transmitters, per PLI module. Up to four PLI modules can
be connected to one NGC-30 UIT2.
Fig. 3.10 PLI module
Set the RS-485 address for the PLI module using the rotary switches provided. Note the
orientation of the clear plastic cover, then remove the cover. Use a slotted screwdriver to rotate
the selector switches to the appropriate positions to select the RS-485 address. Each PLI
module must have a unique address, if two PLI modules, CRM or RMM are assigned the same
address, communication faults will result. The PLI module switch setting can be set from 1-99.
220
.
HN/H GABCN
Fig. 3.11 PLI module rotary switch
6
S2S1
6
110
.
S
+
Norm
Mixed
S
0
0-9
S+
36
nVent.com | 21
Page 22
3.7 THE REMOTE MONITORING MODULE FOR DIGITAL INPUTS (RMM-DI)
Provides the capability for the RAYCHEM NGC controller family to read the status of devices
remotely and can link them back to the electrical heat-tracing circuits.
The RMM-DI has in total 15 digital inputs. Multiple RMM-DI units can communicate with a
single User Interface providing centralized monitoring capabilities.
RS 485
DI-15
DI-14
DI-13
0
0
ADDR
H
L
230V:
IN
1.5 VA
~
L N L N
Out
DI Wiring: Output: min 12V @ 10mA
Fig. 3.12 RMM-DI 3D
Control and monitoring
A RAYCHEM NGC network controls up to 260 heat-tracing circuits per system based on
ambient or pipe temperatures. The RMM-DI module can be used to collect circuit breaker
status, contactor status or other digital information in the field. This information will be
communicated back to a central location via one communication cable, reducing installation
and wiring cost.
ADDR
115V:
DI -2 DI -3 DI -4 DI -5 DI -6 DI -7 DI -8 DI -9 DI -10 DI -11 DI -12
DI -1
L NL N
Out
DI Wiring: Output: min 12V @ 10mA
DI -1
230V:
IN
115V:
~
1.5 VA
DI -2 DI -3DI -4 DI -5 DI -6 DI -7 DI -8 DI -9 DI -10 DI -11 DI -12
DI-13 DI-14 DI-15
ADDR
H
ADDR
L
Fig. 3.13 RMM-DI Front view
RS 485
22 | nVent.com
Page 23
SECTION 4 – APPENDICES
APPENDIX A – REPLACEMENT COMPONENT ORDERING GUIDE
Replacement Components
Description Catalog NumberPart Number
User Interface Terminal
Hazardous and non hazardous C1D2, Zn2
User Interface Terminal with TYPE 4 Enclosure
Nonhazardous (Unclassified) Locations; indoors or
outdoor, remote stand-alone mounting
Proportional (includes soft start for all SSR control modes)
24 | nVent.com
Page 25
Table B.1 Panel Specifications
Monitoring
Temperature
Low alarm range
High alarm range
Ground fault
Alarm range
Trip range
Current
Low alarm range
High alarm range
Voltage100 – 277 Vac supply voltage to heat-tracing
–99°F to 900°F (–73°C to 482°C) or OFF
–99°F to 900°F (–73°C to 482°C) or OFF
10 mA to 200 mA
10 mA to 200 mA or OFF
0 A to 100 A (where 0 equals OFF)
0 A to 100 A (where 0 equals OFF)
(IMPORTANT: Requires the loss of one circuit)
Temperature Sensor Inputs
MonitoringRAYCHEM NGC-30 system can monitor up to 1040 (260 x 4) temperatures
Quantity per circuitUp to four temperature inputs can be assigned to one circuit
Temperature sourcesHard-wired, optional RMM2 Module, optional PLI module
Temperature inputs per control pointStandard:
One input standard per control point
Optional:
Up to three additional RTDs per control point connected via RMM2 and/or PLI Module
Temperature inputs per NGC-UIT2Hard-wired:
Up to 260 hard-wired temperature inputs, one per circuit
RMM2 (optional):
Up to 128 RTD inputs via RMM2 Modules. Up to 8 RTDs per RMM2 Module and up to 16
RMM2 Modules per NGC-30 controller
PLI module (optional):
Up to 127 RTDs via SES Transmitter (per PLI Module)
Up to 127 RTDs via SPC Transmitter (per PLI Module)
Up to 255 RTDs via 700-TT Transmitter (per PLI Module)
Four PLI Modules per circuit, maximums 1040 RTDs
Types100 W platinum RTD, 3-wire, a = 0.00385 ohms/ohm/°C
Can be extended with a 3-conductor shielded cable of 20 W maximum per conductor
(IMPORTANT: power wire and RTD wire should not be housed in the same conduit).
