NTI Lx150-400, Trinity Lx150, Trinity Lx150E, Trinity Lx200, Trinity Lx400 Installation And Operation Instructions Manual

Page 1
Trinity Lx
ndicates a hazardous situation which, if not avoided, will
cates a hazardous situation which, if not avoided,
ndicates a hazardous situation
hazardous
ndicates a hazardous situation which, if not avoided,
NEW FEATURES
Warm Weather Shutdown
Model Numbers: Lx150-400 Version Date: 2010-01-01
Second Central Heat Input
Internal Lead-Lag Control
System Sensor
Modulation Sensor Alternatives
INSTALLATION AND OPERATION INSTRUCTIONS FOR TRINITY LX SERIES
Appendix A - Controller and Touchscreen Display Instructions Appendix B - Boiler Applications: Plumbing and Wiring Appendix C - Water Heater Applications: Plumbing and Wiring
TABLE OF CONTENTS
INTRODUCTION................................................................................................................3
SPECIFICATIONS ..............................................................................................................6
APPLIANCE LOCATION...................................................................................................7
GENERAL VENTING.......................................................................................................11
VENT/AIR-INTAKE TERMINATION CLEARANCES..................................................20
CONDENSATE DRAIN....................................................................................................24
INSTALLING GAS PIPING..............................................................................................25
LIGHTING THE APPLIANCE .........................................................................................27
GAS VALVE AND BURNER SET-UP ............................................................................29
WIRING SCHEMATICS...................................................................................................34
INSTALLATION CHECKLIST ........................................................................................36
ANNUAL MAINTENANCE AND INSPECTION...........................................................37
PARTS LIST ......................................................................................................................39
TROUBLESHOOTING .....................................................................................................45
®
HAZARD SYMBOLS AND DEFINITIONS
Danger Sign: I result in serious injury or death.
Warning Sign: Indi could result in serious injury or death.
Caution Sign plus Safety Alert Symbol: I which, if not avoided, could result in minor or moderate injury.
Caution Sign without Safety Alert Symbol: Indicates a situation which, if not avoided, could result in property damage.
Notice Sign: I could result in property damage.
This Appliance must be installed by a licensed and trained Heating Technician or the Warranty is Void. Failure to properly install this
unit may result in property damage, serious injury to occupants, or possibly death.
Page 2
Trinity Lx
Read Before Proceeding
Installation and Operation Instructions Lx Series
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING_
A) This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the been under water.
appliance and to replace any part of the
OPERATING INSTRUCTIONS_
control system and any gas control which has
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the appliance.
3. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you don't smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the appliance.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Appliance” and call your service
technician or gas supplier.
TO TURN OFF GAS TO THE APPLIANCE_
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the appliance
3. Turn the manual gas valve to the OFF position
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to Section 12.0 for information on handling instructions and recommended personal protective equipment. Installation and service must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the supplied instructions before installing, servicing, or removing this appliance. This appliance contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans).
Void Warranty - This Appliance must have water flowing through it whenever the
burner is on or it will damage the unit and void the warranty. Failure to follow these instructions may result in serious injury or death.
2
Page 3
Lx Series Installation and Operation Instructions │
1.0 INTRODUCTION
Trinity Lx
Installation and Operation Instructions – These instructions apply to the installation
and operation of Trinity Lx150-400 units and covers instructions that are common-to­both boiler and water heater applications. Troubleshooting instructions for the controller and display are covered in Appendix A. Appliance-specific plumbing and wiring instructions for Boilers and Water Heaters are covered in Appendix B and C, respectively. See Table 1-1 for a list of Application Manuals.
Terminology – The following terms in the instruction manuals are used to differentiate between which instructions are common-to-both and which are appliance-specific. The term "APPLIANCE" applies to both kinds of water heating appliances (boilers and water heaters) and is used when conveying instructions which are common-to-both. The term "BOILER" or "WATER HEATER" is used when conveying instructions which are appliance-specific or specific to one or the other, but not both.
Table 1-1 Instruction Manuals
Appliance Model No.
Installation and Operation Instructions (Common-to-Both)
Boiler Lx150-400 Trinity Lx Series Water
Heater
Lx200 & 400 Trinity Lx Series
Application Manuals (Appliance-Specific)
Appendix B Boiler Applications
Appendix C Water Heating Applications
General Installation Requirements
The installation of your NTI Trinity Lx gas appliance must conform to the requirements of this manual, your local authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where required by the Authority, the installation must conform to the standard for “Controls and Safety Devices for Automatically Fired Boilers ANSI/ASME CSD-1.
This document pertains to the correct installation and operation of NTI Trinity Lx appliance, models numbers Lx150, Lx150E, Lx200 and Lx400. The instructions detailed in this document supersede any and all previous instructions provided by NTI, written or otherwise. Each unit is provided with the following:
1) Installation and Operation Instructions Manual for Trinity Lx Series,
2) Appendix A - Controller and Touchscreen Display Instructions for Trinity Lx Series,
3) Appendix B - Boiler Applications: Plumbing and Wiring Instructions,
4) Appendix C - Water Heater Applications: Plumbing and Wiring Instructions, and
5) Natural to LP Conversion Kit * * The conversion kit is required to convert the appliance so it will safely operate with Propane Gas.
Read and understand this entire document prior to proceeding with the installation of the Trinity Lx. Failure to follow the instructions outlined in this document will result in
property damage, serious injury or death.
User Responsibilities
This appliance must be installed and serviced by a qualified installer or service technician. This appliance must be serviced and inspected annually when operating in normal residential applications. Demanding applications or extreme conditions (i.e. commercial) may require more frequent service and inspection. As the User/Owner of this equipment, you are responsible for ensuring the maintenance is performed at the required intervals. It is also the Users responsibility to ensure Vent and Combustion-Air Intake termination is kept clear of ice and snow or any other obstruction. Failure to follow these instructions could result in fire, serious injury, or death.
Failure to have the appliance properly serviced and inspected on a regular basis may result in property damage, serious injury or death.
Failure to keep the Vent and Combustion Air Intake clear of ice, snow, and other debris may result in property damage, serious injury, or death.
3
Page 4
Trinity Lx
Installation and Operation Instructions Lx Series
Installer Responsibilities
As the installing technician it is your responsibility to ensure the installation is performed in accordance with this instruction manual as well as any applicable local or National installation codes. It is also your responsibility to inform the User/Owner of their obligation with respect to the above description under “User Responsibilities”. Failure to follow this warning could result in fire, serious injury, or death.
ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE
The Trinity Lx is factory set to operate with Natural Gas. BEFORE OPERATING WITH PROPANE, the specified LP Conversion Kit must be installed to convert the appliance so it will operate safely with LP Propane. Listed below are the relevant NTI appliance models and their corresponding Natural to LP Propane Conversion Kit number.
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your Trinity Lx appliance is not installed in a pit or similar location that will permit heavier than air gas to collect. Local Codes may require appliances fueled with LP gas be provided with an approved means of removing unburned gases from the room. Check your local codes for this requirement.
NTI Series Model Number Kit Number Trinity Lx 150, 150E, 200 82650-1 Trinity Lx 400 83017-1
Failure to use the appropriate Natural to LP Conversion Kit when operating the Trinity Lx with Propane will result in extremely dangerous burner operation leading to property
damage, serious injury or death. Refer to section titled ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE for appliance models and corresponding conversion kit numbers.
Appliance Vent / Air-Intake Piping
The Trinity Lx is a “Direct Vent” appliance requiring a “Special Venting System”. Vent and Combustion-Air Intake piping must be piped to the outdoors, using the vent material
and rules outlined in these instructions. Failure to follow instructions will result in serious injury or death.
New Features
Second Central Heat Input - The Trinity Lx can be used as a stand alone unit with a lone heat input or with two heat inputs. To configure units for two heat inputs refer to "Second Central Heat Input vs Multiple Boiler Application Settings" in Appendix A and "Stand Alone Boiler Applications" in Appendix B.
Internal Lead-Lag Control - The Trinity Lx controller has the internal capacity to stage or lead-lag up to 8 boilers or water heaters configured in a cascade by "daisy chaining" the controller units together. Refer to "Second Central Heat Input vs Multiple Boiler Application Settings" in Appendix A for controller setup and Appendix B or C for application specific plumbing and wiring instructions.
Modbus Address - In Lead Lag installations, each controller’s Modbus Address must be assigned by the installer. Refer to "System Identification & Access" in Appendix A.
System Sensor - Each LX is provided with an optional system water temperature sensor that allows the system supply or return temperature to be regulated directly. Refer to "Low Voltage Connections" in Appendix B. Not used for Water Heater Applications.
Modulation Sensor Alternatives - New LX models provide increased accuracy and control of a unit’s water
temperature by allowing installers to select the desired modulation sensor for a given demand. Refer to "Modulation Sensor" in Appendix B or C.
Warm Weather Shutdown - When enabled, this feature will "prevent" Central Heat operation when the outdoor temperature exceeds the WWSD setpoint and "permit" Central Heat operation if the outdoor temperature drops below the WWSD setpoint by 4oF. For set up details refer to the "Warm Weather Shutdown Configuration" in Appendix A - Controller and Touchscreen Display. Not used for water heater applications.
Natural to LP Propane Conversion Kit_
4
Page 5
Lx Series Installation and Operation Instructions │
Trinity Lx
IN THE STATE OF MASSACHUSETTS ONLY
(a) For all horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or
in part for residential purposes, including those owned and operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed and on each additional level of the dwelling, building or structure served by the equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of 30 days to comply with the above requirements; provided, however, that during said 30 day period a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS (plate included with appliance).
4. INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall
not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED: When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED:
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer.
5
Page 6
Trinity Lx
2.0 SPECIFICATIONS
Installation and Operation Instructions Lx Series
Table 2-1 Specifications
DESCRIPTION Lx150 Lx150E Lx200 Lx400
CSA Input Modulation btu/hr [kw]
DOE Heating Capacity btu/hr [kw]
Net I=B=R Rating
1,3
btu/hr [kw] DOE AFUE
3
% 95.1 97.0 95.1 94.0
1
1,3
25,000 - 150,000
[7.3 - 44.0]
136,000
[39.8]
118,000
[34.8]
2
25,000 - 150,000
[7.3 - 44.0]
139,000
[40.7]
121,000
[35.4]
25,000 - 199,000
[7.3 - 58.3]
182,000
[53.3]
158,000
[46.3]
75,000 - 399,000
[21.9 - 117]
374,000
[109.6]
325,000
[95.2]
6
Recovery Rating @ 100oF Rise, gal/hr - - 224 450 Water Connections - NPT, in. 1
4
1 1 1-1/4 Gas Connection - NPT, in. 1/2 1/2 1/2 3/4 Vent/Air-Intake Pipe Diameter Vent/Air-Intake, Max. Length, NG / LP
ft. [m] Dimensions H x W x D
in. [mm] Approx. Appliance Weight with Water,
lbs [kg]
Notes:
1
Listed Input and Output ratings are at minimum vent lengths at Sea Level. Numbers will be lower with longer venting
5
, in. [mm]
3 [76] 3 [76] 3 [76] 4 [102] 6 [152]
105 / 50
[32 / 15.2]
29.5 x 17 x 18.5
[749 x 432 x 470]
105 / 50
[32 / 15.2]
29.5 x 17 x 18.5
[749 x 432 x 470]
105 / 50
[32 / 15.2]
29.5 x 17 x 18.5
[749 x 432 x 470]
30
[9.1]
36 x 17 x 24
[915 x 432 x 610]
100 [45.3] 125 [56.7] 125 [56.7] 225 [102]
7
65
7
[19.8]
and/or altitudes greater then 2000 feet [610 m].
2
The maximum output when operating on LP-Gas is limited to 145,000 Btu/hr [42.5 kW].
3
Based on rating plate input capacities, using standard test procedures prescribed by the U.S. Department of Energy.
Ratings have been confirmed by AHRI (GAMA), excluding Lx400.
4
Units sold in Canada are 3/4” NPT.
5
Trinity Lx require a special venting system, use only vent materials and methods detailed in these instructions.
6
Steady-State Efficiency Rating.
7
Max. Length is the same for NG and LP for the Lx400 model only.
This unit requires two people to lift it or property damage and personal injury may result.
High Altitude Operation
The Trinity is designed to operate at its maximum listed capacity in installations less than or equal to 2000 ft [610 m] above Sea Level. Since the density of air decreases as elevation increases, maximum specified capacity should be de-rated for elevations above 2000 ft [610 m] in accordance with Table 2-2.
Table 2-2 De-rate % for High Altitudes
Elevations 2000 ft [610 m] 3000 ft [914 m] 4000 ft [1219 m] 4500 ft [1372 m] 5000 ft [1524 m]
In Canada In USA
Notes:
1
Canada: Altitudes between 2000-4500 ft [610-1372 m], de-rate by 5%. Consult local authorities for de-rating capacities for altitudes above 4500 ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m] over 2000 ft [610 m].
Section 9.0 for instructions on adjusting the input to provide proper operation. It is the Installers responsibility to check the combustion, and to adjust the combustion in accordance to Section 9.0. Failure to follow these instructions may result in property damage, serious injury, or death.
1
de-rate by 5% de-rate by 5% de-rate by 5% de-rate by 5% de-rate % may vary
2
- de-rate by 4% de-rate by 8% - de-rate by 12%
At elevations greater than 2000 feet, the combustion of the appliance must be checked with a calibrated combustion analyzer to ensure safe and reliable operation. Consult
6
Page 7
Front
Top Left Side
Right Side
Rear
Bottom
Lx Series Installation and Operation Instructions │
3.0 APPLIANCE LOCATION
Trinity Lx
In all cases, the Trinity Lx must be installed indoors in a dry location where the ambient temperature must be maintained above freezing and below 100°F [38°C]. Gas components must be protected from dripping, spraying water, or rain during operation and servicing. Consider the proximity of system piping, gas and electrical supply, condensate disposal drain, and proximity to vent termination when determining the best appliance location.
Floor Mounting
The Trinity Lx can be mounted directly on combustible flooring, with the exception of carpeting. Installing the appliance on carpeting is not permissible. Ensure the appliance is mounted above any anticipated flood level.
Water or flood damaged components must be replaced immediately with new factory­approved components as failure to do so may result in fire, serious injury, or death.
Appliance Area Ventilation Air Openings
If appliance area clearances are less then the recommended clearances specified in Table 3-1, the appliance area must be ventilated. Each ventilation air opening must meet the minimum requirements of 1 in2 per 1000 Btu/hr, but not less then 100 in2. The lower ventilation opening must be located within 6” of the floor while the upper opening must be located 6” from the top of the space.
Closet Installations
For closet installations, it is necessary to provide two ventilation air openings as shown in Figure 3-1(a) and (b), each providing a minimum area equal to 1 in2 per 1000 Btu/hr, but not less then 100 in2 and within 6” of the top and bottom of the closet door. All Vent and Air-Intake piping within the closet must be CPVC for both Canada and the US. See Table 3-1 for Minimum and Recommended Clearances.
Alcove Installations
Alcove installations have the same minimum clearances as closet installations, except the front must be completely open to the room at a distance no greater then 18” [457 mm] from the front of the appliance and the room is at least three (3) times the size of the alcove. Provided these conditions are met, the appliance requires no extra ventilation air openings to the space. See Table 3-1 for Minimum and Recommended Clearances.
Residential Garage Installations
When installed in a residential garage, mount the appliance a minimum of 18” [457 mm] above the floor. Locate or protect the appliance so it cannot be damaged by a moving vehicle. Check with your local authorities for other possible regulations pertaining to the installation of an appliance in a garage.
Wall Mounting Installations (Optional)
Each unit is shipped with wall mounting brackets to provide installers with the option of wall mounting the appliance. Refer to Figures 3-2(a) and 3-2(b) for instructions and illustrations on wall mounting the various models. Note that Water Heaters require "Mandatory Wall Mounting Protection". Refer to Section 1.0 in Appendix C, "Water Heater Applications: Plumbing & Wiring Instructions" for further details.
Table 3-1 Minimum Clearances for Installation and Service
Model No. Clearances
Trinity Lx150-200
Trinity Lx400
Notes:
1
6” if surface is removable allowing 24” [610 mm] clearance (i.e. closet installation). See Ventilation Air Opening dimensions in Figure 3-1.
2
Clearances can be as low as 12” [305 mm] if the right side has a clearance of 24” [610 mm].
3
Water Heaters require a minimum clearance of 36” [915 mm] in front for burner access (Lx200 and Lx400 only).
