31 Working ranges ......................................................................................................................... 24
E. 13.11.06 • G. 21.09.11
2
1 General information
Installation of a gas-fired heating system must be performed in accordance with the applicable regulations
and guidelines. It is, therefore, the duty of the installation engineer to ensure that all regulations have been
read carefully and understood. Installation, start-up and maintenance must be performed with utmost care.
The burner must not be operated in rooms with high levels of air humidity (laundry rooms), dust or corrosive
vapours. The boiler room must be ventilated accordingly with ventilation air.
Nu-Way MG1310-2800 M3D Series gas burners are suitable for combustion of natural gas or liquid gas in
accordance with EN 437 and are in compliance with the EN 676 European standard.
2 Checking scope of delivery and electrical data
Before installing the Nu-Way gas burner, please check that all items included in the scope of delivery are
present.
Scope of delivery:
burner housing, gas jacket with burner pipe, mounting kit, documentation and gas train.
Gas installation and commissioning are subject to the applicable national regulations. The gas pipe must
be designed to conform to the flow rate and the available gas flow pressure and routed with the lowest pressure loss over the shortest distance to the burner.
The loss of gas pressure via the gas train and the burner and the resistance on the fuel gas side of the heat
generator must be less than the connection flow pressure.
Caution !
Observe sequence and throughflow direction of valves and fittings.
3 Maintenance and customer service
The complete system should be checked once a year for correct functioning and leaks by a representative
of the manufacturer or other suitably qualified person.
We accept no liability for consequential damage in cases of incorrect installation or repair, the fitting of nongenuine parts or where the equipment has been used for purposes for which it was not intended.
4 Operating instructions
The operating instructions together with this technical information leaflet must be displayed in a clearly visible position in the boiler room. The address of the nearest customer service centre must be displayed on
the back of the operating instructions.
5 Instruction of operating personnel
Faults are often caused by operator error. The operating personnel must be properly instructed in how the
burner works. In the event of recurring faults, Customer Service should be notified.
6 Filter/Strainer
According EN676 a filter/strainer shall be fitted at the inlet of the safety shut-off valve to prevent the ingress
of foreign elements.
E. 13.11.06 • G. 21.09.11
3
7 Key for code designation
MGN(L)1310
Burner output max.
Natural gas LL + E ="N", LPG = "L"
Series
All dimensions are given in mm
M12
Ø260
Ø328
8 Technical specifications
Burner type
Technical dataMG1310MG2100MG2500MG2800
Min. burner output in kW458533639793
Max. burner output in kW1340214825392800
Gas typefor natural gas LL + E = “-N” , LPG = „-L“
Method of operatingmodulating
Voltage3 / PE ~50 Hz 400 V / T 20 A
max. current consumption start/operatiopn 12 A max./
7.1 Aeff.
Electric motor power (at 2800min-1) in kW
Flame failure controller KLC1000
Control boxMPA 22
Air pressure monitorLGW50
Weight in kg110115120125
3.04.04.55.5
14.5 A max. /
10.2 A eff.
16.5 A max./
11.4 A eff.
22.5 A max./
15.5 A eff.
9 Boiler connection dimensions
4
E. 13.11.06 • G. 21.09.11
10 Mounting the gas jacket on the boiler
Air pressure connection
B
Use adhesive to affix the gas-jacket gasket to the
gas jacket.
The boiler connection plate has to be prepared in accordance with the sizes as stated in „9. Boiler connection dimensions“. You can use the gas-jacket gasket as
a template.
Using an 8 mm socket-head wrench, secure the gas
jacket to the boiler with the 4 M 10 fastening screws
and washers. The air pressure connection for the gas
train must be positioned at the top.
11 Mounting the burner housing on the gas jacket (service position)
Position the burner housing in the gas-jacket hinge
and secure it with a rod. The burner is now in the service position.
12 Electrical connection
Make sure that the gasket is correctly seated
between the gas jacket and the burner housing.
Swing the burner closed and insert the second securing rod into the hinge. Tighten the screw at the top to
secure the burner in position.
Always set the main switch to "Off" and remove
the fuse before connecting the cables or removing
electrical components.
The burner must be connected to the electricity supply
in accordance with the wiring diagram. This wok must
be performed by trained, qualified electricians. The
supply cable to the burner must be of the flexible type.
