Nuvo 500, 250 User Manual

C E L L A R nuvo
2 5 0 / 5 0 0
k o o l s pac e
TM
ASSEMBLY & OPERATION MANUAL
~1~
~3~
READ BEFORE YOU START
1. LOCATING YOUR WINE CELLAR - Remember, it is not an appliance, it is a piece of furniture
A. Provide 4” minimum clearance for both sides and back, keep the top completely clear. Under no circumstances should the unit be “built-in” in any way.
B. Never locate your wine cellar outdoors or in an area with extremes of temperature and humidity.
Garages, attics, unnished basements, laundry rooms, breezeways, closets, bedrooms or any unventilated room. In other words these units must be installed in air-conditioned environments which do not “trap” the warm air being exhausted.
C. Temperatures in surrounding area must not exceed 80 °F (25 °C) with humidity levels not to exceed 70% R.H. (Relative Humidity). Never set your temperatures below default (57ºF) whenever ambient conditions are warm (above 75ºF) or humid (above 50%R.H.).
D. Outlet power must be a DEDICATED separately fused, grounded, 15 Amp 110 - 120 V line or
7.5 Amp - 240 V line rated for your unit (CHECK BOX OR SERIAL NUMBER LABEL ON UNIT FOR YOUR LINE VOLTAGE REQUIREMENTS).
E. You must monitor your unit DAILY. If unit is in “Alarm”, unplug the unit inmediately. Always check for any water (condensate) leaks.
Vintage Keeper will not be liable or responsible for incidental or consequential damages. (See Warranty).
F. Place unit in a clean area and allow access to the exterior surfaces for periodic vacuuming of the condensor coil. (See troubleshooting for details.)
G. Always remove all bottles before relocating your wine cellar.
Choose a clear 12’ by 12’ area with a level oor and carpeting to help reduce scratching of surfaces.
3. TOOLS
* Hex wrench (included) * Phillips screwdriver * Carpenter’s level * Helper or two is strongly recommended
4. TEST THE COOLING UNIT
Plug it in for a few minutes on a table top, to verify that controls and display are functional, and that the unit is producing cool air after a few minutes of operation.
Note that the electronic controller has a one-minute cautionary delay between initial plug-in and start-up of the compressor.
NOTE: Fill out the WARRANTY REGISTRATION FORM with the serial number located on the LEFT SIDE of unit.
~2~
HARDWARE KIT
A
Cam Cap
x 26 (x30)*
E
B
Hex bolt
x 22 (x30)*
F
C
Coupler screw
x 8
G
D
Hex wrench
x 1
H
Cam
x 24 (x28)*
I
In Cooling Unit Box
Hex Bolt (Flange)
x 2
Cam Pin
x 24 (x28)*
Coupler hanger
x 4
Panel Insulation Strip
Hinge
x 4
J
*NOTE : Hardware quantities for Model 500 are indicated in parenthesis.
~3~
~5~
STEP 1 : PANEL PREPARATION
PANEL EDGE
CAUTION :
1. Watch for sharp staples on boxes.
2. DO NOT STEP ON PANELS
3. The manual will give a recommended
order to open boxes, it saves time and space.
J
Open Boxes VP6 and VP7.
1
Install INSULATION STRIP (J) to Back, Top, and Bottom Panels. PUSH
IN FULLY!
J
J
J
2
!
Insert Cam Pins (F) in BACK PANEL’S predrilled holes down to TAB. (May
require some force)
CAUTION : DO NOT BREAK CAM PIN TABS!
DO NOT HAMMER!
TAB
TAB
BACK PANEL
F
C
Screw in both
3
screws (C) half way in Coupler Hanger (G) to back panels and tighten fully when both screws are in.
~4~
3
G
STEP 2 : CABINET ASSEMBLY

PANEL EDGE
CAM in LOCKED
POSITION
Use allen key provided or #3 phillips screwdriver.
1
Attach TOP and Bottom to Back by CAREFULLY aligning edge holes over Cam Pins and gently push together to avoid damaging cam pins. DO
NOT BANG OR SLAP PANELS TOGETHER!!!
2
METAL
BOTTOM PANEL
METAL
Insert Cam, push all the way
2
in under panel level (may require some force) and
make sure Arrow points to outside edge.
Gently push down to bring panels together before you tighten the Cam. Start with
cams at each end.
Cam Arrow faces away from
outside edge when tightened.
BOTTOM PANEL
Insert Center COUPLER
3
BAR by guiding edge
holes over bottom Cam Pins. Lightly push out top panel edge to allow Cam Pins to go in Coupler Bar. Insert and tighten Cams.
3
COUPLER BAR INSIDE CABINET
~5~
Loading...
+ 11 hidden pages