Alarm Outputs
Relay outputs3 SPDT Form C. Rating: 3 A 100 – 277 Vac
Each relay may be assigned to alarm outputs
Programming and Setting
MethodVia NGC-UIT2 (User Interface Terminal)
Units°F or °C
Digital display
NGC-UIT2-EX7 inch x 5 ¼ inch LCD color touch screen (17.5 cm X 13.3 cm)
MemoryNonvolatile, restored after power loss
Stored parameters (measured)Minimum and maximum temperatures, contactor cycle count, heater time in use
communications failure, relay failure, relay count, total time heater energized, contactor
failure
nVent.com | 25
Page 26
Table B.1 Panel Specifications
User Interface Terminals (UITs)
NGC-UIT2-EXArea Classification:
Usage:
NGC-UIT2-ORD-RArea Classification:
Usage:
Nonhazardous (Unclassified) or Hazardous Locations
TYPE 4 (indoors or outdoors)
Nonhazardous (Unclassified) Locations
The NGC-UIT2-ORD-R must be installed in a
nonhazardous, indoor or outdoor location.
The NGC-UIT2-ORD-R connects to RAYCHEM NGC-30
panels using RS-485 communications wiring.
TYPE 4 (indoors or outdoors)
Connection Terminals
Heating cable outputScrew terminals, 20–6 AWG
(30 A versions), 14–2 AWG
(60 A versions)
Ground14–4 AWG ground bar
RTD / alarm / communications28–12 AWG spring clamp terminals
Distribution (for RAYCHEM NGC-30 EMR only)
Load power120 / 208 / 240 / 277 / 347 / 480 /
600 Vac
Standard circuit breakersUS (United States country code in ordering details):
Square D type QOB 120 / 208 / 240
Square D type NF 277 / 480
CA (Canada country code in ordering details):
Cutler Hammer (Canada) type BAB 120 / 208 / 240
Cutler Hammer (Canada) type GBH 277 / 480 / 347 / 600
Circuit breaker amperage rating120 Vac
208, 240, 277, 347, 480, 600 Vac
120 Vac
208, 240, 277, 347, 480, 600 Vac
26 | nVent.com
Page 27
APPENDIX C – NGC-30-CRM/-CRMS SPECIFICATIONS
Class I, Div. 2, Groups A,B,C,D
Class I, Zone 2, AEx nC IIC T5
Table C.1 NGC-30-CRM/-CRMS Specifications
General
Approvals/certifications
Supply voltage 12 Vdc ± 10%
Internal power consumption< 5 W per NGC-30-CRM/-CRMS
Operating temperature –40°F to 140°F (–40°C to 60°C)
Storage temperature –40°F to 167°F (–40°C to 75°C)
EnvironmentPD2, CAT III
Max. altitude2000 m
Humidity 0–90% noncondensing
Ex nC IIC T5
Electromagnetic Compatibility
ImmunityHeavy industrial
EmissionResidential, commercial, light industrial
Temperature Sensors
Type100 W platinum RTD, 3 wire, a = 0.00385 ohms/ohm/°C
Can be extended with a 3-conductor shielded cable of 20 ohm maximum per conductor
QuantityUp to five wired directly to each NGC-30-CRM/-CRMS
Current Sensors
MountingDIN Rail – 35 mm
Quantity per NGC-30-CTMFive for ground-current measurement. Five for line-current measurement
Line Current Sensors
Max. current60 A
Accuracy± 2% of reading
Ground-Fault Sensor
Range10–200 mA
Accuracy± 4% of range at 30 A line current
Voltage Sensor
Range 80–290 Vac 50/60 Hz
Accuracy± 1% of span
Outputs
CRM output relaysForm A 3-Amp @ 277 Vac max 50/60 Hz
CRMS SSR outputs12 Vdc @ 30 mA max per output
Alarm relayForm C 3-Amp @ 277 Vac max 50/60 Hz
Communication to NGC-UIT2 or 200N
Type 2-wire RS-485
CableOne shielded twisted pair
Length4000 ft. (1200 m) maximum*
*IMPORTANT: May require an RS-485 repeater if communication length is greater
than 4000 ft.