Minimum Recommended 24 [610] 24 [610] 24 [610] Minimum 24 [610] Recommended 24 [610] 24 [610] 24 [610]
24 [610]
1,3
1,3
Dimensions - inches [mm]
12 [305] 12 [305] 4 [102] 0 0
2
4 [102] 0 0
12 [305] 12 [305] 12 [305] 0 0
2
12 [305] 0 0
7
Page 8
Trinity Lx
1” [25 mm] clearance for hot water and vent pipes
Installation and Operation Instructions Lx Series
Figure 3-1(a) Lx150-200 Models
Closet Installation, Minimum Clearances
Piping must be CPVC
Top 12” [305 mm]
6” [152 mm] max. above vent opening
Ventilation Air Openings are not required if the appliance area meets the listed Recommended Clearances in Table 3-1.
Front 6” [152 mm] - Boilers Front 36” [915 mm] - Water Heaters
Closet Installation, Minimum Clearances
Figure 3-1(b) Lx400 Model
Left Side 12” [305 mm]
Piping must be CPVC
1” [25 mm] clearance for
Top 12” [305 mm]
hot water and vent pipes
Ventilation Air Opening 1 in2 per 1000 Btu/hr, min. 100 in2
Removable Surface or Closet Door
Ventilation Air Opening 1 in2 per 1000 Btu/hr, min. 100 in2
6” [152 mm] max. below vent opening
Right Side 4” [102 mm]
Ventilation Air Openings are not required if the appliance area meets the listed Recommended Clearances in Table 3-1.
Front 6” [152 mm] - Boilers Front 36” [915 mm] - Water Heaters
Closet/alcove installations in US and Canada require approved CPVC vent pipe, fittings, cements and primers (Table 4-3). Failure to comply may result in damage or serious injury.
8
6” [152 mm] max. above vent opening
Ventilation Air Opening 1 in2 per 1000 Btu/hr, min. 100 in2
Removable Surface or Closet Door
Ventilation Air Opening 1 in2 per 1000 Btu/hr, min. 100 in2
6” [152 mm] max. below vent opening
Right Side 12” [305 mm]
Left Side 12” [305 mm]
Page 9
Lx Series Installation and Operation Instructions │
may
Figure 3-2(a) Lx150-200 Models
Remove the upper wall mount bracket from the
back of the appliance.
Wall Mounting Installations
Failure to follow instructions result in fire, serious injury, or death.
Trinity Lx
Secure the upper wall mount bracket to a solid wall using field supplied lag screws (anchors when mounting on a concrete wall) that are adequate to support the weight of the appliance. Ensure the bracket is mounted in the level position. Refer to Table 2-1 Specifications for appliance weight.
Mount the appliance to the bracket by aligning the slots in the back of the appliance with the hooks protruding from the wall bracket. The top of the slots must rest at the bottom of the groove in the hooks of the wall mount bracket.
Pull the bottom of the unit away from the wall to allow the installation of the lower wall mount bracket (included with appliance). The bracket will snap into place using the slots provided in the bottom of the unit (ensure the snaps lock into place, once installed the bracket should not be easily removed).
Water Heaters require "Mandatory Wall Mounting Protection". Refer to Section 1.0 in Appendix C, "Water Heater Applications: Plumbing & Wiring Instructions".
This unit requires two people to lift it or damage and injury may result.
Ensure that the top of each slot rests on the bottom of the grooves in the wall bracket.
9
Page 10
may
it
Trinity Lx
While leaving the upper bracket intact (A), remove the wall mount bracket attached to the bottom-back of the appliance (B). Save the mounting hardware for Step 4.
Secure the wall mount bracket, removed from the bottom of the boiler in Step 1, to a solid wall using field supplied lag screws (anchors when mounting to a concrete wall) that are adequate to support the weight of the appliance (refer to Table 2-1 Specifications). Ensure the wall mount bracket is mounted level and flush to the wall with mounting holes on the bottom, flange pointed upward and angled away from the wall.
Mount the appliance to the wall by aligning the
upper bracket (A) with the wall mount bracket (B). Slide the upper bracket down over the wall mount bracket until it hooks.
Once the appliance is resting securely on the
upper bracket, secure the bottom bracket to the underside of the appliance using the mounting hardware removed in Step 1; then, anchor the bottom bracket to the wall as shown.
Installation and Operation Instructions Lx Series
Figure 3-2(b) Lx400 Model
Wall Mounting Installations
B
Failure to follow instructions result in fire, serious injury, or death.
This unit requires two people to lift or damage and injury may result.
A
B
Ensure that the upper bracket on the back of the appliance (A) slides down over the wall mount bracket (B) and rests securely on it.
Water Heaters require "Mandatory Wall Mounting Protection". Refer to Section 1.0 in Appendix C, "Water Heater Applications: Plumbing & Wiring Instructions".
B
A
10
Page 11
Lx Series Installation and Operation Instructions │
4.0 GENERAL VENTING
The Trinity Lx is a “Direct Vent” appliance requiring a “Special Venting System” designed for pressurized venting. Both the Vent and Air-Intake piping must be piped to the outdoors, using the vent material and rules outlined in this section. Under no conditions may this unit vent gases into a masonry chimney, unless it is vacant, and utilizes the approved venting material and rules described in this section. Installations must comply with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or CSA B149.1 (Canada) and local requirements.
Vent and Air-Intake to be piped separately. The Trinity Lx cannot share a common vent or air-intake with multiple appliances. Failure to comply will result in serious injury or death.
Combustion Air-Intake Contamination
Be careful not to locate the Air-Intake termination in an area where contaminants can be drawn in and used for combustion. Combustion air containing dust, debris or air-borne contaminants will drastically increase the required maintenance and may cause a corrosive reaction in the Heat Exchanger which could result in premature failure, fire, serious injury, or death. See Table 4-1 for a list of areas to avoid when terminating air-intake piping:
Table 4-1 Corrosive Products and Contaminant Sources
Products to Avoid Contaminated Sources to Avoid
Antistatic fabric softeners, bleaches, detergents, cleaners Laundry facilities Perchloroethylene (PCE), hydrocarbon based cleaners Dry cleaning facilities Chemical fertilizer, herbicides/pesticides, dust, methane gas Farms or areas with livestock and manure Paint or varnish removers, cements or glues, sawdust Wood working or furniture refinishing shops Water chlorination chemicals (chloride, fluoride) Swimming pools, hot tubs Solvents, cutting oils, fiberglass, cleaning solvents Auto body or metal working shops Refrigerant charge with CFC or HCFC Refrigerant repair shops Permanent wave solutions Beauty shops Fixer, hydrochloric acid (muriatic acid), bromide, iodine Photo labs, chemical / plastics processing plants Cement powder, crack fill dust, cellulose, fiber based insulation Concrete plant or construction site
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Failure to follow instructions may result in serious injury or death.
Flammable Solvents and Plastic Piping
Due to the extremely flammable characteristics of most glues, cements, solvents and primers used in the process of joining plastic vent and air-inlet pipe, explosive solvent vapors must be evacuated from the vent and air-intake prior to start-up. Avoid using excess cement or primer that may lead to pooling inside the pipe assembly. Freshly assembled piping assembly should be allowed to cure for a minimum of 8 hours before applying power to the gas fired appliance. Refer to Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.
Flammable Cements and Primers – It is the installers’ responsibility to familiarize themselves with the hazards associated with explosive solvents and to take all precautions
to reduce these risks. Failure to follow these instructions can cause explosions, property damage, injury or death.
Near Appliance Vent/Air-Intake Piping
Each Trinity Lx is equipped with a short piece of approved CPVC vent pipe. Insert one end into the appliance flue outlet adapter and cement the other to field venting (see Table 4-3 for approved venting material). The CPVC vent pipe should extend fully into the appliance flue outlet adapter (see Table 4-2). DO NOT insert PVC pipe directly into the flue outlet connection as it can deform from the clamping force of the gear clamp. Ensure that the venting system does not apply a load or strain on the appliance flue outlet adapter. The manufacturer recommends using two elbows to create a “swing joint” to reduce potential strain as shown in Figure 4-1(a), (b).
Gasket Seating - Improper seating can cause leakage and eventual failure of the sealing gasket. Failure to follow these instructions may result in serious injury or death.
Table 4-2 Mandatory Vent Pipe
Model No. CPVC Vent Pipe Size CPVC Vent Pipe Length Full Insertion Depth
Trinity Lx150-200 3” Minimum 5” [127 mm] 2-7/8” [73 mm] Trinity Lx400 4” Minimum 4” [100 mm] 1-7/8” [48 mm]
Trinity Lx
11
Page 12
Swing Joint
Coupling
Exhaust Vent
Flue Outlet
Air Inlet
3” Pipe *
Coupling
Mandatory Vent Pipe
-
CPVC, min. 5” long
Swing Joint
Exhaust Vent
Flue Outlet
Air Inlet
Coupling
Swing Joint
Exhaust Vent
Coupling
Flue Outlet
Air-Inlet
Man
dator
y Vent Pipe
-
Coupling
Exhaust Vent
Flue Outlet
Swing Joint
Coupling
Air-Inlet
4” Pipe *
Trinity Lx
Installation and Operation Instructions Lx Series
- to attain slope in horizontal runs
Figure 4-1(a) Lx150-200 Models Figure 4-1(b) Lx150-200 Models
Near Appliance Venting (CPVC) Near Appliance Venting (PVC)
attain slope in horizontal runs
- to
-
3” Pipe *
- 3” Removable (field supplied)
Near Appliance Venting (CPVC) Near Appliance Venting (PVC)
4”/6” CPVC
-
-
3” CPVC
- Stainless Steel Adapter (factory supplied)
- 3” Removable (field supplied)
(check local codes and Table 4-3)
3” (factory supplied)
Steel Adapter (factory supplied)
Figure 4-2(a) Lx400 Model Figure 4-2(b) Lx400 Model
attain slope in horizontal runs
-
- to
- 4”/6”
PVC (check local codes and Table 4-3)
attain slope in horizontal runs
PVC
- 3” PVC,
- 3” PVC
- Stainless
- to
- 4”/6”x4”
Steel Adapter (factory supplied)
90o elbow typical, or tee and drain cap option for easy cleanouts
In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection.
12
- Stainless
4” Pipe *
- 4” Removable (factory supplied)
4” CPVC, minimum 4” long (factory supplied)
90o elbow typical, or tee and drain cap option for easy cleanouts
Steel Adapter (factory supplied)
Removable (factory supplied)
- Stainless
- 4”
Page 13
Lx Series Installation and Operation Instructions │
1 2 3 4 5 6 7 8 9
Vent/Air-Intake Pipe Material
Table 4-3 Acceptable Vent and Air-Intake Pipe Material
Items 1
Vent Pipe and Fittings
Materials
PVC - DWV ANSI/ASTM D2265 PVC Schedule 40 ANSI/ASTM D1785
2, 3
CPVC Schedule 40 ANSI/ASTM F441
Pipe Cement
PVC ANSI/ASTM D2564 CPVC ANSI/ASTM F493
Primers
Notes:
1
Refer to Table 4-4 for Allowable Vent and Air-Intake Pipe Sizes and Lengths.
2
Closet/alcove installations in US and Canada require approved CPVC vent pipe, fittings, cements, and primers.
3
The Air-Intake does not require high temperature pipe material. Check applicable local codes for acceptable materials.
4
ULC S636 PVC is approved for flue gas temperatures up to 149oF (65oC) and must only be used for low temperature
PVC / CPVC ANSI/ASTM F656
applications. High temperature applications requiring appliance supply water temperatures greater than 140oF (60oC) must use ULC S636 approved CPVC.
Mandatory Pre-commissioning Procedure for Plastic Venting
Do not apply power to the appliance prior to Step 4 in the Mandatory Pre-commissioning Procedure for Plastic Venting.
1) Working with the power turned off to the appliance, completely install the vent and air intake system,
securely cementing joints together. If possible, allow primers/cements to cure for 8 hours before firing the burner. If curing time is less than 8 hours, proceed with Steps 2 through 6.
2) Maintain the appliance gas supply shut-off valve in the off position.
3) Disconnect electrical leads to the Hot Surface or Spark Igniter. Ensure the cables are placed in a fashion
where they will not arc to ground or other conductor.
Spark Igniter Cable - Maintain a minimum 2” separation between spark igniter circuit and
conductors. Failure to follow instructions may result in component failure, injury or death.
4) Turn power on to the appliance and apply a heat demand.
5) Allow for 3 complete trials for ignition, consisting of pre and post purge of the combustion blower, until an
ignition lockout occurs. Repeat the process two more times (i.e. 9 complete ignition sequences in total).
6) Turn power off and reconnect the electrical leads to the Igniter. Vent/Air-Intake Pipe Length Determination
Use Table 4-4 to determine the maximum pipe length that can be used. The table calculates sweep, 90º elbows, and 45º elbows at 5 equivalent feet [1.52 m] each. Allowable equivalent pipe lengths for vent and air-intake pipes are shown separately for Natural Gas and LP. Example: An Lx200 can be installed with 105 equivalent feet [32 m] of air-intake piping and 105 equivalent feet [32 m] of vent piping when operating with Natural Gas.
Table 4-4 Allowable Vent and Air-Intake Pipe Size and Lengths
Model No.
Trinity Lx150
Pipe
Size
Gas
3” Natural Trinity Lx150E Trinity Lx200
Trinity Lx400
3” LP
Natural
4”
& LP
Natural
6”
& LP
The length of one vent pipe (intake or exhaust) may not exceed the length of the other vent pipe by more than 20 equivalent feet (6.1 m). Length calculations need not include the three 90° elbows of the exterior vent
piping (two outlet, one inlet). When operating with Propane Gas (LP), the maximum vent length in equivalent feet is limited to 50’ (3” pipe), 30’ (4” pipe), and 65’ (6” pipe) depending on model number. See Table 4-4.
Length
ft. [m]
105
[32]
50
[15.2]
30
[9.1]
65
[19.8]
Installation Standards
United States
Canada 4
All venting material in
Canada must be
ULC S636 approved.
See Note 4 below for
appropriate temperature
applications.
All Vent and Air-Intake materials installed on gas fired appliances in CAN/US must meet the Standards listed in Table 4-3. Failure to comply could result in fire, serious injury or death.
Number of Elbows (90’s or 45’s) and Equivalent Feet [Meters]
100
[30.5]
45
[13.7]
25
[7.6]
60
[18.3]
95
[28.9]
40
[12.2]
20
[6.1]
55
[16.8]
90
[27.4]
35
[10.7]
15
[4.6]
50
[15.2]
85
[25.9]
30
[9.1]
80
[24.4]
25
[7.6]
10
[3.0] 5 [1.5]
45
[13.7]
40
[12.2]
75
[22.9]
20
[6.1]
70
[21.3]
15
[4.6]
- - - -
35
[10.7]
30
[9.1]
Trinity Lx
65
[19.8]
10
[3.0] 5 [1.5]
25
[7.6]
60
[18.3]
20
[6.1]
13
Page 14
Trinity Lx
Installation and Operation Instructions Lx Series
Two-Pipe Venting Options
Figure 4-3(a) Lx150-200
Two-Pipe Side Wall Termination
Figure 4-3(b) Typical for All Models
Two-Pipe Roof Termination
Figure 4-4(a) Lx400 Figure 4-4(b) Lx400 Only
Two-Pipe Side Wall Termination Two-Pipe Side Wall Termination (Optional Kit)
14
Page 15
Lx Series Installation and Operation Instructions │
Concentric Venting Options
Figure 4-5(a) Lx150-200
Concentric Side Wall Termination (Optional Kit)
Concentric Roof Termination (Optional Kit)
Figure 4-5(b) Lx150-200
Trinity Lx
Optional Termination Kits
Lx400 Side Wall Termination Kit
Use NTI part number 83236 (4” connections; if venting with 6”, must adapt down to 4” at interior trim piece).
Side-wall terminations only.
Instructions included with vent terminal contain more detailed assembly and installation instructions.
Concentric Vent Termination Kit - United States
Use NTI part number 82666 (York part number 1CT0303). Kits no longer approved for use in Canada.
Optional for Trinity models Lx150-200 only (not for use with Lx400).
Instructions included with vent terminal contain more detailed assembly and installation instructions.
Clearance requirements in this manual supersede those of the instructions included with the vent terminal.
Terminal MUST be cemented together during installation.
Concentric Vent Termination Kit - Canada
Use IPEX part number 196006 (Concentric Kit) and 196051 (Vent Screen), certified to ULC S636. Use of
this material is subject to approval by local authorities. Kit 82666/1CT0303 no longer approved for Canada.
Optional for Trinity models Lx150-200 only (not for use with Lx400).
Instructions included with termination kits contain more detailed assembly and installation instructions.
Clearance requirements in this manual supersede those of the instructions included with the vent terminal.
NTI does not stock System 636 PVC Concentric Vent Termination Kits as they are readily available from IPEX via Canadian wholesalers. Canadian customers wanting more information on System 636 Concentric Vent Kits or wholesaler locations can contact IPEX directly at 1-866-473-9462 (toll free in Canada) or www.ipexinc.com.
