Model Numbers: Lx150 - 800
Version Date: 2016-01-27
INSTALLATION AND OPERATION INSTRUCTIONS FOR
TRINITY Lx BOILER
TABLE OF CONTENTS
HAZARD SYMBOLS AND DEFINITIONS
Danger Sign: Indicates a hazardous situation which, if not avoided, will
result in serious injury or death.
Warning Sign: Indicates a hazardous situation which, if not avoided,
could result in serious injury or death.
Caution Sign plus Safety Alert Symbol: Indicates a hazardous situation
which, if not avoided, could result in minor or moderate injury.
Caution Sign without Safety Alert Symbol: Indicates a hazardous
situation which, if not avoided, could result in property damage.
Notice Sign: Indicates a hazardous situation which, if not avoided,
could result in property damage.
This Boiler must be installed by a licensed and trained Heating
Technician or the Warranty is Void. Failure to properly install this
unit may result in property damage, serious injury to occupants, or
possibly death.
H
NTI # 86573
Page 2
2
Trinity Lx│Installation and Operation Instructions Lx Series
Read Before Proceeding
If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING_
A) This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result
in a fire or explosion.
D) Do not use this boiler if any part has been under water. Immediately call a qualified service technician
to inspect the boiler and to replace any part of the control system and any gas control which has been
under water.
OPERATING INSTRUCTIONS_
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you don't smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the boiler.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Boiler” and call your service
technician or gas supplier.
TO TURN OFF GAS TO THE BOILER_
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the boiler
3. Turn the manual gas valve to the OFF position
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or
maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to
Section 15.0 for information on handling instructions and recommended personal protective equipment.
Installation and service must be performed by a qualified installer, service agency or the gas supplier (who must
read and follow the supplied instructions before installing, servicing, or removing this boiler. This boiler
contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans).
Void Warranty - This Boiler must have water flowing through it whenever the burner is
on or it will damage the unit and void the warranty. Failure to follow these instructions
may result in serious injury or death.
Page 3
Lx Series Installation and Operation Instructions│Trinity Lx
3
Energy Saving Feature - This boiler is equipped with a feature that saves energy by
reducing the boiler water temperature as the heating load decreases. This feature is
equipped with an override which is provided primarily to permit the use of an external energy management
system that serves the same function. THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE
OF THE FOLLOWING CONDITIONS IS TRUE:
An external energy management system is installed that reduces the boiler water temperature as the heating
load decreases.
This boiler is not used for any space heating.
This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater.
This boiler is equipped with a tankless coil.
1.0 INTRODUCTION
General Installation Requirements
The installation of your NTI Trinity Lx boiler must conform to the requirements of this manual, your local
authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where
required by the Authority, the installation must conform to the standard for “Controls and Safety Devices for
Automatically Fired Boilers ANSI/ASME CSD-1.
This document pertains to the correct installation and operation of NTI Trinity boiler models Lx150, Lx150E,
Lx200, Lx300, Lx400, Lx500, Lx600, Lx700 and Lx800. The instructions detailed in this document supersede
any and all previous instructions provided by NTI, written or otherwise. Each unit is provided with the
following:
1. Installation and Operating Instructions,
2. Appendix A – Controller and Touchscreen Display Instructions,
3. Trinity User’s Manual, and
4. Natural Gas to LP Conversion Kit*
* The conversion kit is required to convert the boiler so it will safely operate with Propane Gas.
Models Lx600-800 are not approved for operation with Propane (LP Gas). Operating
these models with Propane will result in property damage, serious injury or death.
Read and understand this entire document prior to proceeding with the installation of the
Trinity Lx. Failure to follow the instructions outlined in this document will result in
property damage, serious injury or death.
User Responsibilities
This boiler must be installed and serviced by a qualified installer or service technician. This boiler must be
serviced and inspected annually when operating in normal residential applications. Demanding applications or
extreme conditions (i.e. commercial) may require more frequent service and inspection. As the User/Owner of
this equipment, you are responsible for ensuring the maintenance is performed at the required intervals (see
Section 15 – Annual Maintenance and Inspection).
Failure to have the boiler properly serviced and inspected on a regular basis by a qualified
service technician may result in property damage, serious injury or death.
Failure to keep the Vent and Combustion Air-inlet clear of ice, snow, and other
debris may result in property damage, serious injury, or death.
Installer Responsibilities
A qualified installer is a licensed person who has appropriate training and a working knowledge of the applicable
codes, regulations, tools, equipment and methods necessary to install a boiler. The Installer assumes all
responsibility for a safe installation and that it meets the requirements of the boiler instruction manuals, as well
as National and local installation codes. It is also the installer’s responsibility to inform the User/Owner of their
obligation with respect to the description under “User Responsibilities”. Failure to follow this warning could
result in fire, serious injury, or death.
Page 4
4
Trinity Lx│Installation and Operation Instructions Lx Series
Failure to use the appropriate Natural to LP Conversion Kit and Orifice when operating
the Trinity Lx with Propane will result in extremely dangerous burner operation leading
to property damage, serious injury or death. Refer to section titled ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE for applicable conversion kit and LP
orifice numbers.
ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE
The Trinity Lx is factory set to operate with Natural Gas. BEFORE OPERATING WITH PROPANE, the
specified LP Conversion Kit and Orifice must be installed to convert the boiler so it will operate safely with
LP Propane. The correct kit and LP orifice is listed below (Each kit comes with conversion instructions).
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your Trinity Lx boiler
is not installed in a pit or similar location that will permit heavier than air gas to collect. Local Codes may
require boilers fueled with LP gas be provided with an approved means of removing unburned gases from the
room. Check your local codes for this requirement.
Natural to LP Propane Conversion Kit_Model Number Kit Number LP Orifice Lx150-200 82650-1 52 (5.2mm)
Lx300 82650-1 62 (6.2mm)
Lx400 83017-1 62 (6.2mm)
Lx500 84386-1 No Orifice
Boiler Vent / Air-Inlet Piping
The Trinity Lx is certified as a “Category IV” boiler, and requires a “Special Venting
System” designed for pressurized venting. The exhaust gases must be piped directly to
the outdoors using the vent materials and rules outlined in these instructions. Failure to
follow these instructions will result in serious injury or death.
Page 5
5
IN THE STATE OF MASSACHUSETTS ONLY
(a) For all horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or
in part for residential purposes, including those owned and operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not
limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired
carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas
equipment is to be installed and on each additional level of the dwelling, building or structure served by the
equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next
adjacent floor level.
b. In the event that the requirements of this subdivision cannot be met at the time of completion of
installation, the owner shall have a period of 30 days to comply with the above requirements; provided,
however, that during said 30 day period a battery operated carbon monoxide detector with an alarm shall
be installed.
2. APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating boiler or equipment. The sign shall read, in print size no less than onehalf (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS” (plate included with boiler).
4. INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall
not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b)EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or in part for residential purposes.
(c)MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED: When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or
venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:
1. Detailed instructions for installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d)MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED:
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide
the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be
satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the boiler or equipment installation
instructions; and
2. The “special venting system” shall be Product Approved by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts list for venting instructions, and/or all venting design instructions shall remain with
the boiler or equipment at the completion of the installation.
Lx Series Installation and Operation Instructions│Trinity Lx
Page 6
6
DESCRIPTION
Lx150
Lx150E
Lx200
Lx300
Lx400
Lx500
Lx600
Lx700
Lx800
Gas Connection
(inches, NPT)
½” (Female)
¾” (Female)
1” (Male)
Water Connections
(inches, NPT)
1” (Female)
1-1/4” (Female)
2” (Female)
Exhaust Vent
Connection (inches)
3
4
6
Air-inlet Connection
(inches)
3
4
Cabinet Height
(inches)
29.5
36
43
37
Cabinet Width
(inches)
17
Cabinet Depth
(inches)
18.5
21.5
24
32.5
47.5
63.5
Approximate Weight
with water (lbs)
100
125
180
225
320
380
475
Water Content
(gallons)
1
1.2
2.1
2.4
3.3 4 5.2
Electrical Rating
120V / 1 Phase / 60 Hz / 12A
Notes:
1
Water connections for Lx150 units sold in Canada are 3/4” NPT and Copper union.
DESCRIPTION
Lx150(E)
Lx200
Lx300
Lx400
Lx500
Lx600
Lx700
Lx800
CSA Input
Modulation (MBH)
1
25 – 150
2
25 - 199
55 - 275
75 - 399
100 - 500
120 - 600
160 - 700
160 - 800
DOE Heating
Capacity (MBH)
1,3
136
181
251
375
470
564
658
752
Net I=B=R Rating
(MBH)
1,3
118
157
218
326
409
490
572
654
DOE AFUE (%)
3
93.5
93.7 - - - -
-
Combustion
Efficiency (%)
3
- - -
95
Thermal Efficiency
(%)
3
- - -
94
Notes:
1
Listed Input and Output ratings are at minimum vent lengths at Sea Level. Numbers will be lower with longer venting
and/or altitudes greater than 2000 feet [610 m].
2
The maximum input when operating on LP-Gas is limited to 145 MBH for model Lx150.
3
Based on standard test procedures prescribed by the U.S. Department of Energy. Ratings have been confirmed by AHRI.
Trinity Lx│Installation and Operation Instructions Lx Series
2.0 INTRODUCTION
Table 2-1 General Specifications
Table 2-2 Boiler Performance Specifications
Page 7
7
Elevations
2000 ft [610 m]
3000 ft [914 m]
4000 ft [1219 m]
4500 ft [1372 m]
5000 ft [1524 m]
In Canada1
de-rate by 10%
de-rate by 10%
de-rate by 10%
de-rate by 10%
de-rate % may vary
In USA2
-
de-rate by 12%
de-rate by 16%
de-rate by 18%
de-rate by 20%
Notes:
1
Canada: Altitudes between 2000-4500 ft [610-1372 m], de-rate by 10%. Consult local authorities for de-rating
capacities for altitudes above 4500 ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m], if altitude is over 2000 ft [610 m].
Lx Series Installation and Operation Instructions│Trinity Lx
High Altitude Operation
The Trinity Lx is designed to operate at its maximum listed capacity in installations less than or equal to 2000 ft
[610 m] above Sea Level. Since the density of air decreases as elevation increases, maximum specified capacity
should be de-rated for elevations above 2000 ft [610 m] in accordance with Table 2-3.
Table 2-3 De-rate % for High Altitudes
Combustion – At elevations above 2000 feet, the combustion of the boiler must be
checked with a calibrated combustion analyzer to ensure safe and reliable operation. It is
the Installers responsibility to check the combustion and to adjust the combustion
in accordance to Section 9.0. Failure to follow these instructions may result in property
damage, serious injury, or death.
Page 8
8
Trinity Lx│Installation and Operation Instructions Lx Series
3.0 BOILER LOCATION
In all cases, the Trinity Lx must be installed indoors in a dry location where the ambient temperature must be
maintained above freezing and below 100F [38C]. Gas components must be protected from dripping, spraying
water, or rain during operation and servicing. Consider the proximity of system piping, gas and electrical supply,
condensate disposal drain, and proximity to vent termination when determining the best boiler location.
Floor Mounting
The Trinity Lx can be mounted directly on combustible flooring, with the exception of carpeting. Installing the
boiler on carpeting is not permissible. Ensure the boiler is mounted above any anticipated flood level. Models
Lx150-Lx400 come equipped with stationary, low profile legs. Models Lx500-Lx800 include factory
supplied/field installed leveling legs. Once the unit is removed from the pallet, thread the leveling legs into the
allocated threaded inserts in the bottom of the unit.
Boiler Area Ventilation Air Openings
Direct Vent – If boiler area clearances are less than the recommended clearances specified in Table 3-1, the
boiler area must be ventilated. (Exception: if the boiler area/room has a volume of 150 ft3 or greater,
ventilation of the boiler room is not required). Each ventilation air opening must meet the minimum
requirements of 1 in2 per 1000 Btu/hr, but not less than 100 in2. The lower ventilation opening must be
located within 6” of the floor while the upper opening must be located 6” from the top of the space.
Indoor Combustion Air – When using Indoor Combustion Air in lieu of Direct Vent air-inlet piping (an option
for models Lx500-800), provisions for combustion and ventilation air, in accordance with section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (U.S.), or Clause 8.2,
8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1 (Canada), or applicable
provisions of the local building codes, must be adhered to.
Closet Installations
For closet installations, it is necessary to provide two ventilation air openings as shown in Figure 3-1(a), (b) and
(c), each providing a minimum area equal to 1 in2 per 1000 Btu/hr, but not less than 100 in2 and within 6” of the
top and bottom of the closet door. See Table 3-1for minimum recommended clearances.
Alcove Installations
Alcove installations have the same minimum clearances as closet installations, except the front must be
completely open to the room at a distance no greater than 18” [457 mm] from the front of the boiler and the
room is at least three (3) times the size of the alcove. Provided these conditions are met, the boiler requires no
extra ventilation air openings to the space. See Table 3-1for minimum recommended clearances.
Residential Garage Installations
When installed in a residential garage, mount the boiler a minimum of 18” [457 mm] above the floor. Locate or
protect the boiler so it cannot be damaged by a moving vehicle. Check with your local authorities for other
possible regulations pertaining to the installation of a boiler in a garage.
Wall Mounting Installations (Optional)
Lx150-400 models are shipped with wall mounting brackets to provide installers with the option of wall
mounting the boiler. Lx500-800 models are not available as a wall mountable unit. Refer to Figures 3-3(a) and
3-3(b) for instructions and illustrations on wall mounting applicable models.
Water or flood damaged components must be replaced immediately with new factoryapproved components as failure to do so may result in fire, serious injury, or death.
If the "Boiler Area" does not meet the recommended clearances listed in Table 3-1, and
if the boiler area has a volume less than 150 ft3, it is considered a Closet or Alcove. PVC
vent pipe and fittings shall not be used within the closet or alcove; only approved CPVC,
Polypropylene or Stainless Steel vent pipe and fittings can be used. See Table 4-3 for a
list of approved materials.
Failure to follow instructions may
result in fire, serious injury, or death.
Secure the upper wall mount bracket to a solid
wall using field supplied lag screws (anchors
when mounting on a concrete wall) that are
adequate to support the weight of the boiler.
Ensure the bracket is mounted in the level
position. Refer to Table 2-1 Specifications for
boiler weight.
This unit requires two people to lift it
or damage and injury may result.
Mount the boiler to the bracket by aligning the
slots in the back of the boiler with the hooks
protruding from the wall bracket. The top of
the slots must rest at the bottom of the groove
in the hooks of the wall mount bracket.
Pull the bottom of the unit away from the wall
to allow the installation of the lower wall
mount bracket (included with boiler). The
bracket will snap into place using the slots
provided in the bottom of the unit (ensure the
snaps lock into place, once installed the bracket
should not be easily removed).
Ensure that the top of each
slot rests on the bottom of the
grooves in the wall bracket.
Bottom Bracket is in
Lx Installation Kit Box
Lx Series Installation and Operation Instructions│Trinity Lx
Failure to follow instructions may
result in fire, serious injury, or death.
bottom-back of the boiler (B). Save the
mounting hardware for Step 4.
Secure the wall mount bracket, removed from
the bottom of the boiler in Step 1, to a solid
wall using field supplied lag screws (anchors
when mounting to a concrete wall) that are
adequate to support the weight of the boiler
(refer to Table 2-1 Specifications). Ensure the
wall mount bracket is mounted level and flush
to the wall with mounting holes on the bottom,
flange pointed upward and angled away from
the wall.
This unit requires two people to lift it
or damage and injury may result.
Mount the boiler to the wall by aligning the
upper bracket (A) with the wall mount bracket
(B). Slide the upper bracket down over the
wall mount bracket until it hooks.
Once the boiler is resting securely on the upper
bracket, secure the bottom bracket to the
underside of the boiler using the mounting
hardware removed in Step 1; then, anchor the
bottom bracket to the wall as shown.
B
A
Ensure that the
upper bracket
on the back of
the appliance
(A) slides down
over the wall
mount bracket
(B) and rests
securely on it.
A
B
Bottom Bracket is in
Lx Installation Kit Box
B
Trinity Lx│Installation and Operation Instructions Lx Series
Page 13
13
Lx Series Installation and Operation Instructions│Trinity Lx
4.0 GENERAL VENTING
The Trinity Lx is certified as a “Category IV” boiler requiring a “Special Venting System” designed for
pressurized venting. The Exhaust Vent must be piped to the outdoors, using the vent materials and rules outlined
in this section. Under no conditions may this unit vent gases into a masonry chimney, unless it is vacant, and
utilizes the approved venting material and rules described in this section.
Removing an Existing Boiler from Common Venting System
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining
connected to the common venting system placed in operation, while the other appliances remaining connected to
the common venting system are not in operation.
Steps to Removing an Existing Boiler
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch. Verify that there is no blockage,
restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close fireplace dampers, all building doors and windows and all doors between the
space in which the appliances remaining connected to the common venting system are located and other
spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting
system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at
maximum speed. Do not operate a summer exhaust fan.
4. Place in operation the boiler being inspected. Follow the lighting instructions. Adjust thermostat so boiler
will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system
properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and
any other gas burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code. When resizing any portion of the common venting system, the common venting system
should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code.
Vent and Air-inlet are to be piped separately. The Trinity Lx cannot share a common vent
or air-inlet with multiple appliances.Failure to comply will result in serious injury or
death.
Do not install the Trinity Lx into a common venting system with any other appliances.
Failure to comply with this warning will cause flue gas spillage and leech carbon
monoxide emissions into the surrounding air resulting in serious injury or death.
When an existing boiler is removed from a common venting system, the common
venting system is likely to be too large for proper venting of the remaining appliances
connected to it. Instructions have been provided on how to remove the existing boiler
and how to resize the remaining venting system. Failure to follow these instructions may
result in property damage, serious injury or death.
Page 14
14
Figure 4-1 Installation of Optional Air Filter Kit (P/N 84093)
Remove factory appliance
air-inlet adapter; keep screws
from installation of filter kit
Secure filter kit using factory
screws removed in step 1.
Reuse the factory gasket.
Secure the filter in place
with the brackets and knurled
screws provided in the filter kit.
Trinity Lx│Installation and Operation Instructions Lx Series
Direct Vent Installation (Mandatory for models Lx150-400)
When installed as a Direct Vent boiler the combustion air-inlet must also be piped directly to the outdoors using
the methods described in this section and in accordance with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or
CSA B149.1 (Canada) and local requirements.
Indoor Combustion Air (Optional for models Lx500-800)
When the installation uses Indoor Combustion Air (i.e. piping is not directly connecting the boiler air-inlet fitting
to the outdoors), provisions for combustion and ventilation air, in accordance with section “Air for Combustion
and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (U.S.), or Clause 8.2, 8.3 or 8.4 of
Natural Gas and Propane Installation Code, CAN/CSA B149.1 (Canada), or applicable provisions of the local
building codes, must be adhered to.
Air Filter Kit (P/N 84093) – When using indoor combustion air (non-Direct Vent), it is highly recommended to
use the optional Air Filter Kit (P/N 84093) to limit the amount of dust that enters the combustion system. The
Filter Kit can be installed on boiler models Lx500-800, as illustrated in Figure 4-1 (comprehensive
installation instructions are provided with the Filter Kit).
The boiler shall be located so as not to interfere with proper circulation of combustion,
ventilation, and dilution air.
Make up air requirements for the operation of exhaust fans, kitchen ventilation systems,
clothes dryers, and fireplaces shall be considered in determining the adequacy of a space
to provide combustion air requirements. Failure to ensure adequate make up air to all
appliances may result in personal injury or death.
Controller RPM Adjustments – To avoid the potential boiler lockouts due to wind and
static pressure differences, the Lightoff and Minimum Modulation RPM Rates must be
adjusted as per Figures 4-11 and 4-21 in Appendix A when using indoor combustion air.
Venting Limitation – When using the Air Filter Kit on models Lx500-600, the maximum
equivalent exhaust vent length is limited to 30 ft. with 4” piping, or 90 ft. with 6” piping;
see warning below Table 4-5.
Page 15
Lx Series Installation and Operation Instructions│Trinity Lx
Cement powder, crack fill dust, cellulose, fiber based insulation
Concrete plant or construction site
Combustion Air-inlet Contamination
Be careful not to locate the Air-inlet termination in an area where contaminants can be drawn in and used for
combustion. Combustion air containing dust, debris or air-borne contaminants will drastically increase the
required maintenance and may cause a corrosive reaction in the Heat Exchanger which could result in premature
failure, fire, serious injury, or death. See Table 4-1 for a list of areas to avoid when terminating air-intake piping:
Table 4-1 Corrosive Products and Contaminant Sources
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance. Failure to follow instructions may result in serious injury or death.
It is BEST PRACTICE to pipe the combustion air-inlet directly to the outdoors (Direct
Vent installation) to avoid contamination often contained in indoor air.
Flammable Solvents and Plastic Piping
Due to the extremely flammable characteristics of most glues, cements, solvents and primers used in the process
of joining plastic vent and air-inlet pipe, explosive solvent vapors must be evacuated from the vent and air-intake
prior to start-up. Avoid using excess cement or primer that may lead to pooling inside the pipe assembly. Freshly
assembled piping assembly should be allowed to cure for a minimum of 8 hours before applying power to the gas
fired appliance. Refer to Mandatory Pre-commissioning Procedure for Plastic Ventingin this section.
Flammable Cements and Primers – It is the installers’ responsibility to familiarize
themselves with the hazards associated with explosive solvents and to take all precautions
to reduce these risks. Failure to follow these instructions can cause explosions, property
damage, injury or death.
Mandatory Pre-commissioning Procedure for Plastic Venting (PVC or CPVC)
Do not apply power to the boiler prior to Step 4 in the Mandatory Pre-commissioning
Procedure for Plastic Venting.
Spark Igniter Cable -Maintain a minimum 2” separation between spark igniter circuit
and conductors. Failure to follow instructions may result in component failure, injury or
death.
1) Working with the power turned off to the boiler, completely install the vent and air-inlet system, securely
cementing joints together. If possible, allow primers/cements to cure for 8 hours before firing the burner. If
curing time is less than 8 hours, proceed with Steps 2 through 6.
2) Maintain the boiler gas supply shut-off valve in the off position.
3) Disconnect electrical leads to the Hot Surface or Spark Igniter. Ensure the cables are placed in a fashion
where they will not arc to ground or other conductor. Refer to warning regarding Spark Igniter Cable.
4) Turn power on to the boiler and apply a heat demand.
5) Allow for 3 complete trials for ignition, consisting of pre and post purge of the combustion blower, until an
ignition lockout occurs. Repeat the process two more times (i.e. 9 complete ignition sequences in total).
6) Turn power off and reconnect the electrical leads to the Igniter.
Page 16
16
Model No.
CPVC Vent Pipe Size
CPVC Transition Vent Pipe Length
Full Insertion Depth
Lx150-200
3”
Minimum 5” [127 mm]
2-7/8” [73 mm]
Lx300-600
4”
Minimum 4” [100 mm]
1-7/8” [48 mm]
Lx700-800
6”
Minimum 6” [152 mm]
2-1/2” [63 mm]
Model No.
Vent Material
Venting Brand
Adapter Part No.
