NTI Ti100-200, Ti150-200 Installation And Operation Instructions Manual

H
US Models
NTI # 82419
NTI – TRINITY Ti
INSTALLATION AND OPERATION INSTRUCTIONS
Ti100-200 Boilers and Ti150-200 Combi Models
VERSION DATE: 2013-05-21
TABLE OF CONTENTS
1.0 SPECIFICATIONS ........................................................................................... 4
HAZARD SYMBOL DEFINITIONS
Danger Sign: Indicates a hazardous situation which, if not avoided, will result in serious injury or death.
Warning Sign: Indicates a hazardous situation which, if not avoided, could result in serious injury or death.
Caution Sign plus Safety Alert Symbol: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Caution Sign without Safety Alert Symbol: Indicates a hazardous situation which, if not avoided, could result in property damage.
Notice Sign: Indicates a hazardous situation which, if not avoided could result in property damage.
2
Trinity Installation and Operation Instructions Ti Series
0.0 INTRODUCTION General Installation Requirements
The installation of the NTI Trinity Ti gas boiler must conform to the requirements of this manual, your local authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where required by the Authority Having Jurisdiction, the installation must conform to the standard for “Controls and Safety Devices for Automatically Fired Boilers ANSI/ASME CSD-1.
This document pertains to the correct installation and operation of NTI Trinity Ti boiler models Ti100, Ti150 and Ti200. The instructions detailed in this document supersede any and all previous instructions provided by NTI, written or otherwise. Each unit is provided with the following:
1) Installation and Operation Instruction Manual for Trinity Ti Series,
2) Trinity Users Manual and,
3) Trinity Natural to LP Conversion Kit * * The conversion kit is required to convert the appliance so it will safely operate with Propane Gas.
Read and understand this entire document prior to proceeding with the installation of the Trinity Ti. Failure to follow instructions outlined in this document will result in property damage, injury or death.
User Responsibilities
This appliance must be installed and serviced by a qualified installer or service technician. This appliance must be serviced and inspected annually when operating in normal residential applications. Demanding applications or extreme conditions (i.e. commercial) may require more frequent service and inspection. As the User/Owner of this equipment, you are responsible for ensuring the maintenance is performed at the required intervals. It is also the Users responsibility to ensure the Vent and Combustion-Air Intake termination is kept clear of ice and snow or any other obstruction. Failure to follow these instructions could result in fire, serious injury, or death.
Failure to have the appliance properly serviced and inspected on a regular basis may result in property damage, serious injury or death.
Failure to keep the Vent and Combustion Air Intake clear of ice, snow, and other debris may result in property damage, serious injury, or death.
Installer Responsibilities
As the installing technician it is your responsibility to ensure the installation is performed in accordance with this instruction manual as well as any applicable local or National installation codes. It is also your responsibility to inform the User/Owner of their obligation with respect to the above description under “User Responsibilities”. Failure to follow this warning could result in fire, serious injury, or death.
ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE
The Trinity Ti is factory set to operate with Natural Gas. BEFORE OPERATING WITH PROPANE, the specified LP Conversion Kit must be installed to convert the appliance so it will operate safely with LP Propane. Listed below is the correct Natural to LP Propane Conversion Kit number for Trinity Ti100-200 boiler models. Note: kit number 82650-1 contains two LP conversion orifices. The smaller orifice, labeled 34, must be used in the Ti100, while the larger orifice, labeled 52, must be used in the Ti150 and Ti200.
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your Trinity Ti boiler is not installed in a pit or similar location that will permit heavier than air gas to collect. Local Codes may require appliances fueled with LP gas be provided with an approved means of removing unburned gases from the room. Check your local codes for this requirement.
Natural to LP Propane Conversion Kit_ NTI Series Model Number Kit Number Trinity Ti 100, 150, 200 82650-1
Refer to the above, ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE for correct conversion kit number.
Appliance Vent / Air-Intake Piping
in these instructions. Failure to follow instructions will result in serious injury or death.
Failure to use the appropriate Natural to LP Conversion Kit when operating the Trinity Ti with Propane will result in extremely dangerous burner operation leading to property damage, serious injury or death.
The Trinity Ti is a “Direct Vent” appliance requiring a “Special Venting System”. Vent and Combustion-Air Intake piping must be piped to the outdoors, using the vent material and rules outlined
Ti Series Installation and Operation Instructions Trinity
3
Energy Saving Feature - This boiler is equipped with a feature that saves energy by reducing
the boiler water temperature as the heating load decreases. This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function. THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE :
An external energy management system is installed that reduces the boiler water temperature as the heating load
decreases.
This boiler is not used for any space heating. This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater. This boiler is equipped with a tankless coil.
IN THE STATE OF MASSACHUSETTS ONLY
(a) For all horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or
in part for residential purposes, including those owned and operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed and on each additional level of the dwelling, building or structure served by the equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of 30 days to comply with the above requirements; provided, however, that during said 30 day period a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in
accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS (plate included with appliance).
4. INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall
not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM PROVIDED: When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED:
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide
the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be
satisfied by the manufacturer.
4
DESCRIPTION
Ti100
Ti150
Ti200
CSA Input Modulation
1
btu/hr [kw]
15,000 - 93,000
[4.4 – 29.3]
25,000 - 150,000 2
[7.3 - 44.0]
25,000 - 199,000
[7.3 - 58.3]
DOE Heating Capacity
1,3
btu/hr [kw]
84,000
[24.6]
136,000
[39.8]
181,000
[53]
Net I=B=R Rating
1,3
btu/hr [kw]
73,000
[21.4]
118,000
[34.8]
157,000
[46]
DOE AFUE %
3
93.5
Water Connections - NPT, in.
1 4
1
Gas Connection - NPT, in.
1/2
Vent/Air-Intake Pipe Diameter 5, in. [mm]
3 or 4 [76 or 102]
Vent/Air-Intake, Max. Length, NG / LP ft. [m]
105 / 105
[32 / 32]
105 / 50
[32 / 15.2]
105 / 50
[32 / 15.2]
Dimensions H x W x D in. [mm]
22.5 x 15.5 x 16.75
6
[571 x 394 x 425]
22.5 x 15.5 x 16.75
6
[571 x 394 x 425]
22.5 x 15.5 x 18.25 [571 x 394 x 464]
Approx. Appliance Weight with Water, lbs [kg]
80 [36.3]
80 [36.3]
110 [49.9]
Notes:
1
Listed Input and Output ratings are at minimum vent lengths at Sea Level. Numbers will be lower with longer venting
and/or altitudes greater then 2000 feet [610 m].
2
The maximum output when operating on LP-Gas is limited to 145,000 Btu/hr [42.5 kW].
3
Based on rating plate input capacities, using standard test procedures prescribed by the U.S. Department of Energy.
Ratings have been confirmed by AHRI (GAMA).
4
Units sold in Canada are 3/4” NPT.
5
Trinity Ti units require a special venting system, use only vent materials and methods detailed in these instructions.
6
Ti100 and 150 units sold in Canada have a depth of 14.75”.
Elevations
2000 ft [610 m]
3000 ft [914 m]
4000 ft [1219 m]
4500 ft [1372 m]
5000 ft [1524 m]
In Canada 1
de-rate by 5%
de-rate by 5%
de-rate by 5%
de-rate by 5%
de-rate % may vary
In USA 2
-
de-rate by 4%
de-rate by 8%
-
de-rate by 12%
Notes:
1
Canada: Altitudes between 2000-4500 ft [610-1372 m], de-rate by 5%. Consult local authorities for de-rating capacities for altitudes above 4500 ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m] over 2000 ft [610 m].
Trinity Installation and Operation Instructions Ti Series
1.0 SPECIFICATIONS
Table 1-1 Specifications
This unit requires two people to lift it or property damage and personal injury may result.
High Altitude Operation
The Trinity is designed to operate at its maximum listed capacity in installations less than or equal to 2000 ft [610 m] above Sea Level. Since the density of air decreases as elevation increases, maximum specified capacity should be de-rated for elevations above 2000 ft [610 m] in accordance with Table 1-2.
Table 1-2 De-rate % for High Altitudes
At elevations greater than 2000 feet, the combustion of the appliance must be checked with a calibrated combustion analyzer to ensure safe and reliable operation. Consult Section 8.0 for instructions on
adjusting the input to provide proper operation. It is the Installers responsibility to check the combustion, and to adjust the
combustion in accordance with Section 8.0. Failure to follow these instructions may result in property damage, serious injury, or death.
Ti Series Installation and Operation Instructions Trinity
5
Model No.
Clearances
Dimensions - inches [mm]
Front
Top
Sides
Bottom
Rear
Flue/Water Pipe
Trinity Ti100-200
Minimum
24 [610] 1
12 [305]
12 [305]
9 [229] 0 1 [25]
Recommended
24 [610]
24 [610]
24 [610] 2
9 [229] 0 1 [25]
Notes:
1
6” if surface is removable allowing 24” [610 mm] clearance (i.e. closet installation). See “Appliance Ventilation Air Openings” above.
2
Clearances can be as low as 12” [305 mm] on one side if clearance on the other side is 24” [610 mm].
2.0 BOILER LOCATION
In all cases, the Trinity Ti must be installed indoors in a dry location where the ambient temperature must be maintained above freezing and below 100F [38C]. Gas components must be protected from dripping, spraying water, or rain during operation and servicing. Consider the proximity of system piping, gas and electrical supply, condensate disposal drain, and proximity to vent termination when determining the best appliance location.
Water or flood damaged components must be replaced immediately with new factory-approved components as failure to do so may result in fire, serious injury, or death.
Appliance Area Ventilation Air Openings
If appliance area clearances are less then the recommended clearances specified in Table 2-1, the appliance area must be ventilated. Each ventilation air opening must meet the minimum requirements of 1 in2 per 1000 Btu/hr, but not less then 100in2.
