34. Working ranges .................................................................................................................. 34
2
E. 30.07.07 • G. 07.06.11
Page 3
1. General information
Installation of a dual fuel burner must be performed in accordance with extensive regulations and guidelines. It is therefore the duty of the installer to be familiar with all applicable regulations and requirements.
Installation, start-up and maintenance must be performed with utmost care.
The burner must not be operated in rooms with high levels of air humidity (laundry rooms), dust or corrosive
vapours. The boiler room must be ventilated accordingly with ventilation air.
Light oil in accordance must be used. The burners are suitable for combustion of natural gas or liquid gas
and are in compliance with European standard EN 676 and 267.
2. Scope of delivery
Before installing the Nu-Way Series MDFL760/1070 dual fuel burner, please check that all the items included in the scope of delivery are present.
Scope of delivery:
burner, mounting kit, separate operating instructions, technical information, separate circuit diagram, flange
seal, one 7- pin connector and one 4- pin plug connector (Wieland connector).
Caution !
Oil nozzles are not included in the scope of delivery.
For gas:
Gas train
The gas pipe must be designed to conform to the flow rate and the available gas flow pressure and routed
with the lowest pressure loss over the shortest distance to the burner.
The loss of gas pressure via the gas train and the burner as well as the resistance on the fuel gas side of
the heat generator must be less than the connection flow pressure.
Caution !
Observe sequence and throughflow direction of fittings
3. Maintenance and customer service
The complete system should be checked once a year for correct functioning and leaks in accordance with
DIN 4755 by a representative of the manufacturer or other suitably qualified person.
According to EN 267 it is not permissible to perform repairs on components with a safety function. On the
other hand, the replacement of parts with genuine parts or approved equivalent parts is permitted.
We accept no liability for consequential damage in cases of incorrect installation or repair, the fitting of nongenuine parts or where the equipment has been used for purposes for which it was not intended.
4. Operating instructions
The operating instructions together with this technical information leaflet must be displayed in a clearly visible position in the boiler room. The address of the nearest customer service centre must be displayed on
the back of the operating instructions.
5. Instruction of operating personnel
Faults are often caused by operator error. The operating personnel must be properly instructed in how the
burner works. In the event of recurring faults, Customer Service should be notified.
6. Filter/Strainer
According EN 676 a filter/strainer shall be fitted at the inlet of the safety shut-off valve to prevent the ingress
of foreign elements.
E. 30.07.07 • G. 07.06.11
3
Page 4
7. Key for code designation
MDFL760
Burner output max.
Series
M10
Ø220
Ø250 - 290
8. Technical specifications
Burner type
Technical specificationsMDFL760MDFL1070
Burner output in kW
(in gas-fired operation)
Burner output (in oil-fired operation)
in kg/h
(in kW)
FuelLight oil, natural gas LL + E, LPG
Mode of operationOptionally oil/gas two-stage or gas modulating, oil two-stage
Voltage3 / N / PE ~ 50 Hz / 400 V
Power consumption at start / during opera-
tion
Electric motor power (at 2800rpm) in kW1.12.2
Flame failure controllerKLC 1000
Control boxMPA 22
9. Boiler connection dimensions
280 - 760415 - 1070
23.6 - 64.1
(280 - 760)
6.5 A max./ 3.6 A eff.
(All dimensions are given in mm)
(469 - 1070)
39.5 - 90.2
E. 30.07.07 • G. 07.06.11
4
Page 5
10. Ignition electrode
4
m
m
27 mm
13 mm
Gas ignition electrode
Oil ignition electrode
The following clearances between the nozzle and ignition
electrode should be observed:
The given dimensions are intended for checking purposes after making necessary corrective adjustments or replacing an electrode.
11. Flame failure controller
Commissioning and maintenance
The installation and commissioning must be done by qualified personnel only. Before energising the KLC
flame detector please check the cable and wiring connections are in accordance to the diagram and instructions given above. For good maintenance which will ensure trouble free operation of the KLC flame
detector; please keep the sight glass clean by wiping with a soft dry clean cloth. Warning: Do not use any
kind of cleaning sprays or fluids. During commissioning and after any cleaning maintenance, the flame detector should be checked, as the UV tube is subject to a natural ageing process and towards the end of its
life span it is prone to malfunction.
Operating Indicator LED:
LED is OFF: KLC is not switched on – no power supply
or ‘no flame’ is detected.
LED is FLASHING: KLC has detected a flame; the quality of the flame signal is indicated by the intensity of the
flashing of the LED – fast flashing indicates a healthy
flame signal and vice versa - slow flashing indicates a
weak flame signal.
LED is ON: KLC has detected the strongest level of
flame signal.