PVC In Canada - Safety authorities in some jurisdictions are not allowing PVC venting materials with appliances of any kind, even if System 636 certified. Check with the local
safety inspector to verify compliance prior to installing a PVC Concentric Vent Kit with a Trinity Lx appliance.
Venting Options - Due to potential moisture loading (build-up) along the exterior wall, sidewall venting may not be the preferred venting option. See Figures 4-3(b) and 4-5(b).
15
Page 16
mounts to exterior wall
(typical)
Boiler
Boiler
Boiler
Side-Wall
Termin
ation
Kit
wall Termination Kit
include vent screen, interior
Boiler
(fully assembled and installed)
Vent
Screen
Vent Screen
Screen
Air-Inlet
Trinity Lx
Installation and Operation Instructions Lx Series
Labeling and Identification – Side Wall Terminations
Figure 4-6(a) Typical for All Models
Two-Pipe Side Wall Termination
Figure 4-6(b) Lx400 Only
Two-Pipe Side Wall Termination (Optional Kit)
Gas Vent Directly Below
Keep Free of Obstructions
Exhaust
Vent
Vent
Venting
Insert vent screen into socket joint of termination elbow. Secure by cementing a short piece of venting into the socket.
Warning Plate
Combustion
Vent
Venting
Terminal
Exhaust Vent with Vent Screen
Labeling and Identification – Lx400 Side Wall Termination Kit
Figure 4-7 Lx400 Only
Two-Pipe Side Wall Termination (Optional Kit)
Gas Vent Directly Below
Keep Free of Obstructions
Warning Plate
Combustion Air-Inlet (between back of vent terminal and exterior wall)
Support Couplings / Reducer (must reduce down to 4” at this point if using 6” piping)
Exhaust Vent Piping
From
To
4” Thru-Wall Extension Piping
Combustion Air-Inlet
Vent Screen
Interior Trim
Framing within wall
Vent Terminal - 4” connections standard,
From
To
The Vent and Air-Inlet pipes are field supplied. Major components provided in the Side-
trim and vent terminal.
Side-Wall
Termination Kit
16
Page 17
Lx Series Installation and Operation Instructions │
connection
exhaust
Air-Inlet
Exhaust Vent
appliance
To appliance
End Cap
Vanes
Air-inlet
Exhaust Vent
Exhaust
Vent
Air-Inlet
Chimney
Labeling and Identification – Concentric Vent Kit
Figure 4-8(a) Lx150-200 Figure 4-8(b) Lx150-200
Concentric Vent Side Wall Termination Concentric Vent Detail with Vent Screen
Gas Vent Directly Below
Keep Free of Obstructions
Combustion Air-Inlet (perimeter)
Warning Plate
Concentric “Y” Fitting
Exhaust Vent Outlet (center)
End Cap
From exhaust
air-inlet connection
Combustion
(typical)
Insert vent screen between the end of the appliance exhaust vent and the end cap as shown.
Appliance Air-Inlet Pipe
Appliance Exhaust Vent Pipe
End Cap
Vent Screen (factory supplied with Kit). Refer to Optional Termination Kits.
The End Cap must be secured to the vent pipe via cement or stainless steel screws.
Trinity Lx
Labeling and Identification – Roof Top Terminations
Figure 4-9(a) All Models Figure 4-9(b) Lx150-200
Two-pipe terminations typically penetrate the roof surface. An alternative is to use an existing chimney as a chase way. See Figure 4-12 for more details.
Two-Pipe Roof Top Termination Concentric Vent Roof Top Termination
To prevent water leakage, install adequate roof weather seal flashing (not included) around roof penetration as shown.
Cap
Existing Chimney (used as a chase way)
Flashing
Roof weather seal flashing (field supplied)
Support (field supplied)
From appliance
24” [610 mm] from terminal end cap vanes
To appliance air-inlet
17
Page 18
Trinity Lx
Installation and Operation Instructions Lx Series
Venting Rules and Guidelines
1. Prevailing Winds: Ensure the vent is located where it will not be exposed to normal prevailing winds.
2. Combustion Air-Intake Contamination: Air for combustion must be drawn from outdoors from an area
free of dust and contaminants. Combustion air containing chemicals such as chloride, fluoride, bromine or iodine or dust and debris will cause corrosion damage of the heat exchanger voiding your NTI warranty. Refer to Table 4-1 for a list of corrosive products and contaminants sources to avoid.
3. Vertical Separation: The exhaust must be a minimum of 18” [457 mm] above the air inlet, and the air inlet
must always be a minimum of 12” [305 mm] plus snow allowance above any surface that will support snow. (Two feet plus snow allowance is highly recommended). Consult your weather office, for the maximum typical snowfall for your region.
Example: New Brunswick Canada - typical maximum snowfall is 19”, thus the inlet must be (12”+19”) =
31” above grade and exhaust must be (31”+18”) = 49” above grade.
4. Horizontal Separation: The horizontal distance between the inlet and exhaust must be a minimum of 4”
[102 mm] center to center. When the horizontal distance between the inlet and exhaust is greater than 12” [305 mm], the difference in horizontal distance must be determined and the vertical separation increased by the same amount.
Example: The horizontal distance (HD) = 24” [610 mm], and the vertical separation (VSmin) = 18” [457
mm], the new vertical separation (VSnew) can be calculated using the following equation: VSnew = (HD - 12”) + VS, where VSnew = (24” - 12”) + 18” = 30”. (If the horizontal distance is greater than 6’ [1.83 m], no additional vertical spacing is required. Vertical
separation is never required to be greater than 36” [915 mm].
5. Wall Flashing: Under normal operating conditions this appliance will produce a plume of white gases, and
should be taken into consideration when selecting an adequate location. A 36” [915 mm] diameter stainless,
plastic, or vinyl shield can be used to flash the exterior of the residence.
6. Flue Gas Hazard: Position the vent termination where vapors cannot make accidental contact with people
and pets or damage nearby shrubs and plants.
7. Elbow Extensions: Elbows on outside of wall must be no more than ½” [13 mm] away from the wall.
8. Vent Sloping: All indoor exhaust piping must be on a slope back to the appliance a minimum of ¼” per
linear foot of vent [6.25 mm per linear 305 mm]. For applications where excessive condensation is possible
½” per linear foot [13 mm per linear 305 mm] is recommended.
9. Vent Supports: Where required Vent and Air-intake piping shall be secured to the wall for more rigidity.
All interior vent pipe shall be supported a minimum of every 36” [915 mm]. If 6” diameter pipe is used
with the Lx400, it need only be supported every 48” [1.22 m].
10. Roof Exhaust: In all roof applications the discharge must point away from the pitch of the roof.
11. Roof Flashing: Install adequate flashing where the pipe enters the roof, to prevent water leakage.
12. Rain Cap: Install and seal a rain cap over existing chimney openings, in vacant chimney applications.
13. Venting Below Grade: For installations that exit the wall below grade refer to Figure 4-9.
14. Vent Screens: Install factory supplied vent screens on the outside of the last elbow for both the inlet and
exhaust vent terminal elbows. Install the screen into the female opening of the elbow. Then cut a small piece
of pipe to sandwich the screen into the elbow. NOTE be sure that the small piece of pipe cut, does not
extend past the end of the elbow. Two screens are provided in the package. See Figures 4-6(a) and (b) and
Figures 4-8(a) and (b).
15. Pipe Sizing: It is extremely important that the intake and exhaust vent piping be adapted to the appropriate
size immediately upon exiting the appliance cabinet. Refer to Table 4-2.
16. Condensate Hazard: Do not locate vent over public walkways, driveways or parking lots. Condensate
could drip and freeze resulting in a slip hazard or damage to vehicles and machinery.
17. Warning Plate: Install the warning plate “Gas Vent Directly Below”, directly above (within 4 ft [1.22 m]
vertically) the location of the air inlet pipe, so it is visible from at least 8 ft [2.4 m] away. See Figure 4-10.
18. Wall Thickness: Direct vent terminations are designed to work with any standard wall thickness.
Installation guidelines for min/max wall thickness are as follows: Min.= 1” [25mm], Max.= 60” [1.52 m].
19. Venting Options: Due to potential moisture loading (build-up) along the exterior wall, sidewall venting
may not be the preferred venting option. Refer to Figures 4-3(b) and 4-5(b) for alternative venting options.
18
Page 19
Lx Series Installation and Operation Instructions │
Chimney
Min.
above air
-
inlet
level
Figure 4-10 All Models
Venting Below Grade
Trinity Lx
For installations that exit the wall below grade:
1. Excavate site as shown in Figure 4-9, to a point
below where the pipes are to exit.
2. Ensure that the wall is fully sealed where the
pipes penetrate the wall.
3. The Vent/Air-intake piping MUST be secured
to the side of the building above grade, as shown, to provide rigidity.
4. NTI Provides a mounting bracket PN. 82075 for
securing the exhaust pipes.
5. Ensure that the Vent/Air-Intake clearances are
maintained, see Section 5.0 for details.
Figure 4-11 All Models
Outdoor Horizontal Venting
Vent piping outside the Building is permitted under the following conditions:
1. The maximum length outside the building is 20
feet [6.1 m]. Note that outdoor length must be included in the overall vent length calculation.
2. Only 3” pipe can be used for Lx150-200 models,
only 4” pipe can be used for the Lx400 model.
3. All normal termination clearances are maintained.
4. All exterior exhaust vent pipes are insulated with
3
½” [89 mm]
- ID for Lx150-200, or 4½”[114
mm] - ID for Lx400, ½” [13 mm] thick, Closed
Cell Foamed Polyolefin Tubing i.e., “Tundra Seal Plus” or equivalent.
5. The pipe is supported every 24” [610 mm].
6. The exhaust and inlet are sloped back to the
appliance ½” elevation for every linear foot [13 mm for every linear 305 mm].
Exhaust Vent
Air-Inlet
Gas Vent Directly Below
Keep Free of Obstructions
Apply Warning Plate here
Air-Inlet
12” [305 mm] plus snow allowance above
Exhaust Vent
Mounting Bracket
Supports every 24” [610 mm]
Maximum of 20 ft [6.1 m] is permitted for piping outside a building.
It is permissible to use an existing chimney as a chase way to run the Vent/Air-Intake piping as long as:
1. The chimney is not being used by any other
appliance.
2. Flue gases don’t enter the vacant chimney.
3. Only Trinity certified venting materials are used,
see Section 4.0.
4. Vent lengths are within the maximums specified.
5. The top of the chimney is capped and the
Vent/Air-Inlet pipes are flashed to prevent leakage into the vacant chimney.
Figure 4-12 All Models
Existing Chimney Chase Way
Cap
Existing Chimney (used as a chase way)
Exhaust Vent
Air-Inlet
Exhaust Vent 18” [457 mm]
Air-Inlet Min. 12” [305 mm] above roof / snow
19
Page 20
-
Trinity Lx
5.0 VENT/AIR-INTAKE TERMINATION CLEARANCES
Installation and Operation Instructions Lx Series
The quick reference table below is to be read in conjunction with the numbered notes as
indicated, Figures 5-1 through 5-6, and the Venting Rules and Guidelines in Section 4.0. The instructions detailed in this section are a combination of Trinity Lx specific and National Gas Code restrictions. Compliance alone doesn’t insure a satisfactory installation as good common sense must also be applied. Failure to follow these instructions may result in fire, property damage, serious injury or death.
Table 5-1 Termination Clearances Quick Reference Table
Clearances to Air-Inlet Termination
A Above grade/roofline and snow level 8 12 in. 305 mm 12 in. 305 mm
B Above roof line - Concentric Vent
6, 11, 13
24 in. 610 mm 24 in. 610 mm
C To exhaust vent from any other appliance 36 in. 915 mm 12 in. 305 mm
Clearances to Exhaust Vent Termination Min. Distance Min. Distance
D Minimum vertical separation above air inlet 9 18 in. 457 mm 18 in. 457 mm
E Minimum horizontal separation from air inlet 3 4 in. 102 mm 4 in. 102 mm
F Window, door or building opening 36 in. 915 mm 12 in. 305 mm G To combustion air inlet from any other appliance 36 in. 915 mm 12 in. 305 mm H Non-mechanical air supply inlet to building 36 in. 915 mm 12 in. 305 mm
I Mechanical air supply inlet to building 4 6 ft. 1.83 m 3 ft. 915 mm
J Soffit, overhang, eave or parapet 24 in. 610 mm 24 in. 610 mm
K Soffit vent or vent opening in an overhang, eave or parapet 6 ft. 1.83 m 6 ft. 1.83 m
L Outside corner 10
M Inside corner of an L-shaped structure (including walls and fences) 36 in. 915 mm 36 in. 915 mm
N Electric meters, gas meters, regulators and relief equipment 6 ft. 1.83 m 4 ft. 1.22 m
P Each side of center line above or below meters, regulators and relief devices 5 36 in. 915 mm 36 in. 915 mm Q Above a paved sidewalk, driveway, or parking lot on public property if adjacent
12
R Above a sidewalk, driveway, or parking lot on public property
S Above a sidewalk, driveway on private property between / serving both dwellings
T Under a concrete veranda, porch, deck, or balcony 7 24 in. 610 mm 24 in. 610 mm U Above, under or near exterior stairs V Into a canopy or carport
Notes:
1 - Canadian installations must comply with the current CSA B149.1 Natural Gas and Propane Installation Code and local
building codes. 2 - US installations must comply with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code and local building codes. 3 - Horizontal separation center-to-center (c.c.) 4”-12” (102-305 mm). Refer to “Venting Rules and Guidelines” for
horizontal separation > 12” c.c. as it may impact vertical separation clearances. 4 - For US installations, an exhaust vent may be 3 ft above a mechanical air supply inlet if within 10 ft. [3 m] horizontally. 5 - Horizontal clearance must be observed up to a height of 15 ft. [4.6 m] above/below the meter, regulator, or relief devices 6 - Concentric Vent must protrude from the roof precisely 24” [610 mm] measuring from the terminal end-cap vanes. 7 - Permitted if veranda, porch, deck, or balcony is made of concrete and a minimum of two sides are fully open beneath. 8 - 24” is the recommended snow level allowance above grade/roofline or any surface that will support snow, debris, or ice
(i.e. for roof venting clearances - roofline and snow level). If living in a snowfall region, consult your local weather
office for the maximum typical snowfall for your area. 9 - Note that the vent must maintain a minimum vertical distance above the air inlet. Example: Vent height = 18” (457
mm) above air inlet + 12” (305 mm) for air inlet above grade/roof line and snow level = 30” (762 mm) above grade and
snow level.
0 - Clearances to an outside corner to be in accordance with local installation codes. 11 - In Canada, concentric vent materials are subject to approval by local inspectors. See Termination Kits in Section 4.0. 12 - Above public walkways, driveways or parking lots if adjacent to it and condensate cannot drip, freeze, or create a hazard.
13 - Contact the manufacturer for special exemptions relating to multiple appliance installations using concentric vents.
X
- Not permitted by National gas code(s) and/or recommended by appliance manufacturer.
Canada 1 USA 2
Min. Distance Min. Distance
-
- -
7 ft. 2.13 m 7 ft. 2.13 m
X X X X X X X X
X X X X X X X X
.
20
Page 21
Lx Series Installation and Operation Instructions │
Figure 5-1 All Models
Termination Clearances Quick Reference Diagram
Trinity Lx
Illustrations of Termination Clearances
Side Wall Termination - Clearances Above Grade
Clearance “Q” Adjacent to Public Walkway or Driveway Minimum 7ft [2.13 m]
Figure 5-2 All Models
Two-Pipe Termination
F
G
Q
Clearances “F” and “G” Canada – Minimum 3 ft [915 mm] The US
– Minimum 1 ft [305 mm]
Concentric Vent Termination
G – Letter represents a specific Termination Position. Refer to Table 5-1 for corresponding termination clearances.
21
Page 22
From appliance
and snow
Combustion
5 mm] above
Trinity Lx
Installation and Operation Instructions Lx Series
Two-Pipe Side Wall Clearances Termination Kit Side Wall Clearances
Horizontal Separation 4-12” [102 mm – 305 mm] or greater than 36” [915 mm]
Vertical Separation
Minimum 18 [457 mm]
Minimum 12” [305 mm] above grade and snow level
Figure 5-3 All Models Figure 5-4 Lx400 Only
From appliance exhaust
To appliance air-inlet connection
Minimum 12” [305 mm] above grade and snow level
Figure 5-5 Lx150-200 Models Figure 5-6 Model Specific
Concentric Vent Side Wall Clearances
Roof Top Termination Clearances
Trinity Lx can also be vented through the roof. The
same clearances apply to roof-top terminations as
exhaust
for two-pipe sidewall terminations.
