nuway NDF 100 User guide

Page 1
Installation & Maintenance Manual
NDF 35 - 100
Dual Fuel Burner
Tel: +44 (0) 1905 794331 Fax: +44 (0) 1905 794017 Email: [email protected] Web: www.nu-way.co.uk
Page 2
CONTENTS
BURNER AND COMPONENT IDENTIFICATION FOR NDF MODULATING BURNER ............................ 4
BURNER AND COMPONENT IDENTIFICATION FOR NDF TWO STAGE (HIGH/LOW) BURNER ............ 6
INTRODUCTION .............................................................................................................. 9
FEATURES ...................................................................................................................... 9
Burner Capacity .............................................................................................................................. 9
Fuel ................................................................................................................................................. 9
Air Fan Size ................................................................................................................................... 10
Controls and Safety Systems .......................................................................................................... 10
Operating Mode ............................................................................................................................ 10
Burner Type Nomenclature............................................................................................................10
SITE CONDITIONS AND SERVICES ..................................................................................... 10
Flue and Chimney Requirements ...................................................................................................10
Plant Room Ventilation .................................................................................................................. 11
Existing Appliances ........................................................................................................................ 11
Combustion Chamber Conditions .................................................................................................. 11
Gas Supply ....................................................................................................................................11
Gas Boosters..................................................................................................................................11
Oil Supply .....................................................................................................................................13
Electrical Power Supply.................................................................................................................. 13
UNPACKING AND ASSEMBLY ............................................................................................ 13
INSTALLATION ............................................................................................................... 16
BURNER CONTROL AND OPERATION................................................................................. 17
Air Controls ...................................................................................................................................17
Gas Controls .................................................................................................................................. 17
Oil Controls - Twin Pressure Jet Oil Burners ................................................................................... 25
Oil Controls - Single Spill Back Nozzle Oil Burners. ....................................................................... 26
Control Panel ................................................................................................................................ 29
Burner Controller .......................................................................................................................... 36
Flame Monitor............................................................................................................................... 36
Modulating Controller ................................................................................................................... 36
BURNER OPERATING SEQUENCE ....................................................................................... 37
MODULATING CONTROLS ............................................................................................... 38
Controller ...................................................................................................................................... 38
Commissioning Controls. ............................................................................................................... 38
Temperature Detector. ................................................................................................................... 38
Pressure Detector. ......................................................................................................................... 38
General. ........................................................................................................................................38
COMMISSIONING : GENERAL ........................................................................................... 39
Safety And Emergency Notices ..................................................................................................... 39
Inspection ..................................................................................................................................... 39
Initial Settings ................................................................................................................................ 40
COMMISSIONING : OIL .................................................................................................. 40
Burner Dry Run - Twin Pressure Jet Burners (NDFL35-25 to 100-38 Two Stage (High/Low)) ............ 40
Burner Live Run - Twin Pressure Jet Burners (NDFL35-25 to 100-38 Two Stage (High/Low)) ........... 41
Burner Dry Run - Single Spill Back Burners (NDFL Modulating / NDFR - All Models) ...................... 41
Burner Live Run - Single Spill Back Burners (NDFL Modulating / NDFR - All Models) ..................... 42
COMMISSIONING : GAS ................................................................................................. 45
Burner Dry Run - NDFL/R All Models ............................................................................................ 45
Page 3
Burner Live Run - NDFL/R All Models ........................................................................................... 46
FINAL COMMISSIONING STAGES - OIL AND GAS ................................................................. 48
Checking the Flame Signal ............................................................................................................. 48
Setting the Air Pressure Switch ....................................................................................................... 48
Modulating Control : Landis & Staefa RWF32 ................................................................................ 49
Final Checks .................................................................................................................................. 50
On Completing Commissioning .....................................................................................................50
FUEL CHANGEOVER PROCEDURE ....................................................................................... 50
Switching From Gas To Oil............................................................................................................. 50
Switching From Oil To Gas............................................................................................................. 51
ROUTINE SAFETY CHECKS ............................................................................................... 51
Combustion Air ............................................................................................................................. 51
Flame Detector .............................................................................................................................51
Valve Proving System (If Fitted) ...................................................................................................... 51
ROUTINE MAINTENANCE................................................................................................. 51
Combustion Air Fan - All Models ................................................................................................... 51
Replacing the Air/Gas Ratio Controller - All Models ........................................................................ 51
Burner Inner Assembly - Twin Pressure Jet Burners ......................................................................... 52
Burner Inner Assembly - Single Spill Back Burners .......................................................................... 52
Oil Filters....................................................................................................................................... 52
Oil Preheater - NDFR Only............................................................................................................ 52
FAULT FINDING ............................................................................................................ 52
Burner Motor Fails To Start............................................................................................................. 53
Fan Starts And Burner Goes To Lockout ......................................................................................... 53
Start Flame Failure ......................................................................................................................... 54
Incorrect Rotation Of Burner Motor ............................................................................................... 54
Main Flame Is Not Established ....................................................................................................... 54
Burner Motor Only Runs Continuously .......................................................................................... 54
SPARE PARTS ................................................................................................................ 54
APPENDIX .................................................................................................................... 55
Burner Head Details ...................................................................................................................... 56
Electrode Setting Detail ................................................................................................................. 58
Performance Envelopes................................................................................................................. 59
Oil Commissioning Sheet............................................................................................................... 62
Gas Commisioning Sheet ............................................................................................................... 63
BURNER SERVICE RECORD ............................................................................................... 64
NOTES ....................................................................................................................... 66
IMPORTANT - SAFETY
It is essential that the following instructions and adjustments are carried out by qualified engineers that are experienced in forced draught gas and pressure jet oil burner commissioning. In the UK it is a legal requirement that these engineers must also be CORGI registered. Nu-way cannot be held responsible for any consequential damage, loss or personal injury as a result of customers failing to follow these instructions, or as a result of misuse. Your attention is drawn to the Emergency Instructions on Page 39.
EUROPEAN BOILER EFFICIENCY DIRECTIVE (B.E.D.)
All burners and boiler bodies marked separately should comply with EN267 (oil burners) or EN676 (gas burners) and EN303-1 (boiler bodies).
Burner adjustments must be made in accordance with boiler manufacturersí instructions, and these must include the flue gas temperature, average water temperature and CO2 or O2 concentration.
Models NDF35 to NDF150
Page 3
Page 4
BURNER AND COMPONENT IDENTIFICATION FOR NDF MODULATING BURNER (MODEL NDF125 SHOWN)
Page 5
Models NDF35 to NDF150
Page 5
Page 6
BURNER AND COMPONENT IDENTIFICATION FOR NDF TWO STAGE (HIGH/ LOW) BURNER (MODEL NDF35 SHOWN)
Page 7
Models NDF35 to NDF150
Page 7
Page 8
BURNER DIMENSIONS
g
)
Twin Pressure Jet Oil Nozzle Burners
NDFL35-25 to NDFL100-38 Two Stage (Hi/Lo)
Model
NDFL35-25 885 540 165 410 305 686 280 NDFL35-34 1069 540 165 410 305 686 330 NDFL35-38 1081 540 165 410 305 686 330 NDFL50-28 1069 540 165 410 305 800 370 NDFL50-34 1069 540 165 410 305 800 370 NDFL50-38 1081 540 165 410 305 800 370 NDFL60-28 1069 540 165 410 305 800 360 NDFL60-34 1069 540 165 410 305 800 360 NDFL60-38 1081 540 165 410 305 800 360 NDFL80-28 1069 920 165 550 385 1196 360 NDFL80-34 1069 920 165 550 385 1196 360 NDFL85-38 1081 920 165 550 385 1196 360 NDFL100-38 1081 920 165 550 385 1196 372
ABCDE FG
Dimension (All mm)
Single Spill Back Oil Nozzle Burners
NDFR35 to NDFR 150 Two Stage (Sliding Hi/Lo) & Modulatin NDFL100-41 to NDFL150-44 Two Stage (Sliding Hi/Lo
Model
NDF35-25 810 540 280 410 305 686 210 NDF35-34 967 540 300 410 305 686 260 NDF35-38 1014 540 300 410 305 686 260 NDF50-28 967 540 300 410 305 800 260 NDF50-34 967 540 300 410 305 800 260 NDF50-38 1014 540 300 410 305 800 260 NDF60-28 967 540 300 410 305 800 260 NDF60-34 967 540 300 410 305 800 260 NDF60-38 1014 540 300 410 305 800 260 NDF80-28 967 920 300 550 385 1196 260 NDF80-34 967 920 300 550 385 1196 260 NDF85-38 1014 920 300 550 385 1196 260 NDF100-38 1014 920 300 550 385 1196 260 NDF100-41 1240 920 345 580 416 1196 440 NDF100-44 1240 920 345 580 416 1196 440 NDF125-36 1240 920 345 580 416 1196 440 NDF125-41 1240 920 345 580 416 1196 440 NDF125-44 1240 920 345 580 416 1196 440 NDF150-36 1240 920 345 580 416 1210 440 NDF150-41 1240 920 345 580 416 1210 440 NDF150-44 1240 920 345 580 416 1210 440
ABCDE FG
Dimension (All mm)
Page 9
BURNER MOUNTING ARRANGEMENT
INTRODUCTION
This manual has been produced to enable users to install, commission and use NDF burners safely and efficiently. At each stage, the conditions that should be met and the adjustments and other actions that should be carried out are detailed and the loca­tions of the various components and adjustment mechanisms are identified. Where appropriate, this information is supported by tables and graphs. Lit­erature on the proprietary components used in NDF burner systems is available on request.
FEATURES
Developed through extensive field experience in the UK and overseas markets, the NDF series of dual fuel burners meets all current test authority requirements in these markets and sets new stand­ards in efficient and reliable operation.
NDF burners are designed for flange mounting to the appliance front plate and they are delivered ready to install with a pre-wired packaged control system and plug-in gas train.
Burner Capacity
The figures quoted are nominal burner outputs based on the gross calorific value.
Burner Model Capacity (kW)
NDF35 583 - 1019 NDF50 1000 - 1500 NDF60 1500 - 1850 NDF80 1640 - 2360
NDF85 1840 - 2450 NDF100 1800 - 3000 NDF125 2950 - 3700 NDF150 3600 - 4500
Please refer to the Appendix of this handbook for detailed burner performance data.
Fuel
Burners designated NDFL are suitable for light dis­tillate oil (Class D) and those designated NDFR are suitable for residual oils (Classes E, F and G). All NDF burners are normally configured for natural gas but versions suitable for liquefied petroleum gas (LPG) or manufactured gas (towns gas) can be supplied on request.
Models NDF35 to NDF150
Page 9
Page 10
Air Fan Size
To match NDF burners with the appliance, with respect to both burner output and appliance re­sistance, a number of combustion air fan sizes are available for each model as detailed in the table below.
Burner Model Available Fan Sizes
NDF35 25, 34 & 38 NDF50 28, 34 & 38 NDF60 28, 34 & 38 NDF80 28 & 34
NDF85 38 NDF100 38, 41 & 44 NDF125 36, 41 & 44 NDF150 36, 41 & 44
The fan size quoted is the diameter of the fan impellor (measured in cm) and appears as a suffix to the model number. For example, a burner des­ignated NDFR60 - 34 is a model 60 for residual fuel oil firing with a 34 cm diameter combustion air fan impellor.
Controls and Safety Systems
NDF burners are fitted with a combustion airflow control and an air/fuel ratio control system which together ensure smooth starting and optimum op­erating efficiency.
An air pressure switch provides safe burner shut­down if the combustion air supply becomes insuf­ficient for complete combustion. The burner's ad­ditional safety systems include for gas pressure monitoring (low and high) whilst gas firing, and low oil temperature monitoring (NDFR) whilst fir­ing on fuel oil. Continuous flame supervision is provided by an ultraviolet (UV) cell and automatic programming control unit.
Operating Mode
Standard NDF burners are manufactured for ei­ther fully modulating or two-stage (high/low) op­eration on both fuels. A special variation of the NDFL35 to NDFL100-38 burner is available upon request, designated Modulating - High/Low. In this version, the burner operates in fully modulating mode when firing on gas, and 2 stage (high/low) mode when firing on oil.
Oil Firing
Fully Modulating Operation
All NDF burners manufactured for fully modulat­ing operation use a single spillback oil nozzle.
If the burner has been correctly matched to the appliance, a turndown ratio of up to 3.0:1 may be achieved.
Two Stage Operation
NDFL burners up to and including the NDFL100 ­38 use twin simplex oil nozzles, one for low fire and both for high fire.
The oil nozzles are sized to give a turndown ratio of between 1.8 and 2.0:1.
NDFL burners NDFL100 - 41 and larger, together with all NDFR burners are supplied with a system designated 'Sliding High/Low' which uses a single spillback oil nozzle (similar to that employed in the fully modulating mode) which is constrained to operate at either of two fixed oil flows corre­sponding to the high and low fire rates. If the burner has been correctly matched to the appliance, a turndown ratio of up to 3.0:1 may be achieved.