To check that the flame detector is sound we recommend the following procedures be followed:
•Start the burner with the fuel supply closed-off or remove the flame detector from its mounting flange
and cover the UV tube using a soft cloth to avoid touching the glass lens. The control box will lock-out
at the end of the safety time due to absence of a flame signal.
E. 30.07.07 • G. 07.06.11
5
Page 6
•Remove the flame detector from its mounting flange. Start the burner while exposing the flame detector to an external UV radiation source such as a cigarette lighter flame, or a small gas flame (n.b. electric room lighting or a torch is inadequate). The burner Control Box must go to lock-out due to
detecting an extraneous light source either immediately or at the end of the air pre-purge cycle,
depending on the type/model of the Control Box.
•Close off the fuel supply or remove flame detector from its mounting flange and cover the UV tube
using a soft cloth when the burner is in the "run" position. The control box must go immediately to
lock-out resulting in the burner shutting down.
If any of these safety checks do not function as described i.e. they should always result in burner shutdown
and control box lock-out; then it is essential to replace the flame detector with a new KLC flame detector.
For safety and trouble free burner operation, we recommend that the flame detector should be replaced
after every 10,000 hours of burner operation or approximately every 30months for a burner operating on
an average of 10 hours per day.
12. Oil connection
Oil lines must be routed to the burner as far as necessary to allow the oil hoses to be connected without
tension. Care must be taken to ensure that the burner can easily be moved into the service position.
Important: an oil filter must be installed before the oil pump.
The tables for single and double line installation show the maximum possible pipe length in dependence
on 3 factors with reference to heating oil type EL 4.8 cST.
• Height differential between pump and tank,
• nozzle delivery rate or pump type,
• pipe diameter.
4 brackets, 1 valve and 1 check valve for resistance were factored into the suction line length. Due to possible degassing of the oil, dimension "X" should not exceed a length of 4 m.
To convert the pump for operation on a single line system, the following points must be observed:
remove the return line and the connection nipple. Unscrew the bypass plug in the return line port and tightly
seal the port with a sealing plug. The pump suction flow will then be identical to the flow rate through the
nozzle.
Oil lines must be routed to the burner as far as necessary to allow the oil hoses to be connected without
tension. Care must be taken to ensure that the burner can easily be moved into the service position.
Important: an oil filter must be installed before the oil pump.
To change over the pump for single line operation, the following points should be noted:
disconnect return line and remove connecting nipple. Unscrew the bypass plug in the return line port and
tightly seal the port with a sealing plug. The pump suction flow will then be identical to the flow rate through
the nozzle.
14. External oil pump (option)
1 Three-phase a.c. motor connecting cable
2 Oil pump power cord
3 Oil pressure switch connecting cable
4 Pressure line to burner
5 Oil pressure switch
6 Oil pressure setting screw
7 Oil pump
The external oil pump is supplied for burners which primarily
operate in gas burning mode.
In oil burning mode, the pump starts when a heating request
is issued. Oil pressure switch (5) is fitted for pressure monitoring. In the event of loss of oil pressure, the burner shuts
off automatically. The oil pressure switch is pre-set at the factory. Pressure can be adjusted using the setting screw (6).
E. 30.07.07 • G. 07.06.11
8
Page 9
15. Front panel
Controller (option)
Display and operating unit AM01
On/Off
Selector switch
Oil operation/gas-fired operation
16. Air flap positioning motor
The air flap positioning motor is designed for air flap
adjustment on progressive two-stage burners or modulating burners. The motor is activated electronically
via the microprocessor-controlled control box.
17. Remote switching
Note
If the selector switch under the burner hood is in the "Remote" position, it is not possible to change over
between oil and gas operation with the selector switch on the front panel.
It is only possible to change over between oil and gas operation if the selector switch under the burner hood
is in the "Manual" position.
E. 30.07.07 • G. 07.06.11
9
Page 10
18. Air pressure switch
The air pressure switch is a differential pressure switch
and monitors pressure at the forced-air burner.
The air pressure switch is preset at the factory to
8 mbar.
19. Gas pressure monitor
The gas pressure monitor serves to monitor the gas inlet pressure. The burner is shut down if the gas inlet
pressure drops below the set minimum value (preset at factory). The burner starts up automatically again
when the minimum pressure is exceeded.
20. Function test
The flame monitor must undergo a safety test both at initial start-up and after modifications or if the system
has been out of use for a lengthy period of time.
Start-up test with blacked-out flame sensor:
The burner must go into lockout mode after expiry of the safety interval.
Start-up with exposed flame sensor:
The burner must go into lockout mode after approx. 20 s of pre-ventilation.
Normal start-up; if the burner is in operation, black out the flame sensor:
repeat start-up test, the burner must go into lockout mode after expiry of the safety interval.