1,2
Lx150-200
Polypropylene
DuraVent – PolyPro
300150
Centrotherm - InnoFlue
ISANY0303
Stainless Steel
DuraVent – FasNSeal
300715
Lx300-600
Polypropylene
DuraVent – PolyPro
300151
Centrotherm - InnoFlue
ISAA0404
Stainless Steel
DuraVent – FasNSeal
303631
Lx700-800
Polypropylene
DuraVent – PolyPro
810004281
Centrotherm - InnoFlue
ISAA0606
Stainless Steel
DuraVent – FasNSeal
810005231
Notes:
1
Listed boiler adapters are only approved for use with the respective venting brand; i.e. a PolyPro boiler adapter shall not
be used with InnoFlue venting.
2
PolyPro and FasNSeal boiler adapters are available from DuraVent (1-800-835-4429 or www.duravent.com); InnoFlue
boiler adapters are available from Centrotherm Eco Systems (1-877-434-3432 or www.centrotherm.us.com).
Trinity Lx│Installation and Operation Instructions Lx Series
Near Boiler Vent/Air-inlet Piping
Each Trinity Lx is equipped with a short piece of approved CPVC vent pipe (see Table 4-2 CPVC Vent Pipe
Transition Piece). Insert one end into the boiler flue outlet adapter and cement the other to field venting (see
Table 4-4 for approved venting material). The CPVC vent pipe should extend fully into the boiler flue outlet
adapter (see Table 4-2). Ensure that the venting system does not apply a load or strain on the boiler flue outlet
adapter. The manufacturer recommends using two elbows to create a “swing joint” to reduce potential strain on
vent piping and cemented joints; see Figures 4-2 through 4-5.
Table 4-2 CPVC Vent Pipe Transition Piece (used when venting with PVC)
Gasket Seating - Improper seating can cause leakage and eventual failure of the sealing
gasket. Failure to follow these instructions may result in serious injury or death.
PVC Exhaust Venting – DO NOT insert PVC pipe directly into the boiler exhaust
adapter, as it can deform from the clamping force of the gear clamp. Failure to follow
these instructions may result in gasket failure and/or the dislodging of the exhaust pipe
from the boiler adapter, resulting in property damage, serious injury or death.
Polypropylene or Stainless Steel Venting – When using Polypropylene or Stainless Steel
piping, the appropriate boiler adapters must be used to transition the boiler vent
connections to accept the respective Polypropylene or Stainless Steel venting. See Table
4-3 for a list of approved adapters. Failure to use the correct adapter will result in flue gas
leakage resulting in property damage, serious injury or death.
Table 4-3 Boiler Adapters for Polypropylene and Stainless Steel Venting
Exhaust venting must be supported to reduce strain on piping joints. Failure to
follow these instructions may result in result in damage, serious injury or death.
In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection.
Page 17
17
Figure 4-2(a) Near Boiler Venting (CPVC)
Figure 4-2(b) Near Boiler Venting (PVC)
Models Lx150-200
Models Lx150-200
Figure 4-3(a) Near Boiler Venting (CPVC)
Figure 4-3(b) Near Boiler Venting (PVC)
Models Lx300-400
Models Lx300-400
Flue Outlet
Stainless Steel Adapter
(factory supplied)
Exhaust Vent3” CPVC
Swing Joint
to attain slope in
horizontal runs
Air Inlet3” Pipe *
Coupling
3” Removable
(field supplied)
Air Inlet3” Pipe *
Coupling
3” Removable
(field supplied)
Swing Joint
to attain slope in
horizontal runs
Exhaust Vent - 3” PVC,
(check local codes and
Table 4-3)
Coupling 3” PVC
Flue Outlet
Stainless Steel
Adapter (factory
supplied)
Transition Piece
3” CPVC, minimum 5”
long (factory supplied)
Mandatory Vent Pipe
Transition Piece
See Table 4-2.
Air-Inlet
4” Pipe *
Swing Joint
to attain slope in
horizontal runs
Exhaust Vent
4”/6” CPVC
Flue Outlet
Stainless Steel Adapter
(factory supplied)
Coupling4” Removable
(factory supplied)
90o elbow typical, or tee and
drain cap option for easy cleanouts
Air-Inlet
4” Pipe *
Swing Joint
to attain slope in
horizontal runs
Coupling4”/6”x4” PVC
Flue Outlet
Stainless Steel Adapter
(factory supplied)
Coupling
4” Removable
(factory supplied)
Exhaust Vent
4”/6” PVC (check local
codes and Table 4-3)
Transition Piece
4” CPVC, minimum 4”
long (factory supplied)
90o elbow typical, or tee and
drain cap option for easy cleanouts
Mandatory Vent Pipe
Transition Piece
See Table 4-2.
Lx Series Installation and Operation Instructions│Trinity Lx
Air-Inlet - check with applicable local codes for acceptable pipe material.
Page 18
18
Figure 4-4(a) Near Boiler Venting (CPVC/PVC)
Models Lx500-600
Figure 4-5(a) Near Boiler Venting (CPVC)
Figure 4-5(b) Near Boiler Venting (PVC)
Models Lx700-800
Models Lx700-800
Air-Inlet 4” Pipe *
Exhaust Vent
6” CPVC
Swing Joint
to attain slope in
horizontal runs
Flue Outlet 6”
stainless steel
elbow (factory
supplied)
Air-Inlet Adapter
4” stainless steel
(factory supplied)
90o elbow typical, or tee
and drain cap option for
easy cleanouts
Air-Inlet Adapter
4” stainless steel
(factory supplied)
90o elbow typical, or tee
and drain cap option for
easy cleanouts
Flue Outlet 6”
stainless steel
elbow (factory
supplied)
Exhaust Vent
6” PVC (check
local codes
and Table 4-3)
Coupling 6”
PVC, length 4”
Air-Inlet 4/6” Pipe *
Transition
6” CPVC
Swing Joint
to attain slope in
horizontal runs
Mandatory Vent Pipe Transition Piece
6” CPVC (factory supplied). See Table 4-2.
Air-Inlet
4” Pipe *
Exhaust Vent
4” CPVC
Swing Joint
to attain slope in
horizontal runs
Flue Outlet 4”
stainless steel
(factory supplied)
Air-Inlet Adapter
4” stainless steel
(factory supplied)
90o elbow typical, or tee
and drain cap option for
easy cleanouts
Exhaust Vent
4” PVC (check
local codes
and Table 4-3)
Mandatory Vent Pipe
Transition Piece
4” CPVC (factory supplied).
See Table 4-2.
Transition
4” CPVC
OR
Trinity Lx│Installation and Operation Instructions Lx Series
Air-Inlet - check with applicable local codes for acceptable pipe material.
Page 19
19
Items 1
Materials
2, 3
Installation Standards
All Vent and Air-inlet
materials installed on gas
fired appliances in CAN/US
must meet the Standards
listed in Table 4-4. Failure
to comply could result in
fire, serious injury or death.
United States
Canada 4
Vent Piping
and Fittings
PVC - DWV
ANSI/ASTM D2265
All venting material in
Canada must be
ULC S636 approved.
See Note 4 below for
appropriate temperature
applications.
PVC Schedule 40
ANSI/ASTM D1785
CPVC Schedule 40
ANSI/ASTM F441
AL29-4C
UL-1738
Polypropylene (PP)
-
Pipe Cement
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
Primers
PVC / CPVC
ANSI/ASTM F656
Notes:
1
Refer to Table 4-5 for Allowable Vent and Air-inlet Pipe Sizes and Lengths.
2
PVC venting (exhaust and air-intake) is not permitted within the Closet/alcove of a Closet/alcove installation.
3
The Air-Intake does not require high temperature pipe material. Check applicable local codes for acceptable materials.
4
ULC S636 PVC is approved for flue gas temperatures up to 149oF (65oC) and must only be used for low temperature
applications. High temperature applications requiring boiler supply water temperatures greater than 140oF (60oC) must
use ULC S636 CPVC, PP or AL29-4C.
Lx Series Installation and Operation Instructions│Trinity Lx
Vent/Air-inlet Pipe Material
Table 4-4 Acceptable Vent and Air-inlet Pipe Material
The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel®
(polyphenolsulfone) in the exhaust venting system is prohibited. Failure to follow these
instructions may result in property damage, personal injury or death.
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. Failure
to follow these instructions may result in property damage, personal injury or death.
Page 20
20
Model
Pipe Size
Gas
Length
ft.
Number of Elbows (90’s or 45’s) and Equivalent Feet
1 2 3 4 5 6 7 8 9
Lx150-200
3”
LP
50
45
40
35
30
25
20
15
10
5
3”
NG
105
100
95
90
85
80
75
70
65
60
4”
NG
& LP
105
100
95
90
85
80
75
70
65
60
Lx300-400
4” or 6”
NG
& LP
100
95
90
85
80
75
70
65
60
55
Lx500
4” or 6” 3
NG & LP
100
95
90
85
80
75
70
65
60
55
Lx600
4”or 6” 3
NG 2
100
95
90
85
80
75
70
65
60
55
Lx700-800
6” 1
NG 2
100
95
90
85
80
75
70
65
60
55
Notes:
1
Only 6” exhaust vent is permissible for models Lx700-800. Air-inlet pipe can be 4” or 6” (6” is highly recommended).
2
Models Lx600-800 operate with Natural Gas only.
3
Models Lx500-600 are limited to 30 ft. of 4” or 90 ft. of 6” exhaust venting when using the Air Filter Kit (P/N 84093).
Trinity Lx│Installation and Operation Instructions Lx Series
Vent and Air-inlet Pipe Length Determination
Use Table 4-5 to determine the maximum pipe length that can be used. The table calculates sweep, 90º elbows,
and 45º elbows at 5 equivalent feet each. Note: models Lx150-200 have limitations when operating with
Propane Gas (LP).
Example: An Lx200 can be installed with 105 equivalent feet of air-inlet piping and 105 equivalent feet of
exhaust vent piping when operating with Natural Gas. When operating with Propane Gas (LP), the maximum
length of each the exhaust vent and air-inlet pipe is limited to 50 equivalent feet (3” diameter pipe).
Table 4-5 Allowable Vent and Air-Intake Pipe Size and Lengths
The length of one vent pipe (air-inlet or exhaust) may not exceed the length of the other
vent pipe by more than 20 equivalent feet.
Air Filter Kit venting restrictions - Models Lx500-600 are limited to 30 equivalent feet
of 4” (or 90 equivalent feet of 6”) exhaust vent when using the optional Air Filter Kit.
When transitioning from 4” to 6”, the 4” venting used must be counted 3 times to convert to an equivalent length in 6”.
Example: An application uses one 90º elbow and 5 feet of 4” venting before converting to 6”; therefore, the 4”
venting has an equivalent length of 30’ [(5’+5’) x 3] of 6” venting; thus allowing an additional 60’ equivalent
of 6” venting (Note: Example is only true with Lx500-600 models using the optional Indoor Combustion Air
Kit).
Page 21
21
Description
Vent
Size
Supplier P/N
Figure
Vent Material
Compatibility
Vent Option
Roof
Wall
IPEX Low Profile
(Flush Mount)
7
3”
196985 (NTI P/N 84357)
4-9
PVC/CPVC
7
4”
196986 (NTI P/N 84358)
IPEX Concentric
(Wall/Roof)
5,6,7,8
3”
196116 (NTI P/N 82666)
4-9(b), 4-10(b)
PVC/CPVC7
197117
4”
196021 (NTI P/N 84355)
197021
DuraVent - PolyPro
Concentric (Wall)
3”
3PPS-HK
4-9(d)
PVC/CPVC/PP
4”
4PPS-HK
DuraVent - PolyPro
Concentric (Roof)
3”
3PPS-VK
4-10(c)
PVC/CPVC/PP
4”
4PPS-VK
Centrotherm – InnoFlue
(Flush Mount)
3”
ISLPT0303
4-9
PVC/CPVC/PP
Centrotherm – InnoFlue
Concentric (Wall)
9
3”
ICWS3513 & ICTC0335
4-9(d)
PVC/CPVC/PP
ICWT352 & ICTC0335
4”
ICWS4639 & ICTC0446
Centrotherm – InnoFlue
Concentric (Roof)
9
3”
ICRT3539 & ICTC0335
4-10(c)
PVC/CPVC/PP
4”
ICRT4679 & ICTC0446
Notes:
1
Instructions included with termination kits contain detailed assembly and installation instructions.
2
All factory termination kits are ULC S636 approved.
3
Clearance requirements in this manual supersede those of the instructions included with the vent terminal.
4
Piping MUST be secured to the vent terminal during installation.
5
IPEX Concentric Terminal MUST be cemented together and to the vent pipes during installation.
6
Vent Screens provided with boiler may be used with the IPEX Concentric Vent Kits; otherwise use IPEX vent screens
(3 in. vent screen P/N 196051 – each sold separately).
7
IPEX Low Profile and Concentric kits (excluding P/N 197009) are constructed out of ULC S636 approved PVC; check
with your local authority for the acceptance of PVC as a venting material prior to use.
8
IPEX Concentric kits can be shortened to fit the requirements of the installation; see instructions included with the kit
for more details.
9
Centrotherm Concentric termination kits must use the applicable “Twin pipe to concentric adapter,” part number
ICTC0335 or ICTC0446.
10
3” Vent Termination Kits may only be used with models Lx150-200.
Lx Series Installation and Operation Instructions│Trinity Lx
Termination Options – Direct Vent Installation
The venting system of the Trinity Lx may be terminated using field supplied piping to construct a “Two-Pipe”
termination, see Figures 4-6(b), 4-7(a), 4-7(b) and 4-8(a); alternatively the venting may be terminated using a
factory kit selected from Table 4-6.
Kits certified with the Trinity Lx are listed in Table 4-6 and available from IPEX, DuraVent, Centrotherm and/or
NTI. For more information on System 636 Vent Kits or wholesaler locations contact IPEX directly USA: 1-800463-9572 or www.IPEXamerica.com │CAN: 1-866-473-9462 or www.ipexinc.com. For more information on
PolyPro Vent Kits or wholesaler locations contact DuraVent directly 1-800-835-4429 or www.duravent.com. For
more information on InnoFlue Vent Kits or wholesaler locations contact Centrotherm directly at 1-877-434-3432
or www.centrotherm.us.com.
Table 4-6 Optional Vent Termination Kits
Models Lx300-800 are not approved for use with any of the 3” vent termination kits; only
4” vent termination kits, listed in Table 4-6, are acceptable.
PVC In Canada - Authorities in some jurisdictions may not allow the use of any PVC
venting materials with condensing boilers; check with the local safety inspector to verify
compliance prior to installing a PVC Concentric Vent Kit with a Trinity Lx.
Page 22
22
Figure 4-6(a) Concentric Sidewall Termination
Figure 4-6(b) Two-Pipe Sidewall Termination
(Lx200 Illustrated)
(Lx200 Illustrated)
Figure 4-7(a) Two-Pipe Sidewall Termination
Figure 4-7(b) Two-Pipe Sidewall Termination
(Lx800 Illustrated)
(Lx400 Illustrated)
Trinity Lx│Installation and Operation Instructions Lx Series
Sidewall Termination - Due to potential moisture loading (build-up) along the exterior
wall, sidewall venting may not be the preferred venting option. Refer to Figures 4-8 and
4-10 for roof top venting options.
Sidewall Termination Examples – Direct Vent Installation
Page 23
23
Figure 4-8(a) Two-Pipe Roof Termination
Figure 4-8(b) Concentric Roof Termination
(Lx200 Illustrated)
(Lx200 Illustrated)
Lx Series Installation and Operation Instructions│Trinity Lx
Extra precaution must be taken to adequately support the weight of the Vent/Air-inlet
piping in applications using roof-top terminations. Failure to follow these instructions
may result in venting or boiler component failure resulting in flue gas spillage leading to
property damage, serious injury or death.
Roof Termination Examples – Direct Vent Installation
Page 24
24
Figure 4-9(a)
Figure 4-9(b)
Two-Pipe Termination (Sidewall)
IPEX Concentric Termination (Sidewall)
Refer to documentation included with termination kit for
complete installation instructions.
Figure 4-9(c)
Figure 4-9(d)
Low Profile Termination (Sidewall)
PolyPro / InnoFlue Termination (Sidewall)
Refer to documentation included with termination kit for
complete installation instructions.
Min. 12”
above grade
or snow level
Exhaust
Air-inlet
Exhaust
Air-inlet around
perimeter
Min. 12”
above grade
or snow level
Exhaust center
Air-inlet bottom
Exhaust
Air-inlet
Gas Vent Directly Below
Keep Free of Obstructions
Refer to documentation included with termination kit for
complete installation instructions.
Exhaust
Air-inlet
Min. 12”
above grade
or snow level
Vertical
Min. 18”
Horizontal
4-12” or greater than 36”
Exhaust
Air-inlet
Vent Screen
Vent pipe piece to
retain vent screen
Gas Vent Directly Below
Keep Free of Obstructions
Exhaust
Air-inlet
Min. 12”
above grade
or snow level
Air-inlet around
perimeter (1-2”
from wall)
Exhaust through
center
Vent Screen
Vent pipe piece to
retain vent screen
Trinity Lx│Installation and Operation Instructions Lx Series
Sidewall Termination Details – Direct Vent Installation
Page 25
25
Figure 4-10(a)
Figure 4-10(b)
Two-Pipe Termination (Roof)
IPEX Concentric Termination (Roof)
Figure 4-10(c)
Figure 4-10(d)
PolyPro / InnoFlue Termination (Roof)
Exhaust only Termination (Roof)
Min. 12”
above grade
or snow level
Vent Screen
Vent pipe piece to
retain vent screen
Exhaust
Air-inlet
Vertical
Min. 18”
Horizontal
4-12” or greater
than 36”
Flashing
Min. 12”
above grade
or snow level
Vent Screen
Vent pipe piece to
retain vent screen
Exhaust center
Air-inlet around
perimeter
Flashing
Refer to documentation included with termination kit for
complete installation instructions.
Refer to documentation included with termination kit for
complete installation instructions.
Min. 12”
above grade
or snow level
Flashing
Exhaust
Air-inlet
Figure illustrates two options for exhaust termination only;
neither vent pipe illustrated is for combustion air-inlet.
Min. 12”
above grade
or snow level
Flashing
Vent pipe piece to
retain vent screen
Vent Screen
Exhaust
Option 1
Exhaust
Option 2
Lx Series Installation and Operation Instructions│Trinity Lx
Roof Termination Details – Direct Vent Installation
Page 26
26
Trinity Lx│Installation and Operation Instructions Lx Series
Venting Rules and Guidelines
1. Prevailing Winds: Ensure the vent is located where it will not be exposed to normal prevailing winds.
2. Combustion Air-inlet Contamination: Air for combustion must be drawn from an area free of dust and
contaminants. Combustion air containing chemicals such as chloride, fluoride, bromine or iodine or dust and
debris will cause corrosion damage of the heat exchanger voiding your NTI warranty. Refer to Table 4-1 for
a list of corrosive products and contaminants sources to avoid.
3.Vertical Separation: The exhaust must be a minimum of 18 in. above the air inlet, and the air inlet must
always be a minimum of 12 in. plus snow allowance above any surface that will support snow. (Two feet
plus snow allowance is highly recommended). Consult your weather office for the maximum typical
snowfall for your region.
Example: New Brunswick Canada - typical maximum snowfall is 19 in., thus the inlet must be (12”+19”) =
31 in. above grade and exhaust must be (31”+18”) =49” above grade.
4.Horizontal Separation:The horizontal distance between the inlet and exhaust must be a minimum of 4”
[102 mm] center to center.
5.Wall Flashing: Under normal operating conditions this boiler will produce a plume of white gases, and
should be taken into consideration when selecting an adequate location. A 36 in. diameter stainless, plastic,
or vinyl shield can be used to flash the exterior of the residence.
6.Flue Gas Hazard: Position the vent termination where vapors cannot make accidental contact with people
and pets or damage nearby shrubs and plants.
7. Elbow Extensions: Elbows on outside of wall must be no more than ½ in. away from the wall.
8. Vent Sloping: All indoor exhaust piping must be on a slope back to the boiler a minimum of ¼ in. per
linear foot of vent. For applications where excessive condensation is possible ½ in. per linear foot is
recommended.
9.Vent Supports: Where required Vent and Air-inlet piping shall be secured to the wall for more rigidity. All
interior vent pipe shall be supported a minimum of every 36 in..
10. Roof Exhaust: In all roof applications the discharge must point away from the pitch of the roof.
11. Roof Flashing: Install adequate flashing where the pipe enters the roof, to prevent water leakage.
12. Rain Cap: Install and seal a rain cap over existing chimney openings, in vacant chimney applications.
13. Venting Below Grade: For installations that exit the wall below grade refer to Figure 4-11.
14. Vent Screens: Install factory supplied vent screens on the outside of the last elbow for both the inlet and
exhaust vent terminal elbows. Install the screen into the female opening of the elbow, and then cut a small
piece of pipe to sandwich the screen into the elbow. NOTE: ensure the small piece of pipe cut, does not
extend past the end of the elbow. Two screens are provided in the package. See Figures 4-9 and 4-10.
15.Condensate Hazard: Do not locate vent over public walkways, driveways or parking lots. Condensate
could drip and freeze resulting in a slip hazard or damage to vehicles and machinery.
16.Warning Plate: For Sidewall Venting, install the warning plate “Gas Vent Directly Below”, directly above
(within 4 ft. vertically) the location of the air-inlet pipe, so it is visible from at least 8 ft away. See Figure 4-
9.
17.Wall Thickness: Direct vent terminations are designed to work with any standard wall thickness.
Installation guidelines for min/max wall thickness are as follows: Min. = 1 in., Max. = 60 in..
18.Venting Options: Due to potential moisture loading (build-up) along the exterior wall, sidewall venting
may not be the preferred venting option. Refer to Figures 4-8 and 4-10 for roof top venting options.
The vent for this boiler shall not terminate over public walkways; or near soffit vents or
crawl space vents or other area where condensate of vapor could create a nuisance or
hazard or cause property damage; or where condensate or vapor could cause damage or
could be detrimental to the operation of regulators, relief valves, or other equipment.
Page 27
27
Figure 4-11 Venting Below Grade
For installations that exit the wall below grade:
1. Excavate site to a point below where the pipes
are to exit as shown.
2. Ensure the wall is fully sealed where the pipes
penetrate.
3. The Vent/Air-inlet piping MUST be secured to
the side of the building above grade, as shown,
to provide rigidity.
4. Optional mounting bracket P/N. 82075 for
securing the exhaust pipes (only applicable for 3
in. PVC/CPVC venting).
5. Ensure that the Vent/Air-inlet clearances are
maintained, see Section 5.0 for details.
Figure 4-12 Outdoor Venting
Vent piping outside the building is permitted under
the following conditions:
1. The maximum length outside the building is 20 ft.
Note that outdoor length must be included in the
overall vent length calculation.
2. All normal termination clearances are maintained.
3. The pipe is supported every 24 in..
4. The exhaust and inlet are sloped back to the boiler
½ in. elevation for every linear foot.
Figure 4-13 Existing Chimney Chase Way
It is permissible to use an existing chimney as a chase
way to run the Vent/Air-inlet piping as long as:
1. The chimney is not being used by any other
boiler.
2. Flue gases do not enter the vacant chimney.
3. Only Trinity Lx certified venting materials are
used, see Table 4-4.
4. Vent lengths are within the maximums specified.
5. The top of the chimney is capped and the
Vent/Air-inlet pipes are flashed to prevent
leakage into the vacant chimney.
Exhaust
Air-inlet
Wall Brackets
Supports every
24 in. [610 mm]
12 in. [305 mm] plus snow
allowance above grade
Air-Inlet
Maximum of 20 ft.
[6.1 m] is permitted
for piping outside a
building.