Gas Firing - All Modes
When gas firing, the fuel gas flow is controlled by an automatic valve which, following commission­ing, precisely matches the fuel flow to the air flow to achieve the required fuel/air ratio at any point in the full turndown range. If the burner has been correctly matched to the appliance, a turndown ratio between 2.0 and 2.5:1 may be achieved.
Burner Type Nomenclature
NDF burners are divided into two groups, depend­ing on the oil nozzle employed:
Twin Pressure Jet Burners
Comprising two stage NDFL burners up to and including the NDFL100 - 38
Single Spill Back Burners
Comprising two stage NDFL burners NDFL100 - 41 and larger,
all fully modulating NDFL burners, all two stage NDFR burners, all fully modulating NDFR burners.
Throughout this handbook the burners are referred to by this grouping.
SITE CONDITIONS AND SERVICES
Flue and Chimney Requirements
It is important that:
Models NDF35 to NDF150Page 10
Page 11
- The flue pipe from the appliance and the joint between this flue and the chimney are sealed to prevent leakage of combustion products.
- The flue pipe from the appliance does not protrude into the chimney beyond the in­side wall.
- The top of the flue or chimney shall be higher than any roof within a radius of 10 metres.
- Checks are made to ensure that the chim­ney is suitable for gas and oil fired appliances and that the proposed installation complies with all Local Authority and other regulations covering such installations.
- The flue must be balanced at the appliance outlet.
- If more than one appliance is connected to a common flue or chimney, the cross-sec­tion of this flue or chimney should be ad­equate for the total volume of combustion products from the appliances.
Plant Room Ventilation
The burner must be supplied with dust free air at sufficient rates for all firing conditions, in accord­ance with the appropriate Standards.
Existing Appliances
The appliance should be prepared for installation of the NDF burner by thorough cleaning, includ­ing the removal of all adhering tar, scale and dirt. An inspection should also be carried out to ensure that the appliance is in good condition. Any doubt about the suitability of the appliance for dual fuel firing should be referred to the appliance manu­facturer.
Combustion Chamber Conditions
When the burner is fitted to an appliance designed to work under balanced or negative combustion chamber pressure conditions the over-fire draught must not exceed 0.25 mbar.
It is essential that a 90∞ manual isolation valve is fitted upstream of the gas control train to allow the burner to be isolated for maintenance. The size of this valve should not be less than that of the burner control train in order to avoid any restric­tion in gas flow.
Gas Boosters
When a gas booster is used, the gas pressure at the booster inlet must not fall below 10 mbar un­der any conditions. A low gas pressure switch must be fitted on the upstream side of the booster to prevent it starting if the supply pressure is insuffi­cient.
An additional pressure switch should be used to monitor the pressure downstream of the booster and prevent the burner going to high fire if the pressure is insufficient.
It should be noted that CE marked burners fitted with a low gas pressure switch will not run if the gas pressure from the booster is insufficient. This is due to the low gas switch being set to safegaurd combustion quality at the high fire setting. In this situation the booster outlet pressure switch will have no bearing on the burner control, but can be used to indicate booster failure
The booster should be installed as near to the burner as possible. It should be positioned on a firm, flat, horizontal surface using anti-vibration mountings. All connecting pipework should be well supported and accurately positioned in order to avoid stressing the booster casing. Flexible con­nectors, which reduce both pipework stresses and transmitted noise, must be fitted. The gas supplier should be asked to recommend the size of pipework between the meter and the booster to ensure that the required pressure and flow are available.
Gas Supply
The gas supply pipework to the burner must be appropriate to local conditions and must be con­structed and installed in compliance with appro­priate Codes and Standards. It shall be of sufficient size to satisfy the pressure and volume flow re­quirements of the burner under all firing condi­tions. Checks should be made to ensure that all meters and other components are appropriately rated for the maximum gas flow rate anticipated.
Models NDF35 to NDF150
Page 11
Page 12
A TYPICAL PUMPED OIL RING MAIN
Models NDF35 to NDF150Page 12
Page 13
OIL HANDLING TEMPERATURES AND PRESSURES
p
Fuel Handling Temperatures (°C)
Fuel
Class
D 35 0.35 to 0.70 72.5 Max
E 200 16 16 82
F
G
Viscosity
(Seconds)
960 30 43 110 1500 36 65 118 3500 50 82 132 4200 55 86 140
Minimum
From Tank
Minimum 5 Recommended
Burner
Inlet
Oil Supply
The oil supply pipework to the burner must be appropriate to local conditions and must be con­structed and installed in compliance with appro­priate Codes and Standards. It shall be of sufficient size to satisfy the pressure and volume flow re­quirements of the burner under all firing condi­tions. Checks should be made to ensure that all meters and other components are appropriately rated for the maximum oil flow rate anticipated. Galvanised steel pipe should not be used. The sup­ply pipework should include an appropriate filter. The final connection to the oil pump inlet port should be made using the flexible pipes supplied with the burner.
NDFL burners may employ a pumped ring main or a gravity feed oil supply system.
Where a gravity feed system is used it should be designed and sized such that the oil pressure at the pump inlet is not less than 350 mbar and not more than 689 mbar. A two-pipe system must be used. It is important to ensure that the return pipe is not obstructed as this may result in damage to the pump.
Where it is thought desirable, a pumped ring main (refer to the schematic diagram on Page 12) of ap­propriate capacity may be used for NDFL burners and such a system is essential where the burner is to operate on residual oil (NDFR burners). The ca­pacity of the ring main pump should be at least
1.25 times that of the burner pump(s) that it is re­quired to supply. In the case of NDFR burners the pipework and oil storage tank should be insulated, trace heated and thermostatically controlled in ac­cordance with the data shown in the table on Page
13.
Fuel Delivery Pressures
Atomising
(At Inlet To Burner Oil Pum
2
kg/cm
4 to 5 57 to 71
psi
)
Electrical Power Supply
A 400 Volt, three-phase 50 Hz supply is required. Power requirements are listed in the Tables on Pages 14, 15 and 16. The power supply provided must comply with all relevant Codes and Stand­ards.
UNPACKING AND ASSEMBLY
To safeguard against damage in transit, NDF burn­ers are supplied in partly assembled form.
Twin Pressure Jet Burners
(NDFL35-25 to 100-38 2 Stage (High/Low)) NDFL burner systems comprise two units:
- The burner body, complete with control package, hinged extension and flame tube assembly.
- The gas control train.
To assemble the burner:
- Fit the gas control train to the burner body using the gasket supplied, ensuring that the gasket is fitted correctly with all holes corre­sponding with those on the burner flange.
- Connect the combustion air impulse pipe from the SKP70 air/gas ratio controller to the left side of the hinged extension.
- Connect the multi-pin plug on the gas valve train to the socket on the rear of the control package.
Note: In some circumstances it may be advisable to fit the burner casing to the appliance before attaching the gas control train. It is recommended that lifting gear should be employed if necessary.
Models NDF35 to NDF150
Page 13
Page 14
ELECTRICAL POWER REQUIREMENTS : TWIN PRESSURE JET OIL BURNERS
(NDFL35-25 to NDFL100-38 Two Stage Operation)
Fan
BURNER
NDFL35-25 1.1/1.5 15.8 2.7 1.0 10 NDFL35-34 2.2/3.0 29.3 5.0 1.5 16 NDFL35-38 3.0/4.0 38.6 6.6 2.5 20 NDFL50-28 2.2/3.0 29.3 5.0 1.5 16 NDFL50-34 3.0/4.0 38.6 6.6 2.5 20 NDFL50-38 4.0/5.5 49.7 8.5 2.5 25 NDFL60-28 2.2/3.0 29.3 5.0 1.5 16 NDFL60-34 4.0/5.5 49.7 8.5 2.5 25 NDFL60-38 4.0/5.5 49.7 8.5 2.5 25 NDFL80-28 3.0/4.0 38.6 6.6 2.5 20 NDFL80-34 4.0/5.5 49.7 8.5 2.5 25 NDFL85-38 5.5/7.5 66.1 11.3 2.5 32
NDFL100-38 7.5/10.0 88.9 15.2 4.0 32
NOTE: All above burner fan motors are started D.O.L.
Motor
kW/hp
Start
Current
A/Phase
FLC
A/Phase
Cable
Size
(mm2)
HRC
Fuse
(A)
Single Spill Back Burners
(NDFL Modulating Burners, NDFR Burners) NDFR burner systems comprise four units:
- The burner body, complete with hinged ex­tension and flame tube assembly.
- The gas control train.
- The oil pump unit (NDFL).
- The oil pumping and heating unit (NDFR).
- A free-standing or wall mounted control panel.)
To assemble the burner:
- Fit the gas control train to the burner body using the gasket supplied, ensuring that the gasket is fitted correctly with all holes corre­sponding with those on the burner flange.
- Connect the combustion air impulse pipe from the SKP70 air/gas ratio controller to the left side of the hinged extension.
- Connect the multi-pin plug on the gas valve train to the socket on the rear of the burner mounted terminal panel.
- Place and secure the oil pump/pumping and heating unit in the desired position. The floor mounting arrangements are shown on Page 32 (residual fuels) and Page 33 (distillate fu­els). Connect the unit to the burner pipework using the flexible connectors provided.
- Fix the control panel in an appropriate posi­tion and make the electrical connections to the burner package and oil pump unit, as shown in the wiring diagram contained in the instruction pack attached to the burner.
Note: In some circumstances it may be advisable to fit the burner casing to the appliance before attaching the gas control train. It is recommended that lifting gear should be employed if necessary.
Models NDF35 to NDF150Page 14
Page 15
ELECTRICAL POWER REQUIREMENTS : SINGLE SPILL BACK NOZZLE DISTILLATE OIL BURNERS
(NDFL35-25 to NDFL150-44 Modulating and Two Stage Operation)
Fan
BURNER
NDF35-25 1.1/1.5 0.55/0.75 25.2 4.3 1.5 16 NDF35-34 2.2/3.0 0.55/0.75 38.6 6.6 2.5 20 NDF35-38 3.0/4.0 0.55/0.75 48.0 8.2 2.5 25 NDF50-28 2.2/3.0 1.1/1.5 45.0 7.7 2.5 25 NDF50-34 3.0/4.0 1.1/1.5 54.4 9.3 4.0 32 NDF50-38 4.0/5.5 1.1/1.5 65.5 11.2 4.0 32 NDF60-28 2.2/3.0 0.75/1.0 41.0 7.0 2.5 25 NDF60-34 4.0/5.5 0.75/1.0 61.5 10.5 4.0 32 NDF60-38 4.0/5.5 0.75/1.0 61.5 10.5 4.0 32 NDF80-28 3.0/4.0 0.75/1.0 50.4 8.6 2.5 25 NDF80-34 4.0/5.5 0.75/1.0 61.5 10.5 4.0 32
NDF85-38 5.5/7.5 0.75/1.0 77.9 13.3 4.0 32 NDF100-38 7.5/10.0 1.5/2.0 101.3 17.3 4.0 40 NDF100-41 11.0/15.0 1.5/2.0 97.0 25.3 6.0 40 NDF100-44 11.0/15.0 1.5/2.0 97.0 25.3 6.0 40 NDF125-36 7.5/10.0 1.5/2.0 101.3 17.3 4.0 40 NDF125-41 11.0/15.0 1.5/2.0 97.0 25.3 6.0 40 NDF125-44 11.0/15.0 1.5/2.0 97.0 25.3 6.0 40 NDF150-36 11.0/15.0 1.5/2.0 97.0 25.3 6.0 40 NDF150-41 11.0/15.0 1.5/2.0 97.0 25.3 6.0 40 NDF150-44 15.0/20.0 1.5/2.0 123.6 32.9 10.0 50
Motor
kW/hp
Pump
Motor
kW/hp
Start
Current
A/Phase
FLC
A/Phase
Cable
Size
(mm
HRC
Fuse
2
)
(A)
NOTE: Burner fan motors up to and including 7.5 kW are started D.O.L.
Special Compact Burner Arrangement
Depending on the burner model and application, a special compact version of NDFL Modulating and NDFR burners can be supplied. These burner models are supplied to special order only and are delivered with the oil pumping (pumping and heat­ing) equipment mounted under the burner throat. If additional appliance control requirements are not specified, then the burner control panel can also be burner mounted. The equipment is thus delivered as a packaged arrangement with all of the interconnecting oil pipework and electrical control connections pre-made. The gas control
train will be supplied loose. IMPORTANT: - The NDF compact burner, in par-
ticular the NDFR series, will be heavier than its standard counterpart. This must be taken into con­sideration when fitting the burner to the appliance. It is strongly recommended that lifting gear should be employed when carrying out this task.