10
E. 30.07.07 • G. 07.06.11
Page 11
21. Commissioning:
1
2
OFF
OFFUPr
2
2
2
2
2
or
or
2
and
E OIL
P
9 OIL
P
L/A
Adjustment mode - oil-fired operation
To enter this adjustment mode, the burner must be on standby.
Standby means that the burner is connected to the power supply, but no heating request has been issued and the burner is switched to oil-fired operation. If
OFF appears on the display on MPA 22, the unit is running in standby mode
and has already been configured.
If OFFUPr appears on the display, the MPA 22 is also running in standby mode,
but the unit is still unprogrammed and all setting parameters still have to be entered by the following procedure.
Important: If the setting operation is interrupted within 30 min. or not completed correctly, OFFUPr will also be displayed.
To change new setting parameters or old setting parameters, follow these
steps:
Step 1:
Enter the safety code. Press key 1 and key 2 simultaneously
Step 2:
7 horizontal bars are now displayed. Enter the password as follows.
Note: The intervals between the individual inputs must not be longer than 20
sec., as the MPA 22 will otherwise revert to standby mode. If this is the case,
you will have to start the code entry procedure from the beginning again.
- Press the minus key twice.
- Confirm your entry by pressing key 2 once.
- Press the minus key once.
- Confirm your entry by pressing key 2 twice.
- Press the plus key 4 x.
- Confirm your entry by pressing key 2 once.
- Press the plus key twice.
- Confirm your entry by pressing key 2 once.
- Press the plus key 3 x.
- Confirm your entry by pressing key 2 once.
- Press the minus key 4x.
- Press the enter key once.
Password entry is now finished.
Step 3:
after the correct password has been entered, EOIL appears on the display.
Step 4:
the operating points 9OIL (stage 3), 3OIL (stage 2) and 1OIL (stage 1) can
now be selected by pressing the plus or minus key.
E. 30.07.07 • G. 07.06.11
Step 5:
After Stage 3 has been selected, 9OIL appears on the display. The Stage 3 operating point can be adjusted to values between 0° and 90° by holding down
key 2 and optionally pressing the plus or minus key.
Note: The setting value of Stage 3 should be set to a value 0.1° greater than
the value of Stage 2!
11
Page 12
Step 6:
or
2
and
or
2
and
3 OIL
P
L/A
1 OIL
L/A
P
or
2
and
or
2
and
0 OIL
P
L/A
2 OIL
P
L/A
0 OIL
P
L/A
4 OIL
P
L/A
1
2
or
2
and
and
After you have set Stage 3, press the plus key to set Stage 2 . 3OIL appears
on the display.
The Stage 2 operating point can be adjusted to values between 0° and 90° by
holding down key 2 and optionally pressing the plus or minus key.
For basic setting values, please refer to the adjustment table.
Step 7:
After you have set Stage 2, press the plus key to set Stage 1. 1OIL. appears
on the display.
The Stage 1 operating point can be adjusted to values between 0° and 90° by
holding down key 2 and optionally pressing the plus or minus key.
For basic setting values, please refer to the adjustment table.
Step 8:
After you have set Stage 1 , press the plus key to set the ignition point P0.
0OIL. appears on the display.
The ignition point P0 can be adjusted to values between 0° and 90° by holding
down key 2 and optionally pressing the plus or minus key.
Step 9:
After you have set the ignition point P0 , press the plus key
to set the Stage 1 / 2 switch-over point. 2OIL. appears on the display.
The Stage 1 / 2 switch-over point can be adjusted to values between 0° and 90°
by holding down key 2 and optionally pressing the plus or minus key.
Step 10:
After the Stage 1 / 2 switch-over point has been set, press the plus key. 4OIL
of the Stage3 / 3 switch-over point appears on the display. The setting value
should be at Stage 3. Press the plus key again. OIL.
Appears on the display.
Close the safety loop. The burner should now start up and dwell in the ignition
position. If this is not the case, please repeat the procedure for adjustment of
the ignition point under Step 8.
Step 11:
The setting values are now adjusted in relation to the boiler and the required
burner output. The burner is in operation throughout the adjustment procedure
so that all boilers and measured data relevant to the burner can be recorded.
Adjust the operating points in the order Stage 1, Stage 2, Stage 3 (0.1° greater
than Stage 2), Stage 1 /2 switch-over point, Stage 3 / 4 switch-over point (0.1°
greater than Stage 2) and make adjustments by simultaneously pressing key
2 and the plus or minus key. To switch the burner to normal operation, press
key 1 and key 2 simultaneously for approximately 2 sec. The burner switches
to Stage 1 and then returns to normal operation. The setting procedure is now
completed and the values have been stored.
