NuTone 9905-RO2 Installation Instructions Manual

Page 1
®
Heat-A-Vent Combination
INSTALLATION INSTRUCTIONS
READ & SAVE THESE INSTRUCTIONS!
93⁄4”
MODEL: 9905-RO2
FOR BEST RESULTS
    In a new construction site, install the housing (complete  with heater and ventilator) during rough-in construction of   the building. The grille should be installed when the finished  ceiling is in place.     Installation in an existing, finished building requires  an accessible area (attic or crawl space) above the  planned location. See “INSTALLATION IN EXISTING  CONSTRUCTION.”     Do not install closer than 12 inches to a vertical surface.  Do not install over tub or shower enclosure.
   • 
 For installation in sloped ceilings up to 12/12 pitch.
   • Ductwork must point up.
UNIT DIMENSIONS
Refer to Figure 1 for housing’s dimensions. NOTE: If there will be a finished second floor above, the Model 9905 housing requires a minimum of 2” x 8” joist construction for mounting.
73⁄4”
14”
FIGURE 1
WIRING AND DUCTWORK
1.  Run the required wiring during rough-in stage of construction.
2.  Total connected load: 1630 watts.
3.  Plan to run 120vAC, 60 Hz wiring (with ground) on a  separate 20 Amp circuit from a power source, through  the provided wall switch, to the housing’s junction box.  See wiring diagram.
4.  Use 4” round duct.
INSTALLATION IN NEW CONSTRUCTION
PREPARATION
1.  Loosen hanger bar brackets to allow bars to be inserted.
2.  Refer to Figure 2. Insert hanger bars into brackets.
3.  Refer to Figure 3. Slide hanger bar brackets down to end  of slot closest to outside edge of housing. Tighten brackets  in this position.
4.  Refer to Figure 4. Remove junction box cover by  removing one screw.
5.  Refer to Figure 4. Remove appropriate wiring knockout(s)  and install approved box connector(s).
HANGER BARS
FIGURE 2
VENT
JUNCTION BOX COVER
HEAT
ADJUSTMENT SLOT
KNOCKOUTS
FIGURE 3 FIGURE 4
Page 2
MOUNTING THE HOUSING
HEAT
VENT
HEATER JUNCTION BOX
HEATER (WHITE)
RED
WHT
BLU.
WHT
VENT
SWITCH
BOX
120vAC LINE
GROUND
WHITE
BLACK
T
NOTE: WHEN THERMOSTAT OR TIMER IS USED, CONNECT AT
T
1. Locate housing between joists.
2.  Refer to Figure 5. Using nails, secure hanger bars to joists.
NOTE: The hanger bar brackets are adjustable. Allowing for the thickness of the finished ceiling, mount hanger bars so that edge of housing will be flush with the finished ceiling.
3.  Adjust brackets as required. Tighten brackets.
INSTALLING THE DUCTWORK
1.  Refer to Figure 5. Install duct collar.
2.  Using 4” round duct, connect duct to collar and tape  connection.
INSTALLING THE SWITCH
1.  Install double-gang switch box in chosen location.
2.  Refer to Figure 6. Run wiring and make wiring  connections.
3.  Use supplied screws to secure switch bracket assembly  to switch box.
4.  Using supplied screws, secure wall plate to switch bracket.
INSTALLING AND CONNECTING THE WIRING
Refer to Figure 6. All wiring must comply with local codes and unit must be properly grounded.
1.  Using 12-gauge wire, run 120vAC, 60 Hz wiring (with  ground) from a power source to the wall switch location. 
The unit must be wired on a separate 20 Amp circuit.
2.  Run wiring from switch location to housing as shown in the  wiring diagram.
3.  Make wiring connections as shown in wiring diagram.
4.  Replace junction box cover. Slide slotted hole in cover  over screw. Tighten screw securely.
5.  Secure wire cover with one screw.
6.  Insert heater and ventilator plugs into proper receptacles  as shown.
DUCT COLLAR
FIGURE 5
MOUNTING THE GRILLE ASSEMBLY
1.  Refer to Figure 7. Using two screws (provided), secure  grille to housing.
FIGURE 6
Page 3
INSTALLATION IN EXISTING CONSTRUCTION
    In an existing, finished building, installation of the Heat­Vent Combination requires an accessible area (attic or crawl  space) above the planned location. If the location that has  been chosen for installation has a finished floor above it,   be certain there is sufficient space available to install the  housing and make the necessary duct connection.