Models NDF35 to NDF150
Page 15
Page 16
ELECTRICAL POWER REQUIREMENTS : SINGLE SPILL BACK NOZZLE RESIDUAL OIL BURNERS WITH OIL PRE-HEATER
(NDFL35-25 to NDFL150-44 Modulating and Two Stage Operation)
Pump
BURNER
NDF35-25 1.1/1.5 31.6 14.0 4.0 32.0 6.0 1.5 NDF35-34 1.1/1.5 45.0 16.4 4.0 32.0 6.0 1.5 NDF35-38 1.1/1.5 54.4 18.0 4.0 40.0 6.0 1.5 NDF50-28 1.1/1.5 45.0 18.5 4.0 40.0 7.5 1.5 NDF50-34 1.1/1.5 54.4 20.1 4.0 40.0 7.5 1.5 NDF50-38 1.1/1.5 65.5 22.0 4.0 40.0 7.5 1.5 NDF60-28 1.1/1.5 45.0 18.5 4.0 40.0 7.5 1.5 NDF60-34 1.1/1.5 65.5 22.0 4.0 40.0 7.5 1.5 NDF60-38 1.1/1.5 65.5 22.0 4.0 40.0 7.5 1.5 NDF80-28 1.5/2.0 59.7 21.0 4.0 40.0 7.5 1.5 NDF80-34 1.5/2.0 70.8 22.9 4.0 40.0 7.5 1.5
NDF85-38 1.5/2.0 87.2 25.7 6.0 40.0 7.5 1.5 NDF100-38 1.5/2.0 101.2 28.1 6.0 40.0 7.5 1.5 NDF100-41 1.5/2.0 97.0 36.1 10.0 50.0 7.5 1.5 NDF100-44 1.5/2.0 97.0 36.1 10.0 50.0 7.5 1.5 NDF125-36 1.5/2.0 101.2 30.3 6.0 40.0 9.0 2.5 NDF125-41 1.5/2.0 97.0 38.3 10.0 50.0 9.0 2.5 NDF125-44 1.5/2.0 97.0 38.1 10.0 50.0 9.0 2.5 NDF150-36 1.5/2.0 97.0 42.7 10.0 63.0 12.0 4.0 NDF150-41 1.5/2.0 97.0 42.7 10.0 63.0 12.0 4.0 NDF150-44 1.5/2.0 123.7 50.3 16.0 80.0 12.0 4.0
Motor
kW/hp
Start
Current
A/Phase
FLC
A/Phase
Cable
Size
(mm2)
HRC
Fuse
(A)
Pre-
heater
kW
Cable
Size
(mm2)
NOTE: Burner fan motors up to and including 7.5 kW are started D.O.L. Above 7.5
INSTALLATION
General
Ensure that the appliance is suitable for the heat input of the burner. If there is any doubt in this area reference should be made to the appliance manufacturer. Detailed burner performance data are presented in the Appendix of this handbook.
Fitting to the Appliance
If the burner is to be fitted to a new appliance, refer to the appliance manufacturer's recommen­dations.
Models NDF35 to NDF150Page 16
If the burner is to be fitted to an existing appli­ance, a mounting flange must be provided as de­tailed in the Section on Burner and Components Identification. Ensure that the joint between the burner and the mounting flange is sealed effec­tively using the gasket provided.
The flame tube should be flush with the inner face of the appliance combustion chamber. Up to 10 mm protrusion may be acceptable (refer to the appliance manufacturer) however it is not gener­ally permissible for the flame tube to sit within the appliance firing tunnel.
Page 17
Special extensions may be specified by the appli­ance manufacturer, for example in the case of a reverse flame boiler.
Electrical Power Connection
Connect a three-phase, 50 Hz electrical supply to the burner, observing all applicable Codes and Standards. The electrical connections required are shown in the wiring diagram contained in the in­struction pack attached to the burner. These dia­grams also show the external auxiliary control con­nections which must be made.
If the burner is supplied as part of a packaged ap­pliance/burner unit, refer to the appliance manu­facturer's instructions.
BURNER CONTROL AND OPERATION
All personnel concerned with commissioning and/ or operation of NDF burners should familiarise themselves with the information presented in this Section.
Single Spill Back Burners.
The single spill back burners employ a Landis & Staefa SQM 10 motor as shown on Page 19. This motor activates the damper through an adjustable cam and cable system, and is mounted above the air inlet on all models.
Air Diffuser
The air diffuser is fitted to the front of the burner assembly, within the flame tube (refer to the Ap­pendix). This diffuser controls the combustion air flow and creates a pressure drop across the burner head, promoting good fuel/air mixing and flame stability.
Air Pressure Switch
The air pressure switch is located on the left side of the burner casing. Its function is to ensure that combustion air flow is adequate under all operat­ing conditions.
Air flow failure at any stage beyond the first few seconds of the pre-purge sequence will result in burner lockout.
Air Controls
Air Regulator
NDF 35-25 to NDF 100-38.
The flow of combustion air into the burner is con­trolled by a single adjustable air damper blade lo­cated within the air damper casting on the right hand side (in all cases, such descriptions refer to the system as viewed from the rear) of the burner.
NDF 100-41 to NDF 150-44.
The flow of combustion air into the burner is con­trolled by a multiple-aperture rotary type damper, fitted to the burner casing within the air inlet si­lencer on the right hand side of the burner.
Air Damper Motor
In all cases, the air damper is controlled by a ser­vomotor containing adjustable limit switches for the low and high fire positions.
Twin Pressure Jet Burners.
On twin pressure jet burners a Berger Lahr STM 6 5 cam motor is used, as shown on Page 18. A fully closed position is provided to prevent air flowing through the appliance when the burner is not in operation. On these burners the servomotor is mounted on the rear face of the air inlet and di­rectly coupled to the air damper blade.
Gas Controls
A typical gas train fitted is shown on Page 20.
Gas Nozzle
NDF burners utilise a spiked head design with multiple gas tubes fitted with appropriately sized gas restrictors. Referred to as the "gas nozzle" this is fitted to the front of the burner assembly, within the flame tube (refer to the Appendix). The number and diameter of the gas tubes in this nozzle are specified in accordance with the rating of the burner and the gas to be used (refer to the table in the Appendix).
High Gas Pressure Switch
A high gas pressure switch is fitted at the outlet of the gas train to ensure that any increase in gas sup­ply pressure above the level needed to maintain the set conditions results in a safe burner shutdown. In most cases, high gas pressure would indicate a fault with the air/gas ratio controller.
The pressure switch, which is fitted with an illumi­nated fault indicator and manual reset button, is factory set to the maximum value. Final adjustment of the setting of this switch is described in the Sec­tion on Commissioning.
Models NDF35 to NDF150
Page 17
Page 18
AIR DAMPER SERVOMOTOR : TWIN PRESSURE JET BURNERS
Model : Berger Lahr STM 6
Models NDF35 to NDF150Page 18
Page 19
AIR DAMPER SERVOMOTOR : SINGLE SPILL BACK NOZZLE BURNERS
Model : Landis & Staefa SQM 10
Models NDF35 to NDF150
Page 19
Page 20
TYPICAL GAS TRAIN
Models NDF35 to NDF150Page 20
Page 21
Low Gas Pressure Switch
Provision of a low gas pressure switch is required by European Standard EN 676 - Automatic forced draught burners for gaseous fuels. This pressure switch is fitted to all burners which carry the CE marking but it may not be fitted to non-CE marked burners.
The low gas pressure switch monitors inlet gas pres­sure and ensures that any decrease in gas pressure below the value needed to maintain satisfactory combustion results in a safe burner shutdown. Fi­nal adjustment of the setting of this switch is de­scribed in the Section on Commissioning.
GAS CONTROL VALVE (SKP 70)
Gas Valve Train
In addition to the pressure switches noted above, the gas control train includes an air/gas ratio con­troller, automatic safety shut-off valves and a gov­ernor in the start gas line. A manual isolation valve, which must be fitted and wired during installation at the inlet to the gas train, is electrically interlocked to the burner control circuit. This valve must be in the closed position when firing the burner on oil.
Models NDF35 to NDF150
Page 21
Page 22
SKP70 Air/Gas Ratio Controller
The air/gas ratio controller, shown on Page 21 var­ies the gas pressure in response to changes in com­bustion air pressure to ensure that the air/gas ratio remains constant over the operating range of the burner.
A separate gas pressure governor is not necessary. Two impulse pipes (both factory supplied) are con­nected to the air/gas ratio controller.
The first is connected to the burner hinged exten­sion and supplies air pressure to the ratio control­ler. Note that in installations with negative air pres­sure in the combustion chamber, this pipe must always be under positive pressure. A second pipe connected to the gas line downstream of the valve set provides gas pressure to the ratio controller.
SKP70 combustion chamber impulse connection The impulse connection to the combustion cham-
ber is not required in the majority of applications and is therefore not supplied as part of the burner package.
This is because the resistance of the combustion chamber / flue assembly is assumed to remain con­stant and that the pressure within this chamber will change in proportion to the burner gas and combustion air pressure (as the burner output changes).
If however the pressure in the combustion cham­ber does not change in proportion to the burner gas or air pressure, i.e. the plant is fitted with a flue gas fan, continuously operating flue gas damper or the combustion chamber pressure changes from negative to positive whilst moving from Low to High flame, then a compensating circuit is required.
This means that the pressure in the combustion chamber must be connected to the SKP70 so that the controller can automatically offset the pres­sure changes.
This compensating circuit should also be used if pressure shocks and vibrations, which adversely affect burner start up, develop in the combustion chamber during the start up phase.
Naturally, it must always be taken into considera­tion that the burner output decreases as the pres­sure in the combustion chamber increases, and visa versa.
Installation of combustion chamber impulse pipe A minimum inside pipe diameter of 8mm is rec-
ommended.
The impulse pipe should be as short as possible to allow the controller to respond quickly to sudden burner output changes. It must be installed such that the gases will cool down in the area of the impulse pipe and condensing gases will not enter the controller but run back into the combustion chamber. If necessary, a water trap must be pro­vided.
Valve Proving System
Valve proving systems, as shown schematically on Pages 23 and 24 are standard on all NDF burners with maximum firing rates which exceed 1200 kW. The standard model fitted is the Landis & Staefa LDU 11 (see Page 23) but the Dungs VPS 504 (see Page 24) is available as an option.
When the burner operating sequence is initiated, the burner control box energises the proving sys­tem, which then carries out the following checks.
Landis & Staefa LDU11 The LDU11 control unit is designed to provide auto-
matic gas valve proving (leakage test) based on the pressure proving principle.The system comprises the control unit, which is fixed to a bracket / terminal box assembly close to the main valve block, and a dual pressure switch which is connected to the test space between the main valves. The unit comes pre­wired as part of the gas train harness.
Gas valve proving is initiated automatically upon com­pletion of the burner control circuit prior to burner start up. The proving test is based on the 2-stage pres­sure proving principal. First, the main safety valve (V1) on the upstream side of the gas circuit is tested by evacuating the test space (via the pilot valve V3) and by monitoring the atmospheric pressure in it, then the valves (V2 and V3) on the burner side are tested by pressurising the test space and monitoring the gas pressure. If the pressure increases excessively during the first test phase (TEST 1) or decreases excessively during the second test phase (TEST 2), the control unit inhibits burner start up and goes to lockout. The lockout reset button lights up and signals a fault.
A programme indicator, which stops whenever a fault is signalled, indicates which valve(s) set is leaking.
The control unit requires to be reset manually, either on the unit itself or by a remote resetting if this has been fitted.
Dungs VPS504 The VPS504 is a self-contained unit that operates on
the pressure build up principle. The unit is only suit­able for use on valve line sizes up to and including 2" (DN50).
Models NDF35 to NDF150Page 22
Page 23
VALVE PROVING SYSTEM : LDU 11
S
(Standard Fitting)
Dual Gas Pressure
Switch Assembly
(’Mini-Maxi’)
Low Gas
Pressure Switch
Mounting Bracket
Terminal Box
LDU11 Control Unit
Schematic:
Manual Gas
Valv e With
Electrical Interlock
Gas Inlet
Start Gas
Val ve (V3)
Main Gas
Val ve (V1)
Combined Main Valve
PS PS
Low Gas
Pressure Switch
Mini-Maxi Pressure
And Governor (V2)
PS PS
Start Gas
Governor
witches
Control Position Indicator, ‘Gas Proving Failed’ Neon and Programme Reset Button
To B u rn e r
High Gas
Pressure Switch
Electrical
Connection
LDU 11
Models NDF35 to NDF150
Page 23
Page 24
VALVE PROVING SYSTEM : VPS 504
(Optional Fitting)
The programmer starts functioning when the burner controlling circuit is made. With valves V1, V2 and V3 in the closed position, an internal pump increases the gas pressure within the test section to 20 mbar above the pressure at the inlet to the valve train. During the test time an integral differential pressure switch monitors the test section for leaks. When the test pressure is reached the pump is switched off. If the proving check has been successful (max. 30 sec­onds) the control circuit is released accompanied by illumination of the yellow indicator light on the unit.
Models NDF35 to NDF150Page 24
If the proving check has been unsuccessful or if a pres­sure rise of 20 mbar has not been reached during the test time (max. 26 seconds), the unit will switch to the fault condition accompanied by illumination of the red indicator light. This condition will remain until the unit is manually reset or the control circuit is bro­ken.
Page 25
Oil Controls - Twin Pressure Jet Oil Burners
The oil control system used on NDFL burners with twin pressure jet oil nozzles is shown on Page 25. In addition to the oil pump it includes high and low fire safety shut-off valves (normally closed type) and a manually operated ball valve.
