NuTone ssQTXe110, ssQTXe080 User Manual

MODELS SSQTXE080 • SSQTXE110
LINE
Black
NEUTRAL
White
LINE
Black
NEUTRAL
White
GROUND
Bare
Copper
GROUND
Green
WHITE
BLACK
CONTROL
FAN
LOAD Red
GROUND
Bare
Copper
POWER
LINE
(GFCI
protected
if required)
Broan SmartSense® Intelligent Ventilation System
READ AND SAVE THESE INSTRUCTIONS
Page 1
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. This unit must be grounded.
7. Do not connect this product as a load on a fan speed control or light dimmer.
8. Read and understand entire instructions before proceeding with installation.
INSTALLATION
Install controls and wire them as shown. Use following guidelines:
IMPORTANT: QTXE080 Ultra Silent™ fan must be wired to SMSC080
SmartSense® control.
QTXE110 Ultra Silent™ fan must be wired to SMSC110
SmartSense® control.
• Use minimum 75 °C rated electrical wiring.
• Except for required neutral wire, these controls install like normal switches. Make sure electrician knows each control location must have a neutral wire. Neutral wire at switch locations may be code requirement or regular practice in installation municipality; but unless explicitly specified, electrician might not install it.
• Specify deep device electrical boxes where controls will be installed. These controls fit in most North American electrical boxes; however, deep boxes provide extra working space which eases installation. Labor cost savings can offset higher box costs, which is usually less than a dollar over standard depth boxes. Use boxes that have 18 cu. in. minimum volume and are at least 1-1/2 in. deep.
All controls must be grounded using attached ground wire.
CONTROL OPERATION
MODELS SSQTXE080 • SSQTXE110
Page 2
HOW SYSTEM WORKS
Broan SmartSense® system is design to provide recommended ventilation for desirable indoor air quality. Related ventilation requirements of *ANSI/ASHRAE Standard 62, “Ventilation for Acceptable Indoor Air Quality” are fulfilled when this system is installed accordingly. Ventilation level, which is based on home square footage and number of bedrooms, is easily set during installation. Power outages do not affect settings, since they are stored in power independent (nonvolatile) memory. Energy usage is optimized by monitoring fan on-time and adjusting automatic ventilation as needed. Indoor air quality is provided 24-hours a day, 7-days a week.
A single Broan SmartSense® system is powerful enough to fulfill ventilation rates for larger homes; however, it is recommended to use multiple installations for homes with multiple bathrooms. Multiple installations provide distributed ventilation throughout the home. Multiple installations are linked and communicate through home’s normal power circuits to form an indoor air quality network.
Broan SmartSense® controls are designed and factory set for multiple installation homes. If a single Broan SmartSense®
system is installed then System Level must be adjusted accordingly; otherwise, fan may run continuously.
Additional features, which are turned off at factory, include Vacation and Disabled modes. Vacation mode temporarily disables system until Master fan is manually turned on. Disabled mode removes system from automatic ventilation usage. Disabled mode does not affect manual operation.
* American National Standards Institute / American Society of Heating, Refrigerating and Air-Conditioning Engineers
HOW LED WORKS
LED works differently in Run and Program modes. Run Mode: LED is off when fan is off. LED is on when fan
is on manual ventilation; turned on by pressing ON paddle. LED turns on briefly every second (fast-blink) when fan is on automatic ventilation; turned on by Broan SmartSense® system.
Program Mode: LED is on while SET button is pressed. LED turns on and off every second (slow-blink) when system is in Program mode.
INDOOR AIR QUALITY NETWORK
A single Broan SmartSense® system is powerful enough to fulfill ventilation rates for larger homes; however, it is recommended to use multiple installations for homes with multiple bathrooms. Multiple installations provide distributed ventilation throughout the home.
Multiple installations communicate through a home’s electrical power circuits to form an indoor air quality network. Communication pathways are called links. A phase coupler
is required if multiple installations are connected to both electrical power phases.
Individual systems in a multiple installation home can operate independently; although, it is recommended to link multiple installations as an indoor air quality network. If a
single Broan SmartSense® system is installed or independent system operation is desired, proceed with “How To Set System Level” section. If System Level is not adjusted, fan may not shut off automatically or run unnecessarily too long.
One Broan SmartSense® control is selected as system Master during set up. Any control can be selected as system Master, but typically master bathroom control is chosen. All controls are factory set as system Masters.
SmartSense® controls that are linked to Master control are called Slaves. One Master control can link up to 10 Broan SmartSense® Slave controls.
HOW TO LINK SMARTSENSE® SYSTEM
1. Unless another control is designated and clearly marked on frame, under decorative plate, or documented on this instruction sheet as Master control, go to master bathroom control.