The lower ventilation opening must be located within 6” of the floor while the upper opening must be located 6” from the top of
the space.
Closet Installations
For closet installations, it is necessary to provide two ventilation air openings, each providing a minimum area equal to 1 in2 per 1000 Btu/hr, but not less then 100 in2 and within 6” of the top and bottom of the closet door. All Vent and Air-Intake piping within the closet must be CPVC for both Canada and the US. See Table 2.1 for Minimum and Recommended Clearances.
Alcove Installations
Alcove installations have the same minimum clearances as closet installations, except the front must be completely open to the room at a distance no greater then 18” [457 mm] from the front of the appliance and the room is at least three (3) times the size of the alcove. Provided these conditions are met, the appliance requires no extra ventilation air openings to the space. All Vent and Air-Intake piping within the alcove must be CPVC for both Canada and the US. See Table 2-1 for Minimum and Recommended Clearances.
Residential Garage Installations
When installed in a residential garage, mount the appliance a minimum of 18” [457 mm] above the floor. Locate or protect the appliance so it cannot be damaged by a moving vehicle. Check with your local authorities for other possible regulations pertaining to the installation of an appliance in a garage.
Table 2-1 Minimum Clearances for Installation and Service
The appliance area is considered to be a closet or alcove if the area does not provide the recommended clearances listed in Table 2-1. See special instructions under Closet and Alcove Installations.
6
Products to Avoid
Contaminated Sources to Avoid
Antistatic fabric softeners, bleaches, detergents, cleaners
Laundry facilities
Perchloroethylene (PCE), hydrocarbon based cleaners
Dry cleaning facilities
Chemical fertilizer, herbicides/pesticides, dust, methane gas
Farms or areas with livestock and manure
Paint or varnish removers, cements or glues, sawdust
Wood working or furniture refinishing shops
Water chlorination chemicals (chloride, fluoride)
Swimming pools, hot tubs
Solvents, cutting oils, fiberglass, cleaning solvents
Auto body or metal working shops
Refrigerant charge with CFC or HCFC
Refrigerant repair shops
Permanent wave solutions
Beauty shops
Fixer, hydrochloric acid (muriatic acid), bromide, iodine
Photo labs, chemical / plastics processing plants
Calcium Chloride
De-Icing / Ice Melters
Cement powder, crack fill dust, cellulose, fiber based insulation
Concrete plant or construction site
Trinity Installation and Operation Instructions Ti Series
3.0 GENERAL VENTING
The Trinity Ti is a “Direct Vent” appliance requiring a “Special Venting System” designed for pressurized venting. Both the Vent and Air-Intake piping must be piped to the outdoors, using the vent material and rules outlined in this section. Under no conditions may this unit vent gases into a masonry chimney, unless it is vacant, and utilizes the approved venting material and rules described in this section. Installations must comply with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or CSA B149.1 (Canada) and local requirements.
Vent and Air-Intake to be piped separately. The Trinity Ti cannot share a common vent or air-intake with multiple appliances. Failure to comply will result in serious injury or death.
Combustion Air-Intake Contamination
Be careful not to locate the Air-Intake termination in an area where contaminants can be drawn in and used for combustion. Combustion air containing dust, debris or air-borne contaminants will drastically increase the required maintenance and may cause a corrosive reaction in the Heat Exchanger which could result in premature failure, fire, serious injury, or death. See Table 3-1 for a list of areas to avoid when terminating air-intake piping:
Table 3-1 Corrosive Products and Contaminant Sources
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Failure to follow instructions may result in serious injury or death.
Flammable Solvents and Plastic Piping
Due to the extremely flammable characteristics of most glues, cements, solvents and primers used in the process of joining plastic vent and air-inlet pipe, explosive solvent vapors must be evacuated from the vent and air-intake prior to start-up. Avoid using excess cement or primer that may lead to pooling inside the pipe assembly. Freshly assembled piping should be allowed to cure for a minimum of 8 hours before applying power to the gas fired appliance. Refer to Mandatory Pre-commissioning Procedure
for Plastic Venting in this section.
Flammable Cements and Primers – It is the installers’ responsibility to familiarize themselves with
the hazards associated with explosive solvents and to take all precautions to reduce these risks. Failure
to follow these instructions can cause explosions, property damage, injury or death.
Near Boiler Vent/Air-Intake Piping
Each Trinity Ti is equipped with a short piece of approved CPVC vent pipe. Insert one end into the boiler flue outlet adapter and cement the other to field venting (see Table 3-3 for approved venting material). The CPVC vent pipe should extend fully into the boiler flue outlet adapter (see Table 3-2). DO NOT insert PVC pipe directly into the flue outlet connection as it can deform from the clamping force of the gear clamp. Ensure that the venting system does not apply a load or strain on the boiler flue outlet adapter. The manufacturer recommends using two elbows to create a “swing joint” to reduce potential strain on vent piping and cemented joints. See Figure 3-1 for illustration.