Note:
If you want to change values after finishing the setting procedure, you will have
to start from the beginning again, i.e. OFF.
Note: faults are cleared by pressing the enter key.
E. 30.07.07 • G. 07.06.11
12
Page 13
Adjustment mode - gas-fired operation
1
2
OFF
OFFUPr
2
2
2
2
2
or
2
and
or
GAS Pn
P
9GAS
P
L/A
To enter this adjustment mode, the burner must be on standby.
Standby means that the burner is connected to the power supply, but no heating request has been issued and the burner is switched to gas-fired operation.
If OFF appears on the display on MPA 22,
the unit is running in standby mode and has already been configured.
If OFFUPr appears on the display, the MPA 22 is also running in standby mode,
but the unit is still unprogrammed and all setting parameters still have to be entered by the following procedure.
Important: If the setting operation is interrupted within 30 min. or not completed correctly, OFFUPr will also be displayed.
To change new setting parameters or old setting parameters, follow these
steps:
Step 1:
Enter the safety code. Press key 1 and key 2 simultaneously
Step 2:
7 horizontal bars are now displayed. Enter the password as follows.
Note: The intervals between the individual inputs must not be longer than 20
sec., as the MPA 22 will otherwise revert to standby mode. If this is the case,
you will have to start the code entry procedure from the beginning again.
- Press the minus key twice.
- Confirm your entry by pressing key 2 once.
- Press the minus key once.
- Confirm your entry by pressing key 2 twice.
- Press the plus key 4 x.
- Confirm your entry by pressing key 2 once.
- Press the plus key twice.
- Confirm your entry by pressing key 2 once.
- Press the plus key 3 x.
- Confirm your entry by pressing key 2 once.
- Press the minus key 4x.
- Press the enter key once.
Password entry is now finished.
Step 3:
after the correct password has been entered, EGAS Pn appears on the display.
Step 4:
the operating points P9 (max load), P1 (min load) and P0 (starting point)
can now be selected by pressing the plus or minus key.
E. 30.07.07 • G. 07.06.11
Step 5:
After the operating point P9 has been selected, 9GAS appears on the display.
The max load operating point can be adjusted to values between 0° and 90° by
holding down key 2 and optionally pressing the plus or minus key.
For basic setting values, please refer to the adjustment table.
13
Page 14
or
2
and
or
2
and
1GAS
P
L/A
0GAS
P
L/A
GAS Pn
P
or
2
and
0GAS
P
L/A
or
1GAS
P
L/A
or
2
and
or
or
2
and
9GAS
P
L/A
1
2
and
Step 6:
After you have set P9, press the plus key to set P1. 1 Gas appears on the display.
The min load operating point can now be set to a value between 0° and 90° by
holding down key 2 and optionally pressing the plus or minus key.
For basic setting values, please refer to the adjustment table.
Step 7:
After you have set P1, press the plus key to set P0 (the starting point). 0 Gas
appears on the display.
The operating point (starting point) can now be set to a value between
0° and 90° by holding down key 2 and optionally pressing the plus or minuskey. The value of P1 should preferably be set. If P1, (min. load) is set to a very
low value, it is recommended to set P0 to a higher value than P1 in order to
ensure stable starting.
For basic setting values, please refer to the adjustment table.
Step 8:
After you have set P0, press the plus key.
GAS Pn. appears on the display.
Now close the safety loop and issue a heating request.
The burner should now start up and dwell in the ignition position. If this is not
the case, please repeat the procedure for adjustment of ignition point P0 underStep 7. After the burner has started up, the gas train must be set to the nozzle
pressure specified in the adjustment table.
Step 9:
The setting values are now adjusted in relation to the boiler and the required
burner output. The burner is in operation throughout the adjustment procedure
so that all boilers and measured data relevant to the burner can be recorded.
Adjust the operating points in the order P0,P1 and P9 and make adjustments
by simultaneously pressing key 2 and the plus or minus key. To switch the
burner to normal operation, press key 1 and key 2 simultaneously for approximately 2 sec. The burner switches to min output P1 and then returns to normal
operation.
The setting procedure is now completed.
Note:
If you want to change values after finishing the setting procedure, you will have
to start from the beginning again.
