Models: FTG 600 through FTG 2400
Version Date: 2017-08-14
INSTALLATION AND OPERATION MANUAL
TABLE OF CONTENTS
HAZARD SYMBOLS AND DEFINITIONS
Danger Sign: Indicates a hazardous situation which, if not avoided, will
result in serious injury or death.
Warning Sign: Indicates a hazardous situation which, if not avoided,
could result in serious injury or death.
Caution Sign plus Safety Alert Symbol: Indicates a hazardous situation
which, if not avoided, could result in minor or moderate injury.
Caution Sign without Safety Alert Symbol: Indicates a hazardous
situation which, if not avoided, could result in property damage.
Notice Sign: Indicates a hazardous situation which, if not avoided,
could result in property damage.
This Boiler must be installed by a licensed and trained Heating
Technician or the Warranty is Void. Failure to properly install this
unit may result in property damage, serious injury to occupants, or possibly death.
H
NTI # 85422
Page 2
2
Installation & Operation Manual │FTG
Read Before Proceeding
If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING_
A) This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any boiler.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to turn the gas “shutoff” valve. Never use tools. If the handle will not turn by hand,
do not try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or
explosion.
D) Do not use this boiler if any part has been under water. Immediately call a qualified service technician
to inspect the boiler and to replace any part of the control system and any gas control which has been
under water.
OPERATING INSTRUCTIONS_
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the boiler.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Boiler” and call your service
technician or gas supplier.
TO TURN OFF GAS TO THE BOILER_
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the boiler.
3. Turn the manual gas valve to the OFF position.
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or
maintenance can cause property damage, serious injury (exposure to hazardous
materials) or death. Refer to Section 15.0 for information on handling instructions and recommended personal
protective equipment. Installation and service must be performed by a qualified installer, service agency or the
gas supplier (who must read and follow the supplied instructions before installing, servicing, or removing this
boiler. This boiler contains materials that have been identified as carcinogenic, or possibly carcinogenic, to
humans).
Void Warranty - This Boiler must have water flowing through it whenever the burner is
on or it will damage the unit and void the warranty. Failure to follow these instructions
may result in serious injury or death.
Page 3
FTG│Installation & Operation Manual
3
1.0 INTRODUCTION
General Installation Requirements
The installation of your NTI FTG gas boiler must conform to the requirements of this manual, your local
authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where
required by the Authority, the installation must conform to the standard for “Controls and Safety Devices for
Automatically Fired Boilers ANSI/ASME CSD-1.”
This document pertains to the correct installation and operation of NTI FTG boiler models FTG 600, FTG 800,
FTG 1200, FTG 1400, FTG 2000, FTG 2200 and FTG 2400. The instructions detailed in this document
supersede any and all previous instructions provided by NTI, written or otherwise. Each unit is provided with the
following:
1. Installation and Operation Manual,
2. Appendix A – Controller and Touchscreen Display Instructions,
3. FTG Users’ Manual, and
4. Natural Gas to LP Conversion Kit*
* The conversion kit is required to convert the boiler so it will safely operate with Propane Gas.
Read and understand this entire document prior to proceeding with the installation of the
FTG boiler. Failure to follow the instructions outlined in this document will result in
property damage, serious injury or death.
User Responsibilities
This boiler must be installed and serviced by a qualified installer or service technician. This boiler must be
serviced and inspected annually when operating in normal residential applications. Demanding applications or
extreme conditions (i.e. when operating with LP-Propane) may require more frequent service and inspection. As
the User/Owner of this equipment, you are responsible for ensuring the maintenance is performed at the required
intervals (see Section 15.0 – Annual Maintenance and Inspection).
Failure to have the boiler properly serviced and inspected on a regular basis by a qualified
service technician may result in property damage, serious injury or death.
Failure to keep the Vent and Combustion Air Intake clear of ice, snow, and other debris
may result in property damage, serious injury, or death.
Installer Responsibilities
As the installing technician it is your responsibility to ensure the installation is performed in accordance with this
instruction manual as well as any applicable local or National installation codes. It is also your responsibility to
inform the User/Owner of their obligation with respect to the above description under “User Responsibilities.”
Failure to follow this warning could result in fire, serious injury, or death.
Page 4
Installation & Operation Manual │FTG
4
ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your boiler is not
installed in a pit or similar location that will permit heavier than air gas to collect. Local Codes may require
boilers fueled with LP gas be provided with an approved means of removing unburned gases from the room.
Check your local codes for this requirement.
Natural Gas to LP Conversion Kit
Model
Kit Part Number
LP-Orifice
FTG 600-1400
85418-1
N/A
FTG 2000-2400
85758-1
N/A
FTG boilers are factory set to operate with Natural Gas; BEFORE OPERATING
WITH PROPANE, the boiler must be converted using the appropriate Natural Gas to
LP Conversion Kit – see below; each kit comes with conversion instructions. Failure to
properly convert the unit to safely operate with Propane will cause severe boiler failure,
resulting in property damage, serious injury or death.
Exhaust Vent / Air-Inlet Piping
The FTG is certified as a “Category IV” boiler, and requires a “Special Venting System”
designed for pressurized venting. The exhaust gases must be piped directly to the
outdoors using the vent materials and rules outlined in these instructions. Failure to
follow these instructions will result in serious injury or death.
Page 5
5
IN THE STATE OF MASSACHUSETTS ONLY
(a) For all horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or
in part for residential purposes, including those owned and operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not
limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall
horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired
carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas
equipment is to be installed and on each additional level of the dwelling, building or structure served by the
equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next
adjacent floor level.
b. In the event that the requirements of this subdivision cannot be met at the time of completion of
installation, the owner shall have a period of 30 days to comply with the above requirements; provided,
however, that during said 30 day period a battery operated carbon monoxide detector with an alarm shall
be installed.
2. APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating boiler or equipment. The sign shall read, in print size no less than onehalf (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS” (plate included with boiler).
4. INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall
not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b)EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or in part for residential purposes.
(c)MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED: When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or
venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:
1. Detailed instructions for installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d)MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED:
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide
the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be
satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment
installation instructions; and
2. The “special venting system” shall be Product Approved by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts list for venting instructions, and/or all venting design instructions shall remain with
the appliance or equipment at the completion of the installation.
FTG│Installation & Operation Manual
Page 6
Installation & Operation Manual│FTG
6
DESCRIPTION
FTG 600
FTG 800
FTG 1200
FTG 1400
FTG 2000
FTG 2200
FTG 2400
Gas Connection
(inches, NPT)
1
1-1/4
1-1/2
Water Inlet
(inches, groove-joint)
3
Water Outlet
(inches, groove-joint)
2
3
Exhaust Vent
Connection (inches)
6
8
Air-inlet Connection
(inches)
6
8
Overall Height
(inches)
68-1/2
64-3/8
Overall Width
(inches)
33-7/8
Overall Depth
(inches)
38-3/8
54
70
Approximate Weight
with water (lb.)
930
1500
2140
Water Content
(gallons)
17
34
51
Electrical Rating
120V / 1Ph / 60Hz / less than 12A
(Note 1)
(Note 2)
(Note 3)
Notes:
1
FTG 2000 electrical rating is 120V / 1Ph / 60Hz / less than 16A.
2
FTG 2200 electrical rating is 208V / 3Ph / 60Hz / less than 16A.
3
FTG 2400 electrical rating is 240V / 3Ph / 60Hz / less than 16A.
DESCRIPTION
FTG 600
FTG 800
FTG 1200
FTG 1400
FTG 2000
FTG 2200
FTG 2400
CSA Input
Modulation (MBH)1
80 - 600
80 - 800
120-1200
140-1400
235-2000
235-2200
235-2350
DOE Heating
Capacity (MBH)
1,2
576
760
1153
1344
1920
2103
2237
Net I=B=R Rating
(MBH)
1,2
500
660
1003
1169
1670
1829
1945
Combustion
Efficiency (%)2
97
96
96.2
96
96.1
95.7
95.3
Thermal
Efficiency (%)2
96
95
96.1
96
96
95.6
95.2
Notes:
1
Listed Input and Output ratings are at Sea Level. Numbers will be lower with altitudes greater than 2000 feet.
2
Based on standard test procedures prescribed by the U.S. Department of Energy. Ratings have been confirmed by AHRI.
2.0 SPECIFICATIONS
Table 2-1 General Specifications
Table 2-2 Boiler Performance Specifications
Page 7
7
Elevations
2001 ft [610 m]
3000 ft [914 m]
4000 ft [1219 m]
4500 ft [1372 m]
5000 ft [1524 m]
In Canada1
de-rate by 10%
de-rate by 10%
de-rate by 10%
de-rate by 10%
de-rate % may vary
In USA2
-
de-rate by 12%
de-rate by 16%
de-rate by 18%
de-rate by 20%
Notes:
1
Canada: Altitudes between 2000 & 4500 ft. [610 &1372 m], de-rate by 10%. Consult local authorities for de-rating for
altitudes above 4500ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m], if altitude is above 2000 ft [610 m].
FTG│Installation & Operation Manual
High Altitude Operation
The FTG is designed to operate at its maximum listed capacity in installations located at 0-2000 ft above Sea
Level. Since the density of air decreases as elevation increases, maximum specified capacity should be de-rated
for elevations above 2000 ft [610 m] in accordance with Table 2-3.
Table 2-3 De-rate % for High Altitudes
Combustion – At elevations above 2000 feet, the combustion of the boiler must be
checked with a calibrated combustion analyzer to ensure safe and reliable operation. It is
the Installers responsibility to check the combustion and to adjust the combustion
in accordance with Section 9.0. Failure to follow these instructions may result in
property damage, serious injury, or death.
Page 8
8
Clearances
Dimensions - inches
Front
Top
Sides
Rear
3
Flue Pipe
Minimum
241
12 4 12
1
Recommended
36
24
24
2
24
1
Notes:
1
6 in. if surface is removable allowing a minimum of 24 in. clearance (i.e. closet installation). See Ventilation Air
Opening dimensions in Figure 3-1.
2
Recommend allowing 24” clearance on at least one side for servicing, clearance on opposite side can be as little as 4”.
3
Notice: the rear of the boiler must be accessible for installation and service.
Installation & Operation Manual│ FTG
3.0 BOILER LOCATION
In all cases, the FTG boiler must be installed indoors in a dry location where the ambient temperature must be
maintained above freezing and below 100F [38C]. All boiler components must be protected from dripping,
spraying water, or rain during operation and servicing. Consider the proximity of system piping, gas and
electrical supply, condensate disposal drain, and proximity to vent termination when determining the best boiler
location.
Floor Mounting
The FTG boiler can be mounted directly on combustible flooring, with the exception of carpeting. Installing the
boiler on carpeting is not permissible. Ensure the boiler is mounted above any anticipated flood level. Units
include factory supplied/field installed leveling legs. Once the unit is removed from the pallet, thread the
leveling legs into the allocated threaded inserts in the bottom of the unit.
Boiler Area Ventilation Air Openings
If boiler area clearances are less than the recommended clearances specified in Table 3-1, the boiler area must be
ventilated. EXCEPTION: if the boiler area/room has a volume of 365 ft3 or greater (275 ft3 for models FTG
600-800; 320 ft3 for models FTG 1200-1400), ventilation of the boiler room is not required. Each ventilation air
opening must meet the minimum requirements of 1 in2 per 1000 Btu/hr., but not less than 100 in2. The lower
ventilation opening must be located within 6 in. of the floor while the upper opening must be located 6 in. from
the top of the space.
Closet Installations
For closet installations it is necessary to provide two ventilation air openings as shown in Figure 3-1, each
providing a minimum area equal to 1 in2 per 1000 Btu/hr., but not less than 100 in2 and within 6 in. of the top
and bottom of the closet door. See Table 3-1 for minimum clearances.
Alcove Installations
Alcove installations have the same minimum clearances as closet installations, except the front must be
completely open to the room at a distance no greater than 18 in. [457 mm] from the front of the boiler and the
room is at least three (3) times the size of the alcove. Provided these conditions are met, the boiler requires no
extra ventilation air openings to the space. See Table 3-1 for minimum clearances.
Residential Garage Installations
When installed in a residential garage, mount the boiler a minimum of 18 in. [457 mm] above the floor. Locate
or protect the boiler so it cannot be damaged by a moving vehicle. Check with your local authorities for other
possible regulations pertaining to the installation of a boiler in a garage.
Table 3-1 Minimum Clearances for Installation and Service
Water or flood damaged components must be replaced immediately with new factory-
approved components as failure to do so may result in fire, serious injury, or death.
If the "Boiler Area" does not meet the recommended clearances listed in Table 3-1, and if
the boiler area has a volume less than 365 ft3, it is considered a Closet or Alcove. In
US/Canada, PVC vent pipe and fittings shall not be used within the closet or alcove; only
approved CPVC, Polypropylene or Stainless Steel vent pipe and fittings can be used. See
Table 4-4 for a list of approved materials. Under all circumstances, the minimum
clearances listed in Table 3-1 must be provided.
Exhaust Vent Pipe Clearances
as per Special Vent System
manufacturer’s instructions
Front = 6”
(if removable)
Rear = 12”
Ventilation air
opening 1in2 per 1000
Btu/hr, min. 100in
2
FTG │Installation & Operation Manual
Closet/Alcove installations in US and Canada require approved CPVC, Polypropylene or
Stainless Steel vent and air-inlet pipe and fittings (see Table 4-4); PVC is not permitted.
Failure to follow these instructions may result in damage or serious injury.
Cement powder, crack fill dust, cellulose, fiber based insulation
Concrete plant or construction site
Installation & Operation Manual│ FTG
4.0 GENERAL VENTING
The FTG boiler is certified as a “Category IV” boiler requiring a “Special Venting System” designed for
pressurized venting. The Exhaust Vent must be piped to the outdoors, using the vent materials and rules outlined
in this section. Under no conditions may this unit vent gases into a masonry chimney, unless it is vacant, and
utilizes the approved venting material and rules described in this section.
Vent and Air-inlet are to be piped separately. The FTG boiler cannot share a common
vent or air-inlet with multiple boilers.Failure to comply will result in serious injury or
Direct Vent Installation (Best Practice)
When installed as a Direct Vent boiler the combustion air-inlet must also be piped directly to the outdoors using
the methods described in this section and in accordance with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or
CSA B149.1 (Canada) and local requirements.
Installation Using Indoor Combustion Air
When the installation uses Indoor Combustion Air (i.e. piping is not directly connecting the appliance air-inlet
fitting to the outdoors), provisions for combustion and ventilation air, in accordance with section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (U.S.), or Clause 8.2, 8.3
or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1 (Canada), or applicable provisions of
the local building codes, must be adhered to.
Combustion Air-inlet Contamination
Be careful not to locate the air-inlet termination in an area where contaminants can be drawn in and used for
combustion. Combustion air containing dust, debris or air-borne contaminants will drastically increase the
required maintenance and may cause a corrosive reaction in the Heat Exchanger which could result in premature
failure, fire, serious injury, or death. See Table 4-1 for a list of areas to avoid when terminating air-inlet piping:
Table 4-1 Corrosive Products and Contaminant Sources
death.
The boiler shall be located so as not to interfere with proper circulation of combustion,
ventilation, and dilution air.
Make up air requirements for the operation of exhaust fans, kitchen ventilation systems,
clothes dryers, and fireplaces shall be considered in determining the adequacy of a space
to provide combustion air requirements. Failure to ensure adequate make up air to all
appliances may result in personal injury or death.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other boiler. Failure to follow instructions may result in serious injury or death.
It is BEST PRACTICE to pipe the combustion air-inlet directly to the outdoors (Direct
Vent installation) to avoid contamination often contained in indoor air.
Page 11
11
Model No.
Vent Pipe Size
CPVC Transition Vent Pipe Length
Full Insertion Depth
FTG 600-800
6”
Minimum 6.5” (factory supplied)
2-7/8”
FTG 1200-2400
8”
Minimum 9”
2-7/8”
FTG │Installation & Operation Manual
Flammable Solvents and Plastic Piping
Due to the extremely flammable characteristics of most glues, cements, solvents and primers used in the process
of joining plastic vent and air-inlet pipe, explosive solvent vapors must be evacuated from the vent and air-inlet
prior to start-up. Avoid using excess cement or primer that may lead to pooling inside the pipe assembly. Freshly
assembled piping assembly should be allowed to cure for a minimum of 8 hours before applying power to the gas
fired boiler. Refer to Mandatory Pre-commissioning Procedure for Plastic Ventingin this section.
to reduce these risks. Failure to follow these instructions can cause explosions, property damage, injury or death.
Mandatory Pre-commissioning Procedure for Plastic Venting (PVC or CPVC)
1) Working with the power turned off to the boiler, completely install the vent and air intake system, securely
cementing joints together. If possible, allow primers/cements to cure for 8 hours before firing the burner. If
curing time is less than 8 hours, proceed with Steps 2 through 6.
2) Maintain the boiler gas supply shut-off valve in the off position.
3) Remove the cable from the Spark Ignition Electrode and Ignition Transformer.
4) Turn power on to the boiler and apply a heat demand.
5) Allow for a complete trial for ignition, consisting of pre and post purge of the combustion blower, until an
ignition lockout occurs.
6) Turn power off and reconnect the cable to the Spark Ignition Electrode and Ignition Transformer.
Near Boiler Vent/Air-inlet Piping
Exhaust-vent Connector – the FTG exhaust-vent connector is designed to accept single-wall FasNSeal®
Stainless Steel (SS) Special Gas Venting. To use other types of venting, the appropriate adaptor must be
inserted into the boiler exhaust-vent connector; see Table 4-4 for a list of approved venting materials and
Table 4-3 for a list of approved boiler exhaust-vent adaptors.
Air-inlet Connector (FTG 600-800) – the FTG 600 & 800 employ a universal air-inlet connector that accepts
DuraVent’s 6 in. PolyPro
PVC/CPVC/ABS pipe, without the need for additional adapters. The universal connector incorporates three
seals, one for 6 in. PVC/CPVC/ABS pipe (6.625 in. OD), one for 6 in. PolyPro® PP pipe (5.94 in. OD) and
one for 6 in. FasNSeal® SS pipe (6 in. OD).
Air-inlet Connector (FTG 1200-2400) – the FTG 1200 through 2400 employ an 8 in. rubber coupling that
directly accepts most 8 in. diameter air-inlet pipe material.
PVC Exhaust Venting – When exhaust venting with PVC, insert a length of CPVC Pipe (see Table 4-2) into the
PVC/CPVC exhaust-vent adapter (see Table 4-3); cement the other end of the CPVC Transition Pipe to the
PVC exhaust venting using a field supplied PVC or CPVC coupling; see Figure 4-1(a). Where PVC cements
to CPVC, be sure to use an approved transition cement, see Table 4-4.
Table 4-2 CPVC Vent Pipe Transition Piece (used when venting with PVC)
Flammable Cements and Primers – It is the installers’ responsibility to familiarize
themselves with the hazards associated with explosive solvents and to take all precautions
Do not apply power to the boiler prior to Step 4 in the Mandatory Pre-commissioning
Procedure for Plastic Venting.
Spark Ignition Circuit - Maintain a safe distance (2 in. minimum) from the spark ignition
circuit to avoid injury from electrical shock.
Failure to use the appropriate exhaust-vent adaptor for the type of venting being used,
will lead to flue gas leakage possibly resulting in property damage, Carbon Monoxide
poisoning or death.
®
Polypropylene (PP) or FasNSeal® Stainless Steel (SS) pipe, as well as 6 in.
Page 12
12
Material
Vent Brand
FTG 600-800
FTG 1200-2400
Inlet
Exhaust
Inlet
Exhaust
Stainless
Steel
FasNSeal®
(DuraVent)
(See Note 1)
(See Note 2)
(See Note 3)
(See Note 4)
Z-Vent®
(Z-Flex)
Secure Seal® SS
(Security Chimneys)
SS6PVCU
SS6FFNSAU
SS8FFNSAU
Corr/Guard®
(Metal-Fab)
TBD
TBD
Saf-T Vent®
(Heatfab / Selkirk)
VIC
(ICC Chimney)
SWKL-Vt
(Jeremias)
Poly-
propylene
PolyPro®
(DuraVent)
(See Note 1)
FSA-06M-6PPF
FSA-08M-8PPF
Z-Dens®
(Z-Flex)
2ZDCPVCG6
2ZDZV6
2ZDZV8
InnoFlue®
(Centrotherm)
ISAAL0606
ISSA0606
ISSA0808
PVC/
CPVC
N/A
(See Note 1)
FSA-6FNSM-6PVCF
(factory supplied)
FSA-8FNSM-8PVCF
Notes:
1
The FTG 600-800 combustion air-inlet connector is designed to directly accept 6 in. PVC/CPVC, PolyPro®, FasNSeal®
or Z-Vent® Special Gas Venting; no separate adapter is required.