Gasket Seating - Improper seating can cause leakage and eventual failure of the sealing gasket. Failure to follow these instructions may result in serious injury or death.
Ti Series Installation and Operation Instructions Trinity
7
Swing Joint to attain slope in horizontal runs
Exhaust Vent
3”PVC, (check local
codes and Table 3-3)
Coupling - 3”PVC
Transition Piece
3” CPVC, minimum 5” long (factory
supplied)
Flue Outlet Stainless Steel Adapter (factory supplied)
Air Inlet Adapter Immediately adapt from 1-1/2”
to 3”
Cleanout Recommended on Air Inlet Piping
Figure 3-1(a)
Figure 3-1(b)
Near Boiler Venting (CPVC)
Near Boiler Venting (PVC)
Model No.
CPVC Vent Pipe Size
CPVC Transition Vent Pipe Length
Full Insertion Depth
Trinity Ti100-200
3”
Minimum 5” [127 mm]
2-7/8” [73 mm]
Flue Outlet Stainless Steel Adapter (factory supplied)
Swing Joint to attain slope in horizontal runs
Exhaust Vent
3”CPVC
Air Inlet Adapter Immediately adapt from 1-1/2”
to 3”
Cleanout Recommended on Air Inlet Piping
Air-Inlet - check with applicable local codes for acceptable pipe material.
Exhaust venting must be supported to reduce strain on piping joints. Failure to follow these instructions may result in result in damage, serious injury or death.
In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection.
Table 3-2 Mandatory Vent Pipe Transition Piece
8
Items 1
Materials
2, 3
Installation Standards
All Vent and Air-Intake materials installed on gas fired appliances in CAN/US must meet the Standards listed in Table 3-3. Failure to comply could result in fire, serious injury or death.
United States
Canada 4
Vent Piping and Fittings
PVC - DWV
ANSI/ASTM D2265
All venting material in
Canada must be
ULC S636 approved.
See Note 4 below for
appropriate temperature
applications.
PVC Schedule 40
ANSI/ASTM D1785
CPVC Schedule 40
ANSI/ASTM F441
AL29-4C
UL-1738
Polypropylene (PP)
n/a
Pipe Cement PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
Primers
PVC / CPVC
ANSI/ASTM F656
Notes:
1
Refer to Table 3-4 for Allowable Vent and Air-Intake Pipe Sizes and Lengths.
2
PVC venting (exhaust and air-intake) is not permitted within the Closet/alcove of a Closet/alcove installation.
3
The Air-Intake does not require high temperature pipe material. Check applicable local codes for acceptable materials.
4
ULC S636 PVC is approved for flue gas temperatures up to 149oF (65oC) and must only be used for low temperature applications. High temperature applications requiring appliance supply water temperatures greater than 140oF (60oC) must use ULC S636 CPVC, PP or AL29-4C.
Trinity Installation and Operation Instructions Ti Series
Vent/Air-Intake Pipe Material
Table 3-3 Acceptable Vent and Air-Intake Pipe Material
The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in the exhaust venting system is prohibited. Failure to follow these
instructions may result in property damage, personal injury or death.
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. Failure to follow these instructions may result in property damage, personal injury or death.
Mandatory Pre-commissioning Procedure for Plastic Venting
1) Working with the power turned off to the boiler, completely install the vent and air intake system, securely cementing joints
together. If possible, allow primers/cements to cure for 8 hours before firing the burner. If curing time is less than 8 hours, proceed with Steps 2 through 6.
2) Maintain the boiler gas supply shut-off valve in the off position.
3) Disconnect electrical leads to the Hot Surface or Spark Igniter. Ensure the cables are placed in a fashion where they will not
arc to ground or other conductor.
4) Turn power on to the boiler and apply a heat demand.
5) Allow for 3 complete trials for ignition, consisting of pre and post purge of the combustion blower, until an ignition lockout
occurs. Repeat the process two more times (i.e. 9 complete ignition sequences in total).
6) Turn power off and reconnect the electrical leads to the Igniter.
Do not apply power to the boiler prior to Step 4 in the Mandatory Pre-commissioning Procedure for Plastic Venting.