E. 30.07.07 • G. 07.06.11
14
Page 15
22. Troubleshooting / process description
Defect determined:Cause:Remedy:Fault code
Burner motor does
not start up
Burner starts up and
switches to fault mode
before or after expiry of
safety period
Electric supply lead faultyRectify faults in electrical installation
Fuse faultyReplace
Safety thermostat lockedUnlock42 h
Temperature of controller setting is
exceeded
MPA 22 faultyReplace04 h
Leak Rectify leak44H / 43H
No gasSafeguard gas supply
Gas pressure monitor faultyReplace gas train22 h
Filter in gas train dirtyClean or replace
Air pressure switch not in idle positionCheck air pressure switch (see page 9)20 h
Burner motor faultyReplace
No load at terminal 5Check plug connection and current path of
Mains voltage < 187 V
Air pressure switch does not switch
through during pre-ventilation
Ignition influencing of ionization monitor See Page 1026 h
Gas solenoid valve does not openReplace gas train
Starting gas quantity set too lowIncrease starting gas quantity
No ignitionCheck ignition electrode and setting, igni-
Renewed start attempt after temperature
drop
solenoid valve
Rectify faults in electrical
installation
See Page 921 h
tion transformer and cable
Flame extinguishes
during operation
Phase and zero mixed upConnect connector unit in correct phase
sequence
Flame control faultyCheck according to Page 102BH
Air pressure switch opens during opera-
tion
Gas nozzle dirty or faultyReplace gas nozzle
No gasSafeguard gas supply
Filter in gas train
dirty
Flame blow-offIncorrect burner setting27 h
Air pressure switch contact opensCheck/replace air pressure switch 21 h
Flame signal too weakMeasure flame signal, check ionisation
See Page 921 h
Clean or replace
27 h
electrode
E. 30.07.07 • G. 07.06.11
15
Page 16
Service mode - pneumatic gas-fired operation
Adjustment
point
Adjustment
values
Service mode
symbol
Adjustment
point
Information mode symbol
display
value
The service mode serves to display the set parameters and to read out the fault memory. It can be invoked
in any operating state of the burner.
Important:
setting values cannot be changed in service mode. If no key is pressed for longer than 20 sec., the
display returns to standby mode.
To access the service mode, press the enter key for approx. 2 sec.
The following now appear on the display: point P0 and the air flap positioning motor setting value at ignition in angular degrees, plus a wrench
symbol denoting the service mode.
The following points can be retrieved by repeatedly pressing the enter
key:
- The characteristic curves for points P0, P1 and P9
- The last 6 fault messages P10 to P15 (see fault code MPA)
- The testing times of the valve proving system P16 and P17
- The flame quality P18
- The eBus address of the MPA P19
- The switch setting of the valve proving system P21
- The eBus address of the external controller P24
- The modulation delay
- The set start points P26
To exit the service mode, please press the enter key or wait approx.
20 sec.
Information mode
The information mode is intended for display of consumption figures, operating hours and software data.
To access information mode, press the Enter key for approx. 0.5 sec.
A zero and a value appear on the display.
The following values can be queried in information mode under setting
points 0 to 8. Retrieve by repeatedly pressing the enter key:
Important:
If no key is pressed for longer than 20 sec., the display returns to
normal operating mode.
0 = fuel consumption
1 = total operating hours
2 = for oil only
3 = for oil
only 4 = number of successful start-ups
5 = display of software version
6 = software creation date
7 = hardware number
8 = date of production
E. 30.07.07 • G. 07.06.11
16
Page 17
Troubleshooting the MPA
CodeDescription
04 hInternal hardware fault
05 hInternal hardware fault
06 hInternal hardware fault
07 hInternal hardware fault
09 hInternal hardware fault
10 hInternal hardware fault
11 hInternal hardware fault
12 hInternal hardware fault
13 hInternal hardware fault
14 hInternal hardware fault
15 hInternal hardware fault
20 hAir pressure switch is not in idle position
21 hFailure of air pressure switch
22 hFailure of gas pressure monitor
25 hNo flame after safety period
26 hOutside light
27 hFlame failure during operation
29 hInternal hardware fault
2AHInternal hardware fault
2BHShort-circuit in photo resistor or internal fault
2CHInternal hardware fault
30 hInternal hardware fault
31 hInternal hardware fault
32 hInternal hardware fault
33 hInternal hardware fault
34 hInternal hardware fault
42 hSafety chain interrupted
43 hY3 found to be leaking during leak check
44 hY3 found to be leaking during leak check
45 hInternal hardware fault
46 hInternal hardware fault
47 hInternal hardware fault
48 hInternal hardware fault
Start-up testsProcessor and program memory test / move actuator drives to reference position
State 01Start-up decision (heating request present)
State 02Blower idle state check
State 03Blower start-up
State 04Preventilation / operation of gas flap actuator over speed range
State 05Preventilation / activate and test watchdog
State 06Preventilation / move gas flap actuator to ignition position
State 07Move air flap actuator to ignition position
State 08Pre-ignition depending on parameters
State 09Start-up safety period
State 10Stabilisation period
State 11Move positioning drive from ignition point to operating characteristic
State 12Operation
State 13VPS - evacuate valve cavity / (post-ventilate)
State 14Test duration Y2 / (remaining post-ventilation time)
State 15VPS - fill valve cavity / (remaining post-ventilation time)
State 16Test duration Y3 / (remaining post-ventilation time)
State 17Remaining post-ventilation time
State 18Restart disable time / waiting loop for low gas program
State 20Standby position
18
E. 30.07.07 • G. 07.06.11
Page 19
23. Control unit MPA 22
+
–
1
2
P
S
i
G
L/A
h
l,m
3
Acknowledgment or reset
key
Key 1
Actuation of gasflow control flap
in conjunction
with +/- key
Key 2
Actuation of airflow control flap
in conjunction
with +/- key
Key + / Key In conjunction
with key 1 or 2
On when
setup mode
is selected
Start-up
Lights up during
the run-up phase,
OFF during
operation
Lights up when the
gas-flow control
flap is active
On when
information
mode is active
Lights up when the
air-flow control
flap is active
h = Operating hours indicator
l, m3 = Oil or gas consumption
Operation, flame burning
Fault
Lights up when
service mode
is active
Liquid-crystal
display
Symbols for
open/close flaps
24. MPA 22 control unit display
The MPA 22 is a microprocessor-controlled intermittentduty control box for controlling and monitoring pneumatic
modulating forced-air burners with an actuator drive. For
operation as an automatic gas burner control with integral
valve proving system.