2
The FTG 600-800 exhaust vent outlet connector is designed to directly accept 6 in. FasNSeal® or Z-Vent® Special Gas
Venting; no separate adapter is required.
3
The FTG 1200-2400 use an 8 in. rubber adapter as the combustion air-inlet connector; no special adapter is required to
adapt to the respective brand of combustion air-inlet piping.
4
The FTG 1200-2400 exhaust vent outlet connector is designed to directly accept 8 in. FasNSeal® or Z-Vent® Special Gas
Venting; no separate adapter is required.
Installation & Operation Manual│ FTG
When assembling the venting, follow the instructions provided with the Special Venting
System. Take care not to damage gaskets when inserting pipe into fittings, bevel cut ends
of piping to avoid damaging or dislodging the sealing gasket during installation. For
Table 4-3 Exhaust-vent and Air-inlet Adapters
PVC/CPVC bevel by approximately 1/8 in.
Gasket Seating - Improper gasket seating can cause leakage and eventual failure of the
sealing gasket. Ensure the vent pipe is properly beveled, prior to installation, and that the
pipe is fully inserted into the exhaust-vent adapter. Failure to follow these instructions
may result in serious injury or death.
DO NOT insert PVC pipe directly into the PVC/CPVC exhaust-vent adapter; the
clamping force of the gear clamp can deform the PVC pipe. Failure to follow these
instructions may result in gasket failure and/or the dislodging of the exhaust pipe from the
exhaust-vent adapter, resulting in property damage, serious injury or death.
Exhaust venting must be supported to reduce strain on piping joints. Failure to follow
these instructions may result in result in damage, serious injury or death.
In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection.
Page 13
13
Figure 4-1(a) Near Boiler Venting (PVC)
Figure 4-1(b) Near Boiler Venting (CPVC)
Figure 4-1(c) Near Boiler Venting (PP)
Figure 4-1(d) Near Boiler Venting (SS)
Adapter to CPVC
(see Table 4-3)
PVC Air-inlet Pipe*
CPVC
Exhaust-vent
Air-inlet
Exhaust
Adapter to PP
(field supplied –
see Table 4-3)
PP Air-inlet Pipe
(PolyPro® illustrated)
Air-inlet
Exhaust
PP Exhaust-vent
(PolyPro® illustrated)
SS Air-inlet Pipe
(FasNSeal® illustrated)
Air-inlet
Exhaust
SS Exhaust-vent
(FasNSeal® illustrated)
CPVC Transition
Pipe (see Table 4-2)
Adapter to CPVC
(see Table 4-3)
**CPVC Transition Pipe
is mandatory when
venting with PVC
PVC Coupling
PVC Air-inlet Pipe*
PVC Exhaust-vent
Air-inlet
Exhaust
FTG │Installation & Operation Manual
Air-inlet - check with applicable local codes for acceptable pipe material.
Page 14
14
Items 1
Materials
2, 3
Venting System Standards
All Vent and Air-Inlet
materials installed on gas
fired appliances in CAN/US
must meet the Standards
listed in this Table. Failure
to comply could result in
fire, serious injury or death.
United States
Canada 4
Vent Piping
and Fittings
PVC - DWV
ANSI/ASTM D2265
All venting material in
Canada must be
ULC S636 approved.
PVC Schedule 40
ANSI/ASTM D1785
CPVC Schedule 40
ANSI/ASTM F441
Stainless Steel (SS)
UL-1738
Polypropylene (PP)
ULC S636
Pipe Cement
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
Primers
PVC / CPVC
ANSI/ASTM F656
Notes:
1
Refer to Table 4-5 for Allowable Vent and Air-inlet Pipe Sizes and Lengths.
2
PVC venting (exhaust and air-inlet) is not permitted within the Closet/alcove of a Closet/alcove installation.
3
The Air-inlet does not require high temperature pipe material. Check applicable local codes for acceptable materials.
Model No.
Fuel
Pipe Dia.
(in.)
Length
(ft.)
Number of Elbows (90’s or 45’s) and Equivalent Feet
1 2 3 4 5 6 7 8 9
FTG 600-800
NG 6 150
145
140
135
130
125
120
115
110
105
LP 6 100
95
90
85
80
75
70
65
60
55
FTG 1200-2400
NG/LP
8
150
145
140
135
130
125
120
115
110
105
Notes:
1
Minimum length of each the exhaust vent and combustion air-inlet piping is 5 feet equivalent.
2
For models FTG 600-800, the last 6 ft. of exhaust vent piping (vent termination) can be reduced to 4 or 5 in. diameter
vent pipe.
3
For models FTG 1200-2400, the last 6 ft. of exhaust vent piping (vent termination) can be reduced to 6 or 7 in. diameter
vent pipe.
Installation & Operation Manual│ FTG
Exhaust-vent/Air-inlet Pipe Material
Table 4-4 Approved Vent and Air-Inlet Pipe Material
The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel®
(polyphenolsulfone) in the exhaust venting system is prohibited. Failure to follow these
Vent/Air-inlet Pipe Length Determination
Use Table 4-5 to determine the maximum pipe length that can be used. The table calculates 90º elbows, and 45º
elbows at 5 equivalent feet each.
Table 4-5 Allowable Vent and Air-inlet Pipe Size and Lengths
instructions may result in property damage, personal injury or death.
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. Failure
to follow these instructions may result in property damage, personal injury or death.
Termination Options – Direct Vent Installation
The venting system of the FTG boiler may be terminated using field supplied piping to construct a “Two-Pipe”
termination, see Figures 4-2, 4-4(a) and 4-5(a); alternatively the venting may be terminated using a factory kit
selected from Table 4-6.
Venting Options - Due to potential moisture loading (build-up) along the exterior wall,
sidewall venting may not be the preferred venting option; see Figures 4-2(a), 4-2(c), 4-3(a)
and 4-5.
When sidewall venting, it is recommended to reduce the diameter of the exhaust vent at
the termination, to increase exhaust gas velocity, further directing it away from the
building. The final 6 ft. of exhaust vent can be reduced to a diameter of 4 in. for models
FTG 600-800, and 6 in. for models FTG 1200-2400; see Figures 4-2(a) and 4-2(c).
Page 15
15
Description
Vent
Size
Supplier P/N
Figure
Vent Material
Compatibility
Termination
Roof
Wall
IPEX Low Profile (Wall)
7
4”
196986 (NTI P/N 84358)
4-4(c)
PVC/CPVC
7
-
IPEX Concentric
(Wall/Roof)
5,6,7
4”
196021 (NTI P/N 84355),
197021
4-3(a), 4-4(b),
4-5(b)
PolyPro® Twin Pipe (Wall)
4”
4PPS-HTPL
4-4(c)
PolyPro®
Polypropylene
-
PolyPro® Concentric (Wall)
4”
4PPS-HK
4-3(b), 4-4(d)
PolyPro® Concentric (Roof)
4”
4PPS-VK
4-3(a), 4-5(c)
-
InnoFlue® Concentric
(Wall)
8
4”
(ICWT462 & ICTC0446)
4-3(b), 4-4(d)
InnoFlue®
Polypropylene
-
InnoFlue® Concentric
(Roof)
8
4”
(ICRT4679 & ICTC0446)
4-3(a), 4-5(c)
-
Z-DENS® Horizontal Kit
Low Profile (Wall)
4”
2ZDHKLP4
4-4(c)
Z-DENS®
Polypropylene
-
Z-DENS® Concentric
(Wall)
4”
2ZDHK4
4-3(b), 4-4(d)
Z-DENS® Concentric
(Roof)
4”
2ZDVK4
4-3(a), 4-5(c)
-
Z-VENT® Termination
Hood – Exhaust (Wall)
4-5”
2SVSHTX04, 2SVSHTX05
Z-VENT®
Stainless Steel
-
SS Miter Cut – Exhaust
(Wall)
4-8”
SS4MCU – SS8MCU
Secure Seal®
Stainless Steel
-
Saf-T Vent® Mitered
Termination – Exhaust
(Wall)
4-8”
9490, 9590, 9690, 9790 &
9890
Saf-T Vent®
Stainless Steel
-
ICC Miter Cut – Exhaust
(Wall)
5-8”
HM-5MC – HM-8MC
ICC Chimney
Stainless Steel
-
Notes:
1
Instructions included with termination kits contain detailed assembly and installation instructions.
2
Concentric kits can be shortened to fit the requirements of the installation; see instructions included with the kit for
more details.
3
Clearance requirements in this manual supersede those of the instructions included with the vent terminal.
4
Piping MUST be secured to the vent terminal during installation.
5
IPEX Concentric Terminal MUST be cemented together and to the vent pipes during installation.
6
Vent Screens provided with boiler may be used with the IPEX Concentric Vent Kits; otherwise use IPEX vent screens
(4 in. vent screen P/N 196052 – each sold separately).
7
IPEX Low Profile and Concentric kits (excluding P/N 197021) are constructed out of ULC S636 approved PVC;
check with your local authority for the acceptance of PVC as a venting material prior to use.
8
Centrotherm Concentric termination kits must use the applicable “Twin pipe to concentric adapter,” part number
ICTC0446.
9
4 & 5 in. Vent Termination Kits may only be used with models FTG 600-800.
10
7 & 8 in. Vent Termination Kits may only be used with models FTG 1200-2400.
FTG │Installation & Operation Manual
The vent for this appliance shall not terminate over public walkways; or near soffit vents
or crawl space vents or other area where condensate of vapor could create a nuisance or
hazard or cause property damage; or where condensate or vapor could cause damage or
could be detrimental to the operation of regulators, relief valves, or other equipment.
Optional Termination Kits – Direct Vent Installation
Kits certified with the FTG boiler are listed in Table 4-6 and are available from the respective vent pipe
manufacturer. For more information on each kit, contact the kit manufacturer.
Table 4-6 Optional Vent Termination Kits
Page 16
16
Figure 4-2(a) Two-pipe (Sidewall)
Figure 4-2(b) Two-pipe (Roof)
Figure 4-2(c) Two-pipe (Rooftop / Sidewall)
Combustion Air-inlet
– pointing down, min.
12in. above snow level
Exhaust – pointing
up, min. 18in. above
combustion air-inlet
Combustion Air-inlet
– pointing down, min.
12in. above snow level
Exhaust – pointing
out, min. 18in. above
combustion air-inlet
Combustion Air-inlet
– pointing down, min.
12in. above snow level
Exhaust – pointing
up, min. 12in.
above snow level
Combustion Air-inlet
– pointing down, min.
12in. above snow level
Exhaust – pointing
out, min. 12in.
above snow level
Installation & Operation Manual│ FTG
Page 17
17
Figure 4-3(a) Concentric (Roof)
Figure 4-3(b) Concentric (Sidewall)
Refer to vent-teminal
manufacturer instructions
for correctly connecting
to vent-terminal
Combustion Air-inlet
– drawn from bottom of
bell shape, min. 12in.
above snow level
Exhaust –
exits the top
Exhaust
Air-inlet
Combustion Air-inlet
– drawn from bottom or
circumference, min.
12in. above snow level
Exhaust –
exits the center
Exhaust
Air-inlet
Refer to vent-teminal
manufacturer instructions
for correctly connecting
to vent-terminal
FTG │Installation & Operation Manual
Concentric and Low Profile Vent Termination Kits are only available in sizes up to 4 in.;
therefore they are not an option for models FTG 1200-2400.
Page 18
18
Sidewall Termination Details – Direct Vent Installation
Figure 4-4(a)
Figure 4-4(b)
Two-Pipe Termination (Sidewall)
IPEX Concentric Termination (Sidewall)
Refer to documentation included with termination kit for
complete installation instructions.
Figure 4-4(c)
Figure 4-4(d)
Low Profile Termination (Sidewall)
PolyPro / InnoFlue Termination (Sidewall)
Refer to documentation included with termination kit for
complete installation instructions.
Min. 12”
above grade
or snow level
Exhaust
Air-inlet
Exhaust
Air-inlet around
perimeter
Min. 12”
above grade
or snow level
Exhaust center
Air-inlet bottom
Exhaust
Air-inlet
Gas Vent Directly Below
Keep Free of Obstructions
Refer to documentation included with termination kit for
complete installation instructions.
Exhaust
Air-inlet
Min. 12”
above grade
or snow level
Vertical
Min. 18”
Horizontal
4-12” or greater than 36”
Exhaust
Air-inlet
Vent Screen
Vent pipe piece to
retain vent screen
Gas Vent Directly Below
Keep Free of Obstructions
Exhaust
Air-inlet
Min. 12”
above grade
or snow level
Air-inlet around
perimeter (1-2”
from wall)
Exhaust through
center
Vent Screen
Vent pipe piece to
retain vent screen
Installation & Operation Manual│ FTG
Page 19
FTG │Installation & Operation Manual
19
Roof Termination Details – Direct Vent Installation
Figure 4-5(a)
Figure 4-5(b)
Two-Pipe Termination (Roof)
IPEX Concentric Termination (Roof)
Figure 4-5(c)
Figure 4-5(d)
PolyPro / InnoFlue Termination (Roof)
Exhaust only Termination (Roof)
Min. 12”
above grade
or snow level
Vent Screen
Vent pipe piece to
retain vent screen
Exhaust
Air-inlet
Vertical
Min. 18”
Horizontal
4-12” or greater
than 36”
Flashing
Min. 12”
above grade
or snow level
Vent Screen
Vent pipe piece to
retain vent screen
Exhaust center
Air-inlet around
perimeter
Flashing
Refer to documentation included with termination kit for
complete installation instructions.
Refer to documentation included with termination kit for
complete installation instructions.
Min. 12”
above grade
or snow level
Flashing
Exhaust
Air-inlet
Figure illustrates two options for exhaust termination only;
neither vent pipe illustrated is for combustion air-inlet.
Min. 12”
above grade
or snow level
Flashing
Vent pipe piece to
retain vent screen
Vent Screen
Exhaust
Option 1
Exhaust
Option 2
Page 20
20
Installation & Operation Manual│ FTG
Venting Rules and Guidelines
1. Prevailing Winds: Ensure the vent is located where it will not be exposed to normal prevailing winds.
2. Combustion Air-inlet Contamination: Air for combustion must be drawn from an area free of dust and
contaminants. Combustion air containing chemicals such as chloride, fluoride, bromine or iodine or dust and
debris will cause corrosion damage of the heat exchanger voiding your NTI warranty. Refer to Table 4-1 for
a list of corrosive products and contaminants sources to avoid.
3.Vertical Separation: The exhaust must be a minimum of 18 in. above the air inlet, and the air inlet must
always be a minimum of 12 in. plus snow allowance above any surface that will support snow. (Two feet
plus snow allowance is highly recommended). Consult your weather office for the maximum typical
snowfall for your region.
Example: New Brunswick Canada - typical maximum snowfall is 19 in., thus the inlet must be (12”+19”) =
31 in. above grade and exhaust must be (31”+18”) =49” above grade.
4.Horizontal Separation: The horizontal distance between the inlet and exhaust must be a minimum of 4”
[102 mm] center to center.
5.Wall Flashing: Under normal operating conditions this boiler will produce a plume of white gases, and
should be taken into consideration when selecting an adequate location. A 36 in. diameter stainless, plastic,
or vinyl shield can be used to flash the exterior of the residence.
6.Flue Gas Hazard: Position the vent termination where vapors cannot make accidental contact with people
and pets or damage nearby shrubs and plants.
7. Elbow Extensions: Elbows on outside of wall must be no more than ½ in. away from the wall.
8. Vent Sloping: All indoor exhaust piping must be on a slope back to the boiler a minimum of ¼ in. per
linear foot of vent. For applications where excessive condensation is possible ½ in. per linear foot is
recommended.
9.Vent Supports: Where required Vent and Air-inlet piping shall be secured to the wall for more rigidity. All
interior vent pipe shall be supported a minimum of every 36 in.
10. Roof Exhaust: In all roof applications the discharge must point away from the pitch of the roof.
11. Roof Flashing: Install adequate flashing where the pipe enters the roof, to prevent water leakage.
12. Rain Cap: Install and seal a rain cap over existing chimney openings, in vacant chimney applications.
13. Venting Below Grade: For installations that exit the wall below grade refer to Figure 4-6.
14. Vent Screens: Install factory supplied vent screens on the outside of the last fitting for both the inlet and
exhaust vent terminations. Install the screen into the female opening of the fitting, then cut a small piece of
pipe to sandwich the screen into the elbow. NOTE: ensure the small piece of cut pipe, does not extend past
the end of the fitting. Two screens are provided in the package. See Figures 4-4 and 4-5.
15.Condensate Hazard: Do not locate vent over public walkways, driveways or parking lots. Condensate
could drip and freeze resulting in a slip hazard or damage to vehicles and machinery.
16.Warning Plate: For Sidewall Venting, install the warning plate “Gas Vent Directly Below”, directly above
(within 4 ft. vertically) the location of the air-inlet pipe, so it is visible from at least 8 ft away. See Figure 4-
4.
17.Wall Thickness: Direct vent terminations are designed to work with any standard wall thickness.
Installation guidelines for min/max wall thickness are as follows: Min. = 1 in., Max. = 60 in...
18.Venting Options: Due to potential moisture loading (build-up) along the exterior wall, sidewall venting
may not be the preferred venting option. Refer to Figures 4-2(a), 4-2(c), 4-3(a) and 4-5 for roof top venting
options.
Page 21
21
Figure 4-6 Venting Below Grade
For installations that exit the wall below grade:
1. Excavate site to a point below where the pipes
are to exit as shown.
2. Ensure the wall is fully sealed where the pipes
penetrate.
3. The Vent/Air-inlet piping MUST be secured to
the side of the building above grade, as shown,
to provide rigidity.
4. Ensure that the Vent/Air-inlet clearances are
maintained, see Section 5.0 for details.
Figure 4-7 Outdoor Venting
Vent piping outside the building is permitted under
the following conditions:
1. The maximum length outside the building is 20 ft.
Note that outdoor length must be included in the
overall vent length calculation.
2. All normal termination clearances are maintained.
3. The pipe is supported every 24 in...
4. The exhaust and inlet are sloped back to the boiler
½ in. elevation for every linear foot.
Figure 4-8 Existing Chimney Chase Way
It is permissible to use an existing chimney as a chase
way to run the Vent/Air-inlet piping as long as:
1. The chimney is not being used by any other
boiler.
2. Flue gases do not enter the vacant chimney.
3. Only FTG certified venting materials are used,
see Table 4-4.
4. Vent lengths are within the maximums specified.
5. The top of the chimney is capped and the
Vent/Air-inlet pipes are flashed to prevent
leakage into the vacant chimney.
Exhaust
Air-inlet
Wall Brackets
Supports every
24 in. [610 mm]
12 in. [305 mm] plus snow
allowance above grade
Air-Inlet
Maximum of 20 ft.
[6.1 m] is permitted
for piping outside a
building.
Exhaust
Vent
Gas Vent Directly Below
Keep Free of Obstructions
Air-Inlet
Existing
Chimney
(used as a
chase way)
Chimney
Cap
Exhaust Vent
Exhaust Vent Min.
18 in. above airinlet
Air-Inlet
Min. 12 in. above
roof and snow level
FTG │Installation & Operation Manual
Page 22
22
Clearances to Air-Inlet Termination
Canada 1
USA 2
Min. Distance
Min. Distance
A
Above grade/roofline and snow level 8
12 in.
305 mm
12 in.
305 mm
B
Above roof line - Concentric Vent
6, 11, 13
24 in.
610 mm
24 in.
610 mm
C
To exhaust vent from any other boiler
36 in.
915 mm
12 in.
305 mm
Clearances to Exhaust Vent Termination
Min. Distance
Min. Distance
A
Above grade/roofline and snow level 8
12 in.
305 mm
12 in.
305 mm
D
Minimum vertical separation above air inlet 9
18 in.
457 mm
18 in.
457 mm
E
Minimum horizontal separation from air inlet 3
4 in.
102 mm
4 in.