Oil Supply
Oil can be supplied from a two-pipe garvity sys­tem or from a two-pipe pumped ring main sys­tem. A two-pipe system is essential to enable oil circulation through the oil pump during periods of gas firing to ensure adequate lubrication. The oil must be supplied and maintained at the tempera­tures and pressures given in the Table on Page 13.
Filter
The filter is usually supplied loose and must be attached to the oil pump inlet prior to commis­sioning.
Oil Pump
The oil pump is mounted on the air inlet casing on the right side of the burner. It is driven by the burner motor through a flexible coupling.
When firing on gas for extended periods, it is rec­ommended that this coupling is removed in order to protect the pump from unnecessary wear.
Information on the pumps fitted to the NDF burner range is given in the Table on Page 26.
The pumps are shown on Pages 27 -29.
Manual Valve
The manual valve is fitted with an electrical inter­lock to prove that the valve is in the closed posi­tion before the burner can be run on gas.
Oil Manifold Block
The oil manifold block is located below the burner hinged extension. It connects the oil inner assem­bly to the external oil system.
Oil Nozzles
The two oil nozzles (high and low fire) are held in a nozzle block located within the flame tube (refer to the Appendix). The nozzles are pre-sized by Nu­way in accordance with the heat inputs required and the available operating pressure.
The oil nozzles are usually supplied in the instruc­tion pack attached to the burner and must be fit­ted to the burner nozzle block prior to commis­sioning.
OIL CONTROL SYSTEM : TWIN PRESSURE JET OIL BURNERS
Models NDF35 to NDF150
Page 25
Page 26
OIL PUMPS FITTED
Oil Controls - Single Spill Back Nozzle Oil Burners.
The oil control system comprises the burner mounted components and a separate pumping unit for distillate fuels or pumping/heating unit for re­sidual fuels.The burner mounted components are similar for both light and residual oils. The sepa­rate oil pumping or pumping/heating set is con­nected to the burner utilising the braided high pressure hoses supplied. The burner lance in­corporates hydraulic tip shut off for the oil noz­zle whilst the system controlling valves are closely
FLUIDICS W1 NOZZLE
mounted at the burner head. Schematics of the oil controls are shown on Page
30 for residual fuels and Page 31 for distillate fu­els.
Details of the pumping/heating set (for residual fu­els), including the mounting arrangement are shown on Page 32. The pumping set for distillate fuels is shown on Page 33.
Manual Valve
On NDFL burners, a manual valve is fitted with an electrical interlock, which proves that the valve is in the closed position before the burner can be run on gas.
This valve is not fitted to NDFR burners due to the continual heating and recirculating requirements of residual oils.
Oil Nozzle
NDFL Modulating / NDFR burners use a single oil nozzle (Page 26) within the inner assembly (refer to the Appendix).
This nozzle is factory-specified to deliver optimum performance under the specified operating condi­tions. Any queries regarding the size of the nozzle should be referred to Nu-way.
The nozzle is held in position by the inner assem­bly lance, through which oil flows from the mani­fold block to the nozzle and is recirculated through the spill regulating valve.
Oil Manifold Block
The oil manifold block is located on the left side of the hinged extension. It carries gauges which indi­cate pump pressure, hydraulic pressure and spill pressure.
Models NDF35 to NDF150Page 26
Page 27
SUNTEC OIL PUMP IDENTIFICATION AND PORT SIZING
Models NDF35 to NDF150
Page 27
Page 28
SUNTEC OIL PUMP IDENTIFICATION AND PORT SIZING
Models NDF35 to NDF150Page 28
Page 29
DANFOSS OIL PUMP IDENTIFICATION AND PORT SIZING
Oil Spill Regulating Valve
The oil spill regulating valve is actuated by the mo­tor which actuates the air damper. It varies the spill pressure in order to provide the required oil flow rate at each operating condition.
Oil Pump
The oil pump is incorporated into a free-standing packaged unit as shown schematically on Pages 32 and 33. This package includes the oil filters, an air separation bottle and in the case of NDFR burn­ers the oil preheater tank (including a thermom­eter to indicate outlet oil temperature) and the return thermostat which ensures that the recirculating oil temperature is maintained at an appropriate level during shutdown periods.
Information on the pumps fitted to the NDF burner range is given in the Table on Page 26.
The pumps are shown on Pages 27 -29.
Dummy Oil Inner Assembly
For NDFR burners firing ëGí class fuel, a dummy oil inner assembly is available as an option. This enables the oil lance to be removed during ex­tended periods of gas firing, with the dummy as­sembly replacing it.
This will enable the oil pumping and heating unit to continue to keep the oil system up to tempera­ture without danger of oil being released into the appliance whilst firing the burner on gas.
Control Panel
Twin Pressure Jet Oil Burners
On NDFL 2 stage burners the programming burner controller, ignition transformer, contactors and other items are located in an enclosure mounted on the left side of the burner.
Models NDF35 to NDF150
Page 29
Page 30
OIL CONTROLS : SINGLE SPILL BACK NOZZLE RESIDUAL OIL BURNERS
Models NDF35 to NDF150Page 30
Page 31
OIL CONTROLS : SINGLE SPILL BACK NOZZLE DISTILLATE OIL BURNERS
Models NDF35 to NDF150
Page 31
Page 32
OIL PUMPING/HEATING SET FOR RESIDUAL FUELS
Models NDF35 to NDF150Page 32
Page 33
OIL PUMPING SET FOR DISTILLATE FUELS
The front panel of this enclosure carries the burner On/Off switch and two neon indicator lights. The amber light indicates "BURNER ON" and the red light is illuminated when the burner stops as a re­sult of "EXCESS TEMPERATURE / PRESSURE" in the appliance.
The fuel selector switch and two additional neon indicator lights are mounted on the side of the enclosure. The amber light is illuminated when "OIL" is the chosen fuel and the red light indicates that "GAS" has been selected.
Models NDF35 to NDF150
Single Spill Back Nozzle Oil Burners
On NDF Modulating and Sliding High/Low burn­ers, the enclosure mounted on the left side of the burner serves mainly as a housing for electrical connections, although it also contains the ignition transformers and carries the burner On/Off switch, the Hand/Auto switch and the Inching switch re­quired by modulating burners
A separate free-standing panel contains the pro­gramming burner controller, contactors and other items. This enclosure carries an amber light which indicates "BURNER ON" and a red light which is illuminated when the burner stops as a result of "EXCESS TEMPERATURE / PRESSURE" in the ap­pliance.
Page 33
Page 34
BURNER CONTROLLER : SATRONIC TMG 740
Models NDF35 to NDF150Page 34
Page 35
BURNER CONTROLLER : LANDIS & STAEFA LFL 1
Models NDF35 to NDF150
Page 35
Page 36
MODULATION CONTROLLER : LANDIS & STAEFA RWF 32
Also located on this enclosure are the fuel selector switch and two additional neon indicator lights. The amber light is illuminated when "OIL" is the chosen fuel and the red light indicates that "GAS" has been selected.
Burner Controller
The burner controller, together with the flame monitor (see below), provide a safe light up and shut down sequence for the burner.
Twin Pressure Jet Burners.
Two options are available, the Satronic TMG 740-
3 (shown on Page 34) or the Landis & Staefa LFL
1.333 (shown on Page 35)
Models NDF35 to NDF150Page 36
Single Spill Back Burners.
The Landis & Staefa LFL 1.333 (shown on Page
35) is fitted as standard.
Flame Monitor
In standard configuration, NDF burners are fitted with a continuous flame supervision system which uses an ultraviolet (UV) cell and amplifier (incor­porated within the burner controller) to detect the presence of the flame.
Modulating Controller
The Landis & Staefa RWF 32 (see Page 36) is fit- ted as standard to all fully modulating burners.
Page 37
BURNER CONTROLLER SEQUENCE AND TIMING CHART
BURNER OPERATING SEQUENCE
The NDF burner operating sequence (refer to the controller sequence diagram on Page 37 ) begins with a pre-purge period on full air. When gas is selected this fuel is then supplied to the burner at start rate and ignition initiated. Start gas flame prov­ing is followed by establishment of the main flame.
Models NDF35 to NDF150
When oil is selected, on completion of the pre­purge period the appropriate oil valve or valves open, ignition is initiated and the flame is estab­lished.
In both cases, the burner controller will then con­tinue to its normal operating position and the op­eration of the burner will be controlled by the pres­sure and/or temperature requirements of the ap­pliance.
Page 37
Page 38
MODULATING CONTROLS
Controller
The standard method of operation is based on the Landis & Staefa RWF32 Universal Controller, which has been designed for use in oil and gas fired in­stallations, where it provides temperature or pres­sure control of modulating burners with continu­ously adjustable fuel throughput.
The control output of the RWF32 is a potential free 3-position switch, which is used for the con­trol of reversible motors. The control signals for the open (Y1) and closed (Y2) are indicated on the controller face by light emitting diodes.
Replaceable range insert circuit boards which are used in conjunction with passive detectors of type QAE22 (temperature) and QBE61 (pressure) achieve configuration of the unit to a control value and setting range.
When the boiler control calls for heat, the modu­lating servomotor will travel to the high flame po­sition and interlock the control circuit. An air pre­purge will take place at this position for a pre-de­termined period, at the end of which the burner sequence controller will stop until the modulating servomotor has travelled to the low flame position and interlocked the control circuit again. The se­quence controller will now recommence its op­erational cycle and the burner will light and re­main at low flame until the high flame release sig­nal is given by the sequence controller.
The modulating servomotor will now move to high flame and remain at this position until the desired boiler temperature/pressure is attained. From this stage the modulating unit will commence to move towards the low flame position, but, depending on the temperature/pressure, will stop in any in­termediate position between low and high flame.
Commissioning Controls
Two switches, Hand/Auto and Inching, are in­cluded in the burner panel. In Auto mode the burner will respond to the demand of the boiler via the RWF32 modulating controller. In ëHandí mode, the RWF32 controller is disconnected from the burner modulating servo. This servo can now be 'inched' towards high or low flame by operat­ing the 3 position bias inching switch, thus allow­ing combustion settings to be made at these points.
Whilst in ëHandí mode, care must be exercised when the burner is in a high firing range so that the boiler demand is not exceeded. It is impera­tive that the burner control circuit operating and limiting instruments are fitted and functioning cor­rectly.
Some panels may be fitted with a third switch marked 'Low Flame Hold'. This switch, when operated, has the same effect as starting the burner in the 'Hand' mode. That is, the burner will run through its starting sequence, establishing flame at the low flame rate and remaining at this state until manually commanded otherwise. If the Low Flame Hold switch is activated and the Hand/Auto switch is set in the Auto position, releasing of the Low Flame Hold switch will result in the Modulating Servo driving towards the high flame position as determined by the RWF32 temperature controller.
Temperature Detector
The immersion temperature detector type QAE22 is used in all hot water boiler applications. The detector has a plastic casing to IP42 with a snap on cover and an immersion stem. The connection terminals can be accessed after removal of the cover. Cable entry is made via a cable entry gland Pg11. In all applications an immersion pocket with a flat seal is supplied.
The detector should be installed in an elbow such that the pocket points against the direction of flow. With all detector versions, the immersion length must be a minimum of 60mm.
Pressure Detector
The pressure detector type QBE61 is used in all steam boiler applications. The detector has a plas­tic casing to IP42. It is necessary to mount the wa­ter trap pipe supplied.
General
The detector must not be covered by lagging. Mounting instructions are printed on the packing. The permissible lengths of the measuring cable be-
tween detector and controller are given in the fol­lowing table:
Core
0.6 mm Diam. 5.5 mm 20 m
1.0 mm
1.5 mm
2
2
Outside
Diameter
6.6 mm 80 m
7.2 mm 120 m
Line
Length
Models NDF35 to NDF150Page 38
Page 39
COMMISSIONING : GENERAL
Safety
It is essential that commissioning shall be un­dertaken only by suitably qualified and experi­enced personnel. In the case of NDF burners, commissioning engineers should be experienced in commissioning forced draught oil and gas burners.
In the UK, it is a legal requirement that anyone working on gas installations, as defined in the "Gas Safety (Installation And Use) Regulations 1994", is CORGI registered.
Nu-way can accept no responsibility for conse­quential loss, damage or injury which results from a failure to follow the commissioning in­structions provided or from commissioning pro­cedures being undertaken by unqualified per­sonnel.
In An Emergency
NDF burners are designed and constructed to meet all essential requirements of the Gas Ap­pliance Directive 90/396/EEC.
When used in accordance with the instructions provided, NDF burners are unlikely to produce a hazardous condition. If, however, such a con­dition should arise in connection with the burner, the appliance or any instrument, machine or service in the vicinity of the burner, the FUEL AND ELECTRICITY SUPPLIES SHALL BE ISO­LATED IMMEDIATELY and they shall remain iso­lated until the fault has been identified and rec­tified.
Inspection
Before commissioning is begun it is important to: 1 Check that the electrical wiring is complete and
complies with all applicable Codes and Stand­ards.
2 Ensure that the fuses are fitted and of the cor-
rect ratings. 3 Check electrical earthing. 4 Verify that the gas and oil supply pipework is
correctly sized and that it has been checked
for leakage. 5 Ensure that the manual gas isolation valve at
the inlet to the gas train and the ball valve on
the oil line are operable, fully closed and leak
tight.
