nvent JBS-100-EC Installation Instructions Manual

Page 1
WARNING:
CAUTION:
APPROVALS
Nonhazardous locations
C US
JBS-100-EC
Electronic Controller Replacement kit for JBS-100-ECP-A and JBS-100-ECW-A Installation Instructions
DESCRIPTION
The nVent RAYCHEM JBS-100-EC is a replacement kit that can be used to replace the electronic controller used in the JBS-100­ECP-A and the JBS-100-ECW-A.
For technical support call nVent at (800)545-6258.
TOOLS REQUIRED
• Large slotted screwdriver
• Small slotted screwdriver
KIT CONTENTS
Item Qty Description
A 1 JBS-100-EC board
• To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent, agency certifications, and the National Electrical Code, ground-fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers.
• Component approvals and performance are based on the use of nVent-specified parts only. Do not use substitute parts or vinyl electrical tape.
• The black heating cable core and fibers are conductive and can short. They must be properly insulated and kept dry.
• Damaged bus wires can overheat or short. Do not break bus wire strands when scoring the jacket or core.
• Keep components and heating cable ends dry before and during installation.
• Use only fire resistant insulation materials, such as fiberglass wrap or flame-retardant foam.
HEALTH HAZARD: Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly. Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettes or tobacco.
Consult MSDS RAY5510 for further information.
CHEMTREC 24-hour emergency telephone: (800) 424-9300
Non-emergency health and safety information:
(800) 545-6258
.
Page 2
1
WARNING: Shock Hazard
Before you begin dismantling your controller, turn
OFF THE power and lock out the circuit breaker.
• Remove the outer lid and the safety cover.
nVent.com
2
Wiring template
• Before disconnecting the wires, note their position on this template. You can then use this diagram for reference when rewiring.
• Disconnect all wires.
RTD Alarm
Power
Terminal Block
3 4
• Remove the screws and the PC board.
• Install the new PC board using the four copper screws.
Note: You may need to loosen or remove external fittings on the box to get the PC board out.
2 | nVent.com
Note: Once installed, tighten any external fittings.
Page 3
5
• Reconnect all wiring. Use the wiring diagrams below for reference.
Pipe Mounted Enclosures – JBS-100-ECP-A
Self-regulating heating cable Mineral Insulated heating cable
Heating cable ground
Self-regulating or
MI heating cable
RTD
Wall Mounted Enclosures – JBS-100-ECW-A
Heating cable using junction box
RTD
Power out
Ground
GLCB
Incoming
Power
Phase A
Phase B
GLCB
To Heater
Phase A Phase B Ground
Ground
MI heating cable
MI heating cable using direct connection
Optional
RTD
Alarm
Input
Contacts
MI heating cable
Power
Terminal
Block
RTD
RTD
Incoming
Power
Phase A
GLCB
Alarm
GLCB
Phase B
Ground
Phase A Phase B Ground
6
• Replace wire cover.
• Turn on power from ground-fault circuit breaker.
nVent.com | 3
Page 4
PROGRAMMING THE CONTROLLER
Reprogram controller using battery connection or turning power onto the unit.
7A
Powering Controller via Battery
• Connect 9 VDC battery (not provided) to the supplied
battery connector.
• Plug the battery connector onto the two pins on the controller marked “Battery Connector.”
9 Volt battery
7B
Powering Controller via Line Power
WARNING: Shock Hazard.
Secure the wire cover in place with the four screws
before proceeding.
• Turn on branch circuit breaker that supplies power to the controller and heating cable.
GFCB
Ø Ø
8
Activating and Navigating the Menu in Set-up Mode
• To activate set-up mode, press Menu button for
approximately 5 seconds.
• The display will change to the default mode for units.
• Use the Up and Down buttons to change values. Use the Next button to change to next display code/parameter.
• When completed, secure the enclosure cover.
4 | nVent.com
Menu
Up
Next
Down
Page 5
Parameters
The first parameter displayed during set-up mode is units (°F or °C). Other parameters, their default values, and minimum and maximum values are shown in the following table.
Alarms
The following table lists the error or alarm codes and their respective faults:
Display Code Parameter Default Min. Max.
1
2
Units
°F or °C
Maintain set point
°F
40°F 32°F (0°C) 425°F (218°C)
3 Deadband 5°F 1°F (1°C) 10°F (10°C)
4 High Alarm
5 Low Alarm
Note:
1. The minimum high temperature alarm set point must always be larger than the maintain set
point plus the deadband plus 5°F (3°C).
2. The maximum low temperature alarm set point must always be smaller than the maintain set
point minus the deadband.
1
2
Off 38°F (3°C) 482°F (250°C)
Off 20°F (–6°C) 420°F (216°C)
9
• Replace lid.
Alarm / Error Codes Fault
rtd Err Shorted or open RTD sensor
Hi Alr High Temperature Alarm
Lo Alr Low Temperature Alarm
nVent.com
nVent.com | 5
Page 6
North America
Tel +1.800.545.6258 Fax +1.800.527.5703
thermal.info@nvent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specications without notice.
Raychem-IM-H57564-JBS100EC-EN-1805 PN P000000302
Europe, Middle East, Africa
Tel +32.16.213.511 Fax +32.16.213.604
thermal.info@nvent.com
Asia Pacific
Tel +86.21.2412.1688 Fax +86.21.5426.3167
cn.thermal.info@nvent.com
Latin America
Tel +1.713.868.4800 Fax +1.713.868.2333
thermal.info@nvent.com
nVent.com
Loading...