102 mm
F
Window or door that may be opened, or other building opening
36 in.
915 mm
12 in.
305 mm
G
To combustion air inlet of any other appliance
36 in.
915 mm
12 in.
305 mm
H
Non-mechanical air supply inlet to building
36 in.
915 mm
12 in.
305 mm
I
Mechanical air supply inlet to building 4
6 ft.
1.83 m
3 ft.
915 mm
J
Soffit, overhang, eave or parapet
24 in.
610 mm
24 in.
610 mm
K
Soffit vent or vent opening in an overhang, eave or parapet
6 ft.
1.83 m
6 ft.
1.83 m
L
Outside corner 10
- - -
-
M
Inside corner of an L-shaped structure (including walls and fences)
36 in.
915 mm
36 in.
915 mm
N
Service regulator / vent outlet
36 in.
915 mm
36 in.
915 mm
P
Each side of center line above or below meter / regulator assembly 5
36 in.
915 mm
36 in.
915 mm
Q
Above a paved sidewalk, driveway, or parking lot on public property if adjacent12
7 ft.
2.13 m
7 ft.
2.13 m
R
Above a public walkway
X X X
X
S
Above a sidewalk or paved driveway that is located between two single family
dwellings and services both dwellings
X X X
X
T
Under a concrete veranda, porch, deck, or balcony 7
24 in.
610 mm
24 in.
610 mm
U
Above, under or near exterior stairs
X X X
X
V
Into a canopy or carport
X X X
X
Notes:
1 - Canadian installations must comply with the current CSA B149.1 Natural Gas and Propane Installation Code and local
building codes.
2 - US installations must comply with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code and local building codes.
3 - Horizontal separation center-to-center (c.c.) 4”-12” (102-305 mm).
4 - For US installations, an exhaust vent must be 3 ft above a mechanical air supply inlet if within 10 ft. [3 m] horizontally.
5 -Horizontal clearance must be observed up to a height of 15 ft. [4.6 m] above/below the meter, regulator, or relief devices.
6 - Concentric Vent must protrude from the roof precisely 24” [610 mm] measuring from the terminal end-cap vanes.
7 - Permitted if veranda, porch, deck, or balcony is made of concrete and a minimum of two sides are fully open beneath.
8 - 24” is the recommended snow level allowance above grade/roofline or any surface that will support snow, debris, or ice
(i.e. for roof venting clearances - roofline and snow level). If living in a snowfall region, consult your local weather
office for the maximum typical snowfall for your area.
9 - Note that the vent must maintain a minimum vertical distance above the air-inlet. Example: Vent height = 18” (457
mm) above air inlet + 12” (305 mm) for air inlet above grade/roof line and snow level = 30” (762 mm) above grade and
snow level.
10-Clearances to an outside corner to be in accordance with local installation codes.
11-In Canada, concentric vent materials are subject to approval by local inspectors. See Termination Kits in Section 4.0.
12-Above public walkways, driveways or parking lots if adjacent to it and condensate cannot drip, freeze, or create a hazard.
13-Contact the manufacturer for special exemptions relating to multiple boiler installations using concentric vents.
Installation & Operation Manual│FTG
5.0 VENT/AIR-INLET TERMINATION CLEARANCES
instructions detailed in this section are a combination of FTG specific and National Gas Code restrictions.
Compliance alone does not insure a satisfactory installation as good common sense must also be applied. Failure
to follow these instructions may result in fire, property damage, serious injury or death.
Table 5-1 Termination Clearances Quick Reference Table (See Figures 5-1 and 5-2)
The quick reference table below is to be read in conjunction with the numbered notes as
indicated, Figures 5-1 and 5-2, and the Venting Rules and Guidelines in Section 4.0. The
Page 23
23
G – Letter represents a specific Termination Position. Refer to Table 5-1 for corresponding termination clearances.
Concentric Vent
Termination
Q
Two-Pipe
Termination
F
Clearance “Q”
Adjacent to Public
Walkway or Driveway
Minimum 7ft. [2.13 m]
G
Clearances “F” and “G”
Canada – Minimum 3 ft. [915 mm]
The US– Minimum 1 ft. [305 mm]
FTG │Installation & Operation Manual
Figure 5-1 Termination Clearance Quick Reference Diagram (See Table 5-1)
Illustrations of Termination Clearances
Figure 5-2 Sidewall Termination (See Table 5-1)
Page 24
24
Installation & Operation Manual│FTG
Removing an Existing Boiler from Common Venting System
Upon removal of an existing boiler, the following steps shall be followed for each boiler remaining in the
common venting system; prior to commencing this procedure, shutdown all boilers remaining in the common
venting system.
Steps to Removing an Existing Boiler:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch. Verify that there is no blockage,
restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close fireplace dampers, all building doors and windows and all doors between the
space in which the boilers remaining connected to the common venting system are located and other spaces
of the building. Turn on clothes dryers and any boiler not connected to the common venting system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do
not operate a summer exhaust fan.
4. Place in operation the boiler being inspected. Follow the applicable lighting instructions. Adjust thermostat
so boiler will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each boiler remaining connected to the common venting system properly
vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other
gas burning boiler to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms to
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code. When resizing any portion of the common venting system, the common venting system
should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code.
Extra precaution must be taken to adequately support the weight of the Vent/Air-inlet
piping in applications using roof-top terminations. Failure to follow these instructions
may result in venting or boiler component failure resulting in flue gas spillage leading to
property damage, serious injury or death.
Under no circumstances may an existing chimney or chase-way be used to vent or
provide combustion inlet air to an FTG boiler. Failure to follow these instructions will
result in fire, property damage, serious injury or death.
Do not install the FTG boiler into a common venting system with any other boiler.
Failure to comply with this warning will cause flue gas spillage and leech carbon
monoxide emissions into the surrounding air resulting in serious injury or death.
When an existing boiler is removed from a common venting system, the common venting
system is likely to be too large for proper venting of the remaining boilers connected to
it. Instructions have been provided on how to remove the existing boiler and how to
resize the remaining venting system. Failure to follow these instructions may result in
property damage, serious injury or death.
Page 25
25
FTG │Installation & Operation Manual
6.0 CONDENSATE DRAIN
The FTG boiler produces liquid condensate in the heat exchanger and venting system as a product of
combustion. Steps must be taken to ensure condensate does not collect in the venting system; therefore, all
exhaust piping must slope back to the boiler a minimum ¼ in. per linear foot of vent. Condensate must be
drained from the unit into a household drain.
Check with your municipality, or local gas company to determine if the disposal of
combustion condensate is permitted in your area (e.g. in the State of Massachusetts the
The following are important notes that must be taken into consideration when constructing the condensate drain
system (see Condensate Trap Installation Instructions for further details):
DO NOT install condensate lines outside. A frozen or blocked drain will cause the condensate to back-up
and leak. This may result in damage to boiler components resulting in a no heat condition; property damage
may also occur.
NEVER use copper, steel, or galvanized piping in the construction of the condensate system (condensate is
very corrosive and will corrode most metals).
When a condensate pump is used or required, select a pump that is designed for residential furnaces.
Condensate Trap Installation Instructions (see Figure 6-1)
(Note: the Condensate Trap is factory supplied with the boiler and must be field installed)
1. Identify Condensate Trap & Accessories Provided with the Boiler – A Condensate Trap, Gear Clamp
and Support Bracket (c/w screws) are factory supplied with each FTG boiler, and are needed for properly
securing the Condensate Trap to the boiler (see Figure 6-1).
2. Attach to Boiler Condensate Drain – As illustrated in Figure 6-1(a), slide the Condensate Trap inlet fitting
over the Boiler Condensate Drain; use the factory supplied Gear Clamp to secure the Condensate Trap in
place (ensure that the Condensate Trap cannot be pulled off). With the factory supplied screws, fasten the
Support Bracket into place while trapping the top of the Condensate Trap between the Support Bracket and
boiler, thus ensuring the Condensate Trap stays in the vertical position.
3. Prime Condensate Trap – Fill the Condensate Trap with water to prevent flue gases from escaping during
initial firing of the burner.
4. Outlet to Drain – Direct condensate from the outlet of the Condensate Trap to a household drain,
condensate pump or neutralizer (check with your local authority regarding the disposal of condensate). If
necessary connect suitable tubing to the outlet of the Condensate Trap and route it to drain, being careful
NOT to route it higher than the Condensate Trap outlet (see Figure 6-1).
condensate must be neutralized prior to entering a drain).
All tubing, drains and surfaces that come in contact with condensate draining from the
boiler, must be constructed out of corrosion resistant material; copper, steel and
galvanized are not acceptable materials for draining condensate. Failure to abide by this
caution will result in property damage.
The Condensate Trap must be periodically disassembled and cleaned as part of a regular
maintenance plan. Failure to clean the trap regularly can cause condensate drain blockage
leading to boiler malfunction, property damage and even personal injury.
Carefully follow the above instructions and the accompanying figure – check to ensure
the Condensate Trap is secure and that no strain is placed on it. Failure to install the
condensate trap properly will result in flue gas spillage and leeching of carbon monoxide
emissions into the surroundings resulting in serious injury or death.
Prime Condensate Trap with
water before firing boiler
Position the Condensate Trap
inside the Support Bracket, then
fasten the bracket to the boiler.
Installation & Operation Manual│FTG
Page 27
27
FTG │Installation & Operation Manual
7.0 INSTALLING GAS PIPING
FTG boilers are factory set to operate with Natural Gas; BEFORE OPERATING
WITH PROPANE, the boiler’s gas valve must be adjusted in accordance with the
applicable Natural Gas to LP Conversion Instructions. Failure to properly convert the
unit to safely operate with Propane will cause severe boiler failure, resulting in property
damage, serious injury or death.
Liquefied Petroleum (LP) propane gas is heavier than air. Do not install the boiler in a pit
or similar location that will permit heavier than air gas to collect. Check with Local
Codes as they may require boilers fueled with LP gas to be provided with an approved
means of removing unburned gases from the room. Failure to follow these instructions
Installation
Refer to the current National Fuel Gas Code ANSI Z223.1/NFPA 54 or CAN/CGA B149.1 installation codes,
and local codes for gas piping requirements and sizing. Pipe size running to the unit depends on:
Length of pipe.
Number of fittings.
Type of gas.
Maximum input requirement of all gas boilers in the residence.
Ensure that:
The gas line connection to the boiler does not apply any weight to the gas valve. NTI recommends using
approved flexible gas piping (if acceptable by local codes) to connect the boiler to the gas supply (see Figure
7-1 for details).
You plan the installation so the piping does not interfere with the vent pipe, or the removal of the valve,
burner, and serviceable components.
The Boiler is installed such that the gas ignition system components are protected from water (dripping,
spraying, rain etc.) during installation and servicing.
The gas piping is large enough for all the gas appliances in the home. No appreciable drop in line pressure
should occur when any unit (or combination of units) lights or runs. Use common gas-line sizing practices.
Always use a pipe-threading compound that is resistant to Propane (LP) gas solvent action. Apply sparingly
to all male threads, starting at two threads from the end. Over doping or applying dope to the female end,
can result in a blocked gas line.
DO NOT TIGHTEN FITTINGS WITHOUT SUPPORTING THE INTERNAL GAS LINE CONNECTION
WITHIN THE BOILER as damage to the boiler’s internal gas carrying components could occur.
Install a manual “Equipment Shut-Off Valve” as shown in Figure 7-1. Valve must be listed by a nationally
recognized testing laboratory.
The gas line piping can safely be removed from the boiler for servicing, by strategically placing the gas line
shutoff and union; see example in Figure 7-1.
All gas piping, including gas components in the boiler, are checked for leaks using a “Bubble Test”, prior to
operating the boiler.
may result in serious injury or death.
Strain on the gas valve and fittings may result in vibration, premature component failure
and leakage and may result in a fire, explosion, property damage, serious injury or death.
Do not use an open flame to test for gas leaks. Failure to follow these instructions may
result in fire, property damage, serious injury or death.
When performing a pressure test on the gas line piping, be sure the boiler is disconnected
or isolated if the test pressure is expected to exceed 1/2 PSI (14 in. w.c.), as damage to the
gas valve could occur resulting in fire, property damage, serious injury or death.
Page 28
28
Figure 7-1 Gas Line Connection (Typical)
Apply propane gas compatible pipe sealing compound to the male-end of all treaded
connections before assembly. Support boiler gas line connection during assembly of
gas piping to prevent damage to internal boiler components. Failure to follow these
instructions may result in fire, property damage, serious injury or death.
Test all gas piping, internal and external to the boiler, for leaks. Failure to follow
these instructions may result in fire, property damage, serious injury or death.
Drip Leg / Sediment Trap
(field supplied)
Union
(field supplied)
Manual Gas Shutoff Valve
(Factory Supplied)
Should overheating occur or
the gas supply fails to shutoff,
close the Manual Gas Shutoff
Valve to the boiler.
Gas Supply Line
Must be externally supported.
DO NOT support with boiler
gas line connection.
Installation & Operation Manual│FTG
Page 29
29
FTG │Installation & Operation Manual
8.0 LIGHTING THE BOILER
Before Start-up refer to Mandatory Pre-commissioning Procedure for Plastic Venting
in Section 4.0.Failure to follow these instructions can result in explosions, injury or death.
Prior to turning the gas supply on and lighting the boiler, ensure all aspects of the
installation are complete and in conformance with the instructions provided in this
manual, including the Vent/Air-inlet, Condensate Drain, and System Water Piping. Failure to precisely follow
these instructions will cause a fire or explosion resulting in property damage, serious injury or death.
A) This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
B) BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any boiler.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to turn the gas “shutoff” valve. Never use tools. If the handle will not turn by hand, do
not try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or
explosion.
D) Do not use this boiler if any part has been under water. Immediately call a qualified service technician
to inspect the boiler and to replace any part of the control system and any gas control which has been
under water.
1. STOP! Read the safety information above very carefully.
2. Set the thermostat to lowest setting. Turn off all electric power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device which automatically lights the
burner. Do not try to light the burner by hand.
4. Turn the manual gas valve to the OFF position. Remove front access panel.
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
6. Turn the manual gas valve ON. Wait an additional five (5) minutes smelling for gas.
7. Replace the front access panel.
8. Set thermostat to highest setting. Turn on all electric power to the boiler.
9. Ignition sequence is automatic. Combustion will occur after a brief fan purge.
10. If ignition does not occur, follow the instructions “To Turn Off Gas To Boiler” and call your service
technician or gas supplier.
1. STOP! Read the safety information above very carefully.
2. Turn off all electric power to the boiler
3. Turn the manual gas valve to the OFF position
Do not store or use gasoline or other flammable vapors & liquids in the vicinity of this or
any other boiler. Failure to follow instructions could result in explosion causing property
damage, serious injury or death.
If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, serious injury or death.
Should overheating occur or the gas supply fails to shutoff, close the Manual Gas Shutoff
Valve to the boiler. Failure to follow instructions could result in explosion causing
property damage, serious injury or death.
FOR YOUR SAFETY, READ BEFORE OPERATING_
OPERATING INSTRUCTIONS_
TO TURN OFF GAS TO THE BOILER_
Page 30
30
Installation & Operation Manual│FTG
Ensure the boiler is wired in accordance with this manual.
Ensure the gas shutoff valve is turned on, and that the gas system has been fully tested for leaks.
Ensure the system is completely filled with water, and that ALL the air is purged out.
Ensure the Vent and Air-inlet piping is completely installed in accordance with this manual.
Initial Start-Up
1. Turn on power to the boiler and turn-up the Thermostat(s). The boiler should run through a purge, and
combustion should occur. (The control system has a built-in ignition retry, allowing the system to try at least
two times, before locking-out.)
2. With the unit operating at full capacity, verify that the gas line pressure is 4-10.5 inches w.c. for Natural gas,
and 8-13 inches w.c. for Propane (see Section 9.0 for details).
3. Using an appropriate Oxygen (O2) or Carbon Dioxide (CO2) analyzer, take a sample of the flue gas. The
sample must fall within the acceptable ranges for CO2 (see Section 9.0 for details).
4. Perform at least three ignitions in succession to ensure proper operation.
5. After the three successive ignitions, unplug the flame sensor and allow the unit to cycle again. The flame
safety system will allow the unit to go through 2 ignition cycles before going to “Lockout 110 – Ignition
failure occurred”. Once you have confirmed this behavior, reinstall the wire on the flame sensor, clear the
lockout and reconfirm proper ignition.
located in the burner plate); this device is used for spark ignition and produces 20,000 Volts potential which
would result in an EXTREME ELECTRICAL SHOCK possibly causing serious injury or death.
burner is rough or erratic. Failure to follow these instructions may result in serious injury or death.
Re-lighting Unit
1. Stop and read these instructions very carefully.
2. Set the thermostat to the lowest setting, and then turn off all power to the boiler.
3. This boiler does not have a pilot. It is equipped with an ignition device that automatically lights the burner.
Do not try to light the burner by hand.
4. Turn the gas shutoff valve to the off position, and then remove the front cover.
5. Wait five (5) minutes to clear out any gas. Then check for gas, including near the floor. If you smell gas
“Stop” and follow “B” above (see FOR YOUR SAFETY, READ BEFORE OPERATING). If you do
not detect any gas proceed to the next step.
6. Turn the gas shutoff valve to the on position, wait an addition five (5) minutes and check for gas.
7. Replace the front cover.
8. Set the thermostat to the highest setting, and then turn on all power to the boiler.
9. Ignition sequence is automatic, combustion will occur after a brief fan purge. Ignition will retry once.
10. If ignition does not occur, “Turn off the gas and electricity to the boiler” and contact a qualified service
technician, or gas supplier.
Turning Off the Boiler
1. Set the thermostat to the lowest setting, and then turn off all power to the boiler.
2. Turn the gas shutoff valve to the off position.
The initial lighting of the boiler must be performed by a licensed Gas Technician.
Failure to follow instructions may result in property damage, serious injury or death.
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8
hours,first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.Failure to follow these instructions can result in explosion,
serious injury or death.
The flame probe is located in the burner plate; it has a single white/semi-transparent wire
connected to it. DO NOT remove the orange spark cable from the ignition electrode (also
If the unit fails to light consistently and smoothly, contact NTI for technical assistance at
1-800-688-2575. Never allow the boiler to operate if the ignition or operation of the
Page 31
31
Gas
Line Pressure (inches w.c.)
Offset Pressure
(inches w.c. / [Pa])
4
CO2 (%)
1,2,3
Max. CO
(ppm)
Nominal/
Desired
Min.
Max.
Min.
Max.
Natural
7 4 10.5
-0.01 to 0 / [-3 to -1]
8.7
9.5
175
Propane
11 8 13
-0.04 to -0.03 / [-10 to -8]
10
10.8
175
Notes:
1
Combustion calibration must only be performed with the burner operating at maximum modulation rate.
2
Combustion values listed are for burner operation at maximum modulation rate; CO2 and CO values will be lower at
minimum modulation rate.
3
When tested at minimum modulation rate, the CO2 must be 0.5-1.0% lower than CO2 at maximum modulation rate.
4
The Offset Pressure for models FTG 2000-2400 converted to Propane, must be checked, and if necessary adjusted, in
accordance with the procedure detailed in Figure 9-2.
FTG │Installation & Operation Manual
9.0 GAS VALVE AND BURNER SET-UP
Set-up of the FTG gas valve must be performed by a licensed Gas Technician. Failure to
perform the set-up correctly may result in incorrect operation, component failure,
Gas Line Pressure
The boiler gas valve is equipped with a line pressure test port; see Figure 9-1. Use the following procedure to
measure the gas line pressure to the boiler to ensure if falls within the range given in Table 9-1:
1. Turn the supply of gas to the boiler off.
2. For models FTG 600-1400, use a 3/16 in. hex wrench to remove the plug from the inlet flange of the gas
valve, and install a 1/8 NPT x hose barb adapter suitable for connecting the tubing of the gas pressure
manometer being used to measure gas line pressure. Models FTG 2000-2400 encorporate a bleed screw on
the inlet flange of the gas valve, open it approximately 1-1/2 turns. See Line Pressure Test Port in Figures
9-1(a) and 9-1(b).
3. Slide the gas pressure manometer tubing over the hosebard adapter located on the inlet flange of the gas
valve (bleed screw fitting for models FTG 2000-2400); connect the other end of the tubing to the gas
pressure manometer. Ensure both ends of the tubing make a tight connection.