6 Make all personnel involved in the commis-
sioning aware of the location of the emergency gas, oil and electricity isolation points.
7 Check that fittings such as purge and test points
are available.
8 Establish that the appliance is in an appropri-
ate and safe condition to be fired; for exam­ple, that there is water in the boiler.
9 Set the appliance controls to call for heat. Check
the appliance's ventilation and flueing arrange­ments.
10 Ensure that any warning notices appropriate to
the commissioning procedure are in position.
11 Ensure that all necessary tools and test equip-
ment are available and ready for use. Essential items include a manometer or other approved pressure measuring instrument, means (which may be permanently installed or provided specifically for commissioning) of measuring the flow rates of oil and gas, equip­ment for checking the smoke number of the flue products and a means of analysing the flue products for carbon dioxide (CO2), oxygen (O2) and carbon monoxide (CO).
12 Check that all relevant documentation is avail-
able, including, where appropriate:
- The agreed plant performance specifica­tion.
- Plant drawings and pipework layouts.
- Electrical logic and wiring diagrams.
- Certificates confirming satisfactory com­pletion of procedures such as soundness testing, purging and electrical safety tests.
- Commissioning, operating, emergency shutdown and maintenance instructions for the plant.
13 Establish that the operation of plant other than
that being commissioned will not have an ad­verse effect on the operation of the plant to be commissioned and similarly, that the operation of the plant to be commissioned will not have an adverse effect on other plant.
14 Confirm that the operation of adjacent plant
and machinery will not constitute a hazard to the personnel involved in commissioning.
Models NDF35 to NDF150
Page 39
Page 40
Initial Settings
To prepare the burner for commissioning on oil
and gas:
1 Remove the cover from the air damper mo-
tor and check the cam positions referring to the appropriate diagram shown on Page 18 or 19. Adjust if necessary.
2 Remove the small plate on top of the gover-
nor section of the air/gas ratio controller. Referring to the diagram on Page 21, set the air/gas ratio on scale (1) to 0.8 by adjusting screw (1), anti-clockwise to increase, clock­wise to decrease. Set the ratio on the remain­ing scale to half a division on the positive side of '0' by adjusting screw (2) in the same way; anti-clockwise to increase, clockwise to decrease.
3 Remove the cap from the start gas governor
and set the adjusting screw approximately half way between the maximum and mini­mum settings, turning the screw clockwise to increase the setting and anti-clockwise to decrease it. Replace the cap. Never adjust the governor to its maximum setting.
4 Check and if necessary re-set the ignition
electrode gaps to 2.5 to 3 mm. Access to the burner head is explained on Page 52.
5 Ensure that oil of the correct class is avail-
able at the required temperature (on NDFR systems: refer to the table on Page 13) and pressure.
IT IS RECOMMENDED THAT THE BURNER SHOULD BE COMMISSIONED FOR OIL FIRING IN THE FIRST INSTANCE. SHOULD OIL NOT BE AVAILABLE TO THE BURNER THEN GAS COM­MISSIONING CAN PROCEED ONLY IF THE PUMP DRIVE COUPLING IS REMOVED FROM THOSE BURNERS WHERE THE OIL PUMP IS DRIVEN BY THE BURNER FAN MOTOR. IT MUST BE NOTED IN ALL CASES THAT WHEN OIL IS AVAILABLE TO THE BURNER THE UNIT MUST BE RE-COMMISSIONED ON BOTH FUELS. NO­TICE SHOULD BE MADE OF THIS FACT, BOTH AT THE BURNER AND WITHIN THE BURNER HANDBOOK AND APPLIANCE LOGBOOK.
COMMISSIONING : OIL
Burner Dry Run - Twin Pressure Jet Burners (NDFL35-25 to 100-38 Two Stage (High/ Low))
The following procedure should be followed. It is important that a complete and flawless dry run be completed before fuel is supplied to the system.
1 Check that the gas, oil and electrical power
supplies to the burner are turned off. Turn the fuel selector switch on the control panel to the oil position.
2 Check that the manual gas isolation valve at
the inlet to the gas train is closed and that the ball valve between the oil pump and fuel valves in the burner oil line is open.
3 Ensure that oil is available at the oil pump
on the burner at the required pressure and class.
4 Prime the oil pump by opening the bleed
port until air-free oil flows from it. The pump should not be rotated automatically until it has been primed as this may lead to prema­ture wear or pump seizure.
5 Open the panel door and set the burner to
low flame hold. 6 Set the air pressure switch to minimum. 7 Establish the electricity supply to the burner
and momentarily switch on the burner. Ob-
serve the rotation of the combustion air fan
motor, which should be anti-clockwise
viewed from the motor cowl end. If the di-
rection of rotation of the fan motor is incor-
rect, refer to the Section of this handbook
on Fault Finding. 8 If the fan rotation is correct switch on the
burner. 9 The burner motor will begin to run:
(a) Immediately if the system was switched
off during normal operation.
(b) On resetting the sequence control box
using the Off/On/Reset switch.
If at this stage the burner goes to lockout,
refer to the Section on Fault Finding. 10 The burner will proceed through its pre-purge
and ignition sequences. Check that an igni-
tion spark is present. If there is no spark and
the burner goes to lockout, the air pressure
switch may be at fault - refer to the Section
on Fault Finding.
Models NDF35 to NDF150Page 40
Page 41
11 Allow the burner to light momentarily. Switch
off the burner and the electrical supply to the burner.
12 The burners safety systems have now been
proven on oil firing and commissioning can proceed to the next stage.
Burner Live Run - Twin Pressure Jet Burners (NDFL35-25 to 100-38 Two Stage (High/ Low))
The instructions in this section are presented as a continuous sequence. No separate set of actions (for example, checking the flame signal) should be fol­lowed in isolation without paying particular atten­tion to any safety precautions such as isolating the electrical supply to the burner which should precede such actions. At all stages, the operation of the burner should be checked against the programming con­troller sequence diagram on Page 37.
Setting Oil Flow Rates and Air/Fuel Ratios
From this point the oil commissioning process is con­cerned with setting the high and low fire oil flow rates to appropriate values and ensuring that the combus­tion quality of the system is within acceptable limits. During this process:
AFTER EACH ADJUSTMENT check the flue gas analysis and oil flow rate.
ALWAYS use approved and calibrated test equip­ment.
NEVER rely on visual observation of the flame as the only guide to combustion quality.
1 Open the manual shut-off valve in the burner
oil line.
2 Switch the burner on. Following the pre-purge
period the burner will initiate the ignition spark and open the low fire oil valve.
3 The flame will be established and the UV cell
will begin monitoring. The burner will operate continuously at low fire.
4 Check the oil pump pressure at the pump. Ini-
tially, set the pressure to 20.7 bar (300 psi). Ob­serve the flame through the inspection window at the rear of the burner casing to ensure the flame is established around the outer edge of the diffuser plate. A continuous halo should be visible.
5 The burner is fitted with a five cam air damper
servo (refer to the diagram on Page 18). Adjust the low fire air control cam (cam 2) if neces­sary so that the appearance of the flame is sat­isfactory.
6 Sample the flue products and check the smoke
number. Adjust the low flame air cam until a clean, efficient flame is achieved.
7 Switch off the burner. The flame should go out
immediately with the oil pressure gauge falling to just above zero. Switch off the electrical sup­ply to the burner.
8 Open the control panel door and switch the
burner from low flame hold to normal run po­sition. Re-secure the panel door.
9 Establish the electrical supply and switch on
the burner. Allow the burner to proceed through its operating sequence until it is oper­ating on high fire.
10 Observe that the flame is clear and steady with
a continuous halo visible around the diffusers outer edge.
11 Sample the flue products and check the smoke
number. Adjust the high flame air cam (cam 3) until a clean and efficient flame is achieved.
12 Check the oil flow rate. The appropriate low
fire rate is 55% (1.8:1 turndown) of the high fire rate.
13 Re-adjust the pump pressure if necessary to
correct the oil flow rate at high flame.
14 The servomotor is fitted with 2 cams (refer to
the servomotor details on Page 18) which al­low independent switching of the high flame oil valve when moving from low to high flame and vice-versa. These switches are factory set but may be adjusted to improve the change over characteristics if necessary.
15 Analyse the flue products on both high and low
fire.
16 Repeat the process of checking oil flow rate,
smoke number and flue product analysis until satisfactory results are obtained at both high and low fire.
17 Switch off the burner and the electrical power
supply to the burner.
Burner Dry Run - Single Spill Back Burners
(NDFL Modulating / NDFR - All Models)
The following procedure should be followed. It is
important that a complete and flawless dry run be
completed before fuel is supplied to the system.
1 Check that the gas, oil and electrical supplies
to the burner are turned off. Turn the fuel selector switch on the control panel to the oil position.
Models NDF35 to NDF150
Page 41
Page 42
2 Check that the manual gas isolation valve at
the inlet to the gas train is closed. Do not close the ball valve at the outlet of the oil pumping set.
3 Ensure that oil is available at the oil pump
on the burner at the required pressure and class.
4 NDFL Burners: Prime the oil pump by open-
ing the bleed port until air-free oil flows from it. The pump should not be rotated automati­cally until it has been primed as this may lead to premature wear or pump failure.
5 NDFR Burners:
(a) Fill the oil pre-heater tank by removing
the hot oil filter retaining flange in the outlet pocket on top of the tank. Fill to the neck of the outlet with clean fuel oil only.
(b) Check the pre-heater thermostat set-
tings, the recommended settings are shown on Page 32.
6 Switch on the electricity supply to the burner
and check that the pump rotation is correct to the direction arrows shown on the pump face.
7 Open the manual isolation valve at the out-
let of the pumping set.
8 Open the control panel door and set the
burner for low flame hold. 9 Set the air pressure switch to minimum. 10 Remove the access lid on the modulating cam
box unit. 11 Switch on the burner at the control panel.
On NDFR burners a delay may be experi-
enced whilst the system attains temperature.
The modulating unit camshaft should now
rotate to the high flame setting, and the com-
bustion fan motor will start the air pre-purge
phase. 12 Allow the fan motor to run up to speed and
switch off the burner. Observe the rotation
of the combustion air fan motor, which
should be anti-clockwise viewed from the
motor cowl end. If the direction of rotation
of the fan motor is incorrect, refer to the Sec-
tion of this handbook on Fault Finding. 13 If the fan rotation is correct switch on the
burner.
14 The burner will proceed through its pre-purge
and ignition sequences. Check that an igni­tion spark is present. If there is no spark and the burner goes to lockout, the air pressure switch may be at fault - refer to the Section on Fault Finding.
15 During this run note the spill and line oil pres-
sures at the point of ignition. Reset the se­quence control and repeat the run if neces­sary to check these functions. If necessary, adjust the line pressure at the burner pump to 27.8 bar (400 psi) and the spill pressures to the correct figures stamped on the burner data plate.
16 Allow the burner to light momentarily. Switch
off the burner and the electricity supply to the burner.
17 The burnerís safety systems have now been
proven on oil firing and commissioning can proceed to the next stage.
Burner Live Run - Single Spill Back Burners (NDFL Modulating / NDFR - All Models)
The instructions in this section are presented as a continuous sequence. No separate set of actions (for example, checking the flame signal) should be followed in isolation without paying particular at­tention to any safety precautions such as isolating the electrical supply to the burner which should precede such actions. At all stages, the operation of the burner should be checked against the pro­gramming controller sequence diagram on Page
37. Setting Oil Flow Rates and Air/Fuel Ratios
From this point the oil commissioning process is concerned with setting the high and low fire oil flow rates to appropriate values and ensuring that the combustion quality of the system is within ac­ceptable limits. During this process:
AFTER EACH ADJUSTMENT check the flue gas analysis and oil flow rate.
ALWAYS use approved and calibrated test equip­ment.
NEVER rely on visual observation of the flame as the only guide to combustion quality.
Models NDF35 to NDF150Page 42
Page 43
MODULATING CAM BOX
Models NDF35 to NDF150
Page 43
Page 44
New NDF Modulating burners are generally sup­plied against the firing specification of the appli­ance. In this case the system and spill pressures may be pre-set and require checking and minor adjustments only. The following section describes how to set up the modulating cam box unit from the beginning. The modulating cam box is shown on Page 43.
The modulating cam layshaft can be rotated by hand by using the gearbox disengagement lever in the drive servomotor.
1 Ensure that the modulating cam arrangement
is in the low flame position. Adjust the oil cam (refer to Page 43) so that it gives ap­proximately 1.5mm throw (3mm stroke) and lock in position.
2 Check to ensure that the spill valve push rod
bears lightly against the oil cam (refer to Page
43).
3 Turning to the air cam, rotate the thumb-
screws in or out so that they give a reason­able amount of adjustment in each direction. Adjust the flexible cable (at either end if nec­essary) until the air inlet damper is fully closed (i.e. until all the slack is taken up on the ca­ble).
4 Adjust the thumbscrews to give a small open-
ing of the air damper at low flame.