Exhaust
Vent
Gas Vent Directly Below
Keep Free of Obstructions
Air-Inlet
Existing
Chimney
(used as a
chase way)
Chimney
Cap
Exhaust Vent
Exhaust Vent Min.
18 in. above airinlet
Air-Inlet
Min. 12 in. above
roof and snow level
Lx Series Installation and Operation Instructions│Trinity Lx
Under no circumstances may an existing chimney or chase-way be used to vent or
provide combustion intake air to a Trinity Lx. Failure to follow these instructions will
result in fire, property damage, serious injury or death.
Page 28
28
Clearances to Air-Inlet Termination
Canada 1
USA 2
Min. Distance
Min. Distance
A
Above grade/roofline and snow level 8
12 in.
305 mm
12 in.
305 mm
B
Above roof line - Concentric Vent
6, 11, 13
24 in.
610 mm
24 in.
610 mm
C
To exhaust vent from any other boiler
36 in.
915 mm
12 in.
305 mm
Clearances to Exhaust Vent Termination
Min. Distance
Min. Distance
A
Above grade/roofline and snow level 8
12 in.
305 mm
12 in.
305 mm
D
Minimum vertical separation above air inlet 9
18 in.
457 mm
18 in.
457 mm
E
Minimum horizontal separation from air inlet 3
4 in.
102 mm
4 in.
102 mm
F
Window or door that may be opened, or other building opening
36 in.
915 mm
12 in.
305 mm
G
To combustion air inlet of any other appliance
36 in.
915 mm
12 in.
305 mm
H
Non-mechanical air supply inlet to building
36 in.
915 mm
12 in.
305 mm
I
Mechanical air supply inlet to building 4
6 ft.
1.83 m
3 ft.
915 mm
J
Soffit, overhang, eave or parapet
24 in.
610 mm
24 in.
610 mm
K
Soffit vent or vent opening in an overhang, eave or parapet
6 ft.
1.83 m
6 ft.
1.83 m
L
Outside corner 10
- - -
-
M
Inside corner of an L-shaped structure (including walls and fences)
36 in.
915 mm
36 in.
915 mm
N
Service regulator / vent outlet
36 in.
915 mm
36 in.
915 mm
P
Each side of center line above or below meter / regulator assembly 5
36 in.
915 mm
36 in.
915 mm
Q
Above a paved sidewalk, driveway, or parking lot on public property if adjacent12
7 ft.
2.13 m
7 ft.
2.13 m
R
Above a public walkway
X X X
X
S
Above a sidewalk or paved driveway that is located between two single family
dwellings and services both dwellings
X X X
X
T
Under a concrete veranda, porch, deck, or balcony 7
24 in.
610 mm
24 in.
610 mm
U
Above, under or near exterior stairs
X X X
X
V
Into a canopy or carport
X X X
X
Notes:
1 - Canadian installations must comply with the current CSA B149.1 Natural Gas and Propane Installation Code and local
building codes.
2 - US installations must comply with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code and local building codes.
3 - Horizontal separation center-to-center (c.c.) 4”-12” (102-305 mm).
4 - For US installations, an exhaust vent must be 3 ft above a mechanical air supply inlet if within 10 ft. [3 m] horizontally.
5 -Horizontal clearance must be observed up to a height of 15 ft. [4.6 m] above/below the meter, regulator, or relief devices.
6 - Concentric Vent must protrude from the roof precisely 24” [610 mm] measuring from the terminal end-cap vanes.
7 - Permitted if veranda, porch, deck, or balcony is made of concrete and a minimum of two sides are fully open beneath.
8 - 24” is the recommended snow level allowance above grade/roofline or any surface that will support snow, debris, or ice
(i.e. for roof venting clearances - roofline and snow level). If living in a snowfall region, consult your local weather
office for the maximum typical snowfall for your area.
9 - Note that the vent must maintain a minimum vertical distance above the air-inlet. Example: Vent height = 18” (457
mm) above air inlet + 12” (305 mm) for air inlet above grade/roof line and snow level = 30” (762 mm) above grade and
snow level.
10-Clearances to an outside corner to be in accordance with local installation codes.
11-In Canada, concentric vent materials are subject to approval by local inspectors. See Termination Kits in Section 4.0.
12-Above public walkways, driveways or parking lots if adjacent to it and condensate cannot drip, freeze, or create a hazard.
13-Contact the manufacturer for special exemptions relating to multiple boiler installations using concentric vents.
Trinity Lx│Installation and Operation Instructions Lx Series
5.0 VENT AND AIR-INTAKE TERMINATION CLEARANCES
The instructions detailed in this section are a combination of Trinity Lx specific and National Gas Code
restrictions. Compliance alone doesn’t insure a satisfactory installation as good common sense must also be
applied. Failure to follow these instructions may result in fire, property damage, serious injury or death.
The quick reference table below is to be read in conjunction with the numbered notes as
indicated, Figures 5-1 through 5-6, and the Venting Rules and Guidelines in Section 4.0.
Page 29
29
Lx Series Installation and Operation Instructions│Trinity Lx
Figure 5-2 Sidewall Termination Clearances (See Table 5-1)
G – Letter represents a specific Termination Position. Refer to Table 5-1 for corresponding termination clearances.
Concentric Vent
Termination
Q
Two-Pipe
Termination
F
Clearance “Q”
Adjacent to Public
Walkway or Driveway
Minimum 7ft. [2.13 m]
G
Clearances “F” and “G”
Canada – Minimum 3 ft. [915 mm]
The US– Minimum 1 ft. [305 mm]
Trinity Lx│Installation and Operation Instructions Lx Series
Page 31
31
Figure 6-1 All Models
Condensate Drain Piping
Drain Vent
Do not block or install piping into
the top branch of the condensate
drain tee.
Drain Pipe
Connection to the bottom of the
condensate drain tee must be made
using 1/2” Schedule 40 PVC pipe.
Secure using appropriate PVC
cement. All piping must be below
the level where the condensate
leaves the boiler.
Floor Drain
Check with your local authorities
regarding disposal of condensate
(regulation may require the use of a
neutralizer).
Lx Series Installation and Operation Instructions│Trinity Lx
6.0 CONDENSATE DRAIN
This unit produces liquid condensate in the heat exchanger and venting system as a product of combustion.
Steps must be taken to ensure that condensate does not collect in the venting system; therefore, all exhaust
piping must slope back to the boiler a minimum 1/4” per linear foot of vent. Condensate must be drained from
the unit into a household drain.
condensate must be neutralized prior to entering a drain).
The following are important notes that must be taken into consideration when constructing the condensate drain
system (See Figure 6-1 for further details):
DO NOT install condensate lines outside. A frozen or blocked drain will cause the condensate to fill the
combustion chamber. This will result in a no heat condition, as the unit will shut down, and damage to the
flame sensor, and components can occur.
NEVER use copper, steel, or galvanized piping in the construction of the condensate disposal system as
condensate is very corrosive and will corrode most metallic drains and sewer pipes.
When a condensate pump is used or required, select a pump that is designed for residential furnaces.
the boiler must be inspected for component damage, e.g. the internal insulation at the front and back of the
chamber. Failure to follow these instructions may result in fire, property damage, serious injury or death.
Check with your municipality, or local gas company to determine if the disposal of
combustion condensate is permitted in your area (e.g. in the State of Massachusetts the
If the combustion chamber has been flooded due to the condensate drain backing up, or
for any other reason, the combustion chamber door must be removed and the inside of
Page 32
32
Model Number
LP Conversion Kit Number
LP Orifice
Lx150-200
82650-1
52 (5.2 mm)
Lx300
82650-1
62 (6.2 mm)
Lx400
83017-1
62 (6.2 mm)
Lx500
84386-1
No Orifice
1
Notes:
1
No LP orifice is used with model Lx500, see conversion kit instructions for
information on adjusting the throttle screw convert boiler to LP.
2
Models Lx600-800 cannot be operated with LP – Propane. Use Natural Gas
only.
Trinity Lx│Installation and Operation Instructions Lx Series
7.0 INSTALLING GAS PIPING
Conversion Kit (see Table 7-1) must be installed prior to installing the gas piping to the boiler. Failure to
properly convert the unit to operate with Propane may result in property damage, serious injury or death.
Codes as they may require appliances fueled with LP gas to be provided with an approved means of removing
unburned gases from the room. Failure to follow these instructions may result in serious injury or death.
Table 7-1Natural Gas to LP Propane Conversion Kit
The Trinity Lx is factory equipped to operate with Natural Gas, the installation of a
conversion kit is required prior to operating with Propane Gas. The Natural to LP
Liquefied Petroleum (LP) propane gas is heavier than air. Do not install the boiler in a pit
or similar location that will permit heavier than air gas to collect. Check with Local
Installation
Refer to the current National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 installation codes,
and local codes for gas piping requirements and sizing. Pipe size running to the unit depends on:
Length of pipe.
Number of fittings.
Type of gas.
Maximum input requirement of all gas appliances in the residence.
Ensure that:
The gas line connection to the boiler does not apply any weight to the gas valve. NTI recommends using
approved flexible gas piping (if acceptable by local codes) to connect the boiler to the gas supply (See
Figure 7-1 for details).
You plan the installation so that the piping does not interfere with the vent pipe, or the removal of the valve,
burner, and serviceable components.
The boiler shall be installed such that the gas ignition system components are protected from water
(dripping, spraying, rain etc.) during installation and servicing.
The gas piping is large enough for all the appliances in the home. No appreciable drop in line pressure
should occur when any unit (or combination of units) lights or runs. Use common gas-line sizing practices.
Always use a pipe-threading compound that is resistant to propane (LP) gas solvent action. Apply sparingly
to all male threads, starting at two threads from the end. Over doping or applying dope to the female end,
can result in a blocked gas line.
DO NOT TIGHTEN FITTINGS WITHOUT SUPPORTING THE GAS VALVE as damage to the gas valve
or combustion blower can occur.
Install a manual “Equipment Shut-Off Valve” as shown in Figure 7-1. Valve must be listed by a nationally
recognized testing lab.
The gas line piping can safely be removed from the boiler for servicing, by strategically placing the gas line
shutoff and union; see example in Figure 7-1.
All gas piping, including gas components in the boiler, are checked for leaks using a “Bubble Test”, prior to
operating the boiler.
Page 33
33
Figure 7-1 Gas Line Connection (Typical)
Model Lx200 Illustrated
Manual Shutoff Valve
Union
Drip Leg
Rigid Gas Line Piping
Use only rigid gas line piping within the
appliance cabinet. Rigid piping must
protrude beyond the outside of the
cabinet wall.
Flexible Gas Line Piping
Recommended to eliminate strain
on the appliance gas components
(only use if acceptable by local
codes).
Manual Shutoff Valve - Should
overheating occur or the gas
supply fail to shut off, turn off the
manual gas control valve to the
appliance.
Lx Series Installation and Operation Instructions│Trinity Lx
Strain on the gas valve and fittings may result in vibration, premature component failure
and leakage and may result in a fire, explosion, property damage, serious injury or death.
Flexible gas piping cannot be used within the boiler cabinet and cannot pass through the
cabinet wall, use rigid piping as shown in Figure 7-1. Failure to follow these instructions
may result in fire, property damage, serious injury or death.
Do not use an open flame to test for gas leaks. Failure to follow these instructions may
result in fire, property damage, serious injury or death .
When performing a pressure test on the gas line piping, be sure the boiler is disconnected
or isolated if the test pressure is expected to exceed 1/2 PSI (14” w.c.), as damage to the
valve could occur resulting in fire, property damage, serious injury or death.
Page 34
34
Trinity Lx│Installation and Operation Instructions Lx Series
8.0 LIGHTING THE BOILER
Before Start-up refer to Mandatory Pre-commissioning Procedure for Plastic Venting
in Section 4.0.Failure to follow these instructions can result in explosions, injury or death.
Prior to turning the gas supply on and lighting the boiler, ensure all aspects of the
installation are complete and in conformance with the instructions provided in this
manual, including the Vent/Air-Intake, Condensate Drain, and System Water Piping. Failure to precisely follow
these instructions will cause a fire or explosion resulting in property damage, serious injury or death.
A) This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any boiler.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result
in a fire or explosion.
D) Do not use this boiler if any part has been under water. Immediately call a qualified service technician
to inspect the boiler and to replace any part of the control system and any gas control which has been
under water.
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you don't smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the boiler.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Boiler” and call your service
technician or gas supplier.
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the boiler.
3. Turn the manual gas valve to the OFF position.
Do not store or use gasoline or other flammable vapors & liquids in the vicinity of this or
any other appliance. Failure to follow instructions could result in explosion causing
property damage, serious injury or death.
If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, serious injury or death.
Should overheating occur or the gas supply fail to shut off, turn off the manual gas
control valve to the boiler. Failure to follow instructions could result in explosion
causing property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING_
OPERATING INSTRUCTIONS_
TO TURN OFF GAS TO THE BOILER_
Page 35
35
Lx Series Installation and Operation Instructions│Trinity Lx
The initial lighting of the boiler must be performed by a licensed Gas Technician.
Failure to follow instructions may result in property damage, serious injury or death.
Ensure the boiler is wired in accordance with this manual.
Ensure the gas shut-off valve is turned on, and that the gas system has been fully tested for leaks.
Ensure the system is completely filled with water, and that ALL the air is purged out.
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8
hours,first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.Failure to follow these instructions can result in explosion,
serious injury or death.
Initial Start-Up
1. Turn on power to the Trinity Lx and turn-up the Thermostat(s). The boiler should run through a purge, and
combustion should occur. (The control system has a built in ignition retry, allowing the system to try at least
three times, before locking-out.)
2. With the unit operating at full capacity, verify that the gas line pressure is 5.5-10.5 inches w.c. for Natural
gas, and 9-13 inches w.c. for Propane (See Section 9.0 for details).
3. Using an appropriate Oxygen or Carbon Dioxide analyzer, take a sample of the flue gas. The sample must
fall within the acceptable ranges for Carbon Dioxide, which is 8.8% - 9.8% for Natural gas, and 9.8%-10.8%
for propane (See Section 9.0 for details).
4. Perform at least three lights in succession to ensure proper operation.
5. After the three successive lights, unplug the flame probe, and allow the unit to cycle again. Ensure that it
tries to light, and locks out on safety reset. Once you have successfully activated the flame safety system,
replace the wire on the flame sensor, and reconfirm proper lighting.
If the unit fails to light consistently and smoothly, contact NTI for technical assistance at
1-800-688-2575. Never allow the boiler to operate if the ignition or operation of the
burner is rough or erratic. Failure to follow these instructions may result in serious injury
or death.
The flame probe uses a single electrode located in the burner door at the 6 O’clock
position. DO NOT remove the wire from the dual electrode located in the burner door at
the 3 O’clock position; this device is used for spark igniting and delivers a high voltage
potential which would result in an EXTREME ELECTRICAL SHOCK possibly causing
serious injury or death.
Re-lighting Unit
1. Stop and read these instructions very carefully.
2. Set the thermostat to the lowest setting, and then turn off all power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device that automatically lights the burner.
Do not try to light the burner by hand.
4. Turn the gas shut-off valve to the off position, and then remove the front cover.
5. Wait five (5) minutes to clear out any gas. Then check for gas, including near the floor. If you smell gas
“Stop” and follow “B” above. If you don’t detect any gas proceed to the next step.
6. Turn the gas shut-off valve to the on position, wait an addition five (5) minutes and check for gas.
7. Replace the front cover.
8. Set the thermostat to the highest setting, and then turn on all power to the boiler.
9. Ignition sequence is automatic, combustion will occur after a brief fan purge. Ignition will retry 3 times.
10. If ignition does not occur, “Turn off the gas and electricity to the boiler” and contact a professional service
technician, or gas supplier.
Turning Off The Boiler
1. Set the thermostat to the lowest setting, and then turn off all power to the boiler.
2. Turn the gas shut-off valve to the off position.
Page 36
36
Gas
Line Pressure (inches wc)
CO2 (%) 1
CO (ppm)
Max.
Nominal/Desired
Min.
Max.
Min.
Max.
Natural
7
4 2
10.5
8.8
9.8
175
Propane
11 8 13
9.8
10.8
175
Notes:
1
It is permissible to have higher CO2 values with the burner operating at the minimum modulation rate.
2
The minimum permissible line pressure when operating with Natural Gas is 5.5 inches wc for model Lx500.
Modulation
Rates (rpm)
Lx150
Lx150E
Lx200
Lx300
Lx400
Lx500
Lx600
Lx700
Lx800
Minimum
1150
925
925
1250
1550
1400
1050
1250
1250
Maximum
5850
4450
5950
5850
7250
6400
4350
4300
5300
Trinity Lx│Installation and Operation Instructions Lx Series
9.0 GAS VALVE AND BURNER SET-UP
Gas Line Pressure
The boiler gas valve is equipped with a line pressure test port; see Figures 9-1 through 9-4. Use the following
procedure to measure the gas line pressure to the boiler to ensure if falls within the range given in Table 9-1:
1. Turn the supply of gas to the boiler off.
2. Open the bleed screw of the line pressure test port approximately 1-1/2 turns (Lx150-500 models). This
port is directly connected to the gas line feeding the boiler. For Lx600-800 models, replace 1/8” NPT plug
in the inlet flange of the gas valve with a hose barb fitting suitable for manometer tubing used. See Figures
9-1 through 9-5.
3. Force 1/4 ID tubing over the housing of the line pressure test port; install the other end of the tubing to an
appropriate line pressure test gauge or manometer. Ensure both ends of the tubing make a tight connection.
4. Open the supply of gas to the boiler and check for gas leaks.
5. Observe the line pressure under static conditions and compare it to Table 9-1. The pressure will be greatest
under static conditions.
6. With all other gas appliances in the applications running, operate the burner to the maximum firing rate (see
Table 9-2) and compare the observed line pressure with Table 9-1. The pressure will be lowest during the
maximum flow of gas.
7. Adjust the gas line pressure to ensure the parameters in Table 9-1 are attained under all conditions. If
possible adjust the line pressure to the "Nominal/Desired" value listed in Table 9-1, while the unit is
operating at the maximum modulation rate, see Table 9-2.
8. Continue observing the gas line pressure until the completion of the combustion analyses, incase
adjustments need to be made.
9. Upon completion of the line pressure testing, return the bleed screw of the Line Pressure Test Port to the
closed position. For the Lx600-800 models, replace the installed hose barb fitting with the factory 1/8” NPT
plug; use NG/LP approved thread sealant.
Table 9-1 Line Pressure and Combustion Parameters
The Trinity Lx gas valve must be set-up by a licensed Gas Technician. Improper set-up
may result in incorrect operation, damage to components or property, injury or death.
The line pressure is a function of the gas supply and is affected solely by field provided
parameters such as line size and regulator settings. Under no circumstances can the boiler
gas valve influence or be used to adjust the gas line pressure.
Failure to close the bleed screw of the Line Pressure Test Port will cause a severe leakage
of gas, resulting in a fire or explosion causing property damage, serious injury or death.
Table 9-2 Minimum and Maximum Modulation Rates
Carbon Monoxide - Never leave the boiler operating if emitting Carbon Monoxide (CO)
concentrations in excess of 175ppm. Failure to comply may result in injury of death.Manifold Pressure - DO NOT adjust or measure the Manifold Pressure of the boiler.
Correct manifold pressure is factory set. Field adjustment could result in improper burner
operation resulting in fire, explosion, property damage or death.
Page 37
37
Figure 9-1 Gas Valve and Venturi Assembly (Lx150-300)
Lx150 Orientation Illustrated
Figure 9-2 Gas Valve and Venturi Assembly (Lx150-300)
Lx150E/Lx200 Orientation Illustrated
Orifice Location
(See Kit 82650-1)
Gas Valve
Air-inlet
Manifold Pressure
Test Port
Line Pressure
Test Port
Throttle/Input
Adjustment Screw
Venturi
Gas In
Orifice Location
(See Kit 82650-1)
Throttle/Input Adjustment
Screw
Line Pressure
Test Port
Gas In
Lx150E/Lx200
Orientation Illustrated
Lx300 Assembly Orientation
Rotated Clockwise 90
o
Venturi
Air-inlet
Manifold Pressure
Test Port
Gas Valve
Lx Series Installation and Operation Instructions│Trinity Lx
Page 38
38
Figure 9-3 Gas Valve and Venturi Assembly (Lx400)
Figure 9-4 Gas Valve and Venturi Assembly (Lx500)
Throttle/Input
Adjustment Screw
Venturi
Air Inlet
Line Pressure
Test Port
Gas In
Gas Valve
Orifice Location
(See Kit 83017-1)
Manifold Pressure
Test Port
Gas In
Gas Valve
Throttle/Input
Adjustment Screw
Manifold Pressure
Test Port
Line Pressure
Test Port
Trinity Lx│Installation and Operation Instructions Lx Series
Page 39
39
Figure 9-5 Gas Valve and Venturi Assembly (Lx600-800)
Throttle/Input
Adjustment Screw
Manifold Pressure
Test Port (outlet
flange)
Gas Valve
Venturi
Manual Gas
Shutoff Valve
Air-inlet
Gas In
Line Pressure
Test Port
(inlet flange)
Remove cover to
make adjustments
to the throttle/input
screw
Gas Valve
Regulator
Sensing
Tube
Lx Series Installation and Operation Instructions│Trinity Lx
Adjustment
Input Screw Adjustments - The boiler is equipped with a Throttle/Input Adjustment Screw, located on the Gas
Valve and Venturi Assembly. The Throttle screw is used to adjust the flow of gas leaving the gas valve,
entering the Venturi and hence entering the combustion air stream. By turning the adjustment screw in,
clockwise, the flow of gas is reduced and the combustion becomes leaner, thus reducing the concentration of
CO2 in the flue gases. To increase the CO2 the Throttle screw must be adjusted out, counterclockwise, thus
increasing the flow of gas from the gas valve to the combustion air stream. See Figure 9-6 for screw direction.
Lx150-300 Adjustments - The throttle screw for models Lx150-300 is a multiple turn valve. Typical adjustment
required for Natural Gas is 0-1 full turns in or out from the factory setting. Typical adjustment for LP Gas is
0-3 full turns in or out from the factory setting upon inserting the LP orifice as per the applicable Propane
conversion instructions. See Figures 9-1 and 9-2 for throttle screw location.
Lx400 Adjustments - The throttle screw for the Lx400 is a geared valve with a 4:1 ratio. Adjusting the throttle
screw 4 complete turns will return the valve to the original location, 2 turns from fully open will completely
close the valve. Typical adjustment required is 0-1/4 turn in or out from the factory setting. See Figure 9-3 for
throttle screw location.
Lx500 Adjustments – The throttle screw for the Lx500 is a multiple turn valve. Typical adjustment required for
Natural Gas is 0-1 full turns in or out from the factory setting. To adjust combustion for Propane Gas, turn
the throttle screw all the way in (clockwise until it stops), then turn the throttle screw out (counterclockwise)
4-1/2 turns and set with a combustion analyzer. See Figure 9-4 for throttle screw location.
Lx600-800 Adjustments - Remove the cap and adjust the input screw by turning it clockwise to decrease gas
flow and counter-clockwise to increase gas flow. Typical adjustment required is 0-1/8 turns in or out. See
Figure 9-5 for throttle screw location.
IF FOR ANY REASON THE INPUT SCREW IS ADJUSTED, A "COMBUSTION ANALYZER"
MUST BE USED TO ENSURE SAFE AND PROPER OPERATION OF THE GAS VALVE.