Ti Series Installation and Operation Instructions Trinity
9
Model
Pipe Size
Gas
Length
ft. [m]
Number of Elbows (90’s or 45’s) and Equivalent Feet [Meters]
1 2 3 4 5 6 7 8 9
Ti150 Ti200
3”
LP
50
[15.2]
45
[13.7]
40
[12.2]
35
[10.7]
30
[9.1]
25
[7.6]
20
[6.1]
15
[4.6]
10
[3.0]
5
[1.5]
3”
NG
105
[32]
100
[30.5]
95
[28.9]
90
[27.4]
85
[25.9]
80
[24.4]
75
[22.9]
70
[21.3]
65
[19.8]
60
[18.3]
4”
NG
& LP
105
[32]
100
[30.5]
95
[28.9]
90
[27.4]
85
[25.9]
80
[24.4]
75
[22.9]
70
[21.3]
65
[19.8]
60
[18.3]
Ti100
3” or 4”
NG
& LP
105
[32]
100
[30.5]
95
[28.9]
90
[27.4]
85
[25.9]
80
[24.4]
75
[22.9]
70
[21.3]
65
[19.8]
60
[18.3]
NTI
P/N
IPEX
P/N
Description
1,2,4
Vent Kit Material
Kit
Connection
Vent Option
Roof
Wall
82666
196116
Concentric Vent Termination Kit (CAN)
4,5
ULC S636
PVC
3"
84355
196021
4"
n/a
197009
Concentric Vent Termination Kit (CAN)
4,5
ULC S636
CPVC
3"
84357
196985
Low Profile Termination Kit (Flush Mount)
PVC
3"
84358
196986
4"
Notes:
1
Instructions included with termination kits contain more detailed assembly and installation instructions.
2
Clearance requirements in this manual supersede those of the instructions included with the vent terminal.
3
Terminal MUST be cemented together and to the vent pipes during installation.
4
Certified to ULC S636.
5
Vent Screen provided with boiler may be used with the IPEX Concentric Vent Kits; otherwise use IPEX vent screens (3"
vent screen P/N 196051; 4" vent screen P/N 196052).
Vent and Air-Intake Pipe Length Determination
Use Table 3-4 to determine the maximum pipe length that can be used. The table calculates sweep, 90º elbows, and 45º elbows at 5 equivalent feet [1.52 m] each. Note: models Ti150-200 have limitations when operating with Propane Gas (LP).
Example: A Ti200 can be installed with 105 equivalent feet [32 m] of air-intake piping and 105 equivalent feet [32 m] of vent piping when operating with Natural Gas. When operating with Propane Gas (LP), the maximum vent length in equivalent feet is
limited to 50’ (3” pipe).
The length of one vent pipe (intake or exhaust) may not exceed the length of the other vent pipe by more than 20 equivalent feet (6.1 m).
Table 3-4 Allowable Vent and Air-Intake Pipe Size and Lengths
Termination Options
The venting system of the Trinity Ti may be terminated using field supplied piping to construct a “Two-Pipe” termination, see Figures 3-3, 3-4a, 3-6, 3-9, 3-10 and 3-11. Alternatively, the venting may be terminated used a factory kit, either “Concentric” (see Figures 3-2, 3-4b, 3-5 and 3-7) or “Low Profile” (see Figure 3-8). The Concentric Vent Termination Kit can be either Roof or Sidewall terminated, while the Low Profile Termination Kit may only be Sidewall terminated. See Table 3-5 for details on the optional termination kits.
Venting Options - Due to potential moisture loading (build-up) along the exterior wall, sidewall venting may not be the preferred venting option. See Figs 3-2(b) and 3-3(b).
Optional Termination Kits Kits certified with the Trinity Ti are listed in Table 3-5 and available from IPEX and/or NTI. For more information on System 636
Concentric Vent Kits or wholesaler locations contact IPEX directly. USA: 1-800-463-9572 or www.IPEXamerica.com CAN: 1­866-473-9462 or www.ipexinc.com.
Table 3-5 Optional Vent Termination Kits
10
Figure 3-2(a)
Figure 3-2(b)
Concentric Side Wall Termination (Optional Kit)
Concentric Roof Termination (Optional Kit)
Figure 3-3(a)
Figure 3-3(b)
Two-Pipe Side Wall Termination
Two-Pipe Roof Termination
Trinity Installation and Operation Instructions Ti Series
Ti Series Installation and Operation Instructions Trinity
11
Labeling and Identification – Roof Top Terminations
Figure 3-4(a)
Figure 3-4(b)
Two-Pipe Roof Top Termination
Concentric Vent Roof Top Termination
Two-pipe terminations typically penetrate the roof surface. An alternative is to use an existing chimney as a chase way. See Figure 3-11 for more details.
To prevent water leakage, install adequate roof weather seal flashing (not included) around roof penetration as shown.
Labeling and Identification – Concentric Vent Side Wall Terminations
Figure 3-5(a)
Figure 3-5(b)
Concentric Vent Side Wall Termination
Concentric Vent Detail
Insert vent screen between the end of the boiler exhaust vent and the end cap as shown. The End Cap
Insert vent screen between the end of the boiler exhaust vent and the end cap as shown. The End Cap must be secured to the vent pipe via cement or stainless steel screws.