E. 13.11.06 • G. 21.09.11
5
See Circuit diagram
Cover
1
1
The cover has to be removed and set to the service position in order to permit access to the control unit. Remove the securing screws (1) and fold the cover down
to the left.
Modulating operation
IMPORTANT !
The coding plug X85 with jack X86 must be connected
during two-stage operation (as-delivered condition, see
Fig.).
Once the connection to the electricity supply has been
established, check the wiring and briefly actuate the motor contactor with an electrician's insulated screwdriver
to check the direction of rotation of the burner motor.
The direction of rotation is correct if the fan turns toward
the boiler (see the arrow on the motor flange).
IMPORTANT !
The motor protective relay is set ex-works. The set value
should not be incorrectly adjusted.
E. 13.11.06 • G. 21.09.11
6
13 Air flap positioning motor
14 Air pressure switch
The air flap positioning motor is designed for air flap adjustment on progressive two-stage burners or modulating
burners. The motor is activated electronically via the
microprocessor-controlled control box.
Do not open the air flap positioning motor. The optics
can become damaged irreparably. No warranty will be
given if the seal is broken.
The air pressure switch is a differential pressure switch
and monitors pressure at the forced-air burner.
The air pressure switch is preset at the factory.
15 Gas pressure switch for gas inlet pressure
The gas pressure switch on the gas train serves to monitor the gas inlet pressure. The burner is shut down
if the gas inlet pressure drops below the set minimum value (preset at factory). The burner starts up automatically again when the minimum pressure is exceeded.
16 Gas pressure switch for VPS
The gas pressure switch for VPS is preset to 10 mbar at the factory.
The operating point of the gas pressure switch for VPS must be set to half the inlet flow
pressure.
E. 13.11.06 • G. 21.09.11
7
17 Adjustment of the ignition electrodes
ca. 3 - 4
ca. 5
The ignition electrodes are preset at the factory.
18 Flame control with KLC1000
Operating Indicator LED:
LED is OFF: KLC is not switched on – no power supply
or ‘no flame’ is detected.
LED is FLASHING: KLC has detected a flame; the qual-
ity of the flame signal is indicated by the intensity of the
flashing of the LED – fast flashing indicates a healthy
flame signal and vice versa - slow flashing indicates a
weak flame signal.
LED is ON: KLC has detected the strongest level of
flame signal.
Commissioning and maintenance
The installation and commissioning must be done by qualified personnel only. Before energising the KLC
flame detector please check the cable and wiring connections are in accordance to the diagram and instructions given above. For good maintenance which will ensure trouble free operation of the KLC flame
detector; please keep the sight glass clean by wiping with a soft dry clean cloth. Warning: Do not use any
kind of cleaning sprays or fluids. During commissioning and after any cleaning maintenance, the flame detector should be checked, as the UV tube is subject to a natural ageing process and towards the end of its
life span it is prone to malfunction.
To check that the flame detector is sound we recommend the following procedures be followed:
•Start the burner with the fuel supply closed-off or remove the flame detector from its mounting flange
and cover the UV tube using a soft cloth to avoid touching the glass lens. The control box will lock-out
at the end of the safety time due to absence of a flame signal.
•Remove the flame detector from its mounting flange. Start the burner while exposing the flame detector to an external UV radiation source such as a cigarette lighter flame, or a small gas flame (n.b. electric room lighting or a torch is inadequate). The burner Control Box must go to lock-out due to
detecting an extraneous light source either immediately or at the end of the air pre-purge cycle,
depending on the type/model of the Control Box.
•Close off the fuel supply or remove flame detector from its mounting flange and cover the UV tube
using a soft cloth when the burner is in the "run" position. The control box must go immediately to
lock-out resulting in the burner shutting down.
If any of these safety checks do not function as described i.e. they should always result in burner shutdown
and control box lock-out; then it is essential to replace the flame detector with a new KLC flame detector.
For safety and trouble free burner operation, we recommend that the flame detector should be replaced
after every 10,000 hours of burner operation or approximately every 30months for a burner operating on
an average of 10 hours per day.