4. Open the supply of gas to the boiler and check for gas leaks.
5. Observe the line pressure under static conditions and compare it to Table 9-1. The pressure will be greatest
under static conditions.
6. With all other gas appliances in the application running, operate the burner to the maximum firing rate (see
Table 9-2) and compare the observed line pressure with Table 9-1. The pressure will be lowest during the
maximum flow of gas.
7. Adjust the gas line pressure to ensure the parameters in Table 9-1 are attained under all conditions (see
NOTICE below). If possible, adjust the line pressure to the "Nominal/Desired" value listed in Table 9-1,
while the unit is operating at the maximum modulation rate, see Table 9-2.
8. Continue observing the gas line pressure until the completion of the combustion analyses, in case
adjustments need to be made.
9. Upon completion of the line pressure testing, turn the gas supply off, and then reinstall the Line Pressure
Test Port plug, applying appropriate thread sealant to the threads prior to installing. For models FTG 20002400, close the bleed screw. Turn gas on and check for leaks.
Table 9-1 Line Pressure and Combustion Parameters
property damage, serious injury or death.
The line pressure is a function of the gas supply and is affected solely by field provided
parameters such as line size and regulator settings. Under no circumstances can the boiler
gas valve influence or be used to adjust the gas line pressure.
Failure to properly re-install the Line Pressure Test Port plug (FTG 600-1400), or close
the Line Pressure Test Port bleed screw (FTG 2000-2400) will cause severe leakage of
gas, resulting in a fire or explosion causing property damage, serious injury or death.
Page 32
32
Model
Min. Modulation
Rate (RPM)
Max. Modulation
Rate (RPM)
Model
Min. Modulation
Rate (RPM)
Max. Modulation
Rate (RPM)
FTG 600
1150
5600
FTG 2000
1050
7100
FTG 800
1150
7450
FTG 2200
1050
7200
FTG 1200
1050
8100
FTG 2400
1050
8000
FTG 1400
1050
7800
Throttle/Input Adjustment Screw
Increase gas
Turn Counter Clockwise
Decrease gas
Turn Clockwise
Installation & Operation Manual│FTG
Table 9-2 Minimum and Maximum Modulation Rates
Carbon Monoxide - Never leave the unit operating while producing Carbon Monoxide
(CO) concentrations in excess of 175ppm. Failure to follow this warning may result in
serious injury or death.
Manifold Pressure – DO NOT adjust or measure the Manifold Pressure of boiler models
FTG 600-1400; the correct manifold pressure is factory set. Field adjustment could
result in improper burner operation resulting in fire, explosion, property damage or death.
Adjustments to the Throttle/Input Adjustment Screw may only be made by a qualified
gas technician, while using a calibrated combustion analyzer capable of measuring CO2
and CO. Adjustments may only be performed if the gas line pressure is maintained above
minimum levels throughout the duration of the test, see Table 9-1. Failure to follow these
instructions may result in serious injury or death.
Flue Gas Analysis and Adjustment
Throttle / Input Screw Adjustments – The boiler is equipped with a Throttle/Input Adjustment Screw, located
at the Gas Valve; see Figures 9-1(a) & 9-1(b); it is used to adjust the flow of gas leaving the Gas Valve
entering the Venturi and then the combustion air stream. Turn the Throttle Screw in (clockwise) to reduce
the flow of gas, make combustion leaner, and reduce the concentration of CO2 in the flue gases. Turn the
Throttle screw out (counterclockwise) to increase the concentration of CO2 and flow of gas in the combustion
air stream. Typical adjustment required is 0-1/8 of a turn in or out from the factory setting. See Figure 9-1
for Throttle screw location and Table 9-1 for appropriate CO2 levels.
Combustion Calibration - To calibrate burner operation, perform the following procedure using a calibrated
combustion analyzer capable of measuring CO2 and CO from Natural and Propane Gas burning boilers:
1. Operate the unit at the maximum modulation rate, see Table 9-2.
2. Ensure the gas line pressure is maintained within tolerance, see Table 9-1.
3. While at the maximum modulation rate, measure the CO2 and CO; adjust as necessary, using the Throttle
Screw, to be within the limits listed in Table 9-1.
4. Operate the unit at the minimum modulation rate (see Table 9-2). Ensure the combustion remains
smooth and CO2 and CO values are lower than the values obtained during maximum modulation, as per
notes in Table 9-1. If not, do not adjust further, contact NTI for assistance.
5. For FTG 2000-2400 models converted to LP, perform the Gas Valve Offset Check/Adjustment procedure
detailed in Figure 9-2.
Each FTG boiler is factory set to operate with Natural Gas, for boilers field converted to operate with Propane
Gas, a flue gas analysis and adjustment is mandatory. See Natural to LP Conversion Instructions included with
the boiler.
Failure to perform the flue gas analysis and adjustment detailed in this section may result
in erratic and unreliable burner operation, leading to reduced efficiency, increased fuel
consumption, reduced component life, heat exchanger combustion deposits, and general unsafe operation.
Failure to follow these instructions may result in serious injury or death.
Analysis – Perform flue gas analysis, and adjust throttle/input screw as required until CO2 and CO levels are
(Refer to Offset
Adjustment Procedure –
Figure 9-2)
Gas Valve
Offset Adjustment Screw
(Refer to Offset Adjustment
Procedure – Figure 9-2)
Throttle Adjustment Screw
Line Pressure Test Port
(located on gas valve inlet
flange)
Venturi
Combustion Blower
Air Filter
Low Gas Pres. Switch
(auto-reset)
High Gas Pres. Switch
(manual reset)
Front-Top Cover (must be removed
to access Gas Valve components)
Installation & Operation Manual│FTG
Page 35
35
Figure 9-2 Gas Valve Offset Check/Adjustment (FTG 2000-2400)
The Gas Valve Offset Pressure is factory set for Natural Gas; only applications
operating with Propane need to have the Gas Valve Offset Pressure field adjusted.
Improperly adjusted Gas Valve Offset Pressure will result in unpredictable burner
operating characteristics, which may lead to burner malfunction causing property
damage, serious injury or death.
Offset Adjustment Screw – used
to set offset and combustion at min.
modulation rate; see Figure 9-1(b)
Differential Pressure
Manometer – min. graduation
of 0.01 in. w.c (1 Pa)
Offset Adjustment Procedure:
1) Differential Pressure Manometer –
obtain a meter capable of measuring
differential pressure (“+” and “-“ ports)
with a minimum graduation of 0.01
inches w.c. (or 1 Pa).
2) Installation – with the burner off,
remove the caps from the pressure
tappings. Connect the Feedback
Pressure Tapping to the Positive (+) port
of the manometer; connect the Manifold
Pressure Tapping to the Negative (-)
port of the manometer. Verify that the
manometer is reading zero – zero the
meter if necessary.
3) Calibrate Combustion – operate burner
to maximum modulation rate (seeTable
9-2), ensuring gas line pressure is
maintained above 4 inches w.c.; set
combustion according to Table 9-1 using
the Throttle Screw – record CO2 value.
4) Set Offset – operate burner to minimum
modulation rate (see Table 9-2); set
offset pressure according to Table 9-1
using the Offset Adjustment Screw.
NOTICE: Since the Manifold Pressure
Tapping is connected to the Negative (-)
port of the manometer, a negative Offset
Pressure will read positive; e.g., to
achieve an offset pressure of -0.03,
manometer will read +0.03.
5) Verify Combustion – with the burner
remaining in operation at the minimum
modulation rate, measure combustion
and compare to readings obtained
during maximum modulation – CO2 must
be 0.5 to 1.0% lower at minimum
modulation. If readings are out of
tolerance – CONTACT NTI FOR
ASSISTANCE.
6) Complete Test – shutdown the burner,
remove the manometer tubing and
reinstall the factory caps on Offset
Pressure Tappings.
Positive (+)
Negative (-)
Feedback
Pressure
Manifold
Pressure
Throttle Adjustment Screw –
used to calibrate combustion at max.
modulation rate; see Figure 9-1(b)
FTG │Installation & Operation Manual
Page 36
36
Table 10-1 Boiler System Cleansers and Corrosion Inhibitors
Application
Fernox Product
NTI Part #
Description
Boiler Water Treatment
F1 Protector
83448
Corrosion inhibitor.
Cleanser for new and old systems
F3 Cleaner
83449
Removes flux, grease and carbon residue.
Cleanser for Retrofits
DS-40 System Cleaner
83450
Removes heavy lime scale and sludge deposits.
PH – between 6.6 and 8.5.
Iron – less than 0.5mg/l.
Chloride – less than 125mg/l.
Copper – less than 0.1mg/l.
Conductivity – less than 400µS/cm (at 25ºC); [TDS < 200ppm or Total Hardness < 11.6grains/USgal.]
Installation & Operation Manual│FTG
10.0 BOILER AND HEATING SYSTEM PIPING
The fire tube design of the FTG heat exchanger results in minimal head loss, however it must be considered
when sizing system piping and circulators. Furthermore, the low mass of the FTG heat exchanger requires a
minimum flow rate anytime the burner is operating. To maintain the efficient and reliable operation of the heat
exchanger, and to avoid heat exchanger failure, it is critical to ensure the rules and guidelines in this section are
followed.
Failure to follow the instructions provided in this section will void the NTI warranty and
may result in property damage, fire, serious injury or death.
Boiler System Preparation
Prior to connecting plumbing to the boiler, flush the entire system to ensure it is free of sediment, flux, solder,
scale, debris or other impurities that may be harmful to the system and boiler. During the assembly of the
heating system, it is important to keep the inside of the piping free of any debris including construction and
copper dust, sand and dirt.
For retrofits, all system piping, including radiators, must be cleansed of build-up including sludge and scale. All
systems, old and new, must be cleansed to remove flux, grease and carbon residue; NTI recommends cleaning
the boiler system with “Fernox F3 Cleaner”. For retrofit applications with heavy lime scale and sludge deposits,
a heavier duty cleaner may be required; NTI recommends the use of “Fernox DS-40 System Cleaner”. For
information on performing the cleaning, follow the instructions included with the applicable Fernox Cleaner.
See Table 10-1 for a list of recommended boiler system cleaning and treatment products.
Failure to rid the heating system of the contaminants listed above will void your NTI
warranty and may result in premature heat exchanger failure and property damage.
Boiler Water
Pressure - FTG boilers are intended solely for use in pressurized closed-loop heating systems operating with a
minimum pressure of 12 PSI at the boiler outlet. To obtain the minimum system design pressure, follow the
piping diagrams illustrated in this section.
Oxygen Elimination - This boiler may only be installed in a pressurized closed-loop heating system, free of air
and other impurities. To avoid the presence of oxygen, ensure all of the air is removed from the system
during commissioning via strategically placed, adequately sized air-removal devices; located throughout the
heating system. See figures in this section detailing the location of the primary air-removal device required
for the boiler. Immediately repair any leaks in the system plumbing to avoid the addition of make-up water;
make-up water provides a source of oxygen and minerals that may lead to heat exchanger failure. Failure to
follow these instructions will result in poor performance, unnecessary wear of system components and
premature failure.
The FTG is not approved for operation in an “open system”, thus it cannot be used for
direct potable water heating or process heating of any kind.
Water Chemistry – The installer of the FTG boiler must consider the condition of the water in the heating
system. Ensure the condition of the boiler water falls within the following parameters:
Page 37
37
FTG │Installation & Operation Manual
Treatment - Boiler water that falls outside of the conditions listed above must be treated with a corrosion
inhibitor. For information on performing the treatment, follow the instructions included with the corrosion
inhibitor. See Table 10-1 for a list of recommended boiler system cleaners and corrosion inhibitors.
To maintain protection, the level of corrosion inhibitor must be monitored periodically
for the correct concentration.
Anti-freeze - For systems requiring freeze protection, use only inhibited propylene glycol, specially formulated
for hydronic heating systems; use of other types of antifreeze may be harmful to the system and will void the
warranty. Note: the use of glycol may reduce the usable output capacity of the boiler, thus requiring the unit
to be “down-fired” by limiting the maximum operating capacity and/or the maximum water temperature.
DO NOT use inhibited glycol with non-compatible boiler inhibitors. Non-compatible
inhibitors may counteract each other rendering them ineffective.
Near Boiler Piping
Pressure Relief Valve – A Pressure Relief Valve is factory supplied with each unit, and must be field installed
in the vertical position, with the outlet facing horizontally and piped towards the floor away from where it
could be harmful; see Figure 10-1. NOTICE: FTG boilers have a maximum allowable operating pressure of
160 PSI.
If installed in the incorrect orientation (horizontally with outlet pointing down) the relief
valve may not function properly resulting in property damage or personal injury.
Ensure the discharge of the pressure relief is piped to a location where exiting steam or
hot water will not cause property damage or serious injury.
Pressure & Temperature Gauge – FTG units come with a factory supplied Pressure & Temperature Gauge.
The gauge must be installed in the boiler outlet fitting, as illustrated in Figure 10-1.
Auto Air Vent – An automatic air vent is factory installed on the boiler; see Figure 10-1. Open the auto air
vent’s vent-cap to promote the removal of air during commissioning of the boiler and to avoid
malfunctioning of the LWCO. Once the air is removed from the system, close the vent-cap to prevent water
from leaking onto the boiler.
Low Water Cutoff (LWCO) – FTG boilers are provided with a factory installed LWCO switch which
incorporates a Test Button and Power and Low Water indicator lights. Perform the following Operational
Test Procedure before placing the boiler in service, and ensure Maintenance is carried out with the following
schedule.
Do not run the boiler unattended until the following procedure is completed. Failure to
follow procedure may lead to unsafe boiler operation resulting in fire, property damage
and loss of life.
Operational Test Procedure (LWCO)
1.Before introducing water to the boiler, turn the power on; both the green “POWER” LED and amber “LOW
WATER” LED should illuminate. Generate a burner demand; the burner should not fire and “Lockout 67
ILK OFF” should appear on the screen. Contact NTI for assistance if this does not happen.
2. Fill the boiler with water; the “LOW WATER” LED should turn off. Press the TEST / RESET button on the
LWCO and clear the Lockout from the display board – burner should now fire.
3. With the burner firing, press the TEST / RESET button to simulate a low water condition; the amber “LOW
WATER” LED should illuminate and the burner should turn off.
Maintenance (LWCO)
Every Year – perform Step 3 from the Operational Test Procedure.
Every 5-years – Remove the LWCO and clean all surfaces in contact with water.
Page 38
38
Figure 10-1 Near Boiler Piping
ATTENTION: Boiler piping can be adapted to ANSI pipe thread, flange, or other style piping
connection, immediately upon exiting the boiler. With the exception of the boiler inlet and outlet fittings,
Grooved Joint style piping connections are NOT required.
Low Water Cutoff
(factory installed)
Pressure Relief Valve
(factory supplied)
Pressure/Temperature Gauge
(factory supplied)
Groove Joint Coupling
(factory supplied)
3 in. Groove Joint Coupling
(factory supplied)
Isolation Valve
(Typical)
Y-Strainer
(recommended)
Boiler Drain / Backflush Valve (typical)
Relief Valve Outlet –
Directed Downward (typical)
To System
From System
Isolation Valve
(Typical)
Boiler Drain / Backflush Valve (typical)
Auto Air Vent
(factory supplied)
Installation & Operation Manual│FTG
Page 39
39
Table 10-2 Minimum Flow Rate Requirements
Model
Flow (US gpm)
Model
Flow (US gpm)
FTG 600
19
FTG 2000
63
FTG 800
25
FTG 2200
69
FTG 1200
38
FTG 2400
74
FTG 1400
44
Model
Temp.
Rise (ºF)
Boiler Flow
Rate (GPM)
Boiler Head
Loss (ft.)
Minimum
Pipe Size
Model
Temp.
Rise (ºF)
Boiler Flow
Rate (GPM)
Boiler Head
Loss (ft.)
Minimum
Pipe Size
FTG
600
20
56
6.7
2-1/2 in.
FTG
2000
20
192
11.2
4 in.
25
45
4.2
2 in. 25
154
7.2
3 in.
35
32
2.1
2 in. 35
110
4
3 in.
FTG
800
20
74
12
2-1/2 in.
FTG
2200
20
210
13.2
4 in.
25
59
7.6
2-1/2 in.
25
168
8.3
4 in.
35
42
3.8
2 in. 35
120
4.5
3 in.
FTG
1200
20
115
7.8
3 in.
FTG
2400
20
224
15
4 in.
25
92
5.4
2-1/2 in.
25
179
9.7
4 in.
35
66
3.5
2-1/2 in.
35
128
5
3 in.
FTG
1400
20
134
10
3 in.
25
108
6.9
3 in.
35
77
4.5
2-1/2 in.
FTG │Installation & Operation Manual
Boiler System Plumbing
FTG boilers use a low mass heat exchanger that requires a minimum rate of forced water circulation any time the
burner is operating (See Table 10-2 for minimum flow rate requirements). To ensure the minimum flow rate is
attained, carefully follow the plumbing instructions in this section.
Failure to ensure the minimum water flow rate through the boiler when the burner is
operating will result in “short-cycling”, reduced performance and operating efficiency,
and may also cause overheating and premature failure which will void the warranty.
Failure to follow instructions may result in fire, property damage, serious injury or death.
Circulating Pumps – FTG boilers are equipped with three sets of pump contacts:
1. DHW PUMP - operates during a Domestic Hot Water demand (DHW).
2. CH PUMP - operates during a Central Heat demand (CH).
3. BOILER PUMP - operates during any demand.
Ensure circulating pumps are oriented as per the manufacturers’ instructions. Wiring of these circulators will
depend on the system configuration selected; see Figures 10-3 and 10-4. For wiring details see Section 12.0.
Circulators responsible for forcing water flow through the boiler must be sized to
account for the head loss of the boiler and boiler piping at the required flow rate; see
Table 10-3 and Figure 10-2.
Table 10-3 Boiler Piping Size Requirements
Page 40
40
Figure 10-2(a) FTG 600-800 Head Loss Curve
Figure 10-2(b) FTG 1200-1400 Head Loss Curve
Figure 10-2(c) FTG 2000-2400 Head Loss Curve
Installation & Operation Manual│FTG
Page 41
FTG │Installation & Operation Manual
41
Air Removal – The boiler and system plumbing layout must be configured to promote the removal of air from
the water. Air vents and bleeders must be strategically placed throughout the system to aid in purging the air
from the system during commissioning of the boiler. The system must also employ the use of a strategically
located air removal device, such as an air-scoop or micro-bubbler, designed to remove the air from the water
as it flows through the system.
Follow the installation instructions included with the air removal device when placing it
in the system; air removal devices generally work better when placed higher in the
system. Always locate air removal devices in areas of the system that have a guaranteed
positive pressure, e.g., in close proximity to the water fill and expansion tank.
Expansion Tank – The expansion tank must be sized in accordance with the water volume of the system as well
as the firing rate of the appliance. It is important to locate the expansion tank, and make-up water fill, on the
inlet side of any circulator in the system, as doing so will guarantee the lowest pressure in the system will be
at least equal to the tank and make-up water pressure. See examples in Figures 10-3 and 10-4.
Ensure the expansion tank cannot become isolated from the boiler anytime the system is
operating. The installation of flow checks, motorized valves or other shutoff devices
(other than for the purpose of servicing) are not permitted between the outlet of the boiler
and the expansion tank; see Figures 10-3 and 10-4. Failure to follow these instructions
may result in discharge of the Pressure Relief Valve resulting in property damage or
personal injury.
Indirect Water Heater (IWH) – When installed as per Figure 10-4, the indirect water heater is in series with the
boiler during a demand for DHW. Therefore, its head loss, along with the head loss of the boiler and
associated piping, must be considered when sizing the circulator.
Figures 10-3 and 10-4 illustrate typical piping systems. These piping schematics do not
illustrate all of the required concepts and components required to have a proper
installation. Concepts not shown include: prevention of thermal-siphoning (heat traps),
isolation valves, drain and purge valves, etc. It is the responsibility of the installing
contractor and system designer to determine which system best meets the need of the
installation and to consider all aspects of a proper system design. Contractor
modifications to these instructions may be required, based upon existing piping and
system design; consult NTI for required assistance (1-800-688-2575).
Page 42
42
Figure 10-3 Plumbing Schematic – Single Central Heating Circulator
Figure illustrates the basic plumbing requirements for an FTG boiler installation with a
single Central Heating circulator, and an Indirect Water Heater. Refer to Figure 10-1
for boiler fitting identification.