Warning Plate
From boiler
To boiler air­inlet connection
Exhaust Vent Outlet (center)
Gas Vent Directly Below
Keep Free of Obstructions
Concentric “Y” Fitting
Combustion Air-Inlet (perimeter)
Support (field supplied)
To boiler air-inlet connection
From boiler exhaust Air-Inlet
Roof weather seal flashing (field supplied)
24” [610 mm]
from terminal end cap vanes
Exhaust Vent
Exhaust Vent
Air-Inlet
Chimney Cap
Existing Chimney (used as a chase way)
Flashing
Exhaust Vent
Combustion Air Inlet
End Cap Vanes (typical)
End Cap
Exterior Wall
12
Labeling and Identification – Two Pipe Side Wall
Labeling and Identification – Optional Kit
Figure 3-6
Figure 3-7
Two-Pipe Side Wall Termination
Concentric Vent Termination Kit
Labeling and Identification – Low Profile Termination Kit
Figure 3-8
Low Profile Termination Kit
Warning Plate
Exhaust Vent
Vent Screen
Vent Screen
Insert vent screen into socket joint of termination elbow. Secure by cementing a short piece of venting into the socket.
Venting
Vent Screen
Gas Vent Directly Below
Keep Free of Obstructions
Combustion Air-Inlet
Venting
Fully Assembled
and Installed
Air-Inlet Piping
Exhaust Venting
Approved Orientation
Base
Cap
Low Profile Termination Kit
The vent /air-inlet pipes are field supplied. Vent screens are build in. Major components provided in Low Profile Kit include: base, cap, s.s. screws, and plastic anchors.
Concentric Vent Termination Kit
Insert Vent Screen into the End Cap from the outside, followed by a short piece of vent pipe to retain the Vent Screen in place. The End Cap must be secured to the Exhaust Vent via cement or stainless steel screws. Refer to Figure 4-12 for more details.
Air Inlet Pipe
Exhaust Vent
Vent Screen (Included w. boiler)
End Cap
Retaining Exhaust Pipe Piece
Trinity Installation and Operation Instructions Ti Series
Ti Series Installation and Operation Instructions Trinity
13
Venting Rules and Guidelines
1. Prevailing Winds: Ensure the vent is located where it will not be exposed to normal prevailing winds.
2. Combustion Air-Intake Contamination: Air for combustion must be drawn from outdoors from an area free of dust and
contaminants. Combustion air containing chemicals such as chloride, fluoride, bromine or iodine or dust and debris will cause corrosion damage of the heat exchanger voiding your NTI warranty. Refer to Table 3-1 for a list of corrosive products and contaminants sources to avoid.
3. Vertical Separation: The exhaust must be a minimum of 18” [457 mm] above the air inlet, and the air inlet must always be
a minimum of 12” [305 mm] plus snow allowance above any surface that will support snow. (Two feet plus snow allowance
is highly recommended). Consult your weather office, for the maximum typical snowfall for your region.
Example: New Brunswick Canada - typical maximum snowfall is 19”, thus the inlet must be (12”+19”) = 31” above grade
and exhaust must be (31”+18”) = 49” above grade.
4. Horizontal Separation: The horizontal distance between the inlet and exhaust must be a minimum of 4” [102 mm] center
to center. When the horizontal distance between the inlet and exhaust is greater than 12” [305 mm], the difference in horizontal distance must be determined and the vertical separation increased by the same amount.
Example: The horizontal distance (HD) = 24” [610 mm] and the vertical separation (VSmin) = 18” [457 mm], the new
vertical separation (VSnew) can be calculated using the following equation: VSnew = (HD - 12”) + VS, where VSnew = (24” - 12”) + 18” = 30”. (If the horizontal distance is greater than 6’ [1.83 m], no additional vertical spacing is required. Vertical separation is never
required to be greater than 36” [915 mm].
5. Wall Flashing: Under normal operating conditions this boiler will produce a plume of white gases, and should be taken into
consideration when selecting an adequate location. A 36” [915 mm] diameter stainless, plastic, or vinyl shield can be used to
flash the exterior of the residence.
6. Flue Gas Hazard: Position the vent termination where vapors cannot make accidental contact with people and pets or
damage nearby shrubs and plants.
7. Elbow Extensions: Elbows on outside of wall must be no more than ½” [13 mm] away from the wall.
8. Vent Sloping: All indoor exhaust piping must be on a slope back to the boiler a minimum of ¼” per linear foot of vent [6.25
mm per linear 305 mm]. For applications where excessive condensation is possible ½” per linear foot [13 mm per linear 305
mm] is recommended.
9. Vent Supports: Where required Vent and Air-intake piping shall be secured to the wall for more rigidity. All interior vent
pipe shall be supported a minimum of every 36” [915 mm].
10. Roof Exhaust: In all roof applications the discharge must point away from the pitch of the roof.
11. Roof Flashing: Install adequate flashing where the pipe enters the roof, to prevent water leakage.
12. Rain Cap: Install and seal a rain cap over existing chimney openings, in vacant chimney applications.
13. Venting Below Grade: For installations that exit the wall below grade refer to Figure 3-9.
14. Vent Screens: Install factory supplied vent screens on the outside of the last elbow for both the inlet and exhaust vent
terminal elbows. Install the screen into the female opening of the elbow. Then cut a small piece of pipe to sandwich the
screen into the elbow. NOTE be sure that the small piece of pipe cut, does not extend past the end of the elbow. Two
screens are provided in the package. See Figures 3-6 and 3-7. Vent screens are included in Optional Termination Kits.