Trinity Lx│Installation and Operation Instructions Lx Series
Adjustments to the Throttle screw may only be made by a qualified gas technician, while
using a calibrated combustion analyzer capable of measuring CO2 and CO. Failure to
Combustion Calibration - To calibrate burner operation, perform the following procedure using a calibrated
combustion analyzer capable of measuring CO2 and CO from Natural and Propane Gas burning appliances:
1. Operate the unit at the maximum modulation rate, see Table 9-2.
2. Ensure the gas line pressure is maintained within tolerance, see Table 9-1.
3. While at the maximum modulation rate, measure the CO2 and CO; adjust as necessary, using the Throttle
Screw, to be within the limits listed in Table 9-1.
4. Operate the unit at the minimum modulation rate (Table 9-2). Ensure the combustion remains smooth and
CO2 and CO remain within the limits (Table 9-1). If not, do not adjust further, contact NTI for assistance.
Flue Gas Analysis and Adjustment
Each Trinity Lx is factory set to operate with Natural Gas, for boilers field converted to operate with Propane
Gas, a flue gas analysis and adjustment is mandatory. See Table 7-1 and propane conversion instructions.
Lx500 to operate with Propane Gas requires field calibration of the throttle/input screw; see “Lx500
Adjustments” in Section 9.0 and Propane conversion instructions. Models Lx600-800 only operate with Natural
Gas; conversion to Propane is not an option. Failure to follow these instructions will result in property damage,
personal injury or death.
Analysis - Trinity Lx flue gas test ports are located in the flue outlet adapter assembly. Test port access is either
from inside the boiler cabinet (Lx150, Lx150E & Lx200; Figure 9-7) or from outside the boiler cabinet
(Lx300-800; Figures 9-8 through 9-10). Remove the test port plug, perform flue gas analysis, and adjust
throttle/input screw as required until CO2 and CO levels are within acceptable limits, see Table 9-1 Line
Pressure and Combustion Parameters. Once flue gas sampling completed, re-install test port plug. For model
with a threaded plug, seal threads with Teflon tape before reinstalling plug.
follow these instructions may result in serious injury or death.
Adjustments to the Throttle screw may only be performed if the gas line pressure is
maintained above minimum levels throughout the duration of the test; see Table 9-1.
Failure to follow these instructions may result in serious injury or death.
Models Lx150-400 require the installation of an LP orifice prior to operating with
Propane Gas, see Propane conversion instructions for more details. To convert the
Failure to perform the flue gas analysis and adjustment detailed in this section may result
in erratic and unreliable burner operation, leading to reduced efficiency, increased fuel
consumption, reduced component life, heat exchanger combustion deposits, and general
unsafe operation. Failure to follow these instructions may result in serious injury or
death.
Failure to re-install the test port plug will result in damage to the unit, property damage,
fire, explosion, serious injury or death.
Page 41
41
Figure 9-7 Flue Gas Sampling Using Test Port (Lx150-200)
Figure 9-8 Flue Gas Sampling Using Test Port (Lx300-400)
Test Port
Combustion
Analyzer
FLUE GAS TEST PORT PLUG - Remove test
port plug to perform flue gas analysis. Re-install
plug once sampling completed to prevent flue gas
leakage during appliance operation. Failure to
comply with these instructions will result in serious
injury or death.
Combustion
Analyzer
Test Port
FLUE GAS TEST PORT PLUG - Remove test
port plug to perform flue gas analysis. Re-install
plug once sampling completed to prevent flue gas
leakage during appliance operation. Failure to
comply with these instructions will result in serious
injury or death.
Lx Series Installation and Operation Instructions│Trinity Lx
Page 42
42
Figure 9-9 Flue Gas Sampling Using Test Port (Lx500-600)
Figure 9-10 Flue Gas Sampling Using Test Port (Lx700-800)
Test Port
Combustion
Analyzer
FLUE GAS TEST PORT PLUG - Remove test
port plug to perform flue gas analysis. Re-install
plug once sampling completed to prevent flue gas
leakage during appliance operation. Failure to
comply with these instructions will result in serious
injury or death.
Combustion
Analyzer
Test Port
FLUE GAS TEST PORT PLUG
Remove test port plug to perform
flue gas analysis. Re-install plug
once sampling completed to prevent
flue gas leakage during appliance
operation. Failure to comply with
these instructions will result in
serious injury or death.
Trinity Lx│Installation and Operation Instructions Lx Series
Page 43
43
Table 10-1 Boiler System Cleansers and Corrosion Inhibitors
Application
Fernox Product
NTI Part #
Description
Boiler Water Treatment
F1 Protector
83448
Corrosion inhibitor.
Cleanser for new and old systems
F3 Cleaner
83449
Removes flux, grease and carbon residue.
Cleanser for Retrofits
DS-40 System Cleaner
83450
Removes heavy limescale and sludge deposits.
PH – between 7.5 and 9.5.
Iron – less than 0.5mg/l.
Chloride – less than 125mg/l.
Copper – less than 0.1mg/l.
Conductivity – 100 to 300µS/cm (at 25ºC); [TDS 50 to 150ppm or Total Hardness 3 to 9grains/USgal.]
Lx Series Installation and Operation Instructions│Trinity Lx
10.0 BOILER AND HEATING SYSTEM PIPING
The heat exchanger of the Trinity boiler is designed to attain the highest level of heat transfer in a compact
design. To accomplish this, the heating water flows through a series of fin shaped tubes, designed to maximize
the heat transfer area. To maintain the efficient and reliable operation of the heat exchanger, and to avoid heat
exchanger failure, it is critical to ensure the rules and guidelines in this section are followed.
Failure to follow the instructions provided in this section will void the NTI warranty and
may result in property damage, fire, serious injury or death.
Boiler System Preparation
Prior to connecting plumbing to the boiler, flush the entire system to ensure it is free of sediment, flux, solder,
scale, debris or other impurities that may be harmful to the system and boiler. During the assembly of the
heating system, it is important to keep the inside of the piping free of any debris including construction and
copper dust, sand and dirt.
For retrofits, all system piping including radiators, must be cleansed of all build-up including sludge and scale.
All systems, old and new, must be cleansed to remove flux, grease and carbon residue. NTI recommends
cleansing the boiler system with “Fernox F3 Cleaner”. For retrofit applications with heavy limescale and sludge
deposits, a heavier duty cleaner may be required; NTI recommends the use of “Fernox DS-40 System Cleaner”.
For information on performing the cleansing, follow the instructions included with the Fernox DS-40 System
Cleaner. See Table 10-1 for a list of recommended boiler cleansing products.
Failure to rid the heating system of the contaminants listed above will void your NTI
warranty and may result in premature heat exchanger failure and property damage.
Boiler Water
Pressure - The Trinity boilers are intended solely for use in pressurized closed loop heating systems operating
with a minimum pressure of 15 PSI at the boiler outlet. To obtain the minimum system design pressure,
follow the piping diagrams illustrated in this section.
Oxygen Elimination - This boiler may only be installed in a pressurized closed-loop heating system, free of air
(oxygen) and other impurities. To avoid the presence of oxygen, ensure all of the air is removed from the
system during commissioning via strategically placed adequately sized air-removal devices, located
throughout the heating system. See figures in this section detailing the location of the primary air-removal
device required for the boiler. Immediately repair any leaks in the system plumbing to avoid the addition of
make-up water; make-up water provides a source of oxygen and minerals that may lead to heat exchanger
failure. Failure to follow these instructions will result in poor performance, unnecessary wear of system
components and premature failure.
The Trinity Lx is not approved for operation in an “open system”, thus it cannot be used
for direct potable water heating or process heating of any kind.
Water Chemistry – The installer of the Trinity Lx boiler must consider the condition of the water in the heating
system. Ensure the condition of the boiler water falls within the following parameters:
Page 44
44
Table 10-2 Pressure Relief Valve Specifications
Boiler
Model
Maximum Pressure Relief Valve Setting
/ Boiler MAWP (psi)
Minimum Pressure Relief
Valve Capacity (MBH)
Lx150
30
150
Lx150E
145
150
Lx200
145
200
Lx300
160
300
Lx400
145
400
Lx500
160
500
Lx600
160
600
Lx700
160
700
Lx800
160
800
Notes:
1
Lx150 models sold in US have a MAWP = 145 psi.
Trinity Lx│Installation and Operation Instructions Lx Series
Treatment - Boiler water that falls outside of the conditions listed above must be treated with a corrosion
inhibitor. Each Trinity Lx boiler is provided with at least 1 bottle of “Fernox F1” corrosion inhibitor (Lx500800 come with 2 bottles), adequate to treat a 26.4 gallon (100 liter) heating system to a minimum required
concentration of 0.5%. Systems with greater volume will require more inhibitor. For information on
performing the treatment, follow the instructions included with the Fernox F1 Protector. See Table 10-1 for a
list of recommended boiler system cleansers and corrosion inhibitors.
Anti-freeze - For systems requiring freeze protection, use only inhibited propylene glycol, specially formulated
for hydronic heating systems; use of other types of antifreeze may be harmful to the system and will void the
warranty. Note: the use of glycol may reduce the usable output capacity of the boiler, thus requiring the unit
to be “de-rated” by limiting the maximum operating capacity and/or the maximum water temperature. NTI
recommends against exceeding 35% concentration of glycol.
Near Boiler Plumbing
Pressure Relief Valve - A Pressure Relief Valve is factory supplied with each unit and must be field installed at
the boiler outlet in the vertical position, as shown in Figures 10-1(a) and (b), with the drain pipe outlet exiting
the side of the pressure relief valve horizontally and elbowing down. Lx150-400 models come with a 30 psi
relief valve, while Lx500-800 models come with a 50 psi relief valve. The maximum allowable working
pressure (MAWP) varies with boiler model, see Table 10-2; alternate relief valves may be used, so long as
they are ASME certified and meet the requirements for the respective boiler.
Pressure Gauge – Trinity Lx units come with a factory supplied Pressure Gauge. The pressure gauge must be
installed at the boiler outlet, prior to any circulators, and in the vicinity of the pressure relief valve. See
Figures 10-1(a) and (b).
To maintain protection, the level of corrosion inhibitor must be monitored periodically
for the correct concentration.
DO NOT use inhibited glycol with non-compatible boiler inhibitors. Non-compatible
inhibitors may counteract each other rendering them ineffective.
If installed with the incorrect orientation (horizontally with drain pipe out the bottom) the
relief valve may not function properly resulting in property damage or personal injury.
Ensure the discharge of the pressure relief is piped to a location where the steam or water
will not cause property damage or serious injury.
Page 45
45
Figure 10-1(a) Near Boiler Piping (Lx150-400)
Figure 10-1(b) Near Boiler Piping (Lx500-800)
Pressure Relief
Valve discharge
to floor drain
Outlet
To Boiler and
system plumbing.
Refer to piping
diagrams.
Mandatory Safety
Flow Switch
Pressure Gauge
Pressure Relief Valve
Inlet
Pressure Relief
Valve discharge
to floor drain
Near Boiler
tees and
fittings
Safety Flow Switch
Pressure Relief Valve
Pressure Gauge
Trim-able paddle
Outlet
Inlet
Lx Series Installation and Operation Instructions│Trinity Lx
Page 46
46
Factory Supplied Components
Field Supplied Components
Pressure Relief Valve 1
Boiler Loop Circulator (Pump B in Figure 10-2 or Pump C in Figure 10-3)
Pressure Gauge
DHW Loop Circulator (Pump A in Figure 10-2 and Figure 10-3, for
applications utilizing Indirect Fired Water Heater only)
Flow Switch (Lx500-800 only)
Central Heat (CH) Loop Circulator(s)
(CH Circulator - Pump C in Figure 10-2; Zone Circulators in Figure 10-3)
Central Air Removal Devices (i.e. Micro Bubbler or Air-Scoop)
Pressure Regulating “Fill Valve”
Backflow Preventor
Expansion Tank
Notes:
1
Refer to Table 10-2 for a list minimum Pressure Relief Valve specifications.
Trinity Lx│Installation and Operation Instructions Lx Series
Low Water Cutoff (LWCO) / Safety Flow Switch – Trinity Lx150-400 boilers are provided with a factory
installed Water Pressure Switch; in the event the pressure drops below 10 psi, the burner is inhibited from
firing. Where required by the Authority having jurisdiction, an external LWCO, or Safety Flow Switch, may
have to be installed; see Figures 10-1(a) and (b) for Safety Flow Switch installation.
Boiler System Plumbing
The Trinity Lx boiler uses a low mass heat exchanger that requires a minimum rate of forced water circulation
any time the burner is operating (See Table 10-4 for minimum flow rates). To ensure the minimum flow rate is
attained, the boiler must be installed in a “Primary/Secondary” plumbing configuration utilizing “Closely Spaced Tees” to de-couple the Boiler-Primary loop from the System-Secondary loop(s) (see Figures 10-2 and 10-3 for
examples). As well as a Primary/Secondary Loop Configuration utilizing closely spaced tees, a properly installed
system will as a minimum include the major components in Table 10-3.
Table 10-3System Major Component Checklist
When using a Safety Flow Switch, it must be installed on the boiler outlet fitting (see
Figure 10-1) in accordance with the instructions provided with the flow switch. Install
the flow switch in a 1” diameter line for models Lx150-200, and a 1-1/4” diameter line
for models Lx300-400.
Models Lx500-800 come equipped with a factory installed flow switch installed in a 2”
diameter line. The flow switch is pre-plumbed with a Nema 4 rated enclosure and
prewired via liquid-tight conduit. According to ASME CSD-1, a flow switch must be
used in lieu of a Low Water Cut Off (LWCO) for a water tube boiler.
When external safety devices are used, such as a LWCO, Flow Switch, or a Temperature
Limiting Switch, they must be wired as per the instructions provided in this manual.
Refer to Section 12.0 for wiring instructions.
Circulating Pumps – Trinity Lx150-400 boilers are equipped with three 120VAC pump outputs, while the
Lx500-800 is equipped with 3 pump contacts (relays):
1. PUMP A “DHW Pump” - operates during a Domestic Hot Water demand
2. PUMP B “Boiler Pump” - operates during any demand
3. PUMP C “CH Pump”- operates during a Central Heat demand (CH1 or CH2)
Ensure pumps are oriented as per the manufacturers’ instructions. Wiring of these circulators will depend on the
system configuration chosen; see Figures 10-2 and 10-3. For further wiring details see Section 12.0.
Circulators responsible for forcing the water flow rate through the boiler must be sized
according to Table 10-4, see Figures 10-2 and 10-3 for details.
Failure to ensure the minimum water flow rate through the boiler when the burner is on
will not only reduce the operating efficiency of the boiler, but may also cause premature
failure, overheating and void the warranty. Failure to follow instructions may result in
fire, property damage, serious injury or death.
Page 47
Lx Series Installation and Operation Instructions│Trinity Lx
47
Model
Restriction
Head Loss
Minimum
Pipe Size
Min. Flow
(GPM)
Max Temp.
Rise
Minimum Primary Loop Pump Size
B&G
Grundfos
Taco
Armstrong
150
8' at 7 GPM
1"
6
45F
NRF-36
UPS 15-58
1
0011
Astro 50
150E
4' at 7 GPM
1"
6
45F
NRF-22
1
UPS 15-58
1
0011
Astro 30
200
7' at 10 GPM
1-1/4"
8
45F
NRF-36
UPS 26-99
0011
Astro 50
300
7' at 14 GPM
1-1/4"
11
45F
NRF-36
UPS 26-99
0011
1
E7
400
10' at 20 GPM
1-1/2"
16
45F
NRF-36
UPS 26-99
0011
1
E8
500
12' at 25 GPM
2"
20
45F
PL-36
1
UP 43-100
2400-20
1, 3
E8
1
600
10' at 30 GPM
2"
24
45F
PL-55 5
UPS 26-150
2400-45 4
E15 1
700
9' at 35 GPM
2"
28
45F
PL-55 5
UPS 26-150
1
2400-45 4
E15 1
800
11' at 40 GPM
2"
32
45F
PL-55
5
UP 43-110 2
2400-45 4
E15 1
Notes:
1
NOT recommended for DHW indirect circulator when installed as per Figure 10-3, recommend higher head circulator.
2
Grundfos UPS 32-160 can be used in place of UP 43-110; Grundfos UPS 26-150 can be used in place of UPS 43-100.
3
Taco 2400-40 NOT recommended.
4
Taco 2400-60 NOT recommended.
5
B&G PL-75 and PL-130 NOT recommended.
Table 10-4 Minimum Circulator and Pipe Sizes
Air Removal – The boiler and system plumbing layout must be configured to promote the removal of air from
the water. Air vents and bleeders must be strategically placed throughout the system to aid in purging the air
from the system during commissioning of the boiler. The system must also employ the use of a strategically
located air removal device, such as an air scoop or micro-bubbler, designed to remove the air from the water
as it flows through the system.
Follow the installation instructions included with the air removal device when placing it
in the system; air removal devices generally work better when placed higher in the
system. Always locate air removal devices in areas of the system that have a guaranteed
positive pressure, e.g., in close proximity to the water fill and expansion tank.
Trinity boilers are equipped with an automatic air removal device to aid in the purging of
air from the boiler during the initial fill. This device is NOT intended, nor is it sufficient
to remove the air from the system plumbing, even if the air makes it back to the boiler.
Expansion Tank – The expansion tank must be sized in accordance with the water volume of the system as well
as the firing rate of the boiler. It is important to locate the expansion tank, and make-up water fill, on the
inlet side of any circulator in the system, as doing so will guarantee the lowest pressure in the system will be
at least equal to the tank and make-up water pressure. See examples in Figures 10-2 and 10-3.
A strategically located air removal device must be installed in the system.
Ensure the expansion tank cannot become isolated from the boiler anytime the system is
operating. Failure to follow these instructions may result in discharge of the Pressure
Relief Valve may result in property damage or personal injury.
The installation of flow checks, motorized valves or other shutoff devices (other than for
the purpose of servicing) are not permitted between the location of the “Closely Spaced
Tees” and the expansion tank; see Figures 10-2 and 10-3.
Page 48
48
Lx150
10’ at 6 GPM
Lx500
18’ at 20 GPM
Lx150E
14’ at 6 GPM
Lx600
18’ at 24 GPM
Lx200
14’ at 8 GPM
Lx700
15’ at 28 GPM
Lx300
12’ at 11 GPM
Lx800
12’ at 32 GPM
Lx400
9’ at 16 GPM
Trinity Lx│Installation and Operation Instructions Lx Series
Indirect Fired Water Heater – When installed as per Figure 10-3, the indirect fired water heater is in series
with the boiler during a demand for DHW. Therefore when using this configuration it is important to use an
Indirect Fired Water Heater that has minimal head loss. Indirect fired water heater head loss must not exceed
those specified in Table 10-5, when installed as per Figure 10-3.
Table 10-5 Maximum Indirect Fired Water Heater Head Loss (Boiler Side) at Minimum Flow
Figure 10-2: Single System Circulator Configuration - Often used in applications zoned with “Zone Valves”.
During a demand for central heat, the boiler energizes the System Circulator via the Central Heating (CH)
pump output (PUMP C). The System Circulator must be sized to provide adequate circulation throughout the
heating system. During a Domestic Hot Water (DHW) demand, the boiler de-energizes the System
Circulator (PUMP C) and energizes the DHW Circulator (Pump A). With this configuration the Boiler
Circulator is the only pump that causes flow through the boiler and it is powered during any demand via the
boiler pump output (PUMP B). This circulator must be sized according to Table 10-4.
Figure 10-3: Multiple System Circulator Configuration - Often used in applications with “Zone Circulators”.
This configuration requires the installation of a check valve located at each circulator. During a central
heating demand the boiler energizes the Central Heat Circulator via the Central Heat pump out (PUMP C).
During a Domestic Hot Water (DHW) demand, the boiler de-energizes PUMP C and energizes the DHW
Circulator (Pump A). Both Pump A and C, used in this configuration, are responsible for water flow through
the boiler and must be sized according to Table 10-4. Pump output, PUMP B is not used in this
configuration.
The piping configuration described above requires the Central Heating system and DHW
system to be de-coupled from the “Primary Loop” via closely spaced tees (Figure 10-3).
Figures 10-2 and 10-3 illustrate typical piping systems. These piping schematics do not
illustrate all of the required concepts and components required to have a proper
installation. Concepts not shown include: prevention of thermal-siphoning (heat traps),
isolation valves, drain and purge valves, etc. It is the responsibility of the installing
contractor and system designer to determine which system best meets the need of the
installation and to consider all aspects of a proper system design. Contractor
modifications to these instructions may be required, based upon existing piping and
system design.
Page 49
49
Lx Series Installation and Operation Instructions│Trinity Lx
Figure 10-2 Primary / Secondary Plumbing
(Single System Circulator Configuration)
Page 50
50
Trinity Lx│Installation and Operation Instructions Lx Series
Figure 10-3 Primary / Secondary Plumbing
(Multiple System Circulator Configuration)
Page 51
51
# of
Units
Lx150/150E
Lx200
Lx300
Lx400
Lx500
Lx600
Lx700
Lx800
2
1-1/2"
2"
2”
2-1/2"
2-1/2”
3”
3”
3"
3
2"
2"
2-1/2”
3"
3”
3”
4”
4"
4
2"
2-1/2"
2-1/2”
3"
4”
4”
4”
4" 5 2-1/2"
2-1/2"
3”
4"
4”
4”
4”
5" 6 2-1/2"
3"
3”
4"
4”
4”
5”
5" 7 2-1/2"
3"
4”
4"
4”
5”
5”
5" 8 2-1/2"
3"
4”
4"
5”
5”
5”
5"
Lx Series Installation and Operation Instructions│Trinity Lx
11.0 LEAD LAG INSTRUCTIONS
Multiple Boiler Applications
The Lx controller has the internal capacity to stage or Lead-Lag up to 8 boilers configured in a cascade. This
Lead-Lag capability allows a designated “Master” boiler to communicate with and effectively control each boiler in a multiple boiler system. This function is accomplished by “Daisy Chaining” a 3-wire cable between
each of the boilers and enabling the Master parameter in the boiler of your choice. The boiler with the Master
parameter enabled becomes the single point of contact for Central Heating, Domestic Hot Water and Outdoor
Reset settings and control. Use the instructions detailed in this section to set-up and install the cascade boiler
system; reference Appendix A – Controller and Touchscreen Display Instructions for details on more advanced
settings and for assistance with navigating the touchscreen display.
Lead Lag Instructions - Common
Plumbing – install as many as 8 Lx boilers in parallel in a primary/secondary plumbing configuration as
illustrated in Figure 11-1. Size common piping as per Table 11-1.
Boiler Pump – each boiler must have its own circulator (see Figure 11-1) which is controlled by its PUMP B
output; see Field Wiring Figures and Tables 12-1(a) and 12-1(b). The Boiler Pump must be sized according
to Table 10-4.
Communication Wiring – using 3-wire cable, daisy-chain terminals LL DATA +, LL DATA – and SENSOR
COM of each boiler in parallel; see Field Wiring Tables 12-2(a) and 12-2(b) and Figure 12-2.
System Sensor (Optional) – install a system sensor (NTI P/N: 84010) on the outlet (supply) pipe feeding the
heating system, see Figure 11-1. Wire the system sensor to SENSOR COM and SYSTEM (OD / SYS SENSOR
for Lx500-800 models) of the Master Boiler; see Field Wiring Tables 12-2(a) and 12-2(b) and Figure 12-2.