5 Reset the sequence control and allow the
burner to start. Immediately the burner starts, switch the Hand/Auto selector switch to the 'Hand' position and hold low flame until the appliance is ready to accept high flame. Dur­ing this period, check and adjust the low flame oil throughput.
6 Observe the flame through the inspection
window at the rear of the burner casing to ensure the flame is established around the outer edge of the diffuser plate. A continu­ous halo should be visible. If the flame is dirty, adjust the air cam thumbscrews until the flame becomes clean.
7 After a suitable delay, inch the camshaft to
the high flame position (i.e. through 180∞) by means of the inching switch on the con­trol panel. Adjust the air cam profile by means of the thumbscrews until the air damper is now fully open. At this stage it will be found that all of the thumbscrews between low and high position will require adjusting so as to avoid over stressing the cam profile band. Once this has been done, there should be a fairly smooth profile between low and high flame positions.
8 Ensure that the flame is visually clean
throughout the modulation range at all times.
9 Check the oil consumption. If this is not cor-
rect for the full burner rating, the oil cam must be adjusted as follows: -
(a) Inch the burner to low flame and note
the spill pressure.
(b) To increase the minimum rate, adjust
as shown on Page 43.
(c) Adjust the cam to give more eccentric-
ity for more oil at high flame, and vice­versa.
(d) Return to the minimum setting and
compensate for any changes.
(e) Inch the burner to high flame and again
check the oil flow.
Continue to repeat (a) to (d) until the high flame oil rate is correct.
10 When a satisfactory flame is achieved, again
check the line and spill pressures. Check the pre-heater temperature (if fitted) and adjust if necessary.
11 Inch the camshaft back to the low flame po-
sition. The oil consumption rate should now be between 40 and 50% of the rated maxi­mum.
12 Sample the flue products and check the
smoke number. Adjust the combustion air volume as necessary.
13 Check the burner performance throughout
the range adjusting the air cam profile as necessary to give a clean and efficient flame. When a satisfactory setting has been achieved, lock the air cam thumbscrews with the grubscrews fitted in the side face of the cam body. Refit the modulating cam unit ac­cess cover.
14 Switch off the burner and the electricity sup-
ply to the burner.
Models NDF35 to NDF150Page 44
Page 45
COMMISSIONING : GAS
Burner Dry Run - NDFL/R All Models
The following procedure should be followed. It is important that a complete and flawless dry run be completed before fuel is supplied to the system.
IT IS RECOMMENDED THAT THE BURNER SHOULD BE COMMISSIONED FOR OIL FIRING IN THE FIRST INSTANCE. SHOULD OIL NOT BE AVAILABLE TO THE BURNER THEN GAS COM­MISSIONING CAN PROCEED ONLY IF THE PUMP DRIVE COUPLING IS REMOVED FROM THOSE BURNERS WHERE THE OIL PUMP IS DRIVEN BY THE BURNER FAN MOTOR. IT MUST BE NOTED IN ALL CASES THAT WHEN OIL IS AVAILABLE TO THE BURNER THE UNIT MUST BE RE-COMMISSIONED ON BOTH FUELS. NO­TICE SHOULD BE MADE OF THIS FACT, BOTH AT THE BURNER AND WITHIN THE BURNER HANDBOOK AND APPLIANCE LOGBOOK.
Important Note Regarding Combustion Air Set­tings: -
IF THE BURNER HAS ALREADY BEEN COMMIS­SIONED ON OIL, THE COMBUSTION AIR SET­TING MUST NOT BE RE-ADJUSTED. THE GAS RATE MUST BE MATCHED TO THE EXISTING SETTINGS.
NDFR firing ëGí fuel 1 Check that the gas, oil and electrical power
supplies to the burner are turned off. Turn the fuel selector switch on the control panel to the gas position.
2 Check that the manual gas isolation valve at
the inlet to the gas train and the ball valve in the oil line (NDFL) are closed.
3 On NDFR burners firing class 'G' fuel, if the
dummy inner assembly is to be used (see Page
29), open the hinged extension and remove the oil lance from the gas inner assembly. The lance and nozzle should be flushed through with clean class 'D' oil immediately to pre­vent blockage by the cooling fuel oil.
Fit the three port dummy inner assembly manifold supplied as an option. This will en­able the oil pumping and heating unit to con­tinue to keep the oil system up to tempera­ture without danger of oil being released into the appliance whilst firing the burner on gas.
Fit the inner assembly plug to the back of the gas inner assembly. This maintains the cross sectional area of the annular air passage within the primary air tube, as if the oil lance is fitted.
4 Check that the gas pipework between the
plant isolation valve and the safety shut-off valves has been tested for soundness and purged in accordance with an appropriate Procedure, for example IGE/UP/1 ëSoundness testing and purging on industrial and com­mercial premisesí.
5 Open the control panel cover and set the
burner for low flame hold. (On modulating burners not fitted with a low flame hold switch, set the Hand/Auto switch to the ëHandí position).
6 If a gas booster is fitted, ensure that it is turned
on.
7 Remove the cover from the low gas pressure
switch and fit a temporary link between ter-
minals 2 and 3. Replace the cover. 8 Set the air pressure switch to minimum. 9 Establish the electrical supply to the burner
and momentarily switch on the burner. Ob-
serve the rotation of the combustion air fan
motor, which should be anti-clockwise
viewed from the motor end. If the direction
of rotation of the fan motor is incorrect refer
to the Section of this handbook on Fault Find-
ing. 10 If the fan rotation is correct switch on the
burner. 11 The burner motor will begin to run:
(a) Immediately if the system was switched
off during normal operation.
(b) On pressing the reset button on the
control box.
If at this stage the burner goes to lockout,
refer to the Section on Fault Finding. 12 The burner will proceed through its ignition
sequence. Check that an ignition spark is
present. If there is no spark and the burner
goes to lockout the air pressure switch may
require adjustment - refer to the Section on
Fault Finding. 13 The ignition spark will cease and the system
will go to lockout. Switch off the burner and
the electrical power supply to the burner.
Models NDF35 to NDF150
Page 45
Page 46
14 Switch off the gas booster (if fitted). Remove
the temporary link fitted to the low gas pres­sure switch and replace the cover.
15 The burner's safety systems have now been
proven and commissioning can proceed to the next stage.
Burner Live Run - NDFL/R All Models
General
The instructions in this section are presented as a continuous sequence. No separate set of actions (for example, checking the flame signal) should be followed in isolation without paying particular at­tention to any safety precautions such as isolating the electrical supply to the burner which should precede such actions. At all stages, the operation of the burner should be checked against the pro­gramming controller sequence diagram on Page
37. Before proceeding, check again that: 1 The electrical wiring is complete and com-
plies with all relevant Codes and Standards.
2 All fuses are fitted and are of the correct rat-
ings.
3 The gas and oil supply pipework is correctly
installed and has been leak tested. If, at any time during commissioning, there is a SMELL OF GAS the gas and electricity supplies must be isolated and the leak sealed before pro­ceeding.
4 The appliance is in an appropriate and safe
condition to be fired.
5 The appliance controls are set to call for heat.
Selecting Gas
1 Ensure that the ball valve in the oil line is
closed.
2 Turn the fuel selector switch on the control
panel to the gas position.
Gas Supply Pressure
The supply pressure at the inlet to the burner shall not be less than that required for the maximum required continuous output from the burner, and not more than 100 mbar (up to NDF100-38) or 200 mbar (NDF100-41 and upwards). Refer to the gas inlet pressure graphs (running pressures) con­tained in the appendix of this handbook. Before proceeding with commissioning:
1 Fit a manometer or other approved pressure
measuring instrument to the pressure test point on the upstream side of the first safety shut-off valve.
2 Open the manual gas isolation valve at the
inlet to the gas train.
3 Check that the gas pressure is adequate.
Establishing the Start Gas Flame
1 Remove the control panel cover and remove
the pilot check link. Replace the cover.
2 Establish the electrical supply to the burner
and switch on the burner.
3 The burner controller will run through its se-
quence, initiating the ignition spark and opening the start gas safety shut-off valve.
4 The start gas flame will be established and
the UV cell will begin monitoring. The burner will operate continuously at start gas rate. If the burner goes to lockout, increase the start gas rate slightly at the governor and reset the burner.
5 Confirm the leak tightness of the pipework
downstream of the start gas safety shut-off valve using a proprietary detection fluid.
6 Switch off the burner. Switch on the burner
and allow the ignition sequence to be re­peated, confirming that the start gas flame is reliable.
7 Switch off the burner and the electrical power
supply to the burner. Remove the control panel cover and replace the pilot check link. Replace the cover.
Setting Main Flame Rates and Air/Gas Ratios
From this point the gas commissioning process is concerned with setting the main and start gas flow rates to appropriate values and ensuring that the combustion quality of the system is within accept­able limits. During this process:
AFTER EACH ADJUSTMENT check the flue gas analysis and gas flow rate.
ALWAYS use approved and calibrated test equip­ment.
NEVER rely on visual observation of the flame as the only guide to combustion quality.
Models NDF35 to NDF150Page 46
Page 47
1 Fit a manometer or other approved pressure
measuring instrument to the gas pressure test point nearest to the burner head. The rela­tionship between the pressure at this point and burner heat input is shown in the graphs in the Appendix. This information is provided only as a guide and it should not be used in conjunction with pressure measurements as a substitute for accurate measurement of gas flow rate using, for example, a gas meter.
2 Ensure that the flue gas analysis equipment
is functioning.
3 Close the manual gas isolation valve at the
inlet to the gas train to an opening of ap­proximately 20%.
4 Set the gas inlet pressure switch to its mini-
mum value.
5 With the burner set for low flame hold (hand
operation), re-establish the electrical supply and switch on the burner.
6 The burner controller will run through its se-
quence, initiating the ignition spark and opening the start gas safety shut-off valve. The start gas flame will be established and the UV cell will begin monitoring.
7 The main gas control valve will open and low
fire will be established. Open the upstream manual valve slowly until it is fully open, observing the CO level.
8 If the CO level is too high (see below) reset
the low fire adjusting screw (2) on the air/gas ratio controller (refer to the diagram on Page
21) until an acceptable figure is achieved. In extreme cases the adjustment on screw (2) may be exhausted without achieving an ac­ceptable CO level. In this event, reset the high fire adjusting screw (1) until an accept­able CO level is achieved.
9 Confirm the leak tightness of the pipework
downstream of the main gas safety shut-off valve using a proprietary detection fluid.
10 Switch off the burner and the electrical power
supply to the burner.
11 Open the control panel cover and switch the
burner from low flame hold to normal run position. On modulating and sliding high/low burners select the ëAutoí position of the Hand/ Auto switch. Close the cover.
12 Establish the electrical supply to the burner
and switch on the burner. The burner con-
troller will run through its sequence. Low fire
will be established, expanding to main flame.
Monitor the flame visually during the transi-
tion from low to high fire. If the flame be-
comes more intense and compact this indi-
cates an excess of combustion air. If the flame
becomes large and shapeless, this indicates
an excess of fuel. Either condition is accept-
able at this stage provided that the flame is
stable and the commissioning process con-
tinues immediately. If in doubt, switch off the
burner and adjust screw (1) on the air/gas
ratio controller appropriately before restart-
ing the burner. 13 With the burner running on high fire, meas-
ure the flue CO2 level and adjust screw (1) to
bring the level to an acceptable level. Note
that at this stage the burner may be overfiring
the appliance and producing excessively high
levels of CO. Check the level of O2 to con-
firm the CO2 reading. 14 Set the burner for low flame hold (ëHandí
operation) and switch on the burner. Allow
the burner controller to run through its cycle
until the burner is running on low fire. 15 Adjust the low fire adjusting screw (2) to bring
the CO2 level to an acceptable level. 16 Changing the low fire setting on the air/gas
ratio controller will have a slight effect on
the high fire setting. It may therefore be nec-
essary to repeat steps 13 to 15 several times
in order to achieve acceptable levels of CO
at both firing rates. 17 With the burner running on high fire, check
the gas flow rate with an appropriate instru-
ment, ensuring that the instrument has been
calibrated before use. If the flow rate is to be
measured using the main site gas meter or a
supplementary meter ensure that all other
gas appliances served by that meter are iso-
lated.
2
Models NDF35 to NDF150
Page 47
Page 48
18 Check the gas flow rate with the burner run-
ning on low fire. The appropriate low fire rate is governed by the low fire combustion air setting achieved during the oil commis­sioning phase. The turndown between high and low fire should therefore mirror the fig­ure achieved during this phase. If oil is una­vailable and the burner is commissioned for gas firing only, then the gas rate can be ad­justed by varying the low and high fire posi­tions of the air damper. In this case care should be taken not to exceed the limits of the burner performance envelope shown in the Appendix.
19 Analyse the flue products on both high and
low fire.
Setting the Start Gas rate
Warning: ­Extended firing on start gas rate only can lead to
a build up of volatile gases within the appliance combustion chamber. Running should be kept to a maximum of 5 MINUTES ONLY.
1 Switch off the burner and the electrical power
supply to the burner.
2 Remove the control panel cover and remove
the pilot check link. Replace the cover.
3 Establish the electrical supply to the burner
and switch on the burner. Allow the burner to light and establish the start gas flame.