15. Pipe Sizing: It is extremely important that the intake and exhaust vent piping be adapted to the appropriate size immediately
upon exiting the boiler cabinet. Refer to Figure 3-1 and Table 3-4.
16. Condensate Hazard: Do not locate vent over public walkways, driveways or parking lots. Condensate could drip and
freeze resulting in a slip hazard or damage to vehicles and machinery.
17. Warning Plate: Install the warning plate “Gas Vent Directly Below”, directly above (within 4 ft [1.22 m] vertically) the
location of the air inlet pipe, so it is visible from at least 8 ft [2.4 m] away. See Figures 3-5a and 3-6.
18. Wall Thickness: Direct vent terminations are designed to work with any standard wall thickness. Installation guidelines for
min/max wall thickness are as follows: Min.= 1” [25mm], Max.= 60” [1.52 m].
19. Venting Options: Due to potential moisture loading (build-up) along the exterior wall, sidewall venting may not be the
preferred venting option. Refer to Figures 3-2(b) and 3-3(b) for roof top venting options.
14
Figure 3-9
Venting Below Grade
For installations that exit the wall below grade:
1. Excavate site to a point below where the pipes are to
exit as shown.
2. Ensure that the wall is fully sealed where the pipes
penetrate the wall.
3. The Vent/Air-intake piping MUST be secured to the
side of the building above grade, as shown, to provide rigidity.
4. NTI Provides a mounting bracket PN. 82075 for
securing the exhaust pipes.
5. Ensure that the Vent/Air-Intake clearances are
maintained, see Section 4.0 for details.
Figure 3-10
Outdoor Horizontal Venting
Vent piping outside the Building is permitted under the following conditions:
1. The maximum length outside the building is 20 feet [6.1
m]. Note that outdoor length must be included in the overall vent length calculation.
2. All normal termination clearances are maintained.
3. The pipe is supported every 24” [610 mm].
4. The exhaust and inlet are sloped back to the boiler ½”
elevation for every linear foot [13 mm for every linear 305 mm].
Figure 3-11
Existing Chimney Chase Way
It is permissible to use an existing chimney as a chase way to run the Vent/Air-Intake piping as long as:
1. The chimney is not being used by any other boiler.
2. Flue gases don’t enter the vacant chimney.
3. Only Trinity certified venting materials are used, see
Section 3.0.
4. Vent lengths are within the maximums specified.
5. The top of the chimney is capped and the Vent/Air-Inlet
pipes are flashed to prevent leakage into the vacant chimney.
Air-Inlet
Existing Chimney (used as a chase way)
Chimney Cap
Exhaust Vent
Exhaust Vent Min.
18” [457 mm]
above air-inlet
Air-Inlet
Min. 12” [305 mm]
above roof and snow level
Supports every
24” [610 mm]
12” [305 mm] plus snow
allowance above grade
Air-Inlet
Maximum of 20 ft [6.1 m] is permitted for piping outside a building.
Apply Warning Plate here
Exhaust Vent
Gas Vent Directly Below
Keep Free of Obstructions
Exhaust Vent
Air-Inlet
Mounting Bracket
Trinity Installation and Operation Instructions Ti Series
Ti Series Installation and Operation Instructions Trinity
15
Clearances to Air-Inlet Termination
Canada 1
USA 2
Min. Distance
Min. Distance
A
Above grade/roofline and snow level 8
12 in.
305 mm
12 in.
305 mm
B
Above roof line - Concentric Vent
6, 11, 13
24 in.
610 mm
24 in.
610 mm
C
To exhaust vent from any other boiler
36 in.
915 mm
12 in.
305 mm
Clearances to Exhaust Vent Termination
Min. Distance
Min. Distance
D
Minimum vertical separation above air inlet 9
18 in.
457 mm
18 in.
457 mm
E
Minimum horizontal separation from air inlet 3
4 in.
102 mm
4 in.
102 mm
F
Window, door or building opening
36 in.
915 mm
12 in.
305 mm
G
To combustion air inlet from any other boiler
36 in.
915 mm
12 in.
305 mm
H
Non-mechanical air supply inlet to building
36 in.
915 mm
12 in.
305 mm
I
Mechanical air supply inlet to building 4
6 ft.
1.83 m
3 ft.
915 mm
J
Soffit, overhang, eave or parapet
24 in.
610 mm
24 in.
610 mm
K
Soffit vent or vent opening in an overhang, eave or parapet
6 ft.
1.83 m
6 ft.
1.83 m
L
Outside corner 10
- - -
-
M
Inside corner of an L-shaped structure (including walls and fences)
36 in.
915 mm
36 in.
915 mm
N
Electric meters, gas meters, regulators and relief equipment
6 ft.
1.83 m
4 ft.