The system sensor automatically becomes the modulation sensor for the boiler system, i.e. the control attempts
to achieve setpoint temperature at the location of the sensor. If a system sensor is NOT used, at the Master
boiler set the applicable sensor input to Unconfigured as follows:
Configure – Sensor Configuration – S10 (J10-7) sensor [S5 (J8-11) sensor for Lx500-800 models] Outdoor Sensor (Optional) – wire the outdoor sensor to SENSOR COM and OD SENSOR (OD / SYS SENSOR
for Lx500-800 models) of any one of the boilers in the cascade (for Lx500-800 models, outdoor sensor must
be connected to a non-Master boiler); see Field Wiring Tables 12-2(a) and 12-2(b) and Figure 12-2. Note:
only one outdoor sensor is needed for the multiple boiler system.
Modbus Address – assign a unique MB2 Modbus Address to each boiler in the cascade. Access the MB2
Modbus Address setting via the System Identification & Access menu as follows:
Configure – System Identification & Access – MB2 Modbus Address
Master Enable – choose one (and only one) boiler in the cascade to be the Master, this boiler will receive all
control wiring and will be used for setting control parameters (see steps below). On this one boiler, set Master enable equal to Enabled via the Lead Lag Master Configuration menu, accessed as follows:
Configure – Lead Lag Master Configuration – Master enable
Table 11-1 Minimum Pipe Sizes for Multiple Boiler Applications
Page 52
52
Master
Boiler
Trinity Lx│Installation and Operation Instructions Lx Series
Multiple Boiler Lead-Lag Plumbing Configuration
Figure 11-1 All Models
Page 53
53
Lx Series Installation and Operation Instructions│Trinity Lx
Lead Lag Instructions – Central Heating
Central Heat Demand Switch (Room Thermostat) – connect to R (24VAC) and CH2 (LL) of the Master Boiler;
see Field Wiring Tables 12-2(a) and 12-2(b) and Figure 12-2. Switch must be an isolated end switch (dry
contact).
Central Heat Setpoint – at the Master boiler only, set the CH setpoint via the Lead Lag Master Configuration
menu, accessed as follows:
Configure – Lead Lag Master Configuration – CH setpoint
Outdoor Reset Settings – at the Master boiler only, set the Outdoor reset parameters via the Lead Lag Master
Configuration menu, accessed as follows:
Configure – Lead Lag Master Configuration – Advanced Settings – Outdoor reset
CH Pump – one boiler in the cascade can be chosen to operate the Central Heating pump via its PUMP C output;
see Field Wiring Figures and Tables 12-1(a) and 12-1(b). From the respective boiler display, check the box
next to Use for Lead Lag Master demands for the CH Pump to ensure proper pump behavior. Menu access to
the CH Pump parameters is as follows:
Configure – Pump Configuration – Central Heat pump – Use for Lead Lag Master demands
Sensor Configuration (Lx500-800 models only) – at the Master boiler only, set the Outdoor temperature source
equal to Unconfigured, via the Sensor Configuration menu as follows:
Configure – Sensor Configuration – Outdoor temperature source
Lead Lag Instructions – Domestic Hot Water
Tank Thermostat – connect to SENSOR COM and DHW of the Master Boiler; see Field Wiring Tables 12-2(a)
and 12-2(b) and Figure 12-2. Switch must be an isolated end switch (dry contact).
DHW Setpoint – at the Master boiler only, set the DHW setpoint via the Lead Lag Master Configuration menu,
accessed as follows:
Configure – Lead Lag Master Configuration – DHW setpoint
DHW switch (Lead Lag) – at the Master boiler only, set DHW switch equal to DHW (S6) sensor shorted via the
Lead Lag Master Configuration menu, accessed as follows:
Configure – Lead Lag Master Configuration – Advanced Settings – Domestic Hot Water – DHW switch
DHW enable (Local) – at the Master boiler only, set DHW enable equal to Disabled via the Domestic Hot Water
Configuration menu, accessed as follows:
Configure – Domestic Hot Water Configuration – DHW enable
DHW Pump – one boiler in the cascade can be chosen to operate the DHW pump via its PUMP A output; see
Field Wiring Figures and Tables 12-1(a) and 12-1(b). From the respective boiler display, check the box next
to Use for Lead Lag Master demands for the DHW Pump to ensure proper pump behavior. Menu access to the
DHW Pump parameters is as follows:
Configure – Pump Configuration – DHW pump – Use for Lead Lag Master demands
Tank Sensor – when operating in a cascade system, the boiler controls do not support the
use of a tank sensor; a tank thermostat (switch) must be used.
Page 54
54
Trinity Lx│Installation and Operation Instructions Lx Series
12.0 FIELD WIRING
All wiring must be in accordance with the Canadian Electrical code, CSA C22.2 and any applicable local codes.
Ensure that the wiring complies with this manual. The boiler must be electrically grounded in accordance with
the National Electrical Code ANSI/NFPA 70, local codes, and/or the Canadian Electrical Code CSA C22.1.
Avoid Shocks - To Avoid Electrical Shock, turn off electrical power to the boiler prior to
opening any electrical box within the unit. Ensure the power remains off while any
wiring connections are being made. Failure to follow these instructions may result in
component failure, serious injury or death.
Field Wiring - Wire grommets must be used to secure wiring and prevent chafing when
passing wiring through the cabinet wall. Failure to follow instructions may damage unit.
Line Voltage Connections
Electrical rating for the Trinity Lx is 120V/1 Phase/60 Hz/12A. The Trinity Lx line voltage junction box is
located in the lower right corner of the boiler cabinet on models Lx150-200 and can be accessed by removing the
front door of the boiler, followed by the removal of the line voltage junction box cover. On Lx300-400 models,
the line voltage junction box is located at the top of the boiler cabinet on the right hand side and can be accessed
by removing the top front cover of the boiler. On Lx500-800 models, the line voltage junction box is located at
the back of the boiler cabinet on the power switch side. Remove the top back cover of the boiler to access the
three holes / knockouts needed for routing field wiring into the line voltage junction box. Line voltage field
connections are to be installed in accordance with Figures and Tables 12-1(a) and 12-1(b).
Fuses (120VAC) – The Trinity Lx is equipped with either one or two 7 Amp fuses to protect 120VAC system
components. The fast-acting fuses are located on the front of the control panel box and can be easily
accessed from the outside of the control panel.
Lx150-400 Control Panel:
Fuse A: Protects the blower, spark generator and PUMP B output circuits.
Fuse B: Protects PUMP A and PUMP C output circuits.
Lx500-800 Control Panel:
Fuse A: Protects the 120VAC circuits within the boiler.
Pump Relays (Lx500-800) – In lieu of the 120VAC pump outputs, the Lx500-800 incorporates three non-
powered isolation relay contacts for switching high capacity pumps. Contact Secondary Maximum rating is
1.5HP @ 120V, 3.0HP @ 240V, or 30A. Refer to Figure 12-2(b) for Field Wiring requirements.
Wire Protection - When passing any wiring through the cabinet of the boiler, the
installer must use wire grommets suitable for securing the wiring and preventing chafing.
Failure to follow instructions may result in component failure, serious injury or death.
Power Supply - The Trinity Lx is designed to be powered using a single phase 120VAC
power supply that is fused (or protected via a circuit breaker) to allow a maximum of 15
Amps. Failure to follow instructions may result in component failure, serious injury or
death.
Labeling - Label all wires prior to disconnecting them when servicing controls. Wiring
errors can cause improper and dangerous operation. Failure to follow instructions may
result in property damage or personal injury.
Continuity - Before connecting the line voltage wiring, perform a continuity check
between all wires and ground to make sure that there are no electrical leaks that could
blow a fuse or damage electrical components. Also check the polarity of the line and
neutral wires. Line must measure 120VAC to ground; neutral must measure zero.
Failure to follow instructions may damage the unit.
Max Load – Lx150-400 circulator outputs are each limited to operating a circulator with
a maximum current load of 3 Amps or a maximum 1/6 hp motor. See Table 12-1.
Page 55
55
Table 12-1(a) Line Voltage Field Connections (Lx150-400)
Connection
Location
Description
L1
(120VAC)
1
Location for connecting line voltage of the power supply. Note; most installation codes
require the installation of a service switch to break line voltage to the boiler.
PUMP A
2
120VAC output to the DHW circulator; powered during a demand for DHW.
PUMP B
3
120VAC output to the Boiler circulator; powered during all demands; DHW, local Central
Heat (CH1) and Lead-Lag Central Heat [CH2 (LL)]. This output is not used for all
plumbing configurations, see Section 10.0.
PUMP C
4
120VAC output to the Central Heating circulator; powered during a demand for local
Central Heat (CH1) or Lead-Lag Central Heat [CH2 (LL)].
L2
(Neutral)
5
Location for connecting neutral of the power supply and all circulators.
6
Ground
7
Location for connecting earth ground and for grounding all of the circulators.
8
No Conn.
9
This terminal is used only for factory wiring, do not add or remove wires from this
location.
LINE
NEUTRAL
GND
PUMP A
PUMP B
PUMP C
SERVICE SWITCH
(field supplied)
Green
Green
Green
Black
White
White
Black
White
Black
120VAC SUPPLY
Lx Series Installation and Operation Instructions│Trinity Lx
Figure 12-1(a) Line Voltage Field Wiring (Lx150-400)
Page 56
56
Table 12-1(b) Line Voltage Field Connections (Lx500-800)
Connection
Location
Description
L1 (120VAC)
1
Location for connecting line voltage of the power supply. Note, most installation codes
require the installation of a service switch to break line voltage to the boiler.
L2
(Neutral)
2
Location for connecting neutral of the power supply.
Ground
3
Location for connecting earth ground.
Non-Powered
Dry Contacts
PUMP A
4
Dry Contacts for DHW circulator; Coil A powered during a demand for DHW, closing
Pump A relay contacts.
5
PUMP B
6
Dry Contacts for Boiler circulator; Coil B powered during all demands; DHW, local
Central Heat (CH1) and Lead-Lag Central Heat [CH2 (LL)], closing Pump B relay
contacts. This output is not used for all plumbing configurations, see Section 2.0.
7
PUMP C
8
Dry Contacts for Central Heating circulator; Coil C powered during a demand for local
Central Heat (CH1) or Lead-Lag Central Heat [CH2 (LL)], closing Pump C relay contacts.
9
Trinity Lx│Installation and Operation Instructions Lx Series
Figure 12-1(b) Line Voltage Wiring (Lx500-800)
Page 57
57
Connection
Location
Description
COM
(24VAC)
1
24VAC Common – Neutral for the 24VAC power supply from the boiler. COM can be
used in conjunction with terminal R to provide a power source for a digital thermostat.
R
(24VAC)
2
24VAC Hot - Power supply for inputs LIM, CH1, and CH2 (LL).
3
LIM
4
External Limit – Input requiring 24VAC from terminal R to permit the burner to operate.
Comes factory equipped with a jumper to the R terminal. For installations requiring the
use of an additional safety switch, such as a LWCO, Flow Switch, or auxiliary temperature
limit, remove the factory installed jumper and install the normally open isolated contacts of
the additional limit in its place.
CH1
5
Local Central Heat Demand – Input requiring 24VAC from terminal R to initiate a
“local” CH call. Switch is made using an isolated end switch (dry contact) via thermostat,
zone controller or other device. Typically used as the lone heat input or as the high
temperature input in dual CH temperature systems.
CH2 (LL)
6
Lead-Lag Central Heat Demand – Input requiring 24VAC from terminal R to initiate a
“lead-lag” CH call. Switch is made using an isolated end switch (dry contact) via
thermostat, zone controller or other device. Typically used as a lead-lag input for cascaded
boilers or as the low temperature input in dual CH temperature systems.
Sensor
DHW
7
DHW Tank Demand – Input requiring closure of terminals 7 and 10 to initiate a demand
for DHW. Switch made via isolated end switch (dry contact) from a thermostat (Aquastat)
located in an Indirect Fired Water Heater. Or optional Tank Sensor (P/N 84632), see
Appendix A. (NOTICE: tank sensor cannot be used for cascade boiler arrangements).
OD
SENSOR
8
Outdoor Temperature Sensor – A wall mountable OD Sensor is included with each
boiler. When connected to terminals 8 and 10, the control will indicate the outdoor
temperature and adjust the boiler temperature set point during a Central Heat demand.
SYSTEM
9
System Water Temperature – An optional strap-on System Sensor is available from NTI
(P/N 84010). When connected to terminals 9 and 10, the control will indicate a “CH” or
“Lead-Lag” temperature. The control can be set to use the System Sensor as the
Modulation Sensor for a CH1 or Lead Lag demand; see Appendix A.
SENSOR
COM
10
System Common – Common port for field inputs DHW, OD Sensor, System Sensor and
Communication terminals.
4-20mA
11
External Modulation Control – Using a 4-20mA signal, an external control can be used
to directly modulate the burner firing rate or adjust the active set point. This can be useful
for applications using external staging controls or Building Automation Systems.
12
Communications
LL DATA+
13
Lead-Lag – Connects internally to the controller’s MB2, Modbus communication port.
Terminals 13, 14 and 10 (common) can be "daisy-chained" to multiple boilers (up to 8 in
total) for the purpose of staging.
LL DATA–
14
BMS D+
15
Building Management System (BMS) – Connects internally to the display’s COM2,
Modbus communication port. Terminals 15, 16 and 10 (common) can be connected to a
Gateway for communication to a BMS or other device.
BMS D–
16
ALARM
17
Normally Open Alarm Contacts – Contacts close during a lockout or other alarm
condition. May be connected to a BMS, maximum capacity of 0.63Amps at 24VAC.
18
Lx Series Installation and Operation Instructions│Trinity Lx
Low Voltage Connections
The Trinity Lx low voltage junction box is located in the lower left corner of the boiler cabinet on Lx150-200
models and can be accessed by removing the front door of the boiler, followed by the removal of the low voltage
junction box cover. On Lx300-400 models, the low voltage junction box is located at the top of the boiler
cabinet on the left hand side and can be accessed by removing the top front cover of the boiler. On Lx500-800
models, the low voltage junction box is located at the back of the boiler cabinet and can be accessed by
removing the top back cover of the boiler. Each boiler is provided with one hole and two knockouts for routing
field wiring into the low voltage junction box. Low voltage field connections identified in Tables 12-2(a) and
12-2(b) are to be read in conjunction with Figure 12-2.
Table 12-2(a) Low Voltage Field Connections (Lx150-400)
Page 58
58
Connection
Location
Description
COM (24VAC)
1
24VAC Common – Neutral for the 24VAC power supply from the boiler. COM can be
used in conjunction with terminal R to provide a power source for a digital thermostat.
R1/R2 (24VAC)
2
24VAC Hot - Power supply for inputs EXT. LIM, CH1, and CH2 (LL).
3
EXT. LIM
4
External Limit – Input requiring 24VAC from terminals R1/R2 to permit the burner to
operate. Comes factory equipped with a jumper to the R2 terminal. For installations
requiring the use of an additional safety switch, such as a LWCO or auxiliary temperature
limit, remove the factory installed jumper and install the normally open isolated contacts of
the field supplied additional limit in place of jumper.
GAS LO PR.
5
Gas Low Pressure Switch (Optional) – Comes factory equipped with a jumper. For
applications requiring a Low Gas Pressure Switch, remove jumper and connect normally
open isolated contacts of the Gas Low Pressure Switch. Switch must be installed external to
unit (24VAC circuit). For preapproved High Gas Pressure Switch, see Note 1 below.
6
AUX. PROOF
7
Auxiliary Proof – Comes factory equipped with a jumper. For applications using Indoor
Combustion Air, remove jumper and replace with field supplied end switch incorporated
with motorized damper/louver control.
8
CH1
9
Local Central Heat Demand – Input requiring 24VAC from terminal R to initiate a
“local” CH call. Switch is made using an isolated end switch (dry contact) via thermostat,
zone controller or other device. Typically used as the lone heat input or as the high
temperature input in dual CH temperature systems.
CH2 (LL)
10
Lead-Lag Central Heat Demand – Input requiring 24VAC from terminal R to initiate a
“lead-lag” CH call. Switch is made using an isolated end switch (dry contact) via
thermostat, zone controller or other device. Typically used as a lead-lag input for cascaded
boilers or as the low temperature input in dual CH temperature systems.
Sensor
DHW
11
DHW Tank Demand – Input requiring closure of terminals 11 and 14 to initiate a demand
for DHW. Switch made via isolated end switch (dry contact) from a thermostat (aquastat)
located in an Indirect Fired Water Heater. Or optional Tank Sensor (P/N 84632), see
Appendix A. (NOTICE: tank sensor cannot be used for cascade boiler arrangements).
OD / SYS
SENSOR
12
Outdoor Temperature Sensor – A wall mountable OD Sensor is included with each
boiler. When connected to terminals 12 and 14, the control will indicate the outdoor
temperature and adjust the boiler temperature set point during a Central Heat demand.
System Water Temperature – An optional strap-on System Sensor is available from NTI
(P/N 84010). When connected to terminals 12 and 14, the control will indicate a “LeadLag” temperature. By default, the System Sensor becomes the Modulation Sensor for a
Lead Lag demand.
NOTICE: only one sensor can be connected to terminal 12 (System OR Outdoor Sensor);
see instructions in Appendix A.
TOD
13
Time of Day (Night Time Setback) – Input requiring closure of terminals 13 and 14 to
initiate TOD setback setting. Switch is made using an isolated end switch (dry contact)
using a timer, BAS or other device. [TOD applicable to and available on Lx500-800 only]
SENSOR
COM
14
System Common – Common port for field inputs DHW, OD Sensor and System Sensor.
4-20mA (– / +)
15
External Modulation Control – Using a 4-20mA signal, an external control can be used
to directly modulate the burner firing rate or adjust the active set point. This can be useful
for applications using external staging controls or Building Automation Systems.
16
Communications
LL DATA+
17
Lead-Lag – Connects internally to the controller’s MB2, Modbus communication port.
Terminals 17, 18 and 14 (common) can be "daisy-chained" to multiple boilers (up to 8 in
total) for the purpose of staging.
LL DATA–
18
BMS D+
19
Building Management System (BMS) – Connects internally to the display’s COM2,
Modbus communication port. Terminals 19, 20 and 14 (common) can be connected to a
Gateway for communication to a BMS or other device.
BMS D–
20
ALARM (A&B)
21
Normally Open Alarm Contacts – Contacts close during a lockout or other alarm
condition. May be connected to a BMS, maximum capacity of 0.63Amps at 24VAC.
22
Notes
1
For applications requiring a High Gas Pressure Switch, see supplemental instructions included with NTI High Gas
Pressure Switch Kit, P/N 84094. Note that this is the only High Gas Pressure Switch that has been tested with the unit
and preapproved for field installation within the boiler cabinet.
Trinity Lx│Installation and Operation Instructions Lx Series
Table 12-2(b) Low Voltage Field Connections (Lx500-800)
Page 59
59
Lx Series Installation and Operation Instructions│Trinity Lx
Low Voltage Terminals -Terminals 2 and 3 (R) have 24VAC potential from the internal
transformer. Do not connect power from these terminals to any other terminal other than
terminals 4, 5 and 6 [LIM, CH1, and CH2 (LL)]. Failure to follow these instructions may
damage the unit.
Fuse (24VAC) - Trinity Lx150-400 models are equipped with a “blade style” 2 Amp
fuse to protect the internal transformer located within the slide-out control panel box.
Figure 12-2 Low Voltage Field Wiring (All Models)
Lx150-400 Illustrated
Page 60
60
Figure 13-1(a) Connection Diagram (Lx150-400)
Trinity Lx│Installation and Operation Instructions Lx Series
13.0 WIRING SCHEMATICS
Page 61
61
Figure 13-1(b) Ladder/Logic Diagram (Lx150-400)
Lx Series Installation and Operation Instructions│Trinity Lx
Page 62
62
Figure 13-2(a) Connection Diagram (Lx500-800)
Trinity Lx│Installation and Operation Instructions Lx Series
Page 63
63
Figure 13-2(b) Ladder/Logic Diagram (Lx500-800)
Lx Series Installation and Operation Instructions│Trinity Lx
Page 64
64
Trinity Lx│Installation and Operation Instructions Lx Series
14.0 INSTALLATION CHECKLIST
Installation
1. If operating on Propane Gas, convert boiler using appropriate Kit number. See Table 7-1.
2. Locate the boiler in accordance with Section 3.0 of this manual.
3. Install the Vent/Air-inlet piping in accordance with Sections 4.0 and 5.0 of this manual. Ensure all joints
are secured and cemented properly. Perform the Mandatory Pre-commissioning Procedure for Plastic
Venting in Section 4.0.
4. Connect the condensate drain in accordance with Section 6.0 of this manual.
5. Connect the gas supply in accordance with Section 7.0 of this manual.
6. Install the plumbing in accordance with the appropriate this Manual. Flush/cleanse the internals of the
heating system. Treat system water with Fernox F1 Protector. See Table 10-1.
7. Connect field wiring in accordance with Section 12.0 of this manual.
8. Advise home/building owner of their responsibilities with respect to maintaining the boiler.
The building owner is responsible for keeping the Vent/Air-inlet termination free of snow,
ice, or other potential blockages and for scheduling routine maintenance on the boiler (see
Section 15.0). Failure to properly maintain the boiler may result in serious injury or death.
Start-up
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8
hours,first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.Failure to follow these instructions can result in explosion,
1. Turn gas shut-off valve to the ON position.
2. Turn Power on to boiler.
3. Set Controller to the desired settings.
4. Turn thermostat up, Ignition will occur.
Operational Checklist
1. System is free of gas leaks.
2. System is free of water leaks.
3. Water pressure is maintained above 15 PSI.
4. All air is purged from the heating system piping.
5. Ensure proper water flow rate; unit must not kettle, bang, hiss or flash the water to steam.
6. Ensure gas line pressure is in accordance with Section 9.0.
7. System is free of combustion leaks.
8. Unit must operate smoothly.
9. Ensure the flue gas combustion readings are within the tolerances listed in Table 9-1.
10. Each ignition must be smooth.
11. Verify that all condensate lines are clean and drain freely.
Before Leaving
1. Remove line pressure gauge from gas valve, tighten bleed screw, test screw for leaks. See Section 9.0.
2. Install plug into the flue gas test port and test for leaks, see Section 9.0.
3. Allow the boiler to complete at least one heating cycle, or to operate for at least 15 minutes.
4. Always verify proper operation after servicing.
Instructions to Installing Contractor
1. Ensure that the customer receives the Warranty Documentation included with the installation manual.
2. Leave the manual with the customer so they know when to call for annual maintenance and inspection.
serious injury or death.
This boiler must have water flowing through it whenever the burner is firing. Failure to
comply may damage the unit, void the warranty, and cause serious injury or death.
Allowing the boiler to operate with a dirty combustion chamber will adversely affect its
operation and void the warranty. Failure to clean the heat exchanger on a frequency that
matches the need of the application may result in fire, property damage, or death.
Page 65
65
Lx Series Installation and Operation Instructions│Trinity Lx
15.0 ANNUAL MAINTENANCE AND INSPECTION
This unit must be inspected at the beginning of every heating season by a Qualified Technician.
Annual Inspection Checklist
1. Lighting is smooth and consistent, and the combustion fan is noise & vibration free.
2. The condensate freely flows from the unit, and is cleaned of sediment.
3. Relief Valve and air vents are not weeping.
4. Low water cut off is flushed (if applicable)
5. Examine all venting for evidence of leaks. Ensure vent screens are cleaned and clear of debris.
6. Check the burner plate for signs of leaking.
7. The combustion chamber must be inspected and cleaned.
8. Listen for water flow noises indicating a drop in boiler water flow rate.
The hydronic system may need to be flushed to eliminate hard water scale
(Use Fernox DS-40 Descaler, NTI PN: 83450; see Table 10-1).