Installation & Operation Manual│FTG
Page 43
43
Figure 10-4 Plumbing Schematic – Multiple Central Heating Circulators
Figure illustrates the basic plumbing requirements for an FTG boiler installation with a
multiple Central Heating circulators, and an Indirect Water Heater. Refer to Figure 101 for boiler fitting identification.
FTG │Installation & Operation Manual
Page 44
44
# of
Units
Model
FTG 600
FTG 800
FTG 1200
FTG 1400
FTG 2000
FTG 2200
FTG 2400
2
3 in.
4 in.
4 in.
4 in.
5 in.
5 in.
5 in.
3
4 in.
4 in.
5 in.
5 in.
6 in.
6 in.
6 in.
4
4 in.
4 in.
5 in.
5 in.
6 in.
6 in.
8 in.
5
4 in.
5 in.
6 in.
6 in.
8 in.
8 in.
8 in.
6
5 in.
5 in.
6 in.
6 in.
8 in.
8 in.
8 in.
7
5 in.
5 in.
6 in.
8 in.
8 in.
8 in.
8 in.
8
5 in.
6 in.
8 in.
8 in.
8 in.
8 in.
8 in.
Note: Minimum pipe size based on assumed temperature rise of 25ºF at maximum firing rate.
Installation & Operation Manual│FTG
11.0 LEAD LAG INSTRUCTIONS
Multiple Boiler Applications
The FTG controller has the internal capacity to stage or Lead-Lag up to 8 boilers configured in a cascade. This
Lead-Lag capability allows a designated “Master” boiler to communicate with and effectively control each
boiler in a multiple boiler system. This function is accomplished by “Daisy Chaining” a 3-wire cable between
each of the boilers and enabling the Master parameter in the boiler of your choice. The boiler with the Master
parameter enabled becomes the single point of contact for Central Heating, Domestic Hot Water and Outdoor
Reset settings and control wiring. Use the instructions detailed in this section to set-up and install the cascade
boiler system; reference Appendix A – Controller and Touchscreen Display Instructions for details on more
advanced settings and for assistance with navigating the touchscreen display.
Lead Lag Instructions - Common
Plumbing – install as many as 8 FTG boilers in parallel in a primary/secondary plumbing configuration as
illustrated in Figure 11-1. Size common piping as per Table 11-1.
Boiler Pump – each boiler must have its own circulator (see Figure 11-1) which is controlled by its BOILER
PUMP output; see Field Wiring Figure 12-2 and Table 12-1. The Boiler Pump must be sized according to
Table 10-3.
Communication Wiring – using 3-wire cable, daisy-chain terminals LL DATA +, LL DATA – and COMMUN.
COM of each boiler in parallel; see Field Wiring Table 12-2 and Figure 12-3.
System Sensor (Optional) – install a system sensor (NTI P/N: 84010) on the outlet (supply) pipe feeding the
heating system, see Figure 11-1. Wire the system sensor to the SYSTEM SENSOR terminals of the Master
Boiler; see Field Wiring Table 12-2 and Figure 12-3. The system sensor automatically becomes the
modulation sensor for the boiler system, i.e. the control attempts to achieve setpoint temperature at the
location of the sensor. If a system sensor is NOT used, at the Master boiler set the applicable sensor input to
Unconfigured as follows:
Outdoor Sensor (Optional) – wire the outdoor sensor to the OUTDOOR SENSOR terminals of any one of the
boilers in the cascade; see Field Wiring Table 12-2 and Figure 12-3. Note: only one outdoor sensor is needed
for the multiple boiler system.
Modbus Address – assign a unique MB2 Modbus Address to each boiler in the cascade. Access the MB2
Modbus Address setting via the System Identification & Access menu as follows:
Configure – System Identification & Access – MB2 Modbus Address
Master Enable – choose one (and only one) boiler in the cascade to be the Master, this boiler will receive all
control wiring and will be used for setting control parameters (see steps below). On this one boiler, set
Master enable equal to Enabled via the Lead Lag Master Configuration menu, accessed as follows:
Configure – Lead Lag Master Configuration – Master enable
Table 11-1 Minimum Pipe Sizes for Multiple Boiler Applications
Figure illustrates the basic plumbing requirements for multiple FTG boilers installed in
cascade configuration. Refer to Figure 10-1 for boiler fitting identification.
FTG │Installation & Operation Manual
Page 46
46
Installation & Operation Manual│FTG
Lead Lag Instructions – Central Heating
Central Heat Demand Switch (Room Thermostat) – connect to R (24VAC) and CH2 (LL) of the Master
Boiler; see Field Wiring Table 12-2 and Figure 12-3. Switch must be an isolated end switch (dry contact).
Central Heat Setpoint – at the Master boiler only, set the CH setpoint via the Lead Lag Master Configuration
menu, accessed as follows:
Configure – Lead Lag Master Configuration – CH setpoint
Outdoor Reset Settings – at the Master boiler only, set the Outdoor reset parameters via the Lead Lag Master
Configuration menu, accessed as follows:
Configure – Lead Lag Master Configuration – Advanced Settings – Outdoor reset
CH Pump – one boiler in the cascade can be chosen to operate the Central Heating pump via its CH PUMP
output; see Field Wiring Figure 12-2 and Table 12-1. From the respective boiler display, check the box next
to Use for Lead Lag Master demands for the CH Pump to ensure proper pump behavior. Menu access to the
CH Pump parameters is as follows:
Configure – Pump Configuration – Central Heat pump – Use for Lead Lag Master demands
Lead Lag Instructions – Domestic Hot Water
Tank Thermostat – connect to terminals DHW of the Master Boiler; see Field Wiring Table 12-2 and Figure
12-3. Switch must be an isolated end switch (dry contact).
DHW Setpoint – at the Master boiler only, set the DHW setpoint via the Lead Lag Master Configuration menu,
accessed as follows:
Configure – Lead Lag Master Configuration – DHW setpoint
DHW switch (Lead Lag) – at the Master boiler only, set DHW switch equal to DHW (S6) sensor shorted via the
Lead Lag Master Configuration menu, accessed as follows:
Configure – Lead Lag Master Configuration – Advanced Settings – Domestic Hot Water – DHW switch
DHW enable (Local) – at the Master boiler only, set DHW enable equal to Disabled via the Domestic Hot
Water Configuration menu, accessed as follows:
Configure – Domestic Hot Water Configuration – DHW enable
DHW Pump – one boiler in the cascade can be chosen to operate the DHW pump via its DHW PUMP output;
see Field Wiring Table 12-1 and Figure 12-2. From the respective boiler display, check the box next to Use for Lead Lag Master demands for the DHW Pump to ensure proper pump behavior. Menu access to the
DHW Pump parameters is as follows:
Configure – Pump Configuration – DHW pump – Use for Lead Lag Master demands
Tank Sensor – when operating in a cascade system, the boiler controls do not support the
use of a tank sensor; a tank thermostat (switch) must be used.
Page 47
47
FTG │Installation & Operation Manual
12.0 FIELD WIRING
All wiring must be in accordance with the Canadian Electrical code, CSA C22.2 and any applicable local codes.
Ensure that the wiring complies with this manual. The boiler must be electrically grounded in accordance with
the National Electrical Code ANSI/NFPA 70, local codes, and/or the Canadian Electrical Code CSA C22.1.
Power Supply – The required power supply varies between boiler models; connect a power supply matching the
description provided below for the respective boiler model:
FTG 600-1400 – 120V / 1Ph / 60Hz, fused (or protected via a circuit breaker) to a maximum of 15 Amps.
FTG 2000 – 120V / 1Ph / 60Hz, fused (or protected via a circuit breaker) to a maximum of 20 Amps.
FTG 2200 – 208V / 3Ph / 60Hz, fused (or protected via a circuit breaker) to a minimum of 15 Amps.
FTG 2400 – 240V / 3Ph / 60Hz, fused (or protected via a circuit breaker) to a minimum of 15 Amps.
Failure to connect the correct power supply, fused as specified, may result in component
failure, serious injury or death.
Avoid Shocks - To Avoid Electrical Shock, turn off electrical power to the boiler prior to
opening any electrical box within the unit. Ensure the power remains off while any
wiring connections are being made. Failure to follow these instructions may result in
component failure, serious injury or death.
Wire Protection - When passing any wiring through the cabinet of the boiler, the
installer must use wire grommets, or strain reliefs, suitable for securing the wiring and
preventing chafing. Failure to follow instructions may result in component failure,
Line Voltage Connections
Line voltage field wiring enters the back of the boiler through strain reliefs (field supplied), then routes
internally via a chase-way on the right-hand side of the boiler, to the line voltage junction box located at the
front of the boiler on the right-hand side. Remove the Front and Top-Front panels to access the junction box and
chase-way; see Figure 12-1. Secure field wiring to the chase-way using the factory supplied wire supports.
Terminate line voltage field wiring in accordance with instructions provided in Figure 12-2 and Table 12-1.
FTG 2200-2400 – the 3-phase power supply connects at a factory installed disconnect switch at the back of the
boiler; see Figure 12-1. From the disconnect, the 3-phase wiring is factory routed internally to a Fuse Block
where it is distributed to the combustion blower and 120V transformer; see Figure 12-2. NOTICE: 120V is
factory wired to the Line Voltage Junction Box.
Pump Relays – The FTG incorporates three non-powered isolation relay contacts for switching high capacity
pumps. Contact Secondary Maximum rating is 1.5HP @ 120V, 3.0HP @ 240V, or 30A. Refer to Figure 12-2
for Field Wiring requirements.
Low Voltage Connections
Low voltage field wiring enters the back of the boiler through grommets (factory supplied), then routes
internally, via a chase-way on the left-hand side of the boiler, to the low voltage junction box located at the front
of the boiler on the left-hand side. Remove the Front and Top-Front panels to access the junction box and chaseway; see Figure 12-1. Secure field wiring to the chase-way using the factory supplied wire supports. Terminate
low voltage field wiring in accordance with instructions provided in Figure 12-3 and Table 12-2.
serious injury or death.
Labeling - Label all wires prior to disconnecting them when servicing controls. Wiring
errors can cause improper and dangerous operation. Failure to follow instructions may
result in property damage or personal injury.
Continuity - Before connecting the line voltage wiring, perform a continuity check
between all wires and ground to make sure that there are no electrical leaks that could
blow a fuse or damage electrical components.
Page 48
48
Figure 12-1 Wiring Terminal Access
Field wiring enters the back of the boiler through
strain reliefs/grommets, then is routed internally
via chase-ways to the junction boxes located at
the front of the boiler. Secure internal field wiring
to the chase-way using the factory supplied wire
supports. Field wiring entering the junction boxes
must pass through the factory supplied grommets.
Line Voltage Wiring
Strain Reliefs
(field supplied)
Low Voltage
Wiring Grommets
(factory supplied)
Access Cover – for
securing stain reliefs
Power Disconnect Switch
(FTG 2200/2400 illustrated)
- For FTG 2200/2400, remove cover and
connect 4-wire 3Ph power supply to switch,
as per Figure 12-2
- For FTG 600-2000, route 120V power supply
through strain reliefs, and terminate at the
line voltage Junction Box, as per Figure 12-2
Ethernet Connection
(optional kit required)
Condensate
Pump Receptacle
Field Wiring Chase-
way to Junction Box
(line voltage)
Junction Box Cover
(line voltage)
Junction Box
(line voltage)
Junction Box
(low voltage)
Junction Box Cover
(low voltage)
Field Wiring Chase-
way to Junction Box
(low voltage)
Control Panel
Installation & Operation Manual│FTG
Page 49
49
Figure 12-2 Line Voltage Field Wiring
Connection
Location
Description
L1 (120VAC)
1
Location for connecting line wire of 120V power supply.
NOTICE: 120V
power supply is factory
wired for models FTG
2200 & 2400.
L2 (Neutral)
2
Location for connecting neutral wire of 120V power supply.
GROUND
3
Location for connecting earth ground.
Non-Powered
(Dry Contacts)
DHW PUMP
(PUMP A)
4
DHW Pump Relay – Normally Open Dry Contact for DHW circulator; contact closes
during a demand for DHW. Maximum rating is 1.5HP @ 120V, 3.0HP @ 240V, or
30A.
5
BOILER
PUMP
(PUMP B)
6
Boiler Pump Relay – Normally Open Dry Contact for Boiler circulator; contact closes
during all demands. Maximum rating is 1.5HP @ 120V, 3.0HP @ 240V, or 30A.
7
CH PUMP
(PUMP C)
8
CH Pump Relay – Normally Open Dry Contact for Central Heating circulator;
contact closes during a demand for CH. Maximum rating is 1.5HP @ 120V, 3.0HP @
240V, or 30A.
9
LINE VOLTAGE
JUNCTION BOX
3PH DISCONNECT SWITCH
(FTG 2200/2400 ONLY)
Located at the back of the
boiler; see Figure 12-1
FTG │Installation & Operation Manual
Page 50
50
Figure 12-3 Low Voltage Field Wiring
Installation & Operation Manual│FTG
Page 51
51
Connection
Location
Description
COM
(24VAC)
1
24VAC Common – Neutral for the 24VAC power supply from the boiler. COM can be used
in conjunction with terminal R to provide a power source for a digital thermostat.
R (24VAC)
2
24VAC Hot - Power supply for inputs EXT. LIMIT, CH1, and CH2 (LL).
3
EXT. LIMIT
4
External Limit – Input requiring 24VAC from R-terminal to permit the burner to operate.
Comes factory equipped with a jumper to the R-terminal. For installations requiring the use of
an additional safety switch, such as a Flow Switch or auxiliary temperature limit, remove the
factory installed jumper and install the normally open isolated contacts of the field supplied
additional limit.
AUX.
PROOF
5
Auxiliary Proof – Comes factory equipped with a jumper. For applications using Indoor
Combustion Air, remove jumper and replace with field supplied end switch incorporated with
motorized damper/louver control.
6
CH1
7
Central Heat Demand (Local)– Input requiring 24VAC from R-terminal to initiate a “local”
CH call. Switch is made using an isolated end switch (dry contact) via thermostat, zone
controller or other device. Typically used as the lone heat input or as the high temperature
input in dual CH temperature systems.
CH2 (LL)
8
Central Heat Demand (Lead-Lag)–Input requiring 24VAC from R-terminal to initiate a
“lead-lag” CH call. Switch is made using an isolated end switch (dry contact) via thermostat,
zone controller or other device. Typically used as a lead-lag input for cascaded boilers or as the
low temperature input in dual CH temperature systems.
ALARM
9
Normally Open Alarm Contacts – Contacts close during a lockout or other alarm condition.
May be connected to a BMS, maximum capacity of 0.63Amps at 24VAC.
10
OUTDOOR
SENSOR
11
Outdoor Temperature Sensor – A wall mountable OD Sensor is included with each boiler.
When connected to terminals 11 and 12, the control will indicate the outdoor temperature and
adjust the boiler temperature set point during a Central Heat demand.
12
DHW
13
DHW Tank Demand – Input requiring closure of terminals 13 and 14 to initiate a demand for
DHW. Switch made via isolated end switch (dry contact) from a thermostat (aquastat) located
in an Indirect Water Heater, or optional Tank Sensor (P/N 84632), see Appendix A.
(NOTICE: tank sensor cannot be used for cascade boiler arrangements).
14
SYSTEM
SENSOR
15
System Water Temperature – An optional strap-on System Sensor is available from NTI
(P/N 84010). When connected to terminals 15 and 16, the control will indicate a “CH” or
“Lead-Lag” temperature, which can be used for direct modulation of system temperature. By
default, the System Sensor becomes the Modulation Sensor for a Lead Lag demand.
16
4-20mA
(– / +)
17
External Modulation Control – Using a 4-20mA signal, an external control can be used to
directly modulate the burner firing rate or adjust the active set point. This can be useful for
applications using external staging controls or BAS.
18
LL DATA+
19
Lead-Lag – Connects internally to the controller’s MB2, Modbus communication port.
Terminals 19, 20 and 23 (COMMUN. COM) can be "daisy-chained" to multiple boilers (up to
8 in total) for the purpose of staging.
LL DATA-
20
BMS D+
21
Building Management System (BMS) – Connects internally to the display’s COM2, Modbus
communication port. Terminals 21, 22 and 23 (COMMUN. COM) can be connected to a
Gateway for communication to a BMS or other device.
BMS D-
22
COMMUN.
COM
23
Communication Common – Common port for LL and BMS Communication wiring, as well
as the TOD input.
TOD
24
Time of Day (Night Time Setback) – Input requiring closure of terminals 24 and 23
(COMMUN. COM) to initiate TOD setback settings. Switch is made using an isolated end
switch (dry contact) using a timer, BAS or other device.
FTG │Installation & Operation Manual
Page 52
52
Figure 13-1 FTG Connection Diagram
Installation & Operation Manual│FTG
13.0 WIRING SCHEMATICS
Page 53
53
Figure 13-2 FTG Ladder-Logic Diagram
FTG │Installation & Operation Manual
Page 54
54
Installation & Operation Manual│FTG
14.0 INSTALLATION CHECKLIST
Installation
1. If operating on Propane Gas, convert boiler using the applicable Natural Gas to LP Conversion
Instructions.
2. Locate the boiler in accordance with Section 3.0 of this manual.
3. Install the Vent/Air-inlet piping in accordance with Sections 4.0 and 5.0 of this manual. Ensure all
joints are secured and cemented properly. Perform the Mandatory Pre-commissioning Procedure for
Plastic Venting in Section 4.0.
4. Connect the condensate trap and drain in accordance with Section 6.0 of this manual.
5. Connect the gas supply in accordance with Section 7.0 of this manual.
6. Install the plumbing in accordance with this manual. Flush/cleanse the internals of the heating system.
Treat system water with Fernox F1 Protector when needed.
7. Connect field wiring in accordance with Section 12.0 of this manual.
8. Advise home/building owner of their responsibilities with respect to maintaining the boiler.
The building owner is responsible for keeping the Vent/Air-inlet termination free of snow,
ice, or other potential blockages and for scheduling boiler routine maintenance as
described in the next section. Failure to properly maintain the boiler may result in serious injury or death.
Start-up
Allow primers/cements to cure for 8 hours prior to Start-up. If curing time is less than 8
hours,first perform Steps 2 through 6 of Mandatory Pre-commissioning Procedure for Plastic Venting in Section 4.0.Failure to follow these instructions can result in explosion,
1. Turn gas shut-off valve to the ON position.
2. Turn Power on to the boiler.
3. Set Controller to the desired settings.
4. Turn thermostat up, Ignition will occur.
Operational Checklist
1. System is free of gas leaks.
2. System is free of water leaks.
3. Water pressure is maintained above 15 PSI.
4. All air is purged from the heating system piping.
5. Ensure proper water flow rate; unit must not kettle, bang, hiss or flash the water to steam.
6. Ensure gas line pressure is in accordance with Section 9.0.
7. System is free of combustion leaks.
8. Unit must operate smoothly.
9. Ensure the flue gas combustion readings are within the tolerances listed in Table 9-1.
10. Each ignition must be smooth.
11. Verify that all condensate lines are clean and drain freely.
Before Leaving
1. Seal the Line Pressure Test Port fitting on the inlet flange of the gas valve;, test for leaks. See Section 9.0.
2. Install flue gas test port plug and test for leaks, see Section 9.0.
3. Allow the boiler to complete at least one heating cycle, or to operate for at least 15 minutes.
4. Always verify proper operation after servicing.
Instructions to Installing Contractor
1. Ensure that the customer receives the Warranty Documentation included with the installation manual.
2. Leave the manual with the customer so they know when to call for annual maintenance and inspection.
serious injury or death.
This boiler must have water flowing through it whenever the burner is firing. Failure to
comply may damage the unit, void the warranty, and cause serious injury or death.
Allowing the boiler to operate with a dirty combustion chamber will adversely affect its
operation and void the warranty. Failure to clean the heat exchanger on a frequency that
matches the need of the application may result in fire, property damage, or death.
Page 55
FTG │Installation & Operation Manual
55
15.0 ANNUAL MAINTENANCE AND INSPECTION
This unit must be inspected at the beginning of every heating season by a Qualified Technician.