Air-Inlet (perimeter)
Exhaust Vent Outlet (center)
Min. 12” [305 mm] above grade and snow level
Minimum 12” [305 mm] above grade
To appliance air-inlet connection
Wall clearance must be 1” [25 mm] from end cap vanes to outside of wall
MIN. 18” [457 mm] above air-intake
MIN. 12” [30 snow level
24” [610 mm] above roof from end cap vanes
22
Page 23
Lx Series Installation and Operation Instructions │
Trinity Lx
Extra precaution must be taken to adequately support the weight of the Vent/Air-Intake
piping in applications using roof-top terminations. Failure to follow these instructions may result in venting or appliance component failure resulting in flue gas spillage leading to property damage, serious injury or death.
Under no circumstances may an existing chimney or chase-way be used to vent or provide combustion intake air to a Trinity Lx. Failure to follow these instructions will
result in fire, property damage, serious injury or death.
Removing an Existing Boiler from Common Venting System
Do not install the Trinity Lx into a common venting system with any other appliances. Failure to comply with this warning will cause flue gas spillage and leech carbon
monoxide emissions into the surrounding air resulting in serious injury or death.
When an existing boiler is removed from a common venting system, the common
venting system is likely to be too large for proper venting of the remaining appliances connected to it. Instructions have been provided on how to remove the existing boiler and how to resize the remaining venting system. Failure to follow these instructions may result in property damage, serious injury or death.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Steps to Removing an Existing Boiler
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch. Verify that there is no blockage,
restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close fireplace dampers, all building doors and windows and all doors between the
space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so
appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system
properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms
with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code.
23
Page 24
Drain Vent
Drain Pipe
Floor Drain
Trinity Lx
6.0 CONDENSATE DRAIN
Installation and Operation Instructions Lx Series
This unit produces liquid condensate in the heat exchanger and venting system as a product of combustion. Steps must be taken to ensure that condensate does not collect in the venting system; therefore, all exhaust piping must slope back to the appliance a minimum 1/4” per linear foot of vent. Condensate must be drained from the unit into a household drain.
Check with your municipality, or local gas company to determine if the disposal of
combustion condensate is permitted in your area (e.g. in the State of Massachusetts the condensate must be neutralized prior to entering a drain).
The following are important notes that must be taken into consideration when constructing the condensate drain system (See Figure 6-1 for further details):
DO NOT install condensate lines outside. A frozen or blocked drain will cause the condensate to fill the
combustion chamber. This will result in a no heat condition, as the unit will shut down, and damage to the flame sensor, and components can occur.
NEVER use copper, steel, or galvanized piping in the construction of the condensate system (condensate is
very corrosive and will corrode most metals).
When a condensate pump is used or required, select a pump that is designed for residential furnaces.
If the combustion chamber has been flooded due to the condensate drain backing up, or
for any other reason, the combustion chamber door must be removed and the inside of the appliance must be inspected for component damage, e.g. the internal insulation at the front and back of the chamber. Failure to follow these instructions may result in fire, property damage, serious injury or death.
Figure 6-1 All Models
Condensate Drain Piping
Do not block or install piping into the top branch of the condensate drain tee.
Connection to the bottom of the condensate drain tee must be made using 1/2” Schedule40 PVC pipe. Secure using appropriate PVC cement. All piping must be below the level where the condensate leaves the boiler.
Check with your local authorities regarding disposal of condensate (regulation may require the use of a neutralizer).
24
Page 25
Rigid Gas Line Piping
Flexible Gas Line Piping
Lx Series Installation and Operation Instructions │
7.0 INSTALLING GAS PIPING
Trinity Lx
The Trinity Lx is factory equipped to operate with Natural Gas, the installation of a
conversion kit is required prior to operating with Propane Gas. The Natural to LP Conversion Kit (see Table 7-1) must be installed prior to installing the gas piping to the appliance. Failure to properly convert the unit to operate with Propane may result in property damage, serious injury or death.
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that
your appliance is not installed in a pit or similar location that will permit heavier than air gas to collect. Check with Local Codes as they may require appliances fueled with LP gas be provided with an approved means of removing unburned gases from the room. Failure to follow these instructions may result in serious injury or death.
Table 7-1 Natural to LP Propane Conversion Kit
Series Model Kit Number
Trinity Lx Lx150, Lx150E, Lx200 82650-1 Trinity Lx
Lx400 83017-1
Installation
Refer to the current National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 installation codes, and local codes for gas piping requirements and sizing. Pipe size running to the unit depends on:
Length of pipe.
Number of fittings.
Type of gas.
Maximum input requirement of all gas appliances in the residence.
Figure 7-1 All Models
Gas Line Connection
Manual Shutoff Valve
Manual Shutoff Valve - Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
Union
Drip Leg
Recommended to eliminate strain on the appliance gas components (only use if acceptable by local codes).
Use only rigid gas line piping within the appliance cabinet. Rigid piping must protrude beyond the outside of the cabinet wall.
25
Page 26
Trinity Lx
Installation and Operation Instructions Lx Series
Ensure that:
The gas line connection to the appliance does not apply any weight to the gas valve. NTI recommends using
approved flexible gas piping (if acceptable by local codes) to connect the appliance to the gas supply (See Figure 7-1 for details).
You plan the installation so that the piping does not interfere with the vent pipe, or the removal of the valve,
burner, and serviceable components.
The Appliance shall be installed such that the gas ignition system components are protected from water
(dripping, spraying, rain etc.) during installation and servicing.
The gas piping is large enough for all the appliances in the home. No appreciable drop in line pressure
should occur when any unit (or combination of units) lights or runs. Use common gas-line sizing practices.
Always use a pipe-threading compound that is resistant to propane (LP) gas solvent action. Apply sparingly
to all male threads, starting at two threads from the end. Over doping or applying dope to the female end, can result in a blocked gas line.
DO NOT TIGHTEN FITTINGS WITHOUT SUPPORTING THE GAS VALVE as damage to the valve or
blower motor can occur.
Install a manual “Equipment Shut-Off Valve” as shown in Figure 7-1. Valve must be listed by a nationally
recognized testing lab.
The gas line piping can safely be removed from the appliance for servicing, by strategically placing the gas
line shutoff and union; see example in Figure 7-1.
All gas piping, including gas components in the appliance, are checked for leaks using a “Bubble Test”,
prior to operating the appliance.
Strain on the gas valve and fittings may result in vibration, premature component failure
and leakage and may result in a fire, explosion, property damage, serious injury or death.
Flexible gas piping cannot be used within the appliance cabinet and cannot pass through
the cabinet wall, use rigid piping as shown in Figure 7-1. Failure to follow these instructions may result in fire, property damage, serious injury or death.
Do not use an open flame to test for gas leaks. Failure to follow these instructions may
result in fire, property damage, serious injury or death .
When performing a pressure test on the gas line piping, be sure the appliance is
disconnected or isolated if the test pressure is expected to exceed 1/2 PSI (14” w.c.), as damage to the valve could occur resulting in fire, property damage, serious injury or death.
26
Page 27
Lx Series Installation and Operation Instructions │
8.0 LIGHTING THE APPLIANCE
Before Start-up refer to Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0. Failure to follow these instructions can result in explosions, injury or death.
Prior to turning the gas supply on and lighting the appliance, ensure all aspects of the
installation are complete and in conformance with the instructions provided in this manual, including the Vent/Air-Intake, Condensate Drain, and System Water Piping. Failure to precisely follow these instructions will cause a fire or explosion resulting in property damage, serious injury or death.
Do not store or use gasoline or other flammable vapors & liquids in the vicinity of this or any other appliance. Failure to follow instructions could result in explosion causing
property damage, serious injury or death.
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, serious injury or death.
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. Failure to follow instructions could result in explosion
causing property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING_
A) This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the been under water.
appliance and to replace any part of the
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the appliance.
3. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you don't smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the appliance.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Appliance” and call your service
technician or gas supplier.
TO TURN OFF GAS TO THE APPLIANCE_
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the appliance
3. Turn the manual gas valve to the OFF position
control system and any gas control which has
OPERATING INSTRUCTIONS_
Trinity Lx
27
Page 28
Trinity Lx
Installation and Operation Instructions Lx Series
The initial lighting of the appliance must be performed by a licensed Gas Technician. Failure to follow instructions may result in property damage, serious injury or death.
Ensure the appliance is wired in accordance with this manual.
Ensure the gas shut-off valve is turned on, and that the gas system has been fully tested for leaks.
Ensure the system is completely filled with water, and that ALL the air is purged out.
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8 hours, first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for
Plastic Venting in Section 4.0. Failure to follow these instructions can result in explosion, serious injury or death.
Initial Start-Up
1. Turn on power to the Trinity Lx and turn-up the Thermostat(s). The appliance should run through a purge,
and combustion should occur. (The control system has a built in ignition retry, allowing the system to try at least three times, before locking-out.)
2. With the unit operating at full capacity, verify that the gas line pressure is 4-10.5 inches w.c. for Natural gas,
and 9-13 inches w.c. for Propane (See Section 9.0 for details).
3. Using an appropriate Oxygen or Carbon Dioxide analyzer, take a sample of the flue gas. The sample must
fall within the acceptable ranges for Carbon Dioxide, which is 8.5% - 9.5% for Natural gas, and 9.5%-10.5% for propane (See Section 9.0 for details).
4. Perform at least three lights in succession to ensure proper operation.
5. After the three successive lights, unplug the flame probe, and allow the unit to cycle again. Ensure that it
tries to light, and locks out on safety reset. Once you have successfully activated the flame safety system, replace the wire on the flame sensor, and reconfirm proper lighting.
If the unit fails to light consistently and smoothly, contact NTI for assistance at 1-800­688-2575. Never allow the appliance to continue to operate if the ignition or operation
of the burner is rough or erratic. Failure to follow these instructions could result in serious injury or death.
The flame probe uses a single electrode located in the burner door at the 6 O’clock
position. DO NOT remove the wire from the dual electrode located in the burner door at the 3 O’clock position; this device is used for spark igniting and delivers a high voltage potential which would result in an EXTREME ELECTRICAL SHOCK possibly causing serious injury or death.
Re-lighting Unit
1. Stop and read these instructions very carefully.
2. Set the thermostat to the lowest setting, and then turn off all power to the appliance.
3. This appliance does not have a pilot. It is equipped with an ignition device that automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the gas shut-off valve to the off position, and then remove the front cover.
5. Wait five (5) minutes to clear out any gas. Then check for gas, including near the floor. If you smell gas
“Stop” and follow “B” above. If you don’t detect any gas proceed to the next step.
6. Turn the gas shut-off valve to the on position, wait an addition five (5) minutes and check for gas.
7. Replace the front cover.
8. Set the thermostat to the highest setting, and then turn on all power to the appliance.
9. Ignition sequence is automatic, combustion will occur after a brief fan purge. Ignition will retry 3 times.
10. If ignition does not occur, “Turn off the gas and electricity to the appliance” and contact a professional
service technician, or gas supplier.
Turning Off The Appliance
1. Set the thermostat to the lowest setting, and then turn off all power to the appliance.
2. Turn the gas shut-off valve to the off position.
28
Page 29
Lx Series Installation and Operation Instructions │
9.0 GAS VALVE AND BURNER SET-UP
Trinity Lx
Set-up of the Trinity Lx gas valve must be performed by a licensed Gas Technician.
Failure to perform the set-up correctly may result in incorrect operation, component failure, property damage, serious injury or death.
Gas Line Pressure
The appliance gas valve is equipped with a line pressure test port; see Figures 9-1 and 9-2. Use the following procedure to measure the gas line pressure to the appliance to ensure if falls within the range given in Table 9-1:
1. Turn the supply of gas to the appliance off.
2. Open the bleed screw of the line pressure test port approximately 1-1/2 turns. This port is directly
connected to the gas line feeding the appliance.
3. Force 1/4" ID tubing over the housing of the line pressure test port; install the other end of the tubing to an
appropriate line pressure test gauge or manometer. Ensure both ends of the tubing make a tight connection.
4. Open the supply of gas to the appliance and check for gas leaks.
5. Observe the line pressure under static conditions and compare it to Table 9-1. The pressure will be greatest
under static conditions.
6. With all other gas appliances in the applications running, operate the burner to the maximum firing rate
(See Table 9-2) and compare the observed line pressure with Table 9-1. The pressure will be lowest during the maximum flow of gas.
7. Adjust the gas line pressure to ensure the parameters in Table 9-1 are attained under all conditions. If
possible adjust the line pressure to the "Nominal/Desired" value listed in Table 9-1, while the unit is operating at the maximum modulation rate, see Table 9-2.
8. Continue observing the gas line pressure until the completion of the combustion analyses, incase
adjustments need to be made.
9. Upon completion of the line pressure testing, return the bleed screw of the Line Pressure Test Port to the
closed position.
The line pressure is a function of the gas supply and is affected solely by field provided
parameters such as line size and regulator settings. Under no circumstances can the appliance gas valve influence or be used to adjust the gas line pressure.
Failure to close the bleed screw of the Line Pressure Test Port will cause a severe leakage of gas, resulting in a fire or explosion causing property damage, serious injury or death.
Table 9-1 Line Pressure and Combustion Parameters
Gas
Natural
Propane
Line Pressure (inches wc) CO2 (%)*
Nominal/Desired Min. Max. Min. Max.
7 4 10.5 8.5 9.5 175
11 8 13 9.5 10.5 175
CO (ppm)
Max.
*Note: it is permissible to have higher CO2 values with the burner operating at the minimum modulation rate.
Table 9-2 Minimum and Maximum Modulation Rates
Model Min. Modulation Rate (RPM) Max. Modulation Rate (RPM)
Lx150 1150 5850 Lx150E 925 4450 Lx200 925 5950 Lx400 1550 7200
Never leave the unit operating while producing Carbon Monoxide (CO) concentrations in
excess of 175ppm. Failure to follow this warning may result in serious injury or death.
DO NOT adjust or measure the Manifold Pressure of the appliance. Correct manifold
pressure is factory set. Field adjustment could result in improper burner operation resulting in fire, explosion, property damage or death.
29
Page 30
Test Port
Test Port
Trinity Lx
Manifold Pressure
Installation and Operation Instructions Lx Series
Figure 9-1 Lx150 Orientation
Gas Valve and Venturi Assembly
Orifice Location (See Kit 82650-1)
Throttle/Input Adjustment Screw
Line Pressure Test Port
Venturi
Figure 9-2 Lx150E and Lx200 Orientation
Gas Valve and Venturi Assembly
(Front View)
Gas Valve
Gas In
(Front View)
Line Pressure Test Port
Manifold Pressure
Gas Valve
Gas In
Venturi
Throttle/Input Adjustment Screw
Orifice Location (See Kit 82650-1)
30
Page 31
Lx Series Installation and Operation Instructions │
Figure 9-3 Lx400 Orientation
Gas Valve and Venturi Assembly
(Front View)
Manifold Pressure Test Port
Throttle/Input Adjustment Screw
Line Pressure Test Port
Orifice Location (See Kit 83017-1)
Trinity Lx
Gas In
Venturi
Gas Valve
31
Page 32
Turn Clockwise
Turn Clockwise
Trinity Lx
Adjustment
Installation and Operation Instructions Lx Series
Input Screw Adjustments - The appliance is equipped with a Throttle/Input Adjustment Screw, located on the
Gas Valve and Venturi Assembly. The Throttle screw is used to adjust the flow of gas leaving the gas valve, entering the Venturi and hence entering the combustion air stream. By turning the adjustment screw in, clockwise, the flow of gas is reduced and the combustion becomes leaner, thus reducing the concentration of CO2 in the flue gases. To increase the CO2 the Throttle screw must be adjusted out, counterclockwise, thus increasing the flow of gas from the gas valve to the combustion air stream.
Lx150-200 Adjustments - The input screw for models Lx150-200 is a multiple turn valve. Fully open to close is approximately 17 turns. Typical adjustment for Natural Gas is 0-1 full turns in or out. Typical adjustment for LP Gas is 0-3 full turns in or out. See Figures 9-1 and 9-2 for input screw location.
Lx400 Adjustments - The input screw for the Lx400 is a geared valve with a 4:1 ratio. Adjusting input screw 4 complete turns will returned the valve to the original location, 2 turns from fully open will completely close the valve. Typical adjustment required is 0-1/4 turns in or out. See Figure 9-3 for input screw location.
Decrease gas
Throttle/Input Adjustment Screw
Increase gas
Adjustments to the Throttle screw may only be made by a qualified gas technician, while
using a calibrated combustion analyzer capable of measuring CO2 and CO. Failure to follow these instructions may result in serious injury or death.
Adjustments to the Throttle screw may only be performed if the gas line pressure is
maintained above minimum levels throughout the duration of the test; see Table 9-1. Failure to follow these instructions may result in serious injury or death.
Combustion Calibration - To calibrate burner operation, perform the following procedure using a calibrated combustion analyzer capable of measuring CO2 and CO from Natural and Propane Gas burning appliances:
1. Operate the unit at the maximum modulation rate, see Table 9-2.
2. Ensure the gas line pressure is maintained within tolerance, see Table 9-1.
3. While at the maximum modulation rate, measure the CO2 and CO; adjust as necessary, using the Throttle
Screw, to be within the limits listed in Table 9-1.