Combustion Chamber Cleaning Procedure
Units operating with LP Gas or in an industrial environment will have to be cleaned a minimum of once per year.
Other applications will require the combustion chamber to be cleaned after the first year of operation, with
subsequent cleanings scheduled based on the condition of the combustion chamber at the time. Unless a step is
identified as model specific, the following combustion chamber cleaning procedure is the same for all models.
Crystalline Silica - Read carefully the warnings and handling instructions pertaining to
Refractory Ceramic Fibers before commencing any service work in the combustion
chamber. Take all necessary precautions and use recommended personal protective
Cleaning Checklist
1. Initiate a post-purge cycle to clear any gas from the combustion chamber, then turn gas valve off.
2. Danger Explosion Hazard (Lx300-800): To disconnect the fuel-air metallic tubing between the blower
and the high-vent pressure switch, loosen the compression fitting at the high-vent pressure switch with a
1/2" wrench. At the blower end, support the brass fitting body with a 1/2" wrench to keep it from rotating
while loosening the compression fitting nut with a 9/16" wrench. Remove tubing assembly from blower.
3. Access the combustion chamber by removing the aluminum burner door assembly of the boiler.
4. Remove (or cover) the insulation disc located in the back of the combustion chamber to avoid damaging
it during the cleaning process. The disc is held in place with a 2.5mm "Allen-head" screw.
5. Use a vacuum with a high efficiency filter to remove any loose debris or dust.
6. Wet the inside of the combustion chamber with water. Use a garden hose with a trigger nozzle to direct
pressurized water through the gaps between the heat exchanger tubes. The water should pass in-between
the heat exchanger tubes and exit via the condensate drain. This process may require the use of some dry
rags or plastic to protect electrical components from being damaged by dripping or spraying water.
7. Use a nylon or other non-metallic brush to loosen the incrustations and any other contaminates that have
remained stuck on and in-between the tubes.
8. Repeat steps 6 and 7 until the heat exchanger is clean and water from the condensate drain runs clear.
9. Re-install the insulation disc to the back of the combustion chamber (see Table 16-1, Item 31 for part #).
10. Inspect the insulation disc located on the back-side of the burner door. Replace if damaged (see Table 16-
1, Item 33 for part # by applicable model).
11. Re-install the burner door, gas-supply and Air-inlet pipe, check for gas leaks.
12. Lx300-800: Reconnect the fuel-air metallic tubing between the blower and the high-vent pressure switch.
Ensure the brass fitting body at the blower remains stationary and does not rotate during reconnection.
13. Perform the Operational Check List detailed in Section 14.0.
Chamber Cleaning Procedure for instructions on connecting and disconnecting the metallic tubing. Failure to
follow these instructions will result in serious injury or death.
equipment as required.
Explosion Hazard (Lx300-800) - The fuel-air metallic tubing connecting the blower and
the high-vent pressure switch contains a mixture of fuel and air. Refer to Combustion
Replace any gaskets or insulation discs that show any signs of damage and do not re-use.
Failure to follow these instructions may result in fire, property damage or death.
Page 66
66
Reduce the Risk of Exposure
Precautions and Recommended Personal Protective Equipment
Avoid contact with skin and eyes
Wear long-sleeved clothing, gloves, and safety goggles or glasses.
Avoid breathing in silica dust
Wear a respirator with a N95-rated filter efficiency or better. 1
Use water to reduce airborne dust levels when cleaning the combustion chamber.
Do not dry sweep silica dust. Pre-wet or use a vacuum with a high efficiency filter.
Avoid transferring contamination
When installing or removing RFCs, place the material in a sealable plastic bag.
Remove contaminated clothing after use. Store in sealable container until cleaned.
Wash contaminated clothing separately from other laundry.
First Aid Measures
If irritation persists after implementing first aid measures consult a physician.
Skin - Wash with soap and water.
Eyes - Do not rub eyes; flush with water immediately.
Inhalation – Breathe in fresh air; drink water, sneeze or cough to clear irritated
passage ways.
Notes:
1
Respirator recommendations based on CCOHS and OSHA requirements at the time this document was written. Consult
your local regulatory authority regarding current requirements for respirators, personal protective equipment, handling,
and disposal of RCFs.
For more information on Refractory Ceramic Fibers, the risks, recommended handling procedures and
acceptable disposal practices contact the organization(s) listed below:
Canada (CCOHS): Telephone directory listing
under Government Blue Pages Canada—Health and
Safety—Canadian Centre for Occupational Health
and Safety; or website http://www.ccohs.ca.
United States (OSHA): Telephone directory listing
under United States Government—Department of
Labor—Occupational Safety and Health
Administration; or website http://www.osha.gov.
Trinity Lx│Installation and Operation Instructions Lx Series
Refractory Ceramic Fibers (RFC)
chamber. The insulating material on the inside of the burner door and at the back of the combustion chamber
contains Refractory Ceramic Fibers and should not be handled without personal protective equipment.
(cristobalite), a respirable silica dust. Repeated airborne exposure to crystalline silica dust may result in chronic
lung infections, acute respiratory illness, or death. Crystalline silica is listed as a (potential) occupational
carcinogen by the following regulatory organizations: International Agency for Research on Cancer (IARC),
Canadian Centre for Occupational Health and Safety (CCOHS), Occupational Safety and Health Administration
(OSHA), and National Institute for Occupational Safety and Health (NIOSH). Failure to comply with handling
instructions in Table 15-1 may result in serious injury or death.
maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to
Table 15-1 for handling instruction and recommended personal protective equipment. Installation and service
must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the
supplied instructions before installing, servicing, or removing this boiler. This boiler contains materials that have
been identified as carcinogenic, or possibly carcinogenic, to humans).
Table 15-1 Handling Instructions for Refractory Ceramic Fibers (RCF)
Personal Protective Equipment Recommended - Read the following warnings and
handling instructions carefully before commencing any service work in the combustion
Potential Carcinogen - Use of Refractory Ceramic Fibers in high temperature
applications (above 1000oC) can result in the formation of Crystalline Silica
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or
Page 67
67
Figure 16-1 Cabinet, Vent and Air-inlet Parts (Lx150-200)
44
41
43
45
40
38
39
50
49
48
46
47
72
73
75
66
53
55
64
37
Lx Series Installation and Operation Instructions│Trinity Lx
16.0 PARTS LIST
For a list of parts that corresponds to the item numbers in the bubbles, refer to Table 16-1. Note that that some
item numbers may appear more than once in the parts list depending on which model number is being referenced.
Building Owners - Replacement parts are available from your stocking wholesaler. Contact your local Installer
or Wholesaler for assistance with parts.
Wholesalers - Contact NY Thermal Inc. directly when ordering replacement parts, 1-506-657-6000.
Installers - Contact NY Thermal Inc. directly if technical assistance required, 1-800-688-2575.
Residential Models (Lx150-400)
Page 68
68
Figure 16-2 Heat Exchanger, Gas Valve, Blower and Burner Assembly (Lx150-200)
Figure 16-3 Electrical Housing, Controller, and Display Module (Lx150-400)
56
58
57
52
70
59
62
71
61
63
69
58
60
67
81
68
51
54
65
58
10
11
5 6 7 8 20
19
18
17 9 15
4
14
16 3 29
36
11
34
32
33
31
28
30
27
23
25
21
26
1 2 22
24
13
105
12
Trinity Lx│Installation and Operation Instructions Lx Series
Page 69
69
Figure 16-4 Cabinet, Vent and Air-Intake Parts (Lx300-400)
44
42
39
50
49
46
47
72
73
75
48
37
76
78
77
45
41
Lx Series Installation and Operation Instructions│Trinity Lx
Page 70
70
Figure 16-5 Heat Exchanger, Gas Valve, Blower and Burner Assembly (Lx300-400)
10 2 36
3
5
6
11
34
33
31
28
24
25
19
18
17
15
4
35
13
13
14
4
1
20
26
32
30
29
79
8
7
9
105
Reverse
Angle View
16
114
106
Trinity Lx│Installation and Operation Instructions Lx Series
Page 71
71
Figure 16-6 Cabinet, Vent and Air-inlet Parts (Lx500-800)
76
77
73
72
95
95
95
95
78
101
101
42
98
49
48
96
96
47
46
47
74
100
99
104
75
104
97
41
41
Lx700-800
(Elbow)
Lx500-600
(c/w Tabs)
44
Lx500-600
Flue Adapter
41
Lx Series Installation and Operation Instructions│Trinity Lx
Commercial Models (Lx500-800)
Page 72
72
Figure 16-7 Heat Exchanger, Gas Valve, Blower and Burner Assembly (Lx500)
5
36
11
10
11
32
34
31
33
14
87
89
86
88
20
19
25
15
24
26
93
29
28
4
2
1
80
Reverse
Angle View
3
114
115
18
92
91
106
30
9
Trinity Lx│Installation and Operation Instructions Lx Series
Page 73
73
Figure 16-8 Heat Exchanger, Gas Valve, Blower and Burner Assembly (Lx600-800)
80
1
6 2 4 5 7
9
36
11
10
11
32
34
31
33
14
14
89
90
86
89
20
19
25
15
24
30
85
26
93
13
13
92
91
83
29
14
18
84
87
3
88
94
86
82
94
86
90
89
9
14
13
14
13
87
89
89
Lx700-800
Gas Train
Lx600
Gas Train
28
Reverse
Angle View
44
106
89
114
Lx Series Installation and Operation Instructions│Trinity Lx
Page 74
74
Figure 16-9 Electrical Housing, Controller, and Display Module (Lx500-800)
Item
Part #
Models
Description
1
82657
150
Premix burner 135.8 (Lx100-150; not Lx150E)
1
82658
150E, 200
Premix burner, 200.6 (Lx150E, Lx200)
1
84207
300
Premix burner, (Lx300)
1
83338
400, 500
Premix burner (Lx400-500)
1
84383
600
Premix burner (Lx600)
1
84134
700, 800
Premix burner (Lx700-800)
2
82761
150–500
Premix Burner Gasket (Lx150-500)
2
84133
600–800
Premix Burner Gasket (Lx600-800)
3
82771
150, 150E, 200
Extended Air Tube (Lx100-200)
3
83195
300–500
Extended Air Tube (Lx300-500)
3
84132
600, 700, 800
Conical Air-Gas Inlet Pipe / Stabilor (Lx600-800)
4
82766
150–500
Blower Gasket (Lx150-500)
4
84026
600–800
Blower Gasket (Lx600-800)
5
82052
150
EBM Blower RG130 (Lx100-150, not Lx150E)
5
82661
150E, 200, 300
EBM Blower RG148/1200-3633 (Lx150E-300)
5
82994
400
EBM Blower RG148/Enhanced (Lx400)
5
84322
500
EBM Blower NRG137 (Lx500)
5
84006
600–800
EBM Blower G1G170 (Lx600-800)
6
82054-2
150, 150E, 200, 300
CVI Venturi Gasket (Lx150-300)
6
83106
400
O-ring, Venturi to Blower (Lx400)
6
84084
600–800
O-ring, Venturi to Blower (Lx600-800)
7
82054-1
150, 150E, 200
CVI Venturi 01 (Lx150-200)
51
52
57
56
81
71
70
68
69
60
61
59
62
63
58
65
54
103
58
102
102
102
70
58
58
58
Trinity Lx│Installation and Operation Instructions Lx Series
Table 16-1 Parts List: Trinity Lx
Page 75
75
Item
Part #
Models
Description
7
81994
300
CVI Venturi 51 (Lx300)
7
82990
400
CVI Venturi (Lx400)
7
84013
600–800
CVI Venturi (Lx600-800)
8
82650
150, 150E, 200
CVI 5.20mm Orifice #45.900.444.107B (Lx150-200)
8
84157
300
CVI 6.20mm Orifice (Lx300)
8
82993
400 (NG)
Gas Valve Orifice, 8.0mm, NG (Lx400)
8
83017
400 (LP)
Gas Valve Orifice, 6.2mm, LP (Lx400)
9
82054
150–300
Gas Valve (CVI) VK8115F1134B (Valve Only) (Lx150-300)
9
82989
400
Gas Valve VR8615VB 1044B (Lx400)
9
84318
500
Gas Valve GB-ND 057 (Lx500)
9
84012
600–800
Gas Valve V8730C 1023B (Lx600-800)
10
83870
150–500
Ignition Electrode, Dual – c/w gasket (Lx150-500)
10
84154
600–800
Ignition Electrode, Dual (Lx600-800)
11
82774
All Models
Flame Probe Gasket (Lx Series)
12
82600
150, 150E, 200, 300
Gas Valve Regulator Vent Adapter (Lx150-300)
13
83883
150, 150E, 200, 300
CVI Gas Valve Inlet O-ring Gasket (Lx150-300)
13
83194
400
Gas Valve Connector O-ring, Large (Lx400)
13
84138
600–800
Gas Valve Inlet O-ring (Lx600-800)
14
82065
150, 150E, 200, 300
Gas Valve (CV1) 1/2" NPT elbow #45.900.400-132B (Lx150-300)
14
82991
400
Gas Valve Adapter 45900400-138B, 3/4" NPT (Lx400)
14
84321
500
Gas Valve Adapter 253-517, 3/4” NPT, c/w screws and O-ring (Lx500)
14
84035
600–800
Gas Valve Adapter, 1" NPT (Lx600-800)
15
83606
All Models
Outlet Sensor, Dual (Lx Series)
16
83223-1
150, 150E, 200, 300, 400
Low Water Pressure Switch, 1/4" NPT (Lx150-400)
17
83462
150, 150E, 200
Street Tee, Brass, 1/4" (Lx150-200)
17
82698
300, 400
1/4" NPT Brass Tee (Lx300-400)
18
83007
All Models
1/4"x 1/8" Bushing Brass (Lx Series)
19
82539
All Models
Automatic Air Vent 1/8" (Lx Series)
20
83608
150, 150E, 200, 300, 400
Flue Sensor, Dual (Lx150-400)
20
84039
500–800
Flue Sensor, Dual (Lx Commercial)
21
82765
150, 150E, 200
Composite Flue Outlet Gasket (Lx150-200)
22
82763
150, 150E, 200
Composite Flue Box (Lx150-200)
23
82764
150, 150E, 200
Trinity Flue Box to Heat Exchanger Gasket (Lx150-200)
24
83605
All Models
Inlet Sensor, Single (Lx Series)
25
83706
150, 150E, 200, 300, 400
Plug, Brass, 1/4" NPT (Lx150-400)
25
84075
500–800
Plug, Brass, 1/2" NPT (Lx Commercial)
26
83395
150 (CAN)
Heat Exchanger (CAN - Lx100-150, not Lx150E) – Canada Only
26
83012
150 (US)
Heat Exchanger-ASME (US - Lx100-150, not Lx150E) – US Only
26
83396
150E, 200
Heat Exchanger-ASME (Lx150E-200)
26
84022
300
Heat Exchanger-ASME (Lx300)
26
82926
400
Heat Exchanger-ASME (Lx400)
26
84311
500
Heat Exchanger-ASME (Lx500)
26
84312
600
Heat Exchanger-ASME (Lx600)
26
84005
700, 800
Heat Exchanger-ASME (Lx700-800)
27
83042
150, 150E, 200
Y-Drain Fitting 5/8", White (Lx150-200)
28
83721
All Models
Tee, PVC, 1/2", Sch.40, White (Lx Series)
29
83720
All Models
Elbow, Street, PVC, 1/2", Sch.40, White (Lx Series)
30
83715
150, 150E, 200
Condensate Drain Tube (Lx150-200)
30
83907
300, 400
Condensate Drain Tube (Lx300-400)
30
84313
500, 600
Condensate Drain Tube (Lx500-600)
Lx Series Installation and Operation Instructions│Trinity Lx
Trinity Lx│Installation and Operation Instructions Lx Series
Page 79
79
Lx Series Installation and Operation Instructions│Trinity Lx
17.0 TROUBLESHOOTING
Servicing the Boiler
Disconnect or shut off all energy sources to the boiler: 120VAC power, water and gas.
Identify and mark wires before disconnecting or removing them.
Never bypass electrical fuses or limit devices except temporarily for testing.
Use proper personal protective equipment (PPE) i.e. eye protection, safety footwear.
These procedures should only be performed by qualified service personnel, when abnormal operation of the
boiler is suspected. The boiler incorporates a sophisticated microprocessor based control which normally
responds appropriately to varying conditions. If the boiler operation appears to be incorrect, or it is not
responding at all to a demand for heat, the following is suggested to determine and correct the problem.
Check 120VAC and 24VAC at the Boiler
First, verify the following:
There is 120V being supplied to the boiler:
o The circuit breaker in the electrical panel supplying power to the boiler is not tripped.
o The service switch (if applicable) is in the ON position.
There is a heat call from the thermostat:
o Verify 24VAC to thermostat.
o The thermostat is placed at a sufficiently high setting to create a call for heat to the boiler.
To check for the presence of 120VAC and 24VAC at the boiler follow this procedure:
Remove the boiler front cover.
120VAC
oRemove the Line Voltage junction box cover. First remove the #10 pan-head Phillips screw securing the
cover to the junction box. Lift the cover to release it from the boiler base and withdraw the cover from
the boiler cabinet. This will expose the Line Voltage barrier strip.
oWith an AC voltmeter set on the appropriate scale, measure the voltage across the L1 and L2 terminals
(terminals 1 and 5).
oIf 120VAC is not detected, check the electrical service as suggested above. If the service is verified,
inspect the circuit wiring from the panel to the boiler for broken or disconnected conductors.
24VAC (only check if 120VAC supply is verified).
oRemove the Low Voltage junction box cover. First remove the #10 pan-head Phillips screw securing the
cover to the junction box. Lift the cover to release it from the boiler base and withdraw the cover from
the boiler cabinet. This will expose the Low Voltage barrier strip.
oWith an AC voltmeter set on the appropriate scale, measure the voltage across the R and C terminals
(terminals 3 and 1).
oIf 24VAC is not detected, check Fuse "C" (see below).
Observe the following precautions when servicing the boiler. Failure to comply with
these may result in fire, property damage, serious injury or death.
Before undertaking any troubleshooting procedures it is highly recommended to have
available a digital multimeter(s) capable of measuring AC and DC volts, Amperes,
Resistance (ohms) and Continuity.
Page 80
80
Figure 17-1(a) Lx150-400
Figure 17-1(b) Lx500-800
Control Panel Fuse Locations
Control Panel Fuse Location
Fuse “C” ATO
2A 32V Auto
Blade Type
Fuse “A” 3AG
7A 250V
Fast-Acting
Fuse “B” 3AG
7A 250V
Fast-Acting
Fuse “A” 3AG
7A 250V
Fast-Acting
Trinity Lx│Installation and Operation Instructions Lx Series
Fuses
There are three (3) fuses associated with the Trinity Lx150-400 controller but only one (1) with the Lx500-800
controller. Check these fuses before replacing the controller or any other electrical component; if the fuse is
blown, it will prevent the protected device(s) from functioning.
To check, and if necessary replace, the fuses:
Remove all 120VAC power from the boiler. Be careful to check that the unit is not powered from more than
one source e.g. a UPS (uninterruptible power supply).
Remove the front cover.
On models Lx150-400 the control panel is located below the heat exchanger. Fuses "A" and "B" are
accessible by removing the spring-loaded knurled knob of their respective holders. Push the knob toward
the panel, and twist approximately 1/4 turn counter-clockwise.
To access Fuse "C", remove the two #10 pan-head Phillips screws and lift the top cover from the panel. The
auto blade type fuse is installed in an "inline" style fuse holder.
On models Lx500-800, the control panel is located above the heat exchanger toward the back of the unit.
Fuse "A" is accessible by removing the spring-loaded knurled knob from its holder. Push the knob toward
the panel, and twist approximately 1/4 turn counter-clockwise.
After inspecting and if necessary replacing fuses, replace the panel cover and front cover. Restore power to the
boiler and confirm proper operation.
Only replace fuses with identical parts, see Figures 17-1(a) and (b). Failure to follow
this warning may result in component failure, fire, property damage, serious injury or
death.
Lx Series Installation and Operation Instructions│Trinity Lx
User Interface (Touch-screen Display)
A blank screen does not necessarily indicate a problem; the display may be configured to automatically blank the
screen after a pre-set interval. Simply touch the screen to activate it. Confirm that 120V power is being supplied
to the boiler. If the screen does not become active, perform the following procedure:
Blank Screen
1. Remove the front cover from the boiler.
2. Remove the control panel cover and check Fuse “C” (Auto Blade Type); if faulty check for shorts in the
thermostat wiring, correct, then replace fuse (see Figure 17-1).
3. Ensure the “2 by 2” Molex connector, located behind the display at the top, is connected and that the wires
are fully inserted (see Figure 17-2). Verify that 24VAC is present between the Blue and Red wires; if not
trace wiring back to 24VAC transformer; correct wiring and/or replace transformer [see applicable Figure
13-1(a) or 13-2(a)].
4. Remove the display assembly from the control panel and check the 24VAC wiring connection on the back of
the display; Blue to terminal 7 [24VAC (COM)], Red to terminal 8 [24VAC].
System Disconnected
If the Touch-screen Display is not blank, but is displaying “System Disconnected!” in the middle of the screen,
ensure the 4 by 1 Molex connector, located behind the display at the top, is connected and that the wires are fully
inserted (see Figure 17-2). If the connector appears to be fine, check the wiring connections on the back of the
touch-screen display; Green, Red and Black go to terminals 1, 2 and 3 respectfully.
DO NOT drop the plastic housing or allow it to swing down freely, it may be damaged
by forceful impact.
Page 82
82
Table 17-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Display shows “System
Disconnected” constantly
Communication wire disconnected
See, “System Disconnected!” above.
Faulty Sola controller
If 24VAC present at controller terminals J8 1 & 2,
check Power LED on controller. Verify that
connector J8 is securely plugged into the
controller. Recycle power to boiler, if controller
does not operate, replace the controller.
Burner not operating
Heat demand satisfied; no call for
heat
Check Demand and Set points via Touchscreen.
Check thermostat and DHW aquastat (if
applicable) setting.
Boiler outlet temperature exceeds
“Setpoint - On Hysteresis”
Check outlet temperature, setpoint and hysteresis
settings via Touchscreen.
Hold delay or Lockout
Check Summary page on Touchscreen for code.
Burner switch off
Check Summary page, if Demand indicates
“Burner switch off” go to diagnostics burner test
page and switch on.
Lockout 2 – Waiting for
safety data verification
Safety parameter(s) has been
adjusted
Changing settings that are considered safety
parameters require “Safety data verification”.
Refer to Appendix A.
Lockout 9 – Flame bias out of
range
4-20mA input being overdriven.
If using 4-20mA input, check to ensure current is
not greater than 21mA.
Control malfunction
Cycle power, if problem returns replace control.
Hold 27 – Flame rod shorted
to ground detected
A flame circuit shorted to ground
may show up as a flame circuit
timeout. Zero-ohm shorts can
display as Hold 27.
Check to ensure condensate drain is not blocked.
Check to ensure no voltage applied to R & T
terminals. If using 4-20mA input, check to ensure
current is not greater than 21mA.
Hold 61 – Anti short-cycle
Demand off
Check demand. Delay is to prevent rapid cycling
of burner.
Hold 62 – Fan speed not
proved
Normal Operation (Drive to
Lightoff)
Hold 62 is momentarily displayed prior to burner
ignition during the Drive to Lightoff.