The MPA 22 has e-BUS connectivity.
Gas certification
EU type test approval according to EU Gas Appliance
Directive.
MPA 22 CE-0085AU316
E. 30.07.07 • G. 07.06.11
19
Page 20
25. Calculation principles for gas burner adjustment
V
n
Q
n
η
k
H
×
i n,
--------------------
430kW
0 90 10×4
kWh
m
3
-----------
,,
----------------------------------------=46
m
3
h
------
==
V
B
V
n
f
------
46
m
3
h
------
0 94,
-------------=49
m
3
h
------
==
f
B P
G
+
1013
--------------
273
273 ϑ
G
+
--------------------
×=
The values given in the tables are setting values for start-up.
The necessary system adjustment must be newly determined in each case.
General:
the calorific value (H
for the normal state (0°C, 1013 mbar).
) of fuel gases is generally specified
i,n
Natural gas type EH
Natural gas type LLH
LPG gas (propane)H
= 10.4 kWh/m
i,n
= 9.3 kWh/m
i,n
=25.89 kWh/m
i,n
3
3
3
Gas counters measure the volume of gas in the operational state.
Gas flow determination:
To allow the heat generator load to be adjusted correctly, the gas flow rate must be determined in advance.
Example:
Altitude above sea level 230 m
Barometric air pressure B (acc. to table)989 mbar
Gas pressure PG at meter20 mbar
Gas temperature
Boiler output Q
J
G
n
16°C
430 kW
Efficiency hK (assumed)90%
Calorific value H
i,n
10.4 kWh/m
3
Gas flow in standard state (Vn)
Gas flow in operating state (V B)
Conversion factor (f)
Annual average air pressure
Average geodetic altitude of the
supply region above sea level [m]
Annual average of air pressure (mbar) 1016 1013 1007 1001 995 989 983 977 971965 959 953 947 942 936 930
Legend:
Qn = boiler output [kW]
hK = efficiency [%]
H
= lower standard calorific value [kWh/m3]
i,n
f = conversion factor
B = barometric air pressure [mbar]
= gas pressure at gas meter [mbar]
p
G
J
= gas temperature at gas meter [°C]
G
E. 30.07.07 • G. 07.06.11
20
Page 21
26. Gas train KEV II1 ½" , KEV 2" and KEV DN65
Gas pressure monitor
SKP 10
VGD
Pulse line p
G
SKP 70
Cover plate for
"AIR" air pressure connection
(gas inlet pressure)
Gas pressure monitor
for leak check
Adjustment screws
Direction of flow
Burner
Gas connection
Installing the gas train
Installation positiononly in horizontal line, not tilted.
Minimum distance to walling: 20 mm
Screw the measuring nipple for combustion chamber pressure into the gas jacket at the top.
Route the connecting hose between the measuring nipple for combustion chamber pressure and the gas train in a loose loop.
The air pressure connection nipple must be screwed into the gas jacket at the top.
Connect the blue hose to the "AIR" connection on the gas train and the air pressure connection on the gas
jacket. The blue hose serves as a control line for the gas train and must be routed in a loose loop without
kinking.
Remove the plate for covering the adjustment screws from the gas pressure regulator.
Start the burner.
1. Setting the air surplus in high and low-load operation
•Set the air flap positions P9 for high-load operation and P1 for low-load operation according to
29. Adjustment tables. Follow the setting procedure described in 19. Adjustment mode for pneumatic
gas-fired operation with MPA 22 display.