4 Check the gas flow rate. The appropriate set-
ting is usually found between 25 and 30% of the main flame gas rate. The start gas rate must never be set at a level higher than 33%.
5 If it is necessary to adjust the start gas rate,
turn the adjusting screw in the start gas pres­sure governor clockwise to increase the gas rate and anti-clockwise to reduce it. Make small adjustments and check the gas rate af­ter each change.
6 Switch off the burner and the electrical power
supply to the burner. Remove the control panel cover and replace the pilot check link. Replace the cover.
Setting the High Gas Pressure Switch
1 Remove the cover from the high gas pres-
sure switch.
2 Establish the electrical supply to the burner
and switch on the burner. Allow the burner to proceed through its operating sequence until it is operating on high fire.
3 Turn the adjusting dial on the pressure switch
anti-clockwise slowly until the switch trips, causing the pressure switch indicating light to be illuminated and the burner to shut down.
4 Turn the adjusting dial approximately 20%
clockwise.
5 Refit the cover and reset the pressure switch
by pressing the button on the cover. The burner will restart.
Setting the Low Gas Pressure Switch
1 Switch off the burner and the electrical power
supply to the burner.
2 Remove the cover from the low gas pressure
switch.
3 Establish the electrical supply to the burner
and switch on the burner. Allow the burner to proceed through its operating sequence until it is operating on high fire.
4 Turn the adjusting dial on the pressure switch
clockwise slowly until the switch trips, caus­ing the burner to shut down. Turn the ad­justing dial anti-clockwise slowly until the burner restarts and main flame is established.
FINAL COMMISSIONING STAGES - OIL AND GAS
Checking the Flame Signal
1 Remove the control panel cover and discon-
nect the flame signal check link.
2 Connect a DC micro-ammeter across the ter-
minals.
3 Establish the electrical supply to the burner
and switch on the burner. Allow the burner to light and operate normally.
4 Observe the reading on the ammeter at all
firing levels including start gas. A steady read­ing in excess of 7 microamps is satisfactory. Lower readings may cause intermittent burner lockout and indicate a need for ad­justment of the burner settings - refer to the Section on Fault Finding.
5 Switch off the burner and the electrical power
supply to the burner. Disconnect the amme­ter and replace the flame signal check link. Replace the control panel cover.
Setting the Air Pressure Switch
1 Remove the air pressure switch cover.
Models NDF35 to NDF150Page 48
Page 49
2 Fit a manometer or other approved pressure
measuring instrument to the pressure switch to enable a comparison to be made between the pressure switch indicator and the meas­ured pressure.
3 Remove the control panel cover and remove
the low fire hold link. Replace the cover.
4 Establish the electrical supply to the burner
and switch on the burner. Allow the burner to proceed through its sequence until it is operating on low fire.
5 Increase the pressure switch setting slowly
until the flame is extinguished and the burner goes to lockout.
6 Turn the dial down one division and reset
the burner. If lockout occurs again, turn the dial down a further division and reset the burner. Repeat this process until the burner lights and runs satisfactorily.
7 Turn the adjusting dial down a further two
divisions.
8 Switch off the burner and the electrical power
supply to the burner. Remove the manom­eter. Replace the pressure switch cover.
9 Remove the control panel cover and replace
the low fire hold link. Replace the cover.
Modulating Control : Landis & Staefa RWF32
The RWF32 controller has been specifically de­signed for the control of boiler temperature or steam pressure in oil and gas fired plant.
The unit is normally mounted in the side face of the burner panel and is protected by a clear plas­tic cover, which can be swung downwards for ac­cess to the setting controls.
By using the appropriate setting range insert, the controller is configured for a controlling value and required setting range. This setting range insert forms part of a measuring bridge on the detector side and also carries the setting scale. The setting unit itself is an integral part of the controller.
In addition to the setpoint slider, further setting controls are located beneath the silver fascia plate situated above the digital display unit. All the set­tings can be adjusted whilst the burner is in opera­tion.
Three LEDs indicate the following operational sta­tus: -
Control ON/OFF (0-1) Control Pulse OPEN (II) / CLOSED (I)
The digital display below the LEDs gives the set value / actual value deviation as a percentage of the inserts setting range up to +/- 19%. Measuring and display takes place at 2 second and intervals and in 1% steps.
Settings : General
The setting slider should be adjusted to the setpoint temperature or pressure.
Before and during adjustments : ­1 Write down the setting values found on the
controller units supplied. 2 Alter only one parameter at a time (i.e. do
not alter Xp, Tv and Tn at the same time). 3 Make corrections in small steps only. 4 Make further adjustments only after the pre-
vious adjustment has produced a clear reac-
tion. An increase in the parameter Xp produces greater
control stability but slows down the system re­sponse to load or setpoint changes.
A decrease in the parameter Xp improves the sys­tems response to load changes, but the control sta­bility may suffer i.e. control oscillations may oc­cur.
Commissioning of the plant will be considerably simplified and accelerated when, during the set­ting operations, the load conditions can be kept fairly constant, thus making it easier to recognise clearly the control system's response to load or setpoint changes.
For most general applications we recommend the settings listed in the table on Page 36. However should these settings not prove to be sufficient then the following procedures can be carried out.
Adjustments in the case of a slow correcting
response
Reduce the set values in a stepwise fashion, allow­ing the system time to settle before making further adjustments. Firstly reduce only Xp (down to 5%). If this is not satisfactory then reduce Tv (down to
0) and finally Tn.
Adjustments in the case of an excessively fast
correcting response
Usually in connection with control oscillations, the selected set values should be increased in a stepwise fashion, again allowing the system to sta­bilise before proceeding further. Firstly increase Xp, then Tv (up to approximately 3) and finally Tn until stability is reached.
Models NDF35 to NDF150
Page 49
Page 50
A data sheet containing in depth information on the RWF 32 and its operation is available upon request.
Final Checks
1 Check that all covers have been replaced and
that all locking devices are secure.
2 Check the operation of the appliance con-
trol instruments and safety interlocks.
3 Ensure that the appliance safety controls and
any other interlocks are set to safe limits. 4 COMMISSIONING IS NOW COMPLETE. 5 Establish the electrical supply to the burner
and switch on the burner. Allow the burner
to proceed through its operating sequence
until it is operating on high fire. The burner
will now operate normally until:
(a) It is switched off by the appliance con-
trols. (b) It is switched off manually. (c) There is an electrical power failure. In
this event the burner will restart and
run normally when power is restored.
No manual intervention is required.
On Completing Commissioning
When commissioning has been completed satis­factorily the commissioning engineer shall prepare a report, which shall contain the following:
1 Details of any modifications made to the sys-
tem, together with revised drawings if nec­essary.
2 Customer and plant details, including any
serial numbers.
3 Operating levels and settings, including flue
gas analysis information.
This report shall be passed to the person responsi­ble for the plant. This responsible person shall en­sure that:
1 All personnel concerned with operating, su-
pervising and maintaining the plant receive instruction covering:
- The way in which the plant operates
and the locations and functions of the
plant's safety systems.
- The correct light-up and shutdown pro-
cedures.
- Adjustment of operating variables.
- Checking of plant interlocks.
- The plant's maintenance requirements.
- The actions to be taken in the event of a fault condition.
2 Clear light-up and shutdown procedures are
displayed on the plant and that the pipes, valves and switches involved are clearly marked.
3 CLEAR AND CONCISE EMERGENCY SHUT-
DOWN PROCEDURES ARE DISPLAYED.
FUEL CHANGEOVER PROCEDURE
Note that on completion of the commissioning procedure detailed above the burner is set for gas firing. The procedure to be followed when switch­ing fuels during normal operation is as follows:
Switching From Gas To Light Oil
1 Switch off the burner and the electrical power
supply to the burner. 2 Close the manual gas isolation valve. 3 Open the ball valve in the oil line. 4 Turn the fuel selector switch on the control
panel to the oil position. 5 If the burner has been operated on gas for a
prolonged period, it may be necessary to refit
the burner oil pump coupling and re-prime
the pump. 6 Establish the electrical supply to the burner
and switch on the burner. Allow the burner
to proceed through its operating sequence
until it is operating on high fire.
Switching From Gas To Heavy Oil
1 Switch off the burner and the electrical power
supply to the burner. 2 Close the manual gas isolation valve. 3 On burners which have been firing with the
optional dummy oil inner assembly installed,
remove this assembly and the inner assem-
bly plug. Replace them with the normal oil
lance. 4 Ensure that oil is available at the required
temperature (refer to the table on Page 13)
and pressure. 5 Turn the fuel selector switch on the control
panel to the oil position. 6 Establish the electrical supply to the burner
and switch on the burner. Allow the burner
to proceed through its operating sequence
until it is operating on high fire.
Models NDF35 to NDF150Page 50
Page 51
Switching From Light Oil To Gas
Flame Detector
1 Switch off the burner and the electrical power
supply to the burner. 2 Close the ball valve in the oil line. 3 Open the manual gas isolation valve. 4 Turn the fuel selector switch on the control
panel to the gas position. 5 Establish the electrical supply to the burner
and switch on the burner. Allow the burner
to proceed through its operating sequence
until it is operating on high fire. If the burner
has been operating on oil for a prolonged
period it may be necessary to purge the gas
line of air.
Switching From Heavy Oil To Gas
1 Switch off the burner and the electrical power
supply to the burner. This will also isolate the
oil pump and preheater. 2 SAFETY WARNING : CLASS ëGí OIL BURN-
ERS OPERATE WITH OIL AT 140∞C FOR AT-
OMISATION. THE BURNER SYSTEM
SHOULD BE ALLOWED TO COOL BEFORE
ATTEMPTING THIS OPERATION.
If the optional dummy inner oil assembly is
to be used, remove the oil lance and replace
it with the dummy inner oil assembly and
inner assembly plug. 3 Open the manual gas isolation valve. 4 Turn the fuel selector switch on the control
panel to the gas position. 5 Establish the electrical supply to the burner
and switch on the burner. Allow the burner
to proceed through its operating sequence
until it is operating on high fire. If the burner
has been operating on oil for a prolonged
period it may be necessary to purge the gas
line of air.
ROUTINE SAFETY CHECKS
THESE CHECKS SHOULD BE CARRIED OUT ONLY BY APPROPRIATELY QUALIFIED AND EX­PERIENCED PERSONNEL
Combustion Air
Check that the plant room is well ventilated at all times and inspect the burner air inlet frequently to ensure that there is no obstruction to the air flow.
1 Remove the UV cell from the burner casing
and cover the quartz glass envelope to ex­clude light. Care should be taken not to touch the glass.
2 Establish the electrical supply to the burner
and switch on the burner. The burner should go to lockout at the end of the ignition cycle.
3 Switch off the burner and the electrical power
supply to the burner. Replace the UV cell. Establish the electrical supply to the burner and switch on the burner. Reset the lockout.
Valve Proving System (If Fitted)
1 Introduce a gas leak by slackening the screw
in the pressure test point between the main valves.
2 Switch on the electrical supply to the burner
and the burner itself. The valve proving sys­tem should lock out through failing gas pres­sure as the burner runs through its start cy­cle.
3 Re-tighten the screw in the pressure test point
and reset the lockout button on the valve proving system.
ROUTINE MAINTENANCE
ALWAYS SWITCH OFF THE ELECTRICAL POWER AND FUEL SUPPLIES TO THE BURNER BEFORE CARRYING OUT MAINTENANCE.
Combustion Air Fan - All Models
Remove the burner top cover to gain access to the combustion air fan. Clean the fan blades with a stiff brush, taking care not to damage them. In­spect the burner air inlet frequently and ensure that there is no obstruction to the air flow.
Replacing The Air/Gas Ratio Controller - All Models
If mechanical or electrical failure necessitates re­placement of the air/gas ratio controller, the burner must be recommissioned to ensure that it is re­turned to the correct combustion and throughput settings. Replacement of the air/gas ratio control­ler and the subsequent recommissioning shall be undertaken only by appropriately qualified and experienced personnel.
Models NDF35 to NDF150
Page 51
Page 52
Burner Inner Assembly - Twin Pressure Jet Burners
To gain access to the burner inner assembly, first remove the multi-pin plug from the socket on the control system. Remove the locking nut securing the hinged extension and open this extension. Disconnect the ignition leads. Remove the caphead screw which secures the burner inner assembly to the hinged extension and withdraw the inner as­sembly, taking care not to damage it. Clean the air diffuser and gas nozzle with a stiff brush. Clean and reset the ignition electrodes and check that they are not cracked or worn. Renew the elec­trodes if necessary. Remove the oil nozzle, disman­tle it and wash the internal filter and other com­ponents in a suitable solvent. Remove any remain­ing deposits with a clean, lint-free cloth. The oil nozzle should be replaced after 2000 hours op­eration. Reverse the order of actions detailed above to replace the inner assembly and prepare the burner for normal operation.