Blown fuse
Check Fuse "A", blown fuse prevents blower
from operating.
Wiring defect
Inspect blower wiring, ensure connectors at Sola
controller and blower are securely attached.
- Faulty Sola controller
- Faulty Blower
If Hold 62 persists for 15 seconds or more, while
the blower is running, check "Fan speed"
indicated on display. If "LOW RPM", "HIGH
RPM", “0” or rapidly changing RPM value is
displayed, try connecting another Sola controller.
If problem remains, replace blower.
Trinity Lx│Installation and Operation Instructions Lx Series
Summary and Diagnostics Display – The Trinity Lx controller and Touchscreen display provides detailed
operational and diagnostic information for aid in troubleshooting. When power is applied to the boiler the
initial page displayed is the Summary page. Information presented on the Summary page includes Demand
source, Burner state, status of sensors and pumps, and so forth. Any current Alert or Lockout condition is also
displayed. Accessible from the Summary page are the Diagnostics pages. Refer to the controller manual for
more information.
Lockout and Alert History – The controller maintains a record of the fifteen (15) most recent events for both
Lockouts and Alerts. To display the logs, touch the History button on the Summary page (refer to Section 7.0
in Appendix A - Controller and Touchscreen Display Instructions). In any situation where malfunction is
suspected, always check the Alerts and Lockouts history. Entries recorded in the history provide useful
information for determining the cause of the malfunction.
Page 83
83
Table 17-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Hold 63 – LCI OFF (Limit
control input)
Replacement control incorrectly
configured.
LCI must be set to “enable” on all Lx models,
excluding Lx150/150E units with a serial number
of 49351 or lower and Lx200/400 units with a
serial number of 48251 or lower. See instructions
included with replacement controller.
Lockout or Hold 65 –
Interrupted Air Switch OFF
No problem, normal operation
Hold 65 will normally be displayed momentarily
during the drive to light-off.
Blown fuse
Check Fuse "A", blown fuse prevents blower
from operating.
Faulty blower
If Fuse “A” is good and blower remains off, check
120VAC supply to blower, if present replace
blower. If blower is on proceed to next step.
Blocked venting
Check for blockage of the exhaust vent.
Blocked air inlet
Check for blockage of the air inlet.
Disconnected, damaged or blocked
tubing
Inspect the clear vinyl tubing connecting the air
switch + and – ports to the air metering elbow.
Condensation or other foreign matter may be
obstructing the tubing, preventing the switch from
sensing differential pressure caused by air flow
through the metering elbow.
Incorrect air switch setting
Contact NTI technical support.
Faulty air proving switch
If venting and air inlet are clear, temporarily
jumper the air switch. If the unit lights and
operates smoothly – replace air switch. If the unit
fails to light or lights but runs rough or abruptly
shuts down – check boiler internals for blockage.
WARNING Only jumper the air switch for
diagnosing purposes.
Tripped High Vent Pressure Switch
(Lx300-400 only)
The high vent pressure switch will trip when the
combustion chamber is blocked. Clean
combustion chamber and reset switch.
Tripped Thermal Fuse
(Lx300-400 only)
Check Thermal Fuse on the back of the heat
exchanger (accessed from the rear of the cabinet).
If tripped contact NTI.
Tripped Door Reset Safety Switch
(Lx300-800 only)
The Door Reset Safety Switch will trip with the
combustion chamber gets dirty or the door
insulation fails. Clean the combustion chamber,
inspect the door insulation and reset the switch.
Incorrect air switch wiring
Check that the red and orange wires are connected
to quick connect tabs 3 and 1 respectively.
Hold 66 – Interrupted air
switch ON (and blower is off)
Incorrect air switch setting
Contact NTI technical support.
Incorrect air switch wiring
Check that the red and orange wires are connected
to quick connect tabs 3 and 1 respectively.
Faulty air switch
Disconnect red and orange wires from air switch
and check for open circuit between terminals 1 &
3. If continuity detected, replace air switch.
Hold 66 – Interrupted air
switch ON (and blower is on)
- Blower problem
- Faulty controller
Check low voltage wiring from blower to
controller. Check VDC signal from red–green
and black-green; if not 28-32VDC and 0 VDC
respectfully – replace controller. If signal is
correct – replace blower.
Lx Series Installation and Operation Instructions│Trinity Lx
Page 84
84
Table 17-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Lockout or Hold 67 – ILK
OFF
Insufficient water pressure (Lx150400 only)
Ensure at least 15PSI at boiler outlet. Refer to
Supplementary Documentation section 2.0 System
Piping.
External Limit Tripped
Indication that an external limit (wired to “LIM”)
is open. Not a problem with boiler, check
external limit.
Insufficient flow for Flow Switch
(Lx500-800 only)
Check plumbing, ensure circulator is operating.
Tripped Thermal Fuse (Lx500-800
only)
Check Thermal Fuse on the back of the heat
exchanger (accessed from the rear of the cabinet).
If tripped contact NTI.
Tripped High Vent Pressure Switch
(Lx500-800 only)
The high vent pressure switch will trip when the
combustion chamber is blocked or venting is too
restrictive. Check venting and clean combustion
chamber.
Lockout or Hold 79 – Outlet
High Limit
CH or DHW settings
Check if CH and/or DHW setpoint temperature
plus off hysteresis exceed “High limit” setpoint –
factory setting = 210°F (99°C).
CH or DHW pump problem
See "Inoperative CH or DHW pump" below.
Incorrect “Outlet high limit” setting
Increase “Outlet high limit” setting; maximum
setting = 210°F (99°C).
Incorrect “Outlet high limit
response” setting (Lx150-400 boiler
applications only)
Unless deemed unacceptable by local installation
codes, the “Outlet high limit response” should be set to “recycle and hold” to prevent lockout.
Lockout or Hold 81 – Delta T
limit
OR
Boiler making banging or
hissing sounds
Insufficient water flow
Check Fuse "A"
Check boiler pump.
Ensure plumbing is correct. Refer to
Supplementary Documentation section 2.0
System Piping. Check that water pressure is at
least 15PSI.
Boilers Only - Boiler heat transfer surfaces
may be fouled with scale or magnetite. Clean
with Fernox DS-40 Descaler and Cleanser. See
Table 10-1.
Lockout 82 – Stack limit
Dirty heat exchanger
Inspect and if required clean the combustion
chamber and/or heat exchanger. Refer to Section
14.0 Annual Maintenance and Inspection and
Section 10.0 System Piping.
Incorrect “Stack limit setpoint”
Unless installed in Canada with PVC exhaust
venting, set “Stack limit setpoint” to maximum
setting of 220ºF (104ºC). In Canada PVC exhaust
venting is limited to 149ºF (65ºC).
Faulty sensor
Check resistance of stack sensor and compare to
thermistor resistance chart, see Table 17-2.
Lockout or Hold 85 –
Inlet/Outlet Inversion Limit
Pump flowing in the wrong
direction
Ensure water circulation is flowing into the boiler
at the fitting closest to the wall.
Incorrect factory sensor wiring
Disconnect flue sensor cable; screen should
display “Hold 95 – Stack sensor fault”; if not
contact NTI.
Lockout or Hold 88 – Outlet
T Rise limit
Insufficient water flow
See Lockout or Hold 81.
Trinity Lx│Installation and Operation Instructions Lx Series
Page 85
85
Table 17-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Hold 91– Inlet sensor fault
Sensor disconnected
Verify that 2-position Molex connector on
wiring harness is securely attached to mating
connector on inlet sensor.
Inspect sensor wiring.
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 17-2.
Hold 92 – Outlet sensor fault
Sensor disconnected
Verify that 4-position Molex connector on
wiring harness is securely attached to mating
connector on outlet sensor.
Inspect sensor wiring.
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 17-2.
Hold 95 – Stack sensor fault
Sensor disconnected
Verify that 4-position Molex connector on
wiring harness is securely attached to mating
connector on stack sensor.
Inspect sensor wiring.
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 17-2.
Hold 110 – Ignition failure
occurred, failure to prove
flame after 3 ignition attempts
(Lx150-400 only)
Spark cable disconnected
Ensure that the high voltage spark cable is
securely connected to the spark generator and the
igniter electrode. Check that the green ground
wire is securely attached to the ¼” quick connect
tab on the igniter electrode.
Insufficient gas line pressure
Ensure the manual gas shutoff valve is open.
Refer to manual section 9.0 GAS VALVE AND
BURNER SETUP.
Flame rod disconnected
Verify that the flame rod signal wire is securely
attached to the flame rod, which is located bottom
center of the burner door.
No 120VAC to Spark Generator
Check wiring from controller to spark generator.
With an AC voltmeter measure voltage across J56 and ground (the controller chassis is connected
to the 120VAC supply ground) during trial for
ignition.
Faulty Spark Generator
During trial for ignition check for arc on spark
electrode via the observation port located next to
the spark electrode in the burner door. If the spark
generator is receiving 120VAC and no spark is
observed, replace the spark generator.
No 24VAC to Gas Valve
Check the wiring harness for loose or interrupted
connections of the gas valve wiring. With an AC
voltmeter, measure the voltage from controller
terminals J5-2 to J4-10. There should be 24VAC
present during trial for ignition.
Faulty Gas Valve
The gas valve emits an audible click when it
switches on or off. If the controller is providing
24VAC to the gas valve, and the wiring is intact,
it should be possible to detect if the valve is
responding.
Lockout 113 – Flame circuit
timeout
A flame circuit shorted to ground
may show up as a flame circuit
timeout. High resistance shorts can
display as Lockout 113.
Check to ensure condensate drain is not blocked.
Check to ensure no voltage applied to R & CH
terminals. If using 4-20mA input, check to ensure
current is not greater than 21mA.
Lx Series Installation and Operation Instructions│Trinity Lx
Page 86
86
Table 17-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Lockout 122 – Lightoff rate
proving failed
Blower is not turning on
See “Blower not operating” below.
Missing or incorrect blower
feedback signal
See Hold 62 above.
Blower is always on
See “Blower operating at high speed while burner
is off” below.
Alert 128 - Modulation rate
was limited due to IAS was
open (Air switch open while
burner firing)
Blocked venting
Check for blockage of the exhaust vent.
Blocked air inlet
Check for blockage of the air inlet.
Lockout 173 - Pilot relay
feedback incorrect
Lockout 174 – Safety relay
feedback incorrect
External Electrical Noise
Look for sources of electrical noise, i.e. a large
motor or multiple pieces of equipment starting at
the same time.
Failing Limit Switch in ILK circuit
Check operation of internal LWCO, and/or
external limit (i.e. devise connected between “R” and “LIM”); replace as necessary
Hardware failure of Sola controller
Reset power, If problem persists replace Sola
controller.
Alert 206 – Lead Lag header
temperature was invalid
System Sensor not connected
If desired, install System Sensor and wire to
sensor input connections “SYSTEM” and “SENSOR COM”. Otherwise ignore Alert 206
Alert 233 – Lead Lag outdoor
temperature was invalid
See Alert 248
Alert 248 – CH outdoor
temperature was invalid
Outdoor sensor not connected
The Trinity Lx is factory set with Outdoor Reset
enabled. Connect outdoor sensor or disable
Outdoor Reset.
Outdoor sensor wiring
Check wiring of outdoor sensor. Wires should
connect to Low Voltage barrier terminals 11&12.
Faulty sensor
Check sensor. Should be free of ice and snow.
Check resistance of sensor and compare to
thermistor resistance chart, see Table 17-2.
Alert 311 – Run was
terminated due to interrupted
air flow switch was off
Blocked venting
Check for blockage of the exhaust vent.
Blocked air inlet
Check for blockage of the air inlet.
Disconnected, damaged or blocked
tubing
Inspect the clear vinyl tubing connecting the air
switch + and – ports to the air metering elbow.
Condensation or other foreign matter may be
obstructing the tubing, preventing the switch from
sensing differential pressure caused by air flow
through the metering elbow.
Incorrect air switch setting
Contact NTI technical support.
Blown fuse
Check Fuse "A".
Inoperative CH and/or DHW
pump
Blown fuse
Check Fuse "B".
Faulty controller
If Fuse “B” not blown, and controller is operating,
navigate to pump diagnostic on display. Manually
switch pump on, check for 120VAC at pump
connection terminal on line voltage barrier strip. If
120VAC not detected, replace controller.
Faulty pump
If 120VAC supplied to pump, and pump does not
operate, replace pump.
Trinity Lx│Installation and Operation Instructions Lx Series
Page 87
87
Table 17-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Blower operating at high
speed while burner off
Blower signal cable disconnected
Verify that the 5-position Molex connector on
the wiring harness is securely connected to its
mating connector on the blower.
Check that the 4-position Molex connector on
wiring harness is securely connected to its
mating connector on the controller.
Blower operating at high
speed while burner off
No 24VAC to controller
Check Power LED on controller.
Check Fuse "C".
With an AC voltmeter measure voltage at
terminals J8 1 & 2, 24VAC should be present.
Blower not operating
Blower power disconnected
Verify that the 3-position Molex connector on the
wiring harness is securely connected to its mating
connector on the blower.
Blown fuse
Check Fuse "A" using the procedure described
above. Fuse "A" protects the blower as well as the
ignition spark generator and boiler pump.
Faulty blower
Measure voltage across pins 1 & 2 (black and
white wires) of 3-position connector on wiring
harness. If 120VAC detected, replace power
connector and remove 5-position signal connector.
Blower should rotate at high speed. If blower does
not rotate, replace blower.
Table 17-2 Thermistor Resistance vs. Temperature
Temp °F (°C)
Resistance Ohms (Ω)
Temp °F (°C)
Resistance Ohms (Ω)
-22 (-30)
176,133
122 (50)
3,603
-4 (-20)
96,761
131 (55)
2,986
14 (-10)
55,218
140 (60)
2,488
32 (0)
32,650
149 (65)
2,083
41 (5)
25,390
158 (70)
1,752
50 (10)
19,900
167 (75)
1,481
59 (15)
15,710
176 (80)
1,258
68 (20)
12,490
185 (85)
1,072
77 (25)
10,000
194 (90)
918
86 (30)
8,057
203 (95)
789
95 (35)
6,531
212 (100)
680
104 (40)
5,327
230 (110)
506
113 (45)
4,369 - -
Table 17-3 Hold and Lockout Codes
Code
Description
Note
0
None
Hold / No lockout
1
Unconfigured safety data
Lockout
2
Waiting for safety data verification
Lockout
3
Internal fault: Hardware fault
Hold
4
Internal fault: Safety Relay key feedback error
Hold
5
Internal fault: Unstable power (DCDC) output
Hold
6
Internal fault: Invalid processor clock
Hold
7
Internal fault: Safety relay drive error
Hold
Lx Series Installation and Operation Instructions│Trinity Lx
Page 88
88
Table 17-3 Hold and Lockout Codes
Code
Description
Note
8
Internal fault: Zero crossing not detected
Hold
9
Internal fault: Flame bias out of range
Hold
10
Internal fault: Invalid Burner control state
Lockout
11
Internal fault: Invalid Burner control state flag
Lockout
12
Internal fault: Safety relay drive cap short
Hold
13
Internal fault: PII shorted to ILK
Hold / Lockout
14
Internal fault: HFS shorted to LCI
Hold / Lockout
15
Internal fault: Safety relay test failed due to feedback ON
Lockout
16
Internal fault: Safety relay test failed due to safety relay OFF
Lockout
17
Internal fault: Safety relay test failed due to safety relay not OFF
Lockout
18
Internal fault: Safety relay test failed due to feedback not ON
Lockout
19
Internal fault: Safety RAM write
Lockout
20
Internal fault: Flame ripple and overflow
Hold
21
Internal fault: Flame number of sample mismatch
Hold
22
Internal fault: Flame bias out of range
Hold
23
Internal fault: Bias changed since heating cycle starts
Hold
24
Internal fault: Spark voltage stuck low or high
Hold
25
Internal fault: Spark voltage changed too much during flame sensing time
Hold
26
Internal fault: Static flame ripple
Hold
27
Internal fault: Flame rod shorted to ground detected
Hold
28
Internal fault: A/D linearity test fails
Hold
29
Internal fault: Flame bias cannot be set in range
Hold
30
Internal fault: Flame bias shorted to adjacent pin
Hold
31
Internal fault: SLO electronics unknown error
Hold
32
Internal fault: Safety Key 0
Lockout
33
Internal fault: Safety Key 1
Lockout
34
Internal fault: Safety Key 2
Lockout
35
Internal fault: Safety Key 3
Lockout
36
Internal fault: Safety Key 4
Lockout
37
Internal fault: Safety Key 5
Lockout
38
Internal fault: Safety Key 6
Lockout
39
Internal fault: Safety Key 7
Lockout
40
Internal fault: Safety Key 8
Lockout
41
Internal fault: Safety Key 9
Lockout
42
Internal fault: Safety Key 10
Lockout
43
Internal fault: Safety Key 11
Lockout
44
Internal fault: Safety Key 12
Lockout
45
Internal fault: Safety Key 13
Lockout
46
Internal fault: Safety Key 14
Lockout
47
Flame rod to ground leakage
Hold
48
Static flame (not flickering)
Hold
49
24VAC voltage low/high
Hold
50
Modulation fault
Hold
51
Pump fault
Hold
52
Motor tachometer fault
Hold
53
AC inputs phase reversed
Lockout
54
Safety GVT model ID doesn’t match application’s model ID
Lockout
55
Application configuration data block CRC errors
Lockout
56-57
RESERVED
Trinity Lx│Installation and Operation Instructions Lx Series
Page 89
89
Table 17-3 Hold and Lockout Codes
Code
Description
Note
58
Internal fault: HFS shorted to IAS
Lockout
59
Internal fault: Mux pin shorted
Lockout
60
Internal fault: HFS shorted to LFS
Lockout
61
Anti short cycle
Hold
62
Fan speed not proved
Hold
63
LCI OFF
Hold
64
PII OFF
N/A
65
Interrupted Airflow Switch OFF
Hold
66
Interrupted Airflow Switch ON
Hold
67
ILK OFF
Hold
68
ILK ON
N/A
69
Pilot test hold
Hold
70
Wait for leakage test completion
Hold
71
Input power frequency mismatch
Lockout
72-77
RESERVED
78
Demand lost in run
Hold
79
Outlet high limit
Hold
80
DHW high limit
Disabled
81
Delta T limit
Hold / Lockout
82
Stack limit
Lockout
83
Delta T exchanger/outlet limit
Disabled
84
Delta T inlet/exchanger limit
Disabled
85
Inlet/Outlet inversion limit (See Table 17-1)
Hold
86
Exchanger/outlet inversion limit
Disabled
87
Inlet/exchanger inversion limit
Disabled
88
Outlet T-Rise limit (See Table 17-1)
Lockout
89
Exchanger T-rise limit
Disabled
90
Heat exchanger high limit
Disabled
91
Inlet sensor fault
Hold
92
Outlet sensor fault
Hold
93
DHW sensor fault
Hold
94
Header sensor fault
Hold
95
Stack sensor fault
Hold
96
Outdoor sensor fault
Hold
97
Internal fault: A2D mismatch
Lockout
98
Internal fault: Exceeded VSNSR voltage tolerance
Lockout
99
Internal fault: Exceeded 28V voltage tolerance
Lockout
100
Pressure sensor fault
Hold
101
Exchanger sensor fault
Disabled
102-104
RESERVED
105
Flame detected out of sequence
Hold / Lockout
106
Flame lost in MFEP
Lockout
107
Flame lost early in run
Lockout
108
Flame lost in run
Lockout
109
Ignition failed
Lockout
110
Ignition failure occurred
Hold
111
Flame current lower than WEAK threshold
Hold
112
Pilot test flame timeout
Lockout
113
Flame circuit timeout
Lockout
Lx Series Installation and Operation Instructions│Trinity Lx
Page 90
90
Table 17-3 Hold and Lockout Codes
Code
Description
Note
114-115
RESERVED
116
Wait for OK to Run
Disabled
117
Flap valve condensate fault
Disabled
118
Controller interaction system fault
Hold
119
Controller interaction communications fault
Hold
120
Flap valve backflow fault
Disabled
121
Flap valve fault
Disabled
122
Light off rate proving failed
Lockout
123
Purge rate proving failed
Lockout
124
High fire switch OFF
Hold
125
High fire switch stuck ON
Hold
126
Low fire switch OFF
Hold
127
Low fire switch stuck ON
Hold
128
Fan speed failed during pre-purge
Hold / Lockout
129
Fan speed failed during pre-ignition
Hold / Lockout
130
Fan speed failed during ignition
Hold / Lockout
131
Fan movement detected during standby
Hold
132
Fan speed failed during run
Hold
133-135
RESERVED
136
Interrupted Airflow Switch failed to close
Hold
137
ILK failed to close
Hold
138
Flame too low
Lockout
139-142
RESERVED
143
Internal fault: Flame bias out of range 1
Lockout
144
Internal fault: Flame bias out of range 2
Lockout
145
Internal fault: Flame bias out of range 3
Lockout
146
Internal fault: Flame bias out of range 4
Lockout
147
Internal fault: Flame bias out of range 5
Lockout
148
Internal fault: Flame bias out of range 6
Lockout
149
Flame detected
Hold / Lockout
150
Flame not detected
Hold
151
High fire switch ON
Hold / Lockout
152
Combustion pressure ON
Hold / Lockout
153
Combustion pressure OFF
Hold / Lockout
154
Purge fan switch ON
Hold / Lockout
155
Purge fan switch OFF
Hold / Lockout
156
Combustion pressure and Flame ON
Hold / Lockout
157
Combustion pressure and Flame OFF
Lockout
158
Main valve ON
Lockout
159
Main valve OFF
Lockout
160
Ignition ON
Lockout
161
Ignition OFF
Lockout
162
Pilot valve ON
Lockout
163
Pilot valve OFF
Lockout
164
Block intake ON
Lockout
165
Block intake OFF
Lockout
166-168
RESERVED
169
Safety opto bad in test state
Lockout
170
Safety relay opto feedback incorrect
Lockout
Trinity Lx│Installation and Operation Instructions Lx Series
Page 91
91
Table 17-3 Hold and Lockout Codes
Code
Description
Note
171
Safety relay feedback incorrect in run
Lockout
172
Main relay feedback incorrect
Lockout
173
Pilot relay feedback incorrect
Lockout
174
Safety relay feedback incorrect
Lockout
175
Safety relay open
Lockout
176
Main relay ON at safe start check
Lockout
177
Pilot relay ON at safe start check
Lockout
178
Safety relay ON at safe start check
Lockout
179-180
RESERVED
181
Invalid Blocked condensate enable setting
Disabled
182
Invalid J7-1 configuration, both LFS and Blocked condensate
Disabled
183
Invalid J7-2 configuration, both HFS and Flap valve
Disabled
184
Invalid BLOWER/HSI output setting
Lockout
185
Invalid Delta T limit enable setting
Lockout
186
Invalid Delta T limit response setting
Lockout
187
Invalid DHW high limit enable setting
Lockout
188
Invalid DHW high limit response setting
Lockout
189
Invalid Flame sensor type setting
Lockout
190
Invalid interrupted air switch enable setting
Lockout
191
Invalid interrupted air switch start check enable setting
Lockout
192
Invalid Igniter on during setting
Lockout
193
Invalid Ignite failure delay setting
Lockout
194
Invalid Ignite failure response setting
Lockout
195
Invalid Ignite failure retries setting
Lockout
196
Invalid Ignition source setting
Lockout
197
Invalid Interlock open response setting
Lockout
198
Invalid Interlock start check setting
Lockout
199
Invalid LCI enable setting
Lockout
200
Invalid light off rate setting
Lockout
201
Invalid Light off rate proving setting
Lockout
202
Invalid Main Flame Establishing Period time setting
Lockout
203
Invalid MFEP flame failure response setting
Lockout
204
Invalid NTC sensor type setting
Lockout
205
Invalid Outlet high limit response setting
Lockout
206