•In high-load operation, set the air surplus with the "large flame" adjustment screw on the gas pressure
regulator. The CO2 level in the flue gas should be 9-10% for natural gas.
•In high-load operation, set the air surplus with the "small flame" adjustment screw on the gas pressure
regulator. The CO2 level in the flue gas should be 9-10% for natural gas. The low-load setting influ-
ences the high-load setting.
•In high-load operation, check the air surplus and, if necessary, correct the setting with the "large
flame" adjustment screw on the gas pressure regulator.
2. Setting the output in high and low-load operation
•Check the high-load setting via the gas flow at the gas meter or compare the nozzle pressure with the
values stated in 27. Adjustment tables. The output can be increased by opening the air flap (to
increase P9) and reduced by closing the air flap (to reduce P9). The air surplus is not affected by this
adjustment.
•Check the low-load setting via the gas flow at the gas meter or compare the nozzle pressure with the
values stated in 27. Adjustment tables. The output can be increased by opening the air flap (increase
P1) and reduced by closing the air flap (reduce P1). The air surplus is not affected by this adjustment.
E. 30.07.07 • G. 07.06.11
21
Page 22
27. Gas train KEV25 1" and KEV30 1½"
Gas pressure monitor
Pulse line p
G
pG
V
N
Gas pressure monitor
for leak check
(gas inlet pressure)
Installing the gas train
Installation position only in horizontal line, not tilted.
Minimum distance to walling: 20 mm
Screw the air pressure measuring nipple into the gas jacket at the top.
Route the connecting hose between the air pressure measuring nipple and the gas train in a loose loop.
The air pressure connection nipple must be screwed into the gas jacket at the top.
The blue hose serves as a control line for the gas train and must be routed in a loose loop without kinking.
Cut the blue hose into two sections. Connect the first sections of blue hose to the "pL" connection on the
gas train and the air pressure connection on the gas jacket, and connect the other section to the "pF" measuring point on the combustion chamber. The hose must be routed in such a fashion that any condensate
forming inside the combustion chamber flows back, and not into the gas train.
Start the burner.
1. Setting the air surplus in high and low-load operation
•Set the air flap positions P9 for high-load operation and P1 for low-load operation according to
29. Adjustment tables. Follow the setting procedure described in 19. Adjustment mode for pneumatic
gas-fired operation with MPA 22 display.
•In high-load operation, set the air surplus at the adjustment screw "V" on the gas pressure regulator.
The CO2 level in the flue gas should be 9-10% for natural gas.
•In low-load operation, set the air surplus with the adjustment screw "N" on the gas pressure regulator.
The CO2 level in the flue gas should be 9-10% for natural gas. The low-load setting influences the
high-load setting.
•In high-load operation, check the air surplus and, if necessary, correct the setting using the adjustment
screw "V" on the gas pressure regulator.
2. Setting the output in high and low-load operation
•Check the high-load setting via the gas flow at the gas meter or compare the nozzle pressure with the
values stated in 27. Adjustment tables. The output can be increased by opening the air flap (to
increase P9) and reduced by closing the air flap (to reduce P9). The air surplus is not affected by this
adjustment.
•Check the low-load setting via the gas flow at the gas meter or compare the nozzle pressure with the
values stated in 27. Adjustment tables. The output can be increased by opening the air flap (increase
P1) and reduced by closing the air flap (reduce P1). The air surplus is not affected by this adjustment.
E. 30.07.07 • G. 07.06.11
22
Page 23
20
10
30
40
50
60
70
90
100
110
120
140
160
200
910 11 12 13 14 15 16 17 18 19 20
80
Öl-
durch-
satz
[kg/h]
Brenner-
leistung
[kW]
2100
1800
1500
1300
1100
960
850
750
650
540
480
370
320
250
200
160
130
110
Pumpendruck [bar]
Düsen-
größe
[gph]
30
28
26
24
22
20
18
16
15
14
13
10
8
7
6
5,5
3,5
3
12
9
6,5
5
2,5
2,75
11
7,5
4,5
4
Oil pump pressure [bar]
Burner
output
[kW]
Nozzle
size
[gph]
Oil
throughput
[kg/h]
28. Nozzle selection diagram
If the desired output deviates from the values specified in the tables, the nozzle size and the pump pressure
can be determined on the basis of the following diagram.
