NuTone QTXN110SL User Manual

MODEL QTXN110SL
HUMIDITY SENSING FAN / LIGHT / NIGHT LIGHT
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OB­SERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel and lock the ser­vice disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be
done by a qualied person(s) in accordance
with all applicable codes and standards,
including re-rated construction codes and
standards.
4. Sufcient air is needed for proper combustion and exhausting of gases through the ue (chimney) of fuel burning equipment to pre-
vent backdrafting. Follow the heating equip­ment manufacturer’s guideline and safety standards such as those published by the
National Fire Protection Association (NFPA),
and the American Society for Heating, Re­frigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. Acceptable for use over a tub or shower when
connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit.
8. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in
at ceilings only. DO NOT MOUNT THIS PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specication label on product for
further information and requirements.
Installer: Leave this manual
with the homeowner.
OPERATION
The humidity control and fan can be oper-ated separately. Use a 1- or 2-func­tion wall control. Do not use a dimmer switch to operate the humidity control or light. See “Connect Wiring” for details.
SENSOR OPERATION
This humidity-sensing fan responds to:
(a) rapid to moderate humidity increases and (b) humidity above a 50%-100% rela­tive humidity set-point. (a) and (b) are set
with “SENSITIVITY” adjustment. Fan may occasionally turn on when environ-mental conditions change. If the fan contin-uously responds to changing environ-mental condi­tions, “SENSITIVITY” adjust-ment may be
required (see section below).
STATUS INDICATOR
This indicator can only be seen by looking directly at it. Normal mode is 5-seconds on and off. If it blinks rapidly for 5-seconds and then off, check sensor connections on grille and fan housing.
MANUAL ON WITH TIMED OFF
For odor or vapor control, the fan can be en­ergized by cycling its wall-mounted switch
if one is installed. Once the fan has been
turned on in this manner, it will remain on
for the set “TIMER” period.
To manually energize the fan:
1. Go to Step 2 if switch is already on; otherwise, turn switch on for more than 1 second.
2. Switch off for less than 1 second.
3. Switch back on and fan will turn on.
SENSITIVITY ADJUSTMENT
“SENSITIVITY” has been factory set for most shower applications. If the fan is in a tub area or is used for dampness control, the “SENSITIVITY” may need to be in-
creased toward maximum (“MAX.”). If the
control is responding too often to changing environmental conditions, adjustment to-
ward less (“MIN.”) “SENSITIVITY” may be
required. To adjust the “SENSITIVITY”:
1. Turn power off at electrical service panel.
2. Through t h e g rille, l o c a t e t h e “SENSITIVITY” screwdriver slot.
3. Using a small, at-blade screwdriver,
carefully rotate “SENSITIVITY” adjust-
ment toward “MAX.” or “MIN.”
4. Turn power on and check operation by turning on shower or other humidity source until fan turns on.
5. Repeat above steps if necessary.
To register this product visit:
www.nutone.com
TIMER ADJUSTMENT
This humidity-sensing fan has a “TIMER”. It is user-adjustable from 5 to 60 minutes and is factory-set at 20 minutes. The “TIMER” controls how long the fan remains on (a) after rise in humidity and (b) humidity level
are both below the user-adjustable “SEN­SITIVITY” setting or after being energized by cycling power switch.
To adjust the “TIMER”:
1. Disconnect power at electrical service
2. Through the grille, locate the “TIMER”
3. Using a small, at-blade screwdriver,
4. Check operation by cyclin g power
5. Check “TIMER” setting with watch or
6. Repeat above steps if necessary.
CLEANING & MAINTENANCE
For quiet and efcient operation, long life,
and attractive appearance - lower or remove grille and vacuum interior of unit with the dusting brush attachment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the motor with the exact service motor. The impeller should also be replaced.
SENSOR CLEANING
The humidity sensor is mounted in the grille. The sensor will operate most reliably when cleaned occasionally as follows:
1. Disconnect power at service entrance.
2. Remove the grille. Use a dry dustcloth,
3. DO NOT USE cleaning sprays, solvents,
Page 1
panel.
screwdriver slot.
carefully rotate “TIMER” adjustment to desired setting (5 to 60 minutes).
switch as instructed under “MANUAL ON WITH TIMED OFF” or by turning on
a humidity source until fan turns on.
clock after turning humidity source off if it was turned on it Step 4.
clean toothbrush, or lightly vacuum to
clean sensor and grille. DO NOT USE ABRASIVE CLOTH, STEEL WOOL PADS, OR SCOURING POWDERS.
or water on or near the sensor!
MODEL QTXN110SL
Page 2
TYPICAL INSTALLATIONS
Housing mounted to
I-joists.
Housing mounted
anywhere between
I-joists using hanger bars.
• Locate unit above (GFCI protected circuit required) or
within 5 feet of shower head.
• Locate unit away from heating or cooling sources
which can affect humidity levels.
• Do not locate near window. Unit may respond to the outdoor humidity level.