E. 13.11.06 • G. 21.09.11
8
19 Control unit MPA 22
Enter or Reset key
Key 1
Activation of gas valve
in combination
with +/- key
Key 2
Activation of air valve
in combination
with +/- key
Key + / Key -
Start-up comes on
during start-up, off when
burner is in operation
comes on when
is active
information mode
comes on when
adjustment mode
is active
comes on when
gas flap is active
symbol for
opening /
closing flaps
comes on when
air flap
is active
Visual
LC
h = service hours indicator
l, m3 = oil or gas consumption
comes on when service mode
is active
Fault
Operation, flame present
20 MPA 22 control unit display
The MPA 22 is a microprocessor-controlled intermittentduty control box for controlling and monitoring pneumatic
modulating forced-air burners with an actuator drive. For
operation as an automatic gas burner control with integral
valve proving system.
The MPA 22 has e-BUS connectivity.
21 Start-up
The burner can be put into operation once the gas and electrical installation and assembly work has been
completed.
•Check the connections on the gas train.
•Prepare the flue-gas analyser.
•Start the burner.
•Adjustment of air surplus and output. See 22. Gas train KEV
•Record the setting data.
•Check the gas pressure monitor after start-up. To do so, close ball valve slowly. The burner must shut
down, but must not go into fault mode. If the burner goes into fault mode, increase the setting on the
gas pressure monitor.
E. 13.11.06 • G. 21.09.11
9
1 ½" , KEV 2" and KEV DN65.
II
22 Gas train
Gas pressure switch
SKP 15
VGD
Pulse line p
G
SKP 75
"AIR" air pressure connection
(gas inlet pressure)
Gas pressure switch
for leak check
Installing the gas train
Installation position only in horizontal line, not tilted.
Minimum distance to walling 20 mm
Screw the combustion chamber pressure measuring nipple into the gas jacket at the top (see "10 Mounting the gas jacket on
the boiler").
Route the connecting hose between the measuring nipple for combustion chamber pressure and the gas train in a loose loop.
Screw each air pressure measuring nipple into the top of the gas jacket (see 10. Mounting the gas jacket
on the boiler).
Connect the blue hose to the "AIR" connection on the gas train and the air pressure connection on the gas
jacket. The blue hose serves as a control line for the gas train and must be routed in a loose loop without
kinking.
Remove the plate for covering the adjustment screws from the gas pressure regulator.
Start the burner.
1. Setting the air surplus in high and low-load operation
•Set the air flap positions P9 for high-load operation and P1 for low-load operation as specified in
27. Adjustment tables. Follow the setting procedure described in 25. Adjustment mode - pneumatic
gas-fired operation with MPA 22 display.
•In high-load operation, set the air surplus with the "large flame" adjustment screw on the gas pressure
regulator. The CO2 level in the flue gas should be 9-10% for natural gas.
•In low-load operation, set the air surplus with the "small flame" adjustment screw on the gas pressure
regulator. The CO2 level in the flue gas should be 9-10% for natural gas. The low-load setting influences the high-load setting.
•In high-load operation, check the air surplus and, if necessary, correct the setting with the "large
flame" adjustment screw on the gas pressure regulator.
2. Setting the output in high and low-load operation
•Check the high-load setting via the gas flow at the gas meter or compare the nozzle pressure with the
values stated in 27. Adjustment tables. The output can be increased by opening the air flap (to
increase P9) and reduced by closing the air flap (to reduce P9). The air surplus is not affected by this
adjustment.
•Check the low-load setting via the gas flow at the gas meter or compare the nozzle pressure with the
values stated in 27. Adjustment tables. The output can be increased by opening the air flap (increase
P1) and reduced by closing the air flap (reduce P1). The air surplus is not affected by this adjustment.
To enter this adjustment mode, the burner must be on standby.
Standby means that the burner is connected to the power supply, but no hea-
ting request has been issued. If OFF appears on the display on MPA 22,
the unit is running in standby mode and has already been configured.
If OFFUPr appears on the display, the MPA 22 is also running in standby mode,
but the unit is still unprogrammed and all setting parameters still have to be entered by the following procedure.
Important: If the setting operation is interrupted within 30 min. or not completed correctly, OFFUPr will also be displayed.
To change new setting parameters or old setting parameters, follow these
steps:
Step 1:
Enter the safety code. Press key 1 and key 2 simultaneously
Step 2:
7 horizontal bars are now displayed. Enter the password as follows.