4. Operate the unit at the minimum modulation rate (Table 9-2). Ensure the combustion remains smooth and
CO2 and CO remain within the limits (Table 9-1). If not, do not adjust further, contact NTI for assistance.
Flue Gas Analysis and Adjustment
Each Trinity Lx is factory set to operate with Natural Gas, for appliances field converted to operate with Propane Gas, a flue gas analysis and adjustment is mandatory. See Table 7-1 and propane conversion instructions.
Failure to perform the flue gas analysis and adjustment detailed in this section may result
in erratic and unreliable burner operation, leading to reduced efficiency, increased fuel consumption, reduced component life, heat exchanger combustion deposits, and general unsafe operation. Failure to follow these instructions may result in serious injury or death.
Analysis – The Trinity Lx is equipped with a flue gas test port located in the flue outlet adapter assembly. For models Lx150-200, test port access is from within the appliance cabinet (Figure 9-3). For Lx400 model, test port access is from outside the appliance cabinet (Figure 9-4). Remove the test port plug and perform the flue gas analysis and adjust modulation rate as required until CO2 and CO levels are within acceptable limits. Once flue gas sampling is completed, re-install the test port plug and seal the threads using Teflon tape.
Failure to re-install the test port plug will result in damage to the unit, property damage, fire, explosion, serious injury or death.
32
Page 33
Lx Series Installation and Operation Instructions │
Combustion
Combustion
Figure 9-3 Lx150-200 Models
Flue Gas Sampling Using Test Port
Test Port
Analyzer
Trinity Lx
Figure 9-4 Lx400 Model
Flue Gas Sampling Using Test Port
Test Port
Analyzer
33
Page 34
Trinity Lx
10.0 WIRING SCHEMATICS
Installation and Operation Instructions Lx Series
Figure 10-1(a) All Models
Connection Diagram
34
Page 35
Lx Series Installation and Operation Instructions │
Figure 10-1(b) All Models
Ladder/Logic Diagram
Trinity Lx
35
Page 36
Trinity Lx
11.0 INSTALLATION CHECKLIST
Installation and Operation Instructions Lx Series
Installation
1. If operating on Propane Gas, convert appliance using kit number 82650-1. 2. Locate the appliance in accordance with Section 3.0 of this manual. 3. Install the Vent/Air-Intake piping in accordance with Sections 4.0 and 5.0 of this manual. Ensure all
joints are secured and cemented properly. Both the Vent and Air-Intake pipes must terminate outdoors. Perform the Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.
4. Connect the condensate drain in accordance with Section 6.0 of this manual. 5. Connect the gas supply in accordance with Section 7.0 of this manual. 6. Install the plumbing in accordance with the appropriate Applications Manual (Boiler or Water Heater)
Flush/cleanse the internals of the heating system. Boiler Application - treat system water with Fernox F1 Protector. See Table 2-1 in Appendix B.
7. Connect field wiring in accordance with Section 9.0 of this manual. 8. Advise home/building owner of their responsibilities with respect to maintaining the appliance.
The building owner is responsible for keeping the Vent/Air-Intake termination free of snow, ice, or other potential blockages and for scheduling routine maintenance on the
appliance (see Section 14.0). Failure to properly maintain the appliance may result in serious injury or death.
Start-up
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8 hours, first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for
Plastic Venting in Section 4.0. Failure to follow these instructions can result in explosion, serious injury or death.
1. Turn gas shut-off valve to the ON position. 2. Turn Power on to appliance. 3. Set Controller to the desired settings. 4. Turn thermostat up, Ignition will occur.
Operational Checklist
1. System is free of gas leaks. 2. System is free of water leaks. 3. Water pressure is maintained above 15 PSI. 4. All air is purged from the heating system piping. 5. Ensure proper water flow rate; unit must not kettle, bang, hiss or flash the water to steam. 6. Ensure gas line pressure is in accordance with Section 9.0. 7. System is free of combustion leaks. 8. Unit must operate smoothly. 9. Ensure the flue gas combustion readings are within the tolerances listed in Table 9-1. 10. Each ignition must be smooth.
11. Verify that all condensate lines are clean and drain freely.
Before Leaving
1. Remove line pressure gauge from gas valve, tighten bleed screw, test screw for leaks. See Section 11.0. 2. Install plug into the flue gas test port and test for leaks, see Section 11.0. 3. Allow the appliance to complete at least one heating cycle, or to operate for at least 15 minutes. 4. Always verify proper operation after servicing.
Instructions to Installing Contractor
1. Ensure that the customer receives the Warranty Documentation included with the installation manual. 2. Leave the manual with the customer so they know when to call for annual maintenance and inspection.
This appliance must have water flowing through it whenever the burner is firing. Failure to comply may damage the unit, void the warranty, and cause serious injury or death.
Allowing the appliance to operate with a dirty combustion chamber will adversely affect its operation and void the warranty. Failure to clean the heat exchanger on a frequency
that matches the need of the application may result in fire, property damage, or death.
36
Page 37
Lx Series Installation and Operation Instructions │
12.0 ANNUAL MAINTENANCE AND INSPECTION
This unit must be inspected at the beginning of every heating season by a Qualified Technician.
Annual Inspection Checklist
1. Lighting is smooth and consistent, and the combustion fan is noise & vibration free. 2. The condensate freely flows from the unit, and is cleaned of sediment. 3. Relief Valve and air vents are not weeping. 4. Low water cut off is flushed (if applicable) 5. Examine all venting for evidence of leaks. Ensure vent screens are cleaned and clear of debris. 6. Check the burner plate for signs of leaking. 7. The combustion chamber must be inspected and cleaned. 8. Listen for water flow noises indicating a drop in appliance water flow rate.
Important Boilers Only - The hydronic system may need to be flushed to eliminate hard water scale (Use Fernox DS-40 Descaler, NTI PN: 83450. See Table 2-1 in Appendix B - Boiler Applications).
Boiler Only - Boiler system cleansers and corrosion inhibitors must not be used to flush
contaminants from water heaters or potable water systems.
Combustion Chamber Cleaning Procedure
Units operating with LP Gas or in an industrial environment will have to be cleaned a minimum of once per year. Other applications will require the combustion chamber to be cleaned after the first year of operation, with subsequent cleanings scheduled based on the condition of the combustion chamber at the time. Unless a step is identified as model specific, the following combustion chamber cleaning procedure is the same for all models.
Crystalline Silica - Read carefully the warnings and handling instructions pertaining to
Refractory Ceramic Fibers before commencing any service work in the combustion chamber. Take all necessary precautions and use recommended personal protective equipment as required.
1. Initiate a post-purge cycle to clear any gas from the combustion chamber, then turn gas valve off. 2. Lx400 only: Danger Explosion Hazard. To disconnect the metallic tubing between the blower and the
high-vent pressure switch, loosen the compression fitting at the high-vent pressure switch with a 1/2" wrench. At the blower end, support the brass fitting body with a 1/2" wrench to keep it from rotating while loosening the compression fitting nut with a 9/16" wrench. Remove tubing assembly from blower.
3. Access the combustion chamber by removing the aluminum burner door assembly of the appliance. 4. Remove the insulation disc (P/N 83112) located in the back of the combustion chamber to avoid
damaging it during the cleaning process. The disc is held in place with a 2.5mm "Allen-head" screw.
5. Use a vacuum with a high efficiency filter to remove any loose debris or dust. 6. Wet the inside of the combustion chamber with water. Use a garden hose with a trigger nozzle to direct
pressurized water through the gaps between the heat exchanger tubes. The water should pass in-between the heat exchanger tubes and exit via the condensate drain. This process may require the use of some dry rags or plastic to protect electrical components from being damaged by dripping or spraying water. 7. Use a nylon or other non-metallic brush to loosen the incrustations and any other contaminates that have
remained stuck on and in-between the tubes.
8. Repeat steps 6 and 7 until the heat exchanger is clean and water from the condensate drain runs clear. 9. Re-install the insulation disc (part no. 83112) to the back of the combustion chamber. 10. Inspect the insulation disc located on the back-side of the burner door (p/n 83884). Replace if damaged. 11. Re-install the burner door, gas-supply and Air-inlet pipe, check for gas leaks. 12. Lx400 only: Reconnect the metallic tubing between the blower and the high-vent pressure switch.
Ensure the brass fitting body at the blower remains stationary and does not rotate during reconnection.
13. Perform the Operational Check List detailed in Section 13.0.
Explosion Hazard (Lx400 models) - The metallic tubing connecting the blower and the high-vent pressure switch contains Fuel/Air Mixture. Refer to Combustion Chamber
Cleaning Procedure for instructions on connecting and disconnecting the metallic tubing. Failure to follow these instructions will result in serious injury or death.
Replace any gaskets or insulation discs that show any signs of damage and do not re-use.
Failure to follow these instructions may result in fire, property damage or death.
Trinity Lx
37
Page 38
Trinity Lx
Installation and Operation Instructions Lx Series
Refractory Ceramic Fibers (RFC)
Personal Protective Equipment Recommended - Read the following warnings and
handling instructions carefully before commencing any service work in the combustion chamber. The insulating material on the inside of the burner door and at the back of the combustion chamber contain Refractory Ceramic Fibers and should not be handled without personal protective equipment.
Potential Carcinogen - Use of Refractory Ceramic Fibers in high temperature
applications (above 1000oC) can result in the formation of Crystalline Silica (cristobalite), a respirable silica dust. Repeated airborne exposure to crystalline silica dust may result in chronic lung infections, acute respiratory illness, or death. Crystalline silica is listed as a (potential) occupational carcinogen by the following regulatory organizations: International Agency for Research on Cancer (IARC), Canadian Centre for Occupational Health and Safety (CCOHS), Occupational Safety and Health Administration (OSHA), and National Institute for Occupational Safety and Health (NIOSH). Failure to comply with handling instructions in Table 14-1 may result in serious injury or death.
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to Table 14-1 for handling instruction and recommended personal protective equipment. Installation and service must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the supplied instructions before installing, servicing, or removing this appliance. This appliance contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans).
Table 14-1 Handling Instructions for Refractory Ceramic Fibers (RCF)
Reduce the Risk of Exposure Precautions and Recommended Personal Protective Equipment
Avoid contact with skin and eyes Avoid breathing in silica dust
Wear long-sleeved clothing, gloves, and safety goggles or glasses.
Wear a respirator with a N95-rated filter efficiency or better. 1
Use water to reduce airborne dust levels when cleaning the combustion chamber.
Do not dry sweep silica dust. Pre-wet or use a vacuum with a high efficiency filter.
Avoid transferring contamination
When installing or removing RFCs, place the material in a sealable plastic bag.
Remove contaminated clothing after use. Store in sealable container until cleaned.
Wash contaminated clothing separately from other laundry.
First Aid Measures
If irritation persists after implementing first aid measures consult a physician.
Skin - Wash with soap and water.
Eyes - Do not rub eyes; flush with water immediately.
Inhalation – Breathe in fresh air; drink water, sneeze or cough to clear irritated
passage ways.
Notes:
1
Respirator recommendations based on CCOHS and OSHA requirements at the time this document was written. Consult
your local regulatory authority regarding current requirements for respirators, personal protective equipment, handling, and disposal of RCFs.
For more information on Refractory Ceramic Fibers, the risks, recommended handling procedures and acceptable disposal practices contact the organization(s) listed below:
Canada (CCOHS): Telephone directory listing
under Government Blue Pages Canada—Health and Safety—Canadian Centre for Occupational Health and Safety; or website http://www.ccohs.ca.
38
United States (OSHA): Telephone directory listing under United States Government—Department of Labor—Occupational Safety and Health Administration; or website http://www.osha.gov.
Page 39
Lx Series Installation and Operation Instructions │
13.0 PARTS LIST
Trinity Lx
Building owners must contact their local Installer or Wholesaler. Replacement parts are available from your stocking wholesaler. Installers or Wholesalers may contact NY Thermal Inc. for assistance at 1-506-657-6000.