Annual Inspection Checklist
1. Lighting is smooth and consistent, and the combustion fan is noise & vibration free.
2. The condensate drain flows freely, and is cleaned of sediment.
3. Pressure Relief Valve and air vents are not weeping.
4. Low water cut off is tested (remove and clean a minimum of once every 5 years, see Section 10.0)
5. Examine all venting for evidence of leaks. Ensure vent screens are cleaned and clear of debris.
6. Check the burner plate for signs of leaking.
7. The combustion chamber must be cleaned (cleaning frequency based on need for application – see below)
8. Keep boiler area clear/free from combustible materials, gasoline, and other flammable vapors and liquids.
9. Ensure there is nothing obstructing the flow of combustion and ventilation air.
10. Listen for water flow noises indicating a drop in boiler water flow rate.
Important - The hydronic system may need to be flushed to eliminate hard water scale
(Use Fernox DS-40 Descaler, NTI PN: 83450).
11. Verify proper operation after servicing.
Wiring Labels - Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation.
Combustion Chamber Cleaning Procedure
The combustion chamber must be cleaned after the first year of operation, with subsequent cleanings scheduled
based on the condition of the combustion chamber at the time of the first cleaning. Units operating with LP Gas
or in an industrial environment may require more frequent cleanings.
Crystalline Silica - Read carefully the warnings and handling instructions pertaining to
Refractory Ceramic Fibers before commencing any service work in the combustion
chamber. Take all necessary precautions and use recommended personal protective
equipment as required.
Cleaning Instructions (contact NTI for a more detailed procedure)
1. Power Down – Remove the demand for heat, allow the post-purge cycle to finish, turn gas and power supply
off. Ensure the combustion chamber has cooled before proceeding.
2. Remove Display Assembly – Working inside the cabinet, disconnect tubing and wiring from the display
assembly, remove the display assembly as a whole, leaving the junction boxes attached to the boiler cabinet.
3. Remove Blower, Venturi & Transfer-tube as an Assembly – Disconnect wiring from the Blower, unbolt
the gas-line and remove tubing from the Venturi, and then disconnect the Transfer-tube for the Burner Door.
Remove the Blower, Venturi and Transfer-tube as an assembly. Be careful not to damage or misplace any of
the gaskets – replace if damaged.
4. Remove Burner from the Burner Door; be careful not to damage the gasket – replace if damaged. Inspect
burner for signs of damage – do not re-use a damaged burner.
5. Remove Burner Door – Disconnect wiring from the ignition and flame sensing electrodes, remove the 12
nuts/bolts securing the door to the heat exchanger. Remove the Burner Door, being careful not to damage the
combination gasket/insulation on the inside of the door – replace if damaged.
6. Remove Rear Combustion Chamber Door (if necessary) – From the rear of the boiler, remove the screws
securing the middle access panel to the back of the boiler cabinet. Remove the 12 nuts/bolts securing the rear
door to the heat exchanger and remove the door; be careful not to damage the combination gasket/insulation
on the inside of the door – replace if damaged.
7. Inspect Combustion Chamber – Assess the level of debris inside combustion chamber and at the entrance
to the flue passageways; future cleanings should be scheduled based on this assessment.
8. Clean Combustion Chamber – Vacuum any loose debris or dust, then use a garden hose with a trigger
nozzle to direct pressurized water through the heat exchanger tubes; the water will exit via the condensate
drain on the back. Continue process until the tubes are clear and the water runs clean. Use dry rags or plastic
to protect electrical components from being damaged by dripping or spraying water.
Page 56
56
Reduce the Risk of Exposure
Precautions and Recommended Personal Protective Equipment
Avoid contact with skin and eyes
Wear long-sleeved clothing, gloves, and safety goggles or glasses.
Avoid breathing in silica dust
Wear a respirator with an N95-rated filter efficiency or better. 1
Use water to reduce airborne dust levels when cleaning the combustion chamber.
Do not dry sweep silica dust. Pre-wet or use a vacuum with a high efficiency filter.
Avoid transferring contamination
When installing or removing RFCs, place the material in a sealable plastic bag.
Remove contaminated clothing after use. Store in sealable container until cleaned.
Wash contaminated clothing separately from other laundry.
First Aid Measures
If irritation persists after implementing first aid measures consult a physician.
Skin - Wash with soap and water.
Eyes - Do not rub eyes; flush with water immediately.
Inhalation – Breathe in fresh air; drink water, sneeze or cough to clear irritated
passage ways.
1
Respirator recommendations based on CCOHS and OSHA requirements at the time this document was written. Consult
your local regulatory authority regarding current requirements for respirators, personal protective equipment, handling,
and disposal of RCFs.
For more information on Refractory Ceramic Fibers, the risks, recommended handling procedures and acceptable disposal
practices contact the organization(s) listed below:
Canada (CCOHS): Telephone directory listing under
Government Blue Pages Canada—Health and Safety—
Canadian Centre for Occupational Health and Safety; or
website http://www.ccohs.ca.
United States (OSHA): Telephone directory listing under
United States Government—Department of Labor—
Occupational Safety and Health Administration; or website
http://www.osha.gov.
Installation & Operation Manual│FTG
9. Condensate Trap – Disassemble the condensate trap and thoroughly clean it; then reassemble and securely
connect it to the boiler condensate drain, see Section 6.0.
10. Reassemble – Assembly is in the reverse order as disassembly. Inspect all gaskets and insulation prior to
assembly – replace if damaged.
11. Perform the Start-up and Operational Checklist – See Section 14.0.
Replace gaskets and insulation that show any signs of damage – DO NOT RE-USE.
Failure to follow these instructions may result in fire, property damage or death.
Refractory Ceramic Fibers (RFC)
Personal Protective Equipment Recommended - Read the following warnings and
handling instructions carefully before commencing any service work in the combustion
chamber. The insulating material on the inside of the burner plate contains Refractory Ceramic Fibers and should not be handled without personal protective equipment.
Potential Carcinogen - Use of Refractory Ceramic Fibers in high temperature
applications (above 1000oC) can result in the formation of Crystalline Silica
(cristobalite), a respirable silica dust. Repeated airborne exposure to crystalline silica dust may result in chronic
lung infections, acute respiratory illness, or death. Crystalline silica is listed as a (potential) occupational
carcinogen by the following regulatory organizations: International Agency for Research on Cancer (IARC),
Canadian Centre for Occupational Health and Safety (CCOHS), Occupational Safety and Health Administration
(OSHA), and National Institute for Occupational Safety and Health (NIOSH). Failure to comply with handling
instructions in Table 15-1 may result in serious injury or death.
maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to
Table 15-1 for handling instruction and recommended personal protective equipment. Installation and service
must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the
supplied instructions before installing, servicing, or removing this boiler. This boiler contains materials that have
been identified as carcinogenic, or possibly carcinogenic, to humans).
Table 15-1 Handling Instructions for Refractory Ceramic Fibers (RCF)
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or
Page 57
57
Applicable
Models
Desciption
Location
Component(s) Fused
FTG 600-2400
Ignition Transformer
(120V, 7A)
Right side of control panel
Ignition Transformer
FTG 600-1400
24V Transformer
(24V, 3A – Circuit Breaker)
24V Transformer (on control
panel)
All 24V Components:
- Control board
- Touchscreen display
- Gas Valve
- Limit switches
- Thermostat circuit
- Pump Relays
FTG 2000-2400
24V Transformer – Secondary
(24V, 10A)
Secondary/left-side of 24V
Transformer (on control
panel)
24V Transformer – Primary
(120V, 5A)
Primary/right-side of 24V
Transformer (on control
panel)
24V Transformer
FTG 2200-2400
120V Transformer – Primary
(208/240V, 10A)
Primary/left-side of 120V
Transformer (behind control
panel)
120V Transformer
120V Transformer –
Secondary
(120V, 10A)
Secondary/right-side of 120V
Transformer (behind control
panel)
All 120V Components:
- 24V Transformer
- Ignition Transformer
- Convenience Outlet
- L1 120V Power Supply to Line
Voltage Junction Box
3Ph Fuse Block
(208/240V, 15A, X 3)
3Ph Fuse Block, left of 120V
Transformer (behind control
panel)
All 208/240V Components:
- Combustion Blower
- 120V Transformer
Note:
1
Refer to Figure 16-1 for locating internal fusing.
FTG │Installation & Operation Manual
16.0 TROUBLESHOOTING
Servicing the Boiler
Disconnect or shutoff all energy sources to the boiler: 120VAC power, water and gas.
Identify and mark wires before disconnecting or removing them.
Never bypass electrical fuses or limit devices except temporarily for testing.
Use proper personal protective equipment (PPE) i.e. eye protection, safety footwear.
These procedures should only be performed by qualified service personnel, when abnormal operation of the
boiler is suspected. The boiler incorporates a sophisticated microprocessor based control which normally
responds appropriately to varying conditions. If the boiler operation appears to be incorrect, or it is not
responding at all to a demand for heat, the following is suggested to determine and correct the problem.
Internal Fusing
The power supply to the FTG boiler must be externally fused (or protected via a circuit breaker) according to its
rating plate. In addition, each FTG integrates internal circuit protection, as defined in Table 16-1.
Table 16-1Internal Circuit Protection – Fusing
Observe the following precautions when servicing the boiler. Failure to comply with
these may result in fire, property damage, serious injury or death.
Before undertaking any troubleshooting procedures it is highly recommended to have
available a digital multimeter (s) capable of measuring AC and DC volts, Amperes,
Resistance (Ohms) and Continuity.
Page 58
58
Figure 16-1 FTG Internal Fusing
SHOCK HAZARD – Failure to turn the power supply off at the source prior to
accessing and testing fuses may result in electrical short causing component failure,
fire and property damage, or electrical shock causing serious injury or death.
Only replace fuses with identical parts, see Figure 16-1. Failure to follow this warning
may result in component failure, fire, property damage, serious injury or death.
Control Panel
Cover
120V Transformer
(FTG 2200-2400 Only)
o 208/240V Primary – 10A Fuse
o 120V Secondary – 10A Fuse
24V Transformer (FTG 600-1400)
o24V Secondary – Circuit Breaker
24V Transformer (FTG 2000-2400)
o 120V Primary – 5A Fuse
o 24V Secondary – 10A Fuse
3Ph Fuse Block (remove
cover to access fuses –
FTG 2200-2400 Only)
o208/240V – 3 x 15A Fuses
Ignition Transformer Fuse
(right-side of control panel)
o 120V – 7A Fuse
Installation & Operation Manual│FTG
Summary and Diagnostics Display – The FTG controller and Touchscreen display provides detailed
operational and diagnostic information for aid in troubleshooting. When power is applied to the appliance the
initial page displayed is the Summary page. Information presented on the Summary page includes Demand
source, Burner state, status of sensors and pumps, and so forth. Any current Alert or Lockout condition is also
displayed. Accessible from the Summary page are the Configuration, Diagnostics, Details and History pages.
Refer to Appendix A - Controller and Touchscreen Display Instructions for more information.
Lockout and Alert History – The controller maintains a record of the fifteen (15) most recent events for both
Lockouts and Alerts. To display the logs, touch the History button on the Summary page (refer to Appendix A - Controller and Touchscreen Display Instructions). In any situation where a malfunction is suspected,
always check the Alerts and Lockouts history. Entries recorded in the history provide useful information for
determining the cause of the malfunction.
Page 59
59
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Burner not operating
Heat demand satisfied; no call for heat
Check Demand and Setpoints via Touchscreen.
Check thermostat and DHW aquastat settings (as
applicable).
Appliance outlet temperature exceeds
“Setpoint - On Hysteresis”
Check outlet temperature, setpoint and hysteresis
settings via Touchscreen.
Hold, Delay or Lockout
Check Summary page on Touchscreen for code.
Burner switch off
Check Summary page, if Demand indicates “Burner
switch off” go to diagnostics burner test page and
switch on.
Lockout 2 – Waiting for safety
data verification
Safety parameter(s) has been adjusted
Changing settings that are considered safety
parameters require “Safety data verification”. Refer
to Appendix A.
Lockout 9 – Flame bias out of
range
4-20mA input being overdriven.
If using 4-20mA input, check to ensure current is
not greater than 21mA.
Control malfunction
Cycle power, if problem returns replace control.
Hold 27 – Flame sensor shorted
to ground detected
A flame circuit shorted to ground may
show up as a flame circuit timeout.
Zero-Ohm shorts can display as Hold
27.
Check to ensure condensate drain is not blocked.
Check to ensure no external voltage is applied to R
& CH terminals. If using 4-20mA input, check to
ensure current is not greater than 21mA.
Hold 61 – Anti short-cycle
Normal operation
Allow timer to expire, or reduce Anti short-cycle
setting as needed (See Appendix A)
Hold 62 – Fan speed not proved
Normal Operation (Drive to Lightoff)
Hold 62 is momentarily displayed prior to burner
ignition during the Drive to Lightoff.
Wiring defect
Inspect blower wiring, ensure connectors at Sola
controller and blower are securely attached.
- Faulty Sola controller
- Faulty Blower
If Hold 62 persists for 15 seconds or more, while
the blower is running, check "Fan speed" indicated
on display. If "LOW RPM", "HIGH RPM", “0” or
rapidly changing RPM value is displayed, try
connecting another Sola controller. If problem
remains, replace blower.
Hold 63 – LCI OFF (Limit
control input)
Incorrect Sola controller.
Replace control with correct model (Replacement
part number 85421)
Hold 65 – Interrupted Air
Switch OFF
Incorrect Sola controller.
Replace control with correct model (Replacement
part number 85421)
Hold 66 – Interrupted air switch
ON
Incorrect Sola controller.
Replace control with correct model (Replacement
part number 85421)
Hold / Lockout 67 – ILK OFF
LWCO Switch
Low Water Cutoff switch has opened – check for
proper water level and pressure; ensure the air is
adequately purged from the boiler system. Reset
the LWCO then clear lockout. If error continues,
clean LWCO probe or replace LWCO.
Bloc’d Condensate Switch
Blocked Condensate Switch has opened –
condensate is not draining from the boiler, or the
exhaust venting is too restrictive or has a blockage.
Check for blockages in the condensate trap and
drain; clean accordingly. If drain is not blocked,
check for blockages/restrictions in the exhaust
venting, then clear the lockout.
FTG │Installation & Operation Manual
Page 60
60
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Bloc’d Filter Switch
Blocked Air Filter Switch has opened – clean or
replace the air filter and clear the lockout.
WARNING: DO NOT OPERATE THE
BOILER WITHOUT THE AIR FILTER,
CONTAMINANTS WILL ENTER THE
BURNER RESULTING IN INPROPER
OPERATION LEADING TO PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
Lo Gas Pres. Switch
Low Gas Pressure Switch has opened – the
incoming gas line pressure has dropped below 3.5
in. w.c., causing the low gas pressure switch
(mounted to the side of the gas valve) to open.
Correct gas line pressure problem then clear the
lockout.
Hi Gas Pres. Switch
High Gas Pressure Switch has opened – the gas
valve manifold pressure exceed 3 in. w.c., causing
the high gas pressure switch (installed down-stream
of the gas valve) to open. CONTACT NTI FOR
ASSISTANCE
Ext. Limit Switch
An External Limit Device (field installed and wired
to the “Ext. Limit” contact of the boiler) has
opened. Not a problem with boiler, check the
external limit device.
Aux. Proof Switch
Auxilary Proof Switch (field installed and wired to
the “Aux. Proof” contact of the boiler) has opened.
Not a problem with the boiler, check the auxiliary
proof switch.
Lockout or Hold 79 – Outlet
High Limit
CH or DHW settings
Check if CH and/or DHW setpoint temperature plus
off hysteresis exceed “High limit” setpoint – factory
setting = 210°F (99°C).
CH or DHW pump problem
See "Inoperative CH or DHW pump" below.
Incorrect “Outlet high limit” setting
Increase “Outlet high limit” setting; maximum
setting = 210°F (99°C).
Lockout or Hold 81 – Delta T
limit
OR
Appliance making banging or
hissing sounds
Insufficient water flow
Check appliance pump.
Ensure plumbing is correct. Refer to Section
10.0 System Piping. Check that water pressure is
at least 15PSI.
Boiler heat transfer surfaces may be fouled with
scale or magnetite. Clean with Fernox DS-40
Descaler and Cleanser. See Table 10-1.
Lockout 82 – Stack limit
Dirty heat exchanger
Inspect and if required clean the combustion
chamber and/or heat exchanger. Refer to Section
15.0 Annual Maintenance and Inspection and
Section 10.0 Boiler and Heating System Piping.
Incorrect “Stack limit setpoint”
Unless installed in Canada with PVC exhaust
venting, set “Stack limit setpoint” to maximum
setting of 220ºF (104ºC). In Canada PVC exhaust
venting is limited to 149ºF (65ºC).
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 16-2.
Lockout or Hold 85 –
Inlet/Outlet Inversion Limit
Pump flowing in the wrong direction
Ensure water circulation through the boiler is in the
correct direction, see Figure 10-1.
Incorrect factory sensor wiring
Disconnect flue sensor cable; screen should display
“Hold 95 –Stack sensor fault”; if not contact NTI.
Installation & Operation Manual│FTG
Page 61
61
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Lockout or Hold 88 – Outlet T
Rise limit
Insufficient water flow
See Lockout or Hold 81.
Hold 91– Inlet sensor fault
Sensor disconnected
Check sensor connection located on the bottom of
the heat exchanger. Check connection on control
board.
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 16-2.
Hold 92 – Outlet sensor fault
Sensor disconnected
Check sensor connection located on the top of the
heat exchanger. Check connection on control
board.
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 16-2. (Note
the Outlet sensor incorporates two sensors, check
resistance individually.)
Hold 95 – Stack sensor fault
Sensor disconnected
Check sensor connection located at the bottom of
the flue pipe inside the boiler cabinet. Check
connection on control board.
Hold 95 – Stack sensor fault
Faulty sensor
Check resistance of sensor and compare to
thermistor resistance chart, see Table 16-2. (Note
the Outlet sensor incorporates two sensors, check
resistance individually.)
Lockout 109 – Ignition failure
occurred
Spark cable disconnected
Ensure that the high voltage spark cable is securely
connected to the spark generator and the igniter
electrode. Check that the green ground wire is
securely attached to the ¼” quick connect tab on the
igniter electrode.
Blocked venting
Check for blockage of the exhaust-vent, air-inlet,
combustion blower, gas valve venturi, burner heat
exchanger etc.
Blocked condensate drain.
Clean condensate trap, inspect condensate drain for
blockages and build-up – correct accordingly.
Insufficient gas line pressure
Ensure the manual gas shutoff valve is open. Refer
to Section 9.0 GAS VALVE AND BURNER
SETUP.
Flame sensor disconnected
Verify that the flame rod signal wire is securely
attached to the flame rod and the Sola controller.
No 120VAC to Spark Generator
Check wiring from Sola controller to spark
generator. With an AC voltmeter measure voltage
across J5-6 and ground (the Sola controller chassis
is connected to the 120VAC supply ground) during
trial for ignition.
Faulty Spark Generator
During trial for ignition check for arc on spark
electrode via the observation port located next to the
spark electrode in the burner door. If the spark
generator is receiving 120VAC and no spark is
observed, replace the spark generator.
No 24VAC to Gas Valve
Check the wiring harness for loose or interrupted
connections of the gas valve wiring. With an AC
voltmeter, measure the voltage between Sola
controller terminals J5-2 to J4-10. There should be
24VAC present during trial for ignition, if not
replace Sola controller.
FTG │Installation & Operation Manual
Page 62
62
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Faulty Gas Valve
The gas valve emits an audible click when it
switches on or off. If the Sola controller is providing
24VAC to the gas valve, and the wiring is intact, it
should be possible to detect if the valve is
responding.
Lockout 113 – Flame circuit
timeout
A flame circuit shorted to ground may
show up as a flame circuit timeout.
High resistance shorts can display as
Lockout 113.
Check to ensure condensate drain is not blocked.
Check to ensure no voltage is applied to R & CH
terminals. If using 4-20mA input, check to ensure
current is not greater than 21mA.
Lockout 122 – Lightoff rate
proving failed
Blower is not turning on
See “Blower not operating” below.
Missing or incorrect blower feedback
signal
See Hold 62 above.
Blower is always on
See “Blower operating at high speed while burner is
off” below.
Alert 128 - Modulation rate was
limited due to IAS open
Incorrect Sola controller.
Replace control with correct model.
Hold 137 – ILK failed to close
See Hold / Lockout 67
Lockout 138 – Flame too low
Blocked venting
Check for blockage of the exhaust-vent, Air-inlet,
combustion blower, gas valve venturi, heat
exchanger etc.