Burner Inner Assembly - Single Spill Back Burners
To gain access to the burner inner assembly, first remove the multi-pin plug from the socket on the control system. Remove the locking nut securing the hinged extension and open this extension. Disconnect the ignition leads. Remove the two screws which secure the oil manifold within the hinged extension. Remove the four bolts which locate the inner assembly and withdraw the as­sembly, taking care not to damage it. Clean the air diffuser and gas nozzle with a stiff brush. Clean and reset the ignition electrodes and check that they are not cracked or worn. Renew the elec­trodes if necessary. Remove the oil gun, complete with nozzle, from the centre of the inner assem­bly. Remove the nozzle from the gun and wash it in a suitable solvent, removing any remaining de­posits with a clean, lint-free cloth. The oil nozzle should be replaced after 5000 hours operation. Reverse the order of actions detailed above to re­place the inner assembly and prepare the burner for normal operation.
Oil Filters - NDFL
If the filter fitted in the oil supply line has a dispos­able element this should be replaced at least once a year, more frequently if this is dictated by the condition of the fuel or other local conditions. If the filter element is re-usable it should be cleaned at appropriate intervals.
After filter cleaning operations it will be necessary to remove air from the system by bleeding the pump.
Oil Filters - NDFR
The oil filter located on top of the preheater should be removed and cleaned in paraffin or another suitable solvent.
SAFETY WARNING : CLASS ëGí OIL BURNERS OPERATE WITH OIL AT 140∞C FOR ATOMISA- TION. THE BURNER SYSTEM SHOULD BE TAKEN OFF LINE AND ALLOWED TO COOL BEFORE ATTEMPTING THESE TASKS.
In the case of the cold oil filter, remove the plug from the sump and drain off any sludge and/or water present at six-weekly intervals. The cleaning knob on this filter should be rotated daily. If the filter fitted in the oil supply line has a disposable element this should be replaced at least once a year, more frequently if this is dictated by the con­dition of the fuel or other local conditions. If the filter element is re-usable it should be cleaned at appropriate intervals. After filter cleaning opera­tions it will be necessary to remove air from the system by bleeding the pump.
Oil Preheater - NDFR Only
Regular checks should be made to ensure that the oil temperature is maintained at the correct level (refer to the table on Page 13).
FAULT FINDING
Any changes made in control settings as a result of identifying and remedying fault conditions as described below may necessitate partial or com­plete recommissioning. Recommissioning shall be undertaken only by appropriately qualified and experienced personnel.
Models NDF35 to NDF150Page 52
Page 53
Burner Motor Fails To Start
y
y
s
g
t
t
pp
t
y
y
y
y
y
y
p
y
y
pp
g
y
g
g
g
y
y
y
y
y
p
y
g
y
y
Possible Reason Remed
Reinstate power suppl No power supply to burner
Power supply to burner OK
Gas train disconnected Check and reconnec Appliance controls incorrectl
set Gas supply isolated Restore suppl Low gas pressure Check and rectif Low gas pressure switch incorrectl
set Air pressure switch not in start
osition Fuel selector switch incorrectl
set Oil line ball valve incorrectl
set Valve proving system locked out Oil preheater limit thermostat tri
ed
Low oil temperature
To check that the air pressure switch is in the "start" position:
1 Switch off the electrical power supply to the
burner.
2 Remove the plug-in assembly from the con-
trol box base.
3 Using a suitable instrument, check for elec-
trical continuity between the following ter­minals:
Satronic TMG 740 Terminals 16 and 17 Landis & Staefa LFL 1.333 Terminals 13 and
14.
Check fuse Check burner correctly wired Check appliance controls callin
for hea Check burner not locked ou Check motor overload not tri
ed
Check and adjust as necessar
Check and adjust as necessar
Check as below
Check and reset
Check and reset
Check and reset
Check and rectify
Check thermostat settin
4 If the air pressure switch is not in the start
position turn the setting dial clockwise fully to the maximum setting. Check again for continuity between the above terminals. If there is no continuity the pressure switch is
faulty and should be renewed. If a gas booster is fitted: 1 Ensure that the low inlet gas pressure switch
is not locked out. 2 Check that the booster drive belt is fitted. 3 Verify that the booster motor is rotating cor-
rectly.
Fan Starts And Burner Goes To Lockout
(1) No Ignition
Possible Reasons Remed
Air pressure switch settin Ignition electrode settin Cracked electrode insulation HT lead disconnected or dama Ignition transformer fault Programming controller fault
s incorrect
s incorrect
ed
Possible Reasons Remed
Gas supply isolated
ressure too low Investigate and remed
Gas Air flow incorrect for
as flow
Valves fail to open
Manual isolation valve closed Carbon on diffuser Clean
Reset
Reset
Renew electrode
Reconnect or renew as necessar
Renew electrode
Check and renew as necessar
(2) No Flame - Gas Firing
Check gas supply to burner
Check and adjust as necessar Check wiring, replace valves if fault
Open valve
Models NDF35 to NDF150
Page 53
Page 54
(3) No Flame - Oil Firing
y
p
p
y
y
y
p
p
y
p
y
y
y
y p
g
t
y
g
y
Possible Reasons Remed
Oil supply interrupted
Pum
coupling failed Replace Pump drive motor (if fitted) failed Oil
ressure too low Investigate and remed
Valves fail to open
Oil pump fault Filter blocked Clean or re Nozzle blocked Clean or re Carbon on diffuser Clean Oil temperature too low
Check oil supply to burner
Check wiring, fuses etc.
Check wiring, replace valves if fault Replace
lace lace
Check and rectify
Start Flame Failure
Failure of the start rate flame will produce lockout. Confirm start flame failure by checking the flame signal at the appropriate stage. If the flame signal is low, the cause may be:
1 A dirty or wrongly positioned (it must face
towards the flame) glass envelope on the UV cell.
2 A fault in the UV cell or its wiring - check
and replace if necessary.
3 The flame signal check link has been re-
moved - check and replace.
4 There is insufficient fuel under ignition con-
ditions to allow the flame to be detected adequately - adjust the flow rate.
5 Partial blockage of the oil nozzle - check and
clean if necessary.
6 Carbon on the air diffuser - check and clean
if necessary.
Incorrect Rotation Of Burner Motor
The motor should rotate anti-clockwise as viewed from the motor end. If the direction of rotation is incorrect interchange two phases in the three­phase power supply. If this does not correct the direction of rotation the motor should be renewed.
If it is necessary to change this motor or the com­bustion air fan the following procedure should be followed:
1 Switch off the burner and the electrical power
supply to the burner.
2 Disconnect the multi-pin plug from the
socket on the control system.
3 Remove the screw which holds the control
system to its mounting bracket.
4 Lift the control system from its mounting
bracket and rest it on the gas valve train.
5 The securing studs, fixing nuts and bolts on
the mounting flange are now readily acces­sible.
Main Flame Is Not Established
Possible Reasons Remed
Fuel pressure or flow too low Main gas/oil valve fails to o
en Programming controller fault Low fire hold link removed Gas train gasket incorrectl Air settin
ositioned
incorrect Rese
Check fuel supply to burner Check wiring, replace valve if fault Check and renew as necessar
Replace link
Reposition
Burner Motor Only Runs Continuously
Possible Reasons Remed
Air control damper motor failed Air control damper cam loose Microswitch fails to chan
eover Damper motor incorrectl
wired
Renew
Tighten
Renew
Rewire
SPARE PARTS
For spare parts contact Nu-way's Parts And Com­ponents Division at the address and telephone number listed on the rear cover of this manual. To avoid delays, please provide the burner model and serial numbers.
Models NDF35 to NDF150Page 54
Page 55
APPENDIX
C
This appendix contains additional information and documentation including:
- Burner head details and dimensions
- Electrode setting details
- Burner performance envelopes
- Commissioning sheets (oil and gas). Blank sheets are provided which must be filled in by the engineer on completion of commis­sioning.
For two stage (high/low) burners the pressure, combustion quality and temperature data should be obtained for both high and low fire settings for both oil and gas firing.
For fully modulating burners additional data at intermediate positions in the operating range between high and low fire are required.
A copy of the completed sheet must be sent to the appliance manufacturer.
- Burner service record sheets , to enable the user to maintain a service history
- Blank ëNotesí pages, to allow the user to make any relevant notes, comments or other relevant information.
Burner Head Dimensions (accompanies drawings on Pages 56 and 57)
Model
AB
NDF35-25 178 171 149 70 6 6.0 NDF35-34 178 171 149 70 6 6.0 NDF35-38 178 171 149 70 6 6.0 NDF50-28 219 206 190 89 8 9.5 NDF50-34 219 206 190 89 8 9.5 NDF50-38 219 206 190 89 8 9.5 NDF60-28 219 206 190 89 8 9.5 NDF60-34 219 206 190 89 8 9.5 NDF60-38 219 206 190 89 8 9.5 NDF80-28 254 228 203 89 8 9.5 NDF80-34 254 228 203 89 8 9.5 NDF85-38 254 228 203 89 8 9.5 NDF100-38 254 228 203 89 8 9.5 NDF100-41 305 279 248 89 8 12.7 NDF100-44 305 279 248 89 8 12.7 NDF125-36 305 279 248 89 8 12.7 NDF125-41 305 279 248 89 8 12.7 NDF125-44 305 279 248 89 8 12.7 NDF150-36 305 279 238 89 8 12.7 NDF150-41 305 279 238 89 8 12.7 NDF150-44 305 279 238 89 8 12.7
Dimension
DNo. E F
Models NDF35 to NDF150
Page 55
Page 56
Burner Head Details : Twin Pressure Oil Jet Models
Models NDF35 to NDF150Page 56
Page 57
Burner Head Details : Single Spill Back Oil Nozzle Models
Models NDF35 to NDF150
Page 57
Page 58
Electrode Setting Detail
Models NDF35 to NDF150Page 58
Page 59
Performance Envelopes : NDF 35, NDF 50 And NDF 60
Models NDF35 to NDF150
Page 59
Page 60
Performance Envelopes : NDF 80/85 And NDF 100
Models NDF35 to NDF150Page 60
Page 61
Performance Envelopes : NDF 100 And NDF 150
Models NDF35 to NDF150
Page 61
Page 62
Oil Commissioning Sheet
p
p
The details below are to to be completed by the Commissioning Engineer. The completed sheet must then be
Installer's Name :
Address :
Site Address :
hotocopied and a copy forwarded to the appliance manufacturer.
Appliance
Burner
Type : Size :
Type : Size :
Serial Number Serial Number
:
:
Commissioning Date :
Guarantee Expiry Date :
Fuel Oil Type :
Oil pressure upstream of pump :
Standing bar or psi Running bar or psi
Firing Rate Intermediate Positions
Pressure at burner
Oil
Air
High
Fire
Oil rate
Low
Fire
Units
bar or
mbar or
ins w.c. kg/h or
lb/h
MW or
Heat input
MJ/h or
Btu/h
O
2
CO
2
CO
Flue Temp.
Ambient Temp.
Temp. Difference
% Dry
Basis
% Dry
Basis
ppm Dry
Basis °C or
°C or
°C or
1
si
°F
°F
°F
Efficiency
1
Note : Where a choice of measurement units is shown, delete those not applicable
Models NDF35 to NDF150Page 62
%
Page 63
Gas Commisioning Sheet
g
p
The details below are to to be completed by the Commissioning Engineer. The completed sheet must then be
Installer's Name :
Address :
Site Address :
hotocopied and a copy forwarded to the appliance manufacturer.
Appliance
Burner
Type :
Type :
Size :
Size :
Commissioning Date :
Guarantee Expiry Date :
Fuel Gas Type :
Gas pressure upstream of main governor :
mbar or ins w.g. mbar or ins w.g.Standing Running
Firing Rate
Pressure at burner
Gas
Air
High
Fire
Gas rate
Heat input
O
2
CO
2
CO
Flue Temp.
Ambient Temp.
Temp. Difference
Intermediate Positions
Serial Number Serial Number
:
:
Low
Fire
1
Units
mbar or
ins w.
mbar or
ins w.c.
3
/h or
m
3
MW or MJ/h or
Btu/h
% Dry
Basis
% Dry
Basis
ppm Dry
Basis °C or
°F
°C or
°F
°C or
°F
.
Efficiency
1
Note : Where a choice of measurement units is shown, delete those not applicable
Models NDF35 to NDF150
%
Page 63
Page 64
BURNER SERVICE RECORD
reenignEgnicivreSehtybdetelpmoceboterawolebsliatedehT
cebotteehssihT
etaDecivreSfOsliateDerutangiS
tnemtsujda/ecivreshcaegniwollofdengisdnadetelpmo
Models NDF35 to NDF150Page 64
Page 65
BURNER SERVICE RECORD
reenignEgnicivreSehtybdetelpmoceboterawolebsliatedehT
cebotteehssihT
etaDecivreSfOsliateDerutangiS
tnemtsujda/ecivreshcaegniwollofdengisdnadetelpmo
Models NDF35 to NDF150
Page 65
Page 66
NOTES
Models NDF35 to NDF150Page 66
Page 67
NOTES
Models NDF35 to NDF150
Page 67
Page 68
Enertech Limited, P O Box 1, Vines Lane Droitwich, Worcestershire, WR9 8NA
Tel: +44 (0) 1905 794331 Fax: +44 (0) 1905 794017 Email: [email protected] Web: www.nu-way.co.uk
Loading...