• Unit must be installed in ceiling to properly sense moisture.
• Locate unit only on at ceilings up to 12 feet high for
proper sensing.
• The fan will operate most efciently when located
where the shortest possible duct run and minimum number of elbows will be needed.
2. Plan the wiring.
• Plan to supply the unit with proper line voltage and appropriate power cable. Power cable should be
routed to the switch box rst and then to the unit (See “CONNECT WIRING” on page 3).
• Do not operate this unit with a speed control. Damage to the sensor unit will result.
• Light or night-light may be installed with a wall-
mounted motion control.
Housing mounted to joists.
Housing mounted anywhere
between trusses using
hanger bars.
between trusses using hanger
Housing mounted
anywhere between
joists using hanger bars.
Housing mounted anywhere
bars.
PLAN THE INSTALLATION
1. Choose the installation location.
The location of your humidity sensing fan is very important. Use the follow­ing guidelines for best opera­tion:
6-IN. ROUND
DUCT *
* Purchase
separately
ROOF CAP *
6-IN. ROUND
ELBOW *
WALL
CAP *
INSTALL HOUSING & DUCT
1a. Mount
housing to joist or I-joist.
Use a pliers to
bend housing TABS out
to 900. Hold
housing in place so that the housing tabs contact the bottom of the joist. The housing mounts with
four (4) screws
or nails. Screw or nail housing to joist through lowest holes in each mounting
ange, then through highest holes. NOTE: Mounting to I-JOIST (shown) requires use of SPACERS (included) between the highest hole of each mounting ange and
the I-joist.
(use for mounting to I-Joist)
OR
TABS
SPACER
I-JOIST
MODEL QTXN110SL
MODEL 66V/66W, P66V/P66W
3-FUNCTION CONTROL (PURCHASE SEPARATELY)
LIGHT
(ON/OFF)
COM
NIGHT LIGHT
(ON/OFF)
FAN
(AUTO/OFF)
120 VAC
LINE
IN
SWITCH BOX
WHT
GRD
BLK
BLU
RED
WHT
UNIT
ORG
BLK
WHT
GRD
BLK
RED
LIGHT
NIGHT LIGHT
WHT
WHT
BLK
WHT
BRN
HUMIDITY CONTROL
FAN
MODEL 77DV, 77DW, P77DV, P77DW
4-FUNCTION CONTROL (PURCHASE SEPARATELY)
FAN
(ON/OFF/AUTO)
120
VAC
LINE
IN
SWITCH BOX
GRD
RED
RED
BLU
UNIT
RED
BLU
WHT
GRD
WHT
BLK
BLK
RED
WHT
BLK
NIGHT LIGHT
(ON/OFF)
LIGHT
(ON/OFF)
COM
COM
BLK
BLK
WHT
ORG
WHT
BLK
WHT
BRN
HUMIDITY CONTROL
FAN
WHT
NIGHT LIGHT
LIGHT
Page 3
1b. Mount housing anywhere between
trusses, joists, or I-joists using hanger bars.
Sliding hanger bars are provided to allow for accurate posi-
tioning of housing anywhere between framing. They can be
used on all types of framing (I-joist, standard joist, and truss construction) and span up to 24”.
TAB
SCREWS (4)
HANGER
BAR (4)
Attach the MOUNTING CHANNELS to the housing using the SCREWS supplied. Make sure TABS face “up” as shown. Use the set of channel mounting holes (marked “STD”) to mount the housing ush with the bottom of the drywall. Use the other set of holes (not marked) to mount the housing ush with the top of the drywall.
MOUNTING
CHANNEL (2)
2. Attach damper/ duct connector.
Snap damper / duct con-
nector onto housing. Make sure connector is ush
with top of housing and
damper ap falls closed.
3. Install 6-inch round duc­twork.
Connect 6-inch round
ductwork to damper / duct connector. Run ductwork to a roof cap or wall cap. Tape all ductwork con­nections to make them secure and air tight.
CONNECT WIRING
WIRING OPTION #1 - Allows fan to operate in automatic mode or manual mode (for odor control) by cycling ON/OFF switch.
HOLE FOR OPTIONAL
SCREW MOUNTING (4)
Extend HANGER BARS to the width of the framing.
Hold ventilator in place with the hanger bar tabs wrapping
around the BOTTOM EDGE OF THE FRAMING.
NAIL ventilator to framing or fasten with screws (not provided)
* To ensure a noise-free mount: Secure hanger bars together
through HOLES near nails.
with SCREWS or use a pliers to crimp mounting channels tightly around hanger bars.
NAIL (4)
BOTTOM EDGE
OF FRAMING
SCREW (2)
*
WIRING OPTION #2 - Fan can be turned ON, OFF, or set to operate automatically.
4. Connect electrical wiring.
Run 120 VAC house wiring to installation location. Use
proper UL approved connector to secure house wiring to
wiring plate. Connect wires as shown in wiring diagrams.
Loading...
+ 5 hidden pages