Fowled or faulty flame sensor
Inspect flame sensor for cracks of fowling, clean or
replace as necessary.
Incorrect combustion settings
Check combustion settings, correct accordingly.
Lockout 173 - Pilot relay
feedback incorrect
Lockout 174 – Safety relay
feedback incorrect
External Electrical Noise
Look for sources of electrical noise, i.e. a large
motor or multiple pieces of equipment starting at the
same time.
Failing Limit Switch in ILK circuit
Check operation of internal LWCO, and/or external
limit (i.e. devise connected between “R” and
“LIM”); replace as necessary
Hardware failure of Sola controller
Reset power, If problem persists replace Sola
controller.
Alert 206 – Lead Lag header
temperature was invalid
System Sensor not connected
If desired, install System Sensor and wire to
SENSOR input connections “SYSTEM” and “COM”. Otherwise ignore Alert 206
Alert 233 – Lead Lag outdoor
temperature was invalid
See Alert 248
Alert 248 – CH outdoor
temperature was invalid
Outdoor sensor not connected
The FTG is factory set with Outdoor Reset enabled.
Connect outdoor sensor or disable Outdoor Reset.
Outdoor sensor wiring
Check wiring of outdoor sensor. Wires should
connect to SENSOR inputs “OUTDOOR” and
“COM”.
Faulty sensor
Check sensor. Should be free of ice and snow.
Check resistance of sensor and compare to
thermistor resistance chart, see Table 16-2.
Indicates that the burner had to shut down due to
insufficient flame signal. If Alert persists, refer to
Lockout 138.
Alert 449 – Modulation rate
was limited due to flame
strength
Normal operation
Indicates that the minimum permissible modulation
rate was temporarily increased due to low flame
signal strength. If Alert persists, refer to Lockout
138.
Inoperative CH and/or DHW
Blown fuse
Check Fuse "B".
Installation & Operation Manual│FTG
Page 63
63
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
pump
Faulty Sola controller
If Fuse “B” not blown, and Sola controller is
operating, navigate to pump diagnostic on display.
Manually switch pump on, check for 120VAC at
pump connection terminal on line voltage barrier
strip. If 120VAC not detected, replace Sola
controller.
Faulty pump
If 120VAC supplied to pump, and pump does not
operate, replace pump.
Blower operating at high speed
while burner is off
Blower signal cable disconnected
Verify that the 5-position Molex connector on
the wiring harness is securely connected to its
mating connector on the blower.
Check that the 4-position Molex connector on
wiring harness is securely connected to its
mating connector on the Sola controller.
No 24VAC to Sola controller
Check Power LED on Sola controller.
Reset breaker at 24VAC transformer.
With an AC voltmeter measure voltage at
terminals J8 1 & 2, 24VAC should be present.
Blower not operating
Blower power disconnected
Verify that the 3-position Molex connector on the
wiring harness is securely connected to its mating
connector on the blower.
Faulty blower
Measure voltage across pins 1 & 2 (black and white
wires) of 3-position connector on wiring harness. If
120VAC detected, reconnect then and remove 5position signal connector. Blower should rotate at
high speed. If blower does not rotate, replace
blower.
Table 16-2 Thermistor Resistance vs. Temperature
Temp °F (°C)
Resistance Ohms (Ω)
Temp °F (°C)
Resistance Ohms (Ω)
-22 (-30)
176,133
122 (50)
3,603
-4 (-20)
96,761
131 (55)
2,986
14 (-10)
55,218
140 (60)
2,488
32 (0)
32,650
149 (65)
2,083
41 (5)
25,390
158 (70)
1,752
50 (10)
19,900
167 (75)
1,481
59 (15)
15,710
176 (80)
1,258
68 (20)
12,490
185 (85)
1,072
77 (25)
10,000
194 (90)
918
86 (30)
8,057
203 (95)
789
95 (35)
6,531
212 (100)
680
104 (40)
5,327
230 (110)
506
113 (45)
4,369 - -
FTG │Installation & Operation Manual
Page 64
64
Table 16-3 Hold and Lockout Codes
Code
Description
Note
0
None
Hold / No lockout
1
Unconfigured safety data
Lockout
2
Waiting for safety data verification
Lockout
3
Internal fault: Hardware fault
Hold
4
Internal fault: Safety Relay key feedback error
Hold
5
Internal fault: Unstable power (DCDC) output
Hold
6
Internal fault: Invalid processor clock
Hold
7
Internal fault: Safety relay drive error
Hold
8
Internal fault: Zero crossing not detected
Hold
9
Internal fault: Flame bias out of range
Hold
10
Internal fault: Invalid Burner control state
Lockout
11
Internal fault: Invalid Burner control state flag
Lockout
12
Internal fault: Safety relay drive cap short
Hold
13
Internal fault: PII shorted to ILK
Hold / Lockout
14
Internal fault: HFS shorted to LCI
Hold / Lockout
15
Internal fault: Safety relay test failed due to feedback ON
Lockout
16
Internal fault: Safety relay test failed due to safety relay OFF
Lockout
17
Internal fault: Safety relay test failed due to safety relay not OFF
Lockout
18
Internal fault: Safety relay test failed due to feedback not ON
Lockout
19
Internal fault: Safety RAM write
Lockout
20
Internal fault: Flame ripple and overflow
Hold
21
Internal fault: Flame number of sample mismatch
Hold
22
Internal fault: Flame bias out of range
Hold
23
Internal fault: Bias changed since heating cycle starts
Hold
24
Internal fault: Spark voltage stuck low or high
Hold
25
Internal fault: Spark voltage changed too much during flame sensing time
Hold
26
Internal fault: Static flame ripple
Hold
27
Internal fault: Flame rod shorted to ground detected
Hold
28
Internal fault: A/D linearity test fails
Hold
29
Internal fault: Flame bias cannot be set in range
Hold
30
Internal fault: Flame bias shorted to adjacent pin
Hold
31
Internal fault: SLO electronics unknown error
Hold
32
Internal fault: Safety Key 0
Lockout
33
Internal fault: Safety Key 1
Lockout
34
Internal fault: Safety Key 2
Lockout
35
Internal fault: Safety Key 3
Lockout
36
Internal fault: Safety Key 4
Lockout
37
Internal fault: Safety Key 5
Lockout
38
Internal fault: Safety Key 6
Lockout
39
Internal fault: Safety Key 7
Lockout
40
Internal fault: Safety Key 8
Lockout
41
Internal fault: Safety Key 9
Lockout
42
Internal fault: Safety Key 10
Lockout
43
Internal fault: Safety Key 11
Lockout
44
Internal fault: Safety Key 12
Lockout
45
Internal fault: Safety Key 13
Lockout
46
Internal fault: Safety Key 14
Lockout
47
Flame rod to ground leakage
Hold
48
Static flame (not flickering)
Hold
Installation & Operation Manual│FTG
Page 65
65
Table 16-3 Hold and Lockout Codes
Code
Description
Note
49
24VAC voltage low/high
Hold
50
Modulation fault
Hold
51
Pump fault
Hold
52
Motor tachometer fault
Hold
53
AC inputs phase reversed
Lockout
54
Safety GVT model ID doesn’t match application’s model ID
Lockout
55
Application configuration data block CRC errors
Lockout
56-57
RESERVED
58
Internal fault: HFS shorted to IAS
Lockout
59
Internal fault: Mux pin shorted
Lockout
60
Internal fault: HFS shorted to LFS
Lockout
61
Anti short cycle
Hold
62
Fan speed not proved
Hold
63
LCI OFF
Hold
64
PII OFF
N/A
65
Interrupted Airflow Switch OFF
Hold
66
Interrupted Airflow Switch ON
Hold
67
ILK OFF
Hold
68
ILK ON
N/A
69
Pilot test hold
Hold
70
Wait for leakage test completion
Hold
71
Input power frequency mismatch
Lockout
72-77
RESERVED
78
Demand lost in run
Hold
79
Outlet high limit
Hold
80
DHW high limit
Disabled
81
Delta T limit
Hold / Lockout
82
Stack limit
Lockout
83
Delta T exchanger/outlet limit
Disabled
84
Delta T inlet/exchanger limit
Disabled
85
Inlet/Outlet inversion limit (See Table 16-2)
Hold
86
Exchanger/outlet inversion limit
Disabled
87
Inlet/exchanger inversion limit
Disabled
88
Outlet T-Rise limit (See Table 16-2)
Lockout
89
Exchanger T-rise limit
Disabled
90
Heat exchanger high limit
Disabled
91
Inlet sensor fault
Hold
92
Outlet sensor fault
Hold
93
DHW sensor fault
Hold
94
Header sensor fault
Hold
95
Stack sensor fault
Hold
96
Outdoor sensor fault
Hold
97
Internal fault: A2D mismatch
Lockout
98
Internal fault: Exceeded VSNSR voltage tolerance
Lockout
99
Internal fault: Exceeded 28V voltage tolerance
Lockout
100
Pressure sensor fault
Hold
101
Exchanger sensor fault
Disabled
102-104
RESERVED
105
Flame detected out of sequence
Hold / Lockout
FTG │Installation & Operation Manual
Page 66
66
Table 16-3 Hold and Lockout Codes
Code
Description
Note
106
Flame lost in MFEP
Lockout
107
Flame lost early in run
Lockout
108
Flame lost in run
Lockout
109
Ignition failed
Lockout
110
Ignition failure occurred
Hold
111
Flame current lower than WEAK threshold
Hold
112
Pilot test flame timeout
Lockout
113
Flame circuit timeout
Lockout
114-115
RESERVED
116
Wait for OK to Run
Disabled
117
Flap valve condensate fault
Disabled
118
Controller interaction system fault
Hold
119
Controller interaction communications fault
Hold
120
Flap valve backflow fault
Disabled
121
Flap valve fault
Disabled
122
Light off rate proving failed
Lockout
123
Purge rate proving failed
Lockout
124
High fire switch OFF
Hold
125
High fire switch stuck ON
Hold
126
Low fire switch OFF
Hold
127
Low fire switch stuck ON
Hold
128
Fan speed failed during pre-purge
Hold / Lockout
129
Fan speed failed during pre-ignition
Hold / Lockout
130
Fan speed failed during ignition
Hold / Lockout
131
Fan movement detected during standby
Hold
132
Fan speed failed during run
Hold
133-135
RESERVED
136
Interrupted Airflow Switch failed to close
Hold
137
ILK failed to close
Hold
138
Flame too low
Lockout
139-142
RESERVED
143
Internal fault: Flame bias out of range 1
Lockout
144
Internal fault: Flame bias out of range 2
Lockout
145
Internal fault: Flame bias out of range 3
Lockout
146
Internal fault: Flame bias out of range 4
Lockout
147
Internal fault: Flame bias out of range 5
Lockout
148
Internal fault: Flame bias out of range 6
Lockout
149
Flame detected
Hold / Lockout
150
Flame not detected
Hold
151
High fire switch ON
Hold / Lockout
152
Combustion pressure ON
Hold / Lockout
153
Combustion pressure OFF
Hold / Lockout
154
Purge fan switch ON
Hold / Lockout
155
Purge fan switch OFF
Hold / Lockout
156
Combustion pressure and Flame ON
Hold / Lockout
157
Combustion pressure and Flame OFF
Lockout
158
Main valve ON
Lockout
159
Main valve OFF
Lockout
160
Ignition ON
Lockout
Installation & Operation Manual│FTG
Page 67
67
Table 16-3 Hold and Lockout Codes
Code
Description
Note
161
Ignition OFF
Lockout
162
Pilot valve ON
Lockout
163
Pilot valve OFF
Lockout
164
Block intake ON
Lockout
165
Block intake OFF
Lockout
166-168
RESERVED
169
Safety opto bad in test state
Lockout
170
Safety relay opto feedback incorrect
Lockout
171
Safety relay feedback incorrect in run
Lockout
172
Main relay feedback incorrect
Lockout
173
Pilot relay feedback incorrect
Lockout
174
Safety relay feedback incorrect
Lockout
175
Safety relay open
Lockout
176
Main relay ON at safe start check
Lockout
177
Pilot relay ON at safe start check
Lockout
178
Safety relay ON at safe start check
Lockout
179-180
RESERVED
181
Invalid Blocked condensate enable setting
Disabled
182
Invalid J7-1 configuration, both LFS and Blocked condensate
Disabled
183
Invalid J7-2 configuration, both HFS and Flap valve
Disabled
184
Invalid BLOWER/HSI output setting
Lockout
185
Invalid Delta T limit enable setting
Lockout
186
Invalid Delta T limit response setting
Lockout
187
Invalid DHW high limit enable setting
Lockout
188
Invalid DHW high limit response setting
Lockout
189
Invalid Flame sensor type setting
Lockout
190
Invalid interrupted air switch enable setting
Lockout
191
Invalid interrupted air switch start check enable setting
Lockout
192
Invalid Igniter on during setting
Lockout
193
Invalid Ignite failure delay setting
Lockout
194
Invalid Ignite failure response setting
Lockout
195
Invalid Ignite failure retries setting
Lockout
196
Invalid Ignition source setting
Lockout
197
Invalid Interlock open response setting
Lockout
198
Invalid Interlock start check setting
Lockout
199
Invalid LCI enable setting
Lockout
200
Invalid light off rate setting
Lockout
201
Invalid Light off rate proving setting
Lockout
202
Invalid Main Flame Establishing Period time setting
Lockout
203
Invalid MFEP flame failure response setting
Lockout
204
Invalid NTC sensor type setting
Lockout
205
Invalid Outlet high limit response setting
Lockout
206
Invalid Pilot Flame Establishing Period setting
Lockout
207
Invalid PII enable setting
Lockout
208
Invalid pilot test hold setting
Lockout
209
Invalid Pilot type setting
Lockout
210
Invalid Post-purge time setting
Lockout
211
Invalid Power up with lockout setting
Lockout
212
Invalid Pre-ignition time setting
Lockout
FTG │Installation & Operation Manual
Page 68
68
Table 16-3 Hold and Lockout Codes
Code
Description
Note
213
Invalid Pre-purge rate setting
Lockout
214
Invalid Pre-purge time setting
Lockout
215
Invalid Purge rate proving setting
Lockout
216
Invalid Run flame failure response setting
Lockout
217
Invalid Run stabilization time setting
Lockout
218
Invalid Stack limit enable setting
Lockout
219
Invalid Stack limit response setting
Lockout
220
Unconfigured Delta T limit set point setting
Lockout
221
Unconfigured DHW high limit set point setting
Lockout
222
Unconfigured Outlet high limit set point setting
Lockout
223
Unconfigured Stack limit set point setting
Lockout
224
Invalid DHW demand source setting
Lockout
225
Invalid Flame threshold setting
Lockout
226
Invalid Outlet high limit set point setting
Lockout
227
Invalid DHW high limit set point setting
Lockout
228
Invalid Stack limit set point setting
Lockout
229
Invalid Modulation output setting
Lockout
230
Invalid CH demand source setting
Lockout
231
Invalid Delta T limit delay setting
Lockout
232
Invalid Pressure sensor type setting
Lockout
233
Invalid IAS closed response setting
Lockout
234
Invalid Outlet high limit enable setting
Lockout
235
Invalid Outlet connector type setting
Lockout
236
Invalid Inlet connector type setting
Lockout
237
Invalid DHW connector type setting
Lockout
238
Invalid Stack connector type setting
Lockout
239
Invalid Header connector type setting
Lockout
240
Invalid Outdoor connector type setting
Lockout
241
Exchanger sensor not allowed with stack connector setting
Lockout
242
Invalid DHW auto detect configuration
Lockout
243
Invalid UV with spark interference not compatible with Igniter on throughout
Lockout
244
Internal fault: Safety relay test invalid state
Lockout
245
Invalid Outlet connector type setting for T-rise
Lockout
246
4-20mA cannot be used for both modulation and setpoint control
Lockout
247
Invalid ILK bounce detection enable
Lockout
248
Invalid forced recycle interval
Lockout
249
STAT cannot be demand source when Remote Stat is enabled
Lockout
250
Invalid Fan speed error response
Lockout
251
Lead drop-stage on error setting does not match drop method configuration
Lockout
252
Invalid Line frequency setting
Lockout
253
Lead Lag modulation sensor not valid with setpoint source
Lockout
254
Lead Lag modulation sensor not valid with local setpoint source
Lockout
255
Lead Lag modulation sensor not valid with local modulation source
Lockout
256
Selected Controller interaction enable setting is not allowed
Lockout
257
Controller interaction enable does not match neighbor stack fault setting
Lockout
258
Controller ID must be non-zero if controller interaction is enabled
Lockout
259
Modulation output must be fan if controller interaction is enabled
Lockout
260
Asymmetrical paired (no flap) is set but flap switch input is energized
Lockout
261
Neighbor burner control blower fault detected
Lockout
Installation & Operation Manual│FTG
Page 69
69
Table 16-3 Hold and Lockout Codes
Code
Description
Note
262
Blower fault detected during flap test
Lockout
263
Invalid DHW demand temperature setting
Lockout
264
Invalid preferred outlet high limit setting
Lockout
265
Invalid preferred lightoff rate setting
Lockout
266
Invalid preferred stack limit rate setting
Lockout
Table 16-4 Alert Codes
Code
Description
0
None (No alert)
1
Alert PCB was restored from factory defaults
2
Safety configuration parameters were restored from factory defaults
3
Configuration parameters were restored from factory defaults
4
Invalid Factory Invisibility PCB was detected
5
Invalid Factory Range PCB was detected
6
Invalid range PCB record has been dropped
7
EEPROM lockout history was initialized
8
Switched application annunciation data blocks
9
Switched application configuration data blocks
10
Configuration was restored from factory defaults
11
Backup configuration settings was restored from active configuration
12
Annunciation configuration was restored from factory defaults
13
Annunciation configuration was restored from backup
14
Safety group verification table was restored from factory defaults
15
Safety group verification table was updated
16
Invalid Parameter PCB was detected
17
Invalid Range PCB was detected
18
Alarm silence time exceeded maximum
19
Invalid safety group verification table was detected
20
Backdoor password could not be determined
21
Invalid safety group verification table was not accepted
22
CRC errors were found in application configuration data blocks
23
Backup Alert PCB was restored from active one
24
RESERVED
25
Lead Lag operation switch was turned OFF
26
Lead Lag operation switch was turned ON
27
Safety processor was reset
28
Application processor was reset
29
Burner switch was turned OFF
30
Burner switch was turned ON
31
Program Module (PM) was inserted into socket
32
Program Module (PM) was removed from socket
33
Alert PCB was configured
34
Parameter PCB was configured
35
Range PCB was configured
36
Program Module (PM) incompatible with product was inserted into socket
37
Program Module application parameter revision differs from application processor
38
Program Module safety parameter revision differs from safety processor
39
PCB incompatible with product contained in Program Module
FTG │Installation & Operation Manual
Page 70
70
Table 16-4 Alert Codes
Code
Description
40
Parameter PCB in Program Module is too large for product
41
Range PCB in Program Module was too large for product
42
Alert PCB in Program Module was too large for product
43
IAS start check was forced on due to IAS enabled
44
Low voltage was detected in safety processor
45
High line frequency occurred
46
Low line frequency occurred
47
Invalid subsystem reset request occurred
48
Write large enumerated Modbus register value was not allowed
49
Maximum cycle count was reached
50
Maximum hours count was reached
51
Illegal Modbus write was attempted
52
Modbus write attempt was rejected (NOT ALLOWED)
53
Illegal Modbus read was attempted
54
Safety processor brown-out reset occurred
55
Application processor watchdog reset occurred
56
Application processor brown-out reset occurred
57
Safety processor watchdog reset occurred
58
Alarm was reset by the user at the control
59
Burner control firing rate was > absolute max rate
60
Burner control firing rate was < absolute min rate
61
Burner control firing rate was invalid, % vs. RPM
62
Burner control was firing with no fan request
63
Burner control rate (non-firing) was > absolute max rate
64
Burner control rate (non-firing) was < absolute min rate
65
Burner control rate (non-firing) was absent
66
Burner control rate (non-firing) was invalid, % vs. RPM
67
Fan off cycle rate was invalid, % vs. RPM
68
Set point was over ridden due to sensor fault
69
Modulation was over ridden due to sensor fault
70
No demand source was set due to demand priority conflicts
71
CH 4-20mA signal was invalid.
