nvent EC-TS Installation Instructions Manual

WARNING:
EC-TS
Ambient, Pipe or Slab Sensing Electronic Thermostat With 25 Foot Temperature Sensing Lead Installation Instructions
DESCRIPTION
The nVent RAYCHEM EC-TS electronic thermostat is an ambient, pipe, or slab sensing thermostat that is ideal for pipe freeze protection, flow maintenance, freezer frost heave and floor heating and snow melting applications. The EC-TS can be used to control a single heat-tracing circuit or as a pilot to control a contactor switching multiple heat-tracing circuits.
Thetemperature set point can be visually checked through the
cable status. The stainless steel sensor makes it an ideal
thermostat for applications that require an embedded sensor. The set point range for these thermostats is between 30°F
(–1°C) and 110°F (43°C). It operates at voltages between 100 to 277 Vac and switches current to 30 Amps.
For technical support call nVent at (800)545-6258.
APPROVALS
KIT CONTENTS
Item Qty Description
A 1 Lid B 1 Wire cover C 1 Box with electronics D 1 25 foot temperature sensor E 1 MI cable grounding kit (P000000279) F 1 Pipe support bracket (optional; 707366)
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions.
• To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent, agency certifications,
and the National Electrical Code, ground-fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers.
• Component approvals and performance are based on the use of nVent-specified parts only. Do not use substitute parts or vinyl electrical tape.
• The black heating cable core and fibers are conductive and can short. They must be
TOOLS REQUIRED
• Large slotted screwdriver • Needle nose pliers
• Small slotted screwdriver
ADDITIONAL MATERIALS REQUIRED
• Appropriate mounting fasteners
• MI cable grounding kit (for direct connection of Pyrotenax
heating cables) Catalog No: MI-GROUND-KIT
A
B
C
properly insulated and kept dry.
• Damaged bus wires can overheat or short. Do not break bus wire strands when scoring the jacket or core.
• Keep components and heating cable ends dry before and during installation.
• Use only fire resistant insulation materials, such as fiberglass wrap or flame-retardant foam.
D
E
F
1
• Attach enclosure to the wall using the appropriate mounting fasteners.
2A
Heating Cable using a Junction Box
Hole size
0.17 in (4.3 mm) x 4
Max. screw size 3/16 in (4.5 mm)
Connecting Heating Cable
• Insert the two power wires from the heating cable’s junction
box into the terminal block marked “To Heating Cable” and the ground (braid) marked “Earth” and tighten terminals. Confirm connection by pulling on the wires.
Remote
heating cable
Note: You must bring grounding wire from the MI junction box to the
controller for the ground-fault circuit breaker to work properly.
Mineral Insulated Heating Cable using a Direct Connection without a Separate Junction Box
2B
Heating cable ground (braid)
Note: To ensure the MI heating cable is properly grounded, all MI cables must be installed with a grounding kit, which is ordered separately (P000000279). Failure to use the grounding kit will void the warranty and can be a safety hazard by preventing normal operation of the ground fault circuit breaker.
• Insert the two heating cable wires into the terminal block marked “To Heating Cable” and the ground wire to “Earth” and tighten terminals. Confirm by pulling on the wires.
Junction
box
Power In
Line
Power In
Line
Power
Terminal
Block
To
Heating
Cable
Neutral
Line
Neutral
Line
Power
Terminal
Block
To
Heating
Cable
Neutral
Line
Neutral
Line
Earth
Line
Earth
Line
2 | nVent.com
MI heating cable
Lock washer Grounding strap Conduit hub
3
Connecting Incoming Power
• Pull in 8 to 14 AWG power and ground wires, strip off 1/2 in (3 mm) of insulation and terminate. Confirm by pulling
on the wires.
¹⁄2 in
4 5
Preparing Sensor
• Cut the sensor lead wire to length.
• Being careful not to cut the wires, strip 1-1/2 inches of outer jacket, trim off foil, to expose black white and non insulated drain wire (ground/shield).
Power
Terminal
Block
To
Power In
Heating
Cable
Earth
Line
Neutral
Line
Neutral
Line
Line
GFPD
Ground
Power in
• Strip off 1/4 inch of insulation from black and white
wires. Do not cut the wire strands.
1-¹⁄2 in
6A 6B
Placing Sensor: Ambient Application
• Remove cap and grommet. Slide grommet over
temperature sensor and onto shrink tubing. Tighten cap.
Grommet
Sensor
Shrink tubing
Cap
¹⁄4 in
Placing Sensor: Pipe/Slab Application
• Remove cap and compression grommet. Slide cable
through cap, grommet and through side entry hole.
Tighten cap.
Cap
Sensor
Grommet
nVent.com | 3
7
Connecting Sensor
• Insert the three sensor wires into the terminal block marked “Sensor Input.” Match the colors (White to W, Black to B), and tighten terminals. Confirm connection by
pulling on the wires.
Finished Wiring Diagram
8
• Install wire cover.
• Turn pointer to the desired set point.
• Install lid.
• Leave these instructions
Function LED color Description
Power Green When energized, indicates power to the controller Sensor Red When energized, indicates shorted or open sensor Htr On Green When energized, indicates power to the heating cable
with the end user for future reference.
Heating cable using a junction box
Input
Shield
Power In
Line
Power
Terminal
Block
To
Heating
Cable
Neutral
Line
Neutral
Line
Earth
Line
ShieldBW
White
Sensor
Black
Sensor
Sensor
Sensor
Input
ShieldBW
Shield
Black
White
MI heating cable using direct connection
Power
Terminal
Shield
Power In
Line
Block
Neutral
Line
To
Heating
Cable
Neutral
Line
Earth
Line
ShieldBW
Black
White
Self-regulating
heating cable
Heating cable ground (braid)
North America
Tel +1.800.545.6258 Fax +1.800.527.5703
thermal.info@nvent.com
Sensor
Junction box
Ground Power in
GFPD
Europe, Middle East, Africa
Tel +32.16.213.511 Fax +32.16.213.604
thermal.info@nvent.com
Grounding strap
Conduit hub
MI heating cable
Asia Pacific
Tel +86.21.2412.1688 Fax +86.21.5426.3167
cn.thermal.info@nvent.com
Ground Power in
GFPD
Latin America
Tel +1.713.868.4800 Fax +1.713.868.2333
thermal.info@nvent.com
nVent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specications without notice.
Raychem-IM-H57461-ECTS-EN-1805
Loading...