PLANNING
    Review “INSTALLATION IN NEW CONSTRUCTION” and  follow all instructions that apply.
CAUTION: Check the area above the planned location to make sure that:
(1)  Ducting can be installed or that the area is sufficient for 
proper venting. (2)  Wiring can be run to the planned location. (3)  No wiring or other obstructions might interfere with 
the installation.
INSTALLATION
1.  The housing must be mounted between ceiling joists.
2.  Refer to Figure 8. Mark ceiling for cutout.  
Cutout dimensions: 141⁄8” long x 97⁄8” wide. Make cutout   in ceiling.
3.  Follow steps under “PREPARATION” page 1.
4.  From above, lower housing into the cutout and secure 
hanger brackets. Install duct collar, connect duct, and   run wiring through box connectors.
5.  From below, adjust housing so that it is flush with the 
finished ceiling.
6.  From below, make wiring connections as shown in figure 
6.
7.  Replace junction box cover.
8.  Insert heater and ventilator plugs into proper receptacles.
9.  Install grille.
GRILLE
FIGURE 7
141⁄8”
NOTE: This heater is provided with a Self-Hold resetable 
thermal protector. If the heater shuts off during operation, turn  to off at the wall switch and wait approximately 15 minutes  before turning back on. If heater does not reset or trips  repeatedly, contact a NuTone service center.
97⁄8”
FIGURE 8
Page 4
One Year Limited Warranty WARRANTY OWNER:  Broan-NuTone warrants to the original consumer purchaser of its products that such products will be  free from defects in materials or workmanship for a period of one (1) year from the date of original purchase. THERE ARE  NO OTHER WARRANTIES, EXPRESS  OR  IMPLIED,  INCLUDING, BUT  NOT LIMITED TO, IMPLIED WARRANTIES OF  MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  During this one year period, Broan-NuTone will, at its option, repair or replace, without charge, any product or part which is  found to be defective under normal use and service. THIS WARRANTY DOES NOT EXTEND TO FLUORESCENT LAMP  STARTERS OR TUBES, FILTERS, DUCT, ROOF CAPS, WALL CAPS AND OTHER ACCESSORIES FOR DUCTING. This  warranty does not cover (a) normal maintenance and service or (b) any products or parts which have been subject to misuse,  negligence, accident, improper maintenance or repair (other than by Broan-NuTone), faulty installation or installation contrary  to recommended installation instructions.
The duration of any implied warranty is limited to the one year period as specied for the express warranty. Some states do
not allow limitation on how long an implied warranty lasts, so the above limitation may not apply to you. Broan-NuTone’S OBLIGATION TO REPAIR OR REPLACE, AT Broan-NuTone’S OPTION, SHALL BE THE PURCHASER’S  SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY. Broan-NuTone SHALL NOT BE LIABLE FOR INCIDENTAL,  CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION  WITH  PRODUCT USE OR PER­FORMANCE. Some  states  do not allow  the exclusion or  limitation of incidental  or consequential damages,  so the above 
limitation or exclusion may not apply to you. This warranty gives you specic legal rights, and you may also have other rights,
which vary from state to state. This warranty supersedes all prior warranties. WARRANTY SERVICE: To qualify for warranty service, you must (a) notify Broan-NuTone at the address or telephone num-
ber below, (b) give the model number and part identication and (c) describe the nature of any defect in the product or part.
At the time of requesting warranty service, you must present evidence of the original purchase date. 
Date of Installation 
Builder or Installer
Model No. and Product Description
IF YOU NEED ASSISTANCE OR SERVICE - CONTACT: Broan-NuTone LLC    Hartford, Wisconsin    www.nutone.com    888-336-3948 Broan-NuTone Canada    Mississauga, Ontario    www.nutone.ca    877-896-1119
Rev. 08/2007
Product specifications subject to change without notice.
Printed in Canada, 01/2008, Part No. 100992
Loading...