NuTone 9905-RO2 Installation Instructions Manual

®
Heat-A-Vent Combination
INSTALLATION INSTRUCTIONS
READ & SAVE THESE INSTRUCTIONS!
93⁄4”
MODEL: 9905-RO2
FOR BEST RESULTS
    In a new construction site, install the housing (complete  with heater and ventilator) during rough-in construction of   the building. The grille should be installed when the finished  ceiling is in place.     Installation in an existing, finished building requires  an accessible area (attic or crawl space) above the  planned location. See “INSTALLATION IN EXISTING  CONSTRUCTION.”     Do not install closer than 12 inches to a vertical surface.  Do not install over tub or shower enclosure.
   • 
 For installation in sloped ceilings up to 12/12 pitch.
   • Ductwork must point up.
UNIT DIMENSIONS
Refer to Figure 1 for housing’s dimensions. NOTE: If there will be a finished second floor above, the Model 9905 housing requires a minimum of 2” x 8” joist construction for mounting.
73⁄4”
14”
FIGURE 1
WIRING AND DUCTWORK
1.  Run the required wiring during rough-in stage of construction.
2.  Total connected load: 1630 watts.
3.  Plan to run 120vAC, 60 Hz wiring (with ground) on a  separate 20 Amp circuit from a power source, through  the provided wall switch, to the housing’s junction box.  See wiring diagram.
4.  Use 4” round duct.
INSTALLATION IN NEW CONSTRUCTION
PREPARATION
1.  Loosen hanger bar brackets to allow bars to be inserted.
2.  Refer to Figure 2. Insert hanger bars into brackets.
3.  Refer to Figure 3. Slide hanger bar brackets down to end  of slot closest to outside edge of housing. Tighten brackets  in this position.
4.  Refer to Figure 4. Remove junction box cover by  removing one screw.
5.  Refer to Figure 4. Remove appropriate wiring knockout(s)  and install approved box connector(s).
HANGER BARS
FIGURE 2
VENT
JUNCTION BOX COVER
HEAT
ADJUSTMENT SLOT
KNOCKOUTS
FIGURE 3 FIGURE 4
MOUNTING THE HOUSING
HEAT
VENT
HEATER JUNCTION BOX
HEATER (WHITE)
RED
WHT
BLU.
WHT
VENT
SWITCH
BOX
120vAC LINE
GROUND
WHITE
BLACK
T
NOTE: WHEN THERMOSTAT OR TIMER IS USED, CONNECT AT
T
1. Locate housing between joists.
2.  Refer to Figure 5. Using nails, secure hanger bars to joists.
NOTE: The hanger bar brackets are adjustable. Allowing for the thickness of the finished ceiling, mount hanger bars so that edge of housing will be flush with the finished ceiling.
3.  Adjust brackets as required. Tighten brackets.
INSTALLING THE DUCTWORK
1.  Refer to Figure 5. Install duct collar.
2.  Using 4” round duct, connect duct to collar and tape  connection.
INSTALLING THE SWITCH
1.  Install double-gang switch box in chosen location.
2.  Refer to Figure 6. Run wiring and make wiring  connections.
3.  Use supplied screws to secure switch bracket assembly  to switch box.
4.  Using supplied screws, secure wall plate to switch bracket.
INSTALLING AND CONNECTING THE WIRING
Refer to Figure 6. All wiring must comply with local codes and unit must be properly grounded.
1.  Using 12-gauge wire, run 120vAC, 60 Hz wiring (with  ground) from a power source to the wall switch location. 
The unit must be wired on a separate 20 Amp circuit.
2.  Run wiring from switch location to housing as shown in the  wiring diagram.
3.  Make wiring connections as shown in wiring diagram.
4.  Replace junction box cover. Slide slotted hole in cover  over screw. Tighten screw securely.
5.  Secure wire cover with one screw.
6.  Insert heater and ventilator plugs into proper receptacles  as shown.
DUCT COLLAR
FIGURE 5
MOUNTING THE GRILLE ASSEMBLY
1.  Refer to Figure 7. Using two screws (provided), secure  grille to housing.
FIGURE 6
Loading...
+ 2 hidden pages