NuTone SmartSense QT110H Installation Instructions Manual

IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE. ELECTRIC SHOCK,
OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended by the manufacturer. If you
have questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch power off at service
panel and lock service panel to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
CAUTION:
For general ventilating use only. Do not use to exhaust hazardous
or explosive materials and vapors.
INSTALLATION INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK,
OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards, including fire-rated construction.
B. Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer's guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
C. When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities. D. Ducted fans must always be vented to the outdoors. E. If this unit is to be installed over a tub or shower, it must be marked
as appropriate for the application and be connected to a GFCI
(Ground Fault Circuit Interrupter) - protected branch circuit. F. NEVER place a switch where it can be reached from a tub or shower. G. Handle the sensor unit with care. Avoid direct contact with electronic
components while installing.
Do not install in a ceiling insulated to a value greater than R40.
Not for use in kitchens.
FOR BEST RESULTS
When installing the Ventilator in a new construction site, install
housing during the rough-in construction of the building. The blower unit, sensor unit and grille should be installed after the finished ceiling is in place.
To install a ventilator in an existing building requires an accessible
area (attic or crawl space) above the planned location.
This unit is designed to detect increased humidity levels and to automatically activate the fan. For best results, the fan should be located near the humidity source. Increasing the distance from the source will lengthen the response time of the unit.
INSTALLATION INSTRUCTIONS
READ & SAVE THESE INSTRUCTIONS!
SmartSense
Combination
MODEL: QT110H
SUITABLE FOR USE OVER TUB OR SHOWER ENCLOSURE WHEN INSTALLED IN A GFCI PROTECTED BRANCH CIRCUIT.
FIGURE 1
ROOF CAP (COUVERCLE DE TOÎT)
4" DIAMETER DUCT (CONDUIT DE 4 PO DE DIAMÉTRE)
90° ELBOW (COUDE À 90°)
WALL CAP
(COUVERCLE MURAL)
CEILING INSTALLATION (POSE AU PLAFOND)
INSTALLATION IN A NEW CONSTRUCTION SITE
PREPARATION
1. Remove blower/power unit assembly from housing: A. If necessary, unplug power unit. B. Loosen three (3) mounting screws. C. Slide unit back to free it from mounting screws. D. Remove unit and set aside until needed.
2. Remove one of the wiring knockouts from housing.
MOUNTING THE HOUSING
1. Refer to Figure 4. Insert mounting brackets at each end of housing.
2. Place long side of housing parallel to ceiling joist. Position housing in desired location. Make sure housing flange is even with the planned finished ceiling.
3. Use screws or nails (not provided) to secure mounting brackets to ceiling joists.
4. Refer to Figure 1. Use 4" round duct to discharge the ventilator to the outside.
IMPORTANT: Be sure nothing obstructs the discharge of the
ventilator. Make sure that insulation does not get into the duct work or into the fan.
WIRING
Refer Figure 2.
1. Run 120v AC house power wiring (with ground) through switch box to junction box in ventilator housing.
2. Remove ventilator junction box cover.
3. Referencing figure 2 connect the house power wire (black) to the connector black wire. Connect the house neutral wire (white) to both the connector and motor plug wires (white). Connect the ground wire to the green ground screw. Connect the blue connector wire to the black motor plug wire.
4. Replace junction box cover.
5. Connect house power wire to standard toggle switch.
NOTE: BE SURE VENTILATOR AND SWITCH ARE PROPERLY
GROUNDED. ALL WIRING MUST COMPLY WITH LOCAL ELECTRICAL CODES.
SENSOR UNIT INSTALLATION
Refer Figure 3.
1. Align sensor cover tabs with slots in junction box cover. Firmly press sensor cover to engage connector.
2. Secure sensor unit using mounting screw through hole in unit cover flange.
POWER/BLOWER UNIT INSTALLATION
1. Plug motor into socket in housing's junction box.
2. Position power unit mounting plate over mounting screws in
housing.
3. Slide unit forward until the gasket fits firmly against discharge
opening in housing and mounting screws are seated in narrow end of keyhole slots.
4. Refer to Figure 4. Securely tighten screws.
GRILLE INSTALLATION
1. Refer to Figure 4. Snap grille mounting springs' center loop into
notched bosses on the back of grille.
2. Place grille mounting springs into slots in power unit mounting
plate.
3. Press grille firmly into place against the ceiling.
FIGURE 3
INSTALLATION IN EXISTING CONSTRUCTION
Installing the ventilator in an existing house requires an accessible
area (attic crawl space) above the planned installation location.
Review “INSTALLATION IN A NEW CONSTRUCTION” and
follow all instructions which apply to your installation.
Location – locate ventilator parallel to a ceiling joist. Wiring and Ducting – plan ducting and wiring before proceeding
with installation.
Refer to Figure 2 for wiring and Figure 1 for ducting. CAUTION: Check area above planned installation to be sure that:
1. Ducting can be installed.
2. Wiring can be run to the planned location.
3. No wiring or other obstructions might interfere with installation.
INSTALLATION FROM ACCESSIBLE AREA ABOVE
1. From below, drill a small hole in ceiling at the planned location. Stick clothes hanger through hole to help locate it.
2. Locate hole in attic or crawl space.
3. In attic or crawl space, mark ceiling for cutout by using the housing as a template. The long side of cutout must be parallel to ceiling joist.
4. Make cutout along marked line.
NOTE: If ceiling is plaster, cutout should be made from below
to avoid chipping plaster.
5. Install housing, connect wiring and ducting, install sensor unit, install power unit/blower assembly and install grille.
SENSOR COVER TABS
SENSOR UNIT
JUNCTION BOX COVER
TIMER ADJUSTMENT
FIGURE 2
JUNCTION BOX
WIRING CONNECTIONS
BLACK
BLACK
BLACK
WHITE
WHITE
WHITE
BLUE
MOTOR PLUG
CONNECTOR
120 VOLT
AC SUPPLY
Loading...
+ 2 hidden pages