Note:
The intervals between the individual inputs must not be longer than 20 sec., as
the MPA 22 will otherwise revert to standby mode. If this is the case, you will
have to start the code entry procedure from the beginning again.
- Press the minus key twice.
- Confirm your entry by pressing key 2 once.
- Press the minus key once.
- Confirm your entry by pressing key 2 twice.
- Press the plus key 4 x.
- Confirm your entry by pressing key 2 once.
- Press the plus key twice.
- Confirm your entry by pressing key 2 once.
- Press the plus key 3 x.
- Confirm your entry by pressing key 2 once.
- Press the minus key 4x.
- Press the enter key once.
Password entry is now finished.
Step 3:
after the correct password has been entered, EGAS Pn appears on the display.
Step 4:
the operating points P9 (max load), P1 (min load) and P0 (starting point)
can now be selected by pressing the plus or minus key.
E. 13.11.06 • G. 21.09.11
Step 5:
After the operating point P9 is selected, 9GAS appears on the display. The max
load operating point can be adjusted to values between 0° and 90 ° by holding
down key 2 and optionally pressing the plus or minus key.
For basic setting values, please refer to the adjustment table.
11
or
2
and
or
2
and
1GAS
P
L/A
0GAS
P
L/A
GAS Pn
P
or
2
and
0GAS
P
L/A
or
1GAS
P
L/A
or
2
and
or
or
2
and
9GAS
P
L/A
1
2
and
Step 6:
After you have set P9, press the plus key to set P1. 1Gas appears on the dis-
play.
The min load operating point can be adjusted to values between 0° and 90 ° by
holding down key 2 and optionally pressing the plus or minus key.
For basic setting values, please refer to the adjustment table.
Step 7:
After you have set P1, press the plus key to set P0 (the starting point). 0 Gas
appears on the display.
The operating point (starting point) can now be set to a value between
0° and 90° by holding down key 2 and optionally pressing the plus or minuskey. The value of P1 should preferably be set. If P1, (min. load) is set to a very
low value, it is recommended to set P0 to a higher value than P1 in order to
ensure stable starting.
For basic setting values, please refer to the adjustment table.
Step 8:
After you have set P0, press the plus key.
GAS Pn. appears on the display.
Now close the safety chain and issue a heating request.
The burner should now start up and dwell in the ignition position. If this is not
the case, please repeat the procedure for adjustment of ignition point P0 understep 7.
After the burner has started up, the gas train must be set to the nozzle pressure
specified in the adjustment table.
Step 9:
The setting values are now adjusted in relation to the boiler and the required
burner output. The burner is in operation throughout the adjustment procedure
so that all boilers and measured data relevant to the burner can be recorded.
Adjust the operating points in the order P0,P1 and P9 and make adjustments
by simultaneously pressing key 2 and the plus or minus key. To switch the
burner to normal operation, press key 1 and key 2 simultaneously for approximately 2 sec. The burner switches to min output P1 and then returns to normal
operation.
The setting procedure is now completed.
Note:
If you want to change values after finishing the setting procedure, you will have
to start from the beginning again.
E. 13.11.06 • G. 21.09.11
12
24 Calculation principles for gas burner adjustment
V
n
Q
n
η
k
H
×
i n,
--------------------
220kW
0 92 10×4
kWh
m
3
-----------
,,
----------------------------------------=23
m
3
h
------
==
V
B
V
n
f
------
23
m
3
h
------
0 94,
-------------=24
m
3
h
------
==
f
B P
G
+
1013
--------------
273
273 ϑ
G
+
--------------------
×=
The values given in the tables are setting values for start-up.
The necessary system adjustment must be newly determined in each case.
General:
the calorific value (H
Natural gas type EH
Natural gas type LLH
Gas counters measure the volume of gas in the operational state.
Gas flow determination:
To allow the heat generator load to be adjusted correctly, the gas flow rate must be determined in advance.