Invalid Pilot Flame Establishing Period setting
Lockout
207
Invalid PII enable setting
Lockout
208
Invalid pilot test hold setting
Lockout
209
Invalid Pilot type setting
Lockout
210
Invalid Post-purge time setting
Lockout
211
Invalid Power up with lockout setting
Lockout
212
Invalid Pre-ignition time setting
Lockout
213
Invalid Pre-purge rate setting
Lockout
214
Invalid Pre-purge time setting
Lockout
215
Invalid Purge rate proving setting
Lockout
216
Invalid Run flame failure response setting
Lockout
217
Invalid Run stabilization time setting
Lockout
218
Invalid Stack limit enable setting
Lockout
219
Invalid Stack limit response setting
Lockout
220
Unconfigured Delta T limit set point setting
Lockout
Lx Series Installation and Operation Instructions│Trinity Lx
Page 92
92
Table 17-3 Hold and Lockout Codes
Code
Description
Note
221
Unconfigured DHW high limit set point setting
Lockout
222
Unconfigured Outlet high limit set point setting
Lockout
223
Unconfigured Stack limit set point setting
Lockout
224
Invalid DHW demand source setting
Lockout
225
Invalid Flame threshold setting
Lockout
226
Invalid Outlet high limit set point setting
Lockout
227
Invalid DHW high limit set point setting
Lockout
228
Invalid Stack limit set point setting
Lockout
229
Invalid Modulation output setting
Lockout
230
Invalid CH demand source setting
Lockout
231
Invalid Delta T limit delay setting
Lockout
232
Invalid Pressure sensor type setting
Lockout
233
Invalid IAS closed response setting
Lockout
234
Invalid Outlet high limit enable setting
Lockout
235
Invalid Outlet connector type setting
Lockout
236
Invalid Inlet connector type setting
Lockout
237
Invalid DHW connector type setting
Lockout
238
Invalid Stack connector type setting
Lockout
239
Invalid Header connector type setting
Lockout
240
Invalid Outdoor connector type setting
Lockout
241
Exchanger sensor not allowed with stack connector setting
Lockout
242
Invalid DHW auto detect configuration
Lockout
243
Invalid UV with spark interference not compatible with Igniter on throughout
Lockout
244
Internal fault: Safety relay test invalid state
Lockout
245
Invalid Outlet connector type setting for T-rise
Lockout
246
4-20mA cannot be used for both modulation and setpoint control
Lockout
247
Invalid ILK bounce detection enable
Lockout
248
Invalid forced recycle interval
Lockout
249
STAT cannot be demand source when Remote Stat is enabled
Lockout
250
Invalid Fan speed error response
Lockout
251
Lead drop-stage on error setting does not match drop method configuration
Lockout
252
Invalid Line frequency setting
Lockout
253
Lead Lag modulation sensor not valid with setpoint source
Lockout
254
Lead Lag modulation sensor not valid with local setpoint source
Lockout
255
Lead Lag modulation sensor not valid with local modulation source
Lockout
256
Selected Controller interaction enable setting is not allowed
Lockout
257
Controller interaction enable does not match neighbor stack fault setting
Lockout
258
Controller ID must be non-zero if controller interaction is enabled
Lockout
259
Modulation output must be fan if controller interaction is enabled
Lockout
260
Asymmetrical paired (no flap) is set but flap switch input is energized
Lockout
261
Neighbor burner control blower fault detected
Lockout
262
Blower fault detected during flap test
Lockout
263
Invalid DHW demand temperature setting
Lockout
264
Invalid preferred outlet high limit setting
Lockout
265
Invalid preferred lightoff rate setting
Lockout
266
Invalid preferred stack limit rate setting
Lockout
Trinity Lx│Installation and Operation Instructions Lx Series
Page 93
93
Table 17-4 Alert Codes
Code
Description
0
None (No alert)
1
Alert PCB was restored from factory defaults
2
Safety configuration parameters were restored from factory defaults
3
Configuration parameters were restored from factory defaults
4
Invalid Factory Invisibility PCB was detected
5
Invalid Factory Range PCB was detected
6
Invalid range PCB record has been dropped
7
EEPROM lockout history was initialized
8
Switched application annunciation data blocks
9
Switched application configuration data blocks
10
Configuration was restored from factory defaults
11
Backup configuration settings was restored from active configuration
12
Annunciation configuration was restored from factory defaults
13
Annunciation configuration was restored from backup
14
Safety group verification table was restored from factory defaults
15
Safety group verification table was updated
16
Invalid Parameter PCB was detected
17
Invalid Range PCB was detected
18
Alarm silence time exceeded maximum
19
Invalid safety group verification table was detected
20
Backdoor password could not be determined
21
Invalid safety group verification table was not accepted
22
CRC errors were found in application configuration data blocks
23
Backup Alert PCB was restored from active one
24
RESERVED
25
Lead Lag operation switch was turned OFF
26
Lead Lag operation switch was turned ON
27
Safety processor was reset
28
Application processor was reset
29
Burner switch was turned OFF
30
Burner switch was turned ON
31
Program Module (PM) was inserted into socket
32
Program Module (PM) was removed from socket
33
Alert PCB was configured
34
Parameter PCB was configured
35
Range PCB was configured
36
Program Module (PM) incompatible with product was inserted into socket
37
Program Module application parameter revision differs from application processor
38
Program Module safety parameter revision differs from safety processor
39
PCB incompatible with product contained in Program Module
40
Parameter PCB in Program Module is too large for product
41
Range PCB in Program Module was too large for product
42
Alert PCB in Program Module was too large for product
43
IAS start check was forced on due to IAS enabled
44
Low voltage was detected in safety processor
45
High line frequency occurred
46
Low line frequency occurred
47
Invalid subsystem reset request occurred
48
Write large enumerated Modbus register value was not allowed
Lx Series Installation and Operation Instructions│Trinity Lx
Page 94
94
Table 17-4 Alert Codes
Code
Description
49
Maximum cycle count was reached
50
Maximum hours count was reached
51
Illegal Modbus write was attempted
52
Modbus write attempt was rejected (NOT ALLOWED)
53
Illegal Modbus read was attempted
54
Safety processor brown-out reset occurred
55
Application processor watchdog reset occurred
56
Application processor brown-out reset occurred
57
Safety processor watchdog reset occurred
58
Alarm was reset by the user at the control
59
Burner control firing rate was > absolute max rate
60
Burner control firing rate was < absolute min rate
61
Burner control firing rate was invalid, % vs. RPM
62
Burner control was firing with no fan request
63
Burner control rate (non-firing) was > absolute max rate
64
Burner control rate (non-firing) was < absolute min rate
65
Burner control rate (non-firing) was absent
66
Burner control rate (non-firing) was invalid, % vs. RPM
67
Fan off cycle rate was invalid, % vs. RPM
68
Set point was over ridden due to sensor fault
69
Modulation was over ridden due to sensor fault
70
No demand source was set due to demand priority conflicts
71
CH 4-20mA signal was invalid.
72
Flame strength rate differential was invalid
73
Flame strength step rate was invalid
74
Periodic forced recycle
75
Absolute max fan speed was out of range
76
Absolute min fan speed was out of range
77
Fan gain down was invalid
78
Fan gain up was invalid
79
Fan minimum duty cycle was invalid
80
Fan pulses per revolution was invalid
81
Fan PWM frequency was invalid
82-83
RESERVED
84
Lead Lag CH 4-20mA water temperature setting was invalid
85
No Lead Lag add stage error threshold was configured
86
No Lead Lag add stage detection time was configured
87
No Lead Lag drop stage error threshold was configured
88
No Lead Lag drop stage detection time was configured
89
Lead Lag all boiler off threshold was invalid
90
Modulation output type was invalid
91
Firing rate control parameter was invalid
92
Forced rate was out of range vs. min/max modulation
93
Forced rate was invalid, % vs. RPM
94
Slow start ramp value was invalid
95
Slow start degrees value was invalid
96
Slow start was ended due to outlet sensor fault
97
Slow start was end due to reference set point fault
98
CH max modulation rate was invalid, % vs. RPM
Trinity Lx│Installation and Operation Instructions Lx Series
Page 95
95
Table 17-4 Alert Codes
Code
Description
99
CH max modulation rate was > absolute max rate
100
CH modulation range (max minus min) was too small (< 4% or 40 RPM)
101
DHW max modulation rate was invalid, % vs. RPM
102
DHW max modulation rate was > absolute max rate
103
DHW modulation range (max minus min) was too small (< 4% or 40 RPM)
104
Min modulation rate was < absolute min rate
105
Min modulation rate was invalid, % vs. RPM
106
Manual rate was invalid, % vs. RPM
107
Slow start enabled, but forced rate was invalid
108
Analog output hysteresis was invalid
109
Analog modulation output type was invalid
110
IAS open rate differential was invalid
111
IAS open step rate was invalid
112
Mix max modulation rate was invalid, % vs. RPM
113
Mix max modulation rate was > absolute max or < absolute min rates
114
Mix modulation range (max minus min) was too small (< 4% or 40 RPM)
115
Fan was limited to its minimum duty cycle
116
Manual rate was > CH max modulation rate
117
Manual rate was > DHW max modulation rate
118
Manual rate was < min modulation rate
119
Manual rate in Standby was > absolute max rate
120
Modulation commanded rate was > CH max modulation rate
121
Modulation commanded rate was > DHW max modulation rate
122
Modulation commanded rate was < min modulation rate
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
125
Modulation rate was limited due to stack limit
126
Modulation rate was limited due to anti-condensation
127
Fan Speed out of range in RUN
128
Modulation rate was limited due to IAS was open
129
Slow start ramp setting of zero will result in no modulation rate change
130
No forced rate was configured for slow start ramp
131
CH demand source was invalid
132
CH P-gain was invalid
133
CH I-gain was invalid
134
CH D-gain was invalid
135
CH OFF hysteresis was invalid
136
CH ON hysteresis was invalid
137
CH sensor type was invalid
138
CH hysteresis step time was invalid
139
CH remote control parameter was invalid
140
CH ODR not allowed with remote control
146
CH control was suspended due to fault
147
CH header temperature was invalid
148
CH outlet temperature was invalid
149
CH steam pressure was invalid
151
Minimum water temperature parameter was greater than setpoint
152
Minimum water temperature parameter was greater than time of day setpoint
155
CH modulation rate source parameter was invalid
Lx Series Installation and Operation Instructions│Trinity Lx
Page 96
96
Table 17-4 Alert Codes
Code
Description
157
DHW demand source was invalid
158
DHW P-gain was invalid
159
DHW I-gain was invalid
160
DHW D-gain was invalid
161
DHW OFF hysteresis was invalid
162
DHW ON hysteresis was invalid
163
DHW hysteresis step time was invalid
164
DHW sensor type was invalid
165
Inlet sensor type was invalid for DHW
166
Outlet sensor type was invalid for DHW
167
DHW storage OFF hysteresis was invalid
168
DHW storage ON hysteresis was invalid
169
DHW modulation sensor type was invalid
170
DHW modulation sensor was not compatible for Auto mode
171
DHW control was suspended due to fault
172
DHW temperature was invalid
173
DHW inlet temperature was invalid
174
DHW outlet temperature was invalid
175
DHW high limit must be disabled for Auto mode
176
DHW sensor type was not compatible for Auto mode
177
DHW priority source setting was invalid
178
DHW priority method setting was invalid
179
CH S5 (J8-11) sensor was invalid
180
CH Inlet temperature was invalid
181
CH S10 (J10-7) sensor was invalid
182
Lead Lag CH setpoint source was invalid
183
Lead Lag P-gain was invalid
184
Lead Lag I-gain was invalid
185
Lead Lag D-gain was invalid
186
Lead Lag OFF hysteresis was invalid
187
Lead Lag ON hysteresis was invalid
188
Lead Lag slave enable was invalid
189
Lead Lag hysteresis step time was invalid
190
No Lead Lag Modbus port was assigned
191
Lead Lag base load common setting was invalid
192
Lead Lag DHW demand switch setting was invalid
193
Lead Lag Mix demand switch setting was invalid
194
Lead Lag modulation sensor setting was invalid
195
Lead Lag backup modulation sensor setting was invalid
196
Lead Lag slave mode setting was invalid
197
Lead Lag rate allocation setting was invalid
198
Lead selection setting was invalid
199
Lag selection setting was invalid
200
Lead Lag slave return setting was invalid
201
Lead Lag add stage method setting was invalid
202
STAT may not be a Lead Lag CH demand source when Remote Stat is enabled
203
Lead Lag base load rate setting was invalid
204
Lead Lag master was suspended due to fault
205
Lead Lag slave was suspended due to fault
Trinity Lx│Installation and Operation Instructions Lx Series
Page 97
97
Table 17-4 Alert Codes
Code
Description
206
Lead Lag header temperature was invalid
207
Lead Lag was suspended due to no enabled Program Module installed
208
Lead Lag slave session has timed out
209
Too many Lead Lag slaves were detected
210
Lead Lag slave was discovered
211
Incompatible Lead Lag slave was discovered
212
No base load rate was set for Lead Lag slave
213
Lead Lag slave unable to fire before demand to fire delay expired
214
Adding Lead Lag slave aborted due to add requirement change
215
No Lead Lag slaves available to service demand
216
No Lead Lag active service was set due to demand priority conflicts
217
No Lead Lag add stage method was specified
218
No Lead Lag drop stage method was specified
219
Using backup Lead Lag header sensor due to sensor failure
220
Lead Lag frost protection rate was invalid
221
Lead Lag drop stage method setting was invalid
222
CH frost protection temperature was invalid
223
CH frost protection inlet temperature was invalid
224
DHW frost protection temperature was invalid
225
No anticondensation setpoint was configured for frost protection
226
RESERVED
227
DHW priority override time was not derated due to invalid outdoor temperature
228
Warm weather shutdown was not checked due to invalid outdoor temperature
229
Lead Lag slave communication timeout
230
RESERVED
231
LL set point was invalid
232
LL time of day set point was invalid
233
LL outdoor temperature was invalid
234
LL ODR time of day set point was invalid
235
LL ODR time of day set point exceeded normal set point
236
LL max outdoor set point was invalid
237
LL min outdoor set point was invalid
238
LL min water set point was invalid
239
LL outdoor temperature range was too small (minimum 12 C / 22 F)
240
LL water temperature range was too small (minimum 12 C / 22 F)
241
Lead Lag DHW setpoint was invalid
243
Lead Lag CH demand switch was invalid
244
Lead Lag ODR min water temperature was invalid
245
RESERVED
246
CH set point was invalid
247
CH time of day set point was invalid
248
CH outdoor temperature was invalid
249
CH ODR time of day setpoint was invalid
250
CH ODR time of day set point exceeds normal set point
251
CH max outdoor set point was invalid
252
CH min outdoor setp oint was invalid
253
CH min water set point was invalid
254
CH outdoor temperature range was too small (minimum 12 C / 22 F)
255
CH water temperature range was too small (minimum 12 C / 22 F)
Lx Series Installation and Operation Instructions│Trinity Lx
Page 98
98
Table 17-4 Alert Codes
Code
Description
259
CH ODR min water temperature was invalid
260
RESERVED
261
DHW set point was invalid
262
DHW time of day set point was invalid
263
DHW storage setpoint was invalid
264
STAT may not be a DHW demand source when Remote Stat is enabled
265
No DHW anticondensation setpoint was configured
266
No CH anticondensation setpoint was configured
267
STAT may not be a CH demand source when Remote Stat is enabled
268
CH 4mA water temperature setting was invalid
269
CH 20mA water temperature setting was invalid
270
Steam 4mA water temperature setting was invalid
271
Steam 20mA water temperature setting was invalid
272
Abnormal Recycle: Pressure sensor fault
273
Abnormal Recycle: Safety relay drive test failed
274
Abnormal Recycle: Demand off during Pilot Flame Establishing Period
275
Abnormal Recycle: LCI off during Drive to Purge Rate
276
Abnormal Recycle: LCI off during Measured Purge Time
277
Abnormal Recycle: LCI off during Drive to Light off Rate
278
Abnormal Recycle: LCI off during Pre-Ignition test
279
Abnormal Recycle: LCI off during Pre-Ignition time
280
Abnormal Recycle: LCI off during Main Flame Establishing Period
281
Abnormal Recycle: LCI off during Ignition period
282
Abnormal Recycle: Demand off during Drive to Purge Rate
283
Abnormal Recycle: Demand off during Measured Purge Time
284
Abnormal Recycle: Demand off during Drive to Light off Rate
285
Abnormal Recycle: Demand off during Pre-Ignition test
286
Abnormal Recycle: Demand off during Pre-Ignition time
287
Abnormal Recycle: Flame was on during Safe Start check
288
Abnormal Recycle: Flame was on during Drive to Purge Rate
289
Abnormal Recycle: Flame was on during Measured Purge Time
290
Abnormal Recycle: Flame was on during Drive to Light off Rate
291
Abnormal Recycle: Flame was not on at end of Ignition period
292
Abnormal Recycle: Flame was lost during Main Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
295
Abnormal Recycle: Leakage test failed
296
Abnormal Recycle: Interrupted air flow switch was off during Drive to Purge Rate
297
Abnormal Recycle: Interrupted air flow switch was off during Measured Purge Time
298
Abnormal Recycle: Interrupted air flow switch was off during Drive to Light off Rate
299
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test
300
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time
301
Abnormal Recycle: Interrupted air flow switch was off during Main Flame Establishing Period
302
Abnormal Recycle: Ignition failed due to interrupted air flow switch was off
303
Abnormal Recycle: ILK off during Drive to Purge Rate
304
Abnormal Recycle: ILK off during Measured Purge Time
305
Abnormal Recycle: ILK off during Drive to Light off Rate
306
Abnormal Recycle: ILK off during Pre-Ignition test
307
Abnormal Recycle: ILK off during Pre-Ignition time
Trinity Lx│Installation and Operation Instructions Lx Series
Page 99
99
Table 17-4 Alert Codes
Code
Description
308
Abnormal Recycle: ILK off during Main Flame Establishing Period
309
Abnormal Recycle: ILK off during Ignition period
310
Run was terminated due to ILK was off
311
Run was terminated due to interrupted air flow switch was off
312
Stuck reset switch
313
Run was terminated due to fan failure
314
Abnormal Recycle: Fan failed during Drive to Purge Rate
315
Abnormal Recycle: Fan failed during Measured Purge Time
316
Abnormal Recycle: Fan failed during Drive to Light off Rate
317
Abnormal Recycle: Fan failed during Pre-Ignition test
318
Abnormal Recycle: Fan failed during Pre-Ignition time
319
Abnormal Recycle: Fan failed during Ignition period
320
Abnormal Recycle: Fan failed during Main Flame Establishing Period
321
Abnormal Recycle: Main Valve off after 10 seconds of RUN
322
Abnormal Recycle: Pilot Valve off after 10 seconds of RUN
323
Abnormal Recycle: Safety Relay off after 10 seconds of RUN
324
Abnormal Recycle: Hardware flame bias
325
Abnormal Recycle: Hardware static flame
326
Abnormal Recycle: Hardware flame current invalid
327
Abnormal Recycle: Hardware flame rod short
328
Abnormal Recycle: Hardware invalid power
329
Abnormal Recycle: Hardware invalid AC line
330
Abnormal Recycle: Hardware SLO flame ripple
331
Abnormal Recycle: Hardware SLO flame sample
332
Abnormal Recycle: Hardware SLO flame bias range
333
Abnormal Recycle: Hardware SLO flame bias heat
334
Abnormal Recycle: Hardware SLO spark stuck
335
Abnormal Recycle: Hardware SLO spark changed
336
Abnormal Recycle: Hardware SLO static flame
337
Abnormal Recycle: Hardware SLO rod shorted
338
Abnormal Recycle: Hardware SLO AD linearity
339
Abnormal Recycle: Hardware SLO bias not set
340
Abnormal Recycle: Hardware SLO bias shorted
341
Abnormal Recycle: Hardware SLO electronics
342
Abnormal Recycle: Hardware processor clock
343
Abnormal Recycle: Hardware AC phase
344
Abnormal Recycle: Hardware A2D mismatch
345
Abnormal Recycle: Hardware VSNSR A2D
346
Abnormal Recycle: Hardware 28V A2D
347
Abnormal Recycle: Hardware HFS IAS shorted
348
Abnormal Recycle: Hardware PII INTLK shorted
349
Abnormal Recycle: Hardware HFS LCI shorted
350
Abnormal Recycle: Hardware HFS LFS shorted
351
Abnormal Recycle: Invalid zero crossing
352
Abnormal Recycle: fault stack sensor
353
Abnormal Recycle: stack limit
354
Abnormal Recycle: delta T limit
355
Abnormal Recycle: fault outlet sensor
356
Abnormal Recycle: outlet high limit
Lx Series Installation and Operation Instructions│Trinity Lx
Page 100
100
Table 17-4 Alert Codes
Code
Description
357
Abnormal Recycle: fault DHW sensor
358
Abnormal Recycle: DHW high limit
359
Abnormal Recycle: fault inlet sensor
360
Abnormal Recycle: Check Parameters Failed
361
Internal error: No factory parameters were detected in control
362
Internal error: PID iteration frequency was invalid
363
Internal error: Demand-Rate interval time was invalid
364
Internal error: Factory calibration parameter for modulation was invalid
365
Internal error: CH PID P-scaler was invalid
366
Internal error: CH PID I-scaler was invalid
367
Internal error: CH PID D-scaler was invalid
368
Internal error: DHW PID P-scaler was invalid
369
Internal error: DHW PID I-scaler was invalid
370
Internal error: DHW PID D-scaler was invalid
371
Internal error: Lead Lag master PID P-scaler was invalid
372
Internal error: Lead Lag master PID I-scaler was invalid
373
Internal error: Lead Lag master PID D-scaler was invalid
374
Abnormal Recycle: Hardware flame bias high
375
Abnormal Recycle: Hardware flame bias low
376
Abnormal Recycle: Hardware flame bias delta high
377
Abnormal Recycle: Hardware flame bias delta low
378
Abnormal Recycle: Hardware flame bias dynamic high
379
Abnormal Recycle: Hardware flame bias dynamic low
380
Abnormal Recycle: Fan Speed Not Proven
381
Abnormal Recycle: Fan Speed Range Low
382
Abnormal Recycle: Fan Speed Range High
383
Abnormal Recycle: Pre-Ignition test failed, recycle
384-388
RESERVED
389
Abnormal Recycle: AC power frequency Mismatch
390-447
RESERVED
448
Flame too low
449
Modulation rate was limited due to flame strength
450
RESERVED
451
Circulator control was invalid
452
Circulator P-gain was invalid
453
Circulator I-gain was invalid
454
Circulator temperature was invalid
455
Circulator outlet temperature was invalid
456
Circulator inlet temperature was invalid
457
Circulator outlet temperature was invalid
458
Circulator sensor choice was invalid
459
Circulator PID setpoint was invalid
460
LCI demand lost in run
461
Demand lost in run
462
STAT demand lost in run
463
Demand lost in run due to no flame
464
LCI lost in Combustion Pressure Establishing Period
465
LCI lost in Combustion Pressure Stabilizing Period
466
RESERVED
Trinity Lx│Installation and Operation Instructions Lx Series
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.