PC10A/20A SERIES
Standard low voltage installation
with remote power pack
in accessible tile ceiling
SPECIAL NOTES: One Power Pack can operate 4 sensors and all
low voltage wires are connected in parallel. Some existing lighting
systems are wired directly from Breaker Control Cabinet and therefore have no light switches. For this type of lighting system, it is
sometimes more convenient to install Power Packs close to the
Circuit Breaker Control Cabinet. This allows for ease of circuit identification, and also wiring of low voltage cable to sensor units.
TRPS are UL Listed.
NEUTRAL
120 VAC OR 277 VAC
(LINE)
HOT
POWER PACK
MODEL TRP1 120 VAC
20 AMP 2400 WATTS
POWER PACK
MODEL TRP2 277 VAC
20 AMP 4800 WATTS
BALLAST
LIGHT FIXTURE #1
WHITE
EXISTING SWITCH CAN REMAIN
IN RETROFIT INSTALLATIONS.
IT IS NOT REQUIRED IN NEW
CONSTRUCTION UNLESS MANUAL
OFF IS DESIRED IN WHICH CASE
SIMPLY RUN 22AWG WIRE FROM
TRP AND BREAK THE BLUE WIRE.
BLACK
RED
BLACK
RED
BLUE
LOW VOLTAGE CABLE
3 CONDUCTOR 22 GA.
CLASS 2 WIRING
BALLAST
LIGHT FIXTURE #2
OPTIONAL MANUAL
ON OVERRIDE
SWITCH
LOAD
RED
POWER PACK
MOUNT IN APPROVED
JUNCTION BOX OR
BALLAST HOUSING OF
FIRST LIGHT FIXTURE
SPECIAL NOTES: One Power Pack can operate 4 PC10/PC10H
Units and all low voltage wires are connected in parallel. Some
existing lighting systems are wired directly from Breaker Control
Cabinet and therefore have no light switches. For this type of
lighting system, it is sometimes more convenient to install Power
Packs close to the Circuit Breaker Control Cabinet. This allows for
Power Pack 277V
Model TRP2
or Power Pack 120V
Model TRP1
New Cover With
1/2 K.O. Provision
BALLAST
LIGHT FIXTURE #3
New
Extension
Box
Bend Tabs After
Inserting in K.O.
Hole
New Extension Box
Only Used When
Low Voltage Wiring
Has to be Enclosed
Existing
Junction
Box