Figure 13-1(a) Lx150-200 Models
Cabinet, Vent and Air-Intake Parts
41
44
43
76
47
46
45
48
38
39
49
50
64
73
75
37
40
55
72
53
66
39
Page 40
58
62
81
68
65
58
8
19
36
34
2
Trinity Lx
Installation and Operation Instructions Lx Series
Figure 13-1(b) Lx150-200 Models
22
23
28
21
24
29
Heat Exchanger, Gas Valve, Blower and Burner Assembly
20
16
12
17
15
13
11
18
25
26
27
31
33
14
9
7
5
6
4
10
3
30
32
11
1
Figure 13-2 Common to All Models (Lx150-400)
Electrical Housing, Controller, and Display Module
58
61
60
63
59
56
54
70
57
71
40
52
51
67
69
Page 41
Lx Series Installation and Operation Instructions │
Figure 13-3(a) Lx400 Model
Cabinet, Vent and Air-Intake Parts
Trinity Lx
47
45
39
41
76
44
75
48
42
73
46
78
74
50
37
49
72
77
41
Page 42
5
10
34
31
28
24
18
17
16
9
15
14
26
Trinity Lx
Installation and Operation Instructions Lx Series
Figure 13-3(b) Lx400 Model
Heat Exchanger, Gas Valve, Blower and Burner Assembly
19
35
20
25
29
33
32
11
36
30
1
6
79
2
13
8
7
Table 13-1 Parts List: Lx150-400 Models
Item Part # Models Description
1 82657 150 Premix burner 135.8 (Lx100-150; not Lx150E) 1 82658 150E, 200 Premix burner, 200.6 (Lx150E, Lx200) 1 83173 400 Premix burner, 327 (Lx400) 2 82761 All Models Premix Burner Gasket (Lx Series) 3 82771 150,150E,200 Extended Air Tube (Lx100-200) 3 83195 400 Extended Air Tube (Lx400) 4 82766 All Models Blower Gasket (Lx Series) 5 82052 150 EBM Blower RG130 (Lx100-150, not Lx150E) 5 82661 150E,200 EBM Blower RG148/1200-3633 (Lx150E, Lx200) 5 82994 400 EBM Blower RG148/Enhanced (Lx400) 6 82054-2 150,150E,200 CVI Venturi Gasket 6 83106 400 O-ring, Venturi to Blower (Lx400) 7 82054-1 150,150E,200 CVI Venturi 01 (Lx150-200) 7 82990 400 CVI Venturi (Lx400) 8 82650 150,150E,200 CVI 5.20mm Orifice #45.900.444.107B (field installed on LP converted units) 8 82993 400-NG Gas Valve Orifice, 8.0mm, NG (Lx400) 8 83017 400-LP Gas Valve Orifice, 6.2mm, LP (Lx400) 9 82054 150,150E,200 Gas Valve (CVI) VK8115F1134B (Valve Only)
4
3
13
42
Page 43
Lx Series Installation and Operation Instructions │
Item Part # Models Description
9 82989 400 Gas Valve VR8615VB 1044B (Lx400) 10 83870 All Models Ignition Electrode, Dual – c/w gasket (Lx Series) 11 82774 All Models Flame Probe Gasket (Lx Series) 12 82600 150,150E,200 Gas Valve Regulator Vent Adapter 13 83883 150,150E,200 CVI Gas Valve Inlet O-ring Gasket 13 83194 400 Gas Valve Connector O-ring, Large (Lx400) 14 82065 150,150E,200 Gas Valve (CV1) 1/2" NPT elbow #45.900.400-132B 14 82991 400 Gas Valve Adapter 45900400-138B, 3/4" NPT (Lx400) 15 83606 All Models Outlet Sensor, Dual (Lx Series) 16 83223-1 All Models Low Water Pressure Switch, 1/4" NPT (Lx Series) 17 83462 150,150E,200 Street Tee, Brass, 1/4" 17 82698 400 1/4" NPT Brass Tee (Lx400) 18 83007 All Models 19 82539 All Models 20 83608 All Models 21 82765 150,150E,200 Composite Flue Outlet Gasket (Lx100-200) 22 82763 150,150E,200 Composite Flue Box (Lx100-200) 23 82764 150,150E,200 Trinity Flue Box to Heat Exchanger Gasket 24 83605 All Models 25 83706 All Models Plug, Brass, 1/4" NPT (Lx Series) 26 83395 150 – CAN Heat Exchanger (CAN - Lx100-150, not Lx150E) – Canada Only 26 83012 150 – US Heat Exchanger-ASME (US - Lx100-150, not Lx150E) – US Only 26 83396 150E, 200 Heat Exchanger-ASME (Lx200, Lx150E) 26 82926 400 Heat Exchanger-ASME (Lx400) 27 83042 150,150E,200 Y-Drain Fitting 5/8", White 28 83721 All Models 29 83720 All Models 30 83715 150,150E,200 Condensate Drain Tube (Lx150-200) 30 83907 400 Condensate Drain Tube (Lx400) 31 83112 All Models 32 82770 All Models 33 83808 150,150E,200 Burner Door Ceramic Disc (Lx150-200) 33 83950 400 Burner Door Ceramic Disc (Lx400) 34 83885 150,150E,200 Cast Alum Burner Door (Lx150-200) 34 83949 400 Cast Alum Burner Door (Lx400) 35 83934 400 Nipple, 1/4" x 6", Brass 113-B6 (Lx400) 36 82762 All Models 37 82099 150,150E,200 1-1/2" MJ Coupling 37 83951 400 2" Gear Clamp Assembly (Lx400) 38 83425 150,150E,200 Elbow, Street 90, PVC Sys 15,1-1/2" 39 83426-1 150 – US 1-1/2" PVC Pipe, Sys 15, 1.75" Long 39 83426-2 150E,200 1-1/2" PVC Pipe, Sys 15, 4.5" Long 39 83952 400 Air Inlet Assembly (Lx400) 40 83425-1 150,150E,200 Air Metering Elbow (Lx150-200) 41 83712 150,150E,200 Flue Outlet Adapter (Trinity Lx 3” PVC), c/w plug 41 83213 400 Flue Outlet Adapter (Lx400) 42 82882 400 Coupling, Rubber , 4", Fernco (Lx400) 43 83477 150,150E,200 Bushing, PVC Sch. 40, 3"x1.5" 44 83712-1 150,150E,200 3/8" Stainless Steel Plug 44 83034 400 Exhaust Test Plug (Lx400)
1/4"x 1/8" Bushing Brass (Lx Series) Automatic Air Vent 1/8" (Lx Series) Flue Sensor, Dual (Lx Series)
Inlet Sensor, Single (Lx Series)
Tee, PVC, 1/2", Sch.40, White (Lx Series) Elbow, Street, PVC, 1/2", Sch.40, White (Lx Series)
Trinity Divider Plate Insulation c/w Washer & Screw (Lx Series) Burner Door Viton Gasket (Lx Series)
Flame Rod Rauschert (Lx Series)
Trinity Lx
43
Page 44
Trinity Lx
Item Part # Models Description
45 83873 150,150E,200 TiS Wall Mount Bracket 2 (Lx150-200) 45 83953 400 Wall Mounting Clip (Lx400) 46 83505 150,150E,200 Grommet, Vinyl, 7/8" OD 46 83923 400 Grommet, Vinyl, 3/4" OD (Lx400) 47 83506 150,150E,200 Grommet, Vinyl, 1-3/8" OD 47 83924 400 Grommet, Vinyl, 2" OD (Lx400) 48 83874 150,150E,200 TiS Air Switch Support Clip II (Lx100-200) 48 83954 400 Air Switch Bracket (Lx400) 49 82662 All Models Air Switch Huba 604.E021180 set @ .15" w.c. (Lx Series) 50 83875 150,150E,200 TiS Wall Stand-Off - Bottom (Lx150-200) 50 83955 400 Wall Mounting Support, Bottom (Lx400) 51 83508 All Models Display Molding (Lx Series) 52 83592 All Models Trinity Touch Screen Display (Lx Series) 53 83876 150,150E,200 Electrical J-box Cover R1, Left (Lx100-200) 54 83872 All Models Barrier Strip, Line Voltage (Lx Series) 55 83877 150,150E,200 Electrical J-box, Line Voltage (Lx100-200) 56 83707 All Models Ignition Coil Q652B1006/B (Lx Series) 57 83724 All Models Spark Igniter Wire, 12" (Lx Series) 58 82250 All Models SNAP BUSHING, 1" (Lx Series) 59 83592-1 All Models Power Supply – Touch Screen (Lx Series) 60 83190 All Models 61 83589 All Models 62 83878 All Models 63 83879 All Models 64 83880 150,150E,200 Electrical J-box, Low Voltage (Lx150-200) 65 83871 All Models Barrier Strip, Low Voltage (Lx Series) 66 83876-1 150,150E,200 Lx150-200 Electrical J-box Cover R1 (Right) 67 83517 All Models 68 83881 All Models 69 83837 All Models 70 83882 All Models 71 81027-1 All Models 72 83886 150,150E,200 Cover (Lx150-200) 72 83956 400 Cover (Lx400) 73 83887 150,150E,200 Right Side (Lx150-200) 73 83597 400 Right Side R1 (Lx400) 74 83888 150 - CAN Lx150 Left Side (CAN) 74 83888-1 150 - US Lx150 Left Side (US), not 150E 74 83888-2 150E,200 Lx150E-200 Left Side 74 83958 400 Left Side (Lx400) 75 83889 150,150E,200 Front Top (Lx150-200) 75 82959 400 Front Top (Lx400) 76 83890 150,150E,200 Top Panel Back R1 (Lx150-200) 76 83960 400 Rear Top (Lx400) 77 83961 400 Fuel-Air Metallic Tubing with Ends (Lx400) 78 83915 400 High-Vent Pressure Switch (Lx400) 79 83962 400 Gas Valve Orifice O-ring, Large (Lx400) 80 83001 400 Test Port Retaining clamp (Lx400) 81 84010 All Models System Sensor, Pipe Sensor TSA00A4 (Lx Series)
Installation and Operation Instructions Lx Series
Transformer, 24V, 40VA (Lx Series) ICP Honeywell Sola Controller R7910B1015/B (Lx Series) Drawer Cover (Lx Series) Drawer (Lx Series)
Fuse, Matrix/Lx, 2 Amp (Lx Series) Fuse Holder, 20 Amp at 250VAC Max (Lx Series) Fuse, Littlefuse 7A, 250VAC, Fast Blow (Lx Series) Touch Screen Display Support (Lx Series) Outdoor Sensor, 10K (Lx Series)
44
Page 45
Lx Series Installation and Operation Instructions │
14.0 TROUBLESHOOTING
Trinity Lx
Observe the following precautions when servicing the appliance. Failure to comply with
these may result in fire, property damage, serious injury or death.
Servicing the Appliance
Disconnect or shut off all energy sources to the appliance: 120VAC power, water and gas.
Identify and mark wires before disconnecting or removing them.
Never bypass electrical fuses or limit devices except temporarily for testing.
Use proper personal protective equipment (PPE) i.e. eye protection, safety footwear.
These procedures should only be performed by qualified service personnel, when abnormal operation of the appliance is suspected. The appliance incorporates a sophisticated microprocessor based control which normally responds appropriately to varying conditions. If the appliance operation appears to be incorrect, or it is not responding at all to a demand for heat, the following is suggested to determine and correct the problem.
Before undertaking any troubleshooting procedures it is highly recommended to have
available a digital multimeter(s) capable of measuring AC and DC volts and amperes, resistance (Ohms) and continuity.
Check 120VAC and 24VAC at the Appliance
First, verify the following:
There is 120V being supplied to the appliance:
o The circuit breaker in the electrical panel supplying power to the appliance is not tripped. o The service switch (if applicable) is in the ON position.
There is a heat call from the thermostat:
o Verify 24VAC to thermostat. o The thermostat is placed at a sufficiently high setting to create a call for heat to the appliance.
To check for the presence of 120VAC and 24VAC at the appliance follow this procedure:
Remove the appliance front cover.
120VAC
o Remove the Line Voltage junction box cover. First remove the #10 pan-head Phillips screw securing the
cover to the junction box. Lift the cover to release it from the appliance base and withdraw the cover from the appliance cabinet. This will expose the Line Voltage barrier strip.
o With an AC voltmeter set on the appropriate scale, measure the voltage across the L1 and L2 terminals
(terminals 1 and 5).
o If 120VAC is not detected, check the electrical service as suggested above. If the service is verified,
inspect the circuit wiring from the panel to the appliance for broken or disconnected conductors.
24VAC (only check if 120VAC supply is verified). o Remove the Low Voltage junction box cover. First remove the #10 pan-head Phillips screw securing the
cover to the junction box. Lift the cover to release it from the appliance base and withdraw the cover from the appliance cabinet. This will expose the Low Voltage barrier strip.
o With an AC voltmeter set on the appropriate scale, measure the voltage across the R and C terminals
(terminals 3 and 1).
o If 24VAC is not detected, check Fuse "C" (see below).
Fuses
There are three (3) fuses associated with the Trinity Lx controller. Check these fuses before replacing the controller or any other electrical component; if the fuse is blown, it will prevent the protected device(s) from functioning.
45
Page 46
Trinity Lx
Installation and Operation Instructions Lx Series
Figure 14-1 All Models
Control Panel Fuse Location
Fuse “C” ATO 2A 32V Auto Blade Type
Fuse “A” 3AG 7A 250V Fast-Acting
Fuse “B” 3AG 7A 250V Fast-Acting
To check, and if necessary replace, the fuses:
Remove all 120VAC power from the appliance. Be careful to check that the unit is not powered from more than one source e.g. a UPS (uninterruptible power supply).
Remove the front cover.
The control panel is located below the heat exchanger. Fuses "A" and "B" are accessible by removing the
spring-loaded knurled knob of their respective holders. Push the knob toward the panel, and twist approximately 1/4 turn counter-clockwise.
To access Fuse "C", remove the two #10 pan-head Phillips screws and lift the top cover from the panel. The auto blade type fuse is installed in an "inline" style fuse holder.
After inspecting and if necessary replacing fuses, replace the panel cover and front cover. Restore power to the appliance and confirm proper operation.
Only replace fuses with identical parts, see Figure 14-1. Failure to follow this warning may result in component failure, fire, property damage, serious injury or death.
46
Page 47
-
V
+V
Lx Series Installation and Operation Instructions │
Trinity Lx
Display
A blank screen does not necessarily indicate a problem; the display may be configured to automatically blank the screen after a pre-set interval. Simply touch the screen to activate it. Confirm that 120V power is being supplied to the appliance. Then, if the screen does not become active, check Figures 14-2 and 14-3 and follow the verification procedures as outlined below:
Figure 14-2 All Models
Controller Connection Verification
Position Display Plug
Ensure the display is connected to the controller via its 4-conductor signal cable by following the procedure below:
1. Remove the unit front cover.
2. Remove the two #10 pan-head Phillips screws
securing the plastic display housing to the cabinet.
3. Pivot the housing down until its bottom edge
rests against the extended air tube or cabinet sides.
4. Verify that the two mating 4-position single-row
Molex housings are securely connected as illustrated.
Figure 14-3 All Models
Display Power Supply Verification
Display Power Supply Unit
Ensure that the display power supply is operating properly by following the procedure below:
1. Using a DC voltmeter, check for 12VDC across
the +V and –V terminals of the power supply
2. Remove the unit front cover.
3. Remove the two #10 pan-head Phillips screws
and lift the panel cover off.
4. Locate the 12VDC power supply at the front
right corner of the panel.
5. Measure the voltage across the +V and –V
terminals on the right-hand end of the supply.
6. If 12VDC is not detected across +V and –V,
replace the power supply with NTI PN83592-1.
DO NOT drop the plastic housing or allow it to swing down freely, it may be damaged by forceful impact.
47
Page 48
page and switch on.
Trinity Lx
Installation and Operation Instructions Lx Series
Summary and Diagnostics Display – The Trinity Lx controller and Touchscreen display provides detailed
operational and diagnostic information for aid in troubleshooting. When power is applied to the appliance the initial page displayed is the Summary page. Information presented on the Summary page includes Demand source, Burner state, status of sensors and pumps, and so forth. Any current Alert or Lockout condition is also displayed. Accessible from the Summary page are the Diagnostics pages. Refer to the controller manual for more information.
Lockout and Alert History – The controller maintains a record of the fifteen (15) most recent events for both Lockouts and Alerts. To display the logs, touch the History button on the Summary page (refer to page 26 in the controller manual for more information). In any situation where malfunction is suspected, always check the Alerts and Lockouts history. Entries recorded in the history provide useful information for determining the cause of the malfunction.
Controller and Plug In Module Replacement – The Trinity Lx controller is supplied with a removable memory module called a PIM (Plug In Module). The PIM contains a copy of the non-safety configuration parameters for the specific Trinity Lx model it is installed in. In the event that the controller must be replaced, remove the PIM from the controller being replaced and insert it into the new controller (Note: the PIM may be inserted and removed from the controller with power applied). Restore the settings to the new controller with the following procedure:
If the display is not showing the Summary page, touch the Home icon at the upper left corner of the
screen.
Touch the Configure button at the lower left corner of the Summary page.
Touch the Display Setup button at the lower right corner of the Configuration page.
Touch the Program Module button located near the center of the Display Setup page.
Touch the Login button at the lower right and enter the correct password; “sola”.
Touch the Restore Parameters button.
Confirm the restore operation by touching the Yes button.
Table 14-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Display shows “System Disconnected” constantly
Burner not operating
Blown 24VAC fuse Faulty 24VAC transformer Check Power LED on controller. Verify 24VAC
Faulty controller If 24VAC present at controller terminals J8 1 & 2,
Heat demand satisfied; no call for heat
Appliance outlet temperature exceeded “Off Hysteresis”
Hold or Delay Check Summary page on Touchscreen for
Lockout Check Summary page on Touchscreen for lockout
Burner switch off Check Summary page, if Demand indicates
Check Fuse "C" using procedure above.
to controller by measuring voltage at terminals J8 1 & 2. If no 24VAC detected and Fuse "C" ok, replace transformer.
check Power LED on controller. Verify that connector J8 is securely plugged into the controller. Recycle power to appliance, if controller does not operate, replace the controller. Check Demand and Set points via Touchscreen. Check thermostat and DHW aquastat (if applicable) setting. Check outlet temperature, setpoint and hysteresis settings via Touchscreen. By design, if the outlet temperature exceeds the demand setpoint plus the Off Hysteresis, the burner shuts down.
specific cause of hold or delay.
code.
“Burner switch off” go to diagnostics burner test
48
Page 49
Lx Series Installation and Operation Instructions │
Trinity Lx
Table 14-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Lockout 9 – Flame bias out of range Hold 27 – Flame rod shorted to ground detected
4-20mA input being overdriven. If using 4-20mA input, check to ensure current is
not greater than 21mA. A flame circuit shorted to ground may show up as a flame circuit timeout. Zero-ohm shorts can display as Hold 27.
Check to ensure condensate drain is not blocked.
Check to ensure no voltage applied to R & T
terminals. If using 4-20mA input, check to ensure
current is not greater than 21mA.
Hold 61 – Anti short-cycle Demand off Check demand. Delay is to prevent rapid cycling
of burner.
Hold 62 – Fan speed not proved
Burner ignition Hold 62 is normally seen for a brief period prior
to burner ignition.
- Blower problem
- Faulty controller
If Hold 62 persists for 15 seconds or more, check
"
Fan speed" on Touchscreen. If "LOW RPM",
"
HIGH RPM" or rapidly changing RPM value is displayed, try connecting another blower. If problem remains, replace controller.
Wiring defect Inspect blower wiring, ensure connectors at
controller and blower are securely attached.
Hold 63 – LCI OFF (Limit control input) Hold 65 – Interrupted Air Switch OFF
External limit Check if one (or more) external limit device(s)
tripped.
Blocked venting Check for blockage of the exhaust vent. Blocked air inlet Check for blockage of the air inlet. Disconnected, damaged or blocked tubing
Inspect the clear vinyl tubing connecting the air switch + and – ports to the air metering elbow. Condensation or other foreign matter may be obstructing the tubing, preventing the switch from sensing differential pressure caused by air flow through the metering elbow.
Incorrect air switch setting Contact NTI technical support. Faulty air switch Disconnect red and orange wires from air switch
and check for open circuit between terminals 1 &3. If circuit is open, replace air switch.
Incorrect air switch wiring Check that the red and orange wires are connected
to quick connect tabs 3 and 1 respectively.
Blown fuse
Check Fuse "A", blown fuse prevents blower from operating.
Hold 66 – Interrupted air switch ON
Blower problem Incorrect air switch setting Contact NTI technical support.
Disconnected, damaged or blocked tubing
See "Blower not operating" below.
Inspect the clear vinyl tubing connecting the air switch + and – ports to the air metering elbow. Condensation or other foreign matter may be obstructing the tubing, preventing the switch from sensing differential pressure caused by air flow through the metering elbow.
Faulty air switch Disconnect red and orange wires from air switch
and check for open circuit between terminals 1 &
3. If continuity detected, replace air switch.
Incorrect air switch wiring Check that the red and orange wires are connected
to quick connect tabs 3 and 1 respectively.
Blower problem See “Blower operating at high speed while burner
off” below.
Hold 67 – ILK OFF Insufficient water pressure Ensure at least 15PSI at appliance outlet. Refer to
Supplementary Documentation section 2.0 System Piping.
Hold 79 – Outlet High Limit
CH or DHW settings Check if CH and/or DHW set point temperature
plus off hysteresis exceeds 210°F (99°C).