Example:
Altitude above seal level230 m
Barometric air pressure B (acc. to table)989 mbar
Gas pressure PG at counter20 mbar
Gas temperature
Boiler output Q
Efficiency η
n
(assumed)92%
K
Calorific value H
) of fuel gases is generally specified for the normal state (0°C, 1013 mbar).
i,n
= 10.4 kWh/m
i,n
= 9.3 kWh/m
i,n
ϑ
G
16°C
3
3
220 kW
i,n
10.4 kWh/m
3
Gas flow in standard state (Vn)
Gas flow in operating state (V B)
Conversion factor (f)
Annual average air pressure
Average geodetic altitude of the
supply region above sea level [m]
Annual average of air pressure (mbar) 1016 1013 1007 1001 995 989 983 977 971 965 959 953 947 942 936 930
Burner motor does not start upElectric supply lead faultyRectify faults in electrical installation
Fuse faultyReplace
Safety thermostat lockedUnlock42 h
Burner starts up and switches to fault mode before or
after expiry of safety period
Temperature of controller setting is
exceeded
MPA 22 faultyReplace04 h
Leak Rectify leak44H / 43H
No gasSafeguard gas supply
Gas pressure monitor faultyReplace gas train22 h
Filter in gas train dirtyClean or replace
Air pressure switch not in idle positionCheck air pressure switch (see page 7)20 h
Burner motor faultyReplace
No load at terminal 5Check plug connection and current path of
Mains voltage <
Air pressure monitor does not switch
through during pre-ventilation
Ignition influencing of ionization monitor See Page 826 h
Gas solenoid valve does not openReplace gas train
Starting gas quantity set too lowIncrease starting gas quantity
No ignitionCheck ignition electrode and setting, igni-
187 V
Renewed start attempt after temperature
drop
solenoid valve
Rectify faults in electrical
installation
See Page 721 h
tion transformer and cable
Flame extinguishes
during operation
Phase and zero mixed upConnect connector unit in correct phase
sequence
Flame control faultyCheck according to Page 82BH
Air pressure switch opens during operation
Gas nozzle dirty or faultyReplace gas nozzle
No gasSafeguard gas supply
Filter in gas train
dirty
Flame blow-offIncorrect burner setting27 h
Air pressure monitor contact opensCheck/replace air pressure switch 21 h
Flame signal too weakMeasure flame signal, check ionisation
See Page 721 h
Clean or replace
27 h
electrode
16
E. 13.11.06 • G. 21.09.11
Service mode - pneumatic gas-fired operation
Adjustment point
Adjustment values
Service mode symbol
display value
Adjustment point information mode symbol
The service mode serves to display the set parameters and to read out the fault memory. It can be invoked
in any operating state of the burner.
Important:
setting values cannot be changed in service mode. If no key is pressed for longer than 20 sec., the
display returns to standby mode.
To access the service mode, press the enter key for approx. 2 sec.
The following now appear on the display: point P0 and the air flap posi-
tioning motor setting value at ignition in angular degrees, plus a wrench
symbol denoting the service mode.
The following points can be retrieved by repeatedly pressing the enter
key:
- The characteristic curves for points P0, P1 and P9
- The last 6 fault messages P10 to P15 (see fault code MPA)
- The testing times of the valve proving system P16 and P17
- The flame quality P18
- The eBus address of the MPA P19
- The switch setting of the valve proving system P21
- The eBus address of the external controller P24
- The modulation delay
- The set start points P26
To exit the service mode, please press the enter key or wait approx.
20 sec.
Information mode
The information mode is intended for display of consumption figures, operating hours and software data.
To access information mode, press the enter key for approx. 0.5 sec.
A zero and a value appear on the display.
The following values can be queried in information mode under setting
points 0 to 8. Retrieve by repeatedly pressing the enter key:
Important:
If no key is pressed for longer than 20 sec., the display returns to
normal operating mode.