2. Put Master control in Program mode; press and hold SET button for 3-seconds and then release it.
Note: Master control will automatically exit Program mode
after 4-minutes.
3. LED should be turning on and off every second (slow-blink); if it isn’t then repeat step 2.
4. Go to first control to link as a Slave.
5. Press and hold SET button until fan turns on. If fan doesn’t turn on in less than 5-seconds, make sure Master is in Program mode; which is indicated with LED slow-blink.
Note: At same time Slave turns on, Master fan turns on.
Master fan should turn off automatically in less than 15-seconds.
6. Release Slave’s SET button.
7. If Master control has not automatically turned Slave off then press Slave’s OFF paddle to manually turn it off.
8. If there are more Slave installations then go back to Master control and repeat steps 2 through 8.
Note: Master control will automatically exit Program
mode 4-minutes after it is started. Slave link needs to be made before Master automatically exits Program mode or Master control’s Program mode needs to be started again.
MODELS SSQTXE080 • SSQTXE110
Push to turn ON
Push to
turn OFF
SmartSense
®
®
Page 3
HOW TO SET SYSTEM LEVEL
Installer, homeowner, or building science expert may adjust Broan SmartSense® ventilation system level.
Initial Setting of System Level
1. System Level is only set in Master control. If home has more than one installation then locate Master control; it is usually in master bathroom or it should be clearly marked on frame, under decorative plate, or documented on this instruction sheet.
2. Circle, mark or highlight System Level in Table A using home’s square footage and number of bedrooms.
Note: Building science experts may calculate different
rate based on air infiltration measurements.
3. Circle, mark or highlight same System Level in Table B.
4. If home’s System Level is 90 then next steps are not necessary, since control’s System Level is set at factory to 90.
5. Put Master control in Program mode; press and hold SET button for 3-seconds and then release it.
6. LED should be turning on and off every second (slow-blink); if it is not then repeat step 5.
7. Tap (press and release) ON or OFF paddle number of times from Table B.
8. Exit Program mode; press and release SET button twice.
LED should turn off.
Changing System Level
1. Put Master control in Program mode; press and hold SET button for 3-seconds and then release it.
2. LED should be turning on and off every second (slow-blink); if it isn’t then repeat step 1.
3. Press Master control’s paddle ON once and OFF once; System Level is changed back to factory setting of 90.
4. Tap (press and release) ON or OFF paddle number of times from Table B.
5. Exit Program mode; press and release SET button twice.
LED should turn off.
FEATURE SELECTIONS
Vacation Mode: Used only with Master control. Temporarily
disables Broan SmartSense® system. Master control will not automatically turn on its fan or any other system fan. After Program mode exit, Vacation mode is cancelled when Master control ON paddle is pressed.
Disabled Mode: When Master control is put in Disabled mode, it will not turn on any fans for automatic ventilation and recommended indoor air quality ventilation level is not assured. Manual control fan operation is not affected.
Vacation Mode
1. Put Master control in Program mode; press and hold SET button for 3-seconds and then release it.
TABLE A
Floor Area (ft2)
< 1500 1501 - 3000 3001 - 4500 4501 - 6000 6001 - 7500
> 7500
TABLE B
System
Level
165 +5 150 +4 135 +3 120 +2 105 +1
90 0 75 -1 60 -2 45 -3 30 -4
0 - 1 2 - 3 4 - 5 6 - 7 > 7
30 45 60 75 90 45 60 75 90 105 60 75 90 105 120 75 90 105 120 135 90 105 120 135 150
105 120 135 150 165
Taps
ON
PADDLE
LED
SET BUTTON
Bedrooms
OFF
PADDLE
2. LED should be turning on and off every second (slow-blink); if it is not then repeat step 1.
3. Press Master control’s ON paddle seven times.
LED should turn off and fan turn on. After 1 to 2-seconds
fan turns off.
Vacation mode is maintained after power loss. Vacation mode is cancelled when Master control’s paddle is pressed ON and then OFF; System will then resume automatic operation.
Disabled Mode
1. Put Master control in Program mode; press and hold SET button for 3-seconds and then release it.
2. LED should be turning on and off every second (slow-blink); if it is not then repeat step 1.
3. Press Master control’s OFF paddle seven times.
4. Exit Program mode; press and release SET button twice.
LED should turn off. Disabled mode indefinitely keeps Broan SmartSense®
system from turning fan(s) on automatically to provide recommended ventilation for desirable indoor air quality. Disabled mode is maintained after power loss. Disabled mode is cancelled when Master control System Level is reset following instructions in section “Changing System Level.”
Loading...
+ 5 hidden pages