CH or DHW pump problem
See "Inoperative CH or DHW pump" below.
49
Page 50
observed, replace the spark generator.
Trinity Lx
Installation and Operation Instructions Lx Series
Table 14-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Lockout 81 – Delta T limit
Insufficient water flow OR Appliance making banging or hissing sounds
Lockout 82 – Stack limit
Dirty heat exchanger Inspect and if required clean the combustion
Faulty sensor Check resistance of stack sensor and compare to
Hold 91– Inlet sensor fault
Sensor disconnected
Faulty sensor Check resistance of sensor and compare to
Hold 92 – Outlet sensor fault
Sensor disconnected
Faulty sensor Check resistance of sensor and compare to
Hold 95 – Stack sensor fault
Sensor disconnected
Faulty sensor Check resistance of sensor and compare to
Hold 110 – Ignition failure
Spark cable disconnected Ensure that the high voltage spark cable is occurred (failure to prove flame after 3 ignition attempts)
Insufficient gas line pressure Ensure the manual gas shutoff valve is open.
Flame rod disconnected Verify that the flame rod signal wire is securely
No 120VAC to Spark Generator Check wiring from controller to spark generator.
Faulty Spark Generator During trial for ignition check for arc on spark
Check Fuse "A"
Check appliance pump.
Ensure plumbing is correct. Refer to
Supplementary Documentation section 2.0 System Piping. Check that water pressure is at least 15PSI.
Boilers Only - Boiler heat transfer surfaces
may be fouled with scale or magnetite. Clean with Fernox DS-40 Descaler and Cleanser. See Table 2-1 in Appendix B.
chamber and/or heat exchanger. Refer to 14.0 Annual Manintenance and Inspection and Supplementary Documentation section 2.0 System Piping.
thermistor resistance chart, see Table 14-2.
Verify that 2-position Molex connector on
wiring harness is securely attached to mating connector on inlet sensor.
Inspect sensor wiring.
thermistor resistance chart, see Table 14-2.
Verify that 4-position Molex connector on
wiring harness is securely attached to mating connector on outlet sensor.
Inspect sensor wiring.
thermistor resistance chart, see Table 14-2.
Verify that 4-position Molex connector on
wiring harness is securely attached to mating connector on stack sensor.
Inspect sensor wiring.
thermistor resistance chart, see Table 14-2.
securely connected to the spark generator and the igniter electrode. Check that the green ground wire is securely attached to the ¼” quick connect tab on the igniter electrode.
Refer to manual section 9.0 GAS VALVE AND BURNER SETUP.
attached to the flame rod, which is located bottom center of the burner door.
With an AC voltmeter measure voltage across J5­6 and ground (the controller chassis is connected to the 120VAC supply ground) during trial for ignition.
electrode via the observation port located next to the spark electrode in the burner door. If the spark generator is receiving 120VAC and no spark is
50
Page 51
Lx Series Installation and Operation Instructions │
Table 14-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
No 24VAC to Gas Valve Check the wiring harness for loose or interrupted
connections of the gas valve wiring. With an AC voltmeter, measure the voltage from controller terminals J5-2 to J4-10. There should be 24VAC present during trial for ignition.
Faulty Gas Valve The gas valve emits an audible click when it
switches on or off. If the controller is providing 24VAC to the gas valve, and the wiring is intact, it should be possible to detect if the valve is
responding. Lockout 113 – Flame circuit timeout
was limited due to IAS was open (Air switch open while burner firing) Alert 248 – CH outdoor temperature was invalid
Alert 311 – Run was terminated due to interrupted air flow switch was off
Inoperative CH and/or DHW pump
Blower operating at high speed while burner off
Blower not operating
A flame circuit shorted to ground may show up as a flame circuit timeout. High resistance shorts can display as Lockout 113.
Check to ensure condensate drain is not blocked.
Check to ensure no voltage applied to R & T
terminals. If using 4-20mA input, check to ensure
current is not greater than 21mA.
Blocked venting Check for blockage of the exhaust vent. Alert 128 - Modulation rate Blocked air inlet Check for blockage of the air inlet.
Outdoor sensor not connected The Trinity Lx is factory set with Outdoor Reset
enabled. Connect outdoor sensor or disable
Outdoor Reset.
Outdoor sensor wiring Check wiring of outdoor sensor. Wires should
connect to Low Voltage barrier terminals 11 & 12.
Faulty sensor Check sensor. Should be free of ice and snow.
Check resistance of sensor and compare to
thermistor resistance chart, see Table 14-2.
Blocked venting Check for blockage of the exhaust vent. Blocked air inlet Check for blockage of the air inlet. Disconnected, damaged or blocked tubing
Inspect the clear vinyl tubing connecting the air
switch + and – ports to the air metering elbow.
Condensation or other foreign matter may be
obstructing the tubing, preventing the switch from
sensing differential pressure caused by air flow
through the metering elbow.
Incorrect air switch setting Contact NTI technical support. Blown fuse
Blown fuse
Check Fuse "A".
Check Fuse "B".
Faulty controller If Fuse “B” not blown, and controller is operating,
navigate to pump diagnostic on display. Manually
switch pump on, check for 120VAC at pump
connection terminal on line voltage barrier strip. If
120VAC not detected, replace controller.
Faulty pump If 120VAC supplied to pump, and pump does not
operate, replace pump.
Blower signal cable disconnected
Verify that the 5-position Molex connector on
the wiring harness is securely connected to its mating connector on the blower.
Check that the 4-position Molex connector on
wiring harness is securely connected to its mating connector on the controller.
No 24VAC to controller
Check Power LED on controller.
Check Fuse "C".
With an AC voltmeter measure voltage at
terminals J8 1 & 2, 24VAC should be present.
Blower signal cable disconnected Verify that the 5-position Molex connector on the
wiring harness is securely connected to its mating
connector on the blower.
Trinity Lx
51
Page 52
Trinity Lx
Installation and Operation Instructions Lx Series
Table 14-1 Troubleshooting Chart
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Blower power disconnected Verify that the 3-position Molex connector on the
wiring harness is securely connected to its mating
connector on the blower.
Blown fuse
Check Fuse "A" using the procedure described
above. Fuse "A" protects the blower as well as the
ignition spark generator and appliance pump.
Faulty blower Measure voltage across pins 1 & 2 (black and
white wires) of 3-position connector on wiring
harness. If 120VAC detected, replace power
connector and remove 5-position signal connector.
Blower should rotate at high speed. If blower does
not rotate, replace blower.
Table 14-2 Thermistor Resistance vs. Temperature
Temp °F (°C) Resistance Ohms () Temp °F (°C) Resistance Ohms ()
-22 (-30) 176,133 122 (50) 3,603
-4 (-20) 96,761 131 (55) 2,986 14 (-10) 55,218 140 (60) 2,488
32 (0) 32,650 149 (65) 2,083
41 (5) 25,390 158 (70) 1,752 50 (10) 19,900 167 (75) 1,481 59 (15) 15,710 176 (80) 1,258 68 (20) 12,490 185 (85) 1,072 77 (25) 10,000 194 (90) 918 86 (30) 8,057 203 (95) 789 95 (35) 6,531 212 (100) 680
104 (40) 5,327 230 (110) 506 113 (45) 4,369 - -
Table 14-3 Hold and Lockout Codes
Code Description Note
0 None Hold / No lockout
1 Unconfigured safety data Lockout
2 Waiting for safety data verification Lockout
3 Internal fault: Hardware fault Hold
4 Internal fault: Safety Relay key feedback error Hold
5 Internal fault: Unstable power (DCDC) output Hold
6 Internal fault: Invalid processor clock Hold
7 Internal fault: Safety relay drive error Hold
8 Internal fault: Zero crossing not detected Hold
9 Internal fault: Flame bias out of range Hold
10 Internal fault: Invalid Burner control state Lockout
11 Internal fault: Invalid Burner control state flag Lockout
12 Internal fault: Safety relay drive cap short Hold
13 Internal fault: PII shorted to ILK Hold / Lockout
14 Internal fault: HFS shorted to LCI Hold / Lockout
15 Internal fault: Safety relay test failed due to feedback ON Lockout
16 Internal fault: Safety relay test failed due to safety relay OFF Lockout
17 Internal fault: Safety relay test failed due to safety relay not OFF Lockout
52
Page 53
Lx Series Installation and Operation Instructions │
Table 14-3 Hold and Lockout Codes
Code Description Note
18 Internal fault: Safety relay test failed due to feedback not ON Lockout
19 Internal fault: Safety RAM write Lockout
20 Internal fault: Flame ripple and overflow Hold
21 Internal fault: Flame number of sample mismatch Hold
22 Internal fault: Flame bias out of range Hold
23 Internal fault: Bias changed since heating cycle starts Hold
24 Internal fault: Spark voltage stuck low or high Hold
25 Internal fault: Spark voltage changed too much during flame sensing time Hold
26 Internal fault: Static flame ripple Hold
27 Internal fault: Flame rod shorted to ground detected Hold
28 Internal fault: A/D linearity test fails Hold
29 Internal fault: Flame bias cannot be set in range Hold
30 Internal fault: Flame bias shorted to adjacent pin Hold
31 Internal fault: SLO electronics unknown error Hold
32 Internal fault: Safety Key 0 Lockout
33 Internal fault: Safety Key 1 Lockout
34 Internal fault: Safety Key 2 Lockout
35 Internal fault: Safety Key 3 Lockout
36 Internal fault: Safety Key 4 Lockout
37 Internal fault: Safety Key 5 Lockout
38 Internal fault: Safety Key 6 Lockout
39 Internal fault: Safety Key 7 Lockout
40 Internal fault: Safety Key 8 Lockout
41 Internal fault: Safety Key 9 Lockout
42 Internal fault: Safety Key 10 Lockout
43 Internal fault: Safety Key 11 Lockout
44 Internal fault: Safety Key 12 Lockout
45 Internal fault: Safety Key 13 Lockout
46 Internal fault: Safety Key 14 Lockout
47 Flame rod to ground leakage Hold
48 Static flame (not flickering) Hold
49 24VAC voltage low/high Hold
50 Modulation fault Hold
51 Pump fault Hold
52 Motor tachometer fault Hold
53 AC inputs phase reversed Lockout
54-57 RESERVED
58 Internal fault: HFS shorted to IAS Lockout
59 Internal fault: Mux pin shorted Lockout
60 Internal fault: HFS shorted to LFS Lockout
61 Anti short cycle Hold
62 Fan speed not proved Hold
63 LCI OFF Hold
64 PII OFF N/A
65 Interrupted Airflow Switch OFF Hold
66 Interrupted Airflow Switch ON Hold
67 ILK OFF Hold
68 ILK ON N/A
69 Pilot test hold Hold
Trinity Lx
53
Page 54
Trinity Lx
Installation and Operation Instructions Lx Series
Table 14-3 Hold and Lockout Codes
Code Description Note
70 Wait for leakage test completion Hold
71-77 RESERVED
78 Demand lost in run Hold
79 Outlet high limit Hold
80 DHW high limit Disabled
81 Delta T limit Hold / Lockout
82 Stack limit Lockout
83-90 RESERVED
91 Inlet sensor fault Hold
92 Outlet sensor fault Hold
93 DHW sensor fault Hold
94 Header sensor fault Hold
95 Stack sensor fault Hold
96 Outdoor sensor fault Hold
97 Internal fault: A2D mismatch Lockout
98 Internal fault: Exceeded VSNSR voltage tolerance Lockout
99 Internal fault: Exceeded 28V voltage tolerance Lockout
100 Pressure sensor fault Hold
101-104 RESERVED
105 Flame detected out of sequence Hold / Lockout
106 Flame lost in MFEP Lockout
107 Flame lost early in run Lockout
108 Flame lost in run Lockout
109 Ignition failed Lockout
110 Ignition failure occurred Hold
111 Flame current lower than WEAK threshold Hold
112 Pilot test flame timeout Lockout
113 Flame circuit timeout Lockout
114-121 RESERVED
122 Light off rate proving failed Lockout
123 Purge rate proving failed Lockout
124 High fire switch OFF Hold
125 High fire switch stuck ON Hold
126 Low fire switch OFF Hold
127 Low fire switch stuck ON Hold
128 Fan speed failed during pre-purge Hold / Lockout
129 Fan speed failed during pre-ignition Hold / Lockout
130 Fan speed failed during ignition Hold / Lockout
131 Fan movement detected during standby Hold
132 Fan speed failed during run Hold
133-135 RESERVED
136 Interrupted Airflow Switch failed to close Hold
137 ILK failed to close Hold
138-148 RESERVED
149 Flame detected Hold / Lockout
150 Flame not detected Hold
151 High fire switch ON Hold / Lockout
152 Combustion pressure ON Hold / Lockout
153 Combustion pressure OFF Hold / Lockout
54
Page 55
Lx Series Installation and Operation Instructions │
Table 14-3 Hold and Lockout Codes
Code Description Note
154 Purge fan switch ON Hold / Lockout
155 Purge fan switch OFF Hold / Lockout
156 Combustion pressure and Flame ON Hold / Lockout
157 Combustion pressure and Flame OFF Lockout
158 Main valve ON Lockout
159 Main valve OFF Lockout
160 Ignition ON Lockout
161 Ignition OFF Lockout
162 Pilot valve ON Lockout
163 Pilot valve OFF Lockout
164 Block intake ON Lockout
165 Block intake OFF Lockout
166-171 RESERVED
172 Main relay feedback incorrect Lockout
173 Pilot relay feedback incorrect Lockout
174 Safety relay feedback incorrect Lockout
175 Safety relay open Lockout
176 Main relay ON at safe start check Lockout
177 Pilot relay ON at safe start check Lockout
178 Safety relay ON at safe start check Lockout
179-183 RESERVED
184 Invalid BLOWER/HSI output setting Lockout
185 Invalid Delta T limit enable setting Lockout
186 Invalid Delta T limit response setting Lockout
187 Invalid DHW high limit enable setting Lockout
188 Invalid DHW high limit response setting Lockout
189 Invalid Flame sensor type setting Lockout
190 Invalid interrupted air switch enable setting Lockout
191 Invalid interrupted air switch start check enable setting Lockout
192 Invalid Igniter on during setting Lockout
193 Invalid Ignite failure delay setting Lockout
194 Invalid Ignite failure response setting Lockout
195 Invalid Ignite failure retries setting Lockout
196 Invalid Ignition source setting Lockout
197 Invalid Interlock open response setting Lockout
198 Invalid Interlock start check setting Lockout
199 Invalid LCI enable setting Lockout
200 Invalid light off rate setting Lockout
201 Invalid Light off rate proving setting Lockout
202 Invalid Main Flame Establishing Period time setting Lockout
203 Invalid MFEP flame failure response setting Lockout
204 Invalid NTC sensor type setting Lockout
205 Invalid Outlet high limit response setting Lockout
206 Invalid Pilot Flame Establishing Period setting Lockout
207 Invalid PII enable setting Lockout
208 Invalid pilot test hold setting Lockout
209 Invalid Pilot type setting Lockout
210 Invalid Post-purge time setting Lockout
211 Invalid Power up with lockout setting Lockout
Trinity Lx
55
Page 56
Trinity Lx
Installation and Operation Instructions Lx Series
Table 14-3 Hold and Lockout Codes
Code Description Note
212 Invalid Pre-ignition time setting Lockout
213 Invalid Pre-purge rate setting Lockout
214 Invalid Pre-purge time setting Lockout
215 Invalid Purge rate proving setting Lockout
216 Invalid Run flame failure response setting Lockout
217 Invalid Run stabilization time setting Lockout
218 Invalid Stack limit enable setting Lockout
219 Invalid Stack limit response setting Lockout
220 Unconfigured Delta T limit set point setting Lockout
221 Unconfigured DHW high limit set point setting Lockout
222 Unconfigured Outlet high limit set point setting Lockout
223 Unconfigured Stack limit set point setting Lockout
224 Invalid DHW demand source setting Lockout
225 Invalid Flame threshold setting Lockout
226 Invalid Outlet high limit set point setting Lockout
227 Invalid DHW high limit set point setting Lockout
228 Invalid Stack limit set point setting Lockout
229 Invalid Modulation output setting Lockout
230 Invalid CH demand source setting Lockout
231 Invalid Delta T limit delay setting Lockout
232 Invalid Pressure sensor type setting Lockout
233 Invalid IAS closed response setting Lockout
234 Invalid Outlet high limit enable setting Lockout
235 Invalid Outlet connector type setting Lockout
236 Invalid Inlet connector type setting Lockout
237 Invalid DHW connector type setting Lockout
238 Invalid Stack connector type setting Lockout
239 Invalid Header connector type setting Lockout
240 Invalid Outdoor connector type setting Lockout
241-255 RESERVED
Table 14-4 Alert Codes
Code Description Action/Response