0 = fuel consumption
1 = total operating hours
2 = for oil only
3 = for oil only
4 = number of successful startups
5 = display of software version
6 = software creation date
7 = hardware number
8 = date of production
E. 13.11.06 • G. 21.09.11
17
Troubleshooting the MPA
CodeDescription
04 hInternal hardware fault
05 hInternal hardware fault
06 hInternal hardware fault
07 hInternal hardware fault
09 hInternal hardware fault
10 hInternal hardware fault
11 hInternal hardware fault
12 hInternal hardware fault
13 hInternal hardware fault
14 hInternal hardware fault
15 hInternal hardware fault
20 hAir pressure switch is not in idle position
21 hFailure of air pressure switch
22 hFailure of gas pressure monitor
25 hNo flame after safety period
26 hOutside light
27 hFlame failure during operation
29 hInternal hardware fault
2AHInternal hardware fault
2BHShort-circuit in photo resistor or internal fault
2CHInternal hardware fault
30 hInternal hardware fault
31 hInternal hardware fault
32 hInternal hardware fault
33 hInternal hardware fault
34 hInternal hardware fault
42 hSafety chain interrupted
43 hY3 found to be leaking during leak check
44 hY3 found to be leaking during leak check
45 hInternal hardware fault
46 hInternal hardware fault
47 hInternal hardware fault
48 hInternal hardware fault
4AHInternal hardware fault
5BHInternal hardware fault
4CHInternal hardware fault
4DHInternal hardware fault
4EHInternal hardware fault
50 hInternal hardware fault
51 hInternal hardware fault
52 hInternal hardware fault
53 hInternal hardware fault
54 hInternal hardware fault
55 hInternal hardware fault
56 hInternal hardware fault
57 hInternal hardware fault
58 hInternal hardware fault
59 hInternal hardware fault
18
E. 13.11.06 • G. 21.09.11
CodeDescription
5AHInternal hardware fault
5CHInternal hardware fault
5DHInternal hardware fault
5EHInternal hardware fault
63 hInternal hardware fault
64 hInternal hardware fault
65 hInternal hardware fault
67 hInternal hardware fault
68 hIncorrect feedback from air flap positioning drive
(check connector and cable, actuator drive mounting and air flap mechanism)
6AHAir-flap actuator position is out of tolerance
(check connector and cable, actuator drive mounting and air flap mechanism)
6CHInternal hardware fault
6DHInternal hardware fault
6EHActuator drive interchanged or incorrectly connected
6FHBurner detection error
70 hInternal hardware fault
71 hInternal hardware fault
73 hInternal hardware fault
74 hInternal hardware fault
75 hInternal hardware fault
76 hInternal hardware fault
77 hInternal hardware fault
78 hInternal hardware fault
79 hInternal hardware fault
Process description
Startup testsProcessor and program memory test / move actuator drives to reference position
State 01Startup decision (heating request present)
State 02Blower idle state check
State 03Blower startup
State 04Preventilation / operation of gas flap actuator over speed range
State 05Preventilation / activate and test watchdog
State 06Preventilation / move gas flap actuator to ignition position
State 07Move air flap actuator to ignition position
State 08Pre-ignition depending on parameters
State 09Startup safety period
State 10Stabilisation period
State 11Move positioning drive from ignition point to operating characteristic
State 12Operation
State 13VPS - evacuate valve cavity / (post-ventilate)
State 14Test duration Y2 / (remaining post-ventilation time)
State 15VPS - fill valve cavity / (remaining post-ventilation time)
State 16Test duration Y3 / (remaining post-ventilation time)
State 17Remaining post-ventilation time
State 18Restart disable time / waiting loop for low gas program
State 20Standby position
E. 13.11.06 • G. 21.09.11
19
27 Adjustments log
Please enter the measured values into the Adjustments log.
Boiler typeGas fitting
Measured valuesmin.max.Date
P0 (start point)
P1 (min load)
P9 (max load)
Flue gas temperature°C
Carbon dioxide (CO2 level) %
O2 content%
CO level%
Fluembar
Nozzle pressurembar
Boiler pressurembar
Room temperature°C
Gas type
Setting value V at the fitting
Setting value N at the fitting
20
E. 13.11.06 • G. 21.09.11
28 Explosion drawing
ZBZ 2-170.1
E. 13.11.06 • G. 21.09.11
21
29 Spare parts list
PositionBenennungVEArt. Nr.