72
Flame strength rate differential was invalid
73
Flame strength step rate was invalid
74
Periodic forced recycle
75
Absolute max fan speed was out of range
76
Absolute min fan speed was out of range
77
Fan gain down was invalid
78
Fan gain up was invalid
79
Fan minimum duty cycle was invalid
80
Fan pulses per revolution was invalid
81
Fan PWM frequency was invalid
82-83
RESERVED
84
Lead Lag CH 4-20mA water temperature setting was invalid
85
No Lead Lag add stage error threshold was configured
86
No Lead Lag add stage detection time was configured
87
No Lead Lag drop stage error threshold was configured
88
No Lead Lag drop stage detection time was configured
89
Lead Lag all boiler off threshold was invalid
Installation & Operation Manual│FTG
Page 71
71
Table 16-4 Alert Codes
Code
Description
90
Modulation output type was invalid
91
Firing rate control parameter was invalid
92
Forced rate was out of range vs. min/max modulation
93
Forced rate was invalid, % vs. RPM
94
Slow start ramp value was invalid
95
Slow start degrees value was invalid
96
Slow start was ended due to outlet sensor fault
97
Slow start was end due to reference set point fault
98
CH max modulation rate was invalid, % vs. RPM
99
CH max modulation rate was > absolute max rate
100
CH modulation range (max minus min) was too small (< 4% or 40 RPM)
101
DHW max modulation rate was invalid, % vs. RPM
102
DHW max modulation rate was > absolute max rate
103
DHW modulation range (max minus min) was too small (< 4% or 40 RPM)
104
Min modulation rate was < absolute min rate
105
Min modulation rate was invalid, % vs. RPM
106
Manual rate was invalid, % vs. RPM
107
Slow start enabled, but forced rate was invalid
108
Analog output hysteresis was invalid
109
Analog modulation output type was invalid
110
IAS open rate differential was invalid
111
IAS open step rate was invalid
112
Mix max modulation rate was invalid, % vs. RPM
113
Mix max modulation rate was > absolute max or < absolute min rates
114
Mix modulation range (max minus min) was too small (< 4% or 40 RPM)
115
Fan was limited to its minimum duty cycle
116
Manual rate was > CH max modulation rate
117
Manual rate was > DHW max modulation rate
118
Manual rate was < min modulation rate
119
Manual rate in Standby was > absolute max rate
120
Modulation commanded rate was > CH max modulation rate
121
Modulation commanded rate was > DHW max modulation rate
122
Modulation commanded rate was < min modulation rate
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
125
Modulation rate was limited due to stack limit
126
Modulation rate was limited due to anti-condensation
127
Fan Speed out of range in RUN
128
Modulation rate was limited due to IAS was open
129
Slow start ramp setting of zero will result in no modulation rate change
130
No forced rate was configured for slow start ramp
131
CH demand source was invalid
132
CH P-gain was invalid
133
CH I-gain was invalid
134
CH D-gain was invalid
135
CH OFF hysteresis was invalid
136
CH ON hysteresis was invalid
137
CH sensor type was invalid
138
CH hysteresis step time was invalid
FTG │Installation & Operation Manual
Page 72
72
Table 16-4 Alert Codes
Code
Description
139
CH remote control parameter was invalid
140
CH ODR not allowed with remote control
146
CH control was suspended due to fault
147
CH header temperature was invalid
148
CH outlet temperature was invalid
149
CH steam pressure was invalid
151
Minimum water temperature parameter was greater than setpoint
152
Minimum water temperature parameter was greater than time of day setpoint
155
CH modulation rate source parameter was invalid
157
DHW demand source was invalid
158
DHW P-gain was invalid
159
DHW I-gain was invalid
160
DHW D-gain was invalid
161
DHW OFF hysteresis was invalid
162
DHW ON hysteresis was invalid
163
DHW hysteresis step time was invalid
164
DHW sensor type was invalid
165
Inlet sensor type was invalid for DHW
166
Outlet sensor type was invalid for DHW
167
DHW storage OFF hysteresis was invalid
168
DHW storage ON hysteresis was invalid
169
DHW modulation sensor type was invalid
170
DHW modulation sensor was not compatible for Auto mode
171
DHW control was suspended due to fault
172
DHW temperature was invalid
173
DHW inlet temperature was invalid
174
DHW outlet temperature was invalid
175
DHW high limit must be disabled for Auto mode
176
DHW sensor type was not compatible for Auto mode
177
DHW priority source setting was invalid
178
DHW priority method setting was invalid
179
CH S5 (J8-11) sensor was invalid
180
CH Inlet temperature was invalid
181
CH S10 (J10-7) sensor was invalid
182
Lead Lag CH setpoint source was invalid
183
Lead Lag P-gain was invalid
184
Lead Lag I-gain was invalid
185
Lead Lag D-gain was invalid
186
Lead Lag OFF hysteresis was invalid
187
Lead Lag ON hysteresis was invalid
188
Lead Lag slave enable was invalid
189
Lead Lag hysteresis step time was invalid
190
No Lead Lag Modbus port was assigned
191
Lead Lag base load common setting was invalid
192
Lead Lag DHW demand switch setting was invalid
193
Lead Lag Mix demand switch setting was invalid
194
Lead Lag modulation sensor setting was invalid
195
Lead Lag backup modulation sensor setting was invalid
196
Lead Lag slave mode setting was invalid
Installation & Operation Manual│FTG
Page 73
73
Table 16-4 Alert Codes
Code
Description
197
Lead Lag rate allocation setting was invalid
198
Lead selection setting was invalid
199
Lag selection setting was invalid
200
Lead Lag slave return setting was invalid
201
Lead Lag add stage method setting was invalid
202
STAT may not be a Lead Lag CH demand source when Remote Stat is enabled
203
Lead Lag base load rate setting was invalid
204
Lead Lag master was suspended due to fault
205
Lead Lag slave was suspended due to fault
206
Lead Lag header temperature was invalid
207
Lead Lag was suspended due to no enabled Program Module installed
208
Lead Lag slave session has timed out
209
Too many Lead Lag slaves were detected
210
Lead Lag slave was discovered
211
Incompatible Lead Lag slave was discovered
212
No base load rate was set for Lead Lag slave
213
Lead Lag slave unable to fire before demand to fire delay expired
214
Adding Lead Lag slave aborted due to add requirement change
215
No Lead Lag slaves available to service demand
216
No Lead Lag active service was set due to demand priority conflicts
217
No Lead Lag add stage method was specified
218
No Lead Lag drop stage method was specified
219
Using backup Lead Lag header sensor due to sensor failure
220
Lead Lag frost protection rate was invalid
221
Lead Lag drop stage method setting was invalid
222
CH frost protection temperature was invalid
223
CH frost protection inlet temperature was invalid
224
DHW frost protection temperature was invalid
225
No anticondensation setpoint was configured for frost protection
226
RESERVED
227
DHW priority override time was not derated due to invalid outdoor temperature
228
Warm weather shutdown was not checked due to invalid outdoor temperature
229
Lead Lag slave communication timeout
230
RESERVED
231
LL set point was invalid
232
LL time of day set point was invalid
233
LL outdoor temperature was invalid
234
LL ODR time of day set point was invalid
235
LL ODR time of day set point exceeded normal set point
236
LL max outdoor set point was invalid
237
LL min outdoor set point was invalid
238
LL min water set point was invalid
239
LL outdoor temperature range was too small (minimum 12 C / 22 F)
240
LL water temperature range was too small (minimum 12 C / 22 F)
241
Lead Lag DHW setpoint was invalid
243
Lead Lag CH demand switch was invalid
244
Lead Lag ODR min water temperature was invalid
245
RESERVED
246
CH set point was invalid
FTG │Installation & Operation Manual
Page 74
74
Table 16-4 Alert Codes
Code
Description
247
CH time of day set point was invalid
248
CH outdoor temperature was invalid
249
CH ODR time of day setpoint was invalid
250
CH ODR time of day set point exceeds normal set point
251
CH max outdoor set point was invalid
252
CH min outdoor set point was invalid
253
CH min water set point was invalid
254
CH outdoor temperature range was too small (minimum 12 C / 22 F)
255
CH water temperature range was too small (minimum 12 C / 22 F)
259
CH ODR min water temperature was invalid
260
RESERVED
261
DHW set point was invalid
262
DHW time of day set point was invalid
263
DHW storage setpoint was invalid
264
STAT may not be a DHW demand source when Remote Stat is enabled
265
No DHW anticondensation setpoint was configured
266
No CH anticondensation setpoint was configured
267
STAT may not be a CH demand source when Remote Stat is enabled
268
CH 4mA water temperature setting was invalid
269
CH 20mA water temperature setting was invalid
270
Steam 4mA water temperature setting was invalid
271
Steam 20mA water temperature setting was invalid
272
Abnormal Recycle: Pressure sensor fault
273
Abnormal Recycle: Safety relay drive test failed
274
Abnormal Recycle: Demand off during Pilot Flame Establishing Period
275
Abnormal Recycle: LCI off during Drive to Purge Rate
276
Abnormal Recycle: LCI off during Measured Purge Time
277
Abnormal Recycle: LCI off during Drive to Light off Rate
278
Abnormal Recycle: LCI off during Pre-Ignition test
279
Abnormal Recycle: LCI off during Pre-Ignition time
280
Abnormal Recycle: LCI off during Main Flame Establishing Period
281
Abnormal Recycle: LCI off during Ignition period
282
Abnormal Recycle: Demand off during Drive to Purge Rate
283
Abnormal Recycle: Demand off during Measured Purge Time
284
Abnormal Recycle: Demand off during Drive to Light off Rate
285
Abnormal Recycle: Demand off during Pre-Ignition test
286
Abnormal Recycle: Demand off during Pre-Ignition time
287
Abnormal Recycle: Flame was on during Safe Start check
288
Abnormal Recycle: Flame was on during Drive to Purge Rate
289
Abnormal Recycle: Flame was on during Measured Purge Time
290
Abnormal Recycle: Flame was on during Drive to Light off Rate
291
Abnormal Recycle: Flame was not on at end of Ignition period
292
Abnormal Recycle: Flame was lost during Main Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
295
Abnormal Recycle: Leakage test failed
296
Abnormal Recycle: Interrupted air flow switch was off during Drive to Purge Rate
297
Abnormal Recycle: Interrupted air flow switch was off during Measured Purge Time
298
Abnormal Recycle: Interrupted air flow switch was off during Drive to Light off Rate
Installation & Operation Manual│FTG
Page 75
75
Table 16-4 Alert Codes
Code
Description
299
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test
300
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time
301
Abnormal Recycle: Interrupted air flow switch was off during Main Flame Establishing Period
302
Abnormal Recycle: Ignition failed due to interrupted air flow switch was off
303
Abnormal Recycle: ILK off during Drive to Purge Rate
304
Abnormal Recycle: ILK off during Measured Purge Time
305
Abnormal Recycle: ILK off during Drive to Light off Rate
306
Abnormal Recycle: ILK off during Pre-Ignition test
307
Abnormal Recycle: ILK off during Pre-Ignition time
308
Abnormal Recycle: ILK off during Main Flame Establishing Period
309
Abnormal Recycle: ILK off during Ignition period
310
Run was terminated due to ILK was off
311
Run was terminated due to interrupted air flow switch was off
312
Stuck reset switch
313
Run was terminated due to fan failure
314
Abnormal Recycle: Fan failed during Drive to Purge Rate
315
Abnormal Recycle: Fan failed during Measured Purge Time
316
Abnormal Recycle: Fan failed during Drive to Light off Rate
317
Abnormal Recycle: Fan failed during Pre-Ignition test
318
Abnormal Recycle: Fan failed during Pre-Ignition time
319
Abnormal Recycle: Fan failed during Ignition period
320
Abnormal Recycle: Fan failed during Main Flame Establishing Period
321
Abnormal Recycle: Main Valve off after 10 seconds of RUN
322
Abnormal Recycle: Pilot Valve off after 10 seconds of RUN
323
Abnormal Recycle: Safety Relay off after 10 seconds of RUN
324
Abnormal Recycle: Hardware flame bias
325
Abnormal Recycle: Hardware static flame
326
Abnormal Recycle: Hardware flame current invalid
327
Abnormal Recycle: Hardware flame rod short
328
Abnormal Recycle: Hardware invalid power
329
Abnormal Recycle: Hardware invalid AC line
330
Abnormal Recycle: Hardware SLO flame ripple
331
Abnormal Recycle: Hardware SLO flame sample
332
Abnormal Recycle: Hardware SLO flame bias range
333
Abnormal Recycle: Hardware SLO flame bias heat
334
Abnormal Recycle: Hardware SLO spark stuck
335
Abnormal Recycle: Hardware SLO spark changed
336
Abnormal Recycle: Hardware SLO static flame
337
Abnormal Recycle: Hardware SLO rod shorted
338
Abnormal Recycle: Hardware SLO AD linearity
339
Abnormal Recycle: Hardware SLO bias not set
340
Abnormal Recycle: Hardware SLO bias shorted
341
Abnormal Recycle: Hardware SLO electronics
342
Abnormal Recycle: Hardware processor clock
343
Abnormal Recycle: Hardware AC phase
344
Abnormal Recycle: Hardware A2D mismatch
345
Abnormal Recycle: Hardware VSNSR A2D
346
Abnormal Recycle: Hardware 28V A2D
347
Abnormal Recycle: Hardware HFS IAS shorted
FTG │Installation & Operation Manual
Page 76
76
Table 16-4 Alert Codes
Code
Description
348
Abnormal Recycle: Hardware PII INTLK shorted
349
Abnormal Recycle: Hardware HFS LCI shorted
350
Abnormal Recycle: Hardware HFS LFS shorted
351
Abnormal Recycle: Invalid zero crossing
352
Abnormal Recycle: fault stack sensor
353
Abnormal Recycle: stack limit
354
Abnormal Recycle: delta T limit
355
Abnormal Recycle: fault outlet sensor
356
Abnormal Recycle: outlet high limit
357
Abnormal Recycle: fault DHW sensor
358
Abnormal Recycle: DHW high limit
359
Abnormal Recycle: fault inlet sensor
360
Abnormal Recycle: Check Parameters Failed
361
Internal error: No factory parameters were detected in control
362
Internal error: PID iteration frequency was invalid
363
Internal error: Demand-Rate interval time was invalid
364
Internal error: Factory calibration parameter for modulation was invalid
365
Internal error: CH PID P-scaler was invalid
366
Internal error: CH PID I-scaler was invalid
367
Internal error: CH PID D-scaler was invalid
368
Internal error: DHW PID P-scaler was invalid
369
Internal error: DHW PID I-scaler was invalid
370
Internal error: DHW PID D-scaler was invalid
371
Internal error: Lead Lag master PID P-scaler was invalid
372
Internal error: Lead Lag master PID I-scaler was invalid
373
Internal error: Lead Lag master PID D-scaler was invalid
374
Abnormal Recycle: Hardware flame bias high
375
Abnormal Recycle: Hardware flame bias low
376
Abnormal Recycle: Hardware flame bias delta high
377
Abnormal Recycle: Hardware flame bias delta low
378
Abnormal Recycle: Hardware flame bias dynamic high
379
Abnormal Recycle: Hardware flame bias dynamic low
380
Abnormal Recycle: Fan Speed Not Proven
381
Abnormal Recycle: Fan Speed Range Low
382
Abnormal Recycle: Fan Speed Range High
383
Abnormal Recycle: Pre-Ignition test failed, recycle
384-388
RESERVED
389
Abnormal Recycle: AC power frequency Mismatch
390-447
RESERVED
448
Flame too low
449
Modulation rate was limited due to flame strength
450
RESERVED
451
Circulator control was invalid
452
Circulator P-gain was invalid
453
Circulator I-gain was invalid
454
Circulator temperature was invalid
455
Circulator outlet temperature was invalid
456
Circulator inlet temperature was invalid
457
Circulator outlet temperature was invalid
Installation & Operation Manual│FTG
Page 77
77
Table 16-4 Alert Codes
Code
Description
458
Circulator sensor choice was invalid
459
Circulator PID setpoint was invalid
460
LCI demand lost in run
461
Demand lost in run
462
STAT demand lost in run
463
Demand lost in run due to no flame
464
LCI lost in Combustion Pressure Establishing Period
465
LCI lost in Combustion Pressure Stabilizing Period
466
RESERVED
467
Internal error: EEPROM write was attempted before EEPROM was initialized
468
Internal error: EEPROM cycle count address was invalid
469
Internal error: EEPROM days count address was invalid
470
Internal error: EEPROM hours count address was invalid
471
Internal error: Lockout record EEPROM index was invalid
472
Internal error: Request to write PM status was invalid
473
Internal error: PM parameter address was invalid
474
Internal error: PM safety parameter address was invalid
475
Internal error: Invalid record in lockout history was removed
476
Internal error: EEPROM write buffer was full
477
Internal error: Data too large was not written to EEPROM
478
Internal error: Safety key bit 0 was incorrect
479
Internal error: Safety key bit 1 was incorrect
480
Internal error: Safety key bit 2 was incorrect
481
Internal error: Safety key bit 3 was incorrect
482
Internal error: Safety key bit 4 was incorrect
483
Internal error: Safety key bit 5 was incorrect
484
Internal error: Safety key bit 6 was incorrect
485
Internal error: Safety key bit 7 was incorrect
486
Internal error: Safety key bit 8 was incorrect
487
Internal error: Safety key bit 9 was incorrect
488
Internal error: Safety key bit 10 was incorrect
489
Internal error: Safety key bit 11 was incorrect
490
Internal error: Safety key bit 12 was incorrect
491
Internal error: Safety key bit 13 was incorrect
492
Internal error: Safety key bit 14 was incorrect
493
Internal error: Safety key bit 15 was incorrect
494
Internal error: Safety relay timeout
495
Internal error: Safety relay commanded off
496
Internal error: Unknown safety error occurred
497
Internal error: Safety timer was corrupt
498
Internal error: Safety timer was expired
499
Internal error: Safety timings
500
Internal error: Safety shutdown
550
Delta T inlet/outlet limit was exceeded
553
Inlet/outlet inversion occurred
564
Outlet T-rise limit was exceeded
600
Delta T inlet temperature was invalid
601
Delta T outlet temperature was invalid
603
CH ODR boost max offpoint temperature was invalid
FTG │Installation & Operation Manual
Page 78
78
Table 16-4 Alert Codes
Code
Description
604
CH ODR boost max offpoint temperature was too low
605
Lead Lag ODR boost max offpoint temperature was invalid
606
Lead Lag ODR boost max offpoint temperature was too low
609
Time to rotate lead boiler to next firing slave
610
Time to rotate lead boiler to next available slave
611
Time to rotate lead boiler to first firing slave in order
612
Time to rotate lead boiler to lowest running slave
613
Lead boiler was rotated based on new firing sequence order
614
Lead boiler was rotated based on measured run time
615
Parameter PCB was switched to backup
616
Range PCB was switched to backup
622
Lead Lag modulation sensor was not valid with setpoint source
623
Lead Lag modulation sensor was not valid with local setpoint source
624
Lead Lag modulation sensor was not valid with local modulation rate source
629
Disagreement on number of interacting controls
Installation & Operation Manual│FTG
Page 79
79
Figure 17-1(a) Exploded View - Cabinet
42
62
63
55
53
64
66
72
73
74
75
76
77
80
98
50
51
51
77
17.0 PARTS LIST
For a list of parts that corresponds to the item numbers in the callouts, refer to Table 17-1. Note that some item
numbers may appear more than once in the parts list depending on which model number is being referenced.
Building Owners - Replacement parts are available from your stocking wholesaler. Contact your local Installer
or Wholesaler for assistance with parts.
Wholesalers - Contact NY Thermal Inc. directly when ordering replacement parts, 1-506-657-6000.
Installers - Contact NY Thermal Inc. directly if technical assistance required, 1-800-688-2575.
Page 80
Figure 17-1(b) Exploded View – Control Panel
Figure 17-1(c) Exploded View – Trim/Install Kit
17
30
38
40
41
71
90
81
108
111
92
109
110
47
112 – LP Conversion Instructions
113 – LP Conversion Label
114 – Install & Operation Manual
115 – App. A, Touchscreen Manual
116 – User Instruction Manual
48
49
52
53
55
56
60
61
62
64
66
68,69
70
78
85
102
43
12
67
121
59
91
Page 81
81
Figure 17-1(d) Exploded View – Heat Exchanger & Gas Train