0 None (No alert) 1 Alert PCB was restored from factory defaults 2 Safety configuration parameters were restored from factory defaults 3 Configuration parameters were restored from factory defaults 4 Invalid Factory Invisibility PCB was detected 5 Invalid Factory Range PCB was detected 6 Invalid range PCB record has been dropped 7 EEPROM lockout history was initialized 8 Switched application annunciation data blocks
9 Switched application configuration data blocks 10 Configuration was restored from factory defaults 11 Backup configuration settings was restored from active configuration 12 Annunciation configuration was restored from factory defaults 13 Annunciation configuration was restored from backup 14 Safety group verification table was restored from factory defaults
56
Page 57
Lx Series Installation and Operation Instructions │
Trinity Lx
Table 14-4 Alert Codes
Code Description Action/Response
15 Safety group verification table was updated 16 Invalid Parameter PCB was detected 17 Invalid Range PCB was detected 18 Alarm silence time exceeded maximum 19 Invalid safety group verification table was detected
20-26 RESERVED
27 Safety processor was reset 28 Application processor was reset 29 Burner switch was turned OFF 30 Burner switch was turned ON 31 Program Module (PM) was inserted into socket 32 Program Module (PM) was removed from socket 33 Alert PCB was configured 34 Parameter PCB was configured 35 Range PCB was configured 36 Program Module (PM) incompatible with product was inserted into socket 37 Program Module application parameter revision differs from application processor 38 Program Module safety parameter revision differs from safety processor 39 PCB incompatible with product contained in Program Module 40 Parameter PCB in Program Module is too large for product 41 Range PCB in Program Module was too large for product 42 Alert PCB in Program Module was too large for product 43 IAS start check was forced on due to IAS enabled 44 Low voltage was detected in safety processor 45 High line frequency occurred 46 Low line frequency occurred 47 Invalid subsystem reset request occurred 48 Write large enumerated Modbus register value was not allowed 49 Maximum cycle count was reached 50 Maximum hours count was reached 51 Illegal Modbus write was attempted 52 Modbus write attempt was rejected (NOT ALLOWED) 53 Illegal Modbus read was attempted 54 Safety processor brown-out reset occurred 55 Application processor watchdog reset occurred 56 Application processor brown-out reset occurred 57 Safety processor watchdog reset occurred 58 Alarm was reset by the user at the control 59 Burner control firing rate was > absolute max rate 60 Burner control firing rate was < absolute min rate 61 Burner control firing rate was invalid, % vs. RPM 62 Burner control was firing with no fan request 63 Burner control rate (non-firing) was > absolute max rate 64 Burner control rate (non-firing) was < absolute min rate 65 Burner control rate (non-firing) was absent 66 Burner control rate (non-firing) was invalid, % vs. RPM 67 Fan off cycle rate was invalid, % vs. RPM 68 Set point was over ridden due to sensor fault 69 Modulation was over ridden due to sensor fault
57
Page 58
Trinity Lx
Installation and Operation Instructions Lx Series
Table 14-4 Alert Codes
Code Description Action/Response
70-74 RESERVED
75 Absolute max fan speed was out of range 76 Absolute min fan speed was out of range 77 Fan gain down was invalid 78 Fan gain up was invalid 79 Fan minimum duty cycle was invalid 80 Fan pulses per revolution was invalid 81 Fan PWM frequency was invalid
82-89 RESERVED
90 Modulation output type was invalid 91 Firing rate control parameter was invalid 92 Forced rate was out of range vs. min/max modulation 93 Forced rate was invalid, % vs. RPM 94 Slow start ramp value was invalid 95 Slow start degrees value was invalid 96 Slow start was ended due to outlet sensor fault 97 Slow start was end due to reference set point fault 98 CH max modulation rate was invalid, % vs. RPM 99 CH max modulation rate was > absolute max rate
100 CH modulation range (max minus min) was too small (< 4% or 40 RPM) 101 DHW max modulation rate was invalid, % vs. RPM 102 DHW max modulation rate was > absolute max rate 103 DHW modulation range (max minus min) was too small (< 4% or 40 RPM) 104 Min modulation rate was < absolute min rate 105 Min modulation rate was invalid, % vs. RPM 106 Manual rate was invalid, % vs. RPM 107 Slow start enabled, but forced rate was invalid 108 Analog output hysteresis was invalid 109 Analog modulation output type was invalid 110 IAS open rate differential was invalid 111 IAS open step rate was invalid
112 -114
RESERVED 115 Fan was limited to its minimum duty cycle 116 Manual rate was > CH max modulation rate 117 Manual rate was > DHW max modulation rate 118 Manual rate was < min modulation rate 119 Manual rate in Standby was > absolute max rate 120 Modulation commanded rate was > CH max modulation rate 121 Modulation commanded rate was > DHW max modulation rate 122 Modulation commanded rate was < min modulation rate 123 Modulation rate was limited due to outlet limit 124 Modulation rate was limited due to Delta-T limit 125 Modulation rate was limited due to stack limit 126 Modulation rate was limited due to anti-condensation 127 Fan Speed out of range in RUN 128 Modulation rate was limited due to IAS was open 129 Slow start ramp setting of zero will result in no modulation rate change 130 RESERVED 131 CH demand source was invalid
58
Page 59
Lx Series Installation and Operation Instructions │
Trinity Lx
Table 14-4 Alert Codes
Code Description Action/Response
132 CH P-gain was invalid 133 CH I-gain was invalid 134 CH D-gain was invalid 135 CH OFF hysteresis was invalid 136 CH ON hysteresis was invalid 137 CH sensor type was invalid 138 CH hysteresis step time was invalid 139 CH remote control parameter was invalid 140 CH ODR not allowed with remote control
141-145
RESERVED 146 CH control was suspended due to fault 147 CH header temperature was invalid 148 CH outlet temperature was invalid 149 CH steam pressure was invalid
150-156
RESERVED 157 DHW demand source was invalid 158 DHW P-gain was invalid 159 DHW I-gain was invalid 160 DHW D-gain was invalid 161 DHW OFF hysteresis was invalid 162 DHW ON hysteresis was invalid 163 DHW hysteresis step time was invalid 164 DHW sensor type was invalid 165 Inlet sensor type was invalid for DHW 166 Outlet sensor type was invalid for DHW
167-170
RESERVED 171 DHW control was suspended due to fault 172 DHW temperature was invalid 173 DHW inlet temperature was invalid 174 DHW outlet temperature was invalid
175-182
RESERVED 183 Lead Lag P-gain was invalid 184 Lead Lag I-gain was invalid 185 Lead Lag D-gain was invalid 186 Lead Lag OFF hysteresis was invalid 187 Lead Lag ON hysteresis was invalid 188 Lead Lag slave enable was invalid 189 Lead Lag hysteresis step time was invalid
190-
203 RESERVED 204 Lead Lag master was suspended due to fault 205 Lead Lag slave was suspended due to fault 206 Lead Lag header temperature was invalid 207 Lead Lag was suspended due to no enabled Program Module installed 208 Lead Lag slave session has timed out
209-
221 RESERVED 222 CH frost protection temperature was invalid 223 CH frost protection inlet temperature was invalid 224 DHW frost protection temperature was invalid
225-
230 RESERVED
59
Page 60
Trinity Lx
Installation and Operation Instructions Lx Series
Table 14-4 Alert Codes
Code Description Action/Response
231 LL set point was invalid 232 LL time of day set point was invalid 233 LL outdoor temperature was invalid 234 LL ODR time of day set point was invalid 235 LL ODR time of day set point exceeded normal set point 236 LL max outdoor set point was invalid 237 LL min outdoor set point was invalid 238 LL min water set point was invalid 239 LL outdoor temperature range was too small (minimum 12 C / 22 F) 240 LL water temperature range was too small (minimum 12 C / 22 F)
241-
245 RESERVED 246 CH set point was invalid 247 CH time of day set point was invalid 248 CH outdoor temperature was invalid 249 CH ODR time of day setpoint was invalid 250 CH ODR time of day set point exceeds normal set point 251 CH max outdoor set point was invalid 252 CH min outdoor setp oint was invalid 253 CH min water set point was invalid 254 CH outdoor temperature range was too small (minimum 12 C / 22 F) 255 CH water temperature range was too small (minimum 12 C / 22 F)
256-
260 RESERVED 261 DHW set point was invalid 262 DHW time of day set point was invalid
263-
271 RESERVED 272 Abnormal Recycle: Pressure sensor fault 273 Abnormal Recycle: Safety relay drive test failed 274 Abnormal Recycle: Demand off during Pilot Flame Establishing Period 275 Abnormal Recycle: LCI off during Drive to Purge Rate 276 Abnormal Recycle: LCI off during Measured Purge Time 277 Abnormal Recycle: LCI off during Drive to Light off Rate 278 Abnormal Recycle: LCI off during Pre-Ignition test 279 Abnormal Recycle: LCI off during Pre-Ignition time 280 Abnormal Recycle: LCI off during Main Flame Establishing Period 281 Abnormal Recycle: LCI off during Ignition period 282 Abnormal Recycle: Demand off during Drive to Purge Rate 283 Abnormal Recycle: Demand off during Measured Purge Time 284 Abnormal Recycle: Demand off during Drive to Light off Rate 285 Abnormal Recycle: Demand off during Pre-Ignition test 286 Abnormal Recycle: Demand off during Pre-Ignition time 287 Abnormal Recycle: Flame was on during Safe Start check 288 Abnormal Recycle: Flame was on during Drive to Purge Rate 289 Abnormal Recycle: Flame was on during Measured Purge Time 290 Abnormal Recycle: Flame was on during Drive to Light off Rate 291 Abnormal Recycle: Flame was not on at end of Ignition period 292 Abnormal Recycle: Flame was lost during Main Flame Establishing Period 293 Abnormal Recycle: Flame was lost early in Run 294 Abnormal Recycle: Flame was lost during Run 295 Abnormal Recycle: Leakage test failed
60
Page 61
Lx Series Installation and Operation Instructions │
Trinity Lx
Table 14-4 Alert Codes
Code Description Action/Response
296 Abnormal Recycle: Interrupted air flow switch was off during Drive to Purge Rate 297 Abnormal Recycle: Interrupted air flow switch was off during Measured Purge Time 298 Abnormal Recycle: Interrupted air flow switch was off during Drive to Light off Rate 299 Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test 300 Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time 301
Abnormal Recycle: Interrupted air flow switch was off during Main Flame Establishing Period
302 Abnormal Recycle: Ignition failed due to interrupted air flow switch was off 303 Abnormal Recycle: ILK off during Drive to Purge Rate 304 Abnormal Recycle: ILK off during Measured Purge Time 305 Abnormal Recycle: ILK off during Drive to Light off Rate 306 Abnormal Recycle: ILK off during Pre-Ignition test 307 Abnormal Recycle: ILK off during Pre-Ignition time 308 Abnormal Recycle: ILK off during Main Flame Establishing Period 309 Abnormal Recycle: ILK off during Ignition period 310 Run was terminated due to ILK was off 311 Run was terminated due to interrupted air flow switch was off 312 Stuck reset switch 313 Run was terminated due to fan failure 314 Abnormal Recycle: Fan failed during Drive to Purge Rate 315 Abnormal Recycle: Fan failed during Measured Purge Time 316 Abnormal Recycle: Fan failed during Drive to Light off Rate 317 Abnormal Recycle: Fan failed during Pre-Ignition test 318 Abnormal Recycle: Fan failed during Pre-Ignition time 319 Abnormal Recycle: Fan failed during Ignition period 320 Abnormal Recycle: Fan failed during Main Flame Establishing Period 321 Abnormal Recycle: Main Valve off after 10 seconds of RUN 322 Abnormal Recycle: Pilot Valve off after 10 seconds of RUN 323 Abnormal Recycle: Safety Relay off after 10 seconds of RUN 324 Abnormal Recycle: Hardware flame bias 325 Abnormal Recycle: Hardware static flame 326 Abnormal Recycle: Hardware flame current invalid 327 Abnormal Recycle: Hardware flame rod short 328 Abnormal Recycle: Hardware invalid power 329 Abnormal Recycle: Hardware invalid AC line 330 Abnormal Recycle: Hardware SLO flame ripple 331 Abnormal Recycle: Hardware SLO flame sample 332 Abnormal Recycle: Hardware SLO flame bias range 333 Abnormal Recycle: Hardware SLO flame bias heat 334 Abnormal Recycle: Hardware SLO spark stuck 335 Abnormal Recycle: Hardware SLO spark changed 336 Abnormal Recycle: Hardware SLO static flame 337 Abnormal Recycle: Hardware SLO rod shorted 338 Abnormal Recycle: Hardware SLO AD linearity 339 Abnormal Recycle: Hardware SLO bias not set 340 Abnormal Recycle: Hardware SLO bias shorted 341 Abnormal Recycle: Hardware SLO electronics 342 Abnormal Recycle: Hardware processor clock 343 Abnormal Recycle: Hardware AC phase 344 Abnormal Recycle: Hardware A2D mismatch
61
Page 62
Trinity Lx
Installation and Operation Instructions Lx Series
Table 14-4 Alert Codes
Code Description Action/Response
345 Abnormal Recycle: Hardware VSNSR A2D 346 Abnormal Recycle: Hardware 28V A2D 347 Abnormal Recycle: Hardware HFS IAS shorted 348 Abnormal Recycle: Hardware PII INTLK shorted 349 Abnormal Recycle: Hardware HFS LCI shorted 350 Abnormal Recycle: Hardware HFS LFS shorted 351 Abnormal Recycle: Invalid zero crossing 352 Abnormal Recycle: fault stack sensor 353 Abnormal Recycle: stack limit 354 Abnormal Recycle: delta T limit 355 Abnormal Recycle: fault outlet sensor 356 Abnormal Recycle: outlet high limit 357 Abnormal Recycle: fault DHW sensor 358 Abnormal Recycle: DHW high limit 359 Abnormal Recycle: fault inlet sensor 360 Abnormal Recycle: Check Parameters Failed 361 Internal error: No factory parameters were detected in control 362 Internal error: PID iteration frequency was invalid 363 Internal error: Demand-Rate interval time was invalid 364 Internal error: Factory calibration parameter for modulation was invalid 365 Internal error: CH PID P-scaler was invalid 366 Internal error: CH PID I-scaler was invalid 367 Internal error: CH PID D-scaler was invalid 368 Internal error: DHW PID P-scaler was invalid 369 Internal error: DHW PID I-scaler was invalid 370 Internal error: DHW PID D-scaler was invalid 371 Internal error: Lead Lag master PID P-scaler was invalid 372 Internal error: Lead Lag master PID I-scaler was invalid 373 Internal error: Lead Lag master PID D-scaler was invalid
374-
459 RESERVED 460 LCI demand lost in run 461 Demand lost in run 462 STAT demand lost in run 463 Demand lost in run due to no flame
464-
RESERVED 467 Internal error: EEPROM write was attempted before EEPROM was initialized 468 Internal error: EEPROM cycle count address was invalid 469 Internal error: EEPROM days count address was invalid 470 Internal error: EEPROM hours count address was invalid 471 Internal error: Lockout record EEPROM index was invalid 472 Internal error: Request to write PM status was invalid 473 Internal error: PM parameter address was invalid 474 Internal error: PM safety parameter address was invalid 475 Internal error: Invalid record in lockout history was removed 476 Internal error: EEPROM write buffer was full 477 Internal error: Data too large was not written to EEPROM 478 Internal error: Safety key bit 0 was incorrect 479 Internal error: Safety key bit 1 was incorrect 480 Internal error: Safety key bit 2 was incorrect
62
Page 63
Lx Series Installation and Operation Instructions │
Trinity Lx
Table 14-4 Alert Codes
Code Description Action/Response
481 Internal error: Safety key bit 3 was incorrect 482 Internal error: Safety key bit 4 was incorrect 483 Internal error: Safety key bit 5 was incorrect 484 Internal error: Safety key bit 6 was incorrect 485 Internal error: Safety key bit 7 was incorrect 486 Internal error: Safety key bit 8 was incorrect 487 Internal error: Safety key bit 9 was incorrect 488 Internal error: Safety key bit 10 was incorrect 489 Internal error: Safety key bit 11 was incorrect 490 Internal error: Safety key bit 12 was incorrect 491 Internal error: Safety key bit 13 was incorrect 492 Internal error: Safety key bit 14 was incorrect 493 Internal error: Safety key bit 15 was incorrect 494 Internal error: Safety relay timeout 495 Internal error: Safety relay commanded off 496 Internal error: Unknown safety error occurred 497 Internal error: Safety timer was corrupt 498 Internal error: Safety timer was expired 499 Internal error: Safety timings 500 Internal error: Safety shutdown
63
Page 64
NY Thermal Inc. 65 Drury Cove Road Saint John, NB E3H 2Z8 Canada
Technical Assistance: 1-800-688-2575
Website: www.nythermal.com
Fax: 1-506-432-1135
Loading...