QualityUp to 52* NGC-30-CRM/-CRMS may be connected to one NGC-UIT2
Up to 16 NGC-30-CRM/-CRMS may be connected to one 200N
Connection Terminals
Power supply/pilot relay/RTD/
comm port (RS485)
18–12 AWG (0.8 - 3.3 mm
2
)
nVent.com | 27
Page 28
APPENDIX D – NGC-UIT2 SPECIFICATIONS
LR67275
Nonhazardous Locations
Nonhazardous Locations
Hazardous Locations
RU C-BE-MЮ62.B.02850
Ex nA IIC T5 Gc
Clas
–40°C
Table D.1 NGC-UIT2-EX Specifications
General
ApprovalsNGC-UIT2-EX
|| 3G
ITS15ATEX18221X
≤ Ta ≤ 60°C
IECEx ETL 15.0015X
2
RoHS
4000758
- 0.52 mm2)
s | Div.2 Groups A,B,C,D T5
Area of use Ordinary (nonhazardous) and Hazardous locations,
indoors or outdoors (IP65, Type 4X)
Supply voltage
9 – 30 Vdc, 15 W Max, AWG 18-22 (0.9 mm
Operating temperature–40°C to 60°C (–40°F to 140°F)
Minimum storage temperature–40°C to 80°C (–40°F to 176°F)
Dimensions279 mm W X 229 mm H X 70 mm D (11 in. W X 9 in. H X 2.75 in. D)
Humidity Range10 to 90% Non-Condensing
ApprovalsNGC-UIT2-ORD-R
2Ex nA IIC T5 Gc X
Area of use Nonhazardous, indoors or outdoors (IP65, TYPE4)
Supply voltage 9 – 30 Vdc, 3.6 – 1.2 A
Operating temperature–22°F to 140°F (–30°C to 60°C)
Minimum storage temperature–22°F to 176°F (–30°C to 80°C)
Dimensions11" W X 9" H X 2.75" D (279 mm W X 229 mm H X 70 mm D)
Alarm Outputs
Transistor open collector outputs
Use to drive external relaysRelays may be assigned for alarm outputs
Three open collector outputs, with a range of 5 – 30 Vdc with a max.
sink current of 500 mA
LCD Display
Display LCD is a 8.4 inch XGA, color TFT transflective device with integral LED backlight
Touch screen5-wire resistive touch screen interface for user entry
Network Connection
Local/Remote PortRS-232/RS-485 ports may be used to communicate with host computers
(RAYCHEM Supervisor Software) or DCS
Local RS-232 A non-isolated, 9 pin D sub male
Remote RS-485 #2 2-wire isolated, 9 pin D sub male
Data rate Data Rate 9600 to 57600 baud
Maximum cable length For RS-485 not to exceed 4,000 ft (1,200 m). Cable to be shielded twisted pair.
Field Port RS-485, 2-wire isolated. Used to communicate with external devices, such as
NGC-30-CRM and RMM2. Maximum cable length not to exceed 4,000 ft (1,200 m).
Cable to be shielded twisted pair.
Field RS-485 #12-wire isolated, 9 pin D sub male
Data rateData Rate To 9600 baud
LAN10/100 Base-T Ethernet port with Link and Activity Status LEDs
USB Ports USB 2.0 Host port Type A receptacle (X2)
28 | nVent.com
Page 29
APPENDIX E – DEVICE ADDRESS
Table E.1 Device Address
DeviceDevice TypeSwitch SettingDevice Address
NGC-30-CRM/-CRMSRelay Output/RTD1–991–99
(If RMM2s are equipped or
will be added in the future,
skip addresses 32–47)
RMM2RTD032
RMM2RTD133
RMM2RTD234
RMM2RTD335
RMM2RTD436
RMM2RTD537
RMM2RTD638
RMM2RTD739
RMM2RTD840
RMM2RTD941
RMM2RTDA42
RMM2RTDB43
RMM2RTDC44
RMM2RTDD45
RMM2RTDE46
RMM2RTDF47
PLI moduleRTD1-991-99
nVent.com | 29
Page 30
APPENDIX F – RAYCHEM RMM-DI TECHNICAL SPECIFICATION
Table F.1 RAYCHEM RMM-DI technical specification
General
Area of use Hazardous area when mounted in Ex-d enclosure
RMM-DI panel mount, safe area
Approval
(Russia, Kazakhstan, Belarus)
For other countries contact your local nVent representative.
Ambient operating temperature range–40°C to +60°C
Ambient storage temperature range–51°C to +60°C
Relative humidityMax. 95%, noncondensing
Supply voltage(Nominal) 115/230 Vac +10% -10%
50/60 Hz (jumper selectable)
Dimensions and mounting
Dimensions125 mm x 75 mm x 60 mm, see drawing
MountingDIN rail mountable
Digital input
Type2 wire digital input
Supplied powerMinimum power per DI connection supplied by RMM-DI module
12V 10mA (Sink/source)
Number of signals15 Digital inputs
Communication to RAYCHEM NGC control system
TypeRS-485
ProtocolModbus RTU
Cable typeShielded twisted pair
Length cable1200 m max.
Address switchSelectable on RMM-DI, address range: 1-255
Connection terminals
Supply (in-out)
RS-485 connection
DI connections
2
4 terminals for cables 0.2 mm
to 4 mm
2 x 3 terminals for cables 0.2 mm
15 x 2 terminals for cables 0.2 mm
2
2
to 2.5 mm
2
to 2.5 mm
2
2
Electromagnetic compatibility
EN 60730-1: 2011
EN 61000-6-3:2007+A1:2011 EN 61000-3-2:2006 +A1:2009+A2:2009
EN 61000-3-3:2008
EN 61000-6-2:2005
Ordering details
Part DescriptionRMM-DI
Product Number1244-016442
EAN5414506015560
30 | nVent.com
Page 31
nVent.com | 31
Page 32
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nvent.com