1.22 m
P
Each side of center line above or below meters, regulators and relief devices 5
36 in.
915 mm
36 in.
915 mm
Q
Above a paved sidewalk, driveway, or parking lot on public property if adjacent 12
7 ft.
2.13 m
7 ft.
2.13 m
R
Above a sidewalk, driveway, or parking lot on public property
X X X
X
S
Above a sidewalk, driveway on private property between / serving both dwellings
X X X
X
T
Under a concrete veranda, porch, deck, or balcony 7
24 in.
610 mm
24 in.
610 mm
U
Above, under or near exterior stairs
X X X
X
V
Into a canopy or carport
X X X
X
Notes:
1 - Canadian installations must comply with the current CSA B149.1 Natural Gas and Propane Installation Code and local
building codes. 2 - US installations must comply with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code and local building codes. 3 - Horizontal separation center-to-center (c.c.) 4”-12” (102-305 mm). Refer to “Venting Rules and Guidelines” for
horizontal separation > 12” c.c. as it may impact vertical separation clearances. 4 - For US installations, an exhaust vent may be 3 ft above a mechanical air supply inlet if within 10 ft. [3 m] horizontally. 5 - Horizontal clearance must be observed up to a height of 15 ft. [4.6 m] above/below the meter, regulator, or relief devices. 6 - Concentric Vent must protrude from the roof precisely 24” [610 mm] measuring from the terminal end-cap vanes. 7 - Permitted if veranda, porch, deck, or balcony is made of concrete and a minimum of two sides are fully open beneath. 8 - 24” is the recommended snow level allowance above grade/roofline or any surface that will support snow, debris, or ice
(i.e. for roof venting clearances - roofline and snow level). If living in a snowfall region, consult your local weather
office for the maximum typical snowfall for your area. 9 - Note that the vent must maintain a minimum vertical distance above the air inlet. Example: Vent height = 18” (457
mm) above air inlet + 12” (305 mm) for air inlet above grade/roof line and snow level = 30” (762 mm) above grade and
snow level.
10 - Clearances to an outside corner to be in accordance with local installation codes. 11 - In Canada, concentric vent materials are subject to approval by local inspectors. See Termination Kits in Section 3.0.
12 - Above public walkways, driveways or parking lots if adjacent to it and condensate cannot drip, freeze, or create a hazard. 13 - Contact the manufacturer for special exemptions relating to multiple boiler installations using concentric vents.
4.0 VENT/AIR-INTAKE TERMINATION CLEARANCES
The quick reference table below is to be read in conjunction with the numbered notes as indicated,
Figures 4-1 through 4-6, and the Venting Rules and Guidelines in Section 3.0. The instructions detailed in this section are a combination of Trinity Ti specific and National Gas Code restrictions. Compliance alone doesn’t insure a satisfactory installation as good common sense must also be applied. Failure to follow these instructions may result in fire, property damage, serious injury or death.
Table 4-1 Termination Clearances Quick Reference Table
16
G Letter represents a specific Termination Position. Refer to Table 4-1 for corresponding termination clearances.
Concentric Vent Termination
Q
Two-Pipe Termination
F
Clearance “Q” Adjacent to Public Walkway or Driveway Minimum 7ft [2.13 m]
G
Clearances “F” and “G” Canada – Minimum 3 ft [915 mm] The US – Minimum 1 ft [305 mm]
Trinity Installation and Operation Instructions Ti Series
Figure 4-1
Termination Clearances Quick Reference Diagram
Illustrations of Termination Clearances
Side Wall Termination - Clearances Above Grade
Figure 4-2
Ti Series Installation and Operation Instructions Trinity
17
Figure 4-3 Typical
Figure 4-4
Two-Pipe Side Wall Clearances
Concentric Vent Side Wall Clearances
Figure 4-5
Figure 4-6
Two-Pipe Roof Top Clearances
Concentric Vent Roof Top Clearances
Two-pipe systems can be vented thorough the roof. Minimum heights above snow level still apply.
The same clearances apply to roof-top terminations as for two-pipe sidewall terminations.
Vertical Separation
Horizontal Separation 4-12” [102 mm – 305 mm] or greater than 36” [915 mm]
From boiler exhaust
Minimum 12” [305 mm] above grade and snow level
To boiler air-inlet connection
Minimum 18 [457 mm]
To boiler air-inlet connection
Exhaust from boiler
Wall clearance
must be 1” [25
mm] from end cap vanes to outside of wall
Minimum
12” [305 mm]
above grade and snow
Exhaust Vent Outlet (center)
Combustion Air-Inlet (perimeter)
Min. 12” [305 mm]
above grade and snow level
MIN. 18” [457 mm] above air-intake
MIN. 12” [305 mm] above
snow level
24 [610 mm] above roof from end cap vanes
Clearances from exhaust to another combustion air inlet Canada – Min. 3 ft [915 mm] The US – Min. 1 ft [305 mm]
Loading...
+ 39 hidden pages