1Burner tube MG1310, MG2100147-90-12833
1Burner tube MG2500, MG2800147-90-12834
1Burner tube extended by 200 mm for MG1310, MG2100147-90-21894
1Burner tube extended by 200 mm for MG2500, MG2800147-90-21933
2Flow plate ∅190 for MG 1310147-90-12830
2Flow plate ∅178 for MG 2100147-90-12831
2Flow plate ∅204 for MG2500, MG2800147-90-12832
3Gas nozzle- N147-90-12827
3Gas nozzle - N for MG2800147-90-22848
3Gas nozzle- F147-90-25308
4Ignition electrode136-90-10127
5Ignition cable 247-50-25003
5Ignition cable extended by 200 mm247-50-25482
6Gas nozzle elbar147-90-12829
7Gasket for gas nozzle547-50-12791
8Gas nozzle completet with electrode (Natural gas) for MG1310146-90-12846
8Gas nozzle completet with electrode (Natural gas) for MG2100146-90-12847
8Gas nozzle completet with electrode (Natural gas) for MG2500146-90-12790
8Gas nozzle completet with electrode (Natural gas) for MG2800146-90-22851
8Gas nozzle completet with electrode extended by 200 mm (Natural gas) for MG1310146-90-21895
8Gas nozzle completet with electrode extended by 200 mm (Natural gas) for MG2100146-90-21938
8Gas nozzle completet with electrode extended by 200 mm (Natural gas) for MG2500146-90-12975
8Gas nozzle completet with electrode extended by 200 mm (Natural gas) for MG2800146-90-22921
8Gas nozzle completet with electrode (LPG) for MG1310147-90-22895
8Gas nozzle completet with electrode (LPG) for MG2100147-90-26152
8Gas nozzle completet with electrode (LPG) for MG2500147-90-26794
8Gas nozzle completet with electrode (LPG) for MG2800147-90-26794
8Gas nozzle completet with electrode extended by 200 mm (LPG) for MG1310147-90-26795
8Gas nozzle completet with electrode extended by 200 mm (LPG) for MG2100147-90-26796
8Gas nozzle completet with electrode extended by 200 mm (LPG) for MG2500147-90-26797
8Gas nozzle completet with electrode extended by 200 mm (LPG) for MG2800147-90-26797
9Sealing ring for cover147-90-12982
10Actuator drive SAD 1.5 complete147-90-26383
11Air flap complete147-90-24464
12Cover for sight glas547-50-12106
13Cover147-90-24999
14Sight glas136-90-11544
15Holder for KLC147-90-20434
16Flame detector KLC1000147-90-27184
17Electronic Transformer147-90-26790
18Fan wheel ∅ 280 x 80 for MG1310147-90-22579
18Fan whee ∅ 280 x 100 for MG2100147-90-22580
18Fan whee ∅ 280 x 110 for MG2500147-90-22881
18Fan whee ∅ 290 x 114 for MG2800147-90-22850
193 kW motor for MG1310147-90-12802
194 kW moto for MG2100147-90-12803
194,5 kW motor for MG2500147-90-12804
195,5 kW motor for MG2800147-90-22876
203 kW motor complete with fan wheel for MG1310147-90-26791
204 kW motor complete with fan wheel for MG2100147-90-26798
204,5 kW motor complete with fan wheel for MG2500147-90-26800
205,5 kW motor complete with fan wheel for MG2800147-90-26801
214-pole female connector, green137-90-20744
227-pole female connector, black/brown137-90-20731
23Control box MPA 22147-90-24166
24Star-delta starter YKB7-30 147-90-25176
25Thermal relay 2,4 - 4,0 A (Star-delta) for MG1310147-90-24172
25Thermal relay 4,0 - 6,0 A (Star-delta) for MG2100, MG2500147-90-25173
25Thermal relay 6,0 - 9,0 A (Star-delta) for MG2800147-90-25174
267-pole female connector, green137-90-10831
273-pole female connector, black137-90-20739
28Terminal box cover147-90-25206
29MPA display AM07147-90-24167
30Facing panel147-90-24887
31/33/35Gasket completet147-90-26792
32Gas jacket part 2, completet147-90-12771
34Gas jacket part 1, completet147-90-12770
36Securing rod246-50-12809
37Differerntial 147-90-26723
40Thermal relay (overload) 6,0 - 9,0 A for MG1310147-90-25174
40Thermal relay (overrload)9,0 - 12,0 A for MG2100, MG2500, MG2800147-90-25175
41Motor contactor B7-30-10147-90-25171
-Fan inlet device147-90-12785
-Protective screen146-90-12992
22
E. 13.11.06 • G. 21.09.11
E.13.11.06•G.21.09.11
23
Enertech Limited,
P O Box 1,
Vines Lane
Droitwich,
Worcestershire,
WR9 8NA