1Motor 1.1 kW 50 Hz136-90-11538
2Coupling compl. for pump unit MK147-90-27103
3Hydraulic hose DN 8, 1500 mm lg.147-90-25302
4Pressure switch compl. with cable147-90-25363
5T-piece compl. for pump unit144-90-23080
6Conical nipple AL 14 x 10 x 25037-50-10788
7Pressure pipe nipple547-50-20127
8Conical nipple AL 13 x 18 x 25037-50-11293
9Hose nipple R 1/4“1047-50-20862
10Pressure pipe compl. for pump unit MDFL147-90-27104
11Oil pump AJ4, compl. for pump unit MDFL147-90-27109
12Sealing washer AL 13 x 18 x 25037-50-11293
13Hose nipple NW6 R 1/4“1037-50-11348
14Metal hose NW6 1200 mm lg.147-90-11347
15Screwed sealing plug R 1/4“ with hexagon socket537-50-11798
E. 30.07.07 • G. 07.06.11
25
Page 26
Combined gas/oil burner MDFL760
ZBZ_2-202.1
E. 30.07.07 • G. 07.06.11
26
Page 27
ItemDesignationPUArt. No.
1Burner pipe MDFL760147-90-25517
1Burner pipe MDFL760, extended 100 mm147-90-25514
1Burner pipe MDFL760, extended 200 mm147-90-26419
2Mixing head MDFL welded147-90-27084
2Mixing head MDFL welded, extended 100 mm147-90-27085
2Mixing head MDFL welded, extended 200 mm147-90-27086
9Nozzle holder MDFL compl. pre-assembled, extended 200 mm147-90-26240
10Hydraulic set147-90-27087
11Mixing head MDFL compl. pre-assembled, excl. ignition cable147-90-25473
11Mixing head MDFL compl. pre-assembled, extended 100 mm,
147-90-25562
excl. ignition cable
11Mixing head MDFL compl. pre-assembled, extended 200 mm,
147-90-26108
excl. ignition cable
12Actuator drive SAD 1.5 for MG20-ZM147-90-24763
13Air damper MG20 to 12.08147-90-24663
13Air damper MG20 from 12.08147-90-27030
14Cover for MG20 with seals147-90-10698
15Pressure pipe MDFL760 compl.147-90-25560
17Double solenoid valve block compl.147-90-27105
18Sight glass with seal136-90-11544
19Cover MG20147-90-24857
20Cover for sight glass547-50-12106
21Oil pump AL95, compl. for MDFL760147-90-27125
22Conical nipple AL 13 x 18 x 25037-50-11293
23Hose nipple R 1/4“ x R 3/8“1046-50-10554
24Sealing washer AL 14 x 10 x 25037-50-10788
25Pressure pipe nipple GES 6LLR547-50-20127
26Metal hose NW8 1500 mm lg.157-90-10348
27Coupling compl.136-90-11539
28Fan wheel Ø 218 x 80136-90-11540-01
291.1 kW 400 V / 50 Hz motor147-90-26721
301.1 kW motor with fan wheel147-90-25205
314-pin socket green137-90-20744
327-pin socket black/brown137-90-20731
335-pin socket black137-90-20748
9Nozzle holder MDFL compl. pre-assembled, extended 200 mm147-90-26240
10Hydraulic set147-90-27087
11Mixing head MDFL compl. pre-assembled, excl. ignition cable147-90-25473
11Mixing head MDFL compl. pre-assembled, extended 100 mm,
147-90-25562
excl. ignition cable
11Mixing head MDFL compl. pre-assembled, extended 200 mm,
147-90-26108
excl. ignition cable
12Actuator drive SAD 1.5 for MG20-ZM147-90-24763
13Air damper MG20 to 12.08147-90-24663
13Air damper MG20 from 12.08147-90-27030
14Cover for MG20 with seals147-90-10698
15Cover for sight glass547-50-12106
16Cover MG20147-90-24857
17Sight glass with seal136-90-11544
18Pressure pipe MDFL1070 compl.147-90-25468
19Double solenoid valve block compl.147-90-27105
20Hydraulic coupling compl.147-90-25464
21Hydraulic sealing nipple T2320V, compl.147-90-25465
22Hose nipple R 1/4“ x6LL147-90-20862
23Conical nipple AL 13 x 18 x 25037-50-11293
24Solenoid valve R 1/4“ compl. for MDFL burner147-90-27106
25Oil pump AJ4 compl. for MDFL burner147-90-26063
26Pressure pipe nipple GES 6LLR x 1/8“547-50-20127
27Conical nipple AL 14 x 10 x 25037-50-10788
28Hose nipple R 1/4“ x R 3/8“1046-50-10554
29Metal hose NW8 1500 mm lg.157-90-10348
30Coupling MDFL1070 compl.147-90-27179
31Fan wheel Ø 224 x 82147-90-24847
322.2 kW 400 V / 50 Hz motor147-90-24846
332.2 kW motor with fan wheel147-90-25508
